ESA RFI Attachment F NAVFAC Response.xlsx.pdf
PDF 117 KB Posted
- Solicitation number
- N4008524R2806
About this file
This document is a Request for Information (RFI) related to a federal contract opportunity for PROVIDE BACKUP POWER FOR STORMWATER REMOVAL PUMPS, BLDG 304, DAM NECK ANNEX. The contract will be awarded by the Department of the Navy Naval Facilities Engineering Command.
The RFI seeks information from the offeror on the scope of work for the generator, including the required KW size, runtime, Automatic Transfer Switch (ATS) amps, and enclosure type. It also requests details on the existing electrical system, such as the panels and circuits that feed the pump stations. The RFI also specifies requirements for the remote annunciator, motor control equipment, lighting, telecommunications, and the location and installation of the ATS. The contract opportunity has a solicitation number of N4008524R2806 and a proposal due date of 26 August 2024. Only contractors on the MACC group can submit proposals for this project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 24R2806 AMENDMENT 0005.pdf | ||
| 24R2806 AMENDMENT 0004.pdf | ||
| AttachmentFPPISpreadsheet MIG 1NAVFAC Response.pdf | ||
| MIGGOV PPI Spreadsheet NAVFAC Response.pdf | ||
| 24R2806 AMENDMENT 0003.pdf | ||
| 24R2806 AMENDMENT 0002.pdf | ||
| 24R2806 AMENDMENT 0001.pdf | ||
| Site Visit Sheet.pdf | ||
| va167 (1).txt | TXT text file | |
| Attachment F PPI Spreadsheet.xlsx | XLSX spreadsheet | |
| BLANK SPONSOR VERIFICATION SPREADSHEET.xls | XLS spreadsheet | |
| 1806202_Final DBRFP.pdf | ||
| I Oceana IDIQ Front End SPECS - 20220602.pdf | ||
| SECNAV 5512.pdf | ||
| N4008524R2806 GENERAL REQUIREMENTS_.pdf | ||
| PROVISION 52.204-24.pdf | ||
| DEVGRU SPREADSHEET.xlsx | XLSX spreadsheet | |
| BASE ACCESS INSTRUCTION.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page Section Para. Dwg #
Etolin Strait Associates - Dana
Shirley, Estimator
08/26/24
Please provide pictures of the following:
1. Detailed picture of where the generator will be placed out.
2. Detailed picture of the panel and surrounding area feeding pump station A
3. Detailed picture of the panel and surrounding area feeding pump station B
4. Pictures of the ground anywhere excavation will be required to run conduits for the new generator and ATS.
5. Detailed photos of the panels feeding the pump stations and their nameplates.
6.photo of Panel A in pit that is feeding control panel and pumps at Pump A. 7.
Photo of whatever panel is feeding Pump B and its location.
See pictures provided.
Etolin Strait Associates - Dana
Shirley, Estimator
08/26/24
Note #6 on the as-built drawing shows a
Range Panel (125 Amp, MLO,208/120V)which feeds Pump Station
‘B’ . Which panel in Building 304 feeds the
Range Panel for Pump Station ‘B’?
Panel is unknown. Supplemental drawings provided for information only and may not match what is onsite.
Etolin Strait Associates - Dana
Shirley, Estimator
08/26/24
Note #8 on the as-built drawing mentions the Range Panel that feeds Pump Station
‘A’ but doesn’t list any further information as in conductors size or Panel size but while onsite we found a Panel ‘A’ that feeds
Pump Station ‘A’(100 Amp, 3P Breaker, 208/120V). Which Panel in Building 304 feeds the Range Panel ‘A’?
Panel is unknown. Supplemental drawings provided for information only and may not match what is onsite.
Etolin Strait Associates - Dana
Shirley, Estimator
08/26/24
Please provide the scope of work on the
Generator Kw size. At minimum we need to be provided the kW, required run time on tank, required ATS AMPS, SE or non SE, and enclosure type (NEMA1/3R/4X/12).
Generator KW and ATS amps are to be determined by the Electrical DOR.
Etolin Strait Associates - Dana
Shirley, Estimator 08/26/24 Is there any nameplate data that can be provided for generator sizing.
Nameplate data not available.
Project Title: PROVIDE BACKUP POWER FOR
STORMWATER REMOVAL PUMPS, BLDG 304, DAM NECK
ANNEX
Solicitation / RFP#: N4008524R2806 - PPI Cut Off Date: 26 AUGUST 2024
Amend No.
GOVERNMENT RESPONSE
PPI No.
Offeror
Date
Submitted
REFERENCE
QUESTION
Etolin Strait Associates - Dana
Shirley, Estimator
08/26/24
Preliminary generator sizing based on the information in the RFP indicates a small generator will be required to serve a 48A load. Can a skid mounted fuel tank of approx. 300 gallons (approx. 200 hr run time at 100% rated load) be provided in lieu of a 500 gallon.
Fuel tank shall be as stated in the RFP.
Etolin Strait Associates - Dana
Shirley, Estimator
08/26/24
Do the existing pump controllers have any dedicated control circuits feeding them? If so, which panels are feeding them? Controls are located locally at each controller only.
Etolin Strait Associates - Dana
Shirley, Estimator 08/26/24
The RFP requires a local and remote annunciator. Where is the remote annunciator to be located?
Remote annunciator is to be located inside
Building 304.
Etolin Strait Associates - Dana
Shirley, Estimator
08/26/24
D50 Indicates to provide motor control equipment, lighting, telecommunications, emergency lighting, and exit lighting. Can the government provide supporting information on these systems?
As stated in the RFP, provide systems as necessary and required for a complete and usable system to support the work specified in the RFP.
Etolin Strait Associates - Dana
Shirley, Estimator
08/26/24
RFP indicates interior electrical distribution system requirements. Can the new ATS be located outdoors? If so, will NEMA 4X stainless steel be required?
ATS can be located outdoors and if so, it must be NEMA 4X stainless steel.
Etolin Strait Associates - Dana
Shirley, Estimator 08/26/24
How many bollards will be required around the generator, spacing between, and how far inbedded in the ground?
6 bollards are required. Spacing is based on orientation of equipment pad. Inbedded
3 feet in the ground below grade surface.