For steam pipe insulation, the specification establishes thickness requirements across three primary material types: Fibrous Glass (ranging from 3.5 to 5 inches depending on pipe diameter), Calcium Silicate (ranging from 4 to 6 inches), and Cellular Glass (marked with asterisks indicating equivalent performance alternatives). Insulation thickness increases with pipe diameter, with 1-inch to 2.5-inch pipes requiring 3.5 inches of Fibrous Glass or 4 inches of Calcium Silicate, while larger diameter pipes (8-16 inches) require 5 inches of Fibrous Glass or 6 inches of Calcium Silicate. For condensate pipe insulation, the specification provides minimum thickness requirements for Mineral Fiber (ranging from 2.5 to 3.5 inches) and Fibrous Glass (marked as acceptable alternatives). Condensate pipe sizes range from 1 inch to 18 inches in nominal diameter, with Mineral Fiber thicknesses of 2.5 inches for pipes up to 2.5 inches in diameter, increasing to 3 inches for 3-4 inch pipes and 3.5 inches for pipes 5 inches and larger. The specification includes performance equivalency provisions allowing Fibrous Glass and Cellular Glass materials to substitute for specified materials when they demonstrate insulating efficiency not less than the designated thickness of the alternative material.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Nominal pipe Diameter (Inches)

Fibrous Glass (inches)

Calcium Silicate (inches)

Cellular Glass (inches)

1 3.5 4 *

1.5 3.5 4 * 2 3.5 4 *

2.5 3.5 4 * 3 4 4.5 * 4 4 4.5 * 5 4.5 5 * 6 4.5 5 * 8 5 6 *

10 5 6 * 12 5 6 * 14 5 6 * 16 5 6 *

Nominal pipe Diameter (Inches)

Mineral Fiber (inches)

Fibrous Glass (inches)

1 2.5 *

1.5 2.5 * 2 2.5 *

2.5 2.5 * 3 3 * 4 3 * 5 3.5 * 6 3.5 * 8 3.5 *

10 3.5 * 12 3.5 * 14 3.5 * 16 3.5 * 18 3.5

STEAM PIPE:

CONDENSATE PIPE:

*Fibrous glass pipe insulation having an insulating efficiency not less than that of the specified thickness of mineral fiber may be provided.