N4008525B0015 Dwgs Signed.pdf

PDF 3 MB Posted

Attached to
Repair Heads Building 1826
Solicitation number
N4008526R9056
Issued by

About this file

This document is a construction drawing set for renovation work at Marine Corps Base Camp Lejeune, North Carolina, specifically for Repair Heads Building 1826, Contract Number 25-0015.

The project encompasses comprehensive renovation and demolition of Building 1826's head facilities, including removal of existing metal stud walls, fixtures, and associated utilities, with replacement of plumbing, electrical, HVAC, and mechanical systems. Key renovation work includes new light gauge metal stud walls with moisture and mildew-resistant gypsum board, new plumbing fixtures (water closets, urinals, lavatories, showers, water heater, floor drains), new electrical circuits and lighting with occupancy sensors, waste and vent piping systems, and mechanical systems including exhaust fans and electric heaters. The drawings specify detailed finishing requirements including ceramic tile, signage (interior tactile room signs with braille), and compliance with ADA accessibility standards and Architectural Barriers Act requirements. Demolition notes require removal of existing plumbing fixtures, conduits, switches, and utilities; asbestos-containing materials and lead-based paint must be disposed of through the Camp Lejeune landfill by appointment. The construction documents include floor plans, demolition and renovation notes, building sections, door and frame details, toilet accessory schedules, ceiling framing plans, plumbing plans (domestic water, waste and vent, demolition), mechanical equipment schedules, electrical plans with lighting fixture and panelboard schedules, and complete electrical general notes addressing NEC compliance, device mounting heights, and installation requirements. All work must coordinate with existing systems and maintain building functionality during construction.

View the file

Other files

File Type Posted
N4008525B0015 Specs.pdf PDF
25-0015 Asbestos Report.pdf PDF
RFP PDF.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S1828A

S1827A

S1847D S1847A

S1855

HP503

S1854A

HP576

S1854C

HP502

DUNCAN

S

T

Richlands

US 17

Beulaville

Burgaw

Words Corner

BoltonUS 7

4 &

Acme Delco

Leland

Warsaw

Magnolia

Rosehill

US 117

US 421

Wallace

CAMP LEJUENE

Swansboro

Hampstead

Wilmington

Scott Hill

US

A

A

L T

N T

I

C

Holly Ridge

NEW RIVER

Folkstone

Dixon

Jacksonville

Verona

GRAPHIC SCALE IN MILES

201010

Morehead City

A E

O C

N

Pink Hill

Mt. Olive

Seven Springs

Goldsboro US 70 New Bern

Havelock

NEUSE

Tuscarora

Trenton

Comfort

Kinston Dover

OAK GROVE

Pollacksville

Maysville

CHERRY POINT

US 70

RIVER

Otway

Beaufort

OLD LANDFILL POND

ORDE POND

S560

TBD

S1758

S1752A

S1144

S929

S1024

S1879

S1339

S1015A

S1115A

S906A

S1006A

S1006B S1301A

S496

S1318

S1404D

S1311B

S1828A

S1204A

SHP1018

S1827A

S1401A

S1308C

S1334

S555

S1352

S1025

SFC450

S1007

SFC222

SFC449

S1808E

SFC453

SFC454

SFC456

SFC455

SFC460

SFC438

PVH118D

PV227A

S960

SFC44

SFC389

SFC197

SFC257

S967B

SFC231

SFC42

S1843

CONT162

SFC59

SFC448

S1216

S1320

SFC272

SFC271

SFC254

SFC104

S1418

S1135

S1847D

S1767A

SFC149

PV128A

PVH118C

CONT160

S1877

S1767

S1767B

S567

SFC123

S969A

SFC269

S568

S569

S1832

SFC287

SFC468

S1740

S1324

SHP241

S1326

S1454

S44

S1833

SFC451

S1444

S1426

SFC388 SFC378

S1834

S1522A

S1835

S58N

S1878

SFC465

S1512

S1327

FC444

SFC463

S1325

S1017

SHP244

S566

S969B

S1754

S1838

SFC278

SFC244

SHP232B

SSH51

S1737

SFC466

S969C

SFC54

S1313

SFC265

SHP436

SFC267

S1422

SHP456

S1808E

SFC385

SFC230C

S1782

SHP493

SFC66M

S1221

S1847A

S1739

FC447

S1398

S1340A

SHP252

SFC219

SFC230B

SFC110

SFC345

SFC595

S1046C

SFC64C

SHP210A

SSH41

SFC252

S1510

SFC142

S1312A

SFC66N

S960

S956

S562

S775

S120

S932

S124

S563

S208

SFC299

PARADE FIELD

PARADE FIELD

S67

FC310

FC364

CTR11

HP155

HP135

SFC359

S1855

FC286

FC66A

FC280

HP250

FC285

HP237 1337

FC400

FC115

FC332

HP102

FC371

FC300

FC66

FC359

FC100

FC416

FC412

FC415

FC414

S962

FC65

HP131

FC500

FC308

FC356

D29

HP413

FC230

HP402

HP259

FC51

FC255

FC481

FC375

FC64

FC62

FC63

HP500

FC504

FC507

FC478

FC425

FC303

HP55

HP513

FC45

HP504

HP512

HP465

FC420

FC270

HP455

HP301

FC365

HP53

FC306

HP57

HP308

HP51

FC571

FC574

HP306

FC573

HP307

HP285

FC360

HP550

HP505

HP225

HP435

HP275

FC200

HP508

HP507

HP510

HP255

HP560

FC530

HP445

HP485

HP514

HP509

FC525

FC560

FC520

HP295

FC550

FC565

HP475

FC515

HP503

FC330

FC555

HP245

HP195

FC292

HP165

HP235

HP265

FC263

HP215

HP115

FC291

HP135

HP175

HP125

HP105

HP145

HP155

FC364

HP88

HP185

123A

223A

423A

FC57

FC130

FC127

1880A

FC128

FC129

FC281FC131

HP112

FC298

FC143

HP5

FC173

SSA11

SSA10

FC134

FC253

FC56

1121A

ES101

FC190

1775E

FC355

1775A

1775B

1775C

1775D

1450A

1450B

1450C

1775H

1829A

1829B 1775G

S1752

S1753

FC307

1121B

64A

59F

FC174

59E

FC250

FC50

FC206

1006D

59G

FC207

FC211

309E

235A

309D

309C

1337D

FC320

312E

FC370

SH49

64B

FC67

FC112

1121C

FC58

309F

S90

1701A

219B

219C

FC138

FC136

516A

SFC221

CTR121

FC137

FC310F

FC298A

FC310E

FC310C

FC310B

FC310D

HP155C

FC310G

HP155B

FC140

FC195

FC139

FC443

HP89

CTR149

58F58E

58H58G

CTR138

FC484

SSA1

SSA2

SSA3

FC442

236A

FC445

SFC499

FC101

FC201

FC102

S932

1250J

1250BF

1250L

1250BE

1250E

1250P

1250BB1250BC1250BD

1250D

1250C

1250B

1250K

1250H

1250R

1250Q1250AF1250AL

1250AE

1250AG

FC292F

FC551

FC531

FC566

FC358

HP1016

13A

SFC419

510A

510C

510B

1005G

59D

CTR124

309K

519F

519E

519A

519C

519D

519B

519H

320E

219F

519G

HP495C

905C

905B

HP135C

HP135D

HP495D

309N

CTR905

320B

320C

320D

219E

510E

FC467

516F

316C

219G

219D

CONT289

516E

510D

CTR139

312C

516D

516B

312D

516C

SH63

SH64

SH61

SH62

977B

977A

SSA4

SSA5

SSA6

227C

FC510

1323C

1323B

1323A

1450N

S125C

S125B

1450M

1005A

411C

CTR153

FC45C

1005H

SH60

1742A

SHP505B

S677

1742C

1742B

HP52

HP476

CTR521

CTR143

HP135F

S1220B

HP155F

HP135E

FC311A

HP495F

S579

HP495E

HP155D

HP155E

FC310A

HP135B

HP495G

HP155A

HP135G

HP305

HP495H

CTR905A

FC540

FC251

HP1017

FC120

S1854A

FC40

HP576

FC260

SH50

HP232

FC436

FC294

HP416

HP206

CTR133

FC241

FC362

FC293

FC441

FC230A

FC309B

FC375P

FC132

FC120A

FC375N

HP328

SFC143B

SFC143A

RNGD30

FC311C

FC311B

SFC211C

SFC211D

SFC255C

SFC255B

SFC263B

S1854B

FC354

S1854C

S691

HP502

751B

425C S1765B

HP56

S1765A

HP515

HP511

S1806

FC561

SFC290

FC556

FC382

SFC355A

SFC347

SHP88A

S1042A

SFC366

SHP494

FC286B

SFC66B

SFC66H

SSH12

SSH10

SSA11

SSA10

SHE1

SHE3

SHE5

SHE4 SHE7

SHE8

SHE2

SHE6

SSA1

SSA2

SSA3

SFA8

SFA9

SFA12

SFA10

SHE19

SHE17

SHE20

SHE18

SHE21

SSA4

SSA5

SSA6

SH63

SFA3

SFA4

SFA1

SFA2

SFD4

SFD6

SFD8

SFD5

SFD9

SFD7

SFD3

SFD2

SFD1

SFD11

SFD12

SFD10

SFD14

SFD13

SH22

SH13

GREENW

AY TRAIL

GREENWAY TRAIL

ALZ-5

ALZ-4

ALZ-6

ALZ-26

ALZ-33

TLZ PENGUIN

LO

UIS RD

N

ST

O S T

A ST

L S T

I S T

F ST

G ST

H ST

MCHUGH BLVD

M S

T

TURRET RD

HOPE RD

FIR ST

GONZALEZ BLVD W

TLZ PENG

UIN RD

CONNOR ST

MICHAEL RD

FAITH RD

HAMMOND RD

WEST RD

GUM ST

DUNCAN

S

T

DOGW

OOD ST

SIM

CENTER DR

F17 RANGE RD

CEDAR ST

CO

NN

EC

TO

R

RD

HEMLOCK ST

GIBB RD

EAST RD

VIRGINIA DARE DR

TACTICAL WAY

ASH ST

905 TANK TRL

ELM ST

CENTER RD

HICKORY ST

D

AL

Y R

D

MULBERRY ST

OLD BUS STATION ST

FRANKLIN

ST

914 TAN

K TR

L

O ST

FRANKLIN ST

DUNCAN ST

D ST

POST LN

8 R

D

G O

NZ

AL

EZ

L

O O

P

VIRTUE RD

C ST

B ST

REASONER ST

HONOR RD

CREEK RD

HM SMITH BLVD

LUCY BREW

ER AVE

BARKER ST

G O

N

ZA

LE

Z

BL

VD

E

M O

LLY PITC

H

ER

D

R

TL

Z

PE

NG

UI

N

LO

OP

ANDERSON ST

LO

G

IS

TI

C S

LN

FO

RTITUDE RD

G29 RANGE RD

DOG 11 TANK TRL

F6 RANGE RD

CONST. CONTR. NO.:

CONST. CONTR. NO.

FLOOR PLAN BUILDING 18261

DEMO FLOOR PLAN BUILDING 18262

RENO FLOOR PLAN BUILDING 18263

NORTH

NORTH

NORTH0 5'

1/4" = 1'-0"

10'

0 5' 1/4" = 1'-0"

10'

0 5' 10' 20' 1/8" = 1'-0"

Christopher Maas 30-Jun-2026

TOILET ACCESSORY PLAN1

TOILET FIXTURE/ACCESSORY MOUNTING HEIGHT DETAIL4

CEILING FRAMING PLAN2

FEMALE HEAD INTERIOR ELEVATIONS5

MALE HEAD INTERIOR ELEVATIONS6

0 1'

1/2" = 1'-0" 5'

0 1' 1/2" = 1'-0"

5'

0 5' 1/4" = 1'-0"

10'

0 5' 1/4" = 1'-0"

10'

NEW WORK DIMENSION PLAN3

0 5'

1/4" = 1'-0" 10'

NEW 58" MILDEW AND MOISTURE RESISTANT GYPSUM

BOARD, PAINT OPEN BAY SIDE; FRP TOILET SIDE

NEW HOLLOW METAL FRAME

NEW MTL STUDS @ 16" O.C. W/

R-15 BATT INSULATION

NEW DOOR AS

SCHEDULED

SEALANT AT ALL

EDGES,TYPICAL

HEAD

JAMB

SEALANT AT ALL

EDGES,TYPICAL

NEW DOOR AS

SCHEDULED

NEW MTL STUDS @ 16" O.C. W/

R-15 BATT INSULATION

NEW HOLLOW METAL FRAME

NEW 58" MILDEW AND MOISTURE RESISTANT GYPSUM

BOARD, PAINT OPEN BAY SIDE; FRP TOILET SIDE

CONST. CONTR. NO.

DOOR FRAME DETAIL2

BUILDING SECTION1

0 1'

1/2" = 1'-0" 5'

F1A B F2C F3

GENERAL NOTES - ROOFING:

1. ITEM LOCATION SUCH AS VENTS, GOOSENECKS, EQUIPMENT, TIE ANCHORS, ETC. IS APPROXIMATE. FIELD VERIFY

2. FIELD VERIFY VENT QUANTITIES

3. ALL FLASHING, COUNTER FLASHING, WOOD BLOCKING, WOOD NAILERS, AND RELATED ROOF ITEMS MUST BE REPLACED WITH NEW PER CONSTRUCTION DOCUMENTS

4. UNLESS OTHERWISE NOTED, ALL ROOF PENETRATIONS AND PLUMBING VENTS CURRENTLY LOCATED ON THE ROOF ARE TO REMAIN IN PLACE SUBSEQUENT TO NEW ROOF

INSTALLATION. REMOVE AND REPLACE ALL EXISTING FLASHING ELEMENTS AT ALL PENETRATIONS PRIOR TO NEW ROOFING SYSTEM INSTALLATION.

5. THE CONTRACTOR SHALL COORDINATE ALL UTILITY CONNECTIONS (PLUMBING, ELECTRICAL, HVAC, ETC.) WITH DEMOLITION AND RENOVATION PHASING. COORDINATE ALL

SHUTDOWNS AND/OR MODIFICATIONS OF EXISTING SYSTEMS WITH THE CONSTRUCTION MANAGER.

6. THE CONTRACTOR SHALL DE-ENERGIZE ALL ELECTRIC CIRCUITS PRIOR TO DEMOLITION OF AFFECTED EQUIPMENT, RE-CONNECT, AND RE-ENERGIZE ALL AFFECTED EQUIPMENT AND

ELECTRICAL DEVICES AS NECESSARY TO RETURN THEM TO WORKING CONDITIONS.

7. THE CONTRACTORS MAY ONLY USE THE CAMP LEJEUNE LANDFILL FOR THE DISPOSAL OF ASBESTOS CONTAINING MATERIALS, BUILDING PRODUCTS WITH TIGHTLY ADHERED LEAD

CONTAINING PAINT, NON-CONTAMINATED CLEAN DIRT AND CLEAN GRAVEL. THE HOURS OF OPERATION ARE 0730-1530. DELIVERY OF ACCEPTABLE MATERIALS (LEAD AND ASBESTOS) SHALL BE BY APPOINTMENT ONLY. APPOINTMENTS MADE BY PHONE AT 910-451-5011 OR 910-451-2946.

8. NON-CONTAMINATED MATERIALS (IDENTIFIED ABOVE): ALL OTHER CONTRACTOR GENERATED MATERIAL SHALL BE WEIGHED THROUGH THE BASE LANDFILL SCALES BEFORE BEING REMOVED FROM THE BASE. CONTRACTORS UTILIZING THE BASE SCALES WILL REQUIRE CONTRACTING OFFICER ASSISTED PRE-REGISTRATION WITH THE LANDFILL MANAGER. THE CONTRACTING OFFICER WILL REGISTER THE CONTRACT VIA E-MAIL, WITH THE BASE LANDFILL. ALL HAUL VEHICLES WILL MAINTAIN A SECURE VEHICLE PLACARD AS A CONDITION TO UTILIZE THE SCALE. E-MAIL THE CONTRACT INFORMATION TO THE LANDFILL CLERK, INCLUDING THE NAME ON THE PRIME CONTRACTOR, CONTRACT NUMBER, JOB NAME/DESCRIPTION, COMPLETION DATE AND WHETHER OR NOT ANY OF THE ABOVE MATERIALS WILL BE DELIVERED TO THE LANDFILL. HAULING AND OFF-BASE LANDFILL COSTS

SHALL BE INCLUDED IN THE CONTRACT.

SHOP DRAWING SUBMITTALS:

1. SHOP DRAWINGS MUST BE PROJECT-SPECIFIC

2. SHOP DRAWINGS MUST BE WELL COORDINATED AMONG THE VARIOUS VENDORS/TRADES/SUBCONTRACTORS THAT CONSTITUTE A PARTICULAR BUILDING SYSTEM

3. THE GOVERNMENT WILL REJECT INCOMPLETE SHOP DRAWINGS. COMPLETE SHOP DRAWINGS MUST SHOW ALL INTERFACING COMPONENTS. FOR EXAMPLE, ON BUILDING ENVELOPE

SYSTEMS:

a. OPENING PRODUCTS SUCH AS WINDOWS, DOORS, LOUVERS, PENETRATIONS, ETC. WITHOUT FLASHING, VAPOR BARRIER, THREE-PIECE SILL, INSULATION OF AIR SPACE, ETC., AND/OR

b. COMPONENTS SHOWN IN NON-PROJECT SPECIFIC WAY, AND/OR

c. COMPONENT LAYOUTS LABELED "ITEM BY OTHERS",

4. GOVERNMENT APPROVAL OF SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITY TO PROVIDE THE CORRECT QUANTITIES, CAPABILITIES, PERFORMANCE, COORDINATION WITH ALL TRADES, TO PERFORM THOROUGH FIELD INVESTIGATIONS, TO PROVIDE COMPLETE SYSTEMS IN PLACE AND READY FOR USE IN

ACCORDANCE TO THE CONTRACT DOCUMENTS, REFERENCED CODES, GUIDELINES, ESTABLISHED GOOD PRACTICES, ETC.

SIGNAGE TYPE C

Interior Signage Schedule Signage Type Quantity Door

A 1 100a B 1 101a C 1 102a D 1 103a

SIGNAGE TYPE B

SIGNAGE TYPE A

SIGNAGE TYPE D

MISCELLANEOUS EXTERIOR ELEVATIONS:

1. REMOVE ALL DAMAGED MORTAR JOINTS (DOES NOT INCLUDE DEMOLISHED CONDITIONS SHOWN IN THE HATCHED AREAS). INFILL WITH NEW MORTAR TO MATCH EXISTING

CONDITIONS. FOR BIDDING PURPOSES ASSUME THAT 30 LF OR CMU JOINT MORTARS WILL NEED TO BE REPOINTED.

2. POWER WASH ALL CMU PRIOR TO PAINTING. SCRAPE/REMOVE LOOSE PAINT PRIOR TO PAINTING.

3. ACTUAL SAMPLES OF ALL THE EXTERIOR MATERIALS MUST BE SUBMITTED TO THE BEAP FOR REVIEW AND APPROVAL, NO EXCEPTIONS. COLOR CHIPS, PHOTOCOPIES, ELECTRONIC SAMPLES WILL NOT BE ACCEPTABLE

Additional Interior Signage Schedule Signage Type Quantity Location

E 2 Top of wall on exterior of heads

SIGNAGE TYPE E

T

T T

ELECTRICAL LEGEND

SYMBOL DESCRIPTION

HOME RUN CIRCUITS IN CONDUIT BACK TO PANEL BOARD; SIZED AS

INDICATED

EMERGENCY LIGHTING UNIT, 2-HEAD WITH BATTERY BACK-UP,

WALL MOUNTED, CONNECT TO NON-SWITCHED LEG. SEE DETAIL

NL-26 & LUMNINAIRE SCHEDULE.

RECEPTACLE, DUPLEX, 120VAC, 20A, UNLESS OTHERWISE NOTED.

SEE MOUNTING HEIGHT DETAIL THIS SHEET.

GFCI - GROUND FAULT CIRCUIT INTERRUPTER, 120VAC, 20A

WP - WEATHERPROOF GFCI 120VAC,20A

LIGHT FIXTURE. SEE LIGHTING FIXTURE SCHEDULE.

DISCONNECT SWITCH HEAVY DUTY, SIZE AS INDICATED ON

DRAWINGS

##A = DISCONNECT SIZE / # = NUMBER OF POLES / # = NEMA RATING,

/##AF = FUSE SIZE

30A/3/3R, W/ 30AF

480/277V

208/120V

PANELBOARD, SURFACE OR RECESSED MOUNTED AS SHOWN.

SIZE, RATINGS, AND MOUNTING AS INDICATED ON PANEL

SCHEDULE. CONTRACTOR IS RESPONSIBLE FOR REQUIRED

CLEARANCE IN FRONT OF ELECTRICAL PANEL. SEE NEC TABLE

110.26 WORKING SPACES FOR ADDITIONAL CLEARANCE

CONDITIONS.

MECHANICAL EQUIPMENT; TYPE AND CONNECTION AS INDICATED

DUAL TECHNOLOGY OCCUPANCY SENSOR

WALL SWITCH AT 46" AFF UNLESS OTHERWISE NOTED.

LOW VOLTAGE. ASSOCIATED WIRING IS TO BE PROVIDED BUT IS

NOT SHOWN ON DRAWINGS FOR CLARITY. PROVIDE SWITCHES

COMPATIBLE FOR LUMAIRES/LIGHTING SYSTEM. SEE OCCUPANCY

SENSOR DIAGRAMS (E-106).

S

SWITCHED LEG

NON-SWITCHED LEG

LV

ELECTRICAL GENERAL NOTES:

1. ALL ELECTRICAL WORK MUST BE IN FULL COMPLIANCE WITH NFPA 70 AND ALL

LOCAL CODES AND ORDINANCES AND IN ACCORDANCE WITH THE REQUIREMENTS

OF THE LOCAL AUTHORITY HAVING JURISDICTION.

2. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR MUST BE LISTED AND LABELED

BY A NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE

AUTHORITY HAVING JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL

MATERIAL, EQUIPMENT AND DEVICES MUST BE NEW CURRENT PRODUCTS OF

MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH

PRODUCTS. EQUIPMENT MUST BE SUITABLE FOR ITS APPLICATION (E.G. WHEN

INSTALLED OUTDOORS, IT MUST BE WEATHERPROOF, ETC.)

3. THE CONTRACTOR MUST REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR WORK

REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL EQUIPMENT,

AND LAYOUT HIS WORK IN A COMPATIBLE AND FUNCTIONAL MANNER.

4. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED BY

THE CONTRACTOR MUST BE COMPLETE AND FULLY-FUNCTIONING AFTER

INSTALLATION. INCIDENTAL COMPONENTS MAY NOT BE SHOWN, AND ALL WORK

WHICH MAY BE REASONABLY IMPLIED AS BEING INCIDENTAL TO THIS WORK, BUT

REQUIRED FOR THE PROPER OPERATION OF THE EQUIPMENT OR SYSTEM MUST BE

PROVIDED BY THE CONTRACTOR AND INCLUDED IN THE BID. ADDITIONAL CIRCUITS

MUST BE INSTALLED WHEREVER NEEDED TO CONFORM TO THE SPECIFIC

REQUIREMENTS OF EQUIPMENT.

5. TEMPORARY POWER CONNECTIONS AS REQUIRED MUST BE PROVIDED BY THE

CONTRACTOR AND INCLUDED IN THE BID. ALL TEMPORARY EQUIPMENT WIRING

MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. THE

CONTRACTOR MUST PROVIDE DETAILS, METHODS, MATERIALS, ETC. FOR REVIEW

PRIOR TO MAKING TEMPORARY CONNECTIONS. FURNISH AND INSTALL ALL

EQUIPMENT AND MATERIALS INCLUDING CONTROL EQUIPMENT, MOTOR STARTERS,

BRANCH AND FEEDER CIRCUIT BREAKERS, PANELBOARDS, TRANSFORMERS, ETC.

FOR TEMPORARY POWER. COORDINATE WITH THE UTILITY PROVIDER AS

REQUIRED.

6. THE WORK MUST INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING AT

THE COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR

ADJUSTMENTS NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM AND

EQUIPMENT.

7. ALL ELECTRICAL EQUIPMENT MUST, AT ALL TIMES DURING CONSTRUCTION, BE

ADEQUATELY PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER

AND/OR THE ELEMENTS. ELECTRICAL EQUIPMENT MUST NOT BE STORED OUT OF

DOORS, BUT MUST BE STORED IN DRY PERMANENT SHELTERS. IF AN APPARATUS

HAS BEEN DAMAGED, OR HAS BEEN SUBJECT TO POSSIBLE INJURY BY WATER OR

THE ELEMENTS, SUCH DAMAGE MUST BE REPLACED AT NO ADDITIONAL COST.

8. DO NOT SCALE ELECTRICAL DRAWINGS. CONTRACTOR MUST FIELD VERIFY ALL

DIMENSIONS.

9. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR

OTHER INSTALLATION DETAILS. UNLESS NOTED OTHERWISE, THE EXACT ROUTING

OF FEEDER AND BRANCH CIRCUIT RACEWAYS AND CABLES IS THE RESPONSIBILITY

OF THE CONTRACTOR. RISER AND GENERAL CIRCUIT ARRANGEMENTS ARE

SHOWN SCHEMATICALLY/DIAGRAMMATICALLY ONLY. THE CONTRACTOR MUST

ROUTE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION.

10. UNLESS DIMENSIONED, DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE

APPROXIMATE. ADJUST EXACT LOCATIONS AS REQUIRED TO SERVE THE INTENDED

PURPOSE AND TO AVOID CONFLICTS AND INTERFERENCES WITH OTHER TRADES.

IF NOT SHOWN ON THE ARCHITECTURAL DRAWINGS OR DIMENSIONED ON THE

ELECTRICAL DRAWINGS, VERIFY EXACT LOCATION WITH THE GOVERNMENT PRIOR

TO ROUGH-IN.

11. CONDUIT TERMINATING IN PRESSED STEEL BOXES MUST HAVE DOUBLE LOCKNUTS

AND INSULATED BUSHINGS. CONDUITS TERMINATING IN GASKETED ENCLOSURES

MUST BE TERMINATED WITH GROUNDING TYPE CONDUIT HUBS.

12. BRANCH CIRCUIT HOMERUNS SHOWN ON DRAWINGS INDICATE PHASE

CONDUCTORS, NEUTRAL, EQUIPMENT GROUND CONDUCTORS AS REQUIRED.

ADDITIONAL CONDUCTORS REQUIRED FOR CONTROL MUST BE INCLUDED EVEN IF

NOT EXPLICITLY SHOWN.

13. SEAL ALL CONDUIT OPENINGS THROUGH EXTERIOR BUILDING WALLS AND ROOF

WATERTIGHT.

14. IN WET LOCATIONS AND EXTERIOR, ALL WIRING DEVICES MUST BE

WEATHER-RESISTANT LISTED WITH WEATHERPROOF WHILE IN USE COVER.

15. RACEWAYS PENETRATING FLOORS, CEILINGS OR WALLS MUST BE PROPERLY

SEALED SMOKETIGHT.

16. ALL RACEWAYS MUST BE CONCEALED WHERE POSSIBLE.

17. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY

SURFACES OR STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS AS

MUCH AS POSSIBLE. NO DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS MUST

BE RUN STRAIGHT WITH QUALITY WORKMANSHIP-LIKE MANNER. RUN PARALLEL OR

BANKED RACEWAYS TOGETHER ON COMMON SUPPORTS WHERE PRACTICAL.

MAKE BENDS IN PARALLEL OR BANKED RUNS FROM SAME CENTERLINE TO MAKE

BENDS PARALLEL.

18. PATCHING OF WATERPROOFED SURFACES MUST RENDER THE AREA OF THE

PATCHING COMPLETELY WATERPROOF.

19. ALL MOTORS AND OTHER VIBRATING EQUIPMENT MUST BE CONNECTED TO THE

CONDUIT SYSTEM BY MEANS OF A SHORT SECTION (18 INCH MINIMUM) OF FLEXIBLE

CONDUIT UNLESS OTHERWISE INDICATED. AN EQUIPMENT GROUNDING

CONDUCTOR MUST BE INSTALLED INSIDE THE FLEXIBLE CONDUIT AND TERMINATE

AT THE LOAD END WITH AN APPROVED GROUNDING CLAMP OR LUG.

20. SURFACE MOUNTED PANELBOARDS, JUNCTION, OUTLET AND PULL BOXES,

RACEWAYS, ETC., INSTALLED ON EXTERIOR SURFACES OR INSIDE ON EXTERIOR

WALLS MUST BE SUPPORTED BY SPACERS TO PROVIDE A MINIMUM 1/4" MINIMUM

CLEARANCE BETWEEN THE WALL AND EQUIPMENT.

21. TYPED PANELBOARD DIRECTORIES INSTALLED IN THE PANELBOARD DOOR POCKET

MUST REFLECT FINAL CONDITIONS AND ACTUAL ROOM NAMES AND NUMBERS IN

ADDITION TO THE GENERAL DESCRIPTION SHOWN ON THE PANEL SCHEDULES ON

THE DRAWINGS.

22. DO NOT PULL CONDUCTORS UNTIL THE CONDUIT SYSTEM IS COMPLETE IN EVERY

DETAIL. IN THE CASE OF CONCEALED WORK, "COMPLETE" MEANS UNTIL ALL

ROUGH PLASTERING OR MASONRY HAS BEEN COMPLETED.

23. WHERE SIZE IS NOT SHOWN ON THE DRAWINGS, BRANCH CIRCUITS MUST CONSIST

OF #12 OR #10 AWG MINIMUM PHASE, NEUTRAL AND EQUIPMENT GROUND

CONDUCTORS IN 3/4” MINIMUM RACEWAY.

24. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS WITH A

TOTAL INSTALLED LENGTH GREATER THAN 75 FEET AND/OR BRANCH CIRCUIT

HOMERUNS LONGER THAN 50 FEET, I.E.; #12 AWG INCREASED TO #10 AWG FOR

RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH (INCLUDING THE

HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET. IF 277 VOLT CIRCUITS ARE

SHOWN, USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS

WITH TOTAL INSTALLED LENGTH GREATER THAN 200 FEET AND/OR BRANCH

CIRCUIT HOMERUNS LONGER THAN 125 FEET, I.E.; #12 AWG INCREASED TO #10

AWG FOR RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH

(INCLUDING THE HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET.

25. KEEP CONDUCTOR SPLICES TO A MINIMUM. INSTALL SPLICES AND TAPES THAT

POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION

RATINGS THAN CONDUCTORS BEING SPLICED. USE SPLICE AND TAP CONNECTORS

COMPATIBLE WITH CONDUCTOR MATERIAL. INSTALL CONDUCTORS AT EACH

OUTLET WITH AT LEAST 6 INCHES OF SLACK. CONNECT OUTLETS AND

COMPONENTS TO WIRING AND TO GROUND AS INDICATED AND INSTRUCTED BY

THE MANUFACTURER.

26. DO NOT SPLICE BRANCH CIRCUIT HOMERUNS WITHOUT THE PERMISSION OF THE

GOVERNMENT. HOMERUNS MUST BE CONTINUOUS FROM THE LAST OUTLET BOX

TO THE SERVING PANELBOARD.

27. DO NOT COMBINE BRANCH CIRCUIT HOMERUNS UNLESS SPECIFICALLY INDICATED

ON THE DRAWINGS.

28. INSTALL WIRING DEVICES AT HEIGHTS AS SHOWN ON THE DRAWINGS.

29. PROVIDE GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL IN

ACCORDANCE WITH THE NEC INCLUDING EXTERIOR RECEPTACLES AND

RECEPTACLES IN AREAS SUBJECT TO POSSIBLE WET CONDITIONS.

30. COORDINATE LOCATIONS OF MECHANICAL EQUIPMENT WITH THE RESPECTIVE

CONTRACTOR, VENDORS AND THE GOVERNMENT BEFORE ROUGH-IN. ADJUST

LIGHTING FIXTURES, RECEPTACLES AND ELECTRICAL EQUIPMENT TO

ACCOMMODATE THIS EQUIPMENT. ADVISE THE GOVERNMENT OF CONFLICTS

BEFORE ROUGH-IN.

31. BEFORE COMMENCING WORK OR ORDERING MATERIALS, THE CONTRACTOR MUST

COORDINATE WITH OTHER TRADES AND VERIFY THE NAMEPLATE RATINGS OF ALL

EQUIPMENT (MOTORS, HEATERS, COMPRESSORS, ETC.) AND ADJUST THE RATINGS

OF THE ELECTRICAL EQUIPMENT (SWITCHES, FUSES, CIRCUIT BREAKERS,

FEEDERS, ETC.) AS APPROPRIATE TO SERVE THIS EQUIPMENT.

32. ENERGIZE EQUIPMENT ONLY AFTER OBTAINING PERMISSION FROM THE

CONTRACTOR PROVIDING THE EQUIPMENT.

33. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR MUST MAKE FINAL

CONNECTIONS TO ALL UTILIZATION EQUIPMENT SHOWN ON THE DRAWINGS.

VERIFY THE TYPE OF FINAL CONNECTION AND PROVIDE APPROPRIATE WIRING

METHOD. THE CONTRACTOR MUST COORDINATE WITH THE MECHANICAL TRADE,

PRIOR TO ORDERING OR INSTALLATION OF ANY EQUIPMENT, TO VERIFY

MECHANICAL EQUIPMENT REQUIREMENTS ARE PROVIDED IN THE ELECTRICAL

DESIGN. THE CONTRACTOR WILL NOT BE COMPENSATED FOR COSTS ASSOCIATED

WITH CHANGING THE ELECTRICAL SYSTEMS TO MATCH UTILIZATION EQUIPMENT,

EVEN IF THE ELECTRICAL WORK IS INSTALLED PER THE ELECTRICAL DRAWINGS.

34. THE CONTRACTOR MUST COORDINATE ALL EQUIPMENT TERMINATIONS, PLUGS

AND CORDSETS WITH VENDOR EQUIPMENT AND VERIFY ALL DEVICE LOCATIONS

FOR SPECIALITY EQUIPMENT WITH CASEWORK PRIOR TO ROUGH-IN.

35. INSTALLATION INFORMATION PACKED WITH DEVICES AND EQUIPMENT MUST BE

RETAINED FOR INCLUSION IN THE OPERATIONS AND MAINTENANCE MANUALS.

36. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH THE

EXISTING ELECTRICAL SYSTEMS AND THE EXISTING BUILDING. THE SUBMISSION

OF THE PROPOSAL BY THE CONTRACTOR SHALL BE CONSIDERED EVIDENCE THAT

HE OR HIS REPRESENTATIVE HAS VISITED THE SITE AND BUILDINGS AND NOTED

THE LOCATION AND CONDITIONS UNDER WHICH THE WORK WILL BE PERFORMED

AND THAT HE TAKES FULL RESPONSIBILITY OF ALL FACTORS GOVERNING HIS

WORK. NO EXTRAS WILL BE CONSIDERED BECAUSE OF ADDITIONAL WORK

NECESSITATED BY EXISTING JOB CONDITIONS THAT ARE NOT INDICATED ON THE

DRAWINGS.

37. CONTRACTOR SHALL VERIFY ALL EQUIPMENT AND MECHANICAL CHARACTERISTICS

PRIOR TO BEGINNING WORK. CONTRACTOR SHALL MATCH ELECTRICAL

REQUIREMENTS AS REQUIRED BY MECHANICAL EQUIPMENT.

37. SAFETY

A. COMPLY WITH OSHA AND NEC ARC FLASH PROTECTION REQUIREMENTS.

B. FOR EQUIPMENT BEING REMOVED AND REPLACED, THE CONTRACTOR SHALL

DE-ENERGIZE THE EQUIPMENT AND MAKE IT SAFE PRIOR TO REMOVAL AND

COMPLY WITH OSHA REQUIREMENTS FOR LOCKING-OUT AND TAGGING

EQUIPMENT TO PREVENT INADVERTENT RE-ENERGIZING.

EXIT

FINISHED CEILING

FLOOR

DOOR

ABOVE COUNTER

RECEPTACLE/DATA3"

NOTE:

DETAIL SHOWN FOR REFERENCE ONLY, NOT ALL DEVICES ARE INDICATED ON PLANS.

BACK SPLASHSTRIKE SIDE

HINGE SIDE

COUNTER TOP

LIGHT SWITCH

/DIMMER

CABLE, VOICE/DATA, DUPLEX &

QUADRAPLEX RECEPTACLES

GANG

SWITCHING

MECHANICAL

CASETTE

CLOCK HANGER

RECEPTACLE

WALL MOUNTED EXIT SIGN

ABOVE DOOR (MAX. MT. HT. OF

80" ABOVE TOP OF DOOR)

6"6"

EQ

EQ

EQ.EQ.EQ.

ELECTRICAL DEVICES MOUNTING HEIGHT

CABLE TV

OUTLET

TV RECEPTACLE

A/V OUTLET

(HDMI)

LIGHTING PANEL, LIGHT POLE

LIGHTING

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MOTOR CIRCUIT PROTECTOR

MAIN DISTRIBUTION PANEL

MANUFACTURER

MANHOLE

MAIN LUGS ONLY

MOUNTED

MOUNTING

MANUAL TRANSFER SWITCH

MEDIUM VOLTAGE

NEUTRAL

NOT APPLICABLE

NORMALLY CLOSED

NATIONAL ELECTRIC CODE

NOT IN CONTRACT

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

POLE

PUBLIC ADDRESS

PULL BOX, PUSH-BUTTON

POWER FACTOR

PHASE

PROGRAMMABLE LOGIC CONTROLLER

PANEL

POWER PANEL, POWER POLE

PORTABLE POWER EQUIPMENT CABLE

POTENTIAL TRANSFORMER

POWER

RECEPTACLE

REQUIRED

RIGID GALVANIZED STEEL CONDUIT

ROOM

REMOTE TELEMETRY UNIT

DC MOTOR DRIVE

SHEET

SURGE PROTECTION DEVICE

SPECIFICATION

SELECTOR SWITCH

STAINLESS STEEL

SWITCH

SWITCHBOARD

SWITCH GEAR

TELEPHONE

TWISTED PAIR SHIELDED

TRANSIENT VOLTAGE SURGE SUPPRESSER

TYPICAL

UNDERGROUND

UNIT HEATER

UNLESS OTHERWISE NOTED

UTILITY

VOLTS

VARIABLE FREQUENCY DRIVE

WIRE, WATT

WATT-HOUR

WEATHERPROOF

WEATHERPROOF TELEPHONE ENCLOSURE

TRANSFORMER

EXISTING RELOCATED

A, AMP

AFF

AFG

AHU

AIC

ATS

AWG

BOF

BRKR

C, CND

CAB

CAT

CL

CB

CCTV

CKT

CLG

CP

CR

CS

CV

CT

CU

EF

EMER

EMT

ENCL

EQUIP

EWC

EWH

EPRF

FA

FAAP

FACP

FBO

FLA

FLUOR

FLR

FWE

GEN

G, GND

GFCI

HH

HID

HOA

HP

HPF

HPS

HTR

HV

Hz

IMC

INCAND

JB

K

KCMIL

KVA

KW

KWH

AMPERE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

BOTTOM OF FIXTURE

BREAKER

CONDUIT

CABINET

CATALOG

CHLORINE

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CIRCUIT

CEILING

CONTROL PANEL

CONTROL RELAY, CORROSION RESISTANT

CONTROL SWITCH

CONTROL VALVE

CURRENT TRANSFORMER

COPPER

EXHAUST FAN

EMERGENCY

ELECTRICAL METALLIC TUBING

ENCLOSURE

EQUIPMENT

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

EXPLOSION PROOF

FIRE ALARM

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FURNISHED BY OTHERS

FULL LOAD AMPS

FLUORESCENT

FLOOR

FURNISHED WITH EQUIPMENT

GENERATOR

GROUND

GROUND FAULT CURRENT INTERRUPTER

HANDHOLE

HIGH INTENSITY DISCHARGE

HAND-OFF-AUTO

HORSE POWER

HIGH POWER FACTOR

HIGH PRESSURE SODIUM

HEATER

HIGH VOLTAGE

HERTZ

INTERMEDIATE METALLIC CONDUIT

INCANDESCENT

JUNCTION BOX

THOUSAND

THOUSAND CIRCULAR MILLS

KILOVOLT AMPERE

KILOWATTS

KILOWATT-HOURS

LP

LTG

MCB

MCC

MCP

MDP

MFR

MH

MLO

MTD

MTG

MTS

MV

N / NEUT

NA

NC

NEC

NIC

NL

NO

NTS

P

PA

PB

PF

PH

PLC

PNL

P

PPE

PT

PWR

RECPT, RCP

REQ'D

RGS

RM

RTU

DCM

SH

SPD

SPEC

SS

SST

SW

SWBD

SWGR

TEL

TPS

TVSS

TYP

UGND

UH

UON

UTIL

V

VFD

W

WH

WP

WTE

XFMR

X/R

ABBREVIATIONS

os

G

FC

I

G

FC

I

G

FC

I

G

FC

I

SLV SLV

os os os os

30A/3/3R 30A/3/3R

G

FC

I

G

FC

I

SLV

W

AT

ER

-G

FC

I

MDP-32

MDP-30

MDP-49,51,53

MDP-52

MDP-54

MDP-44,46

MDP-48,50

MDP-25

MDP-31

CONST. CONTR. NO.

EXISTING 200A MDP PANELBOARD W/ 200 MCB. TYPE NQOD SERIES E2. 3 ɸ 4W

208Y/120V, TO REMAIN. PROVIDE NEW BREAKERS TO FEED CIRCUITS REQUIRED.

PROVIDE NEW GFCI RECEPTACLES & CIRCUIT(S) AS INDICATED. MIN. 2 - #12, 1 -

#12 EGC IN 1/2" C. FLUSH IN NEW WALLS.

PROVIDE NEW LUMINAIRES & CIRCUIT(S) AS INDICATED. SEE LIGHTING FIXTURE

SCHEDULE. MIN. 2 - #12, 1 - #12 EGC IN 1/2" C.

PROVIDE NEW CIRCUIT(S) TO EF-1 & EF-2 AS INDICATED. PROVIDE MINIMUM 2 - #12,

1 - #12 EGC IN 12"C.

PROVIDE NEW CIRCUIT(S) FOR ERH-1 & ERH-2. PROVIDE MINIMUM 2 - #10,

1 - #12 EGC IN 34" C. PROVIDE SAFETY DISCONNECT(S) AS REQUIRED.

PROVIDE NEW DUAL TECHNOLOGY OCCUPANCY SENSORS / LOW VOLTAGE

SWITCHING FOR LUMINAIRES AND EXHAUST FANS. LUMINAIRES AND EXHAUST

FANS MUST BE SWITCHED TOGETHER. SEE OCCUPANCY SENSOR DIAGRAM FOR

ADDITIONAL DETAILS.

PROVIDE NEW CIRCUIT TO WATER HEATER (WH-1). MIN. 3 - #6 - 1 #10 EGC IN 1 14" C.

PROVIDE NEW CIRCUIT HOMERUN(S) AND CONNECTION(S) TO EACH HARDWIRED

FLUSH, URINAL, AND LAVATORY CONNECTION (P1, P2, P3). MIN. 2 - #12, 1 -12 EGC

IN 12". COORDINATE WITH MECHANICAL SHEETS.

PROVIDE (2) 120V/20A WEATHER PROOF GFCI RECEPTACLES FROM PANELBOARD

MDP TO SUPPLY ASSE1060 HOT BOX/HEAT TRACE. COORDINATE WITH

MECHANICAL SHEETS & MANUFACTURER REQUIREMENTS. PROVIDE NEW 20A/1

BREAKERS. MIN. 2 - #12, 1 - #12 EGC IN 12"C. PROVIDE SELF REGULATING CABLE

CONNECTION, AS REQUIRED.

1. REMOVE LUMINAIRE(S), CONDUCTOR(S), SWITCH(ES), AND CONDUIT(S) SERVING

THE IDENTIFIED WORK AREA & AS REQUIRED TO COMPLETE NEW WORK. REMOVE

CONDUCTORS COMPLETE BACK TO PANELBOARD.

2. REMOVE RECEPTACLE(S), CONDUCTOR(S), AND CONDUIT(S) SERVING THE

IDENTIFIED WORK AREA. REMOVE CONDUCTORS COMPLETE BACK TO PANELBOARD.

3. REMOVE EXHAUST FANS AND RELATED MECHANICAL SERVING THE WORK AREA.

COORDINATE WITH MECHANICAL SHEETS.

4. EXISTING PANELBOARD TO REMAIN.

5. OTHER ELECTRICAL CONNECTIONS PASSING THROUGH THE WORK AREA ARE

PERMITTED TO BE RECONFIGURED BUT EXISTING FUNCTIONALITY MUST BE

MAINTAINED.

6. PRESERVE AND PROTECT ALL TELECOMMUNICATIONS.

A

A

B B

1. PROVIDE NEW LIGHTING PLAN AS INDICATED. SEE LIGHTING FIXTURE SCHEDULE &

LUMINAIRE PLATES. PROVIDE NEW CONDUCTORS IN CONDUIT TO CIRCUIT IN MDP

PANELBOARD.

2. PROVIDE NEW POWER PLAN AS INDICATED. PROVIDE NEW CONDUCTORS IN

CONDUIT TO CIRCUIT IN MDP PANELBOARD.

3. IF DRYWALL IS CUT OR DAMAGED IT MUST BE PATCHED AND RESTORED TO

ORIGINAL CONDITIONS. REPAINT ENTIRE ROOM TO MATCH EXISTING CONDITIONS.

GENERAL NEW WORK NOTES

KEYED NEW WORK NOTES

NEW WORK: LIGHTING AND POWER PLAN

DEMOLITION PLAN

DEMOLITION NOTES

2 2

SCALE: NTS

SCALE: NTS

CC

SURFACE LED WRAPAROUND

REVISED: NOVEMBER 2020 NL-3LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD ROLLED STEEL, WITH REINFORCEMENT RIBS FOR

RIGIDITY; ENDCAPS SAME MATERIAL AS HOUSING, SECURED TABS, SCREWS, OR

RIVETS. SIZE AS INDICATED IN LUMINAIRE SCHEDULE.

2. OPTICS - ACRYLIC OR POLYCARBONATE LENS AS INDICATED IN LUMINAIRE

SCHEDULE.

3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND

MINIMUM EFFICACY OF 110 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS

INDICATED IN LUMINAIRE SCHEDULE.

4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9

PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD.

ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS

INDICATED IN LUMINAIRE SCHEDULE.

5. CERTIFICATION - UL LISTED FOR DAMP LOCATION, ROHS COMPLIANT, DLC

QUALIFIED. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.

6. MOUNTING - SURFACE MOUNTED.

7. OPTIONS - EMERGENCY BATTERY BACK-UP, INTEGRAL OCCUPANCY/VACANCY

SENSOR, VARIOUS SIZE AND OUTPUT OPTIONS.

NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET

THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR

PREFERENCE.

DIRECT WALL-MOUNTED LINEAR

REVISED: NOVEMBER 2020 NL-7LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - COLD ROLLED STEEL, EXTRUDED ALUMINUM, OR DIE CAST

ALUMINUM BODY WITH DIE CAST END CAPS AND STAINLESS STEEL HARDWARE.

SIZE AS INDICATED IN LUMINAIRE SCHEDULE.

2. OPTICS - REFRACTIVE LENS OPTIMIZED FOR ASYMMETRIC DISTRIBUTION.

3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND

MINIMUM EFFICACY OF 85 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS

INDICATED IN LUMINAIRE SCHEDULE.

4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH

MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT,

AND < 20% THD. ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10%

MINIMUM OR AS INDICATED IN LUMINAIRE SCHEDULE.

5. CERTIFICATION - UL LISTED FOR DAMP LOCATION, ROHS COMPLIANT. COMPLIES

WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.

6. MOUNTING - WALL SURFACE MOUNTED

7. OPTIONS - EMERGENCY BATTERY BACK-UP, AND VARIOUS PROFILE DIMENSIONS

AND RUN LENGTHS. ALSO AVAILABLE WITH INDIRECT LIGHTING ELEMENT.

NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET

THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR

PREFERENCE.

CEILING OCCUPANCY/VACANCY SENSOR DIMMING DIAGRAM

OPERATION

1. BATHROOMS ROOMS MUST ILLUMINATE TO 100% PER OCCUPANCY SENSOR

SIGNAL.

2. AFTER 15 MINUTES OF VACANCY SENSING, LIGHT FIXTURES MUST TURN OFF.

LOAD SERVED

WIRE

SIZE

TRIP

POLE

CKT

NO. A

VA/PHASE

B C

CKT

NO.

TRIP

POLE

WIRE

SIZE LOAD SERVED

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

1. HVAC EQUIPMENT SHALL USE TYPE HACR BREAKERS.

EXISTING PANELBOARD: MDP

TOTAL VOLT/AMPS

CONNECTED AMPS

#12

125A/3

20A/1

20A/1#12

20A/1#12 #1220A/1

BREAKERMAINWITH

ONLYLUGMAINWITH

XSQR.D-E2MFG

XLOAD

WIRE4Ø3

AMP200

AIC

RMSVOLT208Y/120

FLUSH

SURFACE

X

20A/1

20A/1 #1220A/1#12 20A/1 #1220A/1#12 20A/1 #1220A/1#12

20A/1 #1220A/1#12RECEPTACLES

HEATER

LIGHTING

20A/1#12 #1220A/1 20A/1#12 20A/1#12

#12

20A/1#12 20A/1 20A/1 20A/1 20A/1

#12 #12 #12 #12

#6

#1020A/2

200A

LIGHTING

LIGHTING

EXT.LIGHTING

FA.CTRLPNL

PTHP-1

FRIDGE

RECEPTACLES

HEATER

RECEPTACLES

LIGHTS

NMCI

NMCI

WATER-COOLER(NEW)

MARK DESCRIPTION SIZE/APERATURE VOLTS LAMPS WATTS COLOR

A

B

NL-3, SURFACE LED WRAP AROUND 2x4 120V

LED

3500K

4000 LUMN

NL-7, WALL MOUNTED LINEAR VARIES 103500K

800 LUMN

120V

WHITE

WHITE

LIGHTING FIXTURE SCHEDULE

NOTES

1. PANELBOARD SCHEDULE IS A REPRESENTATION OF EXISTING CONDITIONS.

FIELD VERIFY ALL CIRCUTS AND CONDITIONS BEFORE BEGINNING WORK.

2. PROVIDE NEW BREAKERS TO MATCH PANELBOARD AND CIRCUIT

REQUIREMENTS INDICATED.

3. COMPLETELY UPDATE PANELBOARD DIRECTORY INDICATING ALL NEW AND

EXISTING LOADS BEING SERVED.

4. UNUSED OR SPARE BREAKERS ARE PERMITTED TO BE REMOVED WHERE

SPACE IS REQUIRED FOR NEW CIRCUITS.

#1220A/1

EMERGENCY LIGHTING UNIT (ELU)

REVISED: NL-26LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - HIGH-IMPACT, UV-STABILIZED, INJECTION-MOLDED THERMOPLASTIC

HOUSING.

2. LIGHT SOURCE - SOLID STATE LEDS.

3. DRIVER - INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,

OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD.

ON/OFF CONTROL AND BATTERY BACKUP INTEGRAL TO UNIT.

4. CERTIFICATION - NFPA 101. UL LISTED FOR DAMP OR WET LOCATION, ROHS

COMPLIANT. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.

5. MOUNTING - WALL SURFACE MOUNTED.

6. OPTIONS - WHITE OR BLACK FINISH.

NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET

THE

SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR

PREFERENCE.

NOVEMBER 2020

#1220A/2

C NL-26, EMERGENCY LIGHTING UNIT W/ AIMABLE HEADS VARIES 120V

LED

200 LUMN/HD

5 WHITE

LED HEATER

20A/1#12 20A/1#12

LOAD

LOAD

LOAD

LOAD

ASSE1660(NEW)

LOAD

LOAD

WH-1(NEW)

SUBPANEL-"A"

20A/3 LOAD

BTHRM-RECEPT.(NEW)

BTHRM-LIGHTS(NEW)

#1220A/2 FA.TRANSMITTER

FLUSH-SENSOR(NEW)

#1220A/2 HEATPUMP

HEATPUMP

POWER-POLES

#1220A/1 #1220A/1

50A/3

#1220A/1

ERH-1(NEW)

ERH-2(NEW)

EF-1(NEW)#1220A/1

#1220A/1 EF-2(NEW)

#1030A/2

#1030A/2

1/0

FA.CTRLPNL

Sheets and Views
G-1
25-0015 Repair Heads Building 1826 (ArchDoneFinal)-A-104.pdf
Sheets and Views
A-4
25-0015 Repair Heads Building 1826 (ArchDoneFinal)-A-103.pdf
Sheets and Views
A-3
25-0015 Repair Heads Building 1826 (ArchDoneFinal)-A-102.pdf
Sheets and Views
A-2
25-0015 Repair Heads Building 1826 (ArchDoneFinal)-A-101.pdf
Sheets and Views
A-1
M_P_1826-Model P601.pdf
Sheets and Views
Model
M_P_1826-Model p103.pdf
Sheets and Views
Model
M_P_1826-Model p102.pdf
Sheets and Views
Model
M_P_1826-Model p101.PDF
Sheets and Views
Model
M_P_1826-Model M101.pdf
Sheets and Views
Model
25-0015 Repair Heads Building 1826 Electrical-E-103.pdf
Sheets and Views
E-3
25-0015 Repair Heads Building 1826 Electrical-E-102.pdf
Sheets and Views
E-2
25-0015 Repair Heads Building 1826 Electrical-E-101.pdf
Sheets and Views
E-1