2024_1811182_Install canopies for F-31 and F-14 pads_Amendment-0001.pdf

PDF 13 MB Posted

Attached to
INSTALL CANOPY FOR F-14 PAD & F-31 PAD AIRFIELD, NAS OCEANA
Solicitation number
N4008525R2652
Issued by

About this file

This document is a comprehensive set of construction drawings for the installation of canopies at F-14 and F-31 pads at Naval Air Station Oceana in Virginia Beach, Virginia. The project involves installing steel canopies over existing concrete pads, with detailed structural, electrical, and architectural plans spanning 24 sheets. Key technical specifications include:

Structural details show the canopies will be constructed using HSS 6x6x5/16 steel columns, W12 sloped beams, and C10 and C12 channel members, with foundations designed to connect to existing concrete pedestals. The roof will utilize 1.5" deep steel deck with standing seam metal roofing, and the design accounts for specific wind load parameters per ASCE 7-16 standards. Electrical components include LED explosion-proof low bay lighting fixtures rated for Class I, II, and III environments, powered by existing electrical infrastructure, with photocell and lighting contactor controls. The project is being executed by the Naval Facilities Engineering Systems Command Mid-Atlantic, with a final drawing date of 11/26/2024 and an amendment dated 04/23/2025.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WILLOUGHBY BAY

NAVAL SUPPORT

ACTIVITY

U.S. NAVAL STATION

SEWELLS POINT

NORFOLK

U.S. NAVAL

AIR STATION

CHESAPEAKE BAY

LITTLE CREEK

U.S. NAVAL

AMPHIBIOUS BASE

VA BEACH

OCEANA

NAVAL AIR

STATION

CHESAPEAKE

SOUTHERN BRANCH

EASTERN BRANCH

ST. JULIEN'S CREEK

U.S. NAVAL ANNEX

ELIZABETH RIVER

PORTSMOUTH

U.S. ARMY CRANEY

ISLAND DISPOSAL AREA

NANSEMOND RIVER

WESTERN BRANCH

CRANEY

ISLAND NAVY

DEPOT

PROJECT SITE

NORTH

NORTH

F-31 PAD

F-14 PAD

NAVAL AIR STATION OCEANA - VIRGINIA BEACH, VIRGINIA

NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

MID-ATLANTIC

NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND PWD OCEANA,

FACILITIES ENGINEERING AND ACQUISITION DIVISION (FEAD)

FINAL - 11/26/2024

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:3

:4

P

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

G-001

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

C O

V E

R S

H E

E T

CBM

12916615

JLP JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

G -0

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

INSTALL CANOPY AT F-14 AND F-31 PADS

SCALE: NOT TO SCALE

VICINITY MAP

SCALE: NOT TO SCALE

LOCATION MAP

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

A

M E

N D

M E

N T

/2 3/

NIC

ROOM

A1 A-201

ROOM IDENTIFIER

DETAIL NUMBER

SHEET WHERE DRAWN

DETAIL TAG

ROOM NAME

ROOM NUMBER

A-401 INTERIOR ELEVATION

INDICATOR

INTERIOR ELEVATION NUMBER

SHEET WHERE DRAWN

DETAIL NUMBER

SHEET

REFERENCED FROM

EXTERIOR ELEVATION

INDICATOR

ELEVATION NUMBER

DIRECTION OF VIEW

SHEET WHERE DRAWN

A1 A-301

WALL / PARTIAL

BUILDING SECTION

INDICATOR

SECTION NUMBER

SHEET WHERE DRAWN

GENERAL PROJECT SYMBOLS

A1 A-301

BUILDING SECTION

INDICATOR

SECTION NUMBER

SHEET WHERE DRAWN

A1 A-301

BUILDING

KEYNOTE INDICATOR

KEYNOTE NUMBER

A-901 PHOTOGRAPH

INDICATOR

PHOTOGRAPH NUMBER

SHEET WHERE SHOWN

A1

PLAN

NORTH

TRUE NORTH

A-101

A1

A1

A1

A1

A1

SCALE: 1/8" = 1'-0"

PLAN TITLE

A1

DETAIL/SECT/ELEV

SCALE: 1/8" = 1'-0"

A1

A-101

AR ANCHOR ROD

AFF ABOVE FINISHED FLOOR

AHR ANCHOR

APPROX APPROXIMATELY

ARCH ARCHITECTURAL

BD BAR DIAMETER

BOC BOTTOM OF CONCRETE

BOS BOTTOM OF STEEL

BRG BEARING

CFS COLD-FORMED STEEL

CJ CONSTRUCTION JOINT

CL CENTERLINE

CLR CLEAR

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONN CONNECTION

CONC CONCRETE

CONT CONTINUOUS

CTJ CRACK CONTROL JOINT

DCJ DOWELED CONTRACTION / CONSTRUCTION JOINT

DIA Ø DIAMETER

DN DOWN

DWG DRAWING

EA EACH

EF EACH FACE

EJ EXPANSION JOINT

ELEV ELEVATION

EOS EDGE OF SLAB

EQ EQUAL

EW EACH WAY

FD FLOOR DRAIN

FFE FINISHED FLOOR ELEVATION

FOB FACE OF BRICK

FTG FOOTING

GA GAGE

GALV GALVANIZED

HORIZ HORIZONTAL

HS HIGH-STRENGTH

HSS HOLLOW STRUCTURAL SECTION

JBE JOIST BEARING ELEVATION

KIP (k) 1000 LBS

LG LONG

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LRFD LOAD AND RESISTANCE FACTOR DESIGN

MAX MAXIMUM

MFR MANUFACTURER

MIN MINIMUM

MOW MIDDLE OF WALL

NIC NOT IN CONTRACT

NO. NUMBER

NTS NOT TO SCALE

OC ON CENTER

OPP OPPOSITE

PJF PREMOLDED JOINT FILLER

PL PLATE

PLF POUNDS PER LINEAR FOOT

PSF POUNDS PER SQUARE FOOT

REINF REINFORCING

REQD REQUIRED

SCHED SCHEDULE

SD SLAB DEPRESSION

SF STEPPED FOOTING

SIM SIMILAR

SJ SLAB SAWED (CONTRACTION) JOINT

SL SLOPE(D)

SOG SLAB-ON-GRADE

STD STANDARD

SWP SHEAR WALL PANEL

T&B TOP AND BOTTOM

TOC TOP OF CONCRETE

TOF TOP OF FOOTING

TOM TOP OF MASONRY

TOS TOP OF STEEL

TS THICKENED SLAB

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

VERT VERTICAL

WP WORKING POINT

WR WIDE RIB

WWR WELDED WIRE REINFORCEMENT

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:4

P

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

G-002

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

L

IS

T O

F S

H E

E T

S

CBM

12916616

JLP JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

G -0

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

LIST OF SHEETS

SHEET NO.

NAVFAC DWG. NO. SHEET TITLENO. SHEET

GENERAL

1 G-001 12916615 COVER SHEET

2 G-002 12916616 LIST OF SHEETS

3 G-101 12916617 LAYDOWN AREA PLANS

SURVEY

4 V-101 12916618 EXISTING CONDITIONS PLAN (F-14)

5 V-102 12916619 EXISTING CONDITIONS PLAN (F-31)

6 V-901 12916620 AERIAL AND SITE PHOTOGRAPHS (F-14)

7 V-902 12916621 AERIAL AND SITE PHOTOGRAPHS (F-31)

CIVIL

8 C-101 12916622 SITE IMPROVEMENTS PLAN (F-14)

9 C-102 12916623 SITE IMPROVEMENTS PLAN (F-31)

STRUCTURAL

10 S-001 12916624 STRUCTURAL NOTES

11 S-101 12916625 STRUCTURAL PLANS - F-14 PAD

12 S-102 12916626 STRUCTURAL PLANS - F-31 PAD

13 S-501 12916627 STRUCTURAL FOUNDATION DETAILS

14 S-502 12916628 STRUCTURAL FOUNDATION DETAILS

15 S-503 12916629 STRUCTURAL FRAMING DETAILS

16 S-504 12916630 STRUCTURAL FRAMING DETAILS

17 S-505 12916631 STRUCTURAL FRAMING DETAILS

ARCHITECTURAL

18 A-101 12916632 ROOF PLANS

19 A-501 12916633 DETAILS

ELECTRICAL

20 E-001 12916634 ELECTRICAL SYMBOLS, LEGEND, ABBREVIATIONS, AND NOTES

21 ED101 12916635 DEMOLITION PLAN - F-31 PAD

22 E-101 12916636 ELECTRICAL PLANS - F-31 PAD

23 E-102 12916637 ELECTRICAL PLANS - F-14 PAD

24 E-501 12916638 ELECTRICAL DETAILS

GENERAL PROJECT NOTES GOVERNING REGULATIONS

1 WHERE EXISTING CONSTRUCTION IS DAMAGED BY CONSTRUCTION

REQUIRED BY THESE DOCUMENTS. REPAIR THE DAMAGED ITEM(S) WITH

MATERIALS TO MATCH THE ADJACENT MATERIAL, TEXTURE AND COLOR.

2 FIELD VERIFY EXISTING DIMENSIONS, PRIOR TO ORDERING MATERIALS OR

BEGINNING DEMOLITION.

3 ALL ITEMS NOT SHOWING AS "EXISTING" MUST BE PROVIDED AND

INSTALLED UNDER THE REQUIREMENTS OF THIS CONTRACT.

4 COORDINATE LAY DOWN AREA WITH THE CONTRACTING OFFICER PRIOR TO

THE PRECONSTRUCTION MEETING. THE ALLOWABLE AREA SIZE MUST BE

ESTABLISHED BY THE CONTRACTING OFFICER.

5 MANUFACTURER'S TRADE NAMES LISTED ARE NOT INTENDED TO BE

PROPRIETARY. PRODUCTS OF OTHER MANUFACTURERS WILL BE

ACCEPTABLE PROVIDED THEY MATCH THE COLOR, FINISHES, TEXTURES

AND PATTERNS OF THE MANUFACTURER LISTED, AND MEET THE TECHNICAL

REQUIREMENTS OF THE SPECIFICATIONS.

6 OBSERVE AND MAINTAIN BUILDING AND COMPOUND SECURITY

REQUIREMENTS AS DIRECTED BY THE CONTRACTING OFFICER.

7 CONSTRUCTION WILL BE ACCOMPLISHED IN AND AROUND AREAS WHICH

WILL REMAIN OPERATIONAL. AVOID INTERFERENCE WITH THE OPERATIONAL

WORK ROUTINE.

8 ALL SUBMITTALS REQUIRED BY THESE DRAWINGS OR SPECIFICATIONS

MUST BE SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL TO

COMMENCEMENT OF RELATED WORK.

9 ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND

WITH THE AIRFIELD MANAGER (JAMES “GRAMPS” MCDOWELL). IT IS THE

PRIME CONTRACTOR'S RESPONSIBILITY TO ENSURE EMPLOYEES

OPERATING VEHICLES ON THE AIRFIELD POSSESS AN AIRFIELD DRIVER'S

LICENSE, OR COORDINATE AIR OPERATIONS ESCORTS THROUGH THE

CONTRACTING OFFICER. RADIO COMMUNICATIONS MUST BE MAINTAINED

WITH THE CONTROL TOWER BEFORE AND DURING WORK IN THE

CONTROLLED ZONES OF THE AIRFIELD. THE CONTROL TOWER MUST BE

ADVISED WHEN WORK IS COMPLETED DAILY. A RADIO FOR THIS PURPOSE

CAN BE SIGNED OUT AT THE CONTROL TOWER.

BUILDING CODE:

UNIFIED FACILITIES CRITERIA (UFC) 1-200-01 (20 JUNE 2016)

UNIFIED FACILITIES CRITERIA (UFC) 1-200-02 (01 DEC. 2016)

UNIFIED FACILITIES CRITERIA (UFC) 3-110-03 (01 MAY 2012)

ACCESSIBILITY CODE:

UNIFORM ACCESSIBILITY STANDARDS (UFAS)

AMERICANS WITH DISABILITIES ACT (ADA)

ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES (ADAAG)

MECHANICAL CODE:

INTERNATIONAL MECHANICAL CODE (IMC) 2009

ELECTRICAL CODE:

NFPA 70, NATIONAL ELECTRIC CODE

PLUMBING CODE:

INTERNATIONAL PLUMBING CODE (IPC) 2009

FIRE PREVENTION & LIFE SAFETY CODE:

UNIFIED FACILITIES CRITERIA (UFC) 3-600-01 (15 DEC. 2009)

NFPA 101, LIFE SAFETY CODE

ABBREVIATION LIST

M A

R K

D E

S C

R

IP

TI

O

N D

A T

E

A

M E

N D

M E

N T

/2 3/

NIC

NIC

NIC

NIC

NIC

NIC

LAYDOWN AREA

F-14 PAD

F-7

LAYDOWN AREA

F-31 PAD

F-23

F-26

F-22F-21

F-29

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:4

P

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

G-101

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

L A

Y D

O W

N A

R E

A P

L A

N S

CBM

12916617

JLP JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

G -1

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

SCALE: 1" = 30'-0"

A1

LAYDOWN AREA PLAN F-14 PAD

SCALE: 1" = 30'-0"

A3

LAYDOWN AREA PLAN F-31 PAD

PLAN

NORTH

PLAN

NORTH

M A

R K

D E

S C

R

IP

TI

O

N D

A T

E

A

M E

N D

M E

N T

/2 3/

GENERAL SHEET NOTES

GRAPHIC SCALE

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

SURVEY NOTES

EXISTING CONDITIONS PLAN (F-14)

N

F-14 PAD

NAVY ROAD

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

~M

ID

LA

NT

M

ID

LA

N T

PW

D

O C

EA

N

A N

AV

AL

A

IR

S

TA

TI

O

N O

C

EA

N A

- V

IR

G

IN

IA

B

EA

C

H , V

IR

G

IN

IA

N

AV

AL

A

IR

S

TA

TI

O N

O C

EA

N

A

VI

R G

IN

IA

B

EA

C H

, V

IR

G

IN

IA

IN

S

TA

LL

C A

N O

P Y

A T

F-

A N

D F

-3

P A

D S

03 Sept 2024

CBM/JLP

TWA

1811182

Approved by George Heider, Facilities Operations Specialist. with NAVSUP FLCN Oceana, via Email.

EX

IS

TI

N

G C

O N

D

IT

IO

N

S

PL

AN

(F

-1 4)

HRB HRB CBM

AS NOTED

12916618

V-101

HSDC

GENERAL SHEET NOTES

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

SURVEY NOTES

EXISTING CONDITIONS PLAN (F-31)

N

F-31 PAD

HO

RS

EH

O E

DR

IV

EW

AY

A T

FU

EL

S

F-23

DAY TANK

F-20

F-26

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

~M

ID

LA

NT

M

ID

LA

N T

PW

D

O C

EA

N

A N

AV

AL

A

IR

S

TA

TI

O

N O

C

EA

N A

- V

IR

G

IN

IA

B

EA

C

H , V

IR

G

IN

IA

N

AV

AL

A

IR

S

TA

TI

O N

O C

EA

N

A

VI

R G

IN

IA

B

EA

C H

, V

IR

G

IN

IA

IN

S

TA

LL

C A

N O

P Y

A T

F-

A N

D F

-3

P A

D S

03 Sept 2024

CBM/JLP

TWA

1811182

Approved by George Heider, Facilities Operations Specialist. with NAVSUP FLCN Oceana, via Email.

EX

IS

TI

N

G C

O N

D

IT

IO

N

S

PL

AN

(F

-3 1)

HRB HRB CBM

AS NOTED

12916619

V-102

N.I.C.

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GOOGLE EARTH AERIAL IMAGE OF F-14 SITEC1

PHOTOGRAPH LOOKING SOUTHWESTA1 PHOTOGRAPH LOOKING SOUTHEASTA3

N

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

~M

ID

LA

NT

M

ID

LA

N T

PW

D

O C

EA

N

A N

AV

AL

A

IR

S

TA

TI

O

N O

C

EA

N A

- V

IR

G

IN

IA

B

EA

C

H , V

IR

G

IN

IA

N

AV

AL

A

IR

S

TA

TI

O N

O C

EA

N

A

VI

R G

IN

IA

B

EA

C H

, V

IR

G

IN

IA

IN

S

TA

LL

C A

N O

P Y

A T

F-

A N

D F

-3

P A

D S

03 Sept 2024

CBM/JLP

TWA

1811182

Approved by George Heider, Facilities Operations Specialist. with NAVSUP FLCN Oceana, via Email.

AE

R

IA

L

AN

D

S

IT

E

PH

O

TO

G R

AP

H

S (F

-1 4)

HRB HRB CBM

AS NOTED

12916620

V-901

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GOOGLE EARTH AERIAL IMAGE OF F-31 SITEC1

PHOTOGRAPH LOOKING NORTHEASTA1 PHOTOGRAPH LOOKING SOUTHEASTA3

N

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

~M

ID

LA

NT

M

ID

LA

N T

PW

D

O C

EA

N

A N

AV

AL

A

IR

S

TA

TI

O

N O

C

EA

N A

- V

IR

G

IN

IA

B

EA

C

H , V

IR

G

IN

IA

N

AV

AL

A

IR

S

TA

TI

O N

O C

EA

N

A

VI

R G

IN

IA

B

EA

C H

, V

IR

G

IN

IA

IN

S

TA

LL

C A

N O

P Y

A T

F-

A N

D F

-3

P A

D S

03 Sept 2024

CBM/JLP

TWA

1811182

Approved by George Heider, Facilities Operations Specialist. with NAVSUP FLCN Oceana, via Email.

AE

R

IA

L

AN

D

S

IT

E

PH

O

TO

G R

AP

H

S (F

-3 1)

HRB HRB CBM

AS NOTED

12916621

V-902

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NEW WORK KEYNOTES

SITE IMPROVEMENTS PLAN (F-14)

N

F-14 PAD

NAVY ROAD

TOPSOIL AND SEED

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

~M

ID

LA

NT

M

ID

LA

N T

PW

D

O C

EA

N

A N

AV

AL

A

IR

S

TA

TI

O

N O

C

EA

N A

- V

IR

G

IN

IA

B

EA

C

H , V

IR

G

IN

IA

N

AV

AL

A

IR

S

TA

TI

O N

O C

EA

N

A

VI

R G

IN

IA

B

EA

C H

, V

IR

G

IN

IA

IN

S

TA

LL

C A

N O

P Y

A T

F-

A N

D F

-3

P A

D S

03 Sept 2024

CBM/JLP

TWA

1811182

Approved by George Heider, Facilities Operations Specialist. with NAVSUP FLCN Oceana, via Email.

SI

TE

IM

PR

O

VE

M

EN

TS

P

LA

N

(F -1

4)

HRB HRB CBM

AS NOTED

12916622

C-101

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

SITE IMPROVEMENTS PLAN (F-31)

N

F-31 PAD

HO

RS

EH

O E

DR

IV

EW

AY

A T

FU

EL

S

F-23

DAY TANK

F-20

F-26

NEW WORK KEYNOTES

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

~M

ID

LA

NT

M

ID

LA

N T

PW

D

O C

EA

N

A N

AV

AL

A

IR

S

TA

TI

O

N O

C

EA

N A

- V

IR

G

IN

IA

B

EA

C

H , V

IR

G

IN

IA

N

AV

AL

A

IR

S

TA

TI

O N

O C

EA

N

A

VI

R G

IN

IA

B

EA

C H

, V

IR

G

IN

IA

IN

S

TA

LL

C A

N O

P Y

A T

F-

A N

D F

-3

P A

D S

03 Sept 2024

CBM/JLP

TWA

1811182

Approved by George Heider, Facilities Operations Specialist. with NAVSUP FLCN Oceana, via Email.

SI

TE

IM

PR

O

VE

M

EN

TS

P

LA

N

(F -3

1)

HRB HRB CBM

AS NOTED

12916623

C-102

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:4

A

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

S-001

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

S T

R U

C T

U R

A L N

O T

E S

Checker

12916624

Designer Author

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

S -0

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

1. DO NOT PLACE CONCRETE WHEN AMBIENT TEMP IS BELOW 40°F.

2. WATER CURE ALL CONCRETE FOR 7 DAYS BEGINNING IMMEDIATELY AFTER

PLACEMENT. CURING MUST BE WITH FORMS REMAINING IN PLACE AND BY

WETTING THE EXPOSED NON-FORMED SURFACES THOROUGHLY AND

COVERING WITH ASTM C171 POLYETHYLENE FILM. EXPOSED CONCRETE MUST

BE MAINTAINED AS CONSTANTLY WET.

3. REINFORCING MUST BE ASTM 615, GRADE 60, DEFORMED.

4. LAP CONTINUOUS REINFORCING STEEL A MINIMUM LENGTH OF 48X BAR

DIAMETERS OF THE SMALLER BAR BEING LAPPED.

5. CONCRETE COVER TO REINFORCING STEEL MUST CONFORM TO THE MINIMUM

COVER RECOMMENDATIONS IN ACI 318-14 UNLESS THE DRAWINGS SHOW

GREATER COVER REQUIREMENTS.

6. CONCRETE WORK MUST BE PERFORMED IN ACCORDANCE WITH ACI 301,

UNLESS OTHERWISE NOTED.

7. CONCRETE SPECIFICATION:

A. CEMENT MUST CONFORM TO ASTM C150, TYPE I OR II

B. f'c = 4,500 PSI AT 28 DAYS

C. 1" MAXIMUM COARSE AGGREGATE

D. W/C RATIO = 0.45 MAXIMUM

E. AIR ENTRAINMENT = 6%, ±1.5%

8. PERFORM COMPRESSIVE TESTS PER ASTM C39. OBTAIN ONE SET OF FIVE (5)

CYLINDERS PER TRUCK. TEST 2 CYLINDERS AT 7-DAYS, 2 CYLINDERS AT 28-

DAYS, AND HOLD ONE IN RESERVE.

9. PERFORM SLUMP TESTS PER ASTM C143. PERFORM TESTS AT

COMMENCEMENT OF CONCRETE PLACEMENT, WHEN TEST CYLINDERS ARE

MADE, AND FOR EACH BATCH OF CONCRETE.

10. CONSOLIDATE CONCRETE PLACEMENT USING VIBRATORS PER

SPECIFICATIONS. MAINTAIN SPARE VIBRATORS ON SITE AS BACKUP.

EXCAVATION AND FILL NOTES

1. EXERCISE EXTREME CAUTION DURING DEMOLITION/EXCAVATION. LOCATION

OF THE KNOWN EXISTING UTILITIES IS APPROXIMATE. PHYSICALLY VERIFY

THE LOCATION AND ELEVATION OF ALL INDICATED EXISTING UTILITIES TO THE

GREATEST EXTENT POSSIBLE PRIOR TO STARTING THE DEMOLITION AND/OR

EXCAVATION PROCESS. SCAN THE CONSTRUCTION SITE WITHIN THE

NECESSARY LIMITS OF DEMOLITION/EXCAVATION WITH ELECTROMAGNETIC

AND SONIC EQUIPMENT IN ORDER TO IDENTIFY THE PRESENCE AND LOCATION

OF ALL KNOWN AND UNKNOWN EXISTING UTILITIES PRIOR TO STARTING THE

DEMOLITION/EXCAVATION PROCESS. MARK THE SURFACE OF THE GROUND

WHERE SUBSURFACE UTILITIES ARE LOCATED. IF ADDITIONAL SUBSURFACE

UTILITIES OTHER THAN THOSE INDICATED ARE DISCOVERED AT ANY TIME

DURING THE EXECUTION OF WORK, IT MUST IMMEDIATELY BE BROUGHT TO

THE ATTENTION OF THE CONTRACTING OFFICER.

2. EXCAVATE TO CONTOURS, ELEVATIONS, AND DIMENSIONS INDICATED. REUSE

EXCAVATED MATERIALS THAT MEET THE SPECIFIED REQUIREMENTS FOR THE

MATERIAL TYPE REQUIRED AT THE INTENDED LOCATION. KEEP EXCAVATIONS

FREE FROM WATER. EXCAVATE SOIL DISTURBED OR WEAKENED BY

CONTRACTOR'S OPERATIONS. REFILL WITH BACKFILL MATERIAL AS

INDICATED.

3. PROVIDE STRUCTURAL FILL AND BACKFILL TO CONTOURS, ELEVATIONS AND

DIMENSIONS INDICATED. COMPACT EACH LIFT BEFORE PLACING OVERLAYING

LIFT.

4. PLACE ALL STRUCTURAL FILL AND BACKFILL IN 12" (MAXIMUM) LIFTS WITH

EACH LIFT COMPACTED TO 95% OF ASTM D698. PERFORM DENSITY TESTS ON

EACH LIFT AT TWO RANDOMLY SELECTED LOCATIONS, OR AS DIRECTED BY

THE CONTRACTING OFFICER. SUBMIT RESULTS OF ALL COMPACTION/DENSITY

TESTS TO THE CONTRACTING OFFICER.

5. STRUCTURAL FILL AND BACKFILL MATERIAL MUST CONFORM TO ASTM D2487

CLASSIFICATION GW, GP, GC, SW, SP, SC WITH A MAXIMUM OF 10 PERCENT BY

WEIGHT PASSING ASTM D1140, No. 200 SIEVE. IF EXISTING BACKFILL MATERIAL

IS TO BE REUSED, IT MUST BE TESTED FOR CONFORMANCE PRIOR TO REUSE.

6. TOP 12 INCHES OF EXISTING SUBGRADE MUST BE COMPACTED TO 95% OF

ASTM D698.

CONCRETE NOTES STRUCTURAL STEEL NOTES

1. STRUCTURAL STEEL MUST COMPLY WITH THE FOLLOWING SPECIFICATIONS:

A. STRUCTURAL STEEL SHAPES, PLATES AND BARS (EXCEPT AS NOTED

BELOW)- ASTM A36, Fy=36 KSI

B. WIDE FLANGE SHAPES - ASTM A992

C. RECTANGULAR AND SQUARE HSS-SHAPES - ASTM A500, GRADE C, FY=50 KSI

D. ROUND HSS-SHAPES - ASTM A500, GRADE C, FY=46 KSI

E. BOLTS - ASTM F3125, GRADE A325

2. ALL NUTS MUST CONFORM TO ASTM A563, GRADE AND STYLE FOR APPLICABLE

ASTM BOLT STANDARD. ALL WASHERS MUST CONFORM TO ASTM F436. BOLTS

MUST BE FULLY TENSIONED TO 70 % OF THEIR MINIMUM TENSILE STRENGTH.

ALL BOLTS AND HARDWARE MUST BE HOT DIPPED GALVANIZED IN

ACCORDANCE WITH ASTM A153.

3. ALL HOLES IN STEEL MUST BE STANDARD SIZE (1/16" LARGER THAN BOLT

DIAMETER) UNLESS OTHERWISE NOTED. ALL HOLES MUST BE DRILLED OR

PUNCHED. BURNING IS NOT PERMITTED.

4. TORCH CUTTING OF STEEL IS NOT PERMITTED.

5. ALL STEEL MUST BE HOT DIPPED GALVANIZED IN ACCORDANCE WITH ASTM

A123 OR ASTM A153 AS APPLICABLE. REPAIR DAMAGE TO GALVANIZED

COATINGS USING ASTM A780 ZINC RICH PAINT FOR GALVANIZING DAMAGED BY

HANDLING, TRANSPORTING, CUTTING, WELDING, OR BOLTING. DO NOT HEAT

SURFACES TO WHICH REPAIR PAINT HAS BEEN APPLIED. ZINC RICH COMPOUND

MUST BE 95% METALLIC ZINC, BY WEIGHT IN DRIED FILM CONFORMING TO FED.

SPEC. DOD-P-21035A AND MEETING MIL SPEC. MIL-P-26915A. PROVIDE TWO

COATS WITH 2 MIL THICKNESS PER COAT FOR A TOTAL OF 4 MILS.

6. PROVIDE DRAIN HOLES AND VENT HOLES IN HSS ASSEMBLIES AS REQUIRED

FOR GALVANIZING. DRAIN AND VENT HOLE DIAMETERS MUST NOT EXCEED 1/2".

LOCATE DRAIN AND VENT HOLES IN EACH HSS MEMBER SUCH THAT RAINWATER

WILL FULLY DRAIN FROM INSIDE THE MEMBER WHEN IT IS IN ITS ERECTED

POSITION.

7. NONSHRINK GROUT MUST CONFORM TO ASTM C1107 AND BE NONMETALIC.

1. THE STRUCTURES HAVE BEEN DESIGNED IN ACCORDANCE WITH THE

PROVISIONS OF THE INTERNATIONAL BUILDING CODE (IBC) 2021 EDITION.

2. ALLOWABLE NET SOIL BEARING CAPACITY = 1,500 PSF

3. WIND LOAD PARAMETERS IN ACCORDANCE WITH ASCE 7-16:

• RISK CATEGORY II

• V = 123 MPH

• EXPOSURE CATEGORY C

4. SEISMIC LOAD PARAMETERS IN ACCORDANCE WITH ASCE 7-16:

• RISK CATEGORY II

• SITE CLASS E

• S1 = 0.038g

• SS = 0.08g

5. GROUND SNOW LOAD...........10 PSF

DESIGN CRITERIA

STEEL DECK NOTES

1. PROVIDE 11/2" DEEP, 16-GAUGE, TYPE B WIDE RIB ROOF DECK.

2. STEEL ROOF DECK MUST CONFORM TO EITHER ASTM A792 OR ASTM A1008.

MINIMUM YIELD STRENGTH OF DECK MUST BE 33,000 PSI.

3. GALVANIZE ROOF DECK IN ACCORDANCE WITH ASTM A653, Z275 G90 COATING

CLASS OR COAT WITH ALUMINUM-ZINC COATING IN ACCORDANCE WITH ASTM

A792 COATING DESIGNATION AZM164 AZ55.

4. PROVIDE DECK SECTIONS IN LENGTHS TO SPAN 3 OR MORE SPACINGS WHERE

POSSIBLE.

5. LAP DECK ENDS 2 INCHES MINIMUM OVER SUPPORTS.

6. MECHANICAL DECK FASTENERS MUST BE #12 SELF-DRILLING SCREWS.

GALVANIZE FASTENERS IN ACCORDANCE WITH ASTM A153. EACH DECK

FASTENER MUST HAVE THE FOLLOWING MINIMUM ULTIMATE DESIGN VALUES IN

16-GAUGE STEEL:

TENSION......................................................340 LBS.

SHEAR..........................................................950 LBS.

7. FOR SPACING REQUIREMENTS OF FASTENERS AT DECK SUPPORTS AND DECK

SIDELAPS, SEE ROOF FRAMING PLANS ON SHEETS S-101 AND S-102.

ADHESIVE ANCHOR NOTES

1. ADHESIVE ANCHORS MUST CONFORM TO ASTM F1554 GRADE 55. PROVIDE

HEAVY HEX NUTS THAT ARE SUITED FOR USE WITH THE SELECTED ANCHOR

BOLT MATERIAL. WASHERS MUST MEET ASTM F436.

2. EACH ADHESIVE ANCHOR, 5/8" DIAMETER WITH AN EMBEDMENT DEPTH OF 71/2"

IN CONCRETE, MUST HAVE THE FOLLOWING MINIMUM ULTIMATE DESIGN

STRENGTHS IN 4,000 PSI CONCRETE:

2.1 BOND STRENGTH:

2.1.1 TENSION IN UNCRACKED CONCRETE....20,265 LBS.

2.1.2 TENSION IN CRACKED CONCRETE.........11,740 LBS.

2.1.3 SHEAR IN UNCRACKED CONCRETE........43,650 LBS.

2.1.4 SHEAR IN CRACKED CONCRETE.............25,280 LBS.

2.2 STEEL STRENGTH:

2.2.1 TENSILE STRENGTH..................................9,835 LBS.

2.2.2 SHEAR STRENGTH.....................................5,110 LBS.

3. BONDING AGENT MUST CONSIST OF ADHESIVE CAPSULES OR EPOXY BONDING

COMPOUND.

4. EPOXY BONDING COMPOUND MUST CONFORM TO ASTM C881.

M A

R K

D E

S C

R

IP

TI

O

N D

A T

E

TBM

(+0'-0")

E X

IS

T

S

LA

B S

LO

P

E S

D O

W N

(-0'-8"±)

(+0'-0"±)

(-0'-8"±) (-0'-8"±)

(-0'-6"±) (-0'-6"±) (-0'-6"±)

(+0'-0 1/2"±)

C1 S-501

A1

S-501

B1

S-501

15' - 6" ± 15' - 6" ± 15' - 6" ± 15' - 6" ±

1 1 1 1 1

1'

4"

T Y

P

8" ± TYP

8" ± TYP

EXISTING CONCRETE

PEDESTAL, TYP

EXISTING

TRENCH DRAIN

CL EXISTING

PEDESTAL

EXISTING

CONCRETE

CURB, TYP

TYPTYP TYP

AT CORNERS

A1

S-501

OPP

HAND

C1 S-501

TYP

SIM TO

(EXIST. TRENCH NOT SHOWN)

(+0'-0 1/2"±) (+0'-0 1/2"±) (+0'-0 1/2"±) (+0'-0 1/2"±)

(+0'-0 1/2"±)(+0'-0 1/2"±)(-0'-0 1/2"±)

W

X

S

LO

P

E D

(+14'-6 3/8")

C

X

.7

S

LO

P E

D

C12X20.7 (+14'-6")

C12X20.7 (+15'-0 7/8")

C12X20.7 (+14'-6") C12X20.7 (+14'-6") C12X20.7 (+14'-6")

W12X22

C

X

.3 (S

LO

P

E D

SPAN OF ROOF

DECK, TYP

C

X

.7

S

LO

P E

D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

R O

O F

S

LO

P E

S D

O W

N

1/ 4"

P E

R F

O O

T

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

C10X15.3

2L 3X3X1/4

BRACE, TYP

(+15'-0 1/2")

W12X22

(+14'-6 3/8")

W12X22

(+15'-0 1/2")

W12X22

(+14'-6 3/8")

W12X22

(+15'-0 1/2")

W12X22

(+14'-6 3/8")

W12X22

(+15'-0 1/2")

W12X22

C12X20.7 (+15'-0 7/8") C12X20.7 (+15'-0 7/8") C12X20.7 (+15'-0 7/8")

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

C

X

.3 (S

LO

P

E D

0" T

Y P

1' - 6" 15' - 6" ± 15' - 6" ± 15' - 6" ± 15' - 6" ± 1' - 6"

1'

6"

1'

6"

TYP

5' - 2" ±

8'

2"

8'

2"

8'

2"

C1 S-503

C2 S-503

B4 S-503

62' - 0" ±

A2

S-504

TYP AT CORNER

C12 TO C12

CONNECTION

TYP

AT BRACES

C2 S-503

SIM TO (SLOPE OPP DIRECTION)

TYP AT BRACES

C4 S-504

SIM TO

(SLOPE OPP DIRECTION)

C4 S-504

C1

S-504

TYP AT W12 TO W12

CONNECTION, NOT AT COLUMN

C3 S-503

TYP

AT COLUMNS A1

S-504

BEAM TO BEAM

CONNECTION, TYP

C3 S-504

AT C10 CONNECTION

TO W12

TYP

TYP

AT COLUMN

C4 S-503

C1 S-503

OPP

HAND

B4 S-503

C1 S-503

C1 S-503

OPP

HAND

65' - 0" ±

3' - 0"

3'

0"

3' - 0"

3'

0"

ZONE 2

ZONE 1

STEEL DECK ZONES

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:5

A

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

S-101

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

S T

R U

C T

U R

A L P

L A

N S

F

-1 P

A D

CBM

12916625

JLP JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

S -1

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

1 CENTERLINE OF EXISTING CONCRETE PEDESTAL AND HSS 6x6x5/16 STEEL

COLUMN ABOVE.

2 TOP OF STEEL OF C10 TO MATCH TOP OF STEEL OF SLOPED W12 BEAM AT

THE POINT OF INTERSECTION OF THE C10 AND W12.

1/4" = 1' - 0" 0 5' 10' 15'1'

GRAPHIC SCALE(S)

KEYNOTES

GENERAL SHEET NOTES

SCALE: 1/4" = 1'-0"

C1

FOUNDATION AND GROUND FLOOR PLAN - F-14 PAD

PLAN

NORTH

SCALE: 1/4" = 1'-0"

A1

ROOF FRAMING PLAN - F-14 PAD

PLAN

NORTH

SCALE: NOT TO SCALE

ROOF DECK PLAN

STEEL ROOF DECK MUST BE 1 1/2" DEEP, 16 GAUGE, TYPE 'B' ROOF DECK.

PROVIDE DECK IN LENGTHS FOR A 3-SPAN MINIMUM CONDITION. FASTEN ROOF

DECK TO SUPPORTING MEMBERS WITH #12 SELF DRILLING SCREWS. SPACE

SCREWS AT 6" ON CENTER MAXIMUM (36-7 PATTERN) AT SUPPORTS WITHIN ZONE

2. SPACE SCREWS AT 12" ON CENTER MAXIMUM (36-4 PATTERN) AT SUPPORTS

WITHIN ZONE 1. PROVIDE (1) #12 SELF DRILLING SCREW SIDELAP FASTENER PER

SPAN, CENTERED ABOUT EACH SPAN, AT ALL DECK SIDELAP JOINTS.

A. TEMPORARY BENCH MARK IS NOTED ON PLAN AS TBM AND IS LOCATED AT

THE TOP OF EXISTING CONCRETE CURB/PEDESTAL AT THE NORTHWEST

CORNER OF THE EXISTING CONCRETE SLAB. TEMPORARY BENCH MARK

ELEVATION IS 16.31', SEE SURVEY DRAWING SHEET V-101.

B. THE DATUM IS THE TEMPORARY BENCH MARK ELEVATION AND IS NOTED

THUS: (+0'-0") ON PLAN.

C. TOP OF EXISTING SLAB ELEVATIONS ARE NOTED THUS: (±X'-X") ON PLAN

INDICATING DISTANCE ABOVE OR BELOW DATUM.

D. TOP OF STEEL ELEVATIONS ARE NOTED THUS: (+X'-X") ON PLAN INDICATING

DISTANCE ABOVE DATUM.

E. FOR WIDE FLANGE BEAMS WHERE TOP OF STEEL ELEVATIONS ARE NOTED,

TOP OF STEEL ELEVATION OCCURS ALONG THE TOP OF EACH BEAM AT ITS

CENTERLINE, AS THESE BEAMS ARE ROTATED 1/4" ON 12" ABOUT THEIR

LONGITUDINAL AXES.

F. FOR CHANNEL BEAMS WHERE TOP OF STEEL ELEVATIONS ARE NOTED, TOP

OF STEEL ELEVATION OCCURS ALONG THE TOP CORNER OF EACH CHANNEL

WHERE THE FLANGE MEETS THE OUTSIDE FACE OF THE WEB, AS THESE

BEAMS ARE ROTATED 1/4" ON 12" ABOUT THEIR LONGITUDINAL AXES.

G. WHERE STEEL BEAMS ARE INDICATED TO BE SLOPED, AT EACH END OF

EACH SLOPED BEAM, MATCH TOP OF STEEL WITH THE TOP OF STEEL OF THE

BEAM INTO WHICH THAT END OF THE SLOPED BEAM FRAMES.

STEEL ROOF DECK NOTES (APPLY TO THIS SHEET ONLY)

M A

R K

D E

S C

R

IP

TI

O

N D

A

7' - 3" 5' - 0"

4'

7/

8"

/8

6'

3"

TBM

(+0'-0")

6" ± WIDE EXISTING CONCRETE CURB

OUTLINE OF EXISTING

CONCRETE PAD F-31

EXISTING CONCRETE SLAB OVER

ABANDONED UNDERGROUND

FUEL STORAGE TANK

F5.0 (-1'-4")

F5.0 (-1'-4")

1 2

F3.0x11.25 (-2'-8")

A3 S-501

C4

S-501

TYP AT

EACH COLUMN

2' - 6" 7' - 3" 1' - 6"

1'

6" 1'

6"

A1 S-502

6 6

A3 S-501

8'

2" 8'

2"

8'

2"

3' - 3" 7' - 3" 6' - 6"

3' - 7 1/2" 3' - 7 1/2" 3' - 3" 3' - 3"

SPAN OF ROOF

DECK, TYP

R O

O F

S

LO

P E

S D

O W

N

1/ 4"

P E

R F

O O

T

C10x15.3

HSS 10x5x5/16 (+14'-10")

W

X

S

LO

P

E D

W

X

S

LO

P

E D

W

X

S

LO

P

E D

2L 3X3X1/4

BRACE, TYP

W

X

S

LO

P

E D

HSS 10x5x5/16 (+15'-4 1/8")

17' - 0"

C10x15.3C10x15.3C10x15.3C10x15.3

W

X

S

LO

P

E D

W

X

S

LO

P

E D

9 9 9 9

C10x15.3C10x15.3C10x15.3C10x15.3C10x15.3

9 9 9 9 9

0" TYP

B1

S-505

TYP

AT CORNERS

C4 S-505

TYP

AT COLUMNS

C2 S-505

C1 S-505

C4

S-505

SIM TO

(W12 SLOPES

OPP DIRECTION)

A3 S-505

A3 S-505

18' - 0"

3' - 0"

3'

0"

3' - 0"

3'

0"

ZONE 2

ZONE 1

STEEL DECK ZONES

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:4

P

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

S-102

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

S T

R U

C T

U R

A L P

L A

N S

F

-3 P

A D

CBM

12916626

JLP JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

S -1

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

1 CENTERLINE OF HSS 6x6x5/16 COLUMN AND FOOTING BELOW.

2 WORKING LINE IS OUTSIDE VERTICAL FACE OF EXISTING CONCRETE CURB.

3 EXISTING TANK WITH EXISTING PIPING TO REMAIN (EXISTING PIPING NOT

SHOWN FOR CLARITY). TOP MOST POINT OF EXISTING PIPING/TANK IS AT

(+10'-3").

4 EXISTING ELECTRICAL BOX TO REMAIN.

5 EXISTING DRAIN TO REMAIN.

6 F5.0 DENOTES A 5'-0" WIDE BY 5'-0" LONG BY 2'-0" THICK CONCRETE

FOOTING. TOP OF FOOTING ELEVATION IS NOTED THUS; (-X'-XX") ON PLAN

INDICATING DISTANCE BELOW DATUM. TOP OF CONCRETE PEDESTAL IS AT

ELEV. (+0'-0").

7 F3.0x11.25 DENOTES A 3'-0" WIDE BY 11'-3" LONG BY 3'-0" THICK CONCRETE

FOOTING. TOP OF FOOTING ELEVATION IS NOTED THUS; (-X'-XX") ON PLAN

INDICATING DISTANCE BELOW DATUM. TOP OF CONCRETE PEDESTAL IS AT

ELEV. (+0'-0").

8 EXISTING CATHODIC PROTECTION ACCESS.

9 TOP OF STEEL OF C10 TO MATCH TOP OF STEEL OF SLOPED W12 BEAM AT

THE POINT OF INTERSECTION OF THE C10 AND W12. FOR CONNECTION OF

C10/W12, SEE DETAIL B1/S-504.

1/4" = 1' - 0" 0 5' 10' 15'1'

GRAPHIC SCALE(S)

KEYNOTES

GENERAL SHEET NOTES

SCALE: 1/4" = 1'-0"

A1

FOUNDATION AND GROUND FLOOR PLAN - F-31 PAD

PLAN

NORTH

SCALE: 1/4" = 1'-0"

A3

ROOF FRAMING PLAN - F-31 PAD

PLAN

NORTH

A. TEMPORARY BENCH MARK IS NOTED ON PLAN AS TBM AND IS LOCATED AT

THE TOP OF EXISTING CONCRETE CURB AT THE NORTHEAST CORNER OF

THE EXISTING CONCRETE SLAB. TEMPORARY BENCH MARK ELEVATION IS

18.42', SEE SURVEY DRAWING SHEET V-102.

B. THE DATUM IS THE TEMPORARY BENCH MARK ELEVATION AND IS NOTED

THUS: (+0'-0") ON PLAN.

C. TOP OF FOOTING ELEVATIONS ARE NOTED THUS: (±X'-X") ON PLAN

INDICATING DISTANCE BELOW DATUM.

SCALE: NOT TO SCALE

ROOF DECK PLAN

STEEL ROOF DECK MUST BE 1 1/2" DEEP, 16 GAUGE, TYPE 'B' ROOF DECK.

PROVIDE DECK IN LENGTHS FOR A 3-SPAN MINIMUM CONDITION. FASTEN ROOF

DECK TO SUPPORTING MEMBERS WITH #12 SELF DRILLING SCREWS. SPACE

SCREWS AT 6" ON CENTER MAXIMUM (36-7 PATTERN) AT SUPPORTS WITHIN ZONE

2. SPACE SCREWS AT 12" ON CENTER MAXIMUM (36-4 PATTERN) AT SUPPORTS

WITHIN ZONE 1.

STEEL ROOF DECK NOTES (APPLY TO THIS SHEET ONLY)

M A

R K

D E

S C

R

IP

TI

O

N D

A T

E

A

M E

N D

M E

N T

/2 3/

EXISTING #5 CONTINUOUS BARS

AT 1'-0" OC EACH WAY, TOP AND

BOTTOM

1'

6"

6"

TO

EXISTING #6 BARS

EXISTING #3 TIES, TYP

1' - 4" ±

LEVELING NUT, TYP

5/8" ⌀ ADHESIVE ANCHOR

WITH 7 1/2" EMBEDMENT IN

EXISTING CONCRETE, TYP

OF (4)

BASE PL 3/4"x10"x1'-0"

1" NONSHRINK GROUT

1/

2"

6" 6" CL COLUMN, BASE PL AND

EXISTING PEDESTAL

FOR TOP OF EXISTING PEDESTAL ELEV.

SEE PLAN C1/S-101

CL HSS 6X6X5/16

8"

8"

8" ± 8" ±

CL 5/8" ⌀ ADHESIVE ANCHOR WITH

7 1/2" EMBEDMENT IN EXISTING

CONCRETE, TYP OF (4)

BASE PL 3/4"x10"x1'-0"

1 1/2" TYP

1/

2" T

Y P

5" 5"

6" 6"

EDGE OF EXISTING

CONCRETE PEDESTAL

EQ EQ

E Q

E Q

3/16

OUTSIDE FACE OF EXISTING

CONCRETE CURB

OUTSIDE FACE OF EXISTING

CONCRETE CURB

8"

8"

1' - 4" ±

CL HSS 6X6X5/16

CL 5/8" ⌀ ADHESIVE ANCHOR WITH

7 1/2" EMBEDMENT IN EXISTING

CONCRETE, TYP OF (4)

BASE PL 3/4"x10"x1'-0"

1/

2" T

Y P

5" 5"

6" 6"

EDGE OF EXISTING

CONCRETE PEDESTAL

3/16

E Q

E Q

EQ EQ

1 1/2" TYP

OUTSIDE FACE OF EXISTING

CONCRETE CURB

(6) #6 BARS BOTTOM EACH WAY,

EQUALLY SPACED. PROVIDE 90°

HOOKS EACH END, EXTENDING

HOOK LENGTHS TO TOP OF TOP

MAT OF REINFORCING

LEVELING NUT, TYP

3/4" ⌀ HEADED ANCHOR

WITH 1'-2" EMBEDMENT IN

CONCRETE, TYP OF (4)

BASE PL 3/4"x12"x1'-0"

1" NONSHRINK GROUT

6" 6" CL HSS 6x6 COLUMN, BASE PL

AND PEDESTAL

1'

2"

(+0'-0")

3" 3"

2' - 6" 2' - 6"

2'

0"

MATCH EXISTING TOP

OF GRADE ELEV., FOR

ELEV. SEE SHEET V-102

1/

2" C

LR

9" 9"

3/4" CHAMFER, TYP

#4 TIES AT 7 1/2" OC MAX

((2) LAYERS OF BUNDLED

TIES NOT SHOWN FOR

CLARITY, SEE SECTION

C3/S-501)

1'-6"x1'-6" CONCRETE

PEDESTAL

FOR TOP OF FOOTING

ELEV. SEE PLAN

EXTEND VERTICAL BARS TO

BOTTOM REINFORCING MAT

(6) #6 BARS TOP EACH WAY,

EQUALLY SPACED. PROVIDE

STD 90° HOOKS EACH END

5'-0"x5'-0"x2'-0" THICK CONCRETE

FOOTING

C4 S-501

C3 S-501

8"

1 1/2" DEEP BY 3 1/2" WIDE

BY 8" LONG KEY

3" C

LR

1 1/2" CLR 1 1/2" CLR

0" TYP

1/

2" C

LR

9" 9"

CL HSS 6X6X5/16 COLUMN, BASE PL

AND CONCRETE PEDESTAL BELOW

CL 3/4"⌀ HEADED ANCHOR WITH

1'-2" EMBEDMENT IN CONCRETE,

TYP OF (4) ANCHORS

BASE PL 3/4"x12"x1'-0"

1/

2" T

Y P

6" 6"

6" 6"

CONCRETE PEDESTAL BELOW

3/16

9" 9"

1 1/2" TYP

1'

6"

#6 VERTICAL BAR WITH STD 90°

HOOKS EACH END, TYP OF (8)

3/4" CHAMFER, TYP

CONCRETE PEDESTAL

1' - 6"

STD 135° STIRRUP HOOKS

1/

2" C

LR

, T

Y P

#4 TIES AT 7 1/2" OC MAX

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:4

P

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

S-501

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

S T

R U

C T

U R

A L F

O U

N D

A T

IO

N

D E

T A

IL

S

CBM

12916627

JLP JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

S -5

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

1 1/2" = 1' - 0" 0 6" 1' 2'3" 9"

GRAPHIC SCALE(S)

SCALE: 1 1/2" = 1'-0"

C1

S-101 C1

DETAIL OF COLUMN ON EXISTING CONC. PEDESTAL

SCALE: 1 1/2" = 1'-0"

C1

S-101 B1

DETAIL

SCALE: 1 1/2" = 1'-0"

C1

S-101 A1

DETAIL

PLAN

NORTH

PLAN

NORTH

SCALE: 1 1/2" = 1'-0"

A1

S-102 A3

SECTION THROUGH FOOTING

SCALE: 1 1/2" = 1'-0"

A1

S-102 C4

DETAIL

SCALE: 1 1/2" = 1'-0"

A3

S-501 C3

DETAIL

M A

R K

D E

S C

R

IP

TI

O

N D

A T

E

A

M E

N D

M E

N T

/2 3/

(6) #6 LONG BARS BOTTOM, EQUALLY

SPACED. PROVIDE 90° HOOKS EACH END,

EXTENDING HOOK LENGTHS TO TOP OF

TOP MAT OF REINFORCING

1'-6"x1'-6" CONCRETE PEDESTAL, FOR

DETAILS OF PEDESTAL SHOWN BUT

NOT CALLED SEE SECTION A3/S-501

CL HSS 6x6 COLUMN, BASE PL

AND PEDESTAL

3"

3" C

LR

1 1/2" CLR

1' - 6" 1' - 6"

1 1/2" CLR

3'

0"

0" TYP

1/

2" C

LR

MATCH EXISTING TOP

OF GRADE ELEV., FOR

ELEV. SEE SHEET V-102

9" 9"

FOR TOP OF FOOTING

ELEV. SEE PLAN

(6) #6 LONG BARS TOP,

EQUALLY SPACED. PROVIDE

STD 90° HOOKS EACH END

3'-0" WIDE BY 11'-3" LONG

BY 3'-0" DEEP CONCRETE

FOOTING

8"

1 1/2" DEEP BY 3 1/2" WIDE BY 8" LONG KEY.

WHERE SHORT REINF. TOP BARS PASS

UNDER KEY, SHIFT TOP SHORT BARS

DOWN BELOW TOP LONG BARS AS

REQUIRED TO MAINTAIN 1 1/2" CLR

(32) #6 SHORT BARS BOTTOM, EQUALLY

SPACED. PROVIDE 90° HOOKS EACH END,

EXTENDING HOOK LENGTHS TO TOP OF

TOP MAT OF REINFORCING

(32) #6 SHORT BARS TOP,

EQUALLY SPACED. PROVIDE

STD 90° HOOKS EACH END

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:4

P

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

S-502

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

S T

R U

C T

U R

A L F

O U

N D

A T

IO

N

D E

T A

IL

S

CBM

12916628

JLP JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

S -5

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

1 1/2" = 1' - 0" 0 6" 1' 2'3" 9"

GRAPHIC SCALE(S)

SCALE: 1 1/2" = 1'-0"

A1

S-102 A1

SECTION THROUGH FOOTING

M A

R K

D E

S C

R

IP

TI

O

N D

A T

E

A

M E

N D

M E

N T

/2 3/

HSS 6x6 COLUMN, SEE PLAN

2L 3X3X1/4 BRACE

CL 3/4" ⌀ BOLT, TYP OF

(2) BOLTS

3"

1 1 /2"

1"

1 1/2"

TAB PL 3/8", ENSURE 1 1/2" MIN

CLEARANCE BETWEEN BOLT CL AND

ANY EDGE OF PL

3/16 3/16

A1 S-503

CL HSS 6x6 COLUMN AND

3/8" THICK TAB PL

TAB PL 3/8"

3/4"⌀ BOLT, TYP

2L 3x3 BRACE

NOTE:

STEEL DECK OMITTED

FOR CLARITY

HSS 6x6 COLUMN, SEE PLAN

SEE PLAN

TOS

CL COLUMN AND W12

ABOVE

2'

0" 1"

2L 3X3X1/4 BRACE

1' - 6"

W12, COPE AS REQ'D, TYP.

C12 (SLOPED),

SEE PLAN

STIFFENER PL 3/8"x1 7/8", FULL DEPTH

W12 (SLOPED), SEE PLAN

CL W12

FOR CONNECTION OF W12 TO W12

SEE DETAIL A1/S-504

B2

S-503

B1

S-503

CHAMFER PL AS REQUIRED

AT W12 FILLET, TYP

3/16 3/16

3/16 3/16

3/16 2@4

3/16 2@4 W12 BEAM HERE NOT

SHOWN FOR CLARITY

FOR BEAM TO COLUMN

CONNECTION, SEE

DETAIL C4/S-503 NOTE:

ALL ANGLE BRACES

SHOWN ON PLAN A1/S-101

SIMILAR

NOTE:

W12 AND BRACE

OMITTED FOR CLARITY

COLUMN

AT CHANNEL (+14'-6")

TOS

CL COLUMN

PL 1"X10"X1-0" PL 1"X10"X1-0"

1 1/2" TYP.

1/4

1' - 0"

CL 3/4" ∅ BOLT,

TYP OF (4)

CL HSS 6X6X5/16, BEAM TO

COLUMN CONNECTION PLATES

AND TOP OF W12 (NOT SHOWN)

W12X22

(SLOPED)

1/4 1/4

1' - 6"

1/4

1/4

1 1/2" DEEP

STEEL DECK

W12 HERE

NOT SHOWN

FOR CLARITY

C12

(+14'-6 3/8")

TOS AT COLUMN CL

A4 S-503

NOTE:

STEEL DECK OMITTED

FOR CLARITY

COLUMN

SEE PLAN

TOS

CL COLUMN, 2L BRACE

2L 3X3X1/4 BRACE

1/4

1' - 6"

90°

CL

W12

1/4

A2

S-503

A1

S-503

A3

S-504*

NOTE :

CENTERLINE OF W12

COINCIDES WITH COLUMN

CENTERLINE AT TOP OF W12

NOTE:

STEEL DECK OMITTED

FOR CLARITY

VARIES

TOS

CL BEAM

1' - 6"

B1

S-504

B1

S-504

C12, SEE PLAN W12, SEE PLAN

C10, SEE PLAN

C10, SEE PLAN

1 1/2"

2L 3X3X1/4 BRACE

W12 BEAM, SEE PLAN

1"

3"

1 1 /2"

CL 3/4" ⌀ BOLT, TYP OF

(2) BOLTS

TAB PL 3/8", ENSURE 1 1/2" MIN

CLEARANCE BETWEEN BOLT CL

AND ANY EDGE OF PL

3/16 3/16

A2 S-503

NOTE:

STEEL DECK OMITTED

FOR CLARITY

TOP OF W12

CL W12

1/4

CL COLUMN BEYOND, TOP OF W12,

2L BRACE AND 3/8" THICK TAB PL

W12, SEE PLAN

TAB PL 3/8" 1"

M

IN

3/4"⌀ BOLT, TYP

2L 3x3 BRACE

NOTE:

STEEL DECK OMITTED

FOR CLARITY

CL COLUMN AND W12

ABOVE

W12, SEE PLAN

PL 1"X10"X1-0"

CL 3/4" ∅ BOLT,

TYP OF (4)

PL 1"X10"X1-0"

1 1/2" TYP

5" 5"

NOTE:

STEEL DECK AND W12

OMITTED FOR CLARITY

NOTE:

W12 AND BRACE

OMITTED FOR CLARITY

COLUMN

AT CHANNEL (+15'-0 7/8")

TOS

CL COLUMN

PL 1"X10"X1-0" PL 1"X10"X1-0"

1 1/2" TYP.

1/4

1' - 0"

CL 3/4" ∅ BOLT,

TYP OF (4)

CL HSS 6X6X5/16, BEAM TO

COLUMN CONNECTION PLATES

AND TOP OF W12 (NOT SHOWN)

W12X22

(SLOPED)

1/4 1/4

1' - 6"

1/4

1/4

12 1 1/2" DEEP

STEEL DECK

W12 HERE

NOT SHOWN

FOR CLARITY

C12

(+15'-0 1/2")

TOS AT COLUMN CL

A4 S-503

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:5

A

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

S-503

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

S T

R U

C T

U R

A L F

R A

M

IN

G D

E T

A

IL

S

CBM

12916629

JLP JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

S -5

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

SCALE: 3" = 1'-0"

C1

S-503 B1

DETAIL

SCALE: 3" = 1'-0"

B1

S-503 A1

DETAIL 3" = 1' - 0"

0 3" 6" 1'

1" = 1' - 0" 0 6" 1' 3'2'

GRAPHIC SCALE(S)

SCALE: 1" = 1'-0"

A1

S-101 C1

DETAIL

SCALE: 1" = 1'-0"

A1

S-101 C3

DETAIL

SCALE: 1" = 1'-0"

A1

S-101 C2

DETAIL

SCALE: 1" = 1'-0"

A1

S-101 B4

DETAIL

SCALE: 3" = 1'-0"

C1

S-503 B2

DETAIL

SCALE: 3" = 1'-0"

B2

S-503 A2

DETAIL

SCALE: 1" = 1'-0"

C3

S-503 A4

DETAIL

SCALE: 1" = 1'-0"

A1

S-101 C4

DETAIL

M A

R K

D E

S C

R

IP

TI

O

N D

A

NOTE:

STEEL DECK OMITTED

FOR CLARITY

1/2" 2" 1 1/2"

1/

2"

1/ 2"

5" 2"

CL (2) 3/4"⌀ BOLTS

C12, SEE PLAN

CL 3/4"⌀ BOLT, TYP

C10, SEE PLAN

COPE AS REQUIRED

L 4x4x3/8x0'-9"

1/2" 2" 1 1/2"

1/

2"

1/ 2"

5" 2"

CL 3/4"⌀ BOLTS

W12, SEE PLAN

CL 3/4"⌀ BOLT, TYP

C10, SEE PLAN

COPE AS REQUIRED

L 4x4x3/8x0'-9"

C10, SEE PLAN

C10 TO C12 CONNECTION, TYP C10 TO W12 CONNECTION, TYP

1 1/2" DEEP STEEL DECK

C3 S-504

C3

S-504

W12, SEE PLAN

COPE AS REQUIRED AT

COLUMN CONNECTION

COPE AS REQUIRED

W12 BEAM HERE NOT

SHOWN FOR CLARITY

1/2"

1 1/2" TYP 1 1/2" TYP

CHAMFER PL AS REQUIRED

AT W12 FILLET, TYP

3/16 3/16

TYP

3/16 3/16

TYP

3/16 2@4

3/16 2@4STAGGER,

TYP

W12, SEE PLAN

CL (3) 3/4" ⌀ BOLT, TYP

1/

2" 3"

3"

M

IN

1/

2"

T Y

P

STIFFENER PL 3/8"x3 1/2"x 0'-11 3/8", TYP

NOTE:

STEEL DECK OMITTED

FOR CLARITY

NOTE:

COLUMN BELOW AND

CONNECTION TO

COLUMN OMITTED

FOR CLARITY

W12, SEE PLAN

COPE AS REQUIRED, TYP

3/16 3/16

CL (3) 3/4" ⌀ BOLTS, TYP

PL 3/8"x3 1/2"x 0'-9"

NOTE:

STEEL DECK OMITTED

FOR CLARITY

1/2"

1 1/2" TYP1 1/2" TYP

1/

2"

1/ 2"

3" 3"

1/

2"

1/4

C10, SEE PLAN. FOR CONNECTION OF

OTHER END OF C10 TO C12, SEE DETAIL

B1, THIS SHEET

FOR C10 CONNECTION TO W12,

SEE DETAIL B1/S-504, SIM TO

(C10 ON ONLY ONE SIDE OF W12)

NOTE:

STEEL DECK OMITTED

FOR CLARITY

1 1/2" 2 1/2"

1/

2"

1/ 2"

6"

1/ 2"

CL (2) 3/4"⌀ BOLTS

C10, SEE PLAN

CL 3/4"⌀ BOLT, TYP

W12 OR C12,

SEE PLAN

L 4x4x3/8x0'-9"

C12, SEE PLAN

COPE AS REQUIRED, TYP

3/16 3/16

CL (3) 3/4" ⌀ BOLTS

PL 3/8"x3 1/2"x 0'-9"

NOTE:

STEEL DECK OMITTED

FOR CLARITY

1/2"

1 1/2"1 1/2"

1/

2"

1/ 2"

3" 3"

1/

2"

1/4

W12, SEE PLAN

1/4

CL 3/4" ⌀ BOLT, TYP

L 4"x4"x3/8"x0'-9"

5/16"

C12, CONNECTED TO W12 AT

IT'S SUPPORTS, SEE PLAN

C12, SEE PLAN

3/4" ⌀ BOLT, TYP OF (3) BOLTS

EACH ANGLE LEG

B3 S-504

B4 S-504

C12, SEE PLAN

COPE AS REQUIRED, TYP

CL (3) 3/4" ⌀ BOLTS

L 4"x4"x3/8"x0'-9"

NOTE:

STEEL DECK OMITTED

FOR CLARITY

1/4

C12, SEE PLAN

1/4

CL 3/4" ⌀ BOLT, TYP

1/2" 2"

1 1/2"

1/

2"

1/ 2"

3" 3"

1/

2"

C12, SEE PLAN

CL (3) 3/4" ⌀ BOLTS

L 4"x4"x3/8"x0'-9"

NOTE:

STEEL DECK OMITTED

FOR CLARITY

C12, SEE PLAN

CL 3/4" ⌀ BOLT, TYP

2 1/2"

1 1/2"

1/

2"

1/ 2"

3" 3"

1/

2"

C12, SEE PLAN

COPE AS REQUIRED, TYP

CL (3) 3/4" ⌀ BOLTS

L 4x4x3/8"x 0'-9"

EACH SIDE OF W12

NOTE:

STEEL DECK OMITTED

FOR CLARITY

1/2"2"

1 1/2"

1/

2"

1/ 2"

3" 3"

1/

2"

1/4

W12, SEE PLAN

1/4

CL 3/4" ⌀ BOLT, TYP

A5 S-504

NOTE:

STEEL DECK OMITTED

FOR CLARITY

1/

2"

1/ 2"

3" 3"

CL (3) 3/4"⌀ BOLTS

W12 BEYOND,

SEE PLAN

CL 3/4"⌀ BOLT, TYP

C12, SEE PLAN

L 4x4x3/8x0'-9" EACH

SIDE OF W12

1/2"

1 1/2" TYP

TYP

2 1/2"

C12, SEE PLAN

END OF C12END OF C12

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:5

A

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

S-504

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

S T

R U

C T

U R

A L F

R A

M

IN

G D

E T

A

IL

S

Checker

12916630

Designer Author

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

S -5

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

3" = 1' - 0" 0 3" 6" 1'

GRAPHIC SCALE(S)

SCALE: 3" = 1'-0"

B4

S-503 B1

DETAIL

SCALE: 3" = 1'-0"

A1

S-101 A1

DETAIL

SCALE: 3" = 1'-0"

A1

S-101 C1

DETAIL

SCALE: 3" = 1'-0"

A1

S-101 C3

DETAIL

SCALE: 3" = 1'-0"

A1

S-101 C4

DETAIL

SCALE: 3" = 1'-0"

A1

S-101 A2

PLAN DETAIL

SCALE: 3" = 1'-0"

A2

S-504 B3

DETAIL

SCALE: 3" = 1'-0"

A2

S-504 B4

DETAIL

SCALE: 3" = 1'-0"

C2

S-503 A3

DETAIL

SCALE: 3" = 1'-0"

A3

S-504 A5

DETAIL

M A

R K

D E

S C

R

IP

TI

O

N D

A

NOTE:

STEEL DECK OMITTED

FOR CLARITY

HSS 6x6 COLUMN, SEE PLAN

CL HSS 6x6 COLUMN AND HSS 10x5 BEAM

2'

0" 1"

2L 3X3X1/4 BRACE

W12 (SLOPED, SEE PLAN

CL HSS 10x5

FOR CONNECTION, SEE DETAIL

C1/S-505 OR C2/S-505 AS APPLICABLE

B2

S-503

B1

S-503

SEE PLAN

TOS

1/4

A1

S-505

SIM TO

(DETAIL A2/S-503 DOES

NOT APPLY, AS TAB PL

IS CENTERED ABOUT

W12 ABOVE. W12 IS NOT

ROTATED HERE)

CL HSS 6x6 COLUMN AND HSS 10x5 BEAM

CL 3/4"⌀ BOLT, TYP OF (4)

6" 6"

1 1/2" 1 1/2"

PL 1"x12"x1'-0"

PL 1"x12"x1'-0"

1/4

A2 S-505

NOTE:

W12 AND STEEL DECK

ABOVE OMITTED FOR

CLARITY

CL HSS 6x6 COLUMN AND HSS 10x5 BEAM

CL 3/4"⌀ BOLT, TYP OF (4)

6" 6"

1 1/2" 1 1/2"

PL 1"x12"x1'-0"

PL 1"x12"x1'-0"

5/16 5/16

NOTE:

W12 AND STEEL DECK

ABOVE OMITTED FOR

CLARITY

NOTE:

ROOFING OMITTED

FOR CLARITY

CL (3) 3/4"⌀ BOLTS

TOP OF W12

AT CL HSS 10x5

W12 (SLOPED), SEE PLAN

CL HSS 10x5

1/4

1/2" 1 1/2"

1 1/2"

CL 3/4"⌀ BOLT, TYP

1/

2" 2 1/

2"

1/ 2"1

1/ 2"5/ 8"

1/

2"

1/ 2"

C O

P E

HSS 10x5, SEE PLAN

3 1/2"

3/16 3/16

1 1/2" DEEP STEEL DECK,

SEE PLAN

ELEV (+14'-10")

TOS

PL 3/8"x3 1/2"x0'-8"

NOTE:

ROOFING OMITTED

FOR CLARITY

CL (3) 3/4"⌀ BOLTS

TOP OF W12 AT

CL HSS 10x5

W12 (SLOPED), SEE PLAN

CL HSS 10x5

1/4

1/2" 1 1/2"

1 1/2"

CL 3/4"⌀ BOLT, TYP

1/

2" 2 1/

2"

1/ 2"1

1/ 2"5/ 8"

1/

2"

1/ 2"

C O

P E

HSS 10x5, SEE PLAN

3 1/2"

3/16 3/16

1 1/2" DEEP STEEL DECK,

SEE PLAN

ELEV (+15'-4 1/8")

TOS

PL 3/8"x3 1/2"x0'-8"

NOTE:

ROOFING OMITTED

FOR CLARITY

CL W12 (SLOPED),

SEE PLAN

1 1/2" DEEP STEEL DECK,

SEE PLAN

6"

CL W12 BEAM, SEE PLAN

CL HSS 10x5, SEE PLAN

PL 1/4"x5"x0'-10", CUT CORNERS TO RADIUS TO MATCH HSS 10x5, WELD ALL AROUND TO HSS 10x5

3"

FOR CONNECTION, SEE DETAIL

C1/S-505 OR C2/S-505 AS APPLICABLE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:4

P

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

S-505

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

S T

R U

C T

U R

A L F

R A

M

IN

G D

E T

A

IL

S

Checker

12916631

Designer Author

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

S -5

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

SCALE: 1" = 1'-0"

A3

S-102 C4

DETAIL

SCALE: 1 1/2" = 1'-0"

C4

S-505 A1

DETAIL

SCALE: 1 1/2" = 1'-0"

A1

S-505 A2

DETAIL

SCALE: 1 1/2" = 1'-0"

A3

S-102 C2

DETAIL

SCALE: 1 1/2" = 1'-0"

A3

S-102 C1

DETAIL

3" = 1' - 0" 0 3" 6" 1'

1 1/2" = 1' - 0" 0 6" 1' 2'3" 9"

1" = 1' - 0" 0 6" 1' 3'2'

GRAPHIC SCALE(S)

SCALE: 1 1/2" = 1'-0"

A3

S-102 A3

DETAIL

SCALE: 3" = 1'-0"

A3

S-102 B1

PLAN DETAIL

M A

R K

D E

S C

R

IP

TI

O

N D

A T

E

A

M E

N D

M E

N T

/2 3/

S

LO

P E

/4

P

E R

F O

O T

C1 A-501

C3 A-501

C4 A-501

C4

A-501

S

LO

P E

/4

P

E R

F O

O T

B3 A-501

B1 A-501

B4 A-501

B4

A-501

65' - 0" ±

3' - 0" 3' - 0"

3'

0" 3'

0"

3' - 0" 3' - 0"

3'

0" 3'

0"

ZONE 2

ZONE 1

ZONE 3

WIND PRESSURE ACTING DOWNWARD:

ZONE 1: 45.2 PSF

ZONE 2: 67.8 PSF

ZONE 3: 90.4 PSF

UPLIFT WIND PRESSURE:

ZONE 1: 41.4 PSF

ZONE 2: 64.0 PSF

ZONE 3: 124.3 PSF

18' - 0"

3' - 0"

3' - 0"

3'

0" 3'

0"

3' - 0" 3' - 0"

3'

0" 3'

0"

ZONE 3

ZONE 1

ZONE 2

WIND PRESSURE ACTING DOWNWARD:

ZONE 1: 49 PSF

ZONE 2: 73.5 PSF

ZONE 3: 97.9 PSF

UPLIFT WIND PRESSURE:

ZONE 1: 44.9 PSF

ZONE 2: 69.4 PSF

ZONE 3: 134.7 PSF

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:4

P

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

A-101

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

R O

O F

P L A

N S

CBM

12916632

AA JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

A -1

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

1/8" = 1' - 0" 0 5' 10' 15' 30'

GRAPHIC SCALE(S)

WIND DESIGN PRESSURE NOTES

SCALE: 1/8" = 1'-0"

C1

ROOF PLAN F-14 PAD

SCALE: 1/8" = 1'-0"

C3

ROOF PLAN F-31 PAD

SCALE: NOT TO SCALE

A1

ROOF WIND PRESSURE ZONES F-14 PAD

SCALE: NOT TO SCALE

A3

ROOF WIND PRESSURE ZONES F-31 PAD

PLAN

NORTH

PLAN

NORTH

1. WIND DESIGN PRESSURES ARE INDICATED IN PLNAS A1 AND A3 ON THIS

SHEET AND HAVE BEEN DETERMINED FROM ASCE 7-16, LRFD.

2. WIND PRESSURES INDICATED ARE ULTIMATE PRESSURES THAT DO NOT

INCLUDE THE DEAD WEIGHT OF THE ROOF.

3. DESIGN ROOFING AND ROOFING CONNECTIONS TO ADEQUATELY RESIST

THE STATED PRESSURES.

M A

R K

D E

S C

R

IP

TI

O

N D

A T

E

A

M E

N D

M E

N T

/2 3/

SEE STRUCTURAL

TOS

STRUCTURAL

FRAMING

1/4

METAL DECK

STANDING SEAM METAL

ROOFING SYSTEM

FLASHING

1/

2"

SEE STRUCTURAL

TOS

STRUCTURAL

FRAMING

1/4

12 METAL DECK

STANDING SEAM METAL

ROOFING SYSTEM

8"

Z-FLASHING

FLASHING

VARIES

TOS

8"

STRUCTURAL

FRAMING

METAL DECK

STANDING SEAM METAL

ROOFING SYSTEM

FLASHING

Z-FLASHING

SEE STRUCTURAL

TOS

STRUCTURAL

FRAMING

1/4

12 METAL DECK

STANDING SEAM METAL

ROOFING SYSTEM

8"

Z-FLASHING

FLASHING

SEE STRUCTURAL

TOS

7 1/ 2"

STRUCTURAL

FRAMING

1/4

12 METAL DECK

STANDING SEAM METAL

ROOFING SYSTEM

FLASHING

6"

VARIES

TOS

8"

STRUCTURAL

FRAMING

METAL DECK

STANDING SEAM METAL

ROOFING SYSTEM

FLASHING

Z-FLASHING

NIC

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:4

P

M

C R e v it L o c a l F ile s \2

-1

-S

-R jo h a n

.s ta d le r.

rv t

A-501

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

D E

T A

IL

S

CBM

12916633

AA JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

TWA

HSDC

M

ID

L A

N T

P W

D O

C E

A N

A

A -5

Approved by George Heider, Facilities Operations Specialist, with NAVSUP FLCN Oceana, via Email.

3" = 1' - 0" 0 3" 6" 1'

GRAPHIC SCALE(S)

SCALE: 3" = 1'-0"

C1

A-101 C3

DETAIL

SCALE: 3" = 1'-0"

C1

A-101 C1

DETAIL

SCALE: 3" = 1'-0"

C1

A-101 C4

DETAIL

SCALE: 3" = 1'-0"

C3

A-101 B1

DETAIL

SCALE: 3" = 1'-0"

C3

A-101 B3

DETAIL

SCALE: 3" = 1'-0"

C3

A-101 B4

DETAIL

M A

R K

D E

S C

R

IP

TI

O

N D

A T

E

A

M E

N D

M E

N T

/2 3/

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L A

IR

S

T A

T

IO

N O

C E

A N

A

V

IR

G

IN

IA

B

E A

C H

V

A

AS NOTED

/2

/2

:1

:0

P

M

K V

A \O c e a n a N

A S

\S it e w o rk

\S it e U ti lit ie s \F u e l\

In s ta ll c a n o p ie s f o r

F -3 a n d F

-1 p a d s \B

D e s ig n \D

W G

S \M o d e l\

E L

E C

\2

-1

-E -R

.r v t

E-001

IN

S

T A

L L C

A N

O P

Y A

T F

-1 A

N D

F -3

P

A D

S

E L E

C T

R

IC

A L S

Y M

B O

L S

L E

G E

N D

A

B B

R E

V

IA

T

IO

N S

A

N D

N O

T E

S

CBM

12916634

CTO JS

03 Sept 2024

CBM/JLP

1811182

V

IR

G

IN

IA

B

E A

C H

V

IR

G

IN

IA

N A

V A

L A

IR