N4008519B0095 Drawings_Part7.pdf

PDF 7 MB Posted

Attached to
Building 17 and 17A Renovation and Addition
Solicitation number
N6247020R6000
Issued by

View the file

Other files

File Type Posted
Large Cabinet.jpg JPG image
Tabernacle.jpg JPG image
08 62 00 Translucent Wall Panels.pdf PDF
Organ (2).jpg JPG image
Grand Piano.jpg JPG image
Baptismal Font.jpg JPG image
Organ (1).jpg JPG image
Altar (2).jpg JPG image
Amnd 0006 20R6000 Final.pdf PDF
Altar (1).jpg JPG image
Amnd 0005 20R6000 Final.pdf PDF
Amnd 0004 20R6000 Final.pdf PDF
Amnd 0003 20R6000 Final.pdf PDF
Amnd 0002 20R6000 Final.pdf PDF
NAVFAC DWG 60025678.pdf PDF
NAVFAC DWG 60025676.pdf PDF
Amend 0001 20R6000.pdf PDF
N4008519B0095 Drawings_Part8.pdf PDF
N4008519B0095 Drawings_Part3.pdf PDF
N4008519B0095 Drawings_Part6.pdf PDF
N4008519B0095 Specs.pdf PDF
19-0095 Asbestos Survey 011020.pdf PDF
N4008519B0095 Drawings_Part2.pdf PDF
N4008519B0095 Drawings_Part5.pdf PDF
RFP N62470-20-R-6000.pdf PDF
N4008519B0095 Drawings_Part1.pdf PDF
19-0095 Lead Survey 011020.pdf PDF
N4008519B0095 Drawings_Part4.pdf PDF
N4008519B0095 Drawings_Part9.pdf PDF
Master PPI Form Template.xls XLS spreadsheet
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

02/24/2020

The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

HOT WATER COIL

FROM VARIABLE

FREQUENCY DRIVE

FREEZESTAT

AIR

OPPOSED

DAMPER

BLADE

FILTER

OUTSIDE

NC

OPPOSED

DAMPER

BLADE

CW

R

NO

HW

R

HW

S

CW

S

NC

SET AT

5" WG

CHILLED WATER COIL

SUPPLY FAN

M

PRIMARY

AIR

INPUTS

DI

GI

TA

L

HW VALVE CONTROL

CW VALVE CONTROL

A02

AO1

OUTPUTS

A03AN

AL

OG

SUPPLY AIR FAN STATUS

SMOKE DETECTOR

FREEZESTAT

MIXED AIR TEMPERATURE

SUPPLY AIR TEMPERATURE

HW COIL DISCHARGE AVERAGE

UNIT DISCHARGE STATIC PRESSURE

SA DOWN DUCT PRESSURE TRANSMITTER

AI4

AI5

DI1

DI3

DI2

AI2

AI1

AI3

AN

AL

OG

LOCAL DDC CONTROLLER

AHU

OA AIRFLOW MEASURE MOUNT STATIONAI6

A04 OUTSIDE AIR DAMPER CONTROL

AO1

AO4

DM

DM

AMSAI6

AI1

TS FS DI3

AO2

TS

AI3

AO3 AI2

VFD TS SPS

AI4 AI5

SPS

DI1

DPS

NO

LOCATE AT 2/3 DOWN

DUCT FROM AHU

AI7

CONDENSATE HI-LEVELDI4DI4

LS

RA TEMPERATUREAI8

AI8 TS

AI7 HS

PROVIDE 3-WAY CONTROL VALVE. SEE VFD CONTROL

DIAGRAM

AIR

RETURN

RA HUMIDITY

RETURN AIR DAMPER CONTROL

SINGLE ZONE VAV AHU-1 CONTROL DIAGRAM (DDC)

SCALE: NO SCALE M-704A

SEQUENCE OF OPERATION

BUILDING AUTOMATION SYSTEM INTERFACE:

THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE DDC CONTROLLER

OCCUPIED, UNOCCUPIED, OPTIMUM START, NIGHT HEAT/COOL, AND TIMED

OVERRIDE COMMANDS. THE BAS SHALL ALSO SEND SPACE TEMPERATURE

SETPOINT TO THE CONTROLLER. IF COMMUNICATION IS LOST WITH THE BAS, THE

CONTROLLER SHALL OPERATE IN THE OCCUPIED COOLING MODE USING ITS

DEFAULT SPACE TEMPERATURE SETPOINT.

SUPPLY FAN:

THE SUPPLY FAN SHALL BE OFF IN UNOCCUPIED MODE. WHEN THE CONTROLLER IS

IN THE OCCUPIED MODE, THE SUPPLY FAN SHALL BE ENABLED. IF THE SUPPLY FAN

FAILS TO PROVE STATUS FOR 30 SECONDS (ADJ), THE FAN SHALL BE COMMANDED

OFF, THE OUTDOOR AIR DAMPER SHALL BE CLOSED, COOLING/HEATING SHALL BE

DISABLED, AND AN ALARM SHALL BE SENT TO THE BAS. A MANUAL RESET SHALL BE

REQUIRED TO RESTART THE FAN.

HEATING/COOLING MODE:

WHEN THE SPACE TEMPERATURE RISES ONE DEGREE (ADJ) ABOVE THE OCCUPIED

COOLING SETPOINT, THE MODE SHALL TRANSITION TO COOLING. WHEN THE SPACE

TEMPERATURE FALLS ONE DEGREE (ADJ) BELOW THE OCCUPIED HEATING

SETPOINT, THE MODE SHALL TRANSITION TO HEATING. WHEN THE SPACE

TEMPERATURE IS BETWEEN ONE DEGREE (ADJ) ABOVE THE OCCUPIED COOLING

SETPOINT AND ONE DEGREE (ADJ) BELOW THE OCCUPIED HEATING SETPOINT, THE

MODE SHALL REMAIN IN ITS LAST STATE. IF THE SPACE TEMPERATURE INPUT FAILS,

THE MODE SHALL REMAIN IN ITS LAST STATE AND AN ALARM SHALL BE SENT TO

THE BAS. IF THE LOCAL (AND COMMUNICATED) SETPOINTS(S) FAIL, THE

CONTROLLER WILL USE ITS DEFAULT SETPOINTS AND AN ALARM SHALL BE SENT TO

THE BAS.

OCCUPIED MODE:

DURING OCCUPIED MODE, THE OUTDOOR AIR DAMPER SHALL BE OPEN AND THE SUPPLY

FAN SHALL OPERATE AND MODULATE ITS SPEED AS REQUIRED TO MEET THE SPACE

TEMPERATURE SETPOINT. ONCE THE SETPOINT HAS BEEN ACHIEVED, THE OUTDOOR AIR

DAMPER SHALL BE CLOSED AND THE SUPPLY FAN SHALL BE DISABLED.

COOLING MODE:

ON A RISE IN SPACE TEMPERATURE ABOVE THE SPACE COOLING SETPOINT S.P.

(ADJ) THE DDC CONTROLLER SHALL MODULATE THE CHILLED WATER VALVE TO

MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT, 55 DEGREES (ADJ). ON A

CONTINUED RISE IN SPACE TEMPERATURE ABOVE THE SPACE COOLING SETPOINT

(ADJ), ONCE THE CHILLED WATER VALVE IS FULLY OPEN, THE DDC CONTROLLER

SHALL SIGNAL THE SUPPLY FAN VFD TO MODULATE THE SUPPLY FAN SPEED UP TO

ITS MAXIMUM SETTING AS REQUIRED TO MAINTAIN THE SPACE TEMPERATURE

SETPOINT. ON A FALL IN SPACE TEMPERATURE, THE SUPPLY FAN SPEED SHALL BE

MODULATED BACK TO ITS MINIMUM SPEED SETTING. ON A CONTINUED FALL IN

SPACE TEMPERATURE BELOW THE SPACE TEMPERATURE SETPOINT, AND WHEN

THE SUPPLY FAN IS AT ITS MINIMUM SPEED, THE DISCHARGE TEMPERATURE

SETPOINT SHALL BE GRADUALLY RESET UP TO NEUTRAL SPACE TEMPERATURE, 75º

(ADJ).

HEATING MODE:

ON A FALL IN SPACE TEMPERATURE BELOW THE SPACE HEATING TEMPERATURE

SETPOINT (ADJ), THE DDC CONTROLLER SHALL MODULATE THE HOT WATER

RE-HEAT VALVE TO MAINTAIN DISCHARGE AIR TEMPERATURE TO THE SETPOINT OF

THE DDC CONTROLLER. ON A CONTINUED FALL IN SPACE TEMPERATURE BELOW

THE SPACE HEATING TEMPERATURE SETPOINT (ADJ), ONCE THE HOT WATER VALVE

IS FULLY OPEN, THE DDC CONTROLLER SHALL SIGNAL THE SUPPLY FAN VFD TO

MODULATE THE SUPPLY FAN SPEED UP TO ITS MAXIMUM SETTING AS REQUIRED TO

MAINTAIN THE SPACE SETPOINT. ON A RISE IN SPACE TEMPERATURE, THE SUPPLY

FAN SPEED SHALL BE MODULATED BACK TO ITS MINIMUM SPEED SETTING. ON A

CONTINUED RISE IN SPACE TEMPERATURE ABOVE THE SPACE HEATING SETPOINT,

AND WHEN THE SUPPLY FAN IS AT MINIMUM SPEED, THE DISCHARGE

TEMPERATURE SETPOINT SHALL BE GRADUALLY RESET UP TO NEUTRAL SPACE

TEMPERATURE, 75ºF (ADJ). THE DISCHARGE AIR SETPOINT SHALL BE INVERSELY

RESET FROM SPACE TEMPERATURE.

DEHUMIDIFICATION MODE:

ON A RISE IN SPACE RELATIVE HUMIDITY TO THE SETPOINT OF THE DDC

CONTROLLER, THE DDC CONTROLLER SHALL MODULATE THE CHILLED WATER

VALVE FULLY OPEN TO THE COIL. SHOULD THE DEHUMIDIFICATION PROCESS

CAUSE THE SPACE TO OVER COOL, THE DDC CONTROLLER SHALL MODULATE THE

REHEAT VALVE OPEN TO MAINTAIN THE SPACE HEATING TEMPERATURE SETPOINT.

MORNING WARM-UP:

DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS 1.5°F (ADJ) OR MORE

BELOW THE OCCUPIED HEATING SETPOINT, THE MORNING WARM-UP SEQUENCE

SHALL BE ACTIVATED. THE SUPPLY FAN SHALL START, THE HOT WATER VALVE

SHALL MODULATE OPEN, AND THE OUTDOOR AIR DAMPER SHALL REMAIN CLOSED.

MORNING WARM-UP MODE SHALL TERMINATE WHEN THE SPACE TEMPERATURE

REACHES THE OCCUPIED HEATING SETPOINT OR THE OCCUPIED TIME PERIOD HAS

STARTED.

MORNING COOL-DOWN:

DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS 1.5°F (ADJ) OR MORE

ABOVE THE OCCUPIED COOLING SETPOINT, THE MORNING COOL-DOWN SEQUENCE

SHALL BE ACTIVATED. THE SUPPLY FAN SHALL START, THE CHILLED WATER VALVE

SHALL MODULATE OPEN, AND THE OUTDOOR AIR DAMPER SHALL REMAIN CLOSED.

MORNING COOL-DOWN MODE SHALL TERMINATE WHEN THE SPACE TEMPERATURE

REACHES THE OCCUPIED COOLING SETPOINT OR THE OCCUPIED TIME PERIOD HAS

STARTED.

FREEZE PROTECTION:

IF HOT WATER COIL DISCHARGE AIR TEMPERATURE FALLS BELOW 40°F DURING

HEATING MODE, THE FREEZESTAT SHALL CLOSE THE OUTSIDE AIR DAMPER,

DE-ENERGIZE THE AHU SUPPLY FAN AND FULLY OPEN THE HOT WATER AND

CHILLED WATER VALVES TO COIL.

UNOCCUPIED MODE:

DURING UNOCCUPIED MODE THE DDC CONTROLLER SHALL CYCLE THE UNIT TO

MAINTAIN A REDUCED HEATING SETPOINT, 55ºF (ADJ), AND A RAISED COOLING AND

RELATIVE HUMIDITY SETPOINT, 85ºF/60% RH (ADJ), WHILE MAINTAINTING THE

OUTDOOR AIR DAMPER FULLY CLOSED.

SAFETY CONTROL:

SMOKE DETECTOR SHALL BE PROVIDED BY FIRE ALARM CONTRACTOR. THROUGH

DDC CONTROL IT SHALL DE-ENERGIZE THE ASSOCIATED AHU, SIGNAL FIRE ALARM

PANEL AND CLOSE THE OUTSIDE AIR DAMPER UPON THE DETECTION OF THE

PRODUCTS OF COMBUSTION.

ALARMS:

ALARM IF LEAVING AIR TEMPERATURE EXCEEDS 60°F IN COOLING MODE OR DROPS

BELOW 50°F IN HEATING MODE. ALARM IF AHU SUPPLY FAN FAILS TO START OR

FAILS DURING OPERATION. ALARM IF UNIT DISCHARGE STATIC PRESSURE EXCEEDS

5" W.G. ALARM IF CONDENSATE REACHES HIGH LEVEL. ALARM UPON SMOKE

DETECTOR ACTIVATION.

DEMAND CONTROL VENTILATION:

IF ANY SPACE CARBON DIOXIDE LEVEL FALLS BELOW SETPOINT (1,000 PPM, ADJ.),

THE OUTSIDE AIRFLOW RATE SHALL BE AT THE MINIMUM SCHEDULED VALUE AS

INDICATED IN THE EQUIPMENT SCHEDULE. AS LEVEL INCREASES ABOVE SETPOINT,

THE OUTSIDE AIR DAMPER SHALL PROPORTIONALLY MODULATE OPEN TO

GENERATE THE SCHEDULED MAX OUTSIDE AIRFLOW RATE OVER A 1 HOUR (ADJ.)

TIME PERIOD UNTIL THE LEVEL FALLS BELOW THE SETPOINT, AFTER WHICH THE

DAMPER POSITION SHALL RETURN TO MINIMUM.

DI2

SD

AI9

CO2

CO2 SENSORAI9

PUMP SHALL ENERGIZE DURING OCCUPIED HOURS. COORDINATE OCCUPIED HOURS WITH THE GOVERNMENT.

DI

GI

TA

L

PUMP ENABLE/DISABLEDO1

OUTPUTS

PUMP STATUS

DI

GI

TA

L

DI1

LOCAL DDC CONTROLLER

INPUTS

DOMESTIC WATER PUMP

SEQUENCE OF OPERATION

DO1

CSR DI1

DOMESTIC WATER PUMP CONTROL DIAGRAM (DDC)

SCALE: NO SCALE M-704B

PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

02/24/2020

ELECTRICAL DEMOLITION NOTES

GENERAL: DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELD INVESTIGATION PRIOR TO

DEMOLITION.

DASHED ITEMS: ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE EXISTING AND MUST BE REMOVED.

SOLID ITEMS: ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE EXISTING TO REMAIN.

CIRCUITING TO REMAIN: EXISTING CIRCUITING TO REMAIN MUST BE REROUTED OR RECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW WORK IN ORDER TO MAINTAIN CONTINUITY OF THE CIRCUIT.

REUSE OF EXISTING CIRCUITRY: EXISTING CIRCUITRY SERVING LIGHTING FIXTURES AND/OR RECEPTACLES FOR A GIVEN AREA MUST BE REUSED WHERE INDICATED TO SERVE THE NEW LAYOUT. PROVIDE CIRCUIT MODIFICATIONS INDICATED OR AS OTHERWISE REQUIRED TO MAINTAIN THE CONTINUITY OF EXISTING

CIRCUITS THAT REMAIN.

EXISTING CONDUIT: ALL EXISTING CONDUITS AND WIRING THAT WILL NOT BE REUSED MUST BE REMOVED WHERE THEY WILL BE EXPOSED UPON COMPLETION OF NEW WORK. EXISTING CONDUIT TO REMAIN CONCEALED IN WALLS MUST BE ABANDONED. EXISTING CONDUIT TO REMAIN BELOW FLOOR SLAB MUST BE CUT OFF ONE INCH BELOW ROUGH FLOOR AND GROUTED FLUSH. ALL EXISTING WIRING IN CONDUITS

TO BE ABANDONED MUST BE DISCONNECTED FROM POWER SOURCE AND REMOVED.

REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT NO ADDITIONAL COST TO THE OWNER, ANY DAMAGE CAUSED TO EXISTING CONSTRUCTION AND/OR EQUIPMENT TO REMAIN.

ASSOCIATED APPURTENANCES: REMOVE ALL ELECTRICAL APPURTENANCES (DISCONNECTS, STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH ITEMS TO BE REMOVED INCLUDING EQUIPMENT TO BE

REMOVED BY OTHERS.

KNOCKOUT PLUGS AND COVERS: ALL CONDUIT REMOVED MUST BE REMOVED IN ITS ENTIRETY, INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE, ETC. PROVIDE CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS CREATED BY THE REMOVAL OF CONDUIT. PROVIDE BLANK COVER PLATES FOR ALL OPENED

OUTLET BOXES CREATED BY THE REMOVAL OF EQUIPMENT AND/OR DEVICES

DEMOLISHED MATERIALS: ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR DESIGNATED TO BE TURNED OVER TO THE OWNER, MUST BECOME THE PROPERTY OF THE CONTRACTOR

AND MUST BE REMOVED COMPLETELY FROM THE SITE.

SCHEDULE OUTAGES: ALL WORK AND ALL POWER OUTAGES IN THE EXISTING BUILDING MUST BE

SCHEDULED AT TIMES CONVENIENT TO THE OWNER.

NOTIFICATION: NOTIFY THE CONTRACTING OFFICER PRIOR TO TURNING OFF ANY CIRCUITS.

ABANDONED COMMUNICATIONS CABLING: ABANDONED COMMUNICATIONS CABLING (TELEPHONE OR

DATA) ABOVE THE CEILING MUST BE REMOVED PER NEC ARTICLE 645.

LIGHTING FIXTURE

EMERGENCY LIGHTING FIXTURE WITH EMERGENCY BATTERY PACK - CONNECT

EMERGENCY PACK AHEAD OF LOCAL SWITCH.

DOWNLIGHT OR PENDANT MOUNTED FIXTURE

EXIT LIGHTING FIXTURE, WITH DIRECTIONAL ARROWS AS INDICATED WITH BATTERY

PACK - CONNECT AHEAD OF LOCAL SWITCH.

EMERGENCY BATTERY LIGHTING UNIT, CONNECT AHEAD OF LOCAL SWITCH.

LIGHTING FIXTURE TYPE SYMBOL. SEE LIGHTING FIXTURE DETAILS.

SINGLE POLE SWITCH, 20A, 120/277V, 46" AFF UON

THREE-WAY SWITCH, 20A, 120/277V, 46" AFF UON

DIMMER SWITCH, 46" AFF UON. FOR L.E.D. FIXTURES, COORDINATE VOLTAGE AND

RATINGS OF SWITCH WITH TYPE AND QUANTITY OF BALLASTS OR DRIVERS TO BE

CONTROLLED.

EQUIPMENT CONNECTION

JUNCTION BOX

MOTOR CONNECTION

SAFETY SWITCH, 60A-3P, FU @ 30A, 3R

MAGNETIC MOTOR STARTER, MOUNT WITHIN SITE OF MOTOR 5'-0" AFF MAX, UON.

ELECTRICAL PANELBOARD (208/120V, 3 PH, 4 WIRE)

ELECTRICAL CIRCUIT RUN IN CONDUIT AND CIRCUIT HOMERUN TO PANELBOARD

(PANEL AND CIRCUIT DESIGNATION AS INDICATED). AS A MINIMUM CONDITION, EACH

SINGLE PHASE CIRCUIT MUST HAVE 1 #12 PHASE CONDUCTOR, 1 #12 NEUTRAL

CONDUCTOR AND 1 #12 GROUNDING CONDUCTOR IN 1/2" CONDUIT. PROVIDE

ADDITIONAL PHASE CONDUCTORS AS REQUIRED FOR "MULTIPLE PHASED"

ELECTRICAL LOADS. PROVIDE NEUTRAL CONDUCTOR TO ALL WALL SWITCH OUTLET

BOXES WHETHER REQUIRED OR NOT. PROVIDE ADDITIONAL "SWITCH LEG"

CONDUCTORS TO PROVIDE THE LIGHT FIXTURE CONTROL INDICATED. MULTIPLE

SINGLE PHASE CONDUCTORS MAY BE GROUPED TOGETHER IN A COMMON CONDUIT

IN ACCORDANCE WITH THE NEC AND AT THE CONTRACTOR'S DISCRETION.

GROUNDING CONDUCTORS MAY BE SHARED AS ALLOWED BY THE NEC. NEUTRAL

CONDUCTORS MUST NOT BE SHARED. MULTI-POLE BREAKERS MUST BE PROVIDED IN

ACCORDANCE WITH THE NEC WHERE MULTI-WIRE BRANCH CIRCUITS ARE REQUIRED.

CONDUIT LARGER THAN 1/2" AND CONDUCTORS LARGER THAN #12 MUST BE AS

INDICATED.

LIGHTING

POWER

GENERAL

WALL MOUNTED LIGHTING FIXTURE

SPECIAL RECEPTACLE, AS NOTED ON PLANS

NEW WORK NOTE SYMBOL

DEMOLITION NOTE SYMBOL

VARIABLE FREQUENCY DRIVE (UNIT SUPPLIED WITH DISCONNECTING MEANS)

MOTOR RATED SWITCH WITH THERMAL OVERLOADS 20A, 120V, UON, MOUNTED

WITHIN SIGHT OF MOTOR.

TIME CLOCK

PHOTOCELL, 1500W, 120V SPST, MOUNT ON ROOF, AIM NORTH

TRACK LIGHTING FIXTURE. INDICATES AN INDIVIDUAL FIXTURE ON THE TRACK

SURGE PROTECTIVE DEVICE

GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK SHOWN ON

ELECTRICAL DRAWINGS IS NEW WORK TO BE PROVIDED UNDER THIS CONTRACT.

COORDINATION: COORDINATE AND COOPERATE WITH ALL TRADES ON THE

PROJECT. THE CONTRACTOR MUST REVIEW ALL CONTRACT DOCUMENTS

INCLUDING CIVIL, STRUCTURAL, ARCHITECTURAL DRAWINGS AND

SPECIFICATIONS. CONTRACTOR MUST COORDINATE AND ADJUST ACCORDINGLY

AS DIRECTED BY THE CONTRACTING OFFICER.

AS-BUILT DRAWINGS: SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS TO BE

KEPT ON SITE AND MARK, DAILY, THE DRAWINGS IN RED AS THE PROJECT

PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF ALL DEVIATIONS

BETWEEN THE WORK SHOWN ON THE DRAWINGS AND THE WORK WHICH IS

ACTUALLY INSTALLED. THESE MARKED DRAWINGS MUST REFLECT ANY AND ALL

CHANGES AND REVISIONS TO THE ORIGINAL DESIGN WHICH EXISTS IN THE

COMPLETED WORK. DELIVER THE MARKED DRAWINGS TO THE ENGINEER AT

PROJECT CLOSE-OUT.

TESTS: TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE CONNECTING

ANY FIXTURES OR DEVICES. PERFORM INSULATION RESISTANCE TESTS ON ALL

WIRING #6 OR LARGER TO ENSURE THAT ALL PORTIONS ARE FREE FROM

SHORT-CIRCUITS AND GROUNDS.

INSPECTIONS: ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL REQUIRED

INSPECTION CERTIFICATES TO THE CONTRACTING OFFICER.

ELECTRICAL SERVICE: PROVIDE THE ELECTRICAL SERVICE. COMMUNICATE WITH

THE CONTRACTING OFFICER, VERIFY ALL REQUIREMENTS, AND COORDINATE ALL

EFFORTS.

GROUNDING: PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR THE

ENTIRE ELECTRICAL SYSTEM INCLUDING EQUIPMENT FRAMES CONDUITS,

SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS, AND OTHER

EQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN ALL POWER CONDUITS.

LABELS: PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY

SWITCHES, MOTOR-DISCONNECT SWITCHES, AND MOTOR CONTROLLERS. LABELS

MUST BE MACHINE ENGRAVED, LAMINATED PLASTIC, PERMANENTLY ATTACHED

WITH SELF-TAPPING SCREWS OR RIVETS. DO NOT USE SELF-ADHESIVE LABELS.

LABEL MUST INDICATE EQUIPMENT DESIGNATION AND ASSOCIATED PANEL AND

CIRCUIT THAT SERVES IT.

J-BOX LABELING: LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER

IDENTIFYING CIRCUIT NUMBER AND PANELBOARD OF CIRCUITS WITHIN.

WIRING DEVICES: LABEL ALL WIRING DEVICES WITH PANELBOARD AND CIRCUIT

DESIGNATION PERMANENTLY ATTACHED WITH BLACK TYPED DESIGNATION ON

CLEAR TAPE.

PANEL DIRECTORY: PROVIDE TYPEWRITTEN PANELBOARD DIRECTORY CARD IN

EACH PANELBOARD WITH CIRCUIT LOAD INFORMATION AND ROOM NUMBER

CLEARLY IDENTIFIED. USE ACTUAL ROOM NUMBERS IN THE BUILDING, NOT THE

ROOM NUMBERS SHOWN ON THE CONTRACT DRAWINGS, AS THEY ARE OFTEN

DIFFERENT.

CONDUCTORS AND MATCHING LUGS: IN SITUATIONS WHERE CONDUCTOR SIZES

AND/OR QUANTITIES OF PARALLEL SETS HAVE BEEN INCREASED DUE TO

VOLTAGE DROP OR FOR OTHER REASONS, CONTRACTOR MUST PROVIDE THE

APPROPRIATE LUG SIZES/QUANTITIES WITHIN THE EQUIPMENT CONNECTED

(SWITCHBOARD, PANELBOARD, DISCONNECT SWITCH, TRANSFER SWITCH ETC.)

TO PERMIT SATISFACTORY CONNECTION OF THE INDICATED CONDUCTORS.

WHERE SUFFICIENT LUG SIZES AND/OR QUANTITIES CANNOT BE PROVIDED TO

ACCOMMODATE THE CONDUCTORS INDICATED, THEN PROVIDE REDUCING

ADAPTERS, PIN TERMINALS, OR A JUNCTION BOX TO SPLICE LARGER

CONDUCTORS TO APPROPRIATELY SIZED SMALLER CONDUCTORS TO FIT INTO

THE LUGS PROVIDED. ALL CONDUCTORS MUST BE SIZED IN ACCORDANCE WITH

THE NEC.

MOTOR COORDINATION: MOTORS, MOTOR STARTERS, CONTROLLERS, INTEGRAL

DISCONNECT SWITCHES, AND CONTACTORS MUST BE PROVIDED WITH THEIR

RESPECTIVE PIECES OF EQUIPMENT BY THE EQUIPMENT SUPPLIER.

COMMUNICATE WITH THE TRADES PROVIDING THE EQUIPMENT, VERIFYING ALL

REQUIREMENTS, PROVIDE ALL ELECTRICAL CONNECTIONS REQUIRED THEREIN,

AND INSTALL MOTOR STARTERS.

MOTOR DISCONNECTS: ALL MOTORS MUST HAVE DISCONNECTING MEANS.

MOTOR CONTROLLERS: ALL 3-PHASE MOTORS MUST HAVE MAGNETIC MOTOR

CONTROLLERS WITH SOLID STATE OVERLOAD RELAY PROTECTION. THE SOLID

STATE OVERLOAD RELAY MUST HAVE PHASE LOSS AND PHASE OVERCURRENT

PROTECTION WITH AUTOMATIC RESET UPON RETURN OF NORMAL POWER.

MOTOR FUSE PROTECTION: WHERE FUSE PROTECTION IS SPECIFICALLY

REQUIRED BY THE EQUIPMENT MANUFACTURER, PROVIDE FUSED SWITCHES IN

LIEU OF NON-FUSED SWITCHES OR IN LIEU OF ENCLOSED CIRCUIT BREAKERS, OR

OTHER DEVICES INDICATED.

CONNECTION DETAILS: SECURE APPROVED SHOP DRAWINGS SHOWING WIRING

DIAGRAMS, ROUGH-IN AND HOOK UP DETAILS FROM OTHER INVOLVED

CONTRACTORS FOR EQUIPMENT WHICH MUST BE CONNECTED ELECTRICALLY.

COORDINATION DETAILS: MECHANICAL EQUIPMENT WILL BE FURNISHED AND

INSTALLED BY THE MECHANICAL CONTRACTOR. THE LOCATIONS SHOWN ON THE

ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE WITH THE

MECHANICAL CONTRACTOR TO DETERMINE THE EXACT LOCATION OF EACH

PIECE OF EQUIPMENT AND DETERMINE THE EXACT ROUGH-IN AND CONNECTION

REQUIREMENTS.

WORKING CLEARANCE: COORDINATE FINAL LOCATIONS OF ELECTRICAL

EQUIPMENT WITH MECHANICAL DUCTWORK, PIPING ETC. AND ASSURE WORKING

CLEARANCE REQUIRED BY NEC WILL BE MET. SUFFICIENT ACCESS AND WORKING

SPACE MUST BE PROVIDED AND MAINTAINED AROUND ELECTRICAL EQUIPMENT

AS REQUIRED BY THE NATIONAL ELECTRICAL CODE. CONTRACTOR MUST

COORDINATE FINAL LOCATION OF EQUIPMENT PROVIDED AND INSTALLED BY

OTHER TRADES.

STARTER MOUNTING: WHERE AN INDIVIDUALLY MOUNTED SAFETY SWITCH,

STARTER OR CIRCUIT BREAKER IS SHOWN ADJACENT TO ITS RESPECTIVE LOAD

AND NOT MOUNTED ON A WALL, PROVIDE ALL SUPPORTS, BRACKETS,

ANCHORING, ETC. NECESSARY TO PROPERLY SUPPORT THE DEVICE.

LIGHTING ARRANGEMENT: ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH

THE ARCHITECTURAL REFLECTED CEILING PLANS.

LIGHTING COORDINATION: COORDINATE LIGHTING FIXTURES WITH GRILLES,

DIFFUSERS, SPRINKLER HEADS, AND ACCESS PANELS, ETC. PROVIDE FIXTURE

MOUNTING BRACKETS, ACCESSORIES, PLASTER FRAMES, ETC.. SUITABLE FOR

THE CEILING TYPES INDICATED ON THE ARCHITECTURAL PLANS.

LIGHTING CONTROL TESTING: UPON COMPLETION OF THE INSTALLATION OF ALL

LIGHTING SYSTEMS AND CONTROL DEVICES, CONTRACTOR MUST CONFIRM

PROPER OPERATION OF ALL LIGHTING CONTROLS, AND DEMONSTRATE PROPER

OPERATION TO THE CONTRACTING OFFICER.

MATERIAL COORDINATION: VERIFY CEILING AND WALL CONSTRUCTION AND

MATERIAL PRIOR TO ORDERING LIGHT FIXTURES OR OTHER DEVICES TO INSURE

PROPER FIXTURE OR DEVICE IS FURNISHED TO MATCH CONSTRUCTION.

MOUNTING HEIGHTS: MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHED

FLOOR TO THE CENTERLINE OF THE WIRING DEVICE UNLESS OTHERWISE NOTED.

MOUNTING HEIGHTS OF LIGHTING FIXTURES ARE TO THE BOTTOM OF THE

FIXTURE UNLESS OTHERWISE NOTED.

DEVICE LOCATIONS: COORDINATE LOCATIONS OF SWITCHES, RECEPTACLES,

AND TELE/DATA OUTLETS WITH OTHER WALL MOUNTED DEVICES SUCH AS

THERMOSTATS AND CONTROL STATIONS.

EWC RECEPTACLES: RECEPTACLES FOR ELECTRIC WATER COOLERS (EWC)

MUST BE INSTALLED OUT OF VIEW AND BEHIND THE EWC ENCLOSURE. VERIFY

THE MOUNTING HEIGHT WITH THE EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.

DEVICE COORDINATION: THOROUGHLY REVIEW AND COORDINATE ALL

CASEWORK AND CABINET DRAWINGS AND ARCHITECTURAL ELEVATIONS WITH

DEVICE LOCATIONS PRIOR TO ROUGH-IN OF OUTLET BOXES.

MULTI-GANG JUNCTION BOXES: WHERE OUTLETS AND SWITCHES ARE SHOWN

ON PLAN TO BE INSTALLED ADJACENT TO EACH OTHER AND AT THE SAME

MOUNTING HEIGHT, THE DEVICES MUST BE INSTALLED IN A MULTI-GANG

OUTLET BOX, UON. THE SIZE OF THE OUTLET BOX MUST BE DETERMINED BY

THE NUMBER OF DEVICES AND CONDUCTORS THAT MUST BE INSTALLED IN

THE MULTI-GANG OUTLET BOX.

BARRIERS: WHERE A MULTIPLE-GANG BOX HAS CIRCUITS OF DIFFERENT

VOLTAGES OR SYSTEMS WHICH ARE REQUIRED TO BE SEPARATED, PROVIDE THE

CODE-REQUIRED SEPARATION USING A FULL HEIGHT AND DEPTH BARRIER PLATE.

FIRE STOPPING: FOR ANY WALL OR FLOOR PENETRATIONS THROUGH

FIRE-RATED STRUCTURES PROVIDE FIRE-STOPPING TO SEAL ALL THE

PENETRATIONS AFTER THE CONDUIT HAS BEEN INSTALLED. FIRE STOPPING FOR

PENETRATIONS MUST BE UL APPROVED PER THE PENETRATION MADE IN ORDER

TO MAINTAIN FIRE-RATED INTEGRITY OF THE STRUCTURE.

CLEAN UP: ON PROJECT CLOSE-OUT CLEAN ALL ELECTRICAL DEVICES, LIGHTING

FIXTURES, LENSES, AND REMOVE ALL PAINT SPATTERS FROM DEVICES,

FIXTURES AND PLATES. REPAIR ALL INOPERATIVE LIGHTING FIXTURES.

GROUND FAULT PROTECTION: RECEPTACLES LOCATED WITHIN 6'-0" OF THE

EDGE OF SINKS MUST BE PROVIDED WITH GROUND FAULT PROTECTION

WHETHER SHOWN OR NOT.

FIRE ALARM COORDINATION: THE ELECTRICAL CONTRACTOR MUST COORDINATE

WITH THE FIRE ALARM SYSTEM PROVIDER AND PROVIDE POWER CONNECTIONS

TO ALL COMPONENTS WHETHER SHOWN OR NOT. MANUFACTURERS REQUIRE

VARYING QUANTITIES OF POWER CONNECTIONS FOR EQUIPMENT LIKE

EXPANDER PANELS AND POWER SUPPLIES. THESE DEVICES ARE DEPENDENT

UPON THE SPECIFIC MANUFACTURERS SYSTEM. THE FIRE ALARM SYSTEM

SUPPLIER MUST NOTIFY THE OTHER APPROPRIATE SUB-CONTRACTORS ABOUT

THESE REQUIREMENTS AND CONNECTION MUST BE PROVIDED AS PART OF THE

PROJECT.

HVAC DAMPERS, ETC: CONTRACTORS MUST COORDINATE WITH THE EQUIPMENT

AND SYSTEM BEING PROVIDED AND PROVIDE POWER CONNECTIONS

ACCORDINGLY. THESE CONNECTIONS MUST BE FOR FIRE/SMOKE DAMPERS, DDC

CONTROL DEVICES, ETC. CONTRACTOR MUST COORDINATE THE VOLTAGE

REQUIREMENTS AND PROVIDE ALL NECESSARY CONNECTIONS, COMPONENTS,

ETC. THIS INCLUDES TRANSFORMERS, BOXES, ETC.

CEILING PLENUM: THE CEILING SPACE IS A RETURN AIR PLENUM. ALL LOW

VOLTAGE CABLE MUST BE PLENUM RATED. REFER TO NEC ART. 300.22 FOR

PROVISIONS APPLICABLE TO PLENUMS.

THE FOLLOWING SUBSCRIPTS MUST APPLY TO RECEPTACLES WHERE USED:

DETAIL OR SECTION NOTATION

CEILING MOUNTED DUAL TECHNOLOGY ULTRASONIC/PASSIVE INFRARED VACANCY

SENSOR.

WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR WITH SINGLE POLE

SWITCH, 120/277V, MOUNT 46"AFF.

HEAT TAPE CONNECTION, CLASS B GFI DEVICE WITH PUSH TO TEST AND RESET

BUTTONS WITH WEATHER PROOF COVER. CONNECT AHEAD OF HEAT TRACE

THERMOSTAT.

CONTRACTOR MUST PROVIDE AN APPROPRIATE LISTED THROUGH-PENETRATION FIRE STOPPING ASSEMBLY AT EACH PENETRATION OF FIRE RATED CONSTRUCTION (I.E. WALLS AND SLABS, ETC.). SLEEVES MUST ONLY BE PERMITTED WHERE INDICATED IN THE CONTRACTOR SELECTED THROUGH-PENETRATION FIRE STOPPING ASSEMBLY. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION OF ALL RATED ASSEMBLIES AND ASSOCIATED UL DESIGNATIONS. DEVICES INSTALLED RECESSED WITHIN FIRE RATED CONSTRUCTION (I.E. LIGHT SWITCHES, RECEPTACLES, ETC.) ARE ONLY PERMITTED WHEN AN APPROVED LISTED FIRE STOPPING SYSTEM EXISTS FOR THE APPLICATION. IF AN APPROVED LISTED FIRE STOPPING SYSTEM IS UNAVAILABLE, THE CONTRACTOR MUST BRING THE CONDITION TO THE ATTENTION OF THE GOVERNMENT FOR RESOLUTION PRIOR TO PROCEEDING WITH WORK.

GENERAL ELECTRICAL NOTES ELECTRICAL LEGEND

AND

SWITCH RATING

NUMBER OF POLES

FUSE RATING (NF INDICATES NON-FUSED)

NEMA ENCLOSURE IF OTHER THAN NEMA 1

ENUMERATION: A = DETAIL, 1 = SECTION

SHEET WHERE SECTION IS SHOWN

SHEET WHERE SECTION IS CUT

1 HOUR FIRE RATED WALL

2 HOUR FIRE RATED WALL

SPD

A

D

TC

P

V

O

GFI

E J

M

DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, 18" AFF, UON

TWO DUPLEX RECEPTACLES IN COMMON BOX, EACH 20A, 120V, 18" AFF, UON

DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, 46" AFF, UON (OR 6" ABOVE

COUNTER AS APPLICABLE)

TAMPER PROOF/ARC FAULT DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, 18"

AFF, UON.

· GFI: GROUND FAULT INTERRUPTING TYPE RECEPTACLE

· +XX": DEVICE MOUNTING HEIGHT DESIGNATION ABOVE FINISHED FLOOR IF OTHER

THAN 18" OR 46".

· WP: WEATHER RESISTANT GFI RECEPTACLE WITH WEATHERPROOF WHILE-IN-USE

COVER.

· EWC: ELECTRIC WATER COOLER RECEPTACLE, PROVIDE GROUND FAULT INTERRUPTING

TYPE BREAKER. LOCATE BEHIND THE EWC PER MANUFACTURER'S

RECOMMENDATIONS.

ABBREVIATIONS

A AMPERE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

BFG BELOW FINISHED GRADE

C CONDUIT

CB CIRCUIT BREAKER

DDC DIRECT DIGITAL CONTROL

DSS DUCTLESS SPLIT SYSTEM

EBU EMERGENCY BATTERY UNIT

EC EMPTY CONDUIT

EF EXHAUST FAN

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

FACP FIRE ALARM CONTROL PANEL

FLA FULL LOAD AMPS

GFI GROUND FAULT INTERRUPTER

GND GROUND

HP HORSE POWER/HEAT PUMP

KAIC THOUSAND AMPERE

INTERRUPTING CAPACITY

KVA KILO-VOLT-AMPERES

KW KILO-WATTS

LPW LUMENS PER WATT

LTG LIGHTING

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MFR MANUFACTURER

MLO MAIN LUGS ONLY

MTD MOUNTED

NEC NATIONAL ELECTRICAL CODE

NF NON-FUSED

NTS NOT TO SCALE

P POLE

Ø PHASE

PRI PRIMARY

RECEPT RECEPTACLE

REQ'D REQUIRED

SE SERVICE ENTRANCE

SEC SECONDARY

SPD SURGE PROTECTION DEVICE

TBB TELEPHONE BACKBOARD

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLT

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

W WATTS/WIRE

WP WEATHERPROOF

FLOOR MOUNTED DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, UON.

VFD

CEILING MOUNTED DUAL TECHNOLOGY ULTRASONIC/PASSIVE INFRARED

OCCUPANCY SENSOR.

OC

.47

X X

.47

X X

OSX X

OSX X

OS

X

X

OSLX

XOSLX

X

OS

L

X X

OS

L

X X

6 7

US

US

US

US

US

US

US

12.47 / OSL 12.4712.47 / OSL 12.47 / OSL 12.47 / OSL

OS

L

The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

02/24/2020

NELECTRICAL SITE PLAN - DEMOLITION

SCALE: 1" = 20'-0"

REMOVE EXISTING OVERHEAD PRIMARY TAP, SITE LIGHTING

FIXTURE AND CROSS ARMS.

REMOVE EXISTING POLE, POLE MOUNTED TRANSFORMER, SITE

LIGHTING FIXTURE, GUYS AND OVERHEAD CONDUCTORS.

REMOVE EXISTING SERVICE POLE, POLE MOUNTED METER BASE,

SITE LIGHTING FIXTURE, OVERHEAD CONDUCTORS AND

OVERHEAD TO UNDERGROUND TRANSITION.

REMOVE EXISTING POLE, OVERHEAD TO UNDERGROUND

TRANSITIONS, GUYS AND LIGHT FIXTURE.

REMOVE EXISTING UNDERGROUND SERVICE CONDUCTORS FROM

POLE TO BUILDING.

REMOVE POLE, SITE LIGHTING FIXTURE AND OVERHEAD SITE

LIGHTING CIRCUIT.

REMOVE EXISTING SITE LIGHTING FIXTURE AND OVERHEAD SITE

LIGHTING CIRCUIT.

BUILDING TO BE DEMOLISHED IN ITS ENTIRETY.

NOTES THIS SHEET

PT

EXISTING POLE

UG TERM (15KV)

CONDUIT RISER (6", PVC), TYPE C

GROUND

SPARE

PRIMARY IN DUCT

UP

UP

UP

UP

USPANEL MDP

PANEL ALA

SPARE

SECONDARY

IN DUCT

12.47 / OSL

OSL

ALA-7 VIA LIGHTING

CONTACTOR

ALA-9 VIA LIGHTING

CONTACTOR

ALA-11 VIA LIGHTING

CONTACTOR

L L L

L

L

LLL

M M M

L

L

T

12.47 / OSL 12.47 / OSL 12.47 / OSL

The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

02/24/2020

NELECTRICAL SITE PLAN - NEW WORK

SCALE: 1" = 20'-0"

SITE PLAN LEGEND

US

UP

UNDERGROUND SECONDARY CIRCUIT

UNDERGROUND PRIMARY CIRCUIT

E12.47 EXISTING OVERHEAD PRIMARY CIRCUIT; 12.47 KV

ALUMINUM, BARE, 6201 ALLOY, 19 STRAND, 394.5 KCMIL, CODE

NAME CANTON

PAD MOUNTED TRANSFORMER

FRONT

T

EXISTING POLE

PANELBOARD - 208/120V, 3 PHASE, 4 WIRE

PRIMARY ONE-LINE DIAGRAM

NOT TO SCALE

PAD MOUNTED

TRANSFORMER: 150 KVA,

12.47 KV TO 208/120 V, 3

PHASE, 4 WIRE

E12.47

UP 3 #2 EPR 15KV, 133% INSULATION & 1 #2 COPPER

CONCENTRIC NEUTRAL IN 5" PVC CONDUIT AND

ONE 5" PVC SPARE CONDUIT CONCRETE

ENCASED. SEE CONCRETE ENCASED DUCTBANK

- DETAIL 'A' SHEET ES502.

FUSED CUTOUTS: 100A

EOP 7.2 REMOVE EXISTING OVERHEAD PRIMARY, 7.2 KV, SINGLE PHASEX X

EXISTING POLE MOUNTED TRANSFORMER

EXISTING POLE GUY

POLE MOUNTED SURGE ARRESTOR WITH GROUND.

1 TAP EXISTING OVERHEAD PRIMARY, TRANSITION UNDERGROUND AND

EXTEND AS INDICATED.

NOTES THIS SHEET

PRIMARY TAP BOX

OS

OSL

OVERHAED SECONDARY CIRCUIT

OVERHEAD SITE LIGHTING CIRCUIT

PT PRIMARY TAP BOX

SEE POWER RISER DIAGRAM SHEET E-601

FOR ADDITIONAL INFORMATION

PO Box 541, New Bern, NC 28563

252.636.8778 (PHONE)

252.636.8992 (FAX)

WALKER

GROUP

i n c o r p o r a t e d the

ARCHITECTURE

DISCLOSURE OF INFORMATION

CONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR

(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE

(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.

(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

02/24/2020

POLE LINE MATERIAL LIST

FLAT STEEL BRACE (TWO PIECES)

MACHINE BOLT, 3/8" X LENGTH NEEDED WITH WASHER, NUT AND LOCKWASHER

8' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 3 1/2" X 4 1/2"

MACHINE BOLT, 5/8" X LENGTH NEEDED WITH WASHER, NUT AND LOCKWASHER

TIMBER CONNECTOR

LAGSCREW, 1/2" X 4"

ANGLE STEEL BRACE (TWO PIECES)

MACHINE BOLT, 1/2" X LENGTH NEEDED, WITH WASHER, NUT & LOCKWASHER

DEADEND BOX

STEEL PIN

PIN INSULATOR

GRID GAIN, USED ONLY WHEN THERE IS NO POLE GAIN

ANGLE STEEL BRACE (ONE PIECE)

10' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 3 1/2" X 4 1/2"

5/8" EYE NUT

5/8" EYE BOLT, LENGTH AS NEEDED, WITH WASHER, NUT & LOCKWASHER

EXTENSION LINK

BELL TYPE SUSPENSION INSULATOR WITH CONNECTING HARDWARE

STRAIN CLAMP

STEEL ANGLE PIN

CLUSTER MOUNTING BRACKET, STEEL

TRANSFORMER GROUNDING CONNECTION

STIRRUP

SECONDARY LEAD SUPPORT BRACKET

ADAPTER PLATE FOR CLUSTER MOUNTING

CLEVIS BRACKET FOR SPOOL INSULATOR

SPOOL INSULATOR

U BOLT CLAMP

PREFORMED GUY GRIP

GUY HOOK

GUY STRAIN INSULATOR

GUY WIRE, SIZE AS SPECIFIED

#4 WP CU. SOFT DRAWN GROUND WIRE

GROUND CLAMP

CONDUIT COUPLING

CONDUIT BEND

INSULATED BUSHING

PERFORATED STRAPPING, 1-1/2" WIDE

HOT LINE CLAMP

FUSED CUTOUT, AS SPECIFIED

SURGE ARRESTER, AS SPECIFIED

POLE TOP PIN (RIDGE PIN) - 24 INCHES LONG

CROSSARM ANGLE PIN

ANGLE POLE TOP PIN

WEATHERPROOF SOFT DRAWN WIRE-SIZE

T0 MATCH OR EXCEED AMPACITY OF CONNECTING

CABLE, OR

AT 125% OF TRANSFORMER FULL LOAD

CURRENT, BUT NOT LESS THAN NO. 4 AWG

(a)

(b)

OH-1.5JUNE 2002SKETCH DATE STYLE

POLE LINE MATERIAL LIST

UNDERBUILD CIRCUIT

POSITION OF COMMON NEUTRAL

OR MULTIPLEX SECONDARY

CONDUCTOR

CIRCUITCOMM.

PROVIDE 60" CLEARANCE WHEN OPERATING VOLTAGE OF UNDERBUILD

CIRCUIT IS GREATER THAN 15KV.

NOTE

FOR HORIZONTAL SPACING REQUIREMENTS FOR CONDUCTORS ON SAME SUPPORT,

REFER TO THE NATIONAL ELECTRICAL SAFETY CODE, IEEE C2.

1.

Ø-Ø VOLTAGE 0-15KV 15-50KV

SPACING A"

SPACING B"

40"

40"

48"

40"

OH-1.4JUNE 2002SKETCH DATE STYLE

BASIC VERTICAL SPACING REQUIREMENTS

"B"

"A"

40" MIN.

DEDICATED

CLEAR SPACE

POSITION OF LOWEST POWER (SUPPLY)

ATTACHMENT SHALL BE NO LESS THAN

24'-4" ABOVE GRADE.

DEDICATED CLEAR SPACE BETWEEN

POWER (SUPPLY) AND COMMUNICATION

CIRCUITS.

POSITION OF HIGHEST

COMMUNICATION ATTACHMENT

SHALL BE NO HIGHER THAN

21'-0" ABOVE GRADE.

EXPLANATION OF SYMBOLS LISTED FOR POLE ON SKETCH OH-1.3

EXPLANATORY NOTES - METHOD OF SHOWING SYMBOLS

SYMBOLS ARE SHOWN IN THE BASIC ORDER AS THEY APPEAR ON THE

POLE, BY STARTING AT THE TOP AND WORKING DOWN.

NUMERALS PRECEDING THE SYMBOL INDICATE THE MINIMUM REQUIRED

VOLTAGE (KV) RATING (5,15,35) OF THE ASSEMBLY, IF APPLICABLE.

NUMERAL FOLLOWING THE SYMBOL INDICATES THE NUMBER OF CON-

DUCTORS ASSOCIATED WITH THE ASSEMBLY, IF APPLICABLE.

NUMERAL IN PARENTHESIS FOLLOWING THE SYMBOL DENOTES THE

NUMBER OF ASSEMBLIES REQUIRED, IF MORE THAN ONE.

DATA IN PARENTHESIS FOLLOWING THE SYMBOL PROVIDES

INFORMATION RELATIVE TO THE SYMBOL.

1.

2.

3.

4.

5.

PROVIDE 45 FOOT LONG, CLASS 3 POLE CONTAINING:

TF -

S1 -

SDE2 -

GROUND -

X-FB -

35FR3 -

X-FB -

15F3 -

8' CROSSARM WITH FLAT BRACE

35KV INSULATORS, FLAT (MOUNTED HORIZONTAL ON CROSS-

ARM), RIDGE PIN (CENTER PHASE ON POLE TOP PIN), THREE

CONDUCTORS

8' CROSSARM WITH FLAT BRACE

15KV INSULATORS, FLAT (MOUNTED HORIZONTAL ON CROSSARM),

THREE CONDUCTORS. NOTE: THIS SYMBOL CALLS FOR THREE

CROSSARM MOUNTED PINS IN LIEU OF RIDGE PIN ON CENTER

PHASE.

TRANSFORMER ON FLAT (HORIZONTAL) CONSTRUCTION. DATA

IN PARENTHESIS DESCRIBES THE TRANSFORMER CHARACTERISTICS.

GUY (5/16") -

SECONDARY, ONE CONDUCTOR, TANGENT CONSTRUCTION (COMMON

NEUTRAL).

SECONDARY DEADEND, TWO CONDUCTORS, OPEN WIRE

DOWN GUY - WIRE SIZE 5/16"

10" SCREW TYPE ANCHOR WITH 12 FT. GUY LEAD.

NOTE: NO PLATE IS INCLUDED FOR THE ANCHOR SYMBOL.

NO EXPLANATION NECESSARY

ANCHOR -

(10" SCREW)

OH-1.3AJUNE 2002SKETCH DATE STYLE

EXPLANATION OF NOTES/SYMBOLS

13.2 34.5

S N

13.2

N 34.5

PLAN VIEW

POLE # (45'-3)

X-FB, 35FR3

X-FB, 15F3

TF (25KVA, 13.2 GRD. Y/7.6 KV - 120/240 V.)

S1, SDE2

GUY (5/16")

ANCHOR (10" SCREW) (12' GUY LEAD)

GROUND

NOTES

THE SYMBOLS LISTED ABOVE

INCLUDE MATERIALS (DESCRIBED

BY OVERHEAD SKETCHES) WHICH

ARE GRAPHICALLY ILLUSTRATED

BY THIS PICTURE. SEE

SKETCH OH-1.3A FOR

EXPLANATORY NOTES.

EACH SKETCH CONTAINS

MATERIAL ITEMS WHICH COMPRISE

A PART OF EACH INDIVIDUAL

SYMBOL REFERENCED BY THAT

SKETCH, THESE ITEMS ARE

INDICATED BY CIRCLED

NUMERALS WHICH ARE IDENTIFIED

BY SKETCHES OH-1.5

AND OH-1.5A.

SPACING REQUIREMENTS RELATED

TO INDIVIDUAL COMPONENTS OF

A SYMBOL ARE INDICATED ON

THE APPROPRIATE SKETCH.

VERTICAL SPACING

REQUIREMENTS BETWEEN

CIRCUITS AND/OR SYSTEMS

ARE INDICATED ON SKETCH

OH-1.4. ALL OTHER

SEPARATIONS BETWEEN

CIRCUITS, EQUIPMENT, ETC.,

SHALL CONFORM TO THE

NATIONAL ELECTRICAL

SAFETY CODE, IEEE C2.

1.

2.

3.

OH-1.3JUNE 2002SKETCH DATE STYLE

METHOD OF SHOWING SYMBOLS

POLE LINE MATERIAL LIST

TRI-MOUNT BRACKET

TERMINATOR

MOUNTING BRACKET

CABLE GRIP HANGER

HOSE CLAMP

STUD, 3/4" X 1-3/4"

LINE POST INSULATOR

TRIPLE INSULATOR BRACKET

ANGLE CLAMP

INSULATOR, LINE POST CLAMP

4' CROSSARM

CROSSARM GAIN BRACKET

PULLEY BRACKET

WEDGE CLAMP

MIDSPAN SERVICE CLAMP

STUD, 7"

SADDLE, ANGLE

SADDLE CROSSARM

FITTING, POLE TOP

CONNECTOR

SUSPENSION CLAMP

TIE, SERVICE CABLE

54" FIBERGLASS STRAIN INSULATOR

69 PVC RISER SHIELD

PVC EXTENSION SHIELD

PVC BACK PLATE

72 8' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 4 3/4" X 5 3/4"

73 10' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 4 3/4" X 5 3/4"

OH-1.5AJUNE 2002SKETCH DATE STYLE

POLE LINE MATERIAL LIST

BACK-UP CURRENT LIMITING FUSE74

ATTACHMENT

POSITION OF GUY

SEE NOTE 3

SIDE VIEW FRONT VIEW

THIS POLE.

CONTINUES ON BEYOND

NEUTRAL LEVEL, IF

POLE

DEADENDS ON THE

NEUTRAL LEVEL, IF

NOTES

1.

2.

3.

23 39

41 48 41 48

16" 2"

4"

40"

21"

24"

19"36"

OH-31JUNE 2002

(0-25KV)

U.G. TERMINAL

SKETCH DATE STYLE

MODIFY POSITION OF TERMINAL ON DEADENDS TO BE UNDER THE CONDUCTORS AND THE CUTOUTS ON THE BACKSIDE OF

CROSSARM. POLE RISER MUST BE OFFSET TO CLEAR NEUTRAL CLEVIS BRACKET.

CONNECT BOTTOM LEAD OF ARRESTER DIRECTLY TO POLE GROUND. INTERCONNECT CABLE INSULATION SHIELD DRAIN WIRES AND CONDUIT RISER GROUND TO MULTI- GROUNDED NEUTRAL (IF EXISTING) AND POLE GROUND.

CUTOUT PROVIDES A FUSE OR A SOLID BLADE (NON-FUSED) OPTION. COORDINATE

WITH SPECIFIC DESIGN REQUIREMENTS PROVIDED.

TOP VIEW 19 IN

4 IN

POLE AS

INDICATED

36.5 IN

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-CAST ALUMINUM OR DIE-CAST AND EXTRUDED ALUMINUM WITH INTEGRAL,

SELF-CLEANING HEAT SINK FINS, RIBS, OR EQUIVALENT PASSIVE COOLING MECHANISM.

HEAT SINK SHALL BE INCORPORATED DIRECTLY INTO HOUSING TO ENSURE MAXIMUM HEAT

TRANSFER AND DISSIPATION.

2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED WITH BAKED-ON POLYESTER POWDER

COAT. FINISH SHALL PASS 2500 HOUR SALT SPRAY TEST PER ASTM B117. FINISH COLORS

INCLUDE DARK BRONZE, SILVER, OR BLACK WITH CUSTOM COLORS AVAILABLE.

3. POWER SUPPLY/LED DRIVER - PROVIDE IN SEPARATE COMPARTMENT ACCESSIBLE WITHOUT

THE USE OF HAND TOOLS. CLASS 1 DRIVER SHALL OPERATE AT 120/277V, 50/60 HZ; OTHER

VOLTAGES OPTIONAL. POWER FACTOR GREATER THAN 0.9 AND THD LESS THAN 20% AT FULL

LOAD. MINIMUM EFFICACY SHALL BE 60 LM/W AT MAXIMUM 600 mA OPERATING CURRENT.

4. LED OPTICAL ASSEMBLY - NUMBER OF LED ARRAYS SHALL VARY TO ACCOMMODATE

DESIRED LUMINAIRE OUTPUT. PROVIDE WITH EQUIVALENT NEMA TYPE III, IV OR V

DISTRIBUTION AS INDICATED. BUG UPLIGHT RATING OF U0, WITH BACKLIGHT AND GLARE

RATINGS AS DETERMINED BY LIGHTING ZONE INSTALLED. MINIMUM COLOR RENDERING

INDEX (CRI) SHALL BE 70 FOR CORRELATED COLOR TEMPERATURE (CCT) OF 4000 K TO 4500

DEGREES K.

5. SURGE PROTECTION - 6 kV MINIMUM, COMPLIANT WITH ANSI C62.41.2.

6. CERTIFICATION - UL AND/OR ETL LISTED, MINIMUM IP65 RATED PER ANSI/IEC 60529, AND RoHS

COMPLIANT.

7. OTHER - THE ABOVE SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A

LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS AND IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER'S PREFERENCE. ALL DIMENSIONS ARE NOMINAL AND

VARY PER MANUFACTURER.

REVISED: MARCH 2013 XL-03LUMINAIRE PLATE:

LED AREA LUMINAIRE

OPTIONAL

PHOTOCELL

REVISED: MARCH 2013 XL-29LUMINAIRE PLATE:

ANCHOR BASE POLE FOUNDATION

APOLE

HEIGHT

8'-12'

13'-20'

21'-30'

36"

42"

B

12"

31'-40'

72"

78"

16"

24"

30"

"A"

4"

"B"

FINISHED GRADE

INSULATED COPPER GROUNDING

CONDUCTOR ATTACHED TO INTERNAL

LUG WELDED TO INTERIOR OF POLE. SIZE

PER NFPA 70.

CHAMFER ALL EDGES OF CONCRETE BASE

1/2"

HANDHOLE - SEE POLE SKETCH AND

SPECIFICATION

POLE - SEE POLE SKETCH AND

SPECIFICATION

CONDUIT STUBBED UP ADJACENT TO

HANDHOLE; NUMBER AND SIZE AS

REQUIRED

SET TOP OF CONCRETE

FOUNDATION 4" ABOVE

GRADE

COPPER EQUIPMENT

GROUNDING CONDUCTOR

- ATTACH TO INTERNAL

LUG WELDED TO INTERIOR

OF POLE. CONDUCTOR TO

BE SAME SIZE AND TYPE

AS SUPPLY PHASE

CONDUCTOR.

CIRCUIT CONDUCTORS AND

CONDUIT TO POWER

SOURCE OR NEXT POLE

CONCRETE PER

SPECIFICATION

CIRCUIT CONDUCTORS AND

CONDUIT TO POWER SOURCE

OR NEXT POLE

ANCHOR BOLTS AS

RECOMMENDED BY

MANUFACTURER OF POLE

#4 BARS VERTICAL AT 6" EACH

FACE

#3 BARS AT 12" ON CENTER

HORIZONTALLY

3/4" X 10' GROUND ROD

REVISED: MARCH 2013 XL-26LUMINAIRE PLATE:

ANCHOR BASE STEEL/ALUMINUM POLE

TAPERED OR STRAIGHT STEEL OR ALUMINUM POLE. CROSS SECTIONAL

SHAPE AND COLOR AS INDICATED.

NOTES:

COORDINATE TOTAL EPA WITH SPECIFICATIONS.

WIRING HANDHOLE MINIMUM 2 1/2" X 5" CLEAR OPENING WITH COVER AND

STAINLESS STEEL SCREWS.

INTERNAL GROUNDING LUG.

TERMINATE C0NDUITS INTERNALLY, ADJACENT TO HANDHOLE.

FULL BASE COVER - TW0 PIECE GALVANIZED STEEL.

CONCRETE FOUNDATION - SEE PLATE XL-29.

"U"

POLE

TYPE

TENON OPTION - 2-3/8" TENON WITH PROVISION

FOR WIRING. COORDINATE WITH LUMINAIRE.

XL-26

A

XL-26

B

XL-26

C

XL-26

D

XL-26

E

XL-26

F

XL-26

G

MAST ARM OPTION - COORDINATE WIRING AND BOLT HOLES

WITH MAST ARM PROVIDED.

DIM

1'-6"

"U"

9"

12"

L M

L

STYLE NO. & TYPE VOLTAGE MOUNTING NOTESFIXTURE

SYMBOL

NUMBER AND TYPE

OF LAMPS

SITE LIGHTING FIXTURE SCHEDULE

XL-03 (SINGLE) LED UNIVERSALPOLE,

PROVIDE POLE WITH SINGLE LIGHT FIXTURE, 11,676 LUMENS, 4000K COLOR, TYPE 3 DISTRIBUTION, DARK BRONZE FINISH.

POLE: XL-26 B, SQUARE, TAPERED, DARK BRONZE, ALUMINUM.

BASE: XL-29, TOP OF BASE TO BE 36" AFG.

PROVIDE POLE WITH FOUR LIGHT FIXTURES MOUNTED 90 DEGREES APART, 11,676 LUMENS, 4000K COLOR, TYPE 3

DISTRIBUTION, DARK BRONZE FINISH.

POLE: XL-26 B, SQUARE, TAPERED, DARK BRONZE, ALUMINUM.

BASE: XL-29, TOP OF BASE TO BE 36" AFG.

2M XL-03 (QUAD) LED UNIVERSALPOLE

60025690
Sheets and Views
M-704 MECHANICAL CONTROLS
60025691
60025692
60025693
60025694
60025695
60025696