AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

RFP N62742-18-R-1306, WON# 1366475, FY15 MILCON COMBINED COMMUNICATIONS GATEWAY GERALDTON AT THE AUSTRALIAN DEFENCE

SATELLITE COMMUNICATIONS STATION, KOJARENA, WA

Amendment No. 0006 is continued on page 2.

1. CONTRACT ID CODE PAGE OF PAGES

1 7

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X N6274218R1306

X 9B. DATED (SEE ITEM 11)

28-Nov-2017

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

26-Jan-2018

CODE

NAVFAC PACIFIC

A-E/CONSTR CONTRACTS BRANCH (CODE ACQ31)

258 MAKALAPA DR STE 100

JBPHH HI 96860-3134

N62742 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

N6274218R1306 Amendment No. 0006

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

DOCUMENT 00 01 15 LIST OF DRAWINGS

1.2 CONTRACT DRAWINGS

The following drawings are revised as of January 18, 2018:

NAVFAC Dwg. Nos. 19069844, 19069853, 19069854, 19069855, 19069856, 19069857, 19069862, 19069863, 19069865, 19069866, 19069867, 19069868, 19069869, 19069870, 19069871, 19069872, 19069878, 19069881, 19069888, 19069890, 19069891, 19069897, 19069898, 19069899, 19069900, 19069901, 19069902, 19069903, 19069913, 19069915, 19069916, 19069917, 19069918, 19069919, 19069920, 19069921, 19069923, 19069924, 19069925, 19069929, 19069930, 19069934, 19069935, 19069936, 19069947, 19069948, 19069949, 19069951, 19069952, 19069953, 19069954, 19069955, 19069956, 19069957, 19069958, 19069959, 19069960, 19069961, 19069962, 19069963, 19069964, 19069965, 19069966, 19069967, 19069968, 19069969.

These revised drawings accompany this amendment.

On NAVFAC Dwg. No. 19069855 (C-003)

Inset: Revise cross reference “C3/C-006” to: C3/C-007.”

On NAVFAC Dwg. No. 19069859 (C-007)

Holding Tank A1/C-004/C-007: In Plan view, before “OVERFLOW OUTLET”, add “CAP.” In Section view, after “OVERFLOW OUTLET”, add “, CAPPED.”

On NAVFAC Dwg. No. 19069861 (S-001)

In the Structural General Notes, item 13, revise spelling of “THRU” to “THROUGH”.

On NAVFAC Dwg. 19069873 (S-501)

In the Antenna Foundation Notes, item 2, revise “LAP BARS A MINIMUM DISTANCE OF 30 BAR DIAMETERS” to read “REFER TO DRAWING S-002”.

On NAVFAC Dwg.19069874 (S-502)

In Sections A3 and C3, delete leftmost note “N24 CENTERED IN SLAB AT SIDES ONLY” for clarity.

On NAVFAC Dwg. 19069875 (S-601)

In the Fire Protection Water Tank Notes, item 3, revise “194” kPa to read “200” kPa.

On NAVFAC Dwg. 19069887 (A-503)

In Detail C1/A-503, delete handrail on the wall side since the egress stair width is less than 2000mm.

On NAVFAC Dwg. 19069889 (A-701)

In Detail C3/A-701, revise door frame note to read as “INSULATED MET FIRE DOOR FRAME” Revise the door bottom undercut note to read as “10mm MAX UNDERCUT”

On NAVFAC Dwg. 19069911 (P-001)

In the Plumbing Notes, add the following:

10. ALL CONDENSATE DRAIN PIPING AND SANITARY DRAIN PIPING SHALL BE INSTALLED AT A

MINIMUM SLOPE OF 2%.

SECTION 01 11 00 SUMMARY OF WORK

In attachment Project No. BDA 1361-P1 Specification for Provision of new Distribution Transformers and Kiosk Substations, paragraph 1.6 Drawings, delete this paragraph in its entirety and replace with “See section 00 01 15 LIST OF DRAWINGS, paragraph 1.2 CONTRACT DRAWINGS”.

In attachment Project No. BDA 1361-P1 Specification for Provision of new Distribution Transformers and Kiosk Substations, delete Appendix A Drawings in its entirety.

In attachment Project No. BDA 1361-P2 Specification for Provision of new 11kV Switchgear, paragraph 1.6 Drawings, delete this paragraph in its entirety and replace with “See section 00 01 15 LIST OF DRAWINGS, paragraph 1.2 CONTRACT DRAWINGS”.

In attachment Project No. BDA 1361-P2 Specification for Provision of new 11kV Switchgear, delete Appendix A Drawings in its entirety.

In attachment Project No. BDA 1361-P3 Specification for Upgrading of Station Electrical Infrastructure, paragraph

1.5 Drawings, delete this paragraph in its entirety and replace with “See section 00 01 15 LIST OF DRAWINGS, paragraph 1.2 CONTRACT DRAWINGS”.

In attachment Project No. BDA 1361-P3 Specification for Upgrading of Station Electrical Infrastructure, delete Appendix A Drawings in its entirety.

In attachment Project No. BDA 1361-P3 Specification for Upgrading of Station Electrical Infrastructure, delete Appendix B and refer to Section 01 14 00 WORK RESTRICTIONS.

SECTION 03 30 00 CAST-IN-PLACE CONCRETE

Paragraph 1.1 References, insert the following after ASTM E96/E96M):

AUSTRALIAN STANDARDS

CCAA Data Sheet TCS 2005 Tolerances for Concrete Surfaces

AS/NZS ISO 9001 2016 Quality management systems - Requirements

SAA HB 28 1997 Design of residential slabs and footings

AS 1379 2007 Specification and supply of concrete

CCAA Data Sheet HWC 2004 Hot-Weather Concreting

CCAA Data Sheet CWC 2004 Cold-Weather Concreting

AS 3600 2009 Concrete structures

AS 3610 1995 Formwork for concrete

AS/NZS 1554.3 2014 Structural steel welding - Welding of reinforcing steel

AS/NZS 4671 2001 Steel reinforcing materials

AS 1141.1 2015 Methods for sampling and testing aggregates - Definitions

AS 1141.60.1 2014

Methods for sampling and testing aggregates - Potential alkali-silica reactivity - Accelerated mortar bar method

AS 1012.3 2014

Methods of testing concrete - Determination of properties related to the consistency of concrete - Slump test

AS 1012.1 2014 Sampling of concrete

AS 1012.4.3 2014

Methods of testing concrete - Determination of air content of freshly mixed concrete - Measuring air volume when concrete is dispersed in water

AS 1012.8.1 2014

Methods of testing concrete - Method for making and curing concrete - Compression and indirect tensile test specimens

AS 1012.4.2 2014

Methods of testing concrete - Determination of air content of freshly mixed concrete - Measuring reduction in air pressure in chamber above concrete

AS 1012.8.4 2005

Methods of testing concrete - Method for making and curing concrete - Drying shrinkage specimens prepared in the field or in the laboratory

AS 2758.1 2014 Concrete aggregates

AS 1478.1 2000 Admixtures for concrete

AS 3582.1 2016 Fly ash

AS 1012.8.2 2014 Method for making and curing concrete - Flexure test specimens

AS 3582.2 2016

Supplementary cementitious materials - Slag - Ground granulated blast-furnace

AS/NZS 2269.0 2012 Plywood - Structural – Specifications

SECTION 03 30 00 CAST-IN-PLACE CONCRETE

Paragraph 2.3.1.5 Building Walls is amended to delete the last sentence “Maximum slump may be increased 25 mm for methods of consolidation other than vibration”.

SECTION 03 30 00 CAST-IN-PLACE CONCRETE

Delete Paragraph 2.5.1.1 Weldable Reinforcing Bars.

SECTION 03 30 00 CAST-IN-PLACE CONCRETE

Delete Paragraph 2.5.5 Dowels for Load Transfer in Floors.

SECTION 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

Delete first sentence in Paragraph 2.2.3 Sprinklers.

SECTION 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

Paragraph 2.2.5 Pipe Supports, add “and AS2118.9” after “NFPA 13”.

SECTION 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

Paragraph 2.2.8 Fire Department Connections, replace paragraph title in its entirety with “Fire & Rescue (F&R) Western Australia Brigade Booster Assembly”.

SECTION 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

Paragraph 2.2.8 Fire Department Connections, 1st sentence replace “department connection” with “and Rescue Western Australia Brigade Booster Assembly” and add “and in accordance with AS2419.1” after “personnel equipment”.

SECTION 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

Paragraph 2.4.1 Sprinkler Cabinet, add “and AS2118.1” after “NFPA 13”.

SECTION 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

Paragraph 3.2 UNDERGROUND PIPING INSTALLATION, add “, AS2419.1, AS2118.9 ” after “NFPA 24”.

SECTION 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

Paragraph 3.3 ABOVEGROUND PIPING INSTALLATION, add “, AS2419.1, AS2118.9 ” after “NFPA 13”.

SECTION 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

Paragraph 3.3.3 Pipe Joints, add “AS2118.9 and AS4118.2.1” after “NFPA 13”.

SECTION 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

Paragraph 3.3.8 Installation of Fire Department Connection, delete “Fire Department Connection” in subheading title and replace with “Fire and Rescue Western Australia Booster Assembly”.

SECTION 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

Paragraph 3.3.8 Installation of Fire Department Connection, delete paragraph in its entirety and replace with “Fire and Rescue Western Australia booster assembly shall be provided in accordance with AS2419.1”

SECTION 21 22 01.00 20 HFC-227EA FIRE EXTINGUISHING

Paragraph 1.2.1 Description of Work, add “and AS ISO 14520.1” after “NFPA 2001” in second sentence.

SECTION 21 22 01.00 20 HFC-227EA FIRE EXTINGUISHING

Paragraph 1.5 DESIGN OF HFC-227ea FIRE EXTINGUISHING SYSTEMS, add “and AS14520-1” after “NFPA 2001 and”.

SECTION 21 22 01.00 20 HFC-227EA FIRE EXTINGUISHING

Paragraph 1.5.1 Piping Layout and Wiring Diagrams, add “and AS14520-1” after “NFPA 2001”.

SECTION 21 22 01.00 20 HFC-227EA FIRE EXTINGUISHING

Paragraph 1.5.2 Calculations, add “and AS14520-1” after “NFPA 2001”.

SECTION 21 22 01.00 20 HFC-227EA FIRE EXTINGUISHING

Paragraph 2.3.1 Storage Batteries, replace the number “15” with “30” to read “30 minutes”.

SECTION 21 22 01.00 20 HFC-227EA FIRE EXTINGUISHING

Paragraph 2.8 ALARM SIGNALING DEVICES, add “and AS14520.1” after “NFPA 2001”.

SECTION 21 22 01.00 20 HFC-227EA FIRE EXTINGUISHING

Paragraph 2.11.1 Wiring, add “and AS1670.1” after “NFPA 70”.

SECTION 21 30 00 FIRE PUMPS

Paragraph 1.1 SUMMARY, add “and AS2941” after “NFPA 72”.

SECTION 21 30 00 FIRE PUMPS

Paragraph 1.2.1 Fire Pump, delete the sentence “The fire pump shall automatically stop operating when the system reaches 1206 kPa and after the fire pump has operated for the minimum pump run time specified herein”.

SECTION 21 30 00 FIRE PUMPS

Paragraph 2.9 FIRE PUMP CONTROLLER, delete “and stop” in the second sentence.

SECTION 21 30 00 FIRE PUMPS

Paragraph 2.9 FIRE PUMP CONTROLLER, delete the sentence “Automatic stopping shall be accomplished only after all starting causes have returned to normal and after a minimum pump run time has elapsed.”

SECTION 23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS

In Paragraph 2.10.3 Fire Dampers, replace the first sentence “USE 1.5 HOUR RATED FIRE DAMPERS UNLESS OTHERWISE INDICATED.” with “FIRE DAMPER RATING SHALL MATCH THE FIRE RATING OF THE

PROTECTED WALL ASSEMBLY.”

SECTION 28 31 63.00 20 ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM

Paragraph 2.2.8.2 CAPACITY, replace the number “15” with “30” to read “30 minutes”.

SECTION 28 31 63.00 20 ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM

Paragraph 3.1 INSTALLATION OF FIRE ALARM INITIATING AND INDICATING DEVICES, subparagraph (a), delete “1830” and replace with “1850”.

SECTION 28 31 63.00 20 ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM

Paragraph 3.1 INSTALLATION OF FIRE ALARM INITIATING AND INDICATING DEVICES, subparagraph (a), delete “or center the cabinet at 1525 mm, whichever is lower”.

(End of Summary of Changes)