08 62 00 Translucent Wall Panels.pdf
PDF 27 KB Posted
- Attached to
- Building 17 and 17A Renovation and Addition
- Solicitation number
- N6247020R6000
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Large Cabinet.jpg | JPG image | |
| Tabernacle.jpg | JPG image | |
| Organ (2).jpg | JPG image | |
| Grand Piano.jpg | JPG image | |
| Baptismal Font.jpg | JPG image | |
| Organ (1).jpg | JPG image | |
| Altar (2).jpg | JPG image | |
| Amnd 0006 20R6000 Final.pdf | ||
| Altar (1).jpg | JPG image | |
| Amnd 0005 20R6000 Final.pdf | ||
| Amnd 0004 20R6000 Final.pdf | ||
| Amnd 0003 20R6000 Final.pdf | ||
| Amnd 0002 20R6000 Final.pdf | ||
| NAVFAC DWG 60025678.pdf | ||
| NAVFAC DWG 60025676.pdf | ||
| Amend 0001 20R6000.pdf | ||
| N4008519B0095 Drawings_Part8.pdf | ||
| N4008519B0095 Drawings_Part3.pdf | ||
| N4008519B0095 Drawings_Part6.pdf | ||
| N4008519B0095 Specs.pdf | ||
| N4008519B0095 Drawings_Part7.pdf | ||
| 19-0095 Asbestos Survey 011020.pdf | ||
| N4008519B0095 Drawings_Part2.pdf | ||
| N4008519B0095 Drawings_Part5.pdf | ||
| RFP N62470-20-R-6000.pdf | ||
| N4008519B0095 Drawings_Part1.pdf | ||
| 19-0095 Lead Survey 011020.pdf | ||
| N4008519B0095 Drawings_Part4.pdf | ||
| N4008519B0095 Drawings_Part9.pdf | ||
| Master PPI Form Template.xls | XLS spreadsheet |
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Renovation and Addition to Catholic Chapel, Bldg 17 & 17A
SECTION 08 62 00
TRANSLUCENT WALL PANELS
04/06
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 1600 (2000) Voluntary Specification for Skylights
ASTM INTERNATIONAL (ASTM)
ASTM C 297/C 297M (2004) Flatwise Tensile Strength of Sandwich Constructions
ASTM D 1002 (2005) Apparent Shear Strength of Single-Lap-Joint Adhesively Bonded Metal Specimens by Tension Loading (Metal-to-Metal)
ASTM D 1003 (2007e1) Haze and Luminous Transmittance of Transparent Plastics
ASTM D 1037 (2006a) Evaluating Properties of Wood-Base Fiber and Particle Panel Materials
ASTM D 3841 (1997e1; R 2008) Standard Specification for Glass Fiber-Reinforced Polyester Plastic Panels
ASTM D 572 (2004) Rubber Deterioration by Heat and Oxygen
ASTM E 108 (2007a) Fire Tests of Roof Coverings
ASTM E 283 (2004) Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen
ASTM E 331 (2000) Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference
ASTM E 72 (2005) Conducting Strength Tests of Panels for Building Construction
SECTION 08 62 00 Page 1
NATIONAL FENESTRATION RATING COUNCIL (NFRC)
NFRC 100 (2004) Procedure for Determining Fenestration Product U-Factors
NFRC 200 (2004) Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence
1.2 GENERAL REQUIREMENTS
The Contractor shall furnish and install commercially available Translucent Wall Panels which satisfy all requirements contained in this section and have been verified by load testing and independent design analyses (if required) to meet specified design requirements. The Contractor shall provide environmentally preferable products and work practices, applicable to Translucent Wall Panels, considering raw materials acquisition, production, manufacturing, packaging, distribution, reuse, operation, maintenance, and/or disposal of the products or services used in the skylights. The Translucent Wall Panel system shall be UV-stabilized, shatter proof and energy efficient. The plastics used in the manufacture of the skylights shall be light transmitting plastics for daylighting applications.
1.3 SUBMITTALS
The following shall be submitted in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Shop Drawings
Drawings showing fabrication details, materials, dimensions, installation methods, anchors, and relationship to adjacent construction.
SD-03 Product Data
Translucent Wall Panels Manufacturer's descriptive data and catalog cuts.
Warranty
Manufacturer's 5 year complete warranty.
SD-06 Test Reports
Test Reports
Certified test reports from independent testing laboratory for each type and class of panel system. Reports shall verify that the material meets apecified performance requirements. Previously completed test reports will be acceptable if they are current and indicative of products used on this project. Where a Class A, B or C roof is part of the project, a listing certificate for roof covering systems category shall be provided certifying that the product complies with the safety standards of ASTM E 108 and the
SECTION 08 62 00 Page 2
Uniform Building Code.
SD-07 Certificates
Translucent Wall Panels
Manufacturer's certificate stating that products meet or exceed specified requirements. Translucent Wall Panel system shall be evaluated and listed (the whole Translucent Wall Panel as a unit, not just a glazing material in the unit) by the recognized building code authorities: ICC and SBCCI-Public Safety Testing and Evaluation Services Inc. Product ratings determined using NFRC 100 and NFRC 200 shall be authorized for certification and properly labeled by the manufacturer.
Qualifications
Documentation of manufacturer's and installer experience indicating compliance with specified requirements.
1.4 QUALIFICATIONS
The manufacturer shall be a company specializing in the manufacture of the specified products with a minimum of 5 years documented experience. The installer shall have documented experience of 5 years minimum performing the work specified.
1.5 DELIVERY STORAGE AND HANDLING
System modules shall be factory assembled to the greatest extent possible. Panels shall be shipped to the jobsite in rugged shipping units and shall be ready for erection. All skylights shall have conspicuous decals affixed warning individuals against sitting or stepping on the units. Translucent Wall Panel panels shall be stored on the long edge, several inches above the ground, blocked and under cover to prevent warping. Unit Translucent Wall Panel shall be delivered in manufacturer's original containers, dry, undamaged, with seals and labels intact. All products shall be delivered, stored and protected in accordance with manufacturer's recommendations.
1.6 WARRANTY
The Contractor shall provide to the Government the manufacturer's complete warranty for materials, workmanship, and installation. The warranty shall be for 5 years from the time of project completion and shall no be prorated. The warranty shall guarantee, but shall not be limited to, the following:
a. Light transmission and color of the panels shall not change after 5-year exposure at a low angle of 5 degrees in South Florida.
b. There is no delamination of the panel affecting appearance, performance, weatherability or structural integrity of the panels or the completed system.
c. There is no fiberbloom on the panel face.
d. Change in light transmission of no more than 6% in accordance with ASTM D 1003 , and in color (yellowing index) no more than 10
SECTION 08 62 00 Page 3 points in comparison to the original specified value over a 10 year period.
PART 2 PRODUCTS
2.1 Translucent Wall Panels
Translucent Wall Panels shall be fabricated of glass-fiber reinforced thermoset resins panels conforming to the specified requirements and other appropriate lab test specified criteria, weighing not less than 8 ounces/square foot. The Contractor shall submit Test Reports as specified in the Submittals paragraph. Size and color of skylight panels shall be as indicated.
2.2 GLASS-FIBER PANELS
Glass-fiber reinforced polyester panels shall conform to ASTM D 3841 , Class A and to the requirements of AAMA 1600.
2.2.1 Weatherability
The exposed faces of fiberglass sandwich type panels shall have a permanent glass veil erosion barrier embedded integrally to provide maximum long term resistance to reinforcing fiber exposure. The exterior face sheet shall be uniform in strength and be resistant to penetration by pencil point. Sacrificial plastic surface films, coatings or veils are not acceptable.
2.2.2 Non Combustible Grid Core
The aluminum I-beams shall be 6063-T6 with provisions for mechanical interlocking of muntin-mullion and perimeter to prevent high and low intersections which do not allow full bonding surface to contact with face material. Width of I-beam shall be no less than 7/16 inch. I-beam grid shall be machined to tolerances of not greater than plus or minus 0.002 inch for flat panels. Panels shall withstand 1200 degrees F fire for a minimum of one hour without collapse or exterior flaming. Thermally broken panels shall give minimum CRF (Condensation Resistance Factor) of 80 by AAMA 1503 measured on the grid line.
2.2.3 Adhesive
The laminate adhesive shall be heat and pressure resin-type engineered for structural sandwich panel use. Adhesive shall pass testing requirements specified by the International Conference of Building Officials' "Acceptance Criteria for Sandwich Panel Adhesive". Minimum strength shall be:
a. Tensile Strength of 750 psi in accordance with ASTM C 297/C 297M after two exposures to six cycles each of the aging conditions prescribed in ASTM D 1037 .
b. Shear Strength, after exposure to five separate aging conditions in accordance with ASTM D 1002 , shall be:
(1) 540 psi at 50% relative humidity and 73 degrees F.
(2) 800 psi under accelerated aging in accordance with ASTM D 1037 at room temperature.
SECTION 08 62 00 Page 4
(3) 250 psi under accelerated aging in accordance with ASTM D 1037 at 182 degrees F.
(4) 1400 psi after 500 hour Oxygen Bomb in accordance with
ASTM D 572 .
(5) 100 psi at 182 degrees F.
2.2.4 Panel Construction
Panels shall consist of fiberglass faces laminated to an aluminum I-beam grid core and shall deflect no more than 1.9 inches at 30 psf in 10 feet in accordance with ASTM E 72 , without a supporting frame. Quality control inspections and required testing, conducted at least once each year, shall include manufacturing facilities, sandwich panel components and production sandwich panels for conformance with "Acceptance Criteria for Sandwich Panels" as regulated by the ICC-ES or equivalent.
2.3 COMMON PANEL REQUIREMENTS
2.3.1 Appearance
The face sheets shall be uniform in color to prevent splotchy appearance.
Faces shall be completely free of ridges and wrinkles which prevent proper surface contact. Clusters of air bubbles/pinholes which collect moisture and dirt are not acceptable.
2.3.2 Panel Fabrication
Panel construction shall meet the following requirements: Light transmission 30 %; color Crystal.
2.3.3 Thermal Performance
Thermal transmittance for Translucent Wall Panels with insulating glass shall not exceed a U-factor of 0.38 Btu/hr-ft 2-F when determined using
NFRC 100, and a SHGC of 0.40 Btu/hr-ft 2-F when determined using NFRC 200.
Selection and use of the Translucent Wall Panels products in this category should be used in the Southern Climate Zone as determined by the DOE Energy Star Windows program.
2.4 Translucent Wall Panels
The Translucent Wall Panels skylight systems shall meet the following requirements:
a. Integral perimeter framing system assembly shall be by the manufacturer.
b. Exterior panel faces shall be crystal in color. Interior panel faces shall be crystal in color.
c. Air infiltration at 6.24 psf shall be less than 0.1 cfm/ft 2 in accordance with ASTM E 283 .
d. Water penetration at test pressure of 15 psf shall be zero in accordance with ASTM E 331 .
SECTION 08 62 00 Page 5
e. Manufacturer shall be responsible for maximum system deflection, in accordance with the applicable building code, and without damage to system performance. Deflection shall be calculated in accordance with engineering principles.
f. Proper weepage elements shall be incorporated within the perimeter framework of the glazing system for drainage of any condensation or water penetration.
g. System shall accommodate movement within the system; movement between the system and perimeter framing components; dynamic loading and release of loads; and deflection of supporting members. This shall be achieved without damage to system or components, deterioration of weather seals and fenestration properties specified.
h. The exterior panel face shall repel an impact of 70 foot-pounds without fracture or tear when impacted by a 3.25 inch diameter, 5 pound free falling ball. Impact strength shall be measured by the Society of Plastics Industries (SPI) method.
i. Exposed aluminum color shall be selected from the manufacturer's standard range.
j. The system shall require no scheduled recoating to maintain its performance or for UV resistance.
k. Design criteria shall be: Wind Load .
l. Extruded aluminum shall be 6063-T6 and 6063-T5; all fasteners shall be stainless steel or cadmium plated steel.
2.4.1 Framed Translucent Wall Panels
Framed Translucent Wall Panels shall span up to 12 feet. Translucent Wall Panels manufactured in prefabricated sections easy to install are available in a wide range of standardized pitches. Framing members shall be I-beams. A registered professional engineer shall size all framing members and design all structural connections; the Contractor shall submit a copy of the calculations. Framing shall include a primary gutter system with secondary gutters to control water infiltration and condensation runoff from the underside of the glazing material and channel it to the exterior. Translucent Wall Panel structural members shall be designed for a live load and wind load; no objectionable distortion or stress in fastenings and joinery due to expansion and contraction shall be induced when subjected to a 100 degree F temperature change.
2.5 FLEXIBLE SEALING TAPE
Sealing tape shall be manufacturer's standard pre-applied to closure system at the factory under controlled conditions.
PART 3 EXECUTION
3.1 PREPARATION
The Contractor shall verify when structural support is ready to receive all specified work and to convene a pre-installation conference, if
SECTION 08 62 00 Page 6 approved by the Contracting Officer, including the Contractor, skylight installer and all parties directly affecting and affected by the specified work. All submitted opening sizes, dimensions and tolerances shall be field verified; preparation of openings shall include isolating dissimilar materials from aluminum system to avoid damage by electrolysis. The installer shall examine area of installation to verify readiness of site conditions and to notify the Contractor about any defects requiring correction. Work shall not commence until conditions are satisfactory.
3.2 ERECTION
Translucent Wall Panel system shall be erected in accordance with the approved shop drawings supplied by the manufacturer. Fastening and sealing shall be in accordance with the manufacturer's shop drawings. All panel protection shall be removed and, after other trades have completed work on adjacent materials, panel installation shall be carefully inspected and adjusted, if necessary, to ensure proper installation and weather-tight conditions. All staging, lifts and hoists required for the complete installation and field measuring shall be provided. System shall be installed clean of dirt, debris or staining and thoroughly examined for removal of all protective material prior to final inspection of the designated work area. Snow rakes shall not be used on roof windows/skylights.
-- End of Section --