This document appears to be a series of questions and responses related to a Request for Proposal (RFP) for the PROVIDE BACKUP POWER FOR STORMWATER REMOVAL PUMPS, BLDG 304, DAM NECK ANNEX project.

The key details are:

  • The project is to install a new standby diesel generator and automatic transfer switch to provide backup power for existing stormwater removal pumps at Pump Stations A and B located at the Naval Air Station (NAS) Oceana, Dam Neck Annex, Building 304.
  • The solicitation number is N4008524R2806 with a proposal due date of 26 AUGUST 2024.
  • The contracting agency is the Department of the Navy Naval Facilities Engineering Command (NAVFAC).
  • The project includes questions regarding specific panels in Building 304 that feed the pump station range panels, as well as a request for additional information on the generator size, required runtime, and automatic transfer switch specifications.

View the file

Other files

File Type Posted
24R2806 AMENDMENT 0005.pdf PDF
24R2806 AMENDMENT 0004.pdf PDF
MIGGOV PPI Spreadsheet NAVFAC Response.pdf PDF
ESA RFI Attachment F NAVFAC Response.xlsx.pdf PDF
24R2806 AMENDMENT 0003.pdf PDF
24R2806 AMENDMENT 0002.pdf PDF
24R2806 AMENDMENT 0001.pdf PDF
Site Visit Sheet.pdf PDF
va167 (1).txt TXT text file
Attachment F PPI Spreadsheet.xlsx XLSX spreadsheet
BLANK SPONSOR VERIFICATION SPREADSHEET.xls XLS spreadsheet
1806202_Final DBRFP.pdf PDF
I Oceana IDIQ Front End SPECS - 20220602.pdf PDF
SECNAV 5512.pdf PDF
N4008524R2806 GENERAL REQUIREMENTS_.pdf PDF
PROVISION 52.204-24.pdf PDF
DEVGRU SPREADSHEET.xlsx XLSX spreadsheet
BASE ACCESS INSTRUCTION.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page Section Para. Dwg #

MIG

1- Note #6 on the as-built drawing shows a Range Panel (125 Amp, MLO,208/120V)which feeds Pump

Station ‘B’ . Which panel in Building 304 feeds the Range Panel for Pump Station

‘B’?

Panel is unknown. Supplemental drawings provided for information only and may not match what is onsite.

MIG

2- Note #8 on the as-built drawing mentions the Range Panel that feeds

Pump Station ‘A’ but doesn’t list any further information as in conductors size or Panel size but while onsite we found a

Panel ‘A’ that feeds Pump Station ‘A’(100

Amp, 3P Breaker, 208/120V). Which

Panel in Building 304 feeds the Range

Panel ‘A’?

Panel is unknown. Supplemental drawings provided for information only and may not match what is onsite.

MIG

3- I didn’t see anything listed in the scope of work on the Generator Kw size. At minimum they need to provide the kW, required run time on tank, required ATS

AMPS, SE or non SE, and enclosure type (NEMA1/3R/4X/12).

Generator KW and ATS amps are to be determined by the Electrical DOR.

Project Title: PROVIDE BACKUP POWER FOR STORMWATER

REMOVAL PUMPS, BLDG 304, DAM NECK ANNEX

Solicitation / RFP#: N4008524R2806 - PPI Cut Off Date: 26 AUGUST 2024

Amend No.

GOVERNMENT RESPONSE

PPI No.

Offeror

Date

Submitted

REFERENCE

QUESTION