N4008519B0095 Drawings_Part8.pdf
PDF 6 MB Posted
- Attached to
- Building 17 and 17A Renovation and Addition
- Solicitation number
- N6247020R6000
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Large Cabinet.jpg | JPG image | |
| Tabernacle.jpg | JPG image | |
| 08 62 00 Translucent Wall Panels.pdf | ||
| Organ (2).jpg | JPG image | |
| Grand Piano.jpg | JPG image | |
| Baptismal Font.jpg | JPG image | |
| Organ (1).jpg | JPG image | |
| Altar (2).jpg | JPG image | |
| Amnd 0006 20R6000 Final.pdf | ||
| Altar (1).jpg | JPG image | |
| Amnd 0005 20R6000 Final.pdf | ||
| Amnd 0004 20R6000 Final.pdf | ||
| Amnd 0003 20R6000 Final.pdf | ||
| Amnd 0002 20R6000 Final.pdf | ||
| NAVFAC DWG 60025678.pdf | ||
| NAVFAC DWG 60025676.pdf | ||
| Amend 0001 20R6000.pdf | ||
| N4008519B0095 Drawings_Part3.pdf | ||
| N4008519B0095 Drawings_Part6.pdf | ||
| N4008519B0095 Specs.pdf | ||
| N4008519B0095 Drawings_Part7.pdf | ||
| 19-0095 Asbestos Survey 011020.pdf | ||
| N4008519B0095 Drawings_Part2.pdf | ||
| N4008519B0095 Drawings_Part5.pdf | ||
| RFP N62470-20-R-6000.pdf | ||
| N4008519B0095 Drawings_Part1.pdf | ||
| 19-0095 Lead Survey 011020.pdf | ||
| N4008519B0095 Drawings_Part4.pdf | ||
| N4008519B0095 Drawings_Part9.pdf | ||
| Master PPI Form Template.xls | XLS spreadsheet |
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
ROAD SIDE
DIRECTION
OF TRAFFIC
ADDITIONAL
GROUND RODS
(WHEN REQUIRED)
PLAN
ALWAYS CONNECT THE POLE GROUND
LEAD(S) DIRECTLY TO THE NEUTRAL-
ENSURE THAT THE COPPER CONDUCTOR
WILL ALWAYS BE BELOW THE ALUMINUM.
CONNECTOR
NEUTRAL COPPERWELD STAPLES (TYP.)
GROUND
WIRE
POLE
ELEVATION
GROUND ROD
PLASTIC OR FIBER MOLDING
GALVANIZED STAPLES (TYPICAL)
FINISHED
GRADE
#4 BARE
COPPER
POLE
OH-41JUNE 2002SKETCH DATE STYLE
GROUND
24"
MIN.
10'-0"
MIN.
10'-0"
MIN.
24"
12"
8'-0"
MIN.
18"
MAX.
8'-0 MIN.
(FROM 24'-4"
TO 16'-4"
ABOVE GRADE)
ALTERNATE GROUND WIRE
POSITION. (USE WHEN
MULTIPLE GROUNDING
SYSTEMS ARE REQUIRED.)
(SEE NOTE 4)
1.
2.
3.
NOTES
USE ADDITIONAL GROUND RODS, WHEN REQUIRED,
TO OBTAIN RESISTANCE VALUE, AS REQUIRED BY
IEEE C2.
MAKE GROUNDING CONNECTIONS TO ALL EQUIPMENT
ON POLE AS REQUIRED BY IEEE C2.
FOR SYSTEMS OTHER THAN 4 WIRE, MULTI-
GROUNDED, USE SEPARATE GROUNDING
CONDUCTORS AND ELECTRODES FOR PRIMARY
AND SECONDARY SYSTEM DEVICE CONNECTIONS.
#4 600V INSULATED COPPER GROUNDING
CONDUCTOR REQUIRED ON PRIMARY SYSTEM
WHEN SEPARATE SYSTEMS ARE REQUIRED.
4.
AF-1APRIL 2015
GENERAL ARC FLASH WARNING LABEL
SKETCH DATE STYLE
NOTES:
1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO WARN OF ARC
FLASH HAZARDS.
2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE.
3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO QUALIFIED
PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE
EQUIPMENT.
4. THE SIZE OF THE LABEL SHALL BE MINIMUM:
EQUIPMENT TYPE HEIGHT WIDTH
INDOOR 2" 3"
OUTDOOR 3" 4.5"
5. A DOWNLOADABLE WINDOWS METAFILE IS AVAILABLE ON THE WHOLE BUILDING DESIGN GUIDE
WEBSITE (WWW.WDBG.ORG) FOR USE IN A LABEL MAKING MACHINE.
A. THE FILE IS LOCATED ON THE "NAVFAC CADD DETAILS" PAGE. TO NAVIGATE TO THIS
LOCATION, FOLLOW: HOME > DOCUMENTS & REFERENCES > CCB > CADD LIBRARY >
NAVFAC CADD RESOURCES > NAVFAC CADD DETAILS.
B. ALTERNATIVELY, TYPE IN THE FOLLOWING ADDRESS IN INTERNET EXPLORER:
HTTP://WWW.WBDG.ORG/CCB/BROWSE_CAT.PHP?C=232
WIDTH
HEIGHT
(SEE NOTE 1)
SERVICE CAP
CLAMP TYPE
SE
CO
ND
AR
Y
CO
ND
UC
TO
R
NE
UT
RA
L
OR
T
OP
GRADE
FINISHED
GALVANIZED STEEL CONDUIT-SIZE AS INDICATED
SEE NOTE 3
SEE NOTE 2
CONDUIT LOCATION
OF TRAFFIC
DIRECTION
ROAD SIDE
POSITION
RISER
ALTERNATEPOSITION
RISER
POLE
1.
2.
3.
DIRECT BURIED
CABLE
DIRECT BURIED
CONDUIT
TYPE C
OH-35JUNE 2002
(SIZE & TYPE AS INDICATED)
CONDUIT RISER
SKETCH DATE STYLE
TYPE A
CONCRETE ENCASED
CONDUIT
TYPE B
18" MIN.
2"
MIN.
NOTES
ON CONDUIT RISER FOR PRIMARY CIRCUITS, ELIMINATE SERVICE CAP
AND PROVIDE GROUNDING TYPE INSULATING BUSHING.
BOND CONDUIT TO POLE GROUND AND SYSTEM NEUTRAL (IF EXISTING).
SEE GROUNDING NOTES ON SKETCH OH-41.
SPACE STRAPS AT MAXIMUM OF 4' INTERVALS.
1'-6" O.C.
3" MINIMUM
FINISHED GRADE
DUCTBANK MARKING TAPE
3000 P.S.I. CONCRETE
P.V.C. CONDUIT SIZE
AS INDICATED
LEVELING BLOCKS
AT BASE SPACERS
" M
IN
.EQUAL
EQUAL
3" MINIMUM
SEPARATION
(TYP.)
BASE SPACERS
(TYP.)
NOTE: # OF DUCTS SHALL BE AS INDICATED ON PLANS.
3"
SECONDARY
TRANSFORMER BOX
GRADE
TERMINATIONS
LOW VOLTAGE CABLE
CURRENT TRANSFORMERS (800/5)
3-POLE FUSE BLOCK
SECONDARY CIRCUIT
WHD
#4/0 BARE
MIN
2'-0"
GRADE.
PAD. MIN 18" BELOW FINISHED
ENCIRCLING ENTIRE CONCRETE
#4/0 BARE COPPER GROUND LOOP
600V INSULATION
CORNER OF PAD.
OF 4, 1 AT EACH
GROUND ROD, TYP
GROUND PAD (TYP OF 2)
#4/0, 600V
INSULATIONPRIMARY CIRCUIT
CONNECTOR
LOAD BREAK
PRIMARY NEUTRAL
BUSHING INSERT
BREAK OIL SWITCH
2 POSITION LOAD
CURRENT-LIMITING
OIL-IMMERSED
PRIMARY COMPARTMENT
ARRESTERS
SURGE
TRANSFORMER
BUSHING WELL
X0
BAYONET OIL-IMMERSED
EXPULSION FUSES
FUSES
CABLE WELL
TRANSFORMER BOX, SEE DETAIL THIS SHEET.
G
G
G
G GROUND ROD - 3/4" x 10' CONNECT
TO CONDUCTORS BY EXOTHERMIC
WELD (TYP)
PAD MOUNTED COMPARTMENTAL TYPE
TRANSFORMER (SECURE TO TRANSFORMER
BOX PER MANUFACTURER'S
RECOMMENDATION).
SECONDARY NEUTRAL GROUND NO.
4/0 AWG CU MINIMUM
TRANSFORMER
SECTION
EXOTHERMIC WELD (TYP)
EQUIPMENT GROUND
OUTGOING SECONDARY CONDUIT(S)
(NUMBER AS NOTED ON PLANS)
PRIMARY CONDUIT
NUMBER AS NOTED ON
PLANS
EXTEND GRAVEL FILL A
MINIMUM OF ONE FOOT
BEYOND PAD ON ALL SIDES.
WELL COMPACTED GRAVEL
SUBSURFACE SHALL BE 6
INCHES THICK
EXTEND PAD A MINIMUM OF 8
INCHES BEYOND UNIT ON ALL
SIDES
PAD MOUNTED TRANSFORMER DETAIL
NOT TO SCALE
TYPICAL PAD MOUNTED COMPARTMENTAL TRANSFORMER DETAIL
NOT TO SCALE
COMPARTMENT
X10" 10"
6"
9" 18"2-1/2"18"
29"
29"
5"
18"
TRANSFORMER BOX DETAIL
(DETAIL BASED ON PARKING BUMPER COMAPNY STANDARD DETAILS)
CONCRETE ENCASED DUCTBANK - DETAIL 'A'
NOT TO SCALE
CONNECTOR
LOOP FEED
WATTHOUR DEMAND METER: TO
CONFORM TO BASE
STANDARDS. ITRON V&I CS3
SERIES METER.
PRIMARY
JUNCTION
ENCLOSURE
CONCRETE
14"
14"
PLAN
SIDE ELEVATION
FRONT ELEVATION
DEAD FRONT MODULE
'U' STRAPS SUPPLIED WITH
MODULE.
MOUNT 'U' STRAPS CLAMPS (6)
SUPPLIED WITH ENCLOSURE) OVER 'U'
STRAPS TO SECURE TO MODULE.
DEAD FRONT BUSHING WELL
INSERT CONNECTOR.
UNDERGROUND
PRIMARY CONDUIT
UNDERGROUND
PRIMARY CONDUIT
PRIMARY CABLES
FINISHED GRADE
CONCRETE
18"
23"
62"
DEAD FRONT PARKING
STAND
DEAD FRONT MODULE
GROUND LUG (TYPICAL OF
3)
CONCRETE
GRADE
TOP IN OPENED
POSITION.
LIFTING LUGS
(TYPICAL FOR 4)GROUND LINE, DO NOT FILL
INTERIOR OF ENCLOSURE.
46-1/4" 3"
32"
41"
THREE PHASE, FULLY DEAD FRONT, 2-WAY SECTIONALIZING PEDESTAL WITH
15KV, 600 AMP RATINGS. PROVIDE INDUSTRY STANDARD DEAD FRONT
JUNCTION MODULES AND ELBOWS CONFORMING TO ANSI/IEEE 386. UNIT SHALL
BE DESIGNED FOR DIRECT BURIAL WITH THE JUNCTION MODULES MOUNTED
ABOVE GROUND LINE. PEDESTAL SHALL BE IN CONFORMANCE WITH ANSI
C57.12.28 ENCLOSURE IS A ONE PIECE METAL UNIT WITH SWING UP TOP.
CABLES/CONDUIT SHALL ENTER/EXIT SO THAT LOAD BREAK ELBOWS AND
CABLES MAY BE OPERATED FROM FEED THRUS ON PARKING STANDS OR
JUNCTIONS.
DO NOT INSTALL CONDUIT BENDS TO TRAIN ELBOWS. THIS SHALL ALLOW MORE
CABLE MOVEMENT AND FREEDOM FOR FUTURE SWITCHING.
INCOMING CABLES SHALL BE PROPERLY PHASED AND LABELED BEFORE THEY
ARE POSITIONED AS SHOWN.
ENCLOSURE WILL ACCEPT THREE PRIMARY JUNCTION MODULES. DO NOT
INSTALL PRIMARY JUNCTION MODULES WITH WALL MOUNTING BRACKETS.
ENCLOSURE SHALL BE CORROSION RESISTANT AND SHALL BE FABRICATED OF
STAINLESS STEEL CONFORMING TO ASTM A 167, TYPE 304 OR 304L. PAINT
ENCLOSURE MUNSELL 7GY3.29/1.5 GREEN. PAINT COATING SYSTEM SHALL
COMPLY WITH NEMA C57.12.28. THE MUNSELL COLOR NOTATION IS SPECIFIED IN
ASTM D 1535.
PROVIDE 15 KV 600 AMP ELBOW CONNECTOR FOR EACH TERMINATION.
PROVIDE FAULT INDICATORS ON EACH OUTPUT.
1.
2.
3.
4.
5.
6.
7.
NOTES:
PAD MOUNT PRIMARY TAP BOX DETAIL
NOT TO SCALE
E
E
E E
1 1
HEAT PUMP
208V, 1PH
HEAT PUMP
208V, 1PH
HEAT PUMP
208V, 3PH
HEAT PUMP
208V, 3PH
E
1 (TYP)
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
NDEMOLITION FLOOR PLAN
SCALE: 1/8" = 1'-0"
NDEMOLITION MEZZANINE FLOOR PLAN
SCALE: 1/8" = 1'-0"
REMOVE EXISTING LIGHT FIXTURE, EXISTING CIRCUITING TO REMAIN AND
BE REUSED.
EXISTING BUILDING TO BE DEMOLISHED COMPLETELY, SEE ARCHITECTURAL
PLANS.
REMOVE EXISTING AHU CONNECTION IN ATTIC SPACE.
REMOVE EXISTING WATER HEATER CONNECTION.
REMOVE EXISTING PANEL, EXISTING BRANCH CIRCUIT TO REMAIN AND BE
RECONNECTED TO NEW PANEL.
EXISTING LIGHTING CONTROL PANEL TO REMAIN.
EXISTING TELEPHONE SERVICE TO REMAIN.
NOTES THIS SHEET
20 CF
E F G H
0.5
B.1 B.7BA C D
I J K L M N O P
OC
D
V
V D
V V
D
D O
O
D
V
V
OS
OS
OSV V
O
VA
A
A
A
A
A
A
C
C
C
E E E
C
C
D D
E E
B B F F
A A
C C
E E
A
A
A
A
E
K
F
F
ALA-3
ALA-1 ALA-3
C 2
E 2 C 2
G 2 H 2
J 4 C
C C
1 TYP.
1 TYP.
1 TYP.
BABYSITTING
MECH./ ELEC.
TELECOM
OFFICE
OFFICE
VESTIBULE
MEN'S
WOMEN'S
FELLOWSHIP
HALL
KITCHEN
PANTRY
CORRIDOR
JAN.
312UNISEX O
F F
F
F
J 2 TYP
TO
RECEPTACLE
CIRCUIT
MECH.
VESTIBULE
UNISEX
ALTAR
STORAGE
CORRIDOR
CHAPEL
STORAGE
CONFESSIONAL
VESTIBULE 1
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
NNEW WORK FIRST FLOOR PLAN
SCALE: 1/8" = 1'-0"
NNEW WORK MEZZANINE FLOOR PLAN
SCALE: 1/8" = 1'-0"
RELAMP EXISTING INCANDESCENT LAMPS WITH LED LAMPS (SIX LAMPS PER
FIXTURE)
CONNECT TO EXISTING CIRCUIT RETAINED DURING DEMOLITION.
ROUTE CIRCUIT THROUGH TIME CLOCK AND PHOTOCELL, FOR CONTROL.
INTERCEPT EXISTING LIGHTING CIRCUIT AND EXTEND AS INDICATED.
INVERTER FOR "ETERNAL FLAME" LIGHT. 1000W, 120V, 1PH. INTERCEPT
EXISTING CIRCUIT AND EXTEND TO INVERTER AND EXISTING CIRCUIT
BREAKER.
NOTES THIS SHEET
STYLE NO. VOLTAGE MOUNTING NOTESFIXTURE
SYMBOL
NUMBER AND
TYPE OF LAMPS
LIGHTING FIXTURE SCHEDULE
NL-2, 2x4 LED UNIVERSAL RECESSED
SURFACE, WALL 8'-0" AFFLEDNL-67
NL-63 LED SURFACE; UNIVERSAL
UNIVERSAL
UNIVERSAL
FIXTURE LUMENS MUST BE 4800, 38 WATTS, FULLY DIMMABLE DRIVER TO 1%, USING 0-10 VCD CONTROLS. PROVIDE
EMERGENCY BATTERY WHERE INDICATED
FIXTURE LUMENS MUST BE 3300, 26 WATTS, NON-DIMMABLE DRIVER. PROVIDE EMERGENCY BATTERY WHERE INDICATED.
FIXTURE LUMENS MUST BE 4800, 32 WATTS. NON-DIMMABLE DRIVER.
FIXTURE LUMENS MUST BE 4000, 38 WATTS, NON-DIMMABLE DRIVER.
FIXTURE LUMENS MUST BE 3000. 35 WATTS, NON-DIMMABLE DRIVER, PROVIDE EMERGENCY BATTERY WHERE INDICATED.
FIXTURE LUMENS MUST BE 2000, 26 WATTS, NON-DIMMABLE DRIVER.
FIXTURE LUMENS MUST BE 3300, 26 WATTS, NON-DIMMABLE DRIVER.
FIXTURE LUMENS MUST BE 4800, 38 WATTS, NON-DIMMABLE DRIVER.
PROVIDE FIXTURE WITH TWO TYPE E HEADS, POLYCARBONATE WHITE HOUSING
PROVIDE FIXTURE WITH WHITE HOUSING AND VOLTMETER.
PROVIDE FIXTURE WITH WHITE HOUSING AND VOLTMETER. PROVIDE SINGLE FACE, RED LETTERING. UNIVERSAL
MOUNTING.
MOUNT FIXTURE TO SIDE OF BEAM. CONNECT TO EXISTING CIRCUIT. PROVIDE WITH LED LAMP 3,000 LUMENS, 6" DIAMETER FIXTURE. PROVIDE DIMMABLE LED DRIVER TO 10%, DRIVER SHALL BE COMPATIBLE WITH THE EXISTING LINE VOLTAGE
DIMMING SYSTEM.
FIXTURE LUMENS MUST BE 1320, 17 WATTS. NON-DIMMABLE DRIVER.
NL-2, 2X2 LED UNIVERSAL RECESSED
3NL-5, 1X4 LED UNIVERSAL SURFACE
NL-10, 1x4 LED UNIVERSAL SURFACE, 6" ABOVE MIRROR 4
NL-19 LED UNIVERSAL RECESSED 5
6SHEET E-501 LED UNIVERSAL SURFACE, CEILING
7NL-7 LED UNIVERSAL SURFACE, 6" ABOVE MIRROR
NL-5, 2x4 LED UNIVERSAL SURFACE 8
NL-54 LED SURFACE; WALL 8'-0"UNIVERSAL 9
SEE DETAIL
NL-20, MODIFIEDLED UNIVERSAL SURFACE 12
NL-5, 1X2 LED UNIVERSAL SURFACE 13
A
B
C
D
E
F
G
H
J
K
& TYPE
20 CF
E F G H
0.5
B.1 B.7BA C D
I J K L M N O P
AC-1
388MCA, 208V, 3PH
600A-3P, NF, 4X
MDP-38; 3 #750 KCMIL,
1 #2 GND - 4"C.
E
GFI GFI GFI
GFI
GFI
MDP
MDA
VFD
E
E
E E
E
E
VAV-2
120V, 1PH
VAV-3
120V, 1PH
VAV-1
120V, 1PH
VAV-5
120V, 1PH
VAV-4
120V, 1PH
GFI
GFI GFI
GFI
GFI
GFI GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
EWC
ALA
MDA-4
ALA-14
MDA-6
ALA-12
MDA-37; 3 #8, 1
#10 GND - 1"C.
ALA-4
MDA-2
ALA-2
E
E
MDA-1
30A-2P, FU @ 15, 4X
DSS-1B
9A, 208V, 1PH
CONTROL AND
POWER CABLE
ALA-6
ALA-8
ALA-10
ALA-24
ALA-19
VAV-6
120V, 1PH
MDA-12
ALA-23
ALA-25; 3 #6, 1 #6 GND
- 3/4"C.
ALA-21
WP
M
TO LIGHT
CIRCUIT
EF-2
120V, 1PH
ALA-16
E
VAV-7
120V, 1PH
MDA-14
EF-3
120V, 1PH
MDA-26
MDA-10 MDA-8
ALA-22
ALA-20
ALA-18
E
WH-1
9KW, 208V, 3PH
MDA-32; 3 #10, 1 #10
GND - 3/4"C.
60A-3P, NF
M
HWRP-1
120V, 1PH
MDA-30
MDP-4
MDP-2
MDP-10
MDP-8
MDP-6
WP
WP WP
WP
VAV-8
120V, 1PH
E
MDA-16
MDA-5
MDA-7
MDA-9
GFI
CLA
FACP
CLA-22
EF-1
120V, 1PH
TO LIGHT
CLA-20
E
LIFT STATION
TWO 2HP, 208V, 3PH
MDA-31, 3 #10,
1#10GND IN 3/4"C
CLA-26
A
E-201
MDA-24
EF-5
120V, 1PH
DSS-1A
E
UH-2
3KW,208V, 1PH
MDA-20
MECH.
VESTIBULE
UNISEX
ALTAR
STORAGE
CORRIDOR
CHAPEL
STORAGE
CONFESSIONAL
VESTIBULE
M
M
M M
M
M
M
M
M/WP
BABYSITTING
MECH./ ELEC.
TELECOM
OFFICE
OFFICE
VESTIBULE
MEN'S
WOMEN'S
FELLOWSHIP
HALL
KITCHEN
PANTRY
CORRIDOR
E E
E
M M
M
MDA-30
E
M
E
M
MDA-18
VAV-9
120V, 1PH
RECIR PUMP
120V, 1PH
B-1
120V, 1PH
E
M
E
M
VFD
VFD
B-2
120V, 1PH
SHWP-1
3/4HP, 208V, 3PH
SHWP-2
3/4HP, 208V, 3PH
VFD
MDP
MDP-12
MDP-3
MDP-5
MDP-13
MDP-19
MDP-1
MDP-31, 3 #6,
1 #10 GND-3/4"C
AHU-1
10 HP, 208V, 3PH
E
E
E
E
M
MM
UH-1
120V, 1PH
M
MDP-7
EF-4
120V, 1PH
WP
E
WH-2
1.6KW, 120V, 1PH
MDP-9
MDP-14
DDC PANEL, 120V
M
M
M
MDP-16
DAMPER
120V, 1PH
DAMPER
120V, 1PH
TO LIGHTS
E
MDP-11
The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
1/8" = 1'-0"
0 4' 16'8'
NNEW WORK FIRST FLOOR PLAN
SCALE: 1/8" = 1'-0"
NENLARGED PLAN - MECHANICAL ROOM
SCALE: 1/4" = 1'-0"
1/4" = 1'-0"
0 2' 8'4'
A
E-201
AHU-2: 7.5HP, 208V, 3PH
DAMPER: 120V, 1PH.
HOOD: 120V, 1PH.
PROVIDE PANEL IN SAME LOCATION AS REMOVED PANEL. RECONNECT
EXISTING CIRCUITS TO PANEL.
GAS SHUT OFF VALVE CONNECTION, 120V, 1PH.
NOTES THIS SHEET
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
REVISED: AUGUST 2004 NL-67LIGHTING PLATE:
DECORATIVE EMERGENCY LIGHTING UNIT
MR16 HALOGEN LAMPS MUST BE 5 WATTS, HIGH-OUTPUT OR AS INDICATED IN
HOUSING - UV STABLE, FLAME-RATED, HIGH-IMPACT THERMOPLASTIC IN WHITE OR
BLACK TEXTURED FINISH.
INTERNAL COMPONENTS - FULLY AUTOMATIC, SOLID STATE, CONSTANT VOLTAGE,
CURRENT-LIMITED BATTERY CHARGER; MAINTENANCE-FREE LEAD-ACID BATTERY;
EXTERIOR HOUSING INDICATORS - LED AC-ON INDICATOR AND INTEGRAL TEST SWITCH.
LAMP HEADS - UV STABLE, FLAME RATED POLYCARBONATE THERMOPLASTIC.
MOUNTING - DIRECTLY TO 4" OCTAGONAL OR SQUARE OUTLET BOX.
CERTIFICATION - UL LISTED AND LABELED. COMPLIES WITH UL 924 AND NFPA 101
OPTIONS - VOLTMETER, VANDAL-RESISTANT SHIELD, SELF-DIAGNOSTIC/TESTING7.
6.
REQUIREMENTS. LISTED FOR DAMP LOCATIONS.
LUMINAIRE REQUIREMENTS:
1.
3.
5.
4.
2.
AND BUILT-IN OVERLOAD AND LOW-VOLTAGE BATTERY PROTECTION.
13"
NOMINAL
NOMINAL
5"
MAX. DEPTH
4" NOMINAL
ELECTRONICS AND WIRE GUARD.
LIGHTING FIXTURE SCHEDULE.
HOUSING - DIE-CAST ALUMINUM OR HIGH-IMPACT, UV-STABILIZED, INJECTION-MOLDED
LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. RED OR GREEN LETTERS
FINISH (ON CAST ALUMINUM HOUSING ONLY) - TEXTURED POWDER COAT FINISH
OPTIONS INCLUDE WHITE, WHITE WITH BRUSHED ALUMINUM FACE, BLACK, OR BLACK
EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY CHARGER WITH
MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-FIXTURE
ILLUMINATION - PROVIDED BY RED, GREEN OR WHITE HIGH-OUTPUT LEDS INSIDE
1.
2.
3.
4.
5.
6.
LUMINAIRE REQUIREMENTS:
REVISED: AUGUST 2004 NL-63
MOUNTING.
THERMOPLASTIC. SINGLE OR DOUBLE-FACED AS INDICATED.
AS INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR BOTH
MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND
LIGHTING PLATE:
LED EXIT SIGN
13"
NOMINAL
NOMINAL
9"
WITH BRUSHED ALUMINUM FACE.
DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING AS REQUIRED.
TEST SWITCH.
OF FIXTURE HOUSING. PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH
FREQUENCY-MATCHED SILKSCREEN COATING FOR MAXIMUM LED LIGHT OUTPUT.
CERTIFICATION - UL LISTED AND CERTIFIED FOR DAMP LOCATIONS.7.
REMOTE EMERGENCY LIGHTING UNITS
LAMPS AND FINISHES MUST BE COMPATIBLE
WITH PRIMARY UNIT WITH WHICH USED.
FOR USE WITH BATTERY UNIT
1.
NOTES:
TYPE - C
REMOTE FIXTURES
TYPE - E
TYPE - D
TYPE - A TYPE - B
SKETCH DATE JUNE 2002 STYLE NL-54
SURFACE LED WRAPAROUND
REVISED: APRIL 2016 NL-5LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR
RIGIDITY; ENDCAPS SAME MATERIAL AS HOUSING, SECURED WITH TABS, SCREWS OR
RIVETS. OPTIONAL LENGTHS OF 2FT OR 4FT.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH
HIGH-REFLECTANCE, WHITE POLYESTER POWDER COAT, PAINTED AFTER FABRICATION.
3. LENS - 100% VIRGIN ACRYLIC, CLEAR PRISMATIC DIFFUSER WITH MINIMUM 0.1 INCH
THICKNESS, CONTINUOUSLY SUPPORTED ALONG SIDES OF LUMINAIRE.
4. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500K
CCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FOR
COLOR CONSISTENCY, AND MINIMUM EFFICACY OF 95 LUMENS/WATT. INITIAL LUMEN
OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
5. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONIC
DISTORTION. OPTIONAL STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
6. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.
COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED
WITH EMERGENCY BATTERY BACK-UP.
7. MOUNTING - SURFACE ON CEILING OR SUSPENDED.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT
MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A
CERTAIN MANUFACTURER OR PREFERENCE.
DIRECT/INDIRECT FLUORESCENT TROFFER
REVISED: APRIL 2016 NL-2LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR
RIGIDITY; ENDCAPS SECURED WITH TABS, SCREWS OR RIVETS. OPTIONAL SIZES OF 2FT
x 2FT AND 2FT x 4FT AVAILABLE.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH
HIGH-REFLECTANCE, BAKED WHITE ENAMEL OR POLYESTER POWDER COAT.
3. REFLECTORS - TWO-PIECE CURVED ALUMINUM WITH MATTE WHITE FINISH.
4. DIFFUSE BASKET - WHITE PERFORATED OR ACRYLIC.
5. LIGHT SOURCE - LINEAR T8, T5 OR TT5 WITH QUANTITY AND WATTAGE AS INDICATED IN
LUMINAIRE SCHEDULE. 3500K CCT UON; MINIMUM CRI OF 80.
6. BALLAST - PROGRAMMED-START, CLASS P, THERMALLY-PROTECTED, < 20% TOTAL
HARMONIC DISTORTION, HIGH POWER FACTOR (> 0.9), ELECTRONIC TYPE WITH 'A' SOUND
RATING. DIMMING OPTION AVAILABLE.
7. CERTIFICATIONS - UL 1598, DAMP LOCATION, UL 924 WHEN EQUIPPED WITH EMERGENCY
BATTERY BACK-UP.
8. MOUNTING - RECESSED IN SOLID OR ACOUSTICAL TILE CEILING.
9. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT
MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A
CERTAIN MANUFACTURER OR PREFERENCE.
WALL MOUNTED FLUORESCENT
REVISED: APRIL 2016 NL-10LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR
RIGIDITY; END CAPS SAME MATERIAL AS HOUSING, SECURED WITH TABS, SCREWS OR
RIVETS. WHITE ENAMEL FINISH APPLIED AFTER FABRICATION. OPTIONAL LENGTHS OF 2
FT, 3 FT OR 4 FT.
2. LENS - ACRYLIC PRISMATIC (CLEAR PRISMATIC PATTERN A12) OR WHITE OPAL, WITH
MINIMUM THICKNESS OF 0.125 IN.
3. LIGHT SOURCE - LINEAR T8, T5 OR T5HO FLUORESCENT TUBES WITH QUANTITY AND
CHARACTERISTICS AS INDICATED IN LUMINAIRE SCHEDULE.
4. BALLAST - PROGRAMMED-START, CLASS P, THERMALLY-PROTECTED, HIGH POWER
FACTOR (>0.9), ELECTRONIC TYPE WITH <20% THD AND 'A' SOUND RATING.
5. CERTIFICATION - UL 1598, DAMP LOCATION, UL 924 WHEN EQUIPPED WITH EMERGENCY
BATTERY BACK-UP.
6. MOUNTING - SURFACE ON WALL.
7. OPTIONS - EMERGENCY BACK-UP, <10% THD BALLAST, DOWNLIGHT COMPONENT ONLY.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT
MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A
CERTAIN MANUFACTURER OR PREFERENCE.
LED RECESSED DOWNLIGHT
REVISED: APRIL 2016 NL-19LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, OR FORGED ALUMINUM WITH HEAT SINK.
DRIVER MUST BE ACCESSIBLE FROM BOTTOM OF LUMINAIRE. PROVIDE T-BAR HANGERS
FOR INSTALLATION IN ACOUSTICAL TILE CEILINGS OR TABS WHEN MOUNTING IN HARD
CEILINGS.
2. REFLECTOR AND TRIM - SPECIFICATION GRADE, LOW IRRIDESCENT, SPECULAR
ALUMINUM REFLECTOR WITH METALLIC OR PAINTED TRIM RING..
3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500K
CCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FOR
COLOR CONSISTENCY, AND MINIMUM EFFICACY OF 90 LUMENS/WATT. INITIAL LUMEN
OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONIC
DISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.
COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED
WITH EMERGENCY BATTERY BACK-UP.
6. MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING.
7. OPTIONS - EMERGENCY BATTERY BACK-UP, WALL-WASH TRIM, IC RATED FOR DIRECT
CONTACT WITH INSULATION, VARIOUS APERTURE DIAMETERS, AND VARIOUS GLASS
LENSES.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT
MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A
CERTAIN MANUFACTURER OR PREFERENCE.
LED INDUSTRIAL STRIP
REVISED: APRIL 2016 NL-7LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR RIGIDITY
AND SPECULAR ALUMINUM OR HIGHLY-REFLECTIVE PAINTED STEEL REFLECTORS.
OPTIONAL LENGTHS OF 4FT OR 8FT.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH
HIGH-REFLECTANCE, WHITE POLYESTER POWDER COAT, PAINTED AFTER FABRICATION.
3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500K
CCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FOR
COLOR CONSISTENCY, AND MINIMUM EFFICACY OF 100 LUMENS/WATT. INITIAL LUMEN
OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONIC
DISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.
COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED
WITH EMERGENCY BATTERY BACK-UP.
6. MOUNTING - SURFACE ON CEILING OR SUSPENDED.
7. OPTIONS - WIRE GUARD, CHAIN, STEM OR SWIVEL STEM HANGERS.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT
MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A
CERTAIN MANUFACTURER OR PREFERENCE.
INDICATE
LENGTH
SURFACE MOUNT
TYPE A
PENDANT MOUNT
TYPE B
WALL MOUNT
TYPE C
LAMP OPTIONS
2 F13/T4 DOUBLE TWIN TUBE COMPACT FLUORESCENT LAMPS.
2 F26/T4 DOUBLE TWIN TUBE COMPACT FLUORESCENT LAMPS.
LUMINAIRE REQUIREMENTS
HOUSING - ALUMINUM .050"± THICK WITH WHITE ACRYLIC ENAMELED
FINISH. PROVIDE INTERNAL GREEN GROUNDING SCREW.
REFLECTOR - SPECULAR ALUMINUM.
BALLAST - HIGH POWER FACTOR ( > .9) ELECTROMAGNETIC BALLAST.
LENS TRIM RING - ALUMINUM WITH WHITE ACRYLIC ENAMELED
FINISH.
REGRESS - 1" MATTE BLACK FROM TRIM RING UP TO LENS.
LENS - FLAT PRISMATIC GLASS.
1.
2.
1.
2.
3.
4.
5.
6.
7.
8.
9.
SKETCH DATE JUNE 2002 STYLE NL-20
ROUND-SURFACE, PENDANT OR WALL MOUNT
COMPACT FLUORESCENT - INTERIOR/EXTERIOR
MINIMUM FIXTURE EFFICIENCY - 60%.
MINIMUM SPACING CRITERIA: 1.2
HOUSING DIMENSIONS - 12" DIA. ±1" X 6" HIGH ±1".
FIXTURE SHALL HAVE UL LABEL FOR WET OR DAMP LOCATIONS
AS INDICATED.
10.
DETAIL BASED ON LITHONIA LIGHTING, "VR4" SERIES
LUMINAIRE DESCRIPTION:
1. HOUSING MUST BE 0.054" THICK (MINIMUM) MARINE GRADE ALUMINUM
BACK PLATE.
2. HOUSING MUST BE FULLY GASKETED AROUND LENS, AND BETWEEN
LUMINAIRE AND CEILING, WITH DOUBLE BAKED NEOPRENE GASKETS.
PROVIDE INTERNAL GREEN GROUNDING SCREW.
3. LENS MUST BE PRISMATIC POLYCARBONATE HELD IN PLACE WITH 4
STAINLESS STEEL SCREWS.
4. MOUNT BACK PLATE TO CEILING WITH (4) 1/4"Ø SCREWS OR ANCHORS.
5. PROVIDE WIRING COMPARTMENT SUITABLE FOR USE WITH 60°C WIRE
INSULATION.
6. FIXTURE MUST BE UL LISTED FOR WET LOCATIONS.
TYPE LAMP # LAMP TYPE INPUT WATTS VOLTAGE MOUNTING
SURFACE, CEILING120/27726LEDNA
CEILING-MOUNTED VANDAL-RESISTANT LUMINAIRE
12"
8"
LIGHTING DETAIL F - LED
252.636.8778 (PHONE)
252.636.8992 (FAX)
WALKER
GROUP
i n c o r p o r a t e d the
ARCHITECTURE
DISCLOSURE OF INFORMATION
CONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE
(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
PANEL
MDP
800A MCB
208/120V 3P, 4W
22 KAIC
PANEL
CLA
200A MLO
208/120V 3P, 4W
22 KAIC
PANEL
MDA
225A MCB
208/120V 3P, 4W
22 KAIC
PANEL
ALA
150A MLO
208/120V 3P, 4W
22 KAIC
ELECTRICAL LOAD SUMMARY
LOAD CONNECTED DEMAND DEMAND
DESCRIPTION LOAD FACTOR LOAD
LIGHTING 17.1 KVA 100% 17.1 KVA
EXTERIOR LIGHTING 3.0 KVA 100% 3.0 KVA
RECEPTACLES 21.9 KVA NOTE - 116.0 KVA
AIR CONDITIONING 168.3 KVA 100% 168.3 KVA
HEATING 13.9 KVA 100% 13.9 KVA
VENTILATION 2.0 KVA 100% 2.0 KVA
MISCELLANEOUS 6.9 KVA 100% 6.9 KVA
KITCHEN EQUIP. 10.6 KVA 100% 10.6 KVA
WATER HEATER 15.7 KVA 100% 15.7 KVA
TOTAL 259.3 KVA 253.4 KVA
NOTES:
1. 1st 10 KVA @ 100%, REMAINDER @ 50%
PANELBOARD MDP SCHEDULE
SEE POWER RISER DIAGRAM FOR RATINGS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)
LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED
BOILER #1 4.5 20/1P 1 2 20/1P 10.0 HEAT TRACE
BOILER #2 4.5 20/1P 3 4 20/1P 10.0 HEAT TRACE
RECIRC PUMPS 7.0 20/1P 5 6 20/1P 10.0 HEAT TRACE
EF/UH 3.0 20/1P 7 8 20/1P 10.0 HEAT TRACE
WH-2 13.8 20/1P 9 10 20/1P 10.0 HEAT TRACE
GAS VALVE 1.5 20/1P 11 12 20/1P 3.0 RECEPTACLES
SHWP-1 3.5 20/3P 13 14 20/1P 3.0 DDC
3.5 16 20/1P 5.0 DAMPERS
3.5 18 20/1P SPARE
SHWP-2 3.5 20/3P 19 20 20/1P SPARE
3.5 22 20/1P SPARE
3.5 24 20/1P SPARE
PANEL CLA 92.5 200/3P 25 26 20/1P SPARE
70.0 28 20/1P SPARE
90.0 30 20/1P SPARE
AHU-1 30.8 60/3P 31 32 225/3P 197.2 PANEL MDA
30.8 201.6
30.8 138.6
SPD 60/3P 37 38 450/3P 388.0 CHILLER
388.0 388.0
TOTAL 137.8 126.1 136.3 608.2 614.6 539.6 TOTAL
TOTAL CONNECTED AMPS A: 746.0 B: 740.7 C: 675.9
PANELBOARD CLA SCHEDULE
SEE POWER RISER DIAGRAM FOR RATINGS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)
LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED
LTG/RECEPT LEFT 5.0 20/1P 1 2 20/1P 10.0 STEEPLE LIGHTS
LTG/RECEPT CONFESS 5.0 20/1P 3 4 20/1P 5.0 LTG/RECEPT STORAGE
RECEPT - LOFT 5.0 20/1P 5 6 20/1P 5.0 LTG/RECEPT ATTIC
WATER HTR STORAGE 12.0 20/1P 7 8 20/1P 5.0 LTG/RECEPT FOYER
LTG/RECEPT STORAGE 5.0 20/1P 9 10 20/1P SPARE
LTG/RECEPT RIGHT 5.0 20/1P 11 12 20/1P 5.0 LTG ELEC & TOILET
RECEPT - STORAGE 5.0 20/1P 13 14 20/1P 5.0 LTG - BACK HALL
TRACK - BACK STAGE 5.0 20/1P 15 16 20/1P 5.0 TRACK LIGHTING
TRACK - CNR STAGE 5.0 20/1P 17 18 20/1P SPARE
RECEPT - BACK STAGE 5.0 20/1P 19 20 20/1P 1.5 RECEPT - TOILET
RECEPT - BACK STAGE 5.0 20/1P 21 22 20/1P 5.0 FIRE ALARM
DIMMER PANEL 35.0 60/3P 23 24 40/1P 30.0 WATER HEATER
35.0 26 20/1P 9.0 RECEPT -ALTER
35.0 28 20/1P SPARE
SPARE 20/1P 29 30 20/1P SPARE
SPARE 20/1P 31 32 20/1P SPARE
SPARE 20/1P 33 34 20/1P SPARE
SPARE 20/1P 35 36 20/1P SPARE
SPARE 20/1P 37 38 20/1P SPARE
SPARE 20/1P 39 40 20/1P SPARE
SPARE 20/1P 41 42 20/1P SPARE
TOTAL 62.0 55.0 50.0 30.5 15.0 40.0 TOTAL
TOTAL CONNECTED AMPS A: 92.5 B: 70.0 C: 90.0
PANELBOARD MDA SCHEDULE
SEE POWER RISER DIAGRAM FOR RATINGS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)
LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED
TELE RM AC 9.0 15/2P 1 2 20/1P 5.8 VAV-1
DSS-A & B 9.0 4 20/1P 5.8 VAV-2
RECEPT - TEL ROOM 3.0 20/1P 5 6 20/1P 5.8 VAV-3
RECEPT - TEL ROOM 3.0 20/1P 7 8 20/1P 5.8 VAV-4
RECEPT - TEL ROOM 4.5 20/1P 9 10 20/1P 5.8 VAV-5
SPARE 20/1P 11 12 20/1P 5.8 VAV-6
SPARE 20/1P 13 14 20/1P 5.8 VAV-7
SPARE 20/1P 15 16 20/1P 5.8 VAV-8
SPARE 20/1P 17 18 20/1P 5.8 VAV-9
SPARE 20/1P 19 20 20/2P 14.4 UH-2
SPARE 20/1P 21 14.4
SPARE 20/1P 23 24 20/1P 3.0 EF-4
SPARE 20/1P 25 26 20/1P 2.4 EF-3
SPARE 20/1P 27 28 20/1P 3.0 DAMPERS
SPARE 20/1P 29 30 20/1P 2.7 HW RECIRC PUMP
LIFT STATION 18.7 30/3P 31 32 40/3P 25.0 WH-1
18.7 25.0
18.7 25.0
AHU-2 24.2 50/3P 37 38 150/3P 83.1 PANEL ALA
24.2 85.4
24.2 44.6
TOTAL 54.9 56.4 45.9 142.3 145.2 92.7 TOTAL
TOTAL CONNECTED AMPS A: 197.2 B: 201.6 C: 138.6
PANELBOARD ALA SCHEDULE
SEE POWER RISER DIAGRAM FOR RATINGS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)
LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED
LIGHTING 7.5 20/1P 1 2 20/1P 7.5 RECEPT - 311
LIGHTING 4.9 20/1P 3 4 20/1P 6.0 RECEPT - 311
EXTERIOR LIGHTING 4.0 20/1P 5 6 20/1P 3.0 RECEPT - 311
EXTERIOR LIGHTING 4.1 20/1P 7 8 20/1P 3.0 RECEPT - 311
EXTERIOR LIGHTING 12.5 20/1P 9 10 20/1P 4.5 RECEPT - 311
EXTERIOR LIGHTING 4.1 20/1P 11 12 20/1P 10.5 RECEPT - 307
SPARE 20/1P 13 14 20/1P 7.5 RECEPT - 308
SPARE 20/1P 15 16 20/1P 10.5 RECEPT - TOILETS
SPARE 20/1P 17 18 20/1P G 12.5 REECPT - EWC
RECEPT - KIT 314 12.5 20/1P 19 20 20/1P 6.0 RECETP - 304
RECEPT - KIT 314 3.0 20/1P 21 22 20/1P 9.0 RECETP - 304
RECEPT - KIT 314 3.0 20/1P 23 24 20/1P 7.5 RECETP - 304
OVEN 35.0 50/2P 25 26 20/1P SPARE
35.0 28 20/1P SPARE
SPARE 20/1P 29 30 20/1P SPARE
SPARE 20/1P 31 32 20/1P SPARE
SPARE 20/1P 33 34 20/1P SPARE
SPARE 20/1P 35 36 20/1P SPARE
SPARE 20/1P 37 38 20/1P SPARE
SPARE 20/1P 39 40 20/1P SPARE
SPARE 20/1P 41 42 20/1P SPARE
TOTAL 59.1 55.4 11.1 24.0 30.0 33.5 TOTAL
TOTAL CONNECTED AMPS A: 83.1 B: 85.4 C: 44.6
G - INDICATED GFI CIRCUIT BREAKER
POWER RISER DIAGRAM
NOT TO SCALE
SERVICE GROUND:
1 #6 - 1/2"C TO GROUND ROD
1 #3/0 - 1/2"C TO WATER SERVICE
1 #3/0 - 1/2"C TO BUILDING STEEL
1 #3/0 - 1/2"C TO REBAR IN SLAB
SERVICE GROUND:
1 #6 - 1/2"C TO GROUND ROD
1 #2 - 1/2"C TO WATER SERVICE
1 #2 - 1/2"C TO BUILDING STEEL
1 #2 - 1/2"C TO REBAR IN SLAB
4 #1/0, 1 #6 GND - 2"C
4 - #4/0, 1 #4 GND - 2-1/2"C
4 #3/0, 1 #6 GND - 2-1/2"C
TWO 4" CONDUITS WITH
4- 600 KCMIL IN EACH CONDUIT AND ONE
SPARE 4"C TO TRANSFORMER
SPD
4 #6, 1 #8 GND - 3/4"C
CC
TC
P
SITE LIGHTING CONTACTOR:
6 POLE, 120V, 20A.
CONTROL MUST BE
PHOTOCELL ON,
TIME CLOCK OFF
TO SITE LIGHTING
CIRCUITS
SEE PRIMARY ONE-LINE
DIAGRAM SHEET ES102
FOR CONTINUATION
Name: Service Transformer "X" * Type: 120/208, 3p, 150kVA Source N/A Impedance (%Z) 2 Voltage 208 KVA 150 Phase 3 Full Load Amps 417 Voltage Fluctuation: 1.05 Multiplier 50.00 Fault Current 21885
Name: Panel MDP * Conductor Size: 600KCMIL Source: Service Transformer "X" Material: Copper Voltage 208 Conduit Type: Non-Magnetic Phase 3 5 Voltage Rating: Up To 5KV Available Fault Current 21885 Constant 25000 Multiplier 0.846 Conductors/Phase: 2 Fault Current 18515 Length (ft): 50 Load (Amps): 630 1.1 Voltage Drop (%) 1.1 (0.5%)
Name: Panel "CLA" * Conductor Size: #3/0 Source: Panel MDP Material: Copper Voltage 208 Conduit Type: Magnetic Phase 3 7 Voltage Rating: Up To 5KV Available Fault Current 18515 Constant 10638 Multiplier 0.580 Conductors/Phase: 1 Fault Current 10741 Length (ft): 50 Load (Amps): 160 1.3 Voltage Drop (%) 1.3 (0.6%) Name: Panel "MDA" * Conductor Size: #4/0 Source: Panel MDP Material: Copper Voltage 208 Conduit Type: Non-Magnetic Phase 3 5 Voltage Rating: Up To 5KV Available Fault Current 18515 Constant 13514 Multiplier 0.467 Conductors/Phase: 1 Fault Current 8654 Length (ft): 100 Load (Amps): 180 2.3 Voltage Drop (%) 2.3 (1.1%) Name: Panel "ALA" * Conductor Size: #1/0 Source: Panel "MDA" Material: Copper Voltage 208 Conduit Type: Magnetic Phase 3 7 Voltage Rating: Up To 5KV Available Fault Current 8654 Constant 7692 Multiplier 0.914 Conductors/Phase: 1 Fault Current 7913 Length (ft): 10 Load (Amps): 120 0.3 Voltage Drop (%) 0.3 (0.1%)
| 60025695 |
| 60025696 |
| 60025697 |
| 60025698 |
| Sheets and Views |
| E-201 . |
| 60025699 |
| 60025700 |
| 60025701 |