Attachment_7 Questions and Answers.pdf
PDF 176 KB Posted
- Attached to
- Construction Solicitation - HVAC Renovation Project NUWCDIVNPT Federal contract opportunity
- Solicitation number
- N6660420R8248
About this file
This document contains questions and answers regarding a construction solicitation for HVAC renovation work at a Naval facility. The solicitation seeks offers to perform HVAC upgrades in a 3,400 square foot laboratory and office space to provide specialized climate control. The new mechanical system will include direct expansion computer room units for cooling the lab and a chilled water air handling unit for the offices. Electrical upgrades will support the new equipment. Offerors do not need JCP certification but must have an active CAGE code to obtain drawings and specifications. The point of contact for any questions is provided. The proposal due date was extended to October 30, 2020 at 2:00 PM EST. Additional photos of the project site were made available to assist with rigging assessments. Information on the existing fire alarm and control systems is also included.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 9_Additional Questions and Answers from industry.pdf | ||
| Attachment_6_ N6660420R8248 Amendment 3.pdf | ||
| Attachment 5 DOD-GUIDANCE-ON-THE-USE-OF-CLOTH-FACE-COVERINGS.PDF | ||
| Attachment 2 SPECIFICATION - NUWC.pdf | ||
| Attachment 3 Past Performance.pdf | ||
| Attachment 4 Covid Questionare.pdf | ||
| N6660420R8248 Amendment 2..pdf | ||
| N6660420Q8248 Amendment 1.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions from Industry
Q1.Please confirm which proposal due date is correct. SF‐1442 section 10 lists October 30th at 2:00pm and section 13 lists October 29th at 2:00pm.
A1. The Proposal due date is hereby extended to 30 October 2020 @ 2:00PM EST.
Q2. Can you please provide some photos of the back side of the building, showing the location of the louver to install and remove equipment from the mechanical room along with showing the existing conditions of the roadway/hillside so that a proper rigging can be assessed.
A2. Please see attachment # 8 for additional photos.
Q3. What is the manufacturer and model # of the existing fire alarm control panel?
A3. The existing fire alarm system is Notifier, the model # could not be located at this time.
4. Who is the fire alarm testing company of record? Also please provide the fire alarm service company and contact information.
A4. Jeff Lambert, SET
NICET IV #82700
Northeast Operations Manager
Office: 610.627.1600 Ext 219
Fax: 610.627.1657
Cell: 610.751.0282 jlambert@kinetixfire.com
Q5. Does NUWC have a proprietary HVAC control system? If so, who is the control vendor/contractor.
A5. Per the specification, the base control system is Johnson. There is no particular contractor.