This document contains pre-proposal questions and answers related to solicitation number N62742-21-R-1333 for construction of a medical/dental clinic on Guam. The opportunity involves construction of a multi-story branch health clinic to provide primary medical and dental care. Services required include administration, primary care, optometry, behavioral health, preventive medicine, pharmacy, laboratory, radiology, physical therapy, dental clinic, logistics, and common areas. The document addresses questions from potential offerors relating to specifications, drawings, and contract requirements. The estimated value is between $25-100 million and the period of performance is 730 calendar days. The Navy is the contracting agency and the facility will be funded through a contribution from the Government of Japan.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Notice No. 4.pdf | ||
| Notice No. 3.pdf | ||
| Notice No. 2.pdf | ||
| Notice No. 1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE NAVY
NAVAL FACILITIES ENGINEERING COMMAND, PACIFIC
258 MAKALAPA DR., STE. 100
PEARL HARBOR, HI 96860-3134
Notice No. 5
24 November 2020
PRE-PROPOSAL QUESTIONS & ANSWERS
RFP N62742-21-R-1333
J-025 GOJ MEDICAL/DENTAL CLINIC, FINEGAYAN,
US NAVSUPPACT MCB GUAM
NOTE: The following questions and answers are provided for INFORMATION ONLY. The RFP remains unchanged unless it is amended in writing on a Standard Form 30.
149. Please provide spec for P1965-Eyewash, Wall Mounted, Hands-Free listed on Drawing No. Q-100.
ANSWER: Please refer to Section 22 00 70 par. 2.10.5.2.1 EW-1 JSN P1960 should read as JSN P1965. See forthcoming Amendment 0004.
150. Reference Drawing Sheet P-002, Drawing No. Q-100 and Specification Division 22; Item No. P3080S is missing from the specifications. Please advise.
ANSWER: P3080S added in forthcoming Amendment 0004.
151. Reference Drawing Sheet P-002 and Drawing No. Q-100 Item P3080S states “Similar to JSN indicated but with Manual Faucet” in the notes on P-002. On Sheet Q-100, P3080S is listed as Lavatory, Vitreous China, Auto infrared. Please clarify if plumber will provide this sink with Manual Faucet instead of auto infrared sensor faucet.
ANSWER: Use Manual Faucet as noted on P-002.
152. Reference Specification Division 22- Plumbing and Drawing Sheet P-002; P3080S is missing from Specification.
ANSWER: See RFI#150 response.
153. Reference Specification Division 22-Plumbing, Drawing No. P-002 and Drawing No. Q- 100; Item P8710 listed on Q-100 is missing specifications and is not listed on P-002. Please clarify.
ANSWER: Provide OATEY Model T13H153” Utility Center, Plumbing Connection or approved equal. Provide with 2” Drain. See forthcoming Amendment 004.
154. Reference Specification Division 22, Drawing No. P-002, and Drawing No. Q-100; Item P8711 listed on Q-100 is missing specifications and not listed on P-002. Please clarify.
ANSWER: Similar to RFI#153 response but without Hot water and drain connections. See forthcoming Amendment 004.
155. Reference Specification Division 22, Drawing No. P-002, and Drawing No. Q-100;
P9051R listed on Drawing No. P-002 and Q-100 is missing specifications. Spec section 22 00 70 para 2.10.5.9.1 lists item no. P95051R. Please clarify.
ANSWER: Spec Section 22 00 70 par. 2.10.5.9.1 WC-1 should read as (Similar to JSN P9051R). See forthcoming Amendment 004.
156. Reference Specification Division 22, Drawing No. P-002, and Drawing No. Q-100; Item R2201- Fountain, Water, CRS, Wall Mounted, 2 Level, is missing from Equipment Schedule on Drawing No. P-002. Please advise.
ANSWER: Include R2201 as shown in Q-100.
157. Reference Drawing Sheet No. P-002 and Q-100; L2000 is listed on drawing No. Q-100 as Government Furnish Government Installed. However, P-002 lists this item on the Contractor Furnished Equipment Schedule. Please clarify if this item is GFGI or CFCI. If it is a contractor furnished item, please indicate which spec section covers this item.
ANSWER: L2000 is GFGI.
158. Reference Drawing Sheet A-632; Detail A4/A-632 is missing from Window Schedule.
Please advise.
ANSWER: See forthcoming Amendment 0004.
159. Per Notice 4 response to RFI 68, all Cxxx cabinets are not part of Healthcare Casework.
These cabinets are to Plastic-Laminate-Clad Architectural Cabinets. Please provide elevation section details of these cabinets. Cabinets are shown on interior elevation sheets A-433 and A- 434 but missing elevation section details.
ANSWER: Cxxx cabinets are premanufactured. Provide as shown in interior elevations, equipment schedule and specifications.
160. Reference Drawing Sheet A-750; Detail D1/A-750 shows waterproofing is required on the exterior side of wall and footing below grade. Please confirm if Elastomeric Sheet Waterproofing (Spec section 07 13 53) is the material intended for this application. If not, please provide waterproofing type and specification.
ANSWER: Confirmed. Elastomeric sheet waterproofing is intended for below grade wall and footing.
161. Louver No. 14 and No 15 shown on drawing sheet A-141 and A-210 are missing from the Louver Types on sheet A-631. Please advise.
ANSWER: Addressed in Amendment 0003.
162. Due to covid-19 pandemic, holiday season affecting vender and supplier response time, and multiple military bids bidding around the same time, we respectfully request for the proposal due date to be extended for at least 4 weeks from December 2, 2020 to December 23, 2020.
ANSWER: The Government will not be granting an extension.
163. Reference A-630 and A-631; Storefronts 1G02 and 1G04 are shown as Type F with widths of 12.5 feet whereas Type F Storefronts 2G01S and 2G01U have widths of 11.5 feet.
Please advise on the discrepancy and revise Storefront Type F dimensions on sheet A-631 as necessary.
ANSWER: See forthcoming Amendment 0004.
164. Reference Specification Section 07 27 10.00 10 – Air Barrier; Building Wall sections do not show air barrier on walls. Please clarify what type of air barrier material is to be used on exterior walls and provide specification.
ANSWER: The construction materials should make up the air barrier system. Specifications call for contractor to take responsibility for the means, methods, and workmanship of the installation of the air barrier system
165. Specification Section 07 27 10.00 10 para 3.1.3(n) calls for cohesion tests for spray polyurethane foam. Please clarify where spray polyurethane foam is to be used and provide specification.
ANSWER: Specification section indicated to conduct the following tests and inspections as applicable. If polyurethane foam is not used, then the test would not be applicable.
166. Drawing detail B4/A-750 and B5/A-750 includes exterior SSTL Access Panel. Please provide details and specifications for exterior access panel.
ANSWER: Access panels are specified in SECTION 08 31 00 ACCESS DOORS AND
PANELS.
167. Drawing sheet A-504 indicates wall panel PSI. Please clarify what is PSI and provide specifications.
ANSWER: PSI should be PNL1. See forthcoming Amendment 0004.
168. Drawing details specifies different sizes of expansion anchors. Specs section 05 50 13 paragraph 2.2.7.1 calls for expansion anchors shall be evaluated in accordance with ACI 355.2 category 1 or 2 and shall be tested in accordance with ICC ES AC193 for all mandatory and optional tests. Please clarify if all expansion anchors called out in the project including division 13 and 23 should comply with this requirement.
ANSWER: Confirmed. Section 05 50 13 covers requirements for all expansion anchors.
169. Specs section 13 48 00 paragraph 3.3.4.2 pull out testing of expansion & chemically bonded anchor bolts. Please clarify if this section requires only seismic bracing related anchor bolts including fire sprinkler seismic bracings regardless of size.
ANSWER: Confirmed. Section 13 48 00 covers anchor bolts in seismic related installations.
170. Specs section 23 05 48.19 paragraph 3.10.2 pull out testing of expansion and chemically bonded anchor bolts for HVAC equipment. Please confirm if this section requires all anchors to be tested regardless of size.
ANSWER: Confirmed. Section 25 05 48.19 covers all HVAC equipment anchors.
171. Pending release of forthcoming amendment 003 and with the coming thanksgiving holiday, we are requesting the bid due date to be extended by one week.
ANSWER: The Government will not be granting an extension.