N4008519B0095 Drawings_Part5.pdf
PDF 8 MB Posted
- Attached to
- Building 17 and 17A Renovation and Addition
- Solicitation number
- N6247020R6000
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Large Cabinet.jpg | JPG image | |
| Tabernacle.jpg | JPG image | |
| 08 62 00 Translucent Wall Panels.pdf | ||
| Organ (2).jpg | JPG image | |
| Grand Piano.jpg | JPG image | |
| Baptismal Font.jpg | JPG image | |
| Organ (1).jpg | JPG image | |
| Altar (2).jpg | JPG image | |
| Amnd 0006 20R6000 Final.pdf | ||
| Altar (1).jpg | JPG image | |
| Amnd 0005 20R6000 Final.pdf | ||
| Amnd 0004 20R6000 Final.pdf | ||
| Amnd 0003 20R6000 Final.pdf | ||
| Amnd 0002 20R6000 Final.pdf | ||
| NAVFAC DWG 60025678.pdf | ||
| NAVFAC DWG 60025676.pdf | ||
| Amend 0001 20R6000.pdf | ||
| N4008519B0095 Drawings_Part8.pdf | ||
| N4008519B0095 Drawings_Part3.pdf | ||
| N4008519B0095 Drawings_Part6.pdf | ||
| N4008519B0095 Specs.pdf | ||
| N4008519B0095 Drawings_Part7.pdf | ||
| 19-0095 Asbestos Survey 011020.pdf | ||
| N4008519B0095 Drawings_Part2.pdf | ||
| RFP N62470-20-R-6000.pdf | ||
| N4008519B0095 Drawings_Part1.pdf | ||
| 19-0095 Lead Survey 011020.pdf | ||
| N4008519B0095 Drawings_Part4.pdf | ||
| N4008519B0095 Drawings_Part9.pdf | ||
| Master PPI Form Template.xls | XLS spreadsheet |
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
DEMOLITION
EXISTING HVAC PIPING, DUCTWORK, AND EQUIPMENT SHOWN IS BASED ON EXISTING
PLANS AND FIELD OBSERVATION WITHOUT DEMOLITION. AFTER DEMOLITION, ANY
CLARIFICATION REQUIRED TO DETERMINE SCOPE OF WORK SHALL BE BROUGHT TO THE
ATTENTION OF THE COTR.
THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE HIMSELF
WITH THE EXISTING CONDITIONS.
DRAWINGS DO NOT SHOW EVERY EXISTING PIPE, CONDUIT, DUCT, ETC. CONTRACTOR
SHALL TAKE CARE TO REMOVE ONLY ITEMS REQUIRED TO BE REMOVED AND VERIFY
PIPES, DUCTS, ETC. BEFORE REMOVAL.
REMOVAL OF ITEMS SHALL INCLUDE ASSOCIATED HANGERS, ANCHOR BOLTS AND OTHER
APPURTENANCES. WHERE SUCH REMOVAL RESULTS IN OPEN HOLES, VOIDS OR
EXPOSURE OF DAMAGED SURFACES, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
REPAIRING AND FINISHING THE SURFACE TO MATCH ADJACENT CONDITIONS. THIS WORK
SHALL BE COORDINATED WITH ARCHITECTURAL FINISH SCHEDULES WHERE APPLICABLE.
REMOVE EXISTING DUCTWORK AND PIPING NOT TO BE REUSED.
ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR DESIGNATED
TO BE TURNED OVER TO THE GOVERNMENT, SHALL BECOME THE PROPERTY OF THE
CONTRACTOR, UNLESS OTHERWISE NOTED, AND SHALL BE REMOVED COMPLETELY FROM
THE SITE.
GENERAL ITEMS
GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH HVAC DRAWING OF THIS
SET. SEE EACH DRAWING FOR SPECIFIC NOTES APPLICABLE TO THAT DRAWING.
COORDINATE THAT OUTSIDE AIR INTAKE OPENINGS FOR VENTILATION AIR ARE LOCATED
AT LEAST 10 FEET MEASURED IN ANY DIRECTION FROM ANY HAZARDOUS OR NOXIOUS
CONTAMINANT SOURCE SUCH AS FLUES, VENTS, CHIMNEYS, GAS METERS, GAS
REGULATORS, PLUMBING VENTS, ETC., UNLESS TOP OF SUCH INTAKE OPENING IS 3 FEET
OR GREATER BELOW ANY OF THE LISTED ITEMS.
OVERHEAD PIPING IN SPACES WITHOUT HUNG CEILINGS SHALL BE RUN AS CLOSE TO
ROOF DECK OR STRUCTURE ABOVE, AS PRACTICAL, AS CLOSE TO PARALLEL JOISTS AS
POSSIBLE AND ABOVE LIGHTING FIXTURES TO CONCEAL PIPING.
OVERHEAD DUCTWORK AND PIPING IN SPACES WITH CEILINGS SHALL BE CONCEALED
UNLESS OTHERWISE NOTED.
COORDINATE LOCATION OF GRILLES, REGISTERS, DIFFUSERS, THERMOSTATS AND
OTHER WALL OR CEILING MOUNTED HVAC ACCESSORIES WITH REFLECTED CEILING PLAN,
LIGHTING FIXTURE LAYOUT AND ACCESSORIES INSTALLED BY OTHER TRADES SO AS TO
PRESENT A NEAT AND ATTRACTIVE INSTALLATION THROUGHOUT THE ENTIRE BUILDING.
IT IS THE INTENT FOR GRILLES, REGISTERS AND DIFFUSERS TO BE INSTALLED IN THE
CENTER OF CEILING PANELS.
ARRANGE PIPING AND DUCTWORK, PARTICULARLY ABOVE CEILING AS REQUIRED TO
CLEAR STRUCTURE, DUCTS, CONDUITS, ETC. ALLOWING SPACE FOR PIPE HANGERS, AND
ACCESS TO VALVES, FILTERS, AND MAINTENANCE OF EQUIPMENT.
COORDINATE LOCATION AND INSTALLATION OF EQUIPMENT WITH OTHER TRADES.
PROVIDE EMERGENCY CUT-OFF SWITCH FOR EACH GAS BURNER NEAR THE BOILER ROOM
OR EQUIPMENT ROOM DOOR.
DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF
DOORS, WINDOWS, ETC.
THERMOSTATS AND/OR TEMPERATURE SENSORS SHALL BE LOCATED IN THE ROOMS
INDICATED. INSTALL AT APPROX. 46" ABOVE FINISH FLOOR TO MATCH THE HEIGHT OF
WALL SWITCHES OR OTHER WALL MOUNTED DEVICES.
PIPING, DUCTWORK, VENTS, ETC., EXTENDING THROUGH EXTERIOR WALLS AND ROOF
SHALL BE FLASHED AND COUNTER FLASHED IN A WEATHERPROOF MANNER.
VALVES AND SPECIALTIES SHALL BE LINE SIZE EXCEPT FOR CONTROL VALVES OR
UNLESS NOTED OTHERWISE.
EXTEND DRAIN LINES TO NEAREST FLOOR DRAIN OR AS INDICATED. ROUTING SHALL NOT
INTERFERE WITH PASSAGEWAYS AND MAINTENANCE. DRAINS FROM AIR CONDITIONING
CONDENSATE DRAIN PANS SHALL BE TRAPPED. SLOPE CONDENSATE DRAIN PIPING AT
1/4" PER FOOT. VERIFY INVERT IS ESTABLISHED AFTER AIR HANDLING UNIT IS INSTALLED
BUT PRIOR TO DUCTWORK INSTALLATION.
PIPING AND DUCTWORK INSULATION SHALL BE RUN CONTINUOUSLY THROUGH
NON-RATED FLOORS, WALLS, ROOF AND PARTITIONS, UNLESS OTHERWISE INDICATED.
NO PIPING SHALL BE SMALLER THAN 3/4" UNLESS OTHERWISE NOTED.
FOR PIPE SIZES NOT INDICATED ON PLANS, SEE EQUIPMENT CONNECTION DETAILS, FLOW
DIAGRAMS AND RISER DIAGRAMS.
PROVIDE UNION OR FLANGED CONNECTIONS AT EACH PIECE OF EQUIPMENT AND ON
BOTH SIDES OF CONTROL VALVES AND PRESSURE REGULATING VALVES. PROVIDE
SHUT-OFF VALVES ON BOTH SIDES OF AUTOMATIC VALVES.
RELIEF VALVE PIPING SHALL BE EXTENDED TO THE NEAREST FLOOR DRAIN.
FLOOR MOUNTED EQUIPMENT IN THE MECHANICAL ROOMS SHALL BE LOCATED ON 6"
THICK CONCRETE HOUSEKEEPING PADS UNLESS OTHERWISE INDICATED.
PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE SPECIFICATIONS. ADDITIONAL
SUPPORTS OR HANGERS SHALL BE INSTALLED ADJACENT TO ELBOWS TO PREVENT
WEIGHT OF PIPING BEING PLACED ON THE EQUIPMENT.
CORRECT SETTING ON BALANCING FITTINGS SHALL BE PERMANENTLY MARKED.
LOCATE AND SIZE CONCRETE PADS AND CURBS FOR MECHANICAL EQUIPMENT IN
ACCORDANCE WITH ACTUAL EQUIPMENT PURCHASED.
FOR LOCATION OF MOTOR STARTERS, SEE ELECTRICAL DRAWINGS.
THROUGH-PENETRATION FIRESTOP ASSEMBLIES
PROVIDE UL LISTED THROUGH-PENETRATION ASSEMBLIES FOR FIRE RATED PARTITIONS,
WALLS, AND FLOORS. SEE SHEET GI101 FOR FIRE PARTITION LOCATIONS AND UL
LISTINGS.
HOT AND CHILLED WATER PIPING
PROVIDE MINIMUM PITCH SUFFICIENT TO INSURE ADEQUATE VENTING AND DRAINAGE.
PROVIDE MANUAL AIR VENTS AT HIGH POINTS OF SYSTEM.
PROVIDE 1/2" DRAIN VALVES AND CAPPED CONNECTIONS AT LOW POINTS IN PIPING
SYSTEMS FOR DRAINING.
SHEET METAL
PROVIDE ACCESS DOORS IN DUCTWORK WHERE INDICATED OR REQUIRED FOR ACCESS
TO SYSTEM COMPONENTS INCLUDING THE FOLLOWING:
FILTERS
SMOKE DETECTORS
HIGH SIDEWALL REGISTERS OR GRILLES SHALL BE LOCATED 6" FROM CEILING TO TOP OF
REGISTER OR GRILLE.
PROVIDE A MINIMUM OF THREE TIMES THE FAN DIAMETER OF STRAIGHT DUCTWORK OFF
THE SUPPLY FAN DISCHARGE BEFORE ANY TAKEOFFS OR ELBOWS.
DUCTWORK UPSTREAM OF VAV TERMINAL UNITS SHALL BE CONSTRUCTED TO THE
SMACNA STATIC PRESSURE CLASSIFICATION OF 4 IN. WG AND SEAL CLASS "A". OTHER
DUCTWORK SHALL BE CONSTRUCTED TO THE SMACNA STATIC PRESSURE
CLASSIFICATION OF 2 IN. WG AND SEAL CLASS "A".
PROVIDE EXTENDED VOLUME DAMPER CONTROL RODS SO THAT HANDLES ARE WELL
CLEAR OF DUCT INSULATION.
MAINTENANCE
EQUIPMENT WITH FILTERS SHALL BE INSTALLED SO THAT FILTERS CAN BE EASILY
REMOVED AND REPLACED.
EQUIPMENT INSTALLED ABOVE CEILINGS SHALL BE MOUNTED APPROX. 12" ABOVE
CEILING (UON) FOR MAINTENANCE ACCESS.
INSTALL PIPE RUNS AT LEAST 6" ABOVE CEILING TILES. WHERE PRACTICAL INSTALL
VALVES, AND OTHER MAINTAINABLE DEVICES LOW ENOUGH TO REACH WITH A 6' LADDER.
PROVIDE ACCESS TO ANY INSPECTION OR MAINTAINABLE DEVICE, EQUIPMENT, ETC. -
ACCESS OR ACCESS DOOR SHALL BE OF ADEQUATE SIZE TO WORK ON DEVICE.
EXAMINE MANUFACTURER'S LITERATURE TO DETERMINE RECOMMENDED CLEARANCES.
THESE CLEARANCES, IN ADDITION TO MINIMUM CLEARANCES REQUIRED BY THE
NATIONAL ELECTRICAL CODE, SHALL BE ESTABLISHED AND MAINTAINED. THIS APPLIES TO
NEW AND EXISTING EQUIPMENT IMPACTED BY THIS PROJECT AS WELL. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR COORDINATING THESE REQUIREMENTS WITH ALL OTHER
TRADES.
INTERDISCIPLINARY COORDINATION
IF THIS CONTRACTOR SHOULD ELECT TO PROPOSE ANY EQUIPMENT THAT HAS
DIFFERENT PHYSICAL OR ELECTRICAL CHARACTERISTICS, ETC. WHEN COMPARED TO THE
BASIS OF DESIGN EQUIPMENT, THIS CONTRACTOR IS RESPONSIBLE FOR COORDINATING
THESE CHANGES WITH THE OTHER TRADES PRIOR TO ORDERING OF EQUIPMENT. IF
THERE SHOULD BE ANY ADDITIONAL WORK INCURRED BY THE OTHER TRADES AS A
RESULT OF THIS CONTRACTOR'S EQUIPMENT SELECTION, ALL COSTS ASSOCIATED WITH
THE ADDITIONAL WORK SHALL BE BORNE BY THIS CONTRACTOR.
C CO2 SENSOR
RETURN/EXHAUST DUCT SECTION
CEILING DIFFUSER WITH FLEXIBLE DUCTWORK
RETURN/EXHAUST DUCT SECTION THROUGH ROOF
DUCT TURNING DOWN
RETURN/EXHAUST REGISTER
MITERED ELBOW WITH TURNING VANES
DUCT TURNING UP
SUPPLY AIR/OUTSIDE AIR DUCT SECTION THROUGH ROOF
VOLUME DAMPER
SMOKE DETECTOR
DOOR UNDERCUT (1")
(CFM AS INDICATED)
SUPPLY AIR/OUTSIDE AIR DUCT SECTION
GRILLE, REGISTER OR DIFFUSER MARK
MOTORIZED DAMPER
X
S
M
UC
L-1 LOUVER DESIGNATION
SECONDARY HOT WATER PUMP DESIGNATION
VARIABLE AIR VOLUME DESIGNATION
UNIT HEATER DESIGNATION
VAV-1
UH-1
SHWP-1
BOILER DESIGNATION
AIR HANDLING UNIT DESIGNATION
EXHAUST FAN DESIGNATIONEF-1
B-1
AHU-1
NEW WORK NOTE DESIGNATION
DEMOLITION NOTE DESIGNATION
LEGEND and ABBREVIATIONS
AIR COOLED CHILLER DESIGNATION
SHEET WHERE SECTION/PLAN IS SHOWN/CUT
AC-1
SECTION/ENLARGED PLAN
EXPANSION TANK DESIGNATIONET-1
SECONDARY HOT WATER SUPPLY PIPING
SECONDARY HOT WATER RETURN PIPINGHWR/SHWR
HWS/SHWS
PIPE TURNING DOWN
CHILLED WATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
D CONDENSATE DRAIN
DIRECTION OF FLOW
CWS
STRAINER W/ BLOWDOWN VALVE
UNION
THERMOMETER
MANUAL AIR VENT
PIPE TURNING UP
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
STRAINER
BALL VALVE
BALANCING VALVE
CHECK VALVE
ISOLATION VALVE
CWR
BALL VALVE
U.O.N. UNLESS OTHERWISE NOTED
°F
Ø PHASE/DIAMETER
DEGREE FAHRENHEIT
EXTERNAL STATIC PRESSURE
ENTERING WATER TEMPERATURE
LEAVING WATER TEMPERATURE
LEAVING AIR TEMPERATURE
MAX OVERCURRENT PROTECTION
1000 BRITISH THERMAL UNITS PER HOUR
WET BULB TEMPERATURE
REVOLUTIONS PER MINUTE
MAXIMUMMAX
RETURN AIRR.A.
WG
SF
WB
RPM
S.A.
SQUARE FEET
WATER GAUGE
SUPPLY AIR
P.D.
O.A.
MOCP
MCA
MIN
MBH
OUTSIDE AIR
PRESSURE DROP
MIN CIRCUIT AMPACITY
MINIMUM
LWT
HP
LAT
GPM
HORSEPOWER/HEAT PUMP
GALLONS PER MINUTE
FLA
FA
ESP
EWT
ETR
FREE AREA
FULL LOAD AMPS
EXISTING TO REMAIN
ABOVE FINISHED FLOOR
CUBIC FEET PER MINUTE
ENTERING AIR TEMPERATURE
DECIBELSdb
EAT
E.A.
CFM
APPROX.
EXHAUST AIR
APPROXIMATELY
A.F.F.
APD AIR PRESSURE DROP
(TYP.) TYPICAL
DRY BULB TEMPERATUREDB
FT FEET
HD HEAD
IN. INCH
NOISE CRITERIANC
OBD OPPOSED BLADE DAMPER
SEER SEASONAL ENERGY EFFICIENCY RATING
VOLTV
SENS. SENSIBLE
CALC. CALCULATED
WATTW
COTR
LEAVING DRY BULB TEMPERATURELDB
LEAVING WET BULB TEMPERATURELWB
ENTERING DRY BULB TEMPERATUREEDB
EWB ENTERING WET BULB TEMPERATURE
VARIABLE AIR VOLUMEVAV
REFRIGERANT LIQUID PIPING
REFRIGERANT SUCTION PIPINGRS
RL
BOILER SHUT-OFF SWITCHBS
T WALL THERMOSTAT
DIRECT DIGITAL CONTROL PANEL
EMERGENCY HVAC SHUTDOWN BUTTONEB
DDC
PRIMARY HOT WATER RETURN PIPINGPHWR
PRIMARY HOT WATER SUPPLY PIPINGPHWS
DEMAND CONTROL VENTILATIONDCV
DOWNDN
CURRENT SENSING RELAYCSR
CONTRACTING OFFICER'S
TECHNICAL REPRESENTATIVE
SZ SINGLE ZONE
MULTIZONEMZ
02/24/2020
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
ALL MATERIAL AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER'S RECOMMENDATIONS FOR THE INTENDED
PURPOSE. USE THE MORE STRINGENT METHODS WHEN MANUFACTURER'S
RECOMMENDATIONS, AND PLANS & SPECIFICATION REQUIREMENTS
DIFFER. BRING ANY CONFLICTS BETWEEN MANUFACTURER'S
RECOMMENDATIONS AND PLANS & SPECIFICATION REQUIREMENTS TO THE
GOVERNMENT'S ATTENTION.
MANUFACTURER'S RECOMMENDATIONS:
NOTE: VERTICAL FIRE DAMPER INSTALLATION SHOWN.
HORIZONTAL FIRE DAMPER INSTALLATION SIMILAR
EXCEPT FIRE DAMPER SHALL INCLUDE NEGATOR SPRING
CLOSURE MECHANISM.
EXTERIOR
INSULATION (TYP)
6" EACH SIDE (MAX.)
WHERE THE WALL IS NON-
SOLID METAL OR WOOD
STUD, OPENING TO BE
LINED WITH FIRE
RESISTIVE MATERIAL OF
RATING EQUAL TO THAT
OF THE WALL
RETAINING ANGLES - MIN. 1 1/2" x 1 1/2" x 16 GA. ALL 4
SIDES. OVERLAP STRUCTURAL OPENING A MIN. OF 1"
AND COVER CORNERS OF OPENINGS
PLAIN "S" SLIP CONNECTION OR OTHER
APPROVED CONNECTION TO BE USED FOR
DAMPER / DUCT BREAKAWAY CONNECTION.
(TYP) CONNECTION SHALL BE CONSISTENT WITH
DUCT PRESSURE CLASSIFICATION
CLEARANCE - 1/8" PER LINEAR FOOT - BOTH DIMENSIONS
PROVIDE ACCESS DOOR LARGE ENOUGH TO PERMIT
MAINTENANCE AND RESETTING OF FIRE DAMPER
U.L. APPROVED FIRE DAMPER, 2 HOUR RATING,
STYLE B, 165 °F FUSIBLE LINK (REPLACEABLE)
STEEL SLEEVE
CLEARANCE - 1/8" PER LINEAR FOOT - BOTH DIMENSIONS
WHERE WALL IS CONCRETE, MASONRY OR SOLID
METAL STUD FRAMING, NO LINING IS REQUIRED
SECURE RETAINING ANGLES TO SLEEVE ONLY ON 8"
CENTERS WITH 1/4" BOLTS AND NUTS, OR No 10 STEEL
SCREWS OR MIN. 3/16" STEEL RIVETS, OR 1/2" LONG
WELDS
NOTCHED PIECE
BENT DOWN
A-A
CEILING
RUNNER
METAL STUD
FRAMING
SHOWN
FLOOR
RUNNER
DETAIL A-A
24"
O.C. MAX
CEILING
RUNNER
FLOOR
RUNNER
24"
O.C. MAX
12" 1. FRAME WALL OPENINGS AS SHOWN IN FIGURE 1
OR 2.
2. DOUBLE VERTICAL STUDS ARE NOT REQUIRED
FOR OPENINGS 36"W x 36"H OR SMALLER.
3. ALL CONSTRUCTION AND FASTENERS MUST
MEET THE REQUIREMENTS OF THE
APPROPRIATE WALL DESIGN AND/OR LOCAL
CODES.
4. IN WOOD CONSTRUCTION, FIRE RATED GYPSUM
WALL BOARD MUST COVER ALL WOOD STUD
SURFACES.
24" O.C. MAX
(METAL STUD)
2"
FIGURE 1
FIGURE 2
FIRE DAMPER INSTALLATION DETAIL (VERTICAL) FRAMING FOR OPENINGS IN WOOD AND METAL STUD WALL
SCALE: NO SCALE M-101A
A
A-101 BUILDING SECTION TAG
SECTION NUMBER
SHEET WHERE DRAWN
DETAIL
SCALE: XXX X-XXXX
DETAIL NUMBER NAME
SCALE
SHEET REFERENCED FROM
54x20
18x12
54x20
18x12
54x16
18x12
54x16
18x12
30x16
18x12
30x16
18x12
18x16
18x12
18x16
18x12
10x812x1014x1214x14
16x16
9Ø
RS/RLRS/RL
RS/RL
16x6
A
MD101
B
MD101
(TYP)1
15 TON ACCU5
1.5 TON AHU4
1.5 TON HP3
5 TON AHU4
5 TON HP3
RS/RL
2 2
(TYP)1
(TYP)1
(TYP)2
7"Ø (TYP)
T T
RS/RL AND
DRAIN UP
RS/RL AND
DRAIN UP
(TYP)2
(TYP)1
D
16x6 DOWN BELOW BALCONY 18x6 UP TO MEZZANINE
18x6 UP TO MEZZANINE
18x6 DN TO
FIRST
FLOOR
18x6 DN TO
FIRST FLOOR
15 TON AHU
6x6 DN
6x6 DN
8x6
6x6 DN
8x6
15 TON AHU4
RS/RL AND D DN RS/RL AND D DN
8 8
7 7 77
(TYP.)1 (TYP.)1
4x6 4x6
6x6 DN
02/24/2020
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
DEMOLITION NOTES
REMOVE DUCTWORK, INSULATION, HANGERS, AND SUPPORTS COMPLETE.
REMOVE GRILLES, REGISTERS, AND DIFFUSERS COMPLETE.
REMOVE HEAT PUMP, REFRIGERANT PIPING, CONCRETE PAD, CONTROL WIRING,
AND ASSOCIATED APPURTENANCES COMPLETE.
REMOVE AIR HANDLING UNIT, DUCTWORK, PIPING, CONTROLS, WIRING, AND
ASSOCIATED APPURTENANCES COMPLETE.
REMOVE AIR COOLED CONDENSING UNIT, CONCRETE PAD, REFRIGERANT PIPING,
CONTROL WIRING, AND ASSOCIATED APPURTENANCES COMPLETE.
ENTIRE BUILDING TO BE DEMOLISHED. REFER TO ARCHITECTURAL SHEET D-101.
REMOVE EXISTING LOUVER COMPLETE. REFER TO ARCHITECTURAL SHEETS FOR
PATCHING REQUIREMENTS.
REMOVE 48x36 RETURN GRILLE COMPLETE. EXISTING OPENING SHALL BE
REUSED FOR NEW WORK.
REMOVE WALL MOUNTED AIR CONDITIONER AND ALL APPURTENANCES
COMPLETE.
REMOVE EXHAUST FAN, WALL CAP, AND ALL APPURTENANCES COMPLETE.
NMECHANICAL DEMOLITION FIRST FLOOR PLAN
SCALE: 1/8" = 1'-0"
NMECHANICAL DEMOLITION SECOND FLOOR PLAN
SCALE: 1/8" = 1'-0"
A
MD101
NMECHANICAL DEMOLITION MEZZANINE FLOOR PLAN
SCALE: 1/8" = 1'-0"
B
MD101
AC-11
3" CWS/CWR
REFER TO M-201 FOR
PIPING IN THIS AREA
BELOW GRADE
02/24/2020
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
NEW WORK NOTES
PROVIDE AIR COOLED CHILLER AND CONCRETE PAD COMPLETE. SEE CIVIL DRAWINGS
FOR CONTINUATION.
PROVIDE CHILLED WATER PIPING, INSULATION, AND SUPPORTS COMPLETE. PROVIDE
HEAT TRACING FOR EXPOSED PIPING.
PROVIDE 3" TAP WITH BUTTERFLY VALVE AND BLIND FLANGE FOR EMERGENCY
CHILLER CONNECTION.
PROVIDE 1" MAKEUP WATER PIPING. PROVIDE HEAT TRACING FOR EXPOSED PIPING.
CONNECT TO AIR SEPARATOR AT CHILLER.
REFER TO EXTERIOR PIPE SUPPORT DETAIL.
NMECHANICAL SITE PLAN
SCALE: 1" = 20'-0"
20 CF
E F G H
0.5
I J K L M N O P
VAV-1
VAV-2
VAV-3
VAV-4
VAV-5
VAV-6
A
(TYP OF 22)
28"Ø
24"Ø
18"Ø
VAV-7
D
(TYP
OF 12) D
(TYP
OF 4)
C
C
C 200
C
D
DSS-1B
28"Ø
24"Ø
18"Ø
20x30
30x20
5 (TYP)
7 (TYP)
10x10
14x12
16x16
20x14
20x16
DSS-1A
26x16 20x16
10"Ø
10x10
12x10 16x12
1 (TYP)
G
6x6
3 EF-1
L-3
36x30
30x20 SA
BELOW
28x20 RA
ABOVE
20x28 20x28
O 3810 O
32x30
VAV-8
G
M
(TYP OF 2) 10x8
K
L 250
L 290
EF-2
EF-3
T 250T
12x12
L-4
6x6
22x18
10x10
N 850
14x12
VESTIBULE
UNISEX
ALTAR
STORAGE
BABYSITTING
MECH./
ELEC.
TELECOM
OFFICE
OFFICE
VESTIBULE
MEN'S
WOMEN'S
FELLOWSHIP
HALL
KITCHEN
PANTRY
CORR.
303JAN.
UNISEX
EB
EB
CORRIDOR
CHAPEL
STORAGE
STORAGE
VESTIBULE
A M-101
B M-101
C M-101
8"Ø
6x6 UP6x6 UP
16x6
L-3
G
16x14
12x12
(TYP.)13
(TYP.)12
E
UC
UC
EF-56
10x10
C 115
20x30 K
K
C
VAV-9
UC
L-211
L-8
L-7
12x12
M
L-9L-9
UU
6x6
V
D M-101
C
18 20
H-1
6x6
6x6
F
6X6
F
6x66x6 DN
AHU-1
B-1 B-2
SHWP-2
SHWP-1
VFD
VFD
ET-1
36x30 SA
32x30 RA
MECH.
L-1
20x20
M
M
DDC
CHEMICAL
SHOT
FEEDER
BS
UH-115
S
EF-46
L-511
M
L-10
AHU-2
26x16
30x18
MECH./
ELEC.
M M
16x16 OA ABOVE
10x10
S
T T UH-2EF-5UH-216
L-611
M
B.1 B.7BA C D
'-1
0"
'-1
'-7
8'- 5"
'-1
'-7
32x3020x3036x30 SA
28x20 28x20 20x30
20x30
02/24/2020
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
NNEW WORK FIRST FLOOR PLAN - DUCTWORK
SCALE: 1/8" = 1'-0"
NNEW WORK MEZZANINE DUCTWORK PLAN
SCALE: 1/8" = 1'-0"
NEW WORK NOTES
PROVIDE VAV TERMINAL UNIT, HANGERS, AND SUPPORTS COMPLETE.
PROVIDE AIR HANDLING UNIT AND 4" CONCRETE HOUSEKEEPING PAD SUITABLE FOR UNIT
DIMENSIONS COMPLETE.
PROVIDE CABINET EXHAUST FAN, HANGERS, SUPPORTS, AND CONTROL WIRING COMPLETE.
PROVIDE BOILER AND CONCRETE HOUSEKEEPING PAD COMPLETE.
PROVIDE DUCT MOUNTED GRILLE COMPLETE.
PROVIDE EXHAUST FAN AND CONTROL WIRING COMPLETE.
PROVIDE DOUBLE WALL SPIRAL DUCTWORK, INSULATION, HANGERS, AND SUPPORTS
COMPLETE. INNER DUCT SHALL BE 0.028 INCH SOLID SHEET STEEL. INTERSTITIAL INSULATION
SHALL BE 1 INCH FLEXIBLE ELASTOMERIC DUCT LINER COMPLYING WITH ASTM C, TYPE II.
DUCTWORK SHALL BE DARK BROWN AND SHALL BE PROVIDED WITH PAINT GRIP FINISH.
SUPPORTS SHALL BE PAINTED TO MATCH DUCTWORK. SEE ARCHITECTURAL
DRAWINGS/SPECIFICATIONS FOR PAINTING REQUIREMENTS.
PROVIDE EXPANSION TANK AND CONCRETE HOUSEKEEPING PAD COMPLETE.
PROVIDE DDC PANEL COMPLETE.
PROVIDE INLINE SECONDARY HOT WATER PUMP COMPLETE.
MOUNT LOUVER AT 10'-0" MINIMUM ABOVE FINISHED FLOOR.
PROVIDE DUCTWORK, INSULATION, HANGERS, AND SUPPORTS COMPLETE. ROUTE
DUCTWORK THROUGH TRUSS WEBBING LOCATE SUPPLY DUCTWORK ABOVE SUSPENDED
CEILING AND BELOW BOTTOM CHORD OF TRUSS.
PROVIDE DUCTWORK, INSULATION, HANGERS, AND SUPPORT COMPLETE. LOCATE RETURN
DUCTWORK ABOVE BOTTOM CHORD OF TRUSS.
SUPPLY DUCTWORK SHALL PENETRATE WALL AT APPROXIMATELY 8'-5" ABOVE FLOOR TO
BOTTOM OF DUCT. RETURN DUCTWORK SHALL PENETRATE WALL AT APPROXIMATELY 10'-10"
ABOVE FLOOR TO BOTTOM OF DUCT.
PROVIDE GAS-FIRED UNIT HEATER, THERMOSTAT, CONTROL WIRING, HANGERS, SUPPORTS,
AND 3" CONCENTRIC VENT KIT COMPLETE.
PROVIDE ELECTRIC UNIT HEATER, THERMOSTAT, CONTROL WIRING, HANGERS, AND
SUPPORTS COMPLETE.
TERMINATE DUCT WITH WIRE MESH SCREEN.
LOUVER SHALL BE FOR AESTHETIC PURPOSES ONLY. PROVIDE SHEET METAL AND
INSULATION COMPLETE TO BLANK OFF LOUVER AT INTERIOR.
PROVIDE REMOTE OPERATED VOLUME DAMPERS AT THE INDICATED AREAS. DUCTWORK IN
THESE AREAS SHALL BE LOCATED ABOVE THE BOTTOM CHORD OF THE TRUSS. REFER TO
"REMOTE DAMPER OPERATOR DETAIL".
PROVIDE LOUVER WITH MOTORIZED DAMPER. REFER TO RELIEF DAMPER CONTROL DIAGRAM.
PROVIDE FIRE DAMPER COMPLETE. REFER TO DETAIL ON SHEET M-001.
NENLARGED DUCTWORK PLAN
SCALE: 1/4" = 1'-0"
A M-101
NENLARGED DUCTWORK PLAN
SCALE: 1/4" = 1'-0"
B M-101
C M-101
NSECTION 1
SCALE: 1/4" = 1'-0"
D M-101
20 CF
E F G H
0.5
B.1 B.7BA C D
I J K L M N O P
VAV-1
VAV-2
VAV-3
VAV-4VAV-5
VAV-6
VAV-7
DSS-1B
DSS-1A
dynamic block insulation- scale to fit wall & use grips to stretch
CWRCWSHWSHWR
CWRCWSHWSHWR
2"
3/4"
1-1/2"
1-1/2"1"
3/4"
3/4"
3/4" 3/4"
UNDERGROUND 3 (TYP)
2 (TYP)
2 (TYP)
VAV-8
D
RS
/R L
3/4"
T
TT
T
T
T
T
A M-201
B M-201
T
T
T
HWSHWRHWSHWR
9 (TYP)
9 (TYP)
SPLASH BLOCK
C C
C
2-1/2"
3/4"
VAV-9
T
AHU-1
B-1 B-2
SHWP-2
SHWP-1
VFD
VFD
G
ET-1
CWRCWS
CWRCWSHWSHWR
PHWS PHWR
2-1/2"2"
3"
2"
2"
2"
2"
1 (TYP)
2 (TYP)
3 (TYP)
4 GAS METER
DDC
AS-1
CHEMICAL
SHOT
FEEDER
TO CHILLER, REFER TO
MS101 FOR CONTINUATION
UH-1
1-1/4"
3/4"
D
D
3" FD
3" FD
AHU-2
1"
HW
S
HW
R
HW
S
HW
R
3 (TYP)2 (TYP)
CW
R
CW
S
2"
2-1/2"
1-1/2"
D
1-1/4"3" FD
02/24/2020
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
NEW WORK NOTES
PROVIDE GAS PIPING, HANGERS, AND SUPPORTS COMPLETE.
PROVIDE HOT WATER PIPING, INSULATION, HANGERS, AND SUPPORTS COMPLETE.
PROVIDE CHILLED WATER PIPING, INSULATION, HANGERS, AND SUPPORTS COMPLETE.
GAS METER PROVIDED BY PIEDMONT NATURAL GAS.
PROVIDE REFRIGERANT PIPING, INSULATION, HANGERS, AND SUPPORTS COMPLETE.
PROVIDE CONDENSATE DRAIN PIPING, INSULATION, HANGERS, AND SUPPORTS
COMPLETE.
PROVIDE DUCTLESS SPLIT SYSTEM INDOOR UNIT COMPLETE. MOUNT ON WALL
APPROXIMATELY 7'-0" ABOVE FLOOR TO BOTTOM OF UNIT.
PROVIDE DUCTLESS SPLIT SYSTEM OUTDOOR UNIT. MOUNT ON EQUIPMENT PAD.
PROVIDE THERMOSTAT AND CONTROL WIRING COMPLETE.
PROVIDE CONDENSATE DRAIN PIPING COMPLETE. ROUTE TO NEAREST FLOOR DRAIN.
PROVIDE DIFFERENTIAL PRESSURE SENSOR FOR HEATING WATER FLOW CONTROL.
PROVIDE ISOLATION VALVES AND P/T PORTS ON EACH SIDE OF SENSOR.
NMECHANICAL ENLARGED PIPING PLAN
SCALE: 1/4" = 1'-0"
NMECHANICAL NEW WORK FIRST FLOOR PLAN - PIPING
SCALE: 1/8" = 1'-0"
A M-201
NMECHANICAL ENLARGED PIPING PLAN
SCALE: 1/4" = 1'-0"
B M-201
02/24/2020
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
TURNING VANES,
SINGLE
THICKNESS
ELBOW
TEE
MAIN DUCT
45°
45°
W
SA/OA
RA/EA
L = 1/4W
L (4" MIN.)
BRANCH DUCT
BALANCING DAMPER (B.D.)
W
USE ONLY WHERE RECTANGULAR RUN-OUTS ARE INDICATED ON
DRAWINGS
SA/OA
RA/EA MAIN DUCT
BRANCH DUCT
BALANCING DAMPER
(B.D.)
USE ONLY WHERE ROUND RUN-OUTS ARE INDICATED ON DRAWINGS
ROUND
RECTANGULAR
L (4" MIN.)
L = 1/4W
DRAIN PAN TRAPPING FOR SECTION
UNDER NEGATIVE PRESSURE:
L = H + J + PIPE DIAMETER WHERE:
H = 1 INCH FOR EACH INCH OF NEGATIVE
PRESSURE PLUS 1 INCH
J = 1/2 H
DRAIN PAN TRAPPING FOR SECTION
UNDER POSITIVE PRESSURE:
L = H + J + PIPE DIAMETER WHERE:
H = 1/2 INCH (MINIMUM)
J = 1/2 INCH PLUS THE UNIT POSITIVE
STATIC PRESSURE AT COIL DISCHARGE
(LOADED FILTERS)
CLEANOUT (TYP. FOR 2)
DRAIN LINE SHALL BE AT
LEAST THE SAME SIZE AS THE
NIPPLE ON THE DRAIN PAN
PITCH DOWN TOWARD
DRAIN, ROUTE AS
INDICATED ON PLAN
DRAIN PANL
J
H
PROVIDE (3) 1/4"ø VENT HOLES
PRESSURE GAUGE -
0 - 30 PSIG RANGE
CHILLER
MANUAL
AIR VENT
FLOW SWITCH
3" CWR
3" CWS
SUPPORT FROM
STRUCTURE ABOVE
THREADED ROD
(TYPICAL)
STEEL ANGLE
NUT WITH LOCK WASHER
(TYPICAL)
METAL HANGER STRAP
SECURE TO BOTTOM AND
SIDES OF DUCT WITH SHEET
METAL SCREWS
NOTE: FOR ANGLE SIZE AND HANGER STRAP GAUGE, SEE
SMACNA LOW PRESSURE DUCT CONSTRUCTION STANDARDS.
SUPPORT FROM
FLOOR OR ROOF
STRUCTURE ABOVE3/8" THREADED
ROD
CLEVIS HANGER (SIZE
AS REQUIRED)
SUPPORT FROM
FLOOR OR ROOF
STRUCTURE ABOVE
BOLT AND CLAMPING
NUT (TYP.)
STEEL PIPE
STRAP
1-5/8" x 1-5/8" x 12 GAUGE
STEEL CHANNEL
INSULATION SADDLE
3/8" THREADED ROD
LENGTH AS REQUIRED
INSULATION SADDLE
(TYP)MULTIPLE PIPE
RUNS
SINGLE PIPE RUN
6"
SECTION
PLAN
EDGE OF CHILLER
6"
6"6"
GRADE
45° CHAMFER
WWF 6 X 6 - W 2.9 X 2.9
TOP SHALL BE LEVEL
8"
2" M
IN
1'- 6"
STRAIGHT LENGTHS OF UNOBSTRUCTED
PIPE WITHOUT INLINE APPURTENANCES
SHALL BE INSTALLED UP AND DOWNSTREAM
OF FLOW CONTROL BALANCING VALVES PER
MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
THERMOMETER 0 -
200° F (TYP. OF 2)
3/4" DRAIN VALVE WITH
HOSE CONNECTION
FLOW CONTROL
BALANCING VALVE
PRESSURE GAGE TAP WITH
CAP AND PET COCK (TYP.)
COIL
MANUAL AIR VENT
PROVIDE VIBRATION
ISOLATING FLEXIBLE PIPING
CONNECTOR (TYP. FOR 2)
SUPPLY MAIN
RETURN MAIN
MANUAL BALANCING
VALVE W/TAPS
CONDENSATE DRAIN
TRAP. SEE DETAIL3/4" DRAIN VALVE W/
HOSE CONNECTION
DRAIN
DRAIN PAN
MANUAL AIR VENT
THERMOMETER, 30°- 75°F
RANGE (TYP)
PRESSURE GAGE TAP W/
CAP & PET COCK (TYP)
PROVIDE VIBRATION
ISOLATING FLEXIBLE PIPING
CONNECTOR (TYP. FOR 2)
NOTES:
1. ARRANGE PIPING TO PERMIT REMOVAL OF COIL.
2. MANUAL BALANCING VALVES SHALL BE INSTALLED IN
CONFORMANCE WITH VALVE MANUFACTURER'S RECOMMENDED
SPACING UP AND DOWNSTREAM FROM PIPE CHANGES IN
DIRECTION AND/OR OTHER VALVES AND COMPONENTS IN THE PIPING SYSTEM.
APPROX.
46"
THERMOSTAT/
TEMPERATURE SENSOR,
MOUNTED CENTERLINE
WITH ADJACENT WALL
SWITCHES
FINISHED FLOOR
WALL SWITCH
T
WALL FRAMING (TYP.)
3" CWS/CWR
AC-1
THERMOMETER
0°-100°F RANGE (TYP.
FOR 2)
NC
3" OUTDOOR
TEMPORARY CHILLER
CONNECTION
NC
3" CWS/CWR
FLOW SWITCH
UNDERGROUND
FLEXIBLE CONNECTOR (TYP.)
3-WAY CONTROL
VALVE
BY-PASS SQUARE
HEAD COCK
3-WAY CONTROL VALVE
4" ALL AROUND UNIT
45° CHAMFER
FINISHED
FLOOR 6/6 WIRE
MESH
EQUIPMENT
4"
CHECK VALVE
MANUAL FLOW
CONTROL
BALANCING VALVE
NEEDLE VALVE - N.O.
(CLOSE FOR PUMP
SUCTION PRESSURE)
PRESSURE GAUGE 0 - 120
PSIG RANGE
IF PUMP SUCTION
AND DISCHARGE
FLANGES ARE
TAPPED, USE THESE
POINTS FOR
PRESSURE GAUGE
CONNECTIONS
BALL VALVE - N.C.
(OPEN FOR PUMP
SUCTION)
STRAIGHT LENGTHS OF UNOBSTRUCTED PIPE WITHOUT INLINE
APPURTENANCES SHALL BE INSTALLED UP / DOWNSTREAM OF FLOW CONTROL
BALANCING VALVE PER MANUFACTURER'S INSTALLATION INSTRUCTIONS
BALL VALVE
UNION
CONCENTRIC REDUCER
MOTOR
PUMP
CONCENTRIC REDUCER
UNION
BALL VALVE
INLINE CENTRIFUGAL PUMP DETAIL
SCALE: NO SCALE M-501B CHILLED WATER COIL PIPING DETAIL
SCALE: NO SCALE M-501C AHU HOT WATER COIL PIPING DETAIL
SCALE: NO SCALE M-501D
PIPE SUPPORT DETAILS
SCALE: NO SCALE M-501E CONDENSATE DRAIN TRAP DETAIL
SCALE: NO SCALE M-501F CHILLER PAD TYPICAL DETAIL
SCALE: NO SCALE M-501G
CHILLER PIPING DIAGRAM
SCALE: NO SCALE M-501H CONCRETE PAD DETAIL - INTERIOR
SCALE: NO SCALE M-501I
CHILLER PIPING DIAGRAM #2
SCALE: NO SCALE M-501J SWITCH/THERMOSTAT MOUNTING HEIGHT DETAIL
SCALE: NO SCALE M-501K
CONCENTRIC VENT DETAIL
SCALE: NO SCALE M-501L TYPICAL BRANCH CONNECTION
SCALE: NO SCALE M-501M DUCT SUPPORT DETAIL
SCALE: NO SCALE M-501N DUCTWORK FITTING DETAIL
SCALE: NO SCALE M-501O
BY-PASS SQUARE
HEAD COCK
3/4"
FLOORGRADE
NOTES:
1. PROVIDE PRESSURE REGULATOR FOR ALL UNITS.
2. TOTAL LOAD = 600 MBH.
3. GAS PIPING SIZED PER TABLE 402.4(4) OF THE 2015
INTERNATIONAL FUEL GAS CODE FOR SCHEDULE
40 PIPE. TOTAL DEVELOPED LENGTH: 100 FEET.
3/4"(TYP.)
(600 MBH)
PLUG VALVE (TYP.)
WALL SLEEVE
PAINTED STEEL PIPING
GAS METER, SEE
DETAIL ON M-502
MECHANICAL 110
EXTERIOR WALL
B-1
(285 CFH)
B-2
(285 CFH)
VENTLESS PRESSURE
REGULATOR 2 PSIG TO
MANUFACTURER'S
RECOMMENDED
PRESSURE (TYP.)
NATURAL GAS FLOW DIAGRAM
SCALE: NO SCALE M-501A
6" DIRT LEG
(FULL SIZE)
UH-1
(30 CFH)
M
PROVIDE 120 VAC
MOTORIZED GAS
VALVE. INTERLOCK
WITH EMERGENCY
GAS SHUTOFF SWITCH.
AP
PR
OX
. 4
6- 3/
4"
AP
PR
OX
. 3
1- 7/
8"
APPROX. 4-1/2"
EXTERIOR
INTERIOR
3"Ø PVC
INTAKE/COMBUSTION AIR
3"Ø PVC
VENT/EXHAUST
02/24/2020
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
CONTINUE UP TO
STRUCTURAL ROOF
SUPPORT. PROVIDE
INTERMEDIATE SUPPORTS
AS REQUIRED
SPRING VIBRATION
ISOLATOR (TYP.)
NUT & LOCK WASHER
TOP AND BOTTOM
SUPPORT LUGS
(IF PROVIDED)
EQUIPMENT
CHANNEL
C3x6
NUT & LOCK
WASHER
TOP AND
BOTTOM
1/2" THREADED
ROD (TYP.)
THERE IS AN 36 INCH CLEARANCE RESTRICTION ON SIDE OF VAV
BOX FOR SERVICE ACCESSIBILITY. THERE SHALL BE NO
SPRINKLER PIPE, LIGHTS, WALLS, ETC. WITHIN THAT AREA.
ALLOW 48 INCH OF STRAIGHT DUCT DOWNSTREAM OF UNIT
BEFORE FIRST RUNOUT.
PROVIDE THREE WAY VALVE FOR VAV-5 AND VAV-6
MIN. LENGTH OF STRAIGHT DUCT BETWEEN VAV BOX INLET AND 1st
UPSTREAM ELBOW OR REDUCER NOT LESS THAN 4 DUCT DIAMETERS
PRIMARY
AIR
FLOW
PRIMARY AIR DUCT
AIR VALVE/DAMPER
SIZE AS INDICATED
REDUCER
NOTES:
2.
1.
DDC CONTROL BOX
36" SERVICE CLEARANCE
SIZE AS
INDICATED
TRANSITION AS REQUIRED
3/4" DRAIN VALVE WITH HOSE
CONNECTION ON LOWEST PIPE
AUTOMATIC AIR VENT WITH SHUTOFF
COCK
HWS
HWR
SET SLEEVE IN WALL AND
ANCHOR DURING WALL
CONSTRUCTION
ESCUTCHEON PLATES
(BOTH SIDES WHERE
EXPOSED)
INSULATION
PIPE
PACK WITH FIBERGLASS
AND SEAL BOTH SIDES
PIPE SLEEVE
WALL
SET SLEEVE IN WALL
AND ANCHOR DURING
WALL CONSTRUCTION
ESCUTCHEON PLATE
(WHERE EXPOSED)
WATERPROOF
SEALANT
BACK-UP
MATERIAL
EXTERIOR INTERIOR
ANCHOR
PIPE
PIPE SLEEVE
WALL
INSULATION
PIPE WITH HEAT
TAPE
INSULATION AND
METAL JACKET (TYP)
GALVANIZED PIPE EXTENSION
-LENGTH AS REQUIRED (TYP)
3/8"Øx4" LONG GALVANIZED
BOLT SET IN CONCRETE (TYP)
1/4" THICK GALVANIZED
PLATE (TYP)
24"x12"x4" THICK
CONCRETE SUPPORT PAD
PIPE STANCHION SADDLE
(MSS-SP-69 TYPE 37) (TYP)
GRADE
ELECTRICAL POWER
CONNECTION, 120 VOLTS
HEATING CABLE
TEMPERATURE
CONTROLLER PIPING
WRAP WITH ELECTRIC HEATING
CABLE TO PROVIDE 8 WATTS/FOOT
PROVIDE MANUFACTURER'S
RECOMMENDED
ATTACHMENTS AT 6" O.C.
PIPE INSULATIONALUMINUM
JACKET
STAINLESS STEEL
HOSE CLAMP4" THICK CONCRETE
PAD (16" x 16")
APPROX. 15"
APPROX. 10"
5 GALLON MINIMUM
CAPACITY
HOSE BIBB
BALL VALVE
3/4" TO PUMP SUCTION
3-1/2" MIN. OPENING
3/4" TO PUMP DISCHARGE
BALL VALVE
PLUGGED CROSSES (TYP.)
TWIST OFF PRESSURE CAP
TWO-WAY VALVE, U.O.N
SUSPENDED EQUIPMENT SUPPORT DETAIL
SCALE: NO SCALE M-502E
CHEMICAL FEED TANK DETAIL
SCALE: NO SCALE M-502I
PIPE SLEEVE THRU EXTERIOR WALL DETAIL
SCALE: NO SCALE M-502F PIPE SLEEVE THRU INTERIOR WALL DETAIL
SCALE: NO SCALE M-502G SHUT-OFF VAV TERMINAL UNIT - HOT WATER REHEAT DETAIL
SCALE: NO SCALE M-502H
HEATING CABLE DETAIL
SCALE: NO SCALE M-502J EXTERIOR PIPE SUPPORT DETAIL
SCALE: NO SCALE M-502K
METER AND INCOMING GAS
SERVICE BY PIEDMONT
NATURAL GAS Co., 600 CFH AT 2 psi:(7" - 14" W.C.)
3/4"
6" LONG
DIRT LEG
METER
3/4"
GAS METER PIPING DETAIL
SCALE: NO SCALE M-502B
2" MIN.
PROVIDE SAND BEDDING
24" MIN.
COMPACTED BACKFILL
COORDINATE CONCRETE
SIDEWALK AND CONCRETE SLAB
WORK WITH OTHER DISCIPLINES
WHERE APPLICABLE.
UNDISTURBED EARTH
CWS/CWR PIPING SIZE
AS INDICATED
6" MIN.
6" MIN.
PIPE TRENCH DETAIL
SCALE: NO SCALE M-502D
2" MIN.
PROVIDE SAND BEDDING
24" MIN.
COMPACTED BACKFILL
DIRT GRADE
UNDISTURBED EARTH
CWS/CWR PIPING SIZE
AS INDICATED
6" MIN.
6" MIN.
BELOW SIDEWALK BELOW GRADE
3.
HWS/HWR PIPING SIZE
AS INDICATED
HWS/HWR PIPING SIZE
AS INDICATED
1" x 1" TREATED WOOD
NAILER STRIP (TYPICAL)
MOTOR
GUARD
WALL MOUNTED
EXHAUST FAN WITH WIRE
GUARD AND MOTOR
MOUNT: SEE PLANS AND
SCHEDULE FOR
LOCATIONS AND
CAPACITIES
2" x 2" x 1/4" ANGLE, FASTEN
WITH EXPANSION BOLTS TO
CONCRETE BLOCK WALL
AND BELOW FAN
BIRDSCREEN
LOUVER:
SEE
PLANS
SIDEWALL EXHAUST FAN DETAIL
SCALE: NO SCALE M-502C
DUCT
RACK AND PINION OPERATOR.
CONVERTS ROTARY MOTION
OF SHAFT TO PUSH/PULL
MOTION OF WIRE
DIE CAST MOUNTING CUP
2 1/2" METAL STUD
PROVIDE OPENING IN METAL STUD JUST
LARGE ENOUGH TO ENGAGE OPERATOR
SHAFT WITH SOCKET WRENCH
3" DIAMETER PLATED COVER ON
CEILING (REMOVE TO ADJUST DAMPER)
SHEET METAL
SCREW (TYPICAL)
1/2" GYPSUM BOARD
CEILING
SHEET METAL
SCREW (TYPICAL)
FLEXIBLE SPRING
WIRE SHEATH WITH
.050 STAINLESS WIRE
INSIDE
BUTTERFLY DAMPER,
SINGLE BLADE, 90°
OPEN/CLOSE
OPERATION
REMOTE DAMPER OPERATOR DETAIL
SCALE: NO SCALE M-502A
| 60025679 |
| Sheets and Views |
| M-001 MECHANICAL GENERAL NOTES AND LEGEND |
| 60025680 |
| Sheets and Views |
| MD101 MECHANICAL DEMOLITION FLOOR PLANS |
| 60025681 |
| Sheets and Views |
| MS101 MECHANICAL SITE PLAN |
| 60025682 |
| Sheets and Views |
| M-101 MECHANICAL NEW WORK FLOOR PLANS - DUCTWORK |
| 60025683 |
| Sheets and Views |
| M-201 MECHANICAL NEW WORK FLOOR PLANS - PIPING |
| 60025684 |
| Sheets and Views |
| M-501 MECHANICAL DETAILS |
| 60025685 |
| Sheets and Views |
| M-502 MECHANICAL DETAILS |