N4008519B0095 Drawings_Part7.pdf
PDF 7 MB Posted
- Attached to
- Building 17 and 17A Renovation and Addition
- Solicitation number
- N6247020R6000
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Large Cabinet.jpg | JPG image | |
| Tabernacle.jpg | JPG image | |
| 08 62 00 Translucent Wall Panels.pdf | ||
| Organ (2).jpg | JPG image | |
| Grand Piano.jpg | JPG image | |
| Baptismal Font.jpg | JPG image | |
| Organ (1).jpg | JPG image | |
| Altar (2).jpg | JPG image | |
| Amnd 0006 20R6000 Final.pdf | ||
| Altar (1).jpg | JPG image | |
| Amnd 0005 20R6000 Final.pdf | ||
| Amnd 0004 20R6000 Final.pdf | ||
| Amnd 0003 20R6000 Final.pdf | ||
| Amnd 0002 20R6000 Final.pdf | ||
| NAVFAC DWG 60025678.pdf | ||
| NAVFAC DWG 60025676.pdf | ||
| Amend 0001 20R6000.pdf | ||
| N4008519B0095 Drawings_Part8.pdf | ||
| N4008519B0095 Drawings_Part3.pdf | ||
| N4008519B0095 Drawings_Part6.pdf | ||
| N4008519B0095 Specs.pdf | ||
| 19-0095 Asbestos Survey 011020.pdf | ||
| N4008519B0095 Drawings_Part2.pdf | ||
| N4008519B0095 Drawings_Part5.pdf | ||
| RFP N62470-20-R-6000.pdf | ||
| N4008519B0095 Drawings_Part1.pdf | ||
| 19-0095 Lead Survey 011020.pdf | ||
| N4008519B0095 Drawings_Part4.pdf | ||
| N4008519B0095 Drawings_Part9.pdf | ||
| Master PPI Form Template.xls | XLS spreadsheet |
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
02/24/2020
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
HOT WATER COIL
FROM VARIABLE
FREQUENCY DRIVE
FREEZESTAT
AIR
OPPOSED
DAMPER
BLADE
FILTER
OUTSIDE
NC
OPPOSED
DAMPER
BLADE
CW
R
NO
HW
R
HW
S
CW
S
NC
SET AT
5" WG
CHILLED WATER COIL
SUPPLY FAN
M
PRIMARY
AIR
INPUTS
DI
GI
TA
L
HW VALVE CONTROL
CW VALVE CONTROL
A02
AO1
OUTPUTS
A03AN
AL
OG
SUPPLY AIR FAN STATUS
SMOKE DETECTOR
FREEZESTAT
MIXED AIR TEMPERATURE
SUPPLY AIR TEMPERATURE
HW COIL DISCHARGE AVERAGE
UNIT DISCHARGE STATIC PRESSURE
SA DOWN DUCT PRESSURE TRANSMITTER
AI4
AI5
DI1
DI3
DI2
AI2
AI1
AI3
AN
AL
OG
LOCAL DDC CONTROLLER
AHU
OA AIRFLOW MEASURE MOUNT STATIONAI6
A04 OUTSIDE AIR DAMPER CONTROL
AO1
AO4
DM
DM
AMSAI6
AI1
TS FS DI3
AO2
TS
AI3
AO3 AI2
VFD TS SPS
AI4 AI5
SPS
DI1
DPS
NO
LOCATE AT 2/3 DOWN
DUCT FROM AHU
AI7
CONDENSATE HI-LEVELDI4DI4
LS
RA TEMPERATUREAI8
AI8 TS
AI7 HS
PROVIDE 3-WAY CONTROL VALVE. SEE VFD CONTROL
DIAGRAM
AIR
RETURN
RA HUMIDITY
RETURN AIR DAMPER CONTROL
SINGLE ZONE VAV AHU-1 CONTROL DIAGRAM (DDC)
SCALE: NO SCALE M-704A
SEQUENCE OF OPERATION
BUILDING AUTOMATION SYSTEM INTERFACE:
THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE DDC CONTROLLER
OCCUPIED, UNOCCUPIED, OPTIMUM START, NIGHT HEAT/COOL, AND TIMED
OVERRIDE COMMANDS. THE BAS SHALL ALSO SEND SPACE TEMPERATURE
SETPOINT TO THE CONTROLLER. IF COMMUNICATION IS LOST WITH THE BAS, THE
CONTROLLER SHALL OPERATE IN THE OCCUPIED COOLING MODE USING ITS
DEFAULT SPACE TEMPERATURE SETPOINT.
SUPPLY FAN:
THE SUPPLY FAN SHALL BE OFF IN UNOCCUPIED MODE. WHEN THE CONTROLLER IS
IN THE OCCUPIED MODE, THE SUPPLY FAN SHALL BE ENABLED. IF THE SUPPLY FAN
FAILS TO PROVE STATUS FOR 30 SECONDS (ADJ), THE FAN SHALL BE COMMANDED
OFF, THE OUTDOOR AIR DAMPER SHALL BE CLOSED, COOLING/HEATING SHALL BE
DISABLED, AND AN ALARM SHALL BE SENT TO THE BAS. A MANUAL RESET SHALL BE
REQUIRED TO RESTART THE FAN.
HEATING/COOLING MODE:
WHEN THE SPACE TEMPERATURE RISES ONE DEGREE (ADJ) ABOVE THE OCCUPIED
COOLING SETPOINT, THE MODE SHALL TRANSITION TO COOLING. WHEN THE SPACE
TEMPERATURE FALLS ONE DEGREE (ADJ) BELOW THE OCCUPIED HEATING
SETPOINT, THE MODE SHALL TRANSITION TO HEATING. WHEN THE SPACE
TEMPERATURE IS BETWEEN ONE DEGREE (ADJ) ABOVE THE OCCUPIED COOLING
SETPOINT AND ONE DEGREE (ADJ) BELOW THE OCCUPIED HEATING SETPOINT, THE
MODE SHALL REMAIN IN ITS LAST STATE. IF THE SPACE TEMPERATURE INPUT FAILS,
THE MODE SHALL REMAIN IN ITS LAST STATE AND AN ALARM SHALL BE SENT TO
THE BAS. IF THE LOCAL (AND COMMUNICATED) SETPOINTS(S) FAIL, THE
CONTROLLER WILL USE ITS DEFAULT SETPOINTS AND AN ALARM SHALL BE SENT TO
THE BAS.
OCCUPIED MODE:
DURING OCCUPIED MODE, THE OUTDOOR AIR DAMPER SHALL BE OPEN AND THE SUPPLY
FAN SHALL OPERATE AND MODULATE ITS SPEED AS REQUIRED TO MEET THE SPACE
TEMPERATURE SETPOINT. ONCE THE SETPOINT HAS BEEN ACHIEVED, THE OUTDOOR AIR
DAMPER SHALL BE CLOSED AND THE SUPPLY FAN SHALL BE DISABLED.
COOLING MODE:
ON A RISE IN SPACE TEMPERATURE ABOVE THE SPACE COOLING SETPOINT S.P.
(ADJ) THE DDC CONTROLLER SHALL MODULATE THE CHILLED WATER VALVE TO
MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT, 55 DEGREES (ADJ). ON A
CONTINUED RISE IN SPACE TEMPERATURE ABOVE THE SPACE COOLING SETPOINT
(ADJ), ONCE THE CHILLED WATER VALVE IS FULLY OPEN, THE DDC CONTROLLER
SHALL SIGNAL THE SUPPLY FAN VFD TO MODULATE THE SUPPLY FAN SPEED UP TO
ITS MAXIMUM SETTING AS REQUIRED TO MAINTAIN THE SPACE TEMPERATURE
SETPOINT. ON A FALL IN SPACE TEMPERATURE, THE SUPPLY FAN SPEED SHALL BE
MODULATED BACK TO ITS MINIMUM SPEED SETTING. ON A CONTINUED FALL IN
SPACE TEMPERATURE BELOW THE SPACE TEMPERATURE SETPOINT, AND WHEN
THE SUPPLY FAN IS AT ITS MINIMUM SPEED, THE DISCHARGE TEMPERATURE
SETPOINT SHALL BE GRADUALLY RESET UP TO NEUTRAL SPACE TEMPERATURE, 75º
(ADJ).
HEATING MODE:
ON A FALL IN SPACE TEMPERATURE BELOW THE SPACE HEATING TEMPERATURE
SETPOINT (ADJ), THE DDC CONTROLLER SHALL MODULATE THE HOT WATER
RE-HEAT VALVE TO MAINTAIN DISCHARGE AIR TEMPERATURE TO THE SETPOINT OF
THE DDC CONTROLLER. ON A CONTINUED FALL IN SPACE TEMPERATURE BELOW
THE SPACE HEATING TEMPERATURE SETPOINT (ADJ), ONCE THE HOT WATER VALVE
IS FULLY OPEN, THE DDC CONTROLLER SHALL SIGNAL THE SUPPLY FAN VFD TO
MODULATE THE SUPPLY FAN SPEED UP TO ITS MAXIMUM SETTING AS REQUIRED TO
MAINTAIN THE SPACE SETPOINT. ON A RISE IN SPACE TEMPERATURE, THE SUPPLY
FAN SPEED SHALL BE MODULATED BACK TO ITS MINIMUM SPEED SETTING. ON A
CONTINUED RISE IN SPACE TEMPERATURE ABOVE THE SPACE HEATING SETPOINT,
AND WHEN THE SUPPLY FAN IS AT MINIMUM SPEED, THE DISCHARGE
TEMPERATURE SETPOINT SHALL BE GRADUALLY RESET UP TO NEUTRAL SPACE
TEMPERATURE, 75ºF (ADJ). THE DISCHARGE AIR SETPOINT SHALL BE INVERSELY
RESET FROM SPACE TEMPERATURE.
DEHUMIDIFICATION MODE:
ON A RISE IN SPACE RELATIVE HUMIDITY TO THE SETPOINT OF THE DDC
CONTROLLER, THE DDC CONTROLLER SHALL MODULATE THE CHILLED WATER
VALVE FULLY OPEN TO THE COIL. SHOULD THE DEHUMIDIFICATION PROCESS
CAUSE THE SPACE TO OVER COOL, THE DDC CONTROLLER SHALL MODULATE THE
REHEAT VALVE OPEN TO MAINTAIN THE SPACE HEATING TEMPERATURE SETPOINT.
MORNING WARM-UP:
DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS 1.5°F (ADJ) OR MORE
BELOW THE OCCUPIED HEATING SETPOINT, THE MORNING WARM-UP SEQUENCE
SHALL BE ACTIVATED. THE SUPPLY FAN SHALL START, THE HOT WATER VALVE
SHALL MODULATE OPEN, AND THE OUTDOOR AIR DAMPER SHALL REMAIN CLOSED.
MORNING WARM-UP MODE SHALL TERMINATE WHEN THE SPACE TEMPERATURE
REACHES THE OCCUPIED HEATING SETPOINT OR THE OCCUPIED TIME PERIOD HAS
STARTED.
MORNING COOL-DOWN:
DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS 1.5°F (ADJ) OR MORE
ABOVE THE OCCUPIED COOLING SETPOINT, THE MORNING COOL-DOWN SEQUENCE
SHALL BE ACTIVATED. THE SUPPLY FAN SHALL START, THE CHILLED WATER VALVE
SHALL MODULATE OPEN, AND THE OUTDOOR AIR DAMPER SHALL REMAIN CLOSED.
MORNING COOL-DOWN MODE SHALL TERMINATE WHEN THE SPACE TEMPERATURE
REACHES THE OCCUPIED COOLING SETPOINT OR THE OCCUPIED TIME PERIOD HAS
STARTED.
FREEZE PROTECTION:
IF HOT WATER COIL DISCHARGE AIR TEMPERATURE FALLS BELOW 40°F DURING
HEATING MODE, THE FREEZESTAT SHALL CLOSE THE OUTSIDE AIR DAMPER,
DE-ENERGIZE THE AHU SUPPLY FAN AND FULLY OPEN THE HOT WATER AND
CHILLED WATER VALVES TO COIL.
UNOCCUPIED MODE:
DURING UNOCCUPIED MODE THE DDC CONTROLLER SHALL CYCLE THE UNIT TO
MAINTAIN A REDUCED HEATING SETPOINT, 55ºF (ADJ), AND A RAISED COOLING AND
RELATIVE HUMIDITY SETPOINT, 85ºF/60% RH (ADJ), WHILE MAINTAINTING THE
OUTDOOR AIR DAMPER FULLY CLOSED.
SAFETY CONTROL:
SMOKE DETECTOR SHALL BE PROVIDED BY FIRE ALARM CONTRACTOR. THROUGH
DDC CONTROL IT SHALL DE-ENERGIZE THE ASSOCIATED AHU, SIGNAL FIRE ALARM
PANEL AND CLOSE THE OUTSIDE AIR DAMPER UPON THE DETECTION OF THE
PRODUCTS OF COMBUSTION.
ALARMS:
ALARM IF LEAVING AIR TEMPERATURE EXCEEDS 60°F IN COOLING MODE OR DROPS
BELOW 50°F IN HEATING MODE. ALARM IF AHU SUPPLY FAN FAILS TO START OR
FAILS DURING OPERATION. ALARM IF UNIT DISCHARGE STATIC PRESSURE EXCEEDS
5" W.G. ALARM IF CONDENSATE REACHES HIGH LEVEL. ALARM UPON SMOKE
DETECTOR ACTIVATION.
DEMAND CONTROL VENTILATION:
IF ANY SPACE CARBON DIOXIDE LEVEL FALLS BELOW SETPOINT (1,000 PPM, ADJ.),
THE OUTSIDE AIRFLOW RATE SHALL BE AT THE MINIMUM SCHEDULED VALUE AS
INDICATED IN THE EQUIPMENT SCHEDULE. AS LEVEL INCREASES ABOVE SETPOINT,
THE OUTSIDE AIR DAMPER SHALL PROPORTIONALLY MODULATE OPEN TO
GENERATE THE SCHEDULED MAX OUTSIDE AIRFLOW RATE OVER A 1 HOUR (ADJ.)
TIME PERIOD UNTIL THE LEVEL FALLS BELOW THE SETPOINT, AFTER WHICH THE
DAMPER POSITION SHALL RETURN TO MINIMUM.
DI2
SD
AI9
CO2
CO2 SENSORAI9
PUMP SHALL ENERGIZE DURING OCCUPIED HOURS. COORDINATE OCCUPIED HOURS WITH THE GOVERNMENT.
DI
GI
TA
L
PUMP ENABLE/DISABLEDO1
OUTPUTS
PUMP STATUS
DI
GI
TA
L
DI1
LOCAL DDC CONTROLLER
INPUTS
DOMESTIC WATER PUMP
SEQUENCE OF OPERATION
DO1
CSR DI1
DOMESTIC WATER PUMP CONTROL DIAGRAM (DDC)
SCALE: NO SCALE M-704B
PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
ELECTRICAL DEMOLITION NOTES
GENERAL: DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELD INVESTIGATION PRIOR TO
DEMOLITION.
DASHED ITEMS: ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE EXISTING AND MUST BE REMOVED.
SOLID ITEMS: ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE EXISTING TO REMAIN.
CIRCUITING TO REMAIN: EXISTING CIRCUITING TO REMAIN MUST BE REROUTED OR RECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW WORK IN ORDER TO MAINTAIN CONTINUITY OF THE CIRCUIT.
REUSE OF EXISTING CIRCUITRY: EXISTING CIRCUITRY SERVING LIGHTING FIXTURES AND/OR RECEPTACLES FOR A GIVEN AREA MUST BE REUSED WHERE INDICATED TO SERVE THE NEW LAYOUT. PROVIDE CIRCUIT MODIFICATIONS INDICATED OR AS OTHERWISE REQUIRED TO MAINTAIN THE CONTINUITY OF EXISTING
CIRCUITS THAT REMAIN.
EXISTING CONDUIT: ALL EXISTING CONDUITS AND WIRING THAT WILL NOT BE REUSED MUST BE REMOVED WHERE THEY WILL BE EXPOSED UPON COMPLETION OF NEW WORK. EXISTING CONDUIT TO REMAIN CONCEALED IN WALLS MUST BE ABANDONED. EXISTING CONDUIT TO REMAIN BELOW FLOOR SLAB MUST BE CUT OFF ONE INCH BELOW ROUGH FLOOR AND GROUTED FLUSH. ALL EXISTING WIRING IN CONDUITS
TO BE ABANDONED MUST BE DISCONNECTED FROM POWER SOURCE AND REMOVED.
REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT NO ADDITIONAL COST TO THE OWNER, ANY DAMAGE CAUSED TO EXISTING CONSTRUCTION AND/OR EQUIPMENT TO REMAIN.
ASSOCIATED APPURTENANCES: REMOVE ALL ELECTRICAL APPURTENANCES (DISCONNECTS, STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH ITEMS TO BE REMOVED INCLUDING EQUIPMENT TO BE
REMOVED BY OTHERS.
KNOCKOUT PLUGS AND COVERS: ALL CONDUIT REMOVED MUST BE REMOVED IN ITS ENTIRETY, INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE, ETC. PROVIDE CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS CREATED BY THE REMOVAL OF CONDUIT. PROVIDE BLANK COVER PLATES FOR ALL OPENED
OUTLET BOXES CREATED BY THE REMOVAL OF EQUIPMENT AND/OR DEVICES
DEMOLISHED MATERIALS: ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR DESIGNATED TO BE TURNED OVER TO THE OWNER, MUST BECOME THE PROPERTY OF THE CONTRACTOR
AND MUST BE REMOVED COMPLETELY FROM THE SITE.
SCHEDULE OUTAGES: ALL WORK AND ALL POWER OUTAGES IN THE EXISTING BUILDING MUST BE
SCHEDULED AT TIMES CONVENIENT TO THE OWNER.
NOTIFICATION: NOTIFY THE CONTRACTING OFFICER PRIOR TO TURNING OFF ANY CIRCUITS.
ABANDONED COMMUNICATIONS CABLING: ABANDONED COMMUNICATIONS CABLING (TELEPHONE OR
DATA) ABOVE THE CEILING MUST BE REMOVED PER NEC ARTICLE 645.
LIGHTING FIXTURE
EMERGENCY LIGHTING FIXTURE WITH EMERGENCY BATTERY PACK - CONNECT
EMERGENCY PACK AHEAD OF LOCAL SWITCH.
DOWNLIGHT OR PENDANT MOUNTED FIXTURE
EXIT LIGHTING FIXTURE, WITH DIRECTIONAL ARROWS AS INDICATED WITH BATTERY
PACK - CONNECT AHEAD OF LOCAL SWITCH.
EMERGENCY BATTERY LIGHTING UNIT, CONNECT AHEAD OF LOCAL SWITCH.
LIGHTING FIXTURE TYPE SYMBOL. SEE LIGHTING FIXTURE DETAILS.
SINGLE POLE SWITCH, 20A, 120/277V, 46" AFF UON
THREE-WAY SWITCH, 20A, 120/277V, 46" AFF UON
DIMMER SWITCH, 46" AFF UON. FOR L.E.D. FIXTURES, COORDINATE VOLTAGE AND
RATINGS OF SWITCH WITH TYPE AND QUANTITY OF BALLASTS OR DRIVERS TO BE
CONTROLLED.
EQUIPMENT CONNECTION
JUNCTION BOX
MOTOR CONNECTION
SAFETY SWITCH, 60A-3P, FU @ 30A, 3R
MAGNETIC MOTOR STARTER, MOUNT WITHIN SITE OF MOTOR 5'-0" AFF MAX, UON.
ELECTRICAL PANELBOARD (208/120V, 3 PH, 4 WIRE)
ELECTRICAL CIRCUIT RUN IN CONDUIT AND CIRCUIT HOMERUN TO PANELBOARD
(PANEL AND CIRCUIT DESIGNATION AS INDICATED). AS A MINIMUM CONDITION, EACH
SINGLE PHASE CIRCUIT MUST HAVE 1 #12 PHASE CONDUCTOR, 1 #12 NEUTRAL
CONDUCTOR AND 1 #12 GROUNDING CONDUCTOR IN 1/2" CONDUIT. PROVIDE
ADDITIONAL PHASE CONDUCTORS AS REQUIRED FOR "MULTIPLE PHASED"
ELECTRICAL LOADS. PROVIDE NEUTRAL CONDUCTOR TO ALL WALL SWITCH OUTLET
BOXES WHETHER REQUIRED OR NOT. PROVIDE ADDITIONAL "SWITCH LEG"
CONDUCTORS TO PROVIDE THE LIGHT FIXTURE CONTROL INDICATED. MULTIPLE
SINGLE PHASE CONDUCTORS MAY BE GROUPED TOGETHER IN A COMMON CONDUIT
IN ACCORDANCE WITH THE NEC AND AT THE CONTRACTOR'S DISCRETION.
GROUNDING CONDUCTORS MAY BE SHARED AS ALLOWED BY THE NEC. NEUTRAL
CONDUCTORS MUST NOT BE SHARED. MULTI-POLE BREAKERS MUST BE PROVIDED IN
ACCORDANCE WITH THE NEC WHERE MULTI-WIRE BRANCH CIRCUITS ARE REQUIRED.
CONDUIT LARGER THAN 1/2" AND CONDUCTORS LARGER THAN #12 MUST BE AS
INDICATED.
LIGHTING
POWER
GENERAL
WALL MOUNTED LIGHTING FIXTURE
SPECIAL RECEPTACLE, AS NOTED ON PLANS
NEW WORK NOTE SYMBOL
DEMOLITION NOTE SYMBOL
VARIABLE FREQUENCY DRIVE (UNIT SUPPLIED WITH DISCONNECTING MEANS)
MOTOR RATED SWITCH WITH THERMAL OVERLOADS 20A, 120V, UON, MOUNTED
WITHIN SIGHT OF MOTOR.
TIME CLOCK
PHOTOCELL, 1500W, 120V SPST, MOUNT ON ROOF, AIM NORTH
TRACK LIGHTING FIXTURE. INDICATES AN INDIVIDUAL FIXTURE ON THE TRACK
SURGE PROTECTIVE DEVICE
GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK SHOWN ON
ELECTRICAL DRAWINGS IS NEW WORK TO BE PROVIDED UNDER THIS CONTRACT.
COORDINATION: COORDINATE AND COOPERATE WITH ALL TRADES ON THE
PROJECT. THE CONTRACTOR MUST REVIEW ALL CONTRACT DOCUMENTS
INCLUDING CIVIL, STRUCTURAL, ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS. CONTRACTOR MUST COORDINATE AND ADJUST ACCORDINGLY
AS DIRECTED BY THE CONTRACTING OFFICER.
AS-BUILT DRAWINGS: SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS TO BE
KEPT ON SITE AND MARK, DAILY, THE DRAWINGS IN RED AS THE PROJECT
PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF ALL DEVIATIONS
BETWEEN THE WORK SHOWN ON THE DRAWINGS AND THE WORK WHICH IS
ACTUALLY INSTALLED. THESE MARKED DRAWINGS MUST REFLECT ANY AND ALL
CHANGES AND REVISIONS TO THE ORIGINAL DESIGN WHICH EXISTS IN THE
COMPLETED WORK. DELIVER THE MARKED DRAWINGS TO THE ENGINEER AT
PROJECT CLOSE-OUT.
TESTS: TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE CONNECTING
ANY FIXTURES OR DEVICES. PERFORM INSULATION RESISTANCE TESTS ON ALL
WIRING #6 OR LARGER TO ENSURE THAT ALL PORTIONS ARE FREE FROM
SHORT-CIRCUITS AND GROUNDS.
INSPECTIONS: ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL REQUIRED
INSPECTION CERTIFICATES TO THE CONTRACTING OFFICER.
ELECTRICAL SERVICE: PROVIDE THE ELECTRICAL SERVICE. COMMUNICATE WITH
THE CONTRACTING OFFICER, VERIFY ALL REQUIREMENTS, AND COORDINATE ALL
EFFORTS.
GROUNDING: PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR THE
ENTIRE ELECTRICAL SYSTEM INCLUDING EQUIPMENT FRAMES CONDUITS,
SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS, AND OTHER
EQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN ALL POWER CONDUITS.
LABELS: PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY
SWITCHES, MOTOR-DISCONNECT SWITCHES, AND MOTOR CONTROLLERS. LABELS
MUST BE MACHINE ENGRAVED, LAMINATED PLASTIC, PERMANENTLY ATTACHED
WITH SELF-TAPPING SCREWS OR RIVETS. DO NOT USE SELF-ADHESIVE LABELS.
LABEL MUST INDICATE EQUIPMENT DESIGNATION AND ASSOCIATED PANEL AND
CIRCUIT THAT SERVES IT.
J-BOX LABELING: LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER
IDENTIFYING CIRCUIT NUMBER AND PANELBOARD OF CIRCUITS WITHIN.
WIRING DEVICES: LABEL ALL WIRING DEVICES WITH PANELBOARD AND CIRCUIT
DESIGNATION PERMANENTLY ATTACHED WITH BLACK TYPED DESIGNATION ON
CLEAR TAPE.
PANEL DIRECTORY: PROVIDE TYPEWRITTEN PANELBOARD DIRECTORY CARD IN
EACH PANELBOARD WITH CIRCUIT LOAD INFORMATION AND ROOM NUMBER
CLEARLY IDENTIFIED. USE ACTUAL ROOM NUMBERS IN THE BUILDING, NOT THE
ROOM NUMBERS SHOWN ON THE CONTRACT DRAWINGS, AS THEY ARE OFTEN
DIFFERENT.
CONDUCTORS AND MATCHING LUGS: IN SITUATIONS WHERE CONDUCTOR SIZES
AND/OR QUANTITIES OF PARALLEL SETS HAVE BEEN INCREASED DUE TO
VOLTAGE DROP OR FOR OTHER REASONS, CONTRACTOR MUST PROVIDE THE
APPROPRIATE LUG SIZES/QUANTITIES WITHIN THE EQUIPMENT CONNECTED
(SWITCHBOARD, PANELBOARD, DISCONNECT SWITCH, TRANSFER SWITCH ETC.)
TO PERMIT SATISFACTORY CONNECTION OF THE INDICATED CONDUCTORS.
WHERE SUFFICIENT LUG SIZES AND/OR QUANTITIES CANNOT BE PROVIDED TO
ACCOMMODATE THE CONDUCTORS INDICATED, THEN PROVIDE REDUCING
ADAPTERS, PIN TERMINALS, OR A JUNCTION BOX TO SPLICE LARGER
CONDUCTORS TO APPROPRIATELY SIZED SMALLER CONDUCTORS TO FIT INTO
THE LUGS PROVIDED. ALL CONDUCTORS MUST BE SIZED IN ACCORDANCE WITH
THE NEC.
MOTOR COORDINATION: MOTORS, MOTOR STARTERS, CONTROLLERS, INTEGRAL
DISCONNECT SWITCHES, AND CONTACTORS MUST BE PROVIDED WITH THEIR
RESPECTIVE PIECES OF EQUIPMENT BY THE EQUIPMENT SUPPLIER.
COMMUNICATE WITH THE TRADES PROVIDING THE EQUIPMENT, VERIFYING ALL
REQUIREMENTS, PROVIDE ALL ELECTRICAL CONNECTIONS REQUIRED THEREIN,
AND INSTALL MOTOR STARTERS.
MOTOR DISCONNECTS: ALL MOTORS MUST HAVE DISCONNECTING MEANS.
MOTOR CONTROLLERS: ALL 3-PHASE MOTORS MUST HAVE MAGNETIC MOTOR
CONTROLLERS WITH SOLID STATE OVERLOAD RELAY PROTECTION. THE SOLID
STATE OVERLOAD RELAY MUST HAVE PHASE LOSS AND PHASE OVERCURRENT
PROTECTION WITH AUTOMATIC RESET UPON RETURN OF NORMAL POWER.
MOTOR FUSE PROTECTION: WHERE FUSE PROTECTION IS SPECIFICALLY
REQUIRED BY THE EQUIPMENT MANUFACTURER, PROVIDE FUSED SWITCHES IN
LIEU OF NON-FUSED SWITCHES OR IN LIEU OF ENCLOSED CIRCUIT BREAKERS, OR
OTHER DEVICES INDICATED.
CONNECTION DETAILS: SECURE APPROVED SHOP DRAWINGS SHOWING WIRING
DIAGRAMS, ROUGH-IN AND HOOK UP DETAILS FROM OTHER INVOLVED
CONTRACTORS FOR EQUIPMENT WHICH MUST BE CONNECTED ELECTRICALLY.
COORDINATION DETAILS: MECHANICAL EQUIPMENT WILL BE FURNISHED AND
INSTALLED BY THE MECHANICAL CONTRACTOR. THE LOCATIONS SHOWN ON THE
ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE WITH THE
MECHANICAL CONTRACTOR TO DETERMINE THE EXACT LOCATION OF EACH
PIECE OF EQUIPMENT AND DETERMINE THE EXACT ROUGH-IN AND CONNECTION
REQUIREMENTS.
WORKING CLEARANCE: COORDINATE FINAL LOCATIONS OF ELECTRICAL
EQUIPMENT WITH MECHANICAL DUCTWORK, PIPING ETC. AND ASSURE WORKING
CLEARANCE REQUIRED BY NEC WILL BE MET. SUFFICIENT ACCESS AND WORKING
SPACE MUST BE PROVIDED AND MAINTAINED AROUND ELECTRICAL EQUIPMENT
AS REQUIRED BY THE NATIONAL ELECTRICAL CODE. CONTRACTOR MUST
COORDINATE FINAL LOCATION OF EQUIPMENT PROVIDED AND INSTALLED BY
OTHER TRADES.
STARTER MOUNTING: WHERE AN INDIVIDUALLY MOUNTED SAFETY SWITCH,
STARTER OR CIRCUIT BREAKER IS SHOWN ADJACENT TO ITS RESPECTIVE LOAD
AND NOT MOUNTED ON A WALL, PROVIDE ALL SUPPORTS, BRACKETS,
ANCHORING, ETC. NECESSARY TO PROPERLY SUPPORT THE DEVICE.
LIGHTING ARRANGEMENT: ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH
THE ARCHITECTURAL REFLECTED CEILING PLANS.
LIGHTING COORDINATION: COORDINATE LIGHTING FIXTURES WITH GRILLES,
DIFFUSERS, SPRINKLER HEADS, AND ACCESS PANELS, ETC. PROVIDE FIXTURE
MOUNTING BRACKETS, ACCESSORIES, PLASTER FRAMES, ETC.. SUITABLE FOR
THE CEILING TYPES INDICATED ON THE ARCHITECTURAL PLANS.
LIGHTING CONTROL TESTING: UPON COMPLETION OF THE INSTALLATION OF ALL
LIGHTING SYSTEMS AND CONTROL DEVICES, CONTRACTOR MUST CONFIRM
PROPER OPERATION OF ALL LIGHTING CONTROLS, AND DEMONSTRATE PROPER
OPERATION TO THE CONTRACTING OFFICER.
MATERIAL COORDINATION: VERIFY CEILING AND WALL CONSTRUCTION AND
MATERIAL PRIOR TO ORDERING LIGHT FIXTURES OR OTHER DEVICES TO INSURE
PROPER FIXTURE OR DEVICE IS FURNISHED TO MATCH CONSTRUCTION.
MOUNTING HEIGHTS: MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHED
FLOOR TO THE CENTERLINE OF THE WIRING DEVICE UNLESS OTHERWISE NOTED.
MOUNTING HEIGHTS OF LIGHTING FIXTURES ARE TO THE BOTTOM OF THE
FIXTURE UNLESS OTHERWISE NOTED.
DEVICE LOCATIONS: COORDINATE LOCATIONS OF SWITCHES, RECEPTACLES,
AND TELE/DATA OUTLETS WITH OTHER WALL MOUNTED DEVICES SUCH AS
THERMOSTATS AND CONTROL STATIONS.
EWC RECEPTACLES: RECEPTACLES FOR ELECTRIC WATER COOLERS (EWC)
MUST BE INSTALLED OUT OF VIEW AND BEHIND THE EWC ENCLOSURE. VERIFY
THE MOUNTING HEIGHT WITH THE EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.
DEVICE COORDINATION: THOROUGHLY REVIEW AND COORDINATE ALL
CASEWORK AND CABINET DRAWINGS AND ARCHITECTURAL ELEVATIONS WITH
DEVICE LOCATIONS PRIOR TO ROUGH-IN OF OUTLET BOXES.
MULTI-GANG JUNCTION BOXES: WHERE OUTLETS AND SWITCHES ARE SHOWN
ON PLAN TO BE INSTALLED ADJACENT TO EACH OTHER AND AT THE SAME
MOUNTING HEIGHT, THE DEVICES MUST BE INSTALLED IN A MULTI-GANG
OUTLET BOX, UON. THE SIZE OF THE OUTLET BOX MUST BE DETERMINED BY
THE NUMBER OF DEVICES AND CONDUCTORS THAT MUST BE INSTALLED IN
THE MULTI-GANG OUTLET BOX.
BARRIERS: WHERE A MULTIPLE-GANG BOX HAS CIRCUITS OF DIFFERENT
VOLTAGES OR SYSTEMS WHICH ARE REQUIRED TO BE SEPARATED, PROVIDE THE
CODE-REQUIRED SEPARATION USING A FULL HEIGHT AND DEPTH BARRIER PLATE.
FIRE STOPPING: FOR ANY WALL OR FLOOR PENETRATIONS THROUGH
FIRE-RATED STRUCTURES PROVIDE FIRE-STOPPING TO SEAL ALL THE
PENETRATIONS AFTER THE CONDUIT HAS BEEN INSTALLED. FIRE STOPPING FOR
PENETRATIONS MUST BE UL APPROVED PER THE PENETRATION MADE IN ORDER
TO MAINTAIN FIRE-RATED INTEGRITY OF THE STRUCTURE.
CLEAN UP: ON PROJECT CLOSE-OUT CLEAN ALL ELECTRICAL DEVICES, LIGHTING
FIXTURES, LENSES, AND REMOVE ALL PAINT SPATTERS FROM DEVICES,
FIXTURES AND PLATES. REPAIR ALL INOPERATIVE LIGHTING FIXTURES.
GROUND FAULT PROTECTION: RECEPTACLES LOCATED WITHIN 6'-0" OF THE
EDGE OF SINKS MUST BE PROVIDED WITH GROUND FAULT PROTECTION
WHETHER SHOWN OR NOT.
FIRE ALARM COORDINATION: THE ELECTRICAL CONTRACTOR MUST COORDINATE
WITH THE FIRE ALARM SYSTEM PROVIDER AND PROVIDE POWER CONNECTIONS
TO ALL COMPONENTS WHETHER SHOWN OR NOT. MANUFACTURERS REQUIRE
VARYING QUANTITIES OF POWER CONNECTIONS FOR EQUIPMENT LIKE
EXPANDER PANELS AND POWER SUPPLIES. THESE DEVICES ARE DEPENDENT
UPON THE SPECIFIC MANUFACTURERS SYSTEM. THE FIRE ALARM SYSTEM
SUPPLIER MUST NOTIFY THE OTHER APPROPRIATE SUB-CONTRACTORS ABOUT
THESE REQUIREMENTS AND CONNECTION MUST BE PROVIDED AS PART OF THE
PROJECT.
HVAC DAMPERS, ETC: CONTRACTORS MUST COORDINATE WITH THE EQUIPMENT
AND SYSTEM BEING PROVIDED AND PROVIDE POWER CONNECTIONS
ACCORDINGLY. THESE CONNECTIONS MUST BE FOR FIRE/SMOKE DAMPERS, DDC
CONTROL DEVICES, ETC. CONTRACTOR MUST COORDINATE THE VOLTAGE
REQUIREMENTS AND PROVIDE ALL NECESSARY CONNECTIONS, COMPONENTS,
ETC. THIS INCLUDES TRANSFORMERS, BOXES, ETC.
CEILING PLENUM: THE CEILING SPACE IS A RETURN AIR PLENUM. ALL LOW
VOLTAGE CABLE MUST BE PLENUM RATED. REFER TO NEC ART. 300.22 FOR
PROVISIONS APPLICABLE TO PLENUMS.
THE FOLLOWING SUBSCRIPTS MUST APPLY TO RECEPTACLES WHERE USED:
DETAIL OR SECTION NOTATION
CEILING MOUNTED DUAL TECHNOLOGY ULTRASONIC/PASSIVE INFRARED VACANCY
SENSOR.
WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR WITH SINGLE POLE
SWITCH, 120/277V, MOUNT 46"AFF.
HEAT TAPE CONNECTION, CLASS B GFI DEVICE WITH PUSH TO TEST AND RESET
BUTTONS WITH WEATHER PROOF COVER. CONNECT AHEAD OF HEAT TRACE
THERMOSTAT.
CONTRACTOR MUST PROVIDE AN APPROPRIATE LISTED THROUGH-PENETRATION FIRE STOPPING ASSEMBLY AT EACH PENETRATION OF FIRE RATED CONSTRUCTION (I.E. WALLS AND SLABS, ETC.). SLEEVES MUST ONLY BE PERMITTED WHERE INDICATED IN THE CONTRACTOR SELECTED THROUGH-PENETRATION FIRE STOPPING ASSEMBLY. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION OF ALL RATED ASSEMBLIES AND ASSOCIATED UL DESIGNATIONS. DEVICES INSTALLED RECESSED WITHIN FIRE RATED CONSTRUCTION (I.E. LIGHT SWITCHES, RECEPTACLES, ETC.) ARE ONLY PERMITTED WHEN AN APPROVED LISTED FIRE STOPPING SYSTEM EXISTS FOR THE APPLICATION. IF AN APPROVED LISTED FIRE STOPPING SYSTEM IS UNAVAILABLE, THE CONTRACTOR MUST BRING THE CONDITION TO THE ATTENTION OF THE GOVERNMENT FOR RESOLUTION PRIOR TO PROCEEDING WITH WORK.
GENERAL ELECTRICAL NOTES ELECTRICAL LEGEND
AND
SWITCH RATING
NUMBER OF POLES
FUSE RATING (NF INDICATES NON-FUSED)
NEMA ENCLOSURE IF OTHER THAN NEMA 1
ENUMERATION: A = DETAIL, 1 = SECTION
SHEET WHERE SECTION IS SHOWN
SHEET WHERE SECTION IS CUT
1 HOUR FIRE RATED WALL
2 HOUR FIRE RATED WALL
SPD
A
D
TC
P
V
O
GFI
E J
M
DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, 18" AFF, UON
TWO DUPLEX RECEPTACLES IN COMMON BOX, EACH 20A, 120V, 18" AFF, UON
DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, 46" AFF, UON (OR 6" ABOVE
COUNTER AS APPLICABLE)
TAMPER PROOF/ARC FAULT DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, 18"
AFF, UON.
· GFI: GROUND FAULT INTERRUPTING TYPE RECEPTACLE
· +XX": DEVICE MOUNTING HEIGHT DESIGNATION ABOVE FINISHED FLOOR IF OTHER
THAN 18" OR 46".
· WP: WEATHER RESISTANT GFI RECEPTACLE WITH WEATHERPROOF WHILE-IN-USE
COVER.
· EWC: ELECTRIC WATER COOLER RECEPTACLE, PROVIDE GROUND FAULT INTERRUPTING
TYPE BREAKER. LOCATE BEHIND THE EWC PER MANUFACTURER'S
RECOMMENDATIONS.
ABBREVIATIONS
A AMPERE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
BFG BELOW FINISHED GRADE
C CONDUIT
CB CIRCUIT BREAKER
DDC DIRECT DIGITAL CONTROL
DSS DUCTLESS SPLIT SYSTEM
EBU EMERGENCY BATTERY UNIT
EC EMPTY CONDUIT
EF EXHAUST FAN
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
GFI GROUND FAULT INTERRUPTER
GND GROUND
HP HORSE POWER/HEAT PUMP
KAIC THOUSAND AMPERE
INTERRUPTING CAPACITY
KVA KILO-VOLT-AMPERES
KW KILO-WATTS
LPW LUMENS PER WATT
LTG LIGHTING
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MFR MANUFACTURER
MLO MAIN LUGS ONLY
MTD MOUNTED
NEC NATIONAL ELECTRICAL CODE
NF NON-FUSED
NTS NOT TO SCALE
P POLE
Ø PHASE
PRI PRIMARY
RECEPT RECEPTACLE
REQ'D REQUIRED
SE SERVICE ENTRANCE
SEC SECONDARY
SPD SURGE PROTECTION DEVICE
TBB TELEPHONE BACKBOARD
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
W WATTS/WIRE
WP WEATHERPROOF
FLOOR MOUNTED DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, UON.
VFD
CEILING MOUNTED DUAL TECHNOLOGY ULTRASONIC/PASSIVE INFRARED
OCCUPANCY SENSOR.
OC
.47
X X
.47
X X
OSX X
OSX X
OS
X
X
OSLX
XOSLX
X
OS
L
X X
OS
L
X X
6 7
US
US
US
US
US
US
US
12.47 / OSL 12.4712.47 / OSL 12.47 / OSL 12.47 / OSL
OS
L
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
NELECTRICAL SITE PLAN - DEMOLITION
SCALE: 1" = 20'-0"
REMOVE EXISTING OVERHEAD PRIMARY TAP, SITE LIGHTING
FIXTURE AND CROSS ARMS.
REMOVE EXISTING POLE, POLE MOUNTED TRANSFORMER, SITE
LIGHTING FIXTURE, GUYS AND OVERHEAD CONDUCTORS.
REMOVE EXISTING SERVICE POLE, POLE MOUNTED METER BASE,
SITE LIGHTING FIXTURE, OVERHEAD CONDUCTORS AND
OVERHEAD TO UNDERGROUND TRANSITION.
REMOVE EXISTING POLE, OVERHEAD TO UNDERGROUND
TRANSITIONS, GUYS AND LIGHT FIXTURE.
REMOVE EXISTING UNDERGROUND SERVICE CONDUCTORS FROM
POLE TO BUILDING.
REMOVE POLE, SITE LIGHTING FIXTURE AND OVERHEAD SITE
LIGHTING CIRCUIT.
REMOVE EXISTING SITE LIGHTING FIXTURE AND OVERHEAD SITE
LIGHTING CIRCUIT.
BUILDING TO BE DEMOLISHED IN ITS ENTIRETY.
NOTES THIS SHEET
PT
EXISTING POLE
UG TERM (15KV)
CONDUIT RISER (6", PVC), TYPE C
GROUND
SPARE
PRIMARY IN DUCT
UP
UP
UP
UP
USPANEL MDP
PANEL ALA
SPARE
SECONDARY
IN DUCT
12.47 / OSL
OSL
ALA-7 VIA LIGHTING
CONTACTOR
ALA-9 VIA LIGHTING
CONTACTOR
ALA-11 VIA LIGHTING
CONTACTOR
L L L
L
L
LLL
M M M
L
L
T
12.47 / OSL 12.47 / OSL 12.47 / OSL
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
NELECTRICAL SITE PLAN - NEW WORK
SCALE: 1" = 20'-0"
SITE PLAN LEGEND
US
UP
UNDERGROUND SECONDARY CIRCUIT
UNDERGROUND PRIMARY CIRCUIT
E12.47 EXISTING OVERHEAD PRIMARY CIRCUIT; 12.47 KV
ALUMINUM, BARE, 6201 ALLOY, 19 STRAND, 394.5 KCMIL, CODE
NAME CANTON
PAD MOUNTED TRANSFORMER
FRONT
T
EXISTING POLE
PANELBOARD - 208/120V, 3 PHASE, 4 WIRE
PRIMARY ONE-LINE DIAGRAM
NOT TO SCALE
PAD MOUNTED
TRANSFORMER: 150 KVA,
12.47 KV TO 208/120 V, 3
PHASE, 4 WIRE
E12.47
UP 3 #2 EPR 15KV, 133% INSULATION & 1 #2 COPPER
CONCENTRIC NEUTRAL IN 5" PVC CONDUIT AND
ONE 5" PVC SPARE CONDUIT CONCRETE
ENCASED. SEE CONCRETE ENCASED DUCTBANK
- DETAIL 'A' SHEET ES502.
FUSED CUTOUTS: 100A
EOP 7.2 REMOVE EXISTING OVERHEAD PRIMARY, 7.2 KV, SINGLE PHASEX X
EXISTING POLE MOUNTED TRANSFORMER
EXISTING POLE GUY
POLE MOUNTED SURGE ARRESTOR WITH GROUND.
1 TAP EXISTING OVERHEAD PRIMARY, TRANSITION UNDERGROUND AND
EXTEND AS INDICATED.
NOTES THIS SHEET
PRIMARY TAP BOX
OS
OSL
OVERHAED SECONDARY CIRCUIT
OVERHEAD SITE LIGHTING CIRCUIT
PT PRIMARY TAP BOX
SEE POWER RISER DIAGRAM SHEET E-601
FOR ADDITIONAL INFORMATION
PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
POLE LINE MATERIAL LIST
FLAT STEEL BRACE (TWO PIECES)
MACHINE BOLT, 3/8" X LENGTH NEEDED WITH WASHER, NUT AND LOCKWASHER
8' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 3 1/2" X 4 1/2"
MACHINE BOLT, 5/8" X LENGTH NEEDED WITH WASHER, NUT AND LOCKWASHER
TIMBER CONNECTOR
LAGSCREW, 1/2" X 4"
ANGLE STEEL BRACE (TWO PIECES)
MACHINE BOLT, 1/2" X LENGTH NEEDED, WITH WASHER, NUT & LOCKWASHER
DEADEND BOX
STEEL PIN
PIN INSULATOR
GRID GAIN, USED ONLY WHEN THERE IS NO POLE GAIN
ANGLE STEEL BRACE (ONE PIECE)
10' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 3 1/2" X 4 1/2"
5/8" EYE NUT
5/8" EYE BOLT, LENGTH AS NEEDED, WITH WASHER, NUT & LOCKWASHER
EXTENSION LINK
BELL TYPE SUSPENSION INSULATOR WITH CONNECTING HARDWARE
STRAIN CLAMP
STEEL ANGLE PIN
CLUSTER MOUNTING BRACKET, STEEL
TRANSFORMER GROUNDING CONNECTION
STIRRUP
SECONDARY LEAD SUPPORT BRACKET
ADAPTER PLATE FOR CLUSTER MOUNTING
CLEVIS BRACKET FOR SPOOL INSULATOR
SPOOL INSULATOR
U BOLT CLAMP
PREFORMED GUY GRIP
GUY HOOK
GUY STRAIN INSULATOR
GUY WIRE, SIZE AS SPECIFIED
#4 WP CU. SOFT DRAWN GROUND WIRE
GROUND CLAMP
CONDUIT COUPLING
CONDUIT BEND
INSULATED BUSHING
PERFORATED STRAPPING, 1-1/2" WIDE
HOT LINE CLAMP
FUSED CUTOUT, AS SPECIFIED
SURGE ARRESTER, AS SPECIFIED
POLE TOP PIN (RIDGE PIN) - 24 INCHES LONG
CROSSARM ANGLE PIN
ANGLE POLE TOP PIN
WEATHERPROOF SOFT DRAWN WIRE-SIZE
T0 MATCH OR EXCEED AMPACITY OF CONNECTING
CABLE, OR
AT 125% OF TRANSFORMER FULL LOAD
CURRENT, BUT NOT LESS THAN NO. 4 AWG
(a)
(b)
OH-1.5JUNE 2002SKETCH DATE STYLE
POLE LINE MATERIAL LIST
UNDERBUILD CIRCUIT
POSITION OF COMMON NEUTRAL
OR MULTIPLEX SECONDARY
CONDUCTOR
CIRCUITCOMM.
PROVIDE 60" CLEARANCE WHEN OPERATING VOLTAGE OF UNDERBUILD
CIRCUIT IS GREATER THAN 15KV.
NOTE
FOR HORIZONTAL SPACING REQUIREMENTS FOR CONDUCTORS ON SAME SUPPORT,
REFER TO THE NATIONAL ELECTRICAL SAFETY CODE, IEEE C2.
1.
Ø-Ø VOLTAGE 0-15KV 15-50KV
SPACING A"
SPACING B"
40"
40"
48"
40"
OH-1.4JUNE 2002SKETCH DATE STYLE
BASIC VERTICAL SPACING REQUIREMENTS
"B"
"A"
40" MIN.
DEDICATED
CLEAR SPACE
POSITION OF LOWEST POWER (SUPPLY)
ATTACHMENT SHALL BE NO LESS THAN
24'-4" ABOVE GRADE.
DEDICATED CLEAR SPACE BETWEEN
POWER (SUPPLY) AND COMMUNICATION
CIRCUITS.
POSITION OF HIGHEST
COMMUNICATION ATTACHMENT
SHALL BE NO HIGHER THAN
21'-0" ABOVE GRADE.
EXPLANATION OF SYMBOLS LISTED FOR POLE ON SKETCH OH-1.3
EXPLANATORY NOTES - METHOD OF SHOWING SYMBOLS
SYMBOLS ARE SHOWN IN THE BASIC ORDER AS THEY APPEAR ON THE
POLE, BY STARTING AT THE TOP AND WORKING DOWN.
NUMERALS PRECEDING THE SYMBOL INDICATE THE MINIMUM REQUIRED
VOLTAGE (KV) RATING (5,15,35) OF THE ASSEMBLY, IF APPLICABLE.
NUMERAL FOLLOWING THE SYMBOL INDICATES THE NUMBER OF CON-
DUCTORS ASSOCIATED WITH THE ASSEMBLY, IF APPLICABLE.
NUMERAL IN PARENTHESIS FOLLOWING THE SYMBOL DENOTES THE
NUMBER OF ASSEMBLIES REQUIRED, IF MORE THAN ONE.
DATA IN PARENTHESIS FOLLOWING THE SYMBOL PROVIDES
INFORMATION RELATIVE TO THE SYMBOL.
1.
2.
3.
4.
5.
PROVIDE 45 FOOT LONG, CLASS 3 POLE CONTAINING:
TF -
S1 -
SDE2 -
GROUND -
X-FB -
35FR3 -
X-FB -
15F3 -
8' CROSSARM WITH FLAT BRACE
35KV INSULATORS, FLAT (MOUNTED HORIZONTAL ON CROSS-
ARM), RIDGE PIN (CENTER PHASE ON POLE TOP PIN), THREE
CONDUCTORS
8' CROSSARM WITH FLAT BRACE
15KV INSULATORS, FLAT (MOUNTED HORIZONTAL ON CROSSARM),
THREE CONDUCTORS. NOTE: THIS SYMBOL CALLS FOR THREE
CROSSARM MOUNTED PINS IN LIEU OF RIDGE PIN ON CENTER
PHASE.
TRANSFORMER ON FLAT (HORIZONTAL) CONSTRUCTION. DATA
IN PARENTHESIS DESCRIBES THE TRANSFORMER CHARACTERISTICS.
GUY (5/16") -
SECONDARY, ONE CONDUCTOR, TANGENT CONSTRUCTION (COMMON
NEUTRAL).
SECONDARY DEADEND, TWO CONDUCTORS, OPEN WIRE
DOWN GUY - WIRE SIZE 5/16"
10" SCREW TYPE ANCHOR WITH 12 FT. GUY LEAD.
NOTE: NO PLATE IS INCLUDED FOR THE ANCHOR SYMBOL.
NO EXPLANATION NECESSARY
ANCHOR -
(10" SCREW)
OH-1.3AJUNE 2002SKETCH DATE STYLE
EXPLANATION OF NOTES/SYMBOLS
13.2 34.5
S N
13.2
N 34.5
PLAN VIEW
POLE # (45'-3)
X-FB, 35FR3
X-FB, 15F3
TF (25KVA, 13.2 GRD. Y/7.6 KV - 120/240 V.)
S1, SDE2
GUY (5/16")
ANCHOR (10" SCREW) (12' GUY LEAD)
GROUND
NOTES
THE SYMBOLS LISTED ABOVE
INCLUDE MATERIALS (DESCRIBED
BY OVERHEAD SKETCHES) WHICH
ARE GRAPHICALLY ILLUSTRATED
BY THIS PICTURE. SEE
SKETCH OH-1.3A FOR
EXPLANATORY NOTES.
EACH SKETCH CONTAINS
MATERIAL ITEMS WHICH COMPRISE
A PART OF EACH INDIVIDUAL
SYMBOL REFERENCED BY THAT
SKETCH, THESE ITEMS ARE
INDICATED BY CIRCLED
NUMERALS WHICH ARE IDENTIFIED
BY SKETCHES OH-1.5
AND OH-1.5A.
SPACING REQUIREMENTS RELATED
TO INDIVIDUAL COMPONENTS OF
A SYMBOL ARE INDICATED ON
THE APPROPRIATE SKETCH.
VERTICAL SPACING
REQUIREMENTS BETWEEN
CIRCUITS AND/OR SYSTEMS
ARE INDICATED ON SKETCH
OH-1.4. ALL OTHER
SEPARATIONS BETWEEN
CIRCUITS, EQUIPMENT, ETC.,
SHALL CONFORM TO THE
NATIONAL ELECTRICAL
SAFETY CODE, IEEE C2.
1.
2.
3.
OH-1.3JUNE 2002SKETCH DATE STYLE
METHOD OF SHOWING SYMBOLS
POLE LINE MATERIAL LIST
TRI-MOUNT BRACKET
TERMINATOR
MOUNTING BRACKET
CABLE GRIP HANGER
HOSE CLAMP
STUD, 3/4" X 1-3/4"
LINE POST INSULATOR
TRIPLE INSULATOR BRACKET
ANGLE CLAMP
INSULATOR, LINE POST CLAMP
4' CROSSARM
CROSSARM GAIN BRACKET
PULLEY BRACKET
WEDGE CLAMP
MIDSPAN SERVICE CLAMP
STUD, 7"
SADDLE, ANGLE
SADDLE CROSSARM
FITTING, POLE TOP
CONNECTOR
SUSPENSION CLAMP
TIE, SERVICE CABLE
54" FIBERGLASS STRAIN INSULATOR
69 PVC RISER SHIELD
PVC EXTENSION SHIELD
PVC BACK PLATE
72 8' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 4 3/4" X 5 3/4"
73 10' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 4 3/4" X 5 3/4"
OH-1.5AJUNE 2002SKETCH DATE STYLE
POLE LINE MATERIAL LIST
BACK-UP CURRENT LIMITING FUSE74
ATTACHMENT
POSITION OF GUY
SEE NOTE 3
SIDE VIEW FRONT VIEW
THIS POLE.
CONTINUES ON BEYOND
NEUTRAL LEVEL, IF
POLE
DEADENDS ON THE
NEUTRAL LEVEL, IF
NOTES
1.
2.
3.
23 39
41 48 41 48
16" 2"
4"
40"
21"
24"
19"36"
OH-31JUNE 2002
(0-25KV)
U.G. TERMINAL
SKETCH DATE STYLE
MODIFY POSITION OF TERMINAL ON DEADENDS TO BE UNDER THE CONDUCTORS AND THE CUTOUTS ON THE BACKSIDE OF
CROSSARM. POLE RISER MUST BE OFFSET TO CLEAR NEUTRAL CLEVIS BRACKET.
CONNECT BOTTOM LEAD OF ARRESTER DIRECTLY TO POLE GROUND. INTERCONNECT CABLE INSULATION SHIELD DRAIN WIRES AND CONDUIT RISER GROUND TO MULTI- GROUNDED NEUTRAL (IF EXISTING) AND POLE GROUND.
CUTOUT PROVIDES A FUSE OR A SOLID BLADE (NON-FUSED) OPTION. COORDINATE
WITH SPECIFIC DESIGN REQUIREMENTS PROVIDED.
TOP VIEW 19 IN
4 IN
POLE AS
INDICATED
36.5 IN
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-CAST ALUMINUM OR DIE-CAST AND EXTRUDED ALUMINUM WITH INTEGRAL,
SELF-CLEANING HEAT SINK FINS, RIBS, OR EQUIVALENT PASSIVE COOLING MECHANISM.
HEAT SINK SHALL BE INCORPORATED DIRECTLY INTO HOUSING TO ENSURE MAXIMUM HEAT
TRANSFER AND DISSIPATION.
2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED WITH BAKED-ON POLYESTER POWDER
COAT. FINISH SHALL PASS 2500 HOUR SALT SPRAY TEST PER ASTM B117. FINISH COLORS
INCLUDE DARK BRONZE, SILVER, OR BLACK WITH CUSTOM COLORS AVAILABLE.
3. POWER SUPPLY/LED DRIVER - PROVIDE IN SEPARATE COMPARTMENT ACCESSIBLE WITHOUT
THE USE OF HAND TOOLS. CLASS 1 DRIVER SHALL OPERATE AT 120/277V, 50/60 HZ; OTHER
VOLTAGES OPTIONAL. POWER FACTOR GREATER THAN 0.9 AND THD LESS THAN 20% AT FULL
LOAD. MINIMUM EFFICACY SHALL BE 60 LM/W AT MAXIMUM 600 mA OPERATING CURRENT.
4. LED OPTICAL ASSEMBLY - NUMBER OF LED ARRAYS SHALL VARY TO ACCOMMODATE
DESIRED LUMINAIRE OUTPUT. PROVIDE WITH EQUIVALENT NEMA TYPE III, IV OR V
DISTRIBUTION AS INDICATED. BUG UPLIGHT RATING OF U0, WITH BACKLIGHT AND GLARE
RATINGS AS DETERMINED BY LIGHTING ZONE INSTALLED. MINIMUM COLOR RENDERING
INDEX (CRI) SHALL BE 70 FOR CORRELATED COLOR TEMPERATURE (CCT) OF 4000 K TO 4500
DEGREES K.
5. SURGE PROTECTION - 6 kV MINIMUM, COMPLIANT WITH ANSI C62.41.2.
6. CERTIFICATION - UL AND/OR ETL LISTED, MINIMUM IP65 RATED PER ANSI/IEC 60529, AND RoHS
COMPLIANT.
7. OTHER - THE ABOVE SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A
LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS AND IS NOT INTENDED TO
INDICATE A CERTAIN MANUFACTURER'S PREFERENCE. ALL DIMENSIONS ARE NOMINAL AND
VARY PER MANUFACTURER.
REVISED: MARCH 2013 XL-03LUMINAIRE PLATE:
LED AREA LUMINAIRE
OPTIONAL
PHOTOCELL
REVISED: MARCH 2013 XL-29LUMINAIRE PLATE:
ANCHOR BASE POLE FOUNDATION
APOLE
HEIGHT
8'-12'
13'-20'
21'-30'
36"
42"
B
12"
31'-40'
72"
78"
16"
24"
30"
"A"
4"
"B"
FINISHED GRADE
INSULATED COPPER GROUNDING
CONDUCTOR ATTACHED TO INTERNAL
LUG WELDED TO INTERIOR OF POLE. SIZE
PER NFPA 70.
CHAMFER ALL EDGES OF CONCRETE BASE
1/2"
HANDHOLE - SEE POLE SKETCH AND
SPECIFICATION
POLE - SEE POLE SKETCH AND
SPECIFICATION
CONDUIT STUBBED UP ADJACENT TO
HANDHOLE; NUMBER AND SIZE AS
REQUIRED
SET TOP OF CONCRETE
FOUNDATION 4" ABOVE
GRADE
COPPER EQUIPMENT
GROUNDING CONDUCTOR
- ATTACH TO INTERNAL
LUG WELDED TO INTERIOR
OF POLE. CONDUCTOR TO
BE SAME SIZE AND TYPE
AS SUPPLY PHASE
CONDUCTOR.
CIRCUIT CONDUCTORS AND
CONDUIT TO POWER
SOURCE OR NEXT POLE
CONCRETE PER
SPECIFICATION
CIRCUIT CONDUCTORS AND
CONDUIT TO POWER SOURCE
OR NEXT POLE
ANCHOR BOLTS AS
RECOMMENDED BY
MANUFACTURER OF POLE
#4 BARS VERTICAL AT 6" EACH
FACE
#3 BARS AT 12" ON CENTER
HORIZONTALLY
3/4" X 10' GROUND ROD
REVISED: MARCH 2013 XL-26LUMINAIRE PLATE:
ANCHOR BASE STEEL/ALUMINUM POLE
TAPERED OR STRAIGHT STEEL OR ALUMINUM POLE. CROSS SECTIONAL
SHAPE AND COLOR AS INDICATED.
NOTES:
COORDINATE TOTAL EPA WITH SPECIFICATIONS.
WIRING HANDHOLE MINIMUM 2 1/2" X 5" CLEAR OPENING WITH COVER AND
STAINLESS STEEL SCREWS.
INTERNAL GROUNDING LUG.
TERMINATE C0NDUITS INTERNALLY, ADJACENT TO HANDHOLE.
FULL BASE COVER - TW0 PIECE GALVANIZED STEEL.
CONCRETE FOUNDATION - SEE PLATE XL-29.
"U"
POLE
TYPE
TENON OPTION - 2-3/8" TENON WITH PROVISION
FOR WIRING. COORDINATE WITH LUMINAIRE.
XL-26
A
XL-26
B
XL-26
C
XL-26
D
XL-26
E
XL-26
F
XL-26
G
MAST ARM OPTION - COORDINATE WIRING AND BOLT HOLES
WITH MAST ARM PROVIDED.
DIM
1'-6"
"U"
9"
12"
L M
L
STYLE NO. & TYPE VOLTAGE MOUNTING NOTESFIXTURE
SYMBOL
NUMBER AND TYPE
OF LAMPS
SITE LIGHTING FIXTURE SCHEDULE
XL-03 (SINGLE) LED UNIVERSALPOLE,
PROVIDE POLE WITH SINGLE LIGHT FIXTURE, 11,676 LUMENS, 4000K COLOR, TYPE 3 DISTRIBUTION, DARK BRONZE FINISH.
POLE: XL-26 B, SQUARE, TAPERED, DARK BRONZE, ALUMINUM.
BASE: XL-29, TOP OF BASE TO BE 36" AFG.
PROVIDE POLE WITH FOUR LIGHT FIXTURES MOUNTED 90 DEGREES APART, 11,676 LUMENS, 4000K COLOR, TYPE 3
DISTRIBUTION, DARK BRONZE FINISH.
POLE: XL-26 B, SQUARE, TAPERED, DARK BRONZE, ALUMINUM.
BASE: XL-29, TOP OF BASE TO BE 36" AFG.
2M XL-03 (QUAD) LED UNIVERSALPOLE
| 60025690 |
| Sheets and Views |
| M-704 MECHANICAL CONTROLS |
| 60025691 |
| 60025692 |
| 60025693 |
| 60025694 |
| 60025695 |
| 60025696 |