AttachmentFPPISpreadsheet MIG 1NAVFAC Response.pdf
PDF 108 KB Posted
- Solicitation number
- N4008524R2806
About this file
This document appears to be a series of questions and responses related to a Request for Proposal (RFP) for the PROVIDE BACKUP POWER FOR STORMWATER REMOVAL PUMPS, BLDG 304, DAM NECK ANNEX project.
The key details are:
- The project is to install a new standby diesel generator and automatic transfer switch to provide backup power for existing stormwater removal pumps at Pump Stations A and B located at the Naval Air Station (NAS) Oceana, Dam Neck Annex, Building 304.
- The solicitation number is N4008524R2806 with a proposal due date of 26 AUGUST 2024.
- The contracting agency is the Department of the Navy Naval Facilities Engineering Command (NAVFAC).
- The project includes questions regarding specific panels in Building 304 that feed the pump station range panels, as well as a request for additional information on the generator size, required runtime, and automatic transfer switch specifications.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 24R2806 AMENDMENT 0005.pdf | ||
| 24R2806 AMENDMENT 0004.pdf | ||
| MIGGOV PPI Spreadsheet NAVFAC Response.pdf | ||
| ESA RFI Attachment F NAVFAC Response.xlsx.pdf | ||
| 24R2806 AMENDMENT 0003.pdf | ||
| 24R2806 AMENDMENT 0002.pdf | ||
| 24R2806 AMENDMENT 0001.pdf | ||
| Site Visit Sheet.pdf | ||
| va167 (1).txt | TXT text file | |
| Attachment F PPI Spreadsheet.xlsx | XLSX spreadsheet | |
| BLANK SPONSOR VERIFICATION SPREADSHEET.xls | XLS spreadsheet | |
| 1806202_Final DBRFP.pdf | ||
| I Oceana IDIQ Front End SPECS - 20220602.pdf | ||
| SECNAV 5512.pdf | ||
| N4008524R2806 GENERAL REQUIREMENTS_.pdf | ||
| PROVISION 52.204-24.pdf | ||
| DEVGRU SPREADSHEET.xlsx | XLSX spreadsheet | |
| BASE ACCESS INSTRUCTION.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page Section Para. Dwg #
MIG
1- Note #6 on the as-built drawing shows a Range Panel (125 Amp, MLO,208/120V)which feeds Pump
Station ‘B’ . Which panel in Building 304 feeds the Range Panel for Pump Station
‘B’?
Panel is unknown. Supplemental drawings provided for information only and may not match what is onsite.
MIG
2- Note #8 on the as-built drawing mentions the Range Panel that feeds
Pump Station ‘A’ but doesn’t list any further information as in conductors size or Panel size but while onsite we found a
Panel ‘A’ that feeds Pump Station ‘A’(100
Amp, 3P Breaker, 208/120V). Which
Panel in Building 304 feeds the Range
Panel ‘A’?
Panel is unknown. Supplemental drawings provided for information only and may not match what is onsite.
MIG
3- I didn’t see anything listed in the scope of work on the Generator Kw size. At minimum they need to provide the kW, required run time on tank, required ATS
AMPS, SE or non SE, and enclosure type (NEMA1/3R/4X/12).
Generator KW and ATS amps are to be determined by the Electrical DOR.
Project Title: PROVIDE BACKUP POWER FOR STORMWATER
REMOVAL PUMPS, BLDG 304, DAM NECK ANNEX
Solicitation / RFP#: N4008524R2806 - PPI Cut Off Date: 26 AUGUST 2024
Amend No.
GOVERNMENT RESPONSE
PPI No.
Offeror
Date
Submitted
REFERENCE
QUESTION