II.E Technical Approach requiements.pdf

PDF 415 KB Posted

Attached to
High Pressure Proximity Switches
Solicitation number
N66604-24-Q-0374
Issued by

About this file

This file is a technical requirements document detailing the test and inspection criteria for a High Pressure Proximity Sensor (part number 53X-00-100). The document outlines specific pass criteria for multiple test types including physical inspections, electrical measurements, and functional performance requirements.

The testing requirements encompass basic physical inspections (jam nut threading, connector mating, marking), electrical specifications (insulation resistance >10 MΩ for all leads, HiPot tests), and detailed functional parameters. Key functional requirements include signal voltage ranges of 4.0-7.2 VDC in nondetect state and <0.8 VDC in detect state, with current limits of <200 mA for signal current and <20 mA for supply current. The sensor must achieve a Monel 400 target sensing distance of 1.0 ±0.1 mm for both on-to-off and off-to-on transitions. The document also specifies extensive reversed wiring test requirements for various lead combinations (supply, signal, and reference) with specific voltage and current parameters for each configuration.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

The Offeror shall provide their technical approach or procedure for achieving satisfactory test results post manufacture for, 53X-00-100 High Pressure Proximity Sensor, IAW the test/ inspection types and pass criteria referenced in Table 1.

Table 1

Test/ Inspection Pass Criteria Jam Nut Threading Inspection Smoothly Threads Connector Mating Inspection Mates Properly

Marking Inspection Part is marked in accordance with drawing 53X-00-

Insulation Resistance, Black Lead (A) > 10 MΩ Insulation Resistance, White Lead (B) > 10 MΩ

Insulation Resistance, Red Lead (C) > 10 MΩ HiPot Test, Black Lead (A) No Alarm HiPot Test, White Lead (B) No Alarm

HiPot Test, Red Lead (C) No Alarm Functional Test, Nondetect*

-Signal Voltage -Signal Current -Supply Current

4.0 < N < 7.2 VDC

< 200 mA <20 mA

Functional Test, Detect* -Signal Voltage

< 0.8 VDC

< 20 mA

Monel 400 target Sensing Distance (On -> Off) 1.0 +/- 0.1 mm Monel 400 target Sensing Distance (Off -> On) 1.0 +/- 0.1 mm Reversed (Supply & Signal Leads) Wiring Test

-Signal Voltage

12.0 < N < 18.0 VDC

< 5 mA < 300 mA

Post-Reversed (Supply & Signal Leads) Wiring Test, Nondetect*

-Signal Voltage

< 20 mA

Post-Reversed (Supply & Signal Leads) Wiring Test, Detect*

-Signal Voltage

< 20 mA

Reversed (Supply & Reference Leads) Wiring Test -Signal Voltage

-10.8 < N < -7.2 VDC

Post-Reversed (Supply & Reference Leads) Wiring Test, Nondetect*

-Signal Voltage

< 20 mA

Post-Reversed (Supply & Reference Leads) Wiring Test, Detect*

-Signal Voltage

< 20 mA

Reversed (Signal & Reference Leads) Wiring Test -Signal Voltage

-6.0 < N < -4.0 VDC

< 20 mA

Post-Reversed (Signal & Reference Leads) Wiring Test, Nondetect*

-Signal Voltage

< 20 mA

Post-Reversed (Signal & Reference Leads) Wiring Test, Detect*

-Signal Voltage

< 20 mA

*Refers to output readings when the sensor is either detecting or not detecting a target.

File details come from the government source that posted it. Updated .