Amendment N6274225R6504_0001 toktr 080925.pdf
PDF 741 KB Posted
- Solicitation number
- N6274225R6504
About this file
This document is an Amendment of Solicitation/Modification of Contract for a Design-Build project to construct a Boat Maintenance Facility at Naval Base Oyster Bay in Puerto Princesa, Palawan, Philippines. The amendment (Number 0001) includes several key modifications to the original solicitation, specifically addressing site analysis, utilities, roof construction, and exterior enclosure requirements. The proposal due date remains August 14, 2025, at 11:00 a.m. Thailand time.
The amendment provides detailed changes to the Statement of Work, including clarifications on site conditions, power sources, tidal range data, and construction specifications. Notable modifications include adjusting roof overhang dimensions, specifying utility connections, and addressing power infrastructure challenges. The project requires constructing a new boat maintenance facility with provisions for future local power connection, a movable roller gantry crane system, and repair of an existing boat ramp. The contractor will be responsible for conducting their own topographic survey, geotechnical investigations, and ensuring compliance with local and environmental standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Enclosure 4. Blank BOQ.xlsx | XLSX spreadsheet | |
| Enclosure 1. Pre Proposal Inquiry Form.xlsx | XLSX spreadsheet | |
| RFP N6274225R6504 Releaesd w attachments 070425 resized.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
16C. DATE SIGNED
Previous edition unusable STANDARD FORM 30 (REV. 11/2016) Prescribed by GSA FAR (48 CFR) 53.243
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6) CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X) 9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NUMBE
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
Section 00 00 00 - Procurement and Contracting Requirements
The following changes have been made:
Miscellaneous text in this section has been added to:
The following changes will be considered part of this solicitation:
A. Include the following:
- The proposal due date is unchanged and remains August 14, 2025, no later than 11:00 a.m. Thailand time.
B. The following changes are hereby incorporated to solicitation, Parts 3 and 6 under this solicitation.
SUMMARY OF CHANGES
AMENDMENT 0001
PART 3
STATEMENT OF WORK
1. Page 3 of 29, Section 3. SITE ANALYSIS, Sub-section EXISTING SITE CONDITIONS, para. 4
ADD: "There is a port which the military uses exclusively for its operations."
2. Page 4 of 29, Section 3 SITE ANALYSIS, 3.2 UTILITIES, para. 2 and 3
ADD:
"Until PALECO work is complete, the only available power source is the base's existing generator. For construction power, the contractor may use the base generator but shall provide required fuel to support construction activities, or the contractor may provide their own generator. The new facility design must include provisions for connecting to a backup generator per Part 3, Section D5010. Additionally, provision for connection to future local power shall be provided up to 100 meters from the new boat maintenance facility to accommodate future PALECO connection.
The contractor is responsible for providing all necessary electrical infrastructure to complete a fully functional facility, independent of PALECO's timeline."
3. Page 5 of 29, Section 3. SITE ANALYSIS
ADD:
"3.7 TIDAL RANGE OR STORM SURGE DATA
The Government does not possess site-specific tidal range or storm surge data for Naval Base Oyster Bay, Palawan.
However, publicly available data sources indicate that Puerto Princesa (the nearest major city to Naval Base Oyster Bay) experiences the following tidal range data:
1. High tides: Approximately 1.7-2.1 meters above chart datum.
N6274225R65040001
2. Low tides: Approximately 0.2-0.5 meters above chart datum.
3. Typical tidal range: 1.2-1.9 meters.
The awarded contractor shall conduct all surveys and investigations that their Designer of Record deems necessary for facility design completion.
3.7.1 Recommended Data Sources:
1. Philippine Atmospheric, Geophysical and Astronomical Services.
2. Administration (PAGASA): www.pagasa.dost.gov.ph.
3. Permanent Service for Mean Sea Level (PSMSL) Puerto Princesa Station (Station ID 207): psmsl.org.
4. NAMRIA Active Geodetic Station Puerto Princesa (PPPC).
5. UP NOAH Center hazard maps: center.noah.up.edu.ph.
Contractors should verify all data through direct measurement and local surveys, as site-specific conditions may vary significantly from regional estimates."
4. Page 12 of 29, Section 5 WORK REQUIREMENTS, Sub-section 5.3 CLIN 0003: OPTION ITEM 0002 - REPAIR OF EXISTING BOAT RAMP, REMOVAL OF MECHANICAL SYSTEM FOR CRANE, AND ROOF REPLACEMENT /REPAIRS OF EXISTING BOAT HOUSE, Article 1. Repair of Existing Boat Ramp
DELETE: "durable materials such as".
5. Page 12 of 29, Section 6 ENGINEERING SYSTEMS REQUIREMENTS (ESR), Sub-section CLIN 0001: BASE BID ITEM 0001 - CONSTRUCTION OF BOAT MAINTENANCE FACILITY, Article B1020 ROOF CONSTRUCTION
CHANGE FROM:
"Construct an elevated steel rafter roof system with R-19 rockwool insulation on steel framing. Provide minimum of 1.5-m overhang all around. Roofing sheet shall be pre-painted 0.6mm thick long span, gauge 24 metal roof. Provide matching and suitable gutters and PVC downspouts designed for collection of rainwater into a rainwater collection tank above ground. Provide fine mesh corrosion resistant metal screens over gutter and downspouts to filter out debris."
TO:
"Construct an elevated steel rafter roof system with R-19 rockwool insulation on steel framing. Provide overhang with 5m on the long sides and 1m on the gable. Roofing sheet shall be pre-painted 0.6mm thick long span, gauge 24 metal roof.
Provide matching and suitable gutters and PVC downspouts designed for collection of rainwater into a rainwater collection tank above ground. Provide fine mesh corrosion resistant metal screens over gutter and downspouts to filter out debris."
6. Page 14 of 29, Section 6 ENGINEERING SYSTEMS REQUIREMENTS (ESR), Sub-section CLIN 0001: BASE BID ITEM 0001 - CONSTRUCTION OF BOAT MAINTENANCE FACILITY, Article B20 EXTERIOR ENCLOSURE
CHANGE FROM: "b. Construct covered exterior walkway, minimum of 1.5 meters clear, around the building."
TO: "b. Construct covered exterior walkway, and provide overhang that is 5m on the long sides and 1m on the gable ends."
7. Page 25 of 29, Section 6 ENGINEERING SYSTEMS REQUIREMENTS (ESR), Sub-section CLIN 0003:
OPTION ITEM 0002 - REPAIR OF EXISTING BOAT RAMP, REMOVAL OF MECHANICAL SYSTEM
FOR CRANE, AND ROOF REPLACEMENT/REPAIRS OF EXISTING BOAT HOUSE, Article B1020
ROOF CONSTRUCTION
CHANGE FROM:
"Construct an elevated steel rafter roof system with R-19 rockwool insulation on steel framing. Provide minimum of 1.5-m overhang all around. Roofing sheet shall be pre-painted 0.6mm thick long span, gauge 24 metal roof. Provide matching and suitable gutters and PVC downspouts designed for collection of rainwater into a rainwater collection tank above ground. Provide fine mesh corrosion resistant metal screens over gutter and downspouts to filter out debris."
TO:
"Construct an elevated steel rafter roof system with R-19 rockwool insulation on steel framing. Provide overhang that is 5m on the short sides and 2 m on the long side. Roofing sheet shall be pre-painted 0.6mm thick long span, gauge 24 metal roof. Provide matching and suitable gutters and PVC downspouts designed for collection of rainwater into a rainwater collection tank above ground. Provide fine mesh corrosion resistant metal screens over gutter and downspouts to filter out debris."
8. Page 25 of 29, Section 6 ENGINEERING SYSTEMS REQUIREMENTS (ESR), Sub-section CLIN 0003: OPTION ITEM 0002 - REPAIR OF EXISTING BOAT RAMP, REMOVAL OF MECHANICAL SYSTEM FOR CRANE, AND ROOF
REPLACEMENT/REPAIRS OF EXISTING BOAT HOUSE, B20 EXTERIOR ENCLOSURE
CHANGE FROM: "b. Construct covered exterior walkway, minimum of 1.5 meters clear, around the building."
TO: "b. Construct covered exterior walkway, and provide overhang that is 5m on the short sides and 2 m on the "long side.
PART 4
MINIMUM MATERIALS, ENGINEERING AND CONSTRUCTION REQUIREMENTS
9. Page 24 of 30, Section 2 PERFORMANCE TECHNICAL SPECIFICATIONS, Sub-section G. SITE WORK, Article G20 SITE IMPROVEMENTS, Item G2020 PAVED SURFACES
ADD:
"G2020 PAVED SURFACES
Unless noted otherwise in Part 3 or Part 6, provide a minimum compressive strength at 28 days of 3500 psi (25 MPa) concrete. One-bagger mixers are acceptable for foundation concrete provided the concrete meets the minimum 28-day compressive strength requirements and complies with ACI 301 standards. The 210 kg/cm2 limitation cited in Part 4, Section B10 applies specifically to job-mixed superstructure concrete, not foundation elements.
For soil erosion prevention during excavation, ensure excavations are backfilled as soon as possible after concrete placement and work completion, as required by the RFP excavation safety provisions."
B. For clarification, responses to offerors' inquiries are provided under Attachment 1 - PPIs and Answers.
C. The following attachment is incorporated to the RFP:
- Attachment 1 PPIs and Answers.
All other paragraphs, provisions, and conditions remain unchanged.
N6274225R6504_0001 Attachment 1.
Question No. Reference (Sect/Para/Page) QUESTION GOVERNMENT RESPONSE: 2025-08-01 1 Section 2.1, Paragraph 2, Page 3 What is the finished floor level (FFL)? Per Part 3, Section 6. ENGINEERING SYSTEMS REQUIREMENTS (ESR) CLIN 0001: BASE BID ITEM 0001 –
CONSTRUCTION OF BOAT MAINTENANCE FACILITY, Sub-Section G10 SITE PREPARATION, Article G1030 SITE EARTHWORK, Item G1030001 GRADING "b. Finished floor elevations for new facilities shall be a minimum of 50 cm above the ground level".
2 Section 2.1, Paragraph 2, Page 3 What are the tidal ranges and maximum storm surge levels in Oyster Bay?
Per Summary of Changes, Item no. 1. On Page 5 of 29, Section 3. SITE ANALYSIS, "3.7 TIDAL RANGE OR
STORM SURGE DATA
The Government does not possess site-specific tidal range or storm surge data for Naval Base Oyster Bay, Palawan.
However, publicly available data sources indicate that Puerto Princesa (the nearest major city to Naval Base Oyster Bay) experiences the following tidal range data:
1.High tides: Approximately 1.7-2.1 meters above chart datum 2.Low tides: Approximately 0.2-0.5 meters above chart datum 3.Typical tidal range: 1.2-1.9 meters
The awarded contractor shall conduct all surveys and investigations that their Designer of Record deems necessary for facility design completion.
3.7.1 Recommended Data Sources:
1.Philippine Atmospheric, Geophysical and Astronomical Services 2.Administration (PAGASA): www.pagasa.dost.gov.ph 3.Permanent Service for Mean Sea Level (PSMSL) Puerto Princesa Station (Station ID 207): psmsl.org 4.NAMRIA Active Geodetic Station Puerto Princesa (PPPC) 5.UP NOAH Center hazard maps: center.noah.up.edu.ph
Contractors should verify all data through direct measurement and local surveys, as site-specific conditions may vary significantly from regional estimates." was added.
Per Part 2, Section 5, paragraph 1: "Perform topographical survey, soil investigations, field investigations and verification of existing site conditions as may be required to support the development of the design and construction of the project."
The awarded contractor shall conduct all surveys and investigations that their Designer of Record deems necessary for facility design completion.
3 Section 2.3.1, Paragraph 1, Page
What is the bearing capacity of the soil? Is geotechnical investigation available?
Per Part 3, Section 3. SITE ANALYSIS, Sub-section 3.4 SOIL CONDITION "Soil conditions are unknown for this site. However, for the purpose of preparing and submitting a proposal, offerors shall assume a calculated allowable bearing capacities ranging from 72 kPa to 84 kPa at the depth of 1.50 m to 2.00 m. The contractor shall verify this information by performing its own geotechnical investigation in accordance with succeeding sections in this RFP."
4 Section 2.5.3, Page 6 How will surface drainage be managed to avoid contamination of coastal waters?
Per Part 3, Section 3.6 SITE DEVELOPMENT, "Implement suitable approved measures for drainage including siltation and contamination control of the site and surrounding waterways throughout the construction duration and upon project completion." Additionally, per Part 3, Section 3.6, "Install temporary erosion control measures to prevent soil displacement and water runoff that could affect neighboring properties or sensitive areas during site work" and "Coordinate regularly with environmental and regulatory authorities to ensure all construction activities comply with local, national and environmental standards, especially in terms of waste disposal and pollutant control."
SOURCE SELECTION INFORMATION - SEE FAR 2.101 AND 3.104
Question No. Reference (Sect/Para/Page) QUESTION GOVERNMENT RESPONSE: 2025-08-01 5 Section 2.2, Paragraph 4 and 5, Page 3–4 Is there a sea wall, slipway, or launch ramp needed? What are their required slopes and materials?
There is no Section 2.2, Paragraph 4 and 5, Page 3-4" that discusses sea walls, slipways, or launch ramps. The Government response assumes the contractor is referring to the existing boat house repair work under CLIN 0003.
No new sea wall, slipway, or launch ramp is required for this project. Per Part 3, Section 5.3, "CLIN 0003: OPTION ITEM 0002 – REPAIR OF EXISTING BOAT RAMP, REMOVAL OF MECHANICAL SYSTEM FOR CRANE, AND ROOF REPLACEMENT/REPAIRS OF EXISTING BOAT HOUSE" and specifically "Rebuild the ramp using reinforced concrete. Ensure the ramp meets current safety and accessibility standards."
The existing boat ramp will be repaired using reinforced concrete and must address the current steep slope issue. Per Part 3, Section 2, "The upgrades are designed to mitigate the steep incline of the existing ramp, which currently impedes the proper launching of watercraft. The extended ramp will accommodate various vessels, ensuring efficient operations." The ramp must support 11.6m (38ft) unmanned surface vessels and conventional watercraft per Part 3, Section 3.4.
Per Part 4, Section B1010, "The ramp surface should be slip-resistant. Ensure the ramp meets all ADA (Americans with Disabilities Act) requirements for accessibility." The Designer of Record shall determine the specific slope based on vessel requirements, site conditions, and applicable codes. Industry standards for boat ramps supporting 38ft vessels typically require slopes between 1:12 to 1:15 for safe launching operations.
6 Section 2.4, Page 5 What the extend of repair and demolition of the existing structure e.g. the roofing, boat ramp, driveway etc.
Refer to Part 3, Section 5. WORK REQUIREMENTS, Sub-section 5.3 CLIN 0003: OPTION ITEM 0002 – REPAIR
OF EXISTING BOAT RAMP, REMOVAL OF MECHANICAL SYSTEM FOR CRANE, AND ROOF
REPLACEMENT/REPAIRS OF EXISTING BOAT HOUSE for the detailed requirements.
The extent of work includes rebuilding the existing boat ramp with reinforced concrete meeting safety standards, removing all crane mechanical system components with proper disposal and restoring affected structural elements, and complete roof replacement of the existing boat house with new materials and waterproofing systems.
7 Part 4 - A10 Foundation p.4 of
Can we use One bagger Mixer for mixing concrete due to small volume of concrete requirement for footing? This can immediately be poured to every footing excavation completed to avoid soil erotion after excavation.concrete will still be in accordance to contract strength requirement?
Yes, with limitations. Per Part 4, Section 2, SECTION A. SUBSTRUCTURE, A10 FOUNDATION, "Design and construct foundations of reinforced concrete. Comply with IBC and applicable UFGS standards." Additionally, per
Summary of Changes, Item no. 9. 3.On Page 24 of 30, Section 2 PERFORMANCE TECHNICAL SPECIFICATIONS, Sub-section G. SITE WORK, Article G20 SITE IMPROVEMENTS, Item G2020 PAVED
SURFACES, "G2020 PAVED SURFACES
Unless noted otherwise in Part 3 or Part 6, provide a minimum compressive strength at 28 days of 3500 psi (25 MPa) concrete. One-bagger mixers are acceptable for foundation concrete provided the concrete meets the minimum 28-day compressive strength requirements and complies with ACI 301 standards. The 210 kg/cm2 limitation cited in Part 4, Section B10 applies specifically to job-mixed superstructure concrete, not foundation elements.
For soil erosion prevention during excavation, ensure excavations are backfilled as soon as possible after concrete placement and work completion, as required by the RFP excavation safety provisions."
8 B2010 Exterior Walls Part 3
Perimeter Wall of Existing Boat Ramp Facility Corroded Welded Wire mesh with pipe frame, is it going to be included to the replacement including existing Gate?
No. Repair and improvement of perimeter wall, and gate of existing boat ramp facility is not required in the statement of work.
9 Can we use existing port for delivery of materials and equipment using barge.
No. Per Summary of Changes, Item no. 3. 3.On Page 3 of 29, Section 3. SITE ANALYSIS, Sub-section EXISTING SITE CONDITIONS, para. 4, "There is a port which the military uses exclusively for its operations."
Question No. Reference (Sect/Para/Page) QUESTION GOVERNMENT RESPONSE: 2025-08-01 10 We need to clarify the statement:Overhang: 5m in front and 1m on the back and gable ends. Part 4 also mentions a minimum of 2 m overhang all around for the roof construction.
Part 3 states a minimum of 3m overhang in front and 1.5m on back and sides. Which of these must prevail?
Per Summary of Changes Item no 4. On Page 12 of 29, Section 6 ENGINEERING SYSTEMS REQUIREMENTS (ESR), Sub-section CLIN 0001: BASE BID ITEM 0001 – CONSTRUCTION OF BOAT MAINTENANCE FACILITY, Article B1020 ROOF CONSTRUCTION, the statement was change to "Construct an elevated steel rafter roof system with R-19 rockwool insulation on steel framing. Provide overhang with 5m on the long sides and 1m on the gable. Roofing sheet shall be pre-painted 0.6mm thick long span, gauge 24 metal roof. Provide matching and suitable gutters and PVC downspouts designed for collection of rainwater into a rainwater collection tank above ground. Provide fine mesh corrosion resistant metal screens over gutter and downspouts to filter out debris.";
Per Summary of Changes Item no 5.On Page 25 of 29, Section 6 ENGINEERING SYSTEMS REQUIREMENTS (ESR), Sub-section CLIN 0003: OPTION ITEM 0002 – REPAIR OF EXISTING BOAT RAMP, REMOVAL OF MECHANICAL SYSTEM FOR CRANE, AND ROOF REPLACEMENT/REPAIRS OF EXISTING BOAT HOUSE, Article B1020 ROOF CONSTRUCTION, the statement was change to "Construct an elevated steel rafter roof system with R-19 rockwool insulation on steel framing. Provide overhang that is 5m on the short sides and 2 m on the long side. Roofing sheet shall be pre-painted 0.6mm thick long span, gauge 24 metal roof. Provide matching and suitable gutters and PVC downspouts designed for collection of rainwater into a rainwater collection tank above ground.
Provide fine mesh corrosion resistant metal screens over gutter and downspouts to filter out debris.";
Per Summary of Changes Item no. 6.On Page 14 of 29, Section 6 ENGINEERING SYSTEMS REQUIREMENTS (ESR), Sub-section CLIN 0001: BASE BID ITEM 0001 – CONSTRUCTION OF BOAT MAINTENANCE FACILITY, Article B20 EXTERIOR ENCLOSURE, the statement was change to "b.Construct covered exterior walkway, and provide overhang that is 5m on the long sides and 1m on the gable ends."and
Per Summary of Changes Item no. 7.On Page 25 of 29, Section 6 ENGINEERING SYSTEMS REQUIREMENTS (ESR), Sub-section CLIN 0003: OPTION ITEM 0002 – REPAIR OF EXISTING BOAT RAMP, REMOVAL OF MECHANICAL SYSTEM FOR CRANE, AND ROOF REPLACEMENT/REPAIRS OF EXISTING BOAT HOUSE, B20 EXTERIOR ENCLOSURE, the statement was change to "b. Construct covered exterior walkway, and provide overhang that is 5m on the short sides and 2 m on the long side."
11 SCAFFOLDINGS
- Is it acceptable to use coco lumber or good lumber for scaffolding?
Yes, lumber may be used for scaffolding. Per Part 2, Section 31, Sub-section 21.A.i, "Load-carrying timber members shall be a minimum of 1,500 lb-force/in² (10,341 kPa) (stress grade) construction lumber." Additionally, per Sub-section 21.A.j, "Lumber shall be reasonably straight-grained and free of shakes, checks, splits, cross grains, unsound knots or knots in groups, decay and growth characteristics, any condition that would decrease the strength of the material."
All scaffolding construction must comply with EM 385-1-1 requirements and be supervised by a Competent Person for Scaffolding as specified in the contract documents.
12 Please consider additional time for the due date, more time is needed to prepare the proposal
The proposal due date remains 14 August 2025, no later than 11:00 am Thailand time.
13 Please confirm that the only equipment to be provide is the rolling gantry and the boats are not to be included - the cut sheets is provided as reference only
Confirmed. Per Part 3, Section 5, Sub-section 5.2 CLIN 0002: OPTION ITEM 0001 – PROVIDE MAINTENANCE FACILITY EQUIPMENT, "Provide one (1) complete movable roller gantry crane system." Only a movable roller gantry crane system is required to be provided. The cut sheets referenced are for informational purposes only, and boats are not included in the equipment procurement scope.
14 Can the Quality Control and Safety Person be the same person listed as Key Personnel
No.per Part 3, Section 4. PROJECT REQUIREMENTS, Sub-section 4.4 KEY PERSONNEL, the solicitation requires "Dedicated Superintendent, Dedicated Quality Control Manager, and Dedicated Site Safety Health Officer (3 different people on site during production at all times)"
Question No. Reference (Sect/Para/Page) QUESTION GOVERNMENT RESPONSE: 2025-08-01 15 Is this Project VAT Exempt? Per Page 33 of 42, DFAR 252.229-7001 Tax Relief, this project is not VAT exempted.
16 Will there be assistance for Importation of Materials as needed? No. This Design-Build project will not provide assistance for importation of materials to the contractor.
17 Can Contractor set up a personnel living camp on the project site? Yes. Per Part 3 Section 3.3 TEMPORARY CONSTRUCTION FACILITIES AND CONTROL “Contractor shall be allowed to establish temporary workers' barracks in the vicinity of the project site subject to HN approval.”
18 Work will be within the 50km radius. We noticed that powerline from utility ( PALECO ) is not completed yet which means it can included in the proposal?
No, construction shall proceed regardless of PALECO's power line completion status. Per Part 2, Section 2.4, Technical Solution submittal requirements: "Indicate the locations of the internal access roads, drainage systems, connecting utility points (water and power), and the existing road within a 50-kilometer radius of the facility."
Additionally, Part 3, Section 3.2 states: "Contractor is allowed to connect to nearby existing primary power line and water line, with HN coordination. Note that contractor will have to provide their own step-down transformer and facilitate actual connection with supervision from the base engineer."; and Summary of Changes, Item no. 8. On Page 4 of 29, Section 3 SITE ANALYSIS, 3.2 UTILITIES, para. 2 and 3, added "Until PALECO work is complete, the only available power source is the base's existing generator. For construction power, the contractor may use the base generator but shall provide required fuel to support construction activities, or the contractor may provide their own generator. The new facility design must include provisions for connecting to a backup generator per Part 3, Section D5010. Additionally, provision for connection to future local power shall be provided up to 100 meters from the new boat maintenance facility to accommodate future PALECO connection.
The contractor is responsible for providing all necessary electrical infrastructure to complete a fully functional facility, independent of PALECO's timeline."
19 Is there any available data? If none, may we be allowed to enter with our topo survey team?
No, there is no existing topographic data available. Per Part 3, Section 3.5, "The Contractor shall be responsible for providing the services of a geotechnical engineer to conduct any subsurface exploration, investigation, testing, and analysis that the Designer of Record (DOR) deems necessary for the design and construction of the proposed project and site improvements" and "The contractor shall also perform topographic survey of the existing site." Additionally, per Part 3, Section G10, "Perform a topographic survey of the project area that will be impacted by the work. Include the topographic survey in all design submittals."
The contractor must conduct their own topographic survey as part of the contract requirements.
Site access other than during the Pre-Proposal Site Visit (PPSV) which was completed on July 17, 2025, will not be granted at this stage of the solicitation. Per Section 00 21 00, Instructions to Offerors, "Any inspection of the project site outside of the scheduled site visit without Contracting Officer approval will result in Contractor being ineligible for award based on having a competitive advantage over other contractors for conducting an unscheduled site visit."
20 RFP Part 2; Paragraph 9.1 - Design Submittal Required
In the solicitation, UFGS is required. The project is situated in the Philippines, with functional and effective building code, specifications, etc. Can the contractor follow the host nation regulations related to design and construction. Otherwise, will the government provide additional days to compensate the design phase with the UFGS in consideration?
No, there is no existing topographic data available. Per Part 3, Section 3.5, "The Contractor shall be responsible for providing the services of a geotechnical engineer to conduct any subsurface exploration, investigation, testing, and analysis that the Designer of Record (DOR) deems necessary for the design and construction of the proposed project and site improvements" and "The contractor shall also perform topographic survey of the existing site." Additionally, per Part 3, Section G10, "Perform a topographic survey of the project area that will be impacted by the work. Include the topographic survey in all design submittals."
The contractor must conduct their own topographic survey as part of the contract requirements.
Site access other than during the Pre-Proposal Site Visit (PPSV) which was completed on July 17, 2025, will not be granted at this stage of the solicitation. Per Section 00 21 00, Instructions to Offerors, "Any inspection of the project site outside of the scheduled site visit without Contracting Officer approval will result in Contractor being ineligible for award based on having a competitive advantage over other contractors for conducting an unscheduled site visit."
| IDCode: J |
| Page: 1 |
| Pages: 5 |
| AmendNo: 0001 |
| EffDate: 09 Aug 2025 |
| ReqNo: See Continuation Sheet |
| ProjNo: N6274225R6504 |
| IssCode: N62742 |
| AdmCode: |
| IssuedBy: NAVFACSYSCOM PACIFIC |
258 MAKALAPA DR STE 100, JBPHH HI 96860-3134
JBPHH, HI 96860-3134
UNITED STATES
ARTITAR UDIT, Email: artitar.udit.ln@us.navy.mil Telephone: 6622871036 AdminBy:
SCD: PAS:
| ContractorNameAdd: |
| Code: |
| FacCode: |
| SolChg: 1 |
| SolNo: N6274225R6504 |
| SolDate: 02 Jul 2025 |
| AwardChg: Off |
| AwardNo: |
| AwardDate: |
| Amended: 1 |
| OffrExt: Off |
| OffrNoEx: 1 |
| NoCopies: 1 |
| ApprData: See Section G - Contract Administration Data |
| ChgeOrd: Off |
| ChgeOrder: |
| Modify: Off |
| SuppAgre: Off |
| SuppAuth: |
| ModOthr: Off |
| OthrSpec: |
| NoReq: Off |
| Require: Off |
| Copies: |
| Descript: N6274225R6504 D/B Construct Boat Maintenance Facility, Puerto Princesa, Palawan, Philippines |
Detail of Amendment 0001 continues in the following page.
| ContNameTitle: |
| CoNameTitle: Rondel Williams |
| ContDate: |
| CODate: 08 Aug 2025 |