This file is a technical requirements document detailing the test and inspection criteria for a High Pressure Proximity Sensor (part number 53X-00-100). The document outlines specific pass criteria for multiple test types including physical inspections, electrical measurements, and functional performance requirements.
The testing requirements encompass basic physical inspections (jam nut threading, connector mating, marking), electrical specifications (insulation resistance >10 MΩ for all leads, HiPot tests), and detailed functional parameters. Key functional requirements include signal voltage ranges of 4.0-7.2 VDC in nondetect state and <0.8 VDC in detect state, with current limits of <200 mA for signal current and <20 mA for supply current. The sensor must achieve a Monel 400 target sensing distance of 1.0 ±0.1 mm for both on-to-off and off-to-on transitions. The document also specifies extensive reversed wiring test requirements for various lead combinations (supply, signal, and reference) with specific voltage and current parameters for each configuration.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
The Offeror shall provide their technical approach or procedure for achieving satisfactory test results post manufacture for, 53X-00-100 High Pressure Proximity Sensor, IAW the test/ inspection types and pass criteria referenced in Table 1.
Table 1
Test/ Inspection Pass Criteria Jam Nut Threading Inspection Smoothly Threads Connector Mating Inspection Mates Properly
Marking Inspection Part is marked in accordance with drawing 53X-00-
Insulation Resistance, Black Lead (A) > 10 MΩ Insulation Resistance, White Lead (B) > 10 MΩ
Insulation Resistance, Red Lead (C) > 10 MΩ HiPot Test, Black Lead (A) No Alarm HiPot Test, White Lead (B) No Alarm
HiPot Test, Red Lead (C) No Alarm Functional Test, Nondetect*
-Signal Voltage -Signal Current -Supply Current
4.0 < N < 7.2 VDC
< 200 mA <20 mA
Functional Test, Detect* -Signal Voltage
< 0.8 VDC
< 20 mA
Monel 400 target Sensing Distance (On -> Off) 1.0 +/- 0.1 mm Monel 400 target Sensing Distance (Off -> On) 1.0 +/- 0.1 mm Reversed (Supply & Signal Leads) Wiring Test
-Signal Voltage
12.0 < N < 18.0 VDC
< 5 mA < 300 mA
Post-Reversed (Supply & Signal Leads) Wiring Test, Nondetect*
-Signal Voltage
< 20 mA
Post-Reversed (Supply & Signal Leads) Wiring Test, Detect*
-Signal Voltage
< 20 mA
Reversed (Supply & Reference Leads) Wiring Test -Signal Voltage
-10.8 < N < -7.2 VDC
Post-Reversed (Supply & Reference Leads) Wiring Test, Nondetect*
-Signal Voltage
< 20 mA
Post-Reversed (Supply & Reference Leads) Wiring Test, Detect*
-Signal Voltage
< 20 mA
Reversed (Signal & Reference Leads) Wiring Test -Signal Voltage
-6.0 < N < -4.0 VDC
< 20 mA
Post-Reversed (Signal & Reference Leads) Wiring Test, Nondetect*
-Signal Voltage
< 20 mA
Post-Reversed (Signal & Reference Leads) Wiring Test, Detect*
-Signal Voltage
< 20 mA
*Refers to output readings when the sensor is either detecting or not detecting a target.