MANUFACTURER INFORMATION THIRD PARTY INSPECTION AGENCY INFORMATION
NAME: WHITLEY EAST LLC NAME: TR ARNOLD ASSOCIATES
ADDRESS: 64 HESS RD
LEOLA, PA 17540
BUILDING INFORMATION
PROJECT NAME: NAVAL UNDERSEA WARFARE CENTER BUILD 1246 COLLABORATION SPACE
MODEL DESIGNATION: 7837
SITE ADDRESS: 47 CHANDLER STREET, NEWPORT, RI 02841-1716
OCCUPANCY TYPE: B (BUSINESS)
CONSTRUCTION TYPE: V-B (STEEL FRAMED WALLS w/ WOOD SHEAR PANELS - UNPROTECTED)
BUILDING AREA: 1042 FT2
ENCLOSED SPACE: 7292 FT3
BUILDING HEIGHT ABOVE GRADE: 14' - 1"
OCCUPANT LOAD: 11, OR LESS
SPECIAL SYSTEMS: N/A
FIRE ALARM: SYSTEM SUPPLIED
AND INSTALLED ON SITE BY CERTIFIED INSTALLER
FIRE SUPPRESSION: NONE
BUILDING DESIGN LOADS
FLOOR LIVE LOAD UNIFORM 100 PSF
FLOOR LIVE LOAD CONCENTRATED 2000 LBS
FLOOR IMPACT LOAD N/A LBS
FLOOR DEAD LOAD 11.02 PSF
ROOF LIVE LOAD (SNOW) 30 PSF
GROUND SNOW LOAD 30 PSF
ROOF DEAD LOAD 8.58 PSF
FLAT ROOF SNOW LOAD 23.1 PSF
SNOW EXPOSURE FACTOR 1.00
SNOW LOAD IMPORTANCE FACTOR 1.00
THERMAL FACTOR 1.0
RAIN ON SNOW SURCHARGE LOAD N/A
BASIC WIND SPEED (VULT) 130 MPH
BASIC WIND SPEED (VASD) 100.69 MPH
RISK CATEGORY II
WIND EXPOSURE D
DESIGN WIND PRESSURE (HORIZONTAL) 28.76 PSF
DESIGN WIND PRESSURE (UPLIFT) 25.92 PSF
SEISMIC IMPORTANCE FACTOR 1.00
SEISMIC DESIGN CATEGORY B
SPECTRAL RESPONSE COEFFICIENT SDS 0.202
SPECTRAL RESPONSE COEFFICIENT SD1 0.083
SITE CLASS D
BASIC SEISMIC-FORCE-RESISTING SYSTEM A.16
DESIGN BASE SHEAR 1223.32 LBS
BUILDING DESIGN CODES
BU 2021 RISBC-1 (2018 INTERNATIONAL BUILDING CODE w/ RI STATE AMENDMENTS)
ME 2021 RISBC-4 (2018 INTERNATIONAL MECHANICAL CODE w/ RI STATE AMENDMENTS)
PL 2021 RISBC-3 (2018 INTERNATIONAL PLUMBING CODE w/ RI STATE AMENDMENTS)
EL 2021 RISBC-5 (2020 NFPA-70 NATIONAL ELECTRICAL CODE w/ RI STATE AMENDMENTS)
EN 2021 RISBC-8 (2018 INTERNATIONAL ENERGY CONSERVATION CODE w/ RI STATE AMENDMENTS)
FR 2018 NFPA-1 FIRE CODE w/ RI STATE AMENDMENTS
FG 2021 RISBC-19 (2018 INTERNATIONAL FUEL GAS CODE w/ RI STATE AMENDMENTS)
AC 2021 RISBC-1 (2018 INTERNATIONAL BUILDING CODE w/ RI STATE AMENDMENTS)
LS 2018 NFPA-101 LIFE SAFETY CODE w/ RI STATE AMENDMENTS
GENERAL SPECIFICATION NOTES:
1.) BUILDING NOT TO BE LOCATED IN A DESIGNATED FIRE ZONE.
2.) THIS BUILDING SHALL BE LOCATED MORE THAN 10 FEET AWAY FROM ANY
PROPERTY LINE OR ANY INTERIOR LOT LINE BETWEEN IT AND ANY OTHER
BUILDING.
3.) THIS BUILDING NOT TO BE LOCATED IN A FLOOD PRONE AREA.
4.) WHITLEY MFG. CO., INC. IS NOT RESPONSIBLE FOR THE LOCAL
BUILDING CODE REQUIREMENTS OVER AND ABOVE THE ENCLOSED
SPECIFICATIONS. THE SPECIFICATIONS ARE BASED ON THE DESIGN
PARAMETERS OF THE CODES LISTED ABOVE.
5.) DRINKING FOUNTAINS AND SERVICE SINKS SHALL BE PROVIDED
AND INSTALLED BY CERTIFIED INSTALLER.
6.) ADDITIONAL RESTROOM AND HANDICAPPED RESTROOM FACILITIES (IF REQUIRED
DUE TO BULDING OCCUPANT LOAD) SHALL BE READILY ACCESSIBLE AND THE PATH
OF TRAVEL SHALL NOT BE MORE THAN A TRAVEL DISTANCE OF 500'.
LOCAL BUILDING OFFICIAL TO VERIFY EXISTING FACILITIES.
7.) DUPLICATES OF THIS BUILDING CAN BE BUILT AS A MIRROR IMAGE.
8.) DUPLICATES OF THIS BUILDING CAN BE BUILT AS A SHELL.
9.) SITE BUILDER/CERTIFIED INSTALLER SHALL BE RESPONSIBLE FOR ON SITE BARRIER
FREE PROVISIONS INCLUDING: ALL ADA REQUIRED STEPS, RAMPS
HANDRAILS, PARKING, AND APPLICABLE SIGNAGE (INTERIOR AND
EXTERIOR) FOR THE VISUALLY IMPARED AND NON-AMBULATORY.
A101
SIM
A101
SIM
0 0
0 0
1t
Room name
150 SF
1 View Name 1/8" = 1'-0"
VIEW NUMBER,
NAME AND SCALE
ELEVATION SYMBOL
SECTION SYMBOL
WINDOW TAG
ROOM NAME,
NUMBER AND AREA
WELD SYMBOL
GENERAL SYMBOL LEGEND
REVISION TAG 1
DOOR TAG 101
BATT INSULATION
CONCRETE
STEEL
WOOD
RIGID INSULATION
PLYWOOD / OSB
GYPSUM
1st- floor12 1st- w alls- columns24 1st- flel- drs10 1st- flel9 1st-flme- p11 1st- walls23 common27 1st-common1 1st- floor- dim130 0
Drawn By: Serial No.
Page No.
Scale:
THIS DRAWING AND ALL INFORMATION
CONTAINED HEREON IS THE
PROPERTY OF WHITLEY MFG. CO. INC.,
AND IS NOT TO BE REPRODUCED
WITHOUT THE EXPRESS PERMISSION
OF WHITLEY MFG. CO., INC.
WHITLEY MFG. CO. INC., ASSUMES NO
RESPONSIBILITY FOR UNAUTHORIZED
USE OF THIS DRAWING.
Quote No.
Model No.
Job No.
Date:
Rev:
Checked By:
No. Description Date Whitley East, LLC
64 HESS ROAD
LEOLA, PA 17540
PHONE: 717.656.2081
www.whitleyman.com
C U
ST
O
M
ER
A
PP
R O
VA
L
SE
T
SPACE RESERVED FOR P.E. SEAL ONLYSPACE RESERVED FOR THIRD
PARTY INSPECTION SEAL ONLY
SPACE RESERVED FOR STATE
INSIGNIA OF APPROVAL
6/
/2
7:
:3
AM
As indicated
6/30/2022
7:00:30 AM
A0.02022-072-WP
EP 2696-97
49675-99
DL/CZ
(2) 10'-0" x 52'-0" MODULES
COVER SHEET
SUSTAINABLE MODULAR MANAGEMENT
NAVAL UNDERSEA WARFARE CENTER
SITE ADDRESS:
47 CHANDLER STREET
NEWPORT, RI 02841-1716
SUSTAINABLE MODULAR MANAGEMENT
NAVAL UNDERSEA WARFARE CENTER
INDEX (12 TOTAL):
A0.0 COVER SHEET
A0.1 SPECIFICATIONS
A1.0 EXTERIOR ELEVATIONS
A2.1 ARCHITECUTRAL PLANS AND ELEVATIONS
A7.1 ROOFTOP PLAN
E1.0 ELECTRICAL NOTES AND DETAILS
E2.1 ELECTRICAL PLAN
M2.1 MECHANICAL PLAN
P2.1 PLUMBING SCHEMATICS
S0.1 SUGGESTED BLOCKING PLAN
S1.1 FRAME PLAN
S5.1 BUILDING SECTIONS
SPACE RESERVED FOR P.E. SEAL ONLYSPACE RESERVED FOR THIRD
PARTY INSPECTION SEAL ONLY
SPACE RESERVED FOR STATE SEAL ONLY
Module Shipping Information
Module Serial Number Module Number Module Size
Module Shipping Height
Module Shipping Weight
Allowable Ship Loose Weight / Ballast
Axle Quantity Tire Size Coupler Type Coupler Size Coupler MFR.
Coupler Height Above Grade
2696 1 12'-4" x 56'-4" 13' - 6" 21,100 lbs 2,200 lbs 4 8:00 x 14.5 14 PLY BALL 0' - 2 5/16" VENTURE 1' - 4 3/4"
2697 2 12'-4" x 57'-0" 13' - 6" 23,100 lbs 2,000 lbs 4 8:00 x 14.5 14 PLY BALL 0' - 2 5/16" VENTURE 1' - 4 3/4"
GENERAL CONTRACTOR NOTES:
1. DIMENSIONS LISTED HEREIN TO BE HELD TO STANDARD CONSTRUCTION TOLERANCES
AT THE DISCRETION OF THE WHITLEY MANUFACTURING UNLESS OTHERWISE NOTED.
2. TERMINOLOGY USED WITHIN THE MODULAR BUILDING INDUSTRY OR
WHITELY MANUFACTURING MAY DIFFER FROM THE COMMON CONSTRUCTION
NOMENCLATURE IN THE CONSTRUCTION INDUSTRY. WHITLEY MANUFACTURING
RESERVES THE RIGHT TO US USE AND INTERPRET LANGUAGE AS IT DEEMS NECESSARY
TO CONVEY ITS METHODS OF MODULAR CONSTRUCTION.
3. ADDITIONAL SITE INSTALLED EQUIPMENT, MATERIALS OR OTHER ATTACHMENTS
(SUPPLIED AND INSTALLED BY OTHERS) OUTSIDE OF APPROVED DRAWINGS AND SUPPLY FROM,
OR BY WHITLEY MANUFACTURING, IS SUBJECT TO COMPLIANCE WITH LOCAL
BUILDING CODES AND THE LOCAL AUTHORITY HAVING JURISDICTION
AND IT IS THE SOLE RESPONSIBILITY OF THOSE MAKING THOSE ADDITIONS
OR CHANGES TO REVIEW, ENGINEER AND/OR SUBMIT THESE ADDITIONS
OR CHANGES TO THE LOCAL AUTHORITY HAVING JURISDICTION.
4. WHITLEY MANUFACTURING IS NOT RESPONSIBLE FOR ADDITIONAL LOADS
IMPOSED ON ITS BUILDINGS BY ADDITIONAL SITE INSTALLED EQUIPMENT
OR MATERIALS NOT DESIGNED OR CALCULATED FOR AT TIME OF BID.
ANY ADDITIONAL LOADING MUST BE REVIEWED AND APPROVED BY A
LICENSED PROFESSIONAL ENGINEER AND/OR IS SUBJECT TO REVIEW AND
APPROVAL BY THE LOCAL AUTHORITY HAVING JURISDICTION.
5. ALL WORK PERFORMED UNDER THIS PROJECT SHALL ONLY INCLUDE ITEMS,
INCLUDING PART NUMBERS, SPECIFICALLY DEFINED AND LISTED IN WHITLEY’S
BID DOCUMENTS. ANY WORK PERFORMED, OR MATERIAL SUPPLIED, IN CONJUNCTION
WITH THIS PROJECT SHALL BE GOVERNED BY THE TERMS AND CONDITIONS ATTACHED HERETO.
6. ANY DRAWING, PURCHASING, CUSTOMER CHANGE OR CHANGE-IN-CONSTRUCTION
NOT AFFECTING CODE APPROVAL MAY BE CHANGED
AT THE DISCRETION OF WHITLEY MANUFACTURING,
SO LONG AS DRAWINGS REFLECT THE APPROPRIATE REVISION MARKS TO INDICATE
WHERE THE REVISION HAS TAKEN PLACE ON THE DRAWING AND IS DATED ELECTRONICALLY
IN THE MANUFACTURERS ELECTRONIC FILE FOR THE PROJECT.
7. THE WHITLEY EAST LIMITED WARRANTY IS FOR 12 MONTHS FROM THE ORIGINAL
DATE OF MANUFACTURER’S INVOICE ONLY AND ITS TERMS AND CONDITIONS ARE
HEREBY MADE PART OF THIS DRAWING SET. A COPY OF THE LIMITED WARRANTY IS
INCLUDED WITHIN EACH MODULE SHIPPED FROM THE FACTORY. A COPY MAY BE
OBTAINED BY EMAIL FROM THE FACTORY BY CALLING: 717.656.2081. PLEASE READ
THE LIMITED WARRANTY AS TERMS AND CONDITIONS APPLY FOR TRANSPORT.
8. WHITLEY EAST SHALL NOT BE OBLIGATED TO PERFORM ANY WORK NOT SPECIFICALLY LISTED.
9. WHITLEY RESERVES THE RIGHT TO SUBSTITUTE AND/OR CHANGE NON-SPECIFIC
MATERIALS WITHOUT NOTICE. ANY MATERIALS SPECIFIED BY THE END-USER
WILL ONLY BE CHANGED THROUGH CHANGE-ORDER REQUEST.
10. TRANSPORTATION ARRANGEMENTS ARE TO BE MADE BY THE PURCHASER
ACCORDING TO THE TERMS AND CONDITIONS OUTLINED IN THE WHITLEY EAST LIMITED WARRANTY, UNLESS OTHERWISE SPECIFIED IN THE BID DOCUMENTS.
11. SET-UP OF THE BUILDING OR BUILDING UNITS SHALL BE CONDUCTED BY QUALIFIED
AND/OR STATE APPROVED MODULAR BUILDING CONTRACTOR FAMILIAR WITH THE SET-UP,
INSTALLATION AND FINISH REQUIREMENTS FOR MODULAR STRUCTURES, SUCH AS
(NOT ALL INCLUSIVE) PROPER BLOCKING AND LEVELING, FINAL DOOR ADJUSTMENTS,
MEP SERVICE CONNECTIONS, AND MATE-LINE WEATHER-PROOFING.
12. A COPY OF THE APPROVED CONSTRUCTION DRAWINGS IS SHIPPED WITH
EACH PROJECT FOR USE BY THE SITE CONSTRUCTION CREW TO STAY IN
COMPLIANCE WITH THE STAMPED AND APPROVED BUILDING DRAWINGS AND CODES,
FIRE SEPARATION DISTANCES, CUSTOMER SPECIFICATIONS, AND THE LIMITED WARRANTY.
ADDITIONAL DRAWING SETS MAY BE OBTAINED FROM THE FACTORY, IF NEEDED.
WHITLEY EAST LLC IS NOT RESPONSIBLE FOR ASSUMPTIONS MADE BY OTHERS AT TIME OF QUOTE;
COORDINATION OF SITE SCOPES WITH THE FACTORY ARE RECOMMENDED BEFORE TIME OF QUOTE.
13. ANY FIRE SEPARATION OR PROTECTION (FIRE WALLS) BASED ON
PROPERTY LINES OR EXISTING BUILDINGS, AS REQUIRED BY STATE BUILDING CODES, IS NOT INCLUDED.
PROTECTED OPENINGS, IF REQUIRED, ALSO HAVE NOT BEEN QUOTED
UNLESS NOTED AS SUCH WITHIN THE ABOVE SPECIFICATIONS.
14. LOCAL CODES, FEDERAL REGULATIONS OR OTHER IMPLIED ORDINANCES ARE
NOT QUOTED BY WHITLEY EAST UNLESS FORWARDED AND OTHERWISE SPECIFIED
IN THE BID DOCUMENTS OR SHOWN IN THE DRAWING DOCUMENTS.
15. GAS LINES ARE REQUIRED TO BE INSTALLED AND TESTED BY A LOCAL,
CERTIFIED LICENSED PLUMBER AT SITE
16. DETAILS PERTAINING TO SITE SET AND CLOSE UP INCLUDED IN THIS SET MUST BE ADHERED TO.
FAILURE TO COMPLY WITH DETAILS LISTED HEREIN WITHOUT CONSULTATION OF WHITLEY
MANUFACTURING WILL ABSOLVE WHITLEY EAST FROM ANY LIABILITY.
ABBREVIATIONS
Abbv. Word
+#" UP #" A.F.F.
A AMP
A.F.F. ABOVE FINISHED FLOOR
ACT ACOUSTICAL TILE
BD BOARD
CAB CABINET
CLG CEILING
COL COLUMN
CONC CONCRETE
CPT CARPET
CU. FT. CUBIC FOOT
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DTHW DOMESTIC TEMPERED HOT WATER
DTL DETAIL
DWG DRAWING
EER ENERGY EFFICIENCY RATIO
EOS EDGE OF STUD
EQ EQUAL
EXG EXISTING
EXT. EXTERIOR
FLR FLOOR
FRT FIRE TREATED
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GLS GLASS
GWB GYPSUM WALLBOARD
GYP GYPSUM
HPP HIGH PRESSURE PNEUMATIC
HVAC HEATING, VENTILATION, AIR CONDITONING
HWD HARDWOOD
INT. INTERIOR
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
MTD MOUNTED
N/A NOT APPLICABLE
NTS NOT TO SCALE
O.C. ON CENTER
PNL PANEL
PT PRESSURE TREATED
RM ROOM
SAN SANITARY
SHT SHEET
SIM SIMILAR
SQ. FT. SQUARE FOOT
STD STANDARD
STL STEEL
TEL TELEPHONE
TYP. TYPICAL
UNO UNLESS NOTED OTHERWISE
V VOLT
VT VENT
VTR VENT THROUGH ROOF
WD WOOD
WP WEATHERPROOF
Ø DIAMETER
HATCH LEGEND
WHITLEY EAST LLC
64 HESS RD
LEOLA, PA 17540
717-656-2081
APPROVED:
APPROVED AS NOTED:
RETURN FOR CORRECTION:
BY:
DATE:
UPON APPROVAL, THESE DRAWINGS WILL TAKE
PRECEDENCE OVER ALL PREVIOUS DRAWINGS
FOR THIS PROJECT
MODULE SIZES INCLUDE HITCH AND OVERHANGS.
SIZES SUBJECT TO GROWTH DURING CONSTRUCTION;
DIMENSIONS TO BE FIELD VERIFIED BEFORE UNIT
SHIPS AND DEALER TO BE NOTIFIED WITH
FINAL FIELD VERIFIED DIMENSIONS
No. Description Date 1 Revisions per customer comments 06.29.2022
EXTERIOR DOOR WITH
VISION LITE
INTERIOR DOOR
2" 2"
2" 2"
M A
X
3' - 0"
3' - 4"
3' - 0"
3' - 4"
5"
1st- floor12 1st- w alls- columns24 1st- flel- drs10 1st- flel9 1st-flme- p11 1st- walls23 common27 1st-common1 1st- floor- dim130 0
Drawn By: Serial No.
Page No.
Scale:
THIS DRAWING AND ALL INFORMATION
CONTAINED HEREON IS THE
PROPERTY OF WHITLEY MFG. CO. INC.,
AND IS NOT TO BE REPRODUCED
WITHOUT THE EXPRESS PERMISSION
OF WHITLEY MFG. CO., INC.
WHITLEY MFG. CO. INC., ASSUMES NO
RESPONSIBILITY FOR UNAUTHORIZED
USE OF THIS DRAWING.
Quote No.
Model No.
Job No.
Date:
Rev:
Checked By:
No. Description Date Whitley East, LLC
64 HESS ROAD
LEOLA, PA 17540
PHONE: 717.656.2081
www.whitleyman.com
C U
ST
O
M
ER
A
PP
R O
VA
L
SE
T
6/
/2
7:
:3
AM
3/4" = 1'-0"
6/30/2022
7:00:31 AM
A0.12022-072-WP
EP 2696-97
49675-99
DL/CZ
(2) 10'-0" x 52'-0" MODULES
SPECIFICATIONS
SUSTAINABLE MODULAR MANAGEMENT
NAVAL UNDERSEA WARFARE CENTER
DEALER NAME: Sustainable Modular Management PROJECT NAME: Naval Undersea Warfare Center
SERIAL NUMBER: 2696-97
MODEL NUMBER: 7837
JOB I.D. # 2022-072-WP
MODEL SIZE: 20'X52' (2) 10'-0"x52'-0" MODULES
A-FRAME
NOTE: FRAME(S) TO BE MIG WELDED, INCLUDING SPRING HANGER
ATTACHMENT AND HITCH CONSTRUCTION
1 TYPE: PERIMETER
2 MAIN BEAM: W10 X 12# BEAM (A992 GRADE MINIMUM)
3 X-MEMBER: W8"x10# AT 48" O.C.
4 X-MEMBER: W10"x12# AT AXLE-MOUNTING AREAS
5 HITCH: BOLT-ON BALL COUPLER
6 AXLES: FOUR (BOGIE) -- w/ TIRES OUTBOARD OF MAIN RAIL
NOTE: WHEEL WELL BOXES INSTALLED FOR TRANSPORTATION
7 SPRINGS: MULTI-LEAF, UNDERSLUNG
w/ HANGERS, EQUALIZERS, AND AXLE ATTACHING PARTS
8 TIRES: 8:00 X 14.5, 14 PLY
9 TIE DOWN: OVER THE FRAME
NOTE: PROVIDED & INSTALLED BY CERTIFIED INSTALLER
SEE SUGGESTED BLOCKING PLAN FOR TIE DOWN LOCATIONS
10 MISC: PUNCH OR DRILL 1/2" DIA. HOLES AT 32" O.C. AT TOP FLANGE OF
PERIMETER OF FRAME FOR ATTACHING JOIST FRAMING TO CHASSIS FRAME
11 MISC: I BEAM CLAMPS SHIPPED LOOSE FOR INSTALL BY CERTIFIED INSTALLER
12 MISC: THIS UNIT WILL HAVE STEEL TUBE COLUMNS
13 MISC: THIS UNIT WILL HAVE STEEL DIAG. SHIPPING STRAPS
14 MISC: 3/4" PLYWOOD EXTERNAL WHEEL WELLS AT OUTBOARD SIDES OF FRAME
NOTE: EXTERNAL WHEEL WELLS TO BE REMOVED ON SITE WITH AXLES
15 UNDER COATING: RUST INHIBITIVE LATEX TYPE PAINT, BLACK: 100%
COVERAGE OF STRUCTURAL MEMBERS.
B-FLOOR
1 BOTTOM BOARD: FS-25, CLASS A, SHEPWEAVE II
NOTE: SHIP LOOSE BOTTOM BOARD & INSULATION FOR WHEEL-
WELL AREAS, TO BE INSTALLED BY CERTIFIED INSTALLER.
2 INSULATION: R-30c KRAFT FACED FIBERGLASS BATT 3 JOISTS: 2 x 8 (SPF #2) AT 16-IN O.C. NOMINAL
LONGITUDINAL JOISTS
w/ DBL SIDERAILS
(FRAME OUT WHEEL WELLS)
4 DECKING: 3/4" T&G UNDERLAYMENT PLYWOOD (RATED 48/24)
(HOLD BACK DECKING 11" AT MATELINE)
5 COVERING: 1/8" VINYL COMPOSITION TILE (12"x12" TILES)
(HOLD BACK COVERING AT SEAM LINE 17")
6 MISC: VINYL COVE BASE; 6"H IN RESTROOM AND 4"H IN REMAINING AREAS
C-EXTERIOR WALLS
NOTE: AT OPEN MATELINE AREAS TO BE COVERED W/VISQUEEN, INSTALL
PANELING STRIPS AT 2' O.C. VERTICALLY, FOR THE FIRST SIX-
FEET LENGTH OF OPEN AREA.
NOTE: DO NOT REMOVE TEMPORARY ROOF BRACING SUPPORTS AT MODULE
SIDES UNTIL MODULE IS SET ON PERMANENT FOUNDATION.
1 STUDS: 1 5/8" X 6" (18 GA.) STEEL 16" O.C.
W/DBL. STUDS EACH END OF SIDEWALLS
w/ 3" x 6" 18ga JAMBSTUDS AND HEADERS w/ 14ga CLIPS w/ LUMBER NAILERS INSTALLED AT THE INTERIOR OF WALL OPENINGS
2 BOTTOM PLATE: 1 1/4"D. x 6" (18 GA.) STEEL TRACK 3 TOP PLATE: 1 1/4"D. x 6" (18 GA.) STEEL TRACK
4 COVERING: 1/2" VINYL COV. GYP. BOARD (CLASS I F.S.)
NOTE: VINYL COVERED BATTENS AS REQUIRED
4a COVERING: 0.090" F.R.P. LAMINATED TO 1/2" UNIFINISHED GYP. BOARD w/ NUDO V-15 INSIDE CORNER TRIMS, AND NUDO V-25
VERTICAL BATTEN TRIMS
5 SHEATHING: 1/2" FRT CDX PLYWOOD (RATED 32/16)
6 SHEATHING: WEATHER-RESISTIVE BARRIER (TYVEK OR EQUAL)
7 SCREW BACKER: 16 GA. x 3" FLAT STEEL HORIZONTAL STRAP AT
3'-3 7/8" A.F.F. AND 7'-3 7/8" A.F.F. TO BOTTOM
8 INSULATION: R-19 F.S.K. FIBERGLASS BATT
9 INSULATION: 1 1/2" THICK EPS RIGID INSULATION BOARD (R-7.5)
OVER F.R.T. PLYWOOD SHEATHING
10 SIDING: 29 GA. STEEL PANEL w/ 3/4"D. VERT. RIB
NOTE: START SIDING 2 1/4" ABOVE TOP OF MAIN RAIL
NOTE: ALL DOORS/WINDOWS TO BE INSTALLED BEFORE SIDING
11 TRIM: 29 GA. STEEL
J-CHANNEL AT DOORS
NOTE: COLOR MATCHING U-CHANNEL INSIDE J-CHANNEL WHEN HIGH RIB IS NOT IN J-CHANNEL
BOTTOM TRIM
TOP TRIM
OUTSIDE CORNER TRIM
12 SKIRTING: 29 GA. STEEL PANEL w/ 3/4"D. VERT. RIB
AVERAGE 36" HIGH (SHIP 3X9 SHEETS)
13 COLUMNS: HSS3x3x3/16 STEEL TUBE
D-INTERIOR WALLS
1 STUDS: 2 x 4 (SPF #2) AT 16" O.C.
W/DBL. STUDS EACH END OF WALLS (SPF #2)
SGL. JAMBSTUD AT DOORS (SPF #2);
SGL. JACKSTUD UNDER DOORS HEADERS (SPF #2);
W/ DBL. 2 x 4 HEADERS (SPF #2)
NOTE: INSTALL CONTINUOUS BLOCKING BETWEEN STUDS
UP 94 1/2" TO BOTTOM OF BLOCK AT FULL HEIGHT INTERIOR WALLS
2 BOTTOM PLATE: (1) 2 x 4 (SPF #2) 3 TOP PLATE: (2) 2 x 4 (SPF #2)
4 COVERING: 1/2" VINYL COV. GYP. BOARD (CLASS I F.S.)
NOTE: VINYL COVERED BATTENS AS REQUIRED
5 COVERING: 0.090" F.R.P. LAMINATED TO 1/2" UNIFINISHED GYP. BOARD
w/ NUDO V-15 INSIDE CORNER TRIMS, AND NUDO V-25
VERTICAL BATTEN TRIMS
6 INSULATION: R-11 UNFACED FIBERGLASS BATT
7 MISC: 2x4 PLENUM WALL (STUDS AT 16" O.C.)
LINED w/ MIN. 1/2" GYPSUM BOARD 8 MISC: 2x4 CHASE WALL (STUDS AT 16" O.C.)
9 MISC: 2x6 CHASE WALL (STUDS AT 16" O.C.)
10 COLUMNS: (3) 2 x 6 (#2 SPF) NON-DADO FOR ROOF BEAM
NOTE: BASE OF COLUMN TO REST ON FLOOR DECK
E-ROOF
1 RAFTERS: 2 x 10 (SPF #2) AT 16" O.C.
NOTE: RAFTERS TO BE DADOED
2 MATE BEAM: LVL, 2.0 E (3100Fb) x 1 1/2" THICK, 11 7/8"H, 2- PLY MAX SPAN: 17' - 3"
NOTE: DBL. 2x4 (SPF#2) LEDGER
NOTE: LUMBER TAPER OVER MATE BEAM
4 CEILING: SUSPENDED T-GRID w/ 2'x 4' U.S.G. LAY-IN TILE
FINISH CEILING HT: 7' - 10 1/2"
NOTE: CEILING TILE, GRID TEES, & WALL ANGLE FOR MATE LINE
SHIPPED LOOSE FOR INSTALLATION BY CERTIFIED INSTALLER.
5 TRUE CEILING: FS-25, CLASS A, SHEPWEAVE II, ATTACHED TO UNDERSIDE
OF RAFTERS TO SUPPORT INSULATION
6 INSULATION: R-38c KRAFT-FACED FIBERGLASS BATT 7 SHEATHING: 7/16" OSB w/ MULE-HIDE FR ADHESIVE OR 7/16" OSB CLASS "C" FR DECK 8 ROOFING: EPDM RUBBER 1-PC. MEMBRANE, 45 mil, BLACK
11 VENTS: AURA ROOF TOP VENTILATION SYSTEM
AV-14-C6-NF EXHAUST VENT (SHIPPED LOOSE)
PV-14-C6-NF INTAKE VENT (SHIPPED LOOSE)
SF-14-2 BASE FLANGE (INSTALLED IN FACTORY)
CAP-14 TEMPORARY ALUMINUM CAP
F-DOORS
SEE DOOR SCHEDULE ON A0.1
G-WINDOWS
SEE WINDOW SCHEDULE ON A0.1
H-ELECTRICAL
1 PANELBOARD: 208/120 V, 3-PH, 60Hz, 4-WIRE - UP 70" A.F.F. TO TOP OF BOX
NOTE: WITH COBBER BUS BAR
NOTE: WITH BOLT-IN BREAKERS
NOTE: PANELBOARDS TO BE 10kAIC
2 SERV ENT: 2" EMT FROM WEATHERPROOF 120/208V 3 PH. PIN AND SLEEVE RECEPTACLE
MELTRIC 31-94237-K16 OR EQUAL
w/ LL CONDUIT BODY AND WEATHERPROOF SURFACE-MOUNT BACK BOX
MELTRIC 715C3N20, OR EQUAL
UP 48" A.F.F. TO BOTTOM
3 WIRING: #12-2 w/GND MIN., TYPE NM-B 90oC COPPER; IN WALL FRAMING CAVITIES ONLY 4 WIRING: MC CABLE w/ INTERLOCKING TAPE SHEATH
(#12 MIN WIRE SIZE) - TYPE THHN IN CEILING CAVITY ONLY
5 CROSS-SEAM WIRING: PIGTAIL AND JUNCTION BOX
6 INT. LIGHTS: 24" x 48" L.E.D. (LAY-IN) w/ LENSE
4000K/4000 LUMEN MINIMUM
7 INT. LIGHTS: 24" x 48" L.E.D. (LAY-IN) w/ LENSE, AND BATTERY BACK-UP
4000K/4000 LUMEN MINIMUM
8 EXT. LIGHTS: 12W L.E.D. WALL PACK w/ PHOTOCELL CONTROLS AND BATTERY BACK-UP
(WEATHERPROOF) - UP 74" A.F.F. TO BOTTOM
9 EGRESS LIGHTS: EXIT/EMERGENCY LIGHT W/ BATTERY PACK
- UP 90" TO BOTTOM
10 RECEPTS: 125V/20A DUPLEX
UP 18" TO BOTTOM OF BOX UNLESS NOTED OTHERWISE
10a RECEPTS: 125V/20A QUADRUPLEX
UP 18" TO BOTTOM OF BOX UNLESS NOTED OTHERWISE
11 RECEPTS: 125V/20A DUPLEX (GFCI) - UP 18" A.F.F. TO BOTTOM UNLESS NOTED OTHERWISE
12 RECEPTS: 125V/20A DUPLEX (GFCI BREAKER PROTECTED) -
UP 18" A.F.F. TO BOTTOM UNLESS NOTED OTHERWISE FOR REFRIGERATOR
13 HEAT TAPE RECPT: 125V/20A DUPLEX GFEP BREAKER PROTECTED, INSTALLED BELOW FLOOR
14 RECEPTS: 125V/20A DUPLEX WEATHER-RESISTANT GFCI RECEPTACLE
INSTALLED w/ WEATHER-PROOF IN-USE COVER - UP 6" A.F.F. TO BOTTOM 14a RECEPTS: 120V/20A L5-20R "TWIST-LOCK" SINGLE - CEILING MOUNTED
NOTE: ALL RECEPTS ARE TO BE GROUNDING TYPE
15 SWITCHES: 120V/20A 3-WAY - UP 44" A.F.F. TO BOTTOM
16 SWITCHES: 120V OCCUPANCY/VACANCY SENSOR, WALL-MOUNTED -
UP 44" A.F.F. TO BOTTOM
17 SWITCHES: 120V OCCUPANCY/VACANCY SENSOR, CEILING-MOUNTED
18 DATA DROPS: 2x4 JUNCTION BOX, UP 18" TO BOTTOM, UNLESS NOTED OTHERWISE w/ 3/4" FLEXIBLE NON-METALLIC CONDUIT TO CEILING CAVITY 19 DATA PULL BOX: EXTERIOR 24"x24"x8"D NEMA 4X ENCLOSURE w/ 4" EMT CONDUIT AND LB
CONDUIT BODY TO INTERIOR CEILING CAVITY - UP 60" A.F.F. TO TOP OF BOX
20 FIRE ALARM: ROUGH-IN ONLY FOR PULL STATION -- 2x4 BOX
UP 44" A.F.F. TO BOTTOM, w/ 3/4" EMT TO A/V ROUGH-IN 21 FIRE ALARM: ROUGH-IN ONLY FOR AUDIO/VISUAL DEVICE -- 4x4 BOX
UP 80" A.F.F. TO BOTTOM, w/ 3/4" EMT TO CEILING CAVITY
22 FIRE ALARM: ROUGH-IN ONLY FOR SMOKE DETECTOR (CLG. MT'D.)
2-GANG BOX AT UNDERSIDE OF RAFTERS; TAGGED FOR USE
NOTE: FIRE ALARM SYSTEM TO BE PROVIDED AND INSTALLED
ON SITE BY CERTIFIED INSTALLER, NOT BY FACTORY.
NOTE: ALL CONDUIT ROUGH-INS TO HAVE PULL WIRES INSTALLED.
J-PLUMBING
1 WTR CLST: TANK TYPE (H/C ACCESSIBLE) W/ ELONGATED BOWL AND
OPEN FRONT SEAT
FLUSH CONTROL ON APPROACH ("WIDE") SIDE OF TOILET
2 LAVATORY: VITREOUS CHINA WALL HUNG w/ 4" CENTERSET H/C ACCESSIBLE FAUCET
NOTE: SINGLE-FIXTURE TEMPERING VALVE REQUIRED FOR ALL ACCESSIBLE
HAND WASHING FACILITIES; MAX. WATER TEMPERATURE 110oF
3 WTR HTR: 4 GALLON ELECTRIC (1440W/120V MINI TANK) EEMAX EMT4 OR EQUAL
NOTE: WATER HEATER INLET & OUTLET CONNECTIONS SHALL HAVE A
DIELECTRIC UNITON AND SHUT OFF VALVE
NOTE: BOTTOM FED WATER HEATERS SHALL HAVE A VACUUM RELIEF
VALVE
4 SUPPLY: PEX (CROSS-LINKED POLYETHYLENE)
NOTE: INSULATE HOT WATER & HOT WATER RETURN PIPING; INSULATE
COLD WATER PIPING IN CEILING CAVITY
NOTE: CROSS-SEAM SUPPLY LINES, FTGS., & INSTALLATION
OTHERS ON SITE.
5 DWV: SCHEDULE 40 PVC
NOTE: MULTIPLE DROPS STUBBED THRU FLOOR. INTER-
CONNECTING MANIFOLD BY CERTIFIED INSTALLER
NOTE: SHIPLOOSE PLUMBING VENT EXTENSIONS, FOR ON-SITE
INSTALLATION BY CERTIFIED INSTALLER.
6 MISC. 15"x15" STAINLESS STEEL SINK W/ GOOSENECK FAUCET
W/ H/C CONTROLS
7 MISC. GRAB BARS (SEE FLOOR PLAN AND RESTROOM ELEVATIONS)
SIDE BAR: 42"L BACK BAR: 36"L VERTICAL BAR: 18"L
8 MISC: 18"Wx36"H STAINLESS STEEL EDGED MIRROR
9 MISC: TOILET PAPER DISPENSER
K-H.V.A.C.
1 HEATING/ WALL-MOUNT, 2.5-TON COOLING, 9.0kW
COOLING: AIR CONDITIONER w/ ELEC. HEAT w/ BUILT-IN DISCONNECT & (0-25%) FRESH AIR DAMPER
NOTE: VALUE IN PARENTHESIS REPRESENTS PERCENTAGE OF OUTDOOR AIR
AVAILABLE, BASED UPON UNIT RATED AIRFLOW.
BARD W30AB-B09XWXXXX OR EQUAL
NOTE: OUTDOOR INTAKE AIR DAMPER TO BE IN CLOSED POSITION
FOR SHIPPING.
NOTE: INTAKE AIR DAMPER MUST BE ADJUSTED ON SITE FOR
PROPER AIRFLOW -- SEE HVAC UNIT OPERATING INSTRUCTIONS.
2 SUPPLY DUCT: SINGLE 1" FIBERGLASS DUCTBOARD IN CEILING CAVITY
NOTE: INSTALL H.V.A.C. UNITS W/ MFR'S. RECOMMENDED
CLEARANCE AT FIRST 3' OF SUPPLY DUCT
3 DIFFUSERS: 24" X 24" LAY-IN w/ADJ. DAMPER (CEILING) 4 DIFFUSERS: 12" X 12" w/ ADJ. DAMPER (CEILING) (4 WAY)
5 RETURN AIR: 28" X 14" AT PLENUM WALL (RG-3W OR EQUAL)
6 EXH FAN: 80 CFM (CEILING MOUNTED)
7 THERMOSTAT: FOR WALL-MOUNTED H.V.A.C. UNIT - UP 48" A.F.F.
PROGRAMMABLE,
AUTO CHANGEOVER HEAT & COOL
L-FURNITURE & INTERIOR FURNISHINGS
1 SINK BASE CABINET: 48"W DOUBLE DOOR
NOTE: ALL CABINETS ARE MERILLAT MAPLE w/ SENECA RIDGE STYLE DOORS w/ MATCHING FILLERS AS REQUIRED.
3 COUNTERTOP: 24" DEEP H.P. LAMINATED
NOTE: COUNTERTOP TO BE H.P. LAMINATE OVER DOUBLE
LAYER OF 5/8" SUBSTRATE w/ FINISHED EDGES AND
4"H BACK AND SIDE SPLASHES
M-MISCELLANEOUS
1 SHIP LOOSE: EXTERIOR & INTERIOR MATELINE CLOSE-UP MATERIAL
SHIPPED LOOSE FOR INSTALLATION BY CERTIFIED INSTALLER.
UNIT LABELS
THIRD PARTY LABEL
DATA PLATES AND LABELS LOCATED ABOVE SUSPENDED
CEILING ON THE "FRONT" WALL OF THE MODULE
MBI LABEL
RI/IIBC LABEL
DECAL TYPE
NONE
MODEL APPROVAL
THIRD PARTY AND REGISTERED ARCHITECT OR ENGINEER
STATE OF RI
Door Schedule Mark Description Count Width Height Rough Width Rough Height Frame Type Frame Throat Lite Fire Rating Hardware Set Comments
F1 18ga COMM. INSULATED STEEL DOOR 2 3' - 0" 7' - 0" 3' - 2" 7' - 1" 16ga STEEL K.D. 8 5/8" 5 x 20 N/A A F2 SOLID CORE WOOD 1 3' - 0" 6' - 8" 3' - 2" 6' - 9" 16ga STEEL K.D. 4 5/8" N/A N/A B
Door Hardware Schedule Hardware Set ID Description Comments
A LEVER LOCKSET w/ SFIC
CONSTRUCTION CORE
GRADE 2; STOREROOM FUNCTION
4.5"x4.5" NRP BB HINGES US32D FINISH
DOOR CLOSER GRADE 2
WEATHERSTRIPPING
DRIP CAP
THRESHOLD
DOOR SWEEP
Door Hardware Schedule Hardware Set ID Description Comments
B
LEVER LOCKSET GRADE 2; PRIVACY FUNCTION
4.5"x4.5" BB HINGES US26D FINISH
DOOR CLOSER GRADE 2
DOOR STOP FLOOR-MOUNTED
3/4" = 1'-0"1 Door Elevations
Room Finish Schedule Name Number Perimeter Area Floor Finish Base Finish Wall Finish Ceiling Finish
OPEN OFFICE 101 137' - 0" 852 SF 1/8" VCT (12"x12" TILES) 4"H VINYL
COVE BASE
1/2" VINYL COVERED
GYPSUM
2' x 4' SUSPENDED CEILING GRID w/ LAY-IN TILES
RESTROOM 102 34' - 6 3/4" 72 SF 1/8" VCT (12"x12" TILES) 6"H VINYL
COVE BASE
.090" PEBBLED
SURFACE FRP
2' x 4' SUSPENDED CEILING GRID w/ LAY-IN TILES
Material Color Chart Material Color Comments
1/8" VCT TO BE SELECTED FROM MFRS. STD. COLORS 12"x12" TILES VINYL COVE BASE TO BE SELECTED FROM MFRS. STD. COLORS 6"H IN RESTROOM AND 4"H IN REMAINDER OF ROOMS
1/2" VINYL COVERED GYPSUM TO BE SELECTED FROM MFRS. STD. COLORS w/ MATCHING BATTENS AS REQUIRED .090" F.R.P. LAMINATED TO 1/2" GYPSUM TO BE SELECTED FROM MFRS. STD. COLORS PEBBLED SURFACE; w/ MATCHING TRIMS
INTERIOR DOOR PANEL TO BE SELECTED FROM MFRS. STD. COLORS SOLID CORE PRIMED HARDBOARD INTERIOR DOOR FRAMES TO BE SELECTED FROM MFRS. STD. COLORS SHERWIN WILLIAMS DTM PAINT
29ga STEEL SIDING TO BE SELECTED FROM MFRS. STD. COLORS w/ 3/4"D RIBS 29ga STEEL TRIMS TO BE SELECTED FROM MFRS. STD. COLORS SEE TRIM PROFILES ON A1.0
29ga STEEL SKIRTING TO BE SELECTED FROM MFRS. STD. COLORS w/ 3/4"D RIBS EXTERIOR DOOR SLABS TO BE SELECTED FROM MFRS. STD. COLORS INSULATED STEEL DOOR; SHERWIN WILLIAMS DTM PAINT
EXTERIOR DOOR FRAMES TO BE SELECTED FROM MFRS. STD. COLORS SHERWIN WILLIAMS DTM PAINT
VINYL WINDOW FRAMES TO BE WHITE
INTERIOR WOOD WINDOW JAMB AND CASING TO BE WHITE 1x LUMBER JAMB AND SILL w/ 2 1/4" CLAM SHELL CASING
SUSPENDED CEILING GRID TO BE WHITE
ACOUSTIC CEILING TILE TO BE WHITE 2' x 4' LAY-IN
EPDM ROOF MEMBRANE TO BE BLACK
INTERIOR LIGHT FRAMES TO BE WHITE 2' x 4' LAY-IN
INTERIOR LIGHT LENSES TO BE FROSTED
EXTERIOR LIGHT HOUSING TO BE BRONZE WALL PACK
RECEPTACLES, SWITCHES, AND COVERPLATES TO BE WHITE
WALL-MOUNTED H.V.A.C. UNIT TO BE BEIGE BAKED ENAMEL FINISH
DIFFUSERS TO BE WHITE 12"x12" AND 24"x24"
RETURN GRILLE TO BE WHITE WALL-MOUNTED AT PLENUM WALL
EXHAUST FAN GRILLE TO BE WHITE CEILING-MOUNTED
CABINETS TO BE TOFFEE STAIN MAPLE w/ SENECA RIDGE STYLE DOORS/DRAWERS COUNTERTOP TO BE SELECTED FROM MFRS. STD. COLORS H.P. LAMINATE; INCLUDES BACK AND SIDE SPLASHES
QUOTE NUMBER 49675-99 DATE 6/3/2022
MODULAR MANUFACTURERS SCOPE CLARIFICATIONS
SECTION
FLOOR
THIS BUILDING HAS WHEEL WELLS REMOVAL OF PROTECTIVE WELL COVER AND INFILL REQUIRED ON SITE
BOTTOM BOARD BOTTOM BOARD MATERIAL SHIPS LOOSE IN AXLE AREA, INSTALLATION
IN THIS AREA BY OTHERS ON SITE
INSULATION INSULATION SHIPPED LOOSE IN AXLE AREAS, INSTALLATION BY
OTHERS ON SITE
INSULATION INSULATION FOR MATE LINES SHIPS LOOSE FOR INSTALLATION BY OTHERS
DECKING DECKING HELD BACK AT MATE LINES, INSTALLATION AT MATE LINES BY
OTHERS ON SITE
FLOOR COVERING COVERING HELD BACK AT MODULE MATE LINES, MATERIAL SHIPPED
LOOSE FOR INSTALLATION BY OTHERS
COVE BASE COVE BASE SHIPPED LOOSE WHERE FLOOR COVERING IS HELD OUT FOR
INSTALLATION BY OTHERS
WALLS AND PARTITIONS
WALL COVERING WALL COVERING HELD BACK AT MATE LINE, SEAM CLOSURE MATERIAL SHIPS
LOOSE FOR INSTALL BY OTHERS
SIDING SIDING NOT HELD BACK AT MATE LINE, STEELCLOSURE SHIPS LOOSE FOR
INSTALLATION BY OTHERS
INSULATION FOAM INSULATION BOARD NOT HELD BACK, SHIP LOOSE FOAM BACKER
ROD FOR SEAMS
AIR BARRIER AIR BARRIER ROLLED BACK AT MATE LINES, TAPING OF THE SEAMS AT MATE
LINE BY OTHERS
SKIRT MATCHING SKIRT SHIPS LOOSE IN FULL SHEETS FOR INSTALLATION BY OTHERS
ROOF
ROOFING MATE LINE FLASHING SHIPS LOOSE FOR INSTALLATION BY OTHERS
INSULATION INSULATION FOR MATE LINE SHIPS LOOSE FOR INSTALLATION BY OTHERS
VENT EXTENSIONS VENT PIPING THROUGH ROOF IS SHIPPED LOOSE FROM FACTORY FOR
INSTALLATION BY OTHERS AT SITE
VENT EXTENSIONS VENT FLASHING SHIPPED LOOSE FOR INSTALLATION BY OTHERS
EXHAUST CAPS CAPS AND FLASHING SHIP LOOSE FOR INSTALLATION BY OTHERS
ATTIC VENTS BASE INSTALLED AT FACTORY, EXTENSIONS AND CAPS SHIP LOOSE FOR
INSTALLATION BY OTHERS
DOORS
ADJUSTMENTS FINAL ADJUSTMENTS OF DOORS AFTER MODULES ARE SET IS BY OTHERS
KEYING DOORS KEYED PER FUNCTION
QUOTE NUMBER 49675-99 DATE 6/3/2022
MODULAR MANUFACTURERS SCOPE CLARIFICATIONS
SECTION
ELECTRIC
LOAD CENTER ONE LOAD CENTER PER MODULE, INTERCONNECT TO MDP BY OTHERS
LOAD CENTER MDP BY FACTORY
LIGHTING REMOTE EMERGENCY HEADS SHIP LOOSE FOR INSTALLATION BY OTHERS
EGRESS LIGHTING CONNECTION OF BATTERIES REQUIRED ON SITE BY OTHERS
RECEPTS HEAT TAPE SUPPLIED AND INSTALLED BY OTHERS ON SITE
ROUGH IN'S PVC CONDUIT TO ABOVE CEILING WITH PULL WIRE ONLY, ALL WIRING AND DEVICES BY OTHERS
SWITCHES OCCUPANCY SENSORS MAY REQUIRE ADJUSTMENT BY OTHERS ON SITE
LOW VOLTAGE LOW VOLTAGE WIRING SUPPLIED AND INSTALLED BY OTHERS ON SITE
PLUMBING
SUPPLY PIPING BACK FLOW PREVENTER BY OTHERS
WASTE PIPING PLUMBING DROP PER FIXTURE, MANIFOLD SUPPLIED AND INSTALLED BY OTHERS WASTE PIPING VENT PIPING TERMINATES AT UNDER SIDE OF ROOF, EXTENSION INSTALLED BY OTHERS ON SITE
WASTE PIPING VENT PIPE FLASHING SHIPPED LOOSE FOR INSTALLATION BY OTHERS
HVAC
GRILLS AND DIFFUSERS GRILLES AND DIFFUSERS STRAPPED TO SUB CEILING WHERE GRID CEILING IS HELD OUT BY FACTORY
EXHAUST EXHAUST FAN CAPS AND FLASHING SHIP LOOSE FOR INSTALLATION BY OTHERS
CONTROLS THERMOSTAT INSTALLED BY FACTORY, START UP AND PROGRAMMING BY OTHERS
TESTING TESTING OF HVAC SYSTEM AFTER START UP BY OTHERS
BALANCING BALANCING OF HVAC SYSTEM AFTER START UP BY OTHERS
MISC
CASEWORK ADJUSTMENT OF DOORS MAY BE REQUIRED BY OTHERS ON SITE
WARRANTY
WARRANTY MANUFACTURERS STANDARD WARRANTY APPLIES, DOCUMENTS SHIP LOOSE IN WARRANTY PACK
WARRANTY COMPONENT MANUFACTURERS EXTENDED WARRANTY ARE PASSED TO END USER
WARRANTY MANUFACTURING PLANT MUST BE NOTIFIED OF ANY WARRANTY CLAIMS
WARRANTY WARRANTY CLAIMS WILL NOT BE REIMBURSED WITHOUT NOTIFICATION AND PRIOR APPROVAL
No. Description Date 1 Revisions per customer comments 06.29.2022
Window Schedule Mark Description Count Width Height Rough Width Rough Height Sill Height Glazing U-Factor SHGC VT Ventilation Comments
G1 VINYL-FRAMED HORIZONTAL SLIDER 4 3' - 10" 2' - 3" 3' - 10 1/2" 2' - 3 1/2" 4' - 7" "CLEAR" D.I.G. w/ ARGON GAS FILL 0.29 0.30 0.56 87 CFM
1st Floor 2' - 11 1/2"
Roof Peak Height 13' - 6"
OUTSIDE CORNER
TRIM (TYP)
BOTTOM TRIM (TYP)
TOP TRIM (TYP)
J-CHANNEL
AROUND WINDOW
1/4" / 1'-0"1/4" / 1'-0"
G1G1 2.5T/9kW
SPVAC
EXHAUST CAP;
FROM EXH FAN
1st Floor 2' - 11 1/2"
Roof Peak Height 13' - 6"
OUTSIDE CORNER
TRIM (TYP)
BOTTOM TRIM (TYP)
TOP TRIM (TYP)
1/4" / 1'-0" 1/4" / 1'-0"
F1
G1 G1
J-CHANNEL
AROUND DOOR
J-CHANNEL
AROUND WINDOW2.5T/9kW
SPVAC
EXTERIOR LIGHT
EXT. DUPLEX
RECEPTACLE w/
IN-USE W.P. COVER
1st Floor 2' - 11 1/2"
Roof Peak Height 13' - 6"
OUTSIDE CORNER
TRIM (TYP)
BOTTOM TRIM (TYP)
TOP TRIM (TYP)
J-CHANNEL
AROUND DOOR
EXTERIOR LIGHT
EXT. DUPLEX
RECEPTACLE w/
IN-USE W.P. COVER
(5) PIN, PIN AND SLEEVE
FEMALE RECEPTACLE
F1
DPB
1st Floor 2' - 11 1/2"
Roof Peak Height 13' - 6"
OUTSIDE CORNER
TRIM (TYP)
BOTTOM TRIM (TYP)
TOP TRIM (TYP)
EXT. DUPLEX
RECEPTACLE w/
IN-USE W.P. COVER
2.5T/9kW
SPVAC
2.5T/9kW
SPVAC
J-CHANNEL AROUND
WALL-MOUNTED
H.V.A.C. UNITS (TYP)
BASE TRIM
/2
1"
/2
COLOR SIDE
/8
4 1/8"
1"
1"
/8
5/8"
COLOR SIDE
OUTSIDE CORNER
COLOR SIDE
/8
7/8"
2 1/8"
J-CHANNEL
SIDING PROFILE
6"
TOP TRIM
COLOR SIDE
/4
9"
COLOR SIDE
/4
U-CHANNEL INSERT TRIM
3/4"
1st- floor12 1st- w alls- columns24 1st- flel- drs10 1st- flel9 1st-flme- p11 1st- walls23 common27 1st-common1 1st- floor- dim130 0
Drawn By: Serial No.
Page No.
Scale:
THIS DRAWING AND ALL INFORMATION
CONTAINED HEREON IS THE
PROPERTY OF WHITLEY MFG. CO. INC.,
AND IS NOT TO BE REPRODUCED
WITHOUT THE EXPRESS PERMISSION
OF WHITLEY MFG. CO., INC.
WHITLEY MFG. CO. INC., ASSUMES NO
RESPONSIBILITY FOR UNAUTHORIZED
USE OF THIS DRAWING.
Quote No.
Model No.
Job No.
Date:
Rev:
Checked By:
No. Description Date Whitley East, LLC
64 HESS ROAD
LEOLA, PA 17540
PHONE: 717.656.2081
www.whitleyman.com
C U
ST
O
M
ER
A
PP
R O
VA
L
SE
T
6/
/2
7:
:3
AM
As indicated
6/30/2022
7:00:32 AM
A1.02022-072-WP
EP 2696-97
49675-99
DL/CZ
(2) 10'-0" x 52'-0" MODULES
EXTERIOR ELEVATIONS
SUSTAINABLE MODULAR MANAGEMENT
NAVAL UNDERSEA WARFARE CENTER
3/8" = 1'-0"1 South Elevation
3/8" = 1'-0"2 North Elevation
3/8" = 1'-0"3 West Elevation 3/8" = 1'-0"4 East Elevation
3" = 1'-0"5 Steel Siding and Trims
No. Description Date 1 Revisions per customer comments 06.29.2022
R ef rig er at or
EX/EM
EX
/E
M
PCE
S
S
PC
E
80 CFM
PCE
EX/EM
G
FC
I R
H T
W P
O
M F
S
T
MODULE 2
S/N: 2697
MODULE 1
S/N: 26962.
5T /9 kW
SP
VA
C
2.
5T
/9 kW
SP
VA
C
PN
L-
PN
L-
/2
F1
F1
F2
S5.1
SIDING TO SIDING
52' - 5 1/2"
D
PB
MODULE LENGTH
52' - 0" TYP
S
ID
IN
G
T O
S
ID
I N G
M O
D U
L E
W
ID
T H
M A
T E
G A
P /2
T
Y P
M O
D U
L E
W
ID
T H
/8
10' - 9"
G1 G1
G1G1
A2.13Ty p
Typ
A2.1 5 Ty p
Typ
M
IN
18"
/4
/4
17' - 4" 17' - 9 1/2" 17' - 4"
17' - 4" 17' - 9 1/2" 13' - 2 3/4" 4' - 1 1/4"
852 SF
OPEN OFFICE
72 SF
RESTROOM
PN
L-
PNL-2
2.
5T
/9 kW
SP
VA
C 2.
5T /9 kW
SP
VA
C
W R
G W
R G
REPRESENTS SHIPPED
LOOSE CEILING TILE, GRID,
AND WALL ANGLE FOR
INSTALL BY CERTIFIED INSTALLER
MODULE 2
S/N: 2697
MODULE 1
S/N: 2696
D
PB
F1
F1
F2
/1
3' - 9 1/2" 21 1/4"
/2
/2
21 1/4"
PNL
ITEMS REPRESENTED BY DASHED LINES TO BE
SHIPPED LOOSE FOR INSTALL ON SITE BY OTHERS
Legend
120/208V 3-PH
PANELBOARD
5-PIN 120/208V 3-PH
PIN AND SLEEVE
RECEPTACLE
2'x4' L.E.D. LAY-IN PANEL LIGHT w/
LENSE
2'x4' L.E.D. LAY-IN PANEL LIGHT w/
LENSE AND BATTERY
BACK-UP
EXTERIOR LIGHT w/
PHOTOCELL CONTROLS
AND BATTERY BACK-UP
EXIT/EMERGENCY LIGHT
w/ BATTERY BACK-UP
125V/20A DUPLEX
RECEPTACLE - UP
18" A.F.F., UNO
125V/20A GFCI DUPLEX
RECEPTACLE - UP
18" A.F.F., UNO
125V/20A GFCI BREAKER
PROTECTED DUPLEX
RECEPTACLE FOR REFRIGERATOR
UP 18" A.F.F., UNO
125V/20A GFEP BREAKER
PROTECTED DUPLEX
RECEPTACLE FOR HEAT TAPE
125V/20A WEATHER-RESISTANT
GFCI DUPLEX RECEPTACLE w/
WEATHER-PROOF IN-USE COVER
UP 6" A.F.F.
120V/20A 3-WAY SWITCH
UP 44" A.F.F.
120V/20A OCCUPANCY/VACANCY
SENSOR; WALL MOUNTED
UP 44" A.F.F.
120V/20A OCCUPANCY/VACANCY
SENSOR; CEILING MOUNTED
D PB 24"x24"x8"D DATA PULL
BOX - UP 60" A.F.F. TO TOP
DATA ROUGH-IN
UP 18" A.F.F.
MANUAL PULL STATION
FIRE ALARM ROUGH-IN
UP 44" A.F.F.
AUDIO/VISUAL DEVICE
FIRE ALARM ROUGH-IN
UP 44" A.F.F.
SMOKE DETECTOR
FIRE ALARM ROUGH-IN
GRAB BAR; SEE FLOOR PLAN
AND INTERIOR ELEVATIONS
18" x 36" STAINLESS STEEL
FRAMED MIRROR
TOILET PAPER
DISPENSER
24" x 24" SUPPLY AIR
DIFFUSER (LAY-IN)
12" x 12" SUPPLY AIR
DIFFUSER (LAY-IN)
W R
G WALL RETURN GRILLE
AT PLENUM WALL
80 CFM 80 CFM CEILING-
MOUNTED EXHAUST FAN
PROGRAMMABLE
THERMOSTAT
UP 48" A.F.F.
125V/20A QUADRUPLEX
RECEPTACLE - UP
18" A.F.F., UNO
125V/20A L5-20R "TWIST-LOCK"
RECEPTACLE - CELING MOUNTED
1st Floor 2' - 11 1/2"
HOLD
31 1/2" CLEAR
15"x15" BAR SINK w/
GOOSENECK
FAUCET
4' - 1"
48" SINK BASE
125V/20A GFCI
APPLIANCE
RECEPTACLES
125V/20A GFCI
PROTECTED
DUPLEX RECEPTACLE 3
/4
SIDESPLASH
1st Floor 2' - 11 1/2"
25"
/4
/2
4"
1st Floor 2' - 11 1/2"
M A
X
M A
X
WALL-HUNG
LAVATORY w/ 4"
CENTERSET FAUCET
18" x 36" STAINLESS
STEEL FRAMED MIRROR
M
IN
1st Floor 2' - 11 1/2"
42" MIN
MAX
12"
54" MIN
39" - 41"
M
IN
M
INM
IN
/2
24" MIN
42" MAX
GRAB BAR
TOILET PAPER
DISPENSER
TANK-TYPE WATER
CLOSET
1st Floor 2' - 11 1/2"
24" MIN
MIN
12"
36" MIN
16" - 18"
TANK-TYPE WATER
CLOSET
GRAB BAR
1st- floor12 1st- w alls- columns24 1st- flel- drs10 1st- flel9 1st-flme- p11 1st- walls23 common27 1st-common1 1st- floor- dim130 0
Drawn By: Serial No.
Page No.
Scale:
THIS DRAWING AND ALL INFORMATION
CONTAINED HEREON IS THE
PROPERTY OF WHITLEY MFG. CO. INC.,
AND IS NOT TO BE REPRODUCED
WITHOUT THE EXPRESS PERMISSION
OF WHITLEY MFG. CO., INC.
WHITLEY MFG. CO. INC., ASSUMES NO
RESPONSIBILITY FOR UNAUTHORIZED
USE OF THIS DRAWING.
Quote No.
Model No.
Job No.
Date:
Rev:
Checked By:
No. Description Date Whitley East, LLC
64 HESS ROAD
LEOLA, PA 17540
PHONE: 717.656.2081
www.whitleyman.com
C U
ST
O
M
ER
A
PP
R O
VA
L
SE
T
6/
/2
7:
:3
AM
As indicated
6/30/2022
7:00:33 AM
A2.12022-072-WP
EP 2696-97
49675-99
DL/CZ
(2) 10'-0" x 52'-0" MODULES
ARCHITECTURAL PLANS AND ELEVATIONS
SUSTAINABLE MODULAR MANAGEMENT
NAVAL UNDERSEA WARFARE CENTER
3/8" = 1'-0"1 Floor Plan
3/8" = 1'-0"2 Reflected Ceiling Plan
No. Description Date 1 Revisions per customer comments 06.29.2022
3/8" = 1'-0"3 Casework Elevation
3/8" = 1'-0"4 Casework Section
1/2" = 1'-0"5 Restroom Elevation 1
1/2" = 1'-0"6 Restroom Elevation 2
1/2" = 1'-0"7 Restroom Elevation 3
1"
4" 4 1/2"
4 1/2"4" 1"1"
4"4 1/2"
4 1/2" 4" 1"
25"25"
STEP #1
PLACE COLLAR BASE ON ROOFING (PER PLAN
LOCATIONS) AND TRACE INSIDE OF COLLAR.
STEP #2
CUT OUT ROOFING AND SHEATHING USING A RECIPROCAL SAW WITH A
4"L BLADE, CUTTING AROUND THE TRACED LINES PER STEP #1
STEP #3
PLACE COLLAR BASE, CENTERED OVER CUT-OUT.
FASTEN DOWN WITH #10-16 x 1 1/2"L PAN-HEAD
SHEET METAL SCREWS PER PATTERN SHOWN.
STEP #4
USING 6" WIDE SEAM TAPE, FLASH AROUND PERIMETER
OF BASE COLLAR, AND APPLY LAP SEALANT AT
OUTBOARD AND INBOARD EDGES OF FLASHING TAPE
3" 3"
STEP #5
INSTALL CAP OVER BASE COLLAR FOR SHIPMENT; AURA OR POP VENT WITH 6"
COLLARS TO BE SHIPPED LOOSE IN MODULES FOR INSTALLATION ON SITE BY
OTHERS
INTAKE FRAMING
VENT (TYP)
EXHAUST FRAMING
VENT (TYP)
1/4" / 1'-0" 1/4" / 1'-0"
A7.1
Typ
A7.1
Typ
A7.1
Typ
A7.1
Typ
A7.1
Typ
MATELINE
EXT. WALL STRUCTURE
ROOF STRUCTURE
ROOF MEMBRANE
29ga STEEL TOP TRIM;
HORIZTONAL LEG
INSTALLED OVER ROOF
MEMBRANE (TYP)
29ga STEEL SIDING
1 1/2"T FOIL-FACED
RIGID INSULATION
1/2" F.R.T. PLYWOOD
SHEATHING (TYP)
LUMBER NAILER
AT TOP OF WALL
HEX WASHER HEAD SCREW
AT TOP TRIM AT 6" O.C.
6"W SEAM TAPE OVER
HORIZONTAL LEG OF
TOP TRIM; TAPE PRIMER
APPLIED OVER ROOF
MEMBRANE AND HORIZTONAL
LEG OF TOP TRIM
CONTINUOUS BEAD OF
LAP SEALANT AT OUTBOARD
EDGE OF SEAM TAPE
ROOF STRUCTURE
EPDM PIPE BOOT; SHIPPED
LOOSE AND INSTALLED BY
CERTIFIED INSTALLER
VENT-THRU ROOF
PIPE EXTENSION; SHIPPED
LOOSE AND INSTALLED BY
CERTIFIED INSTALLER
TAPE PRIMER; SHIPPED
LOOSE AND APPLIED BY
CERTIFIED INSTALLER
WATER CUT-OFF MASTIC;
SHIPPED LOOSE AND APPLIED
BY CERTIFIED INSTALLER
STAINLESS STEEL PIPE
CLAMP; SHIPPED LOOSE
AND INSTALLED BY
CERTIFIED INSTALLER
LAP SEALANT APPLIED
AROUND PERIMETER OF
PIPE BOOT; SHIPPED
LOOSE AND INSTALLED
BY CERTIFIED INSTALLER
LAP SEALANT APPLIED
AROUND PERIMETER OF
PIPE BOOT; SHIPPED
LOOSE AND INSTALLED
BY CERTIFIED INSTALLER
1st- floor12 1st- w alls- columns24 1st- flel- drs10 1st- flel9 1st-flme- p11 1st- walls23 common27 1st-common1 1st- floor- dim130 0
Drawn By: Serial No.
Page No.
Scale:
THIS DRAWING AND ALL INFORMATION
CONTAINED HEREON IS THE
PROPERTY OF WHITLEY MFG. CO. INC.,
AND IS NOT TO BE REPRODUCED
WITHOUT THE EXPRESS PERMISSION
OF WHITLEY MFG. CO., INC.
WHITLEY MFG. CO. INC., ASSUMES NO
RESPONSIBILITY FOR UNAUTHORIZED
USE OF THIS DRAWING.
Quote No.
Model No.
Job No.
Date:
Rev:
Checked By:
No. Description Date Whitley East, LLC
64 HESS ROAD
LEOLA, PA 17540
PHONE: 717.656.2081
www.whitleyman.com
C U
ST
O
M
ER
A
PP
R O
VA
L
SE
T
6/
/2
7:
:3
AM
As indicated
6/30/2022
7:00:35 AM
A7.12022-072-WP
EP 2696-97
49675-99
DL/CZ
(2) 10'-0" x 52'-0" MODULES
ROOFTOP PLAN
SUSTAINABLE MODULAR MANAGEMENT
NAVAL UNDERSEA WARFARE CENTER
1/2" = 1'-0"3 Roof Vent Install Instructions
ALL ROOF PENETRATIONS TO BE MARKED ON ROOFING;
I.E. "EXH.", "VENT" ETC.
3/8" = 1'-0"1 Roof Top Plan
1 1/2" = 1'-0"2 Roofing Detail - Edge Termination
1 1/2" = 1'-0"4 Roof Flashing Detail - VTR
No. Description Date
S P
E C
IF
IC
A T
IO
N
S
H E
IG
H
T P
E R
TWO-GANG METALLIC
JUNCTION BOX (TYP)
MUD-RING EXTENSION
WALL COVERING
FINISHED FLOOR
NOTE:
PER NATIONAL ELECTRICAL CODE,
ARTICLE 314.20, MUD-RING EXTENSIONS
SHALL BE FLUSH WITH WALL COVERINGS
WITH A MAXIMUM DEPTH BEHIND THE
SURFACE OF THE COVERING OF 1/4"
FOR WOOD WALL COVERINGS, THE MUD-
RING EXTENSION SHALL BE FLUSH OR
EXTEND BEYOND THE SURFACE OF THE
WALL COVERING
DATA OUTLET
CONDUIT STUBBED
TO ABOVE CEILING CAVITY
FOR COMPLETION AT SITE
BLANK COVER PLATE
INSTALLED IN FACTORY
CEILING
MC CABLE TO TERMINATION MC CABLE TO TERMINATION
PRE-WIRED GREENFIELD "WHIP" OUT OF
JUNCTION BOX TO BE WIRED TO RELATED
JUNCTION BOX IN ADJACENT MODULE
NOTE:
ALL CROSS-SEAM CONNECTIONS MUST BE LABELED
BY PANEL NAME AND CIRCUIT NUMBER (i.e. "PNL1-1")
LIGHTING CIRCUITS TO HAVE ADDITIONAL NOMENCLATURE
FOR SWITCHLEG OR TRAVELER (i.e. PNL1-1 S/L)
1st- floor12 1st- w alls- columns24 1st- flel- drs10 1st- flel9 1st-flme- p11 1st- walls23 common27 1st-common1 1st- floor- dim130 0
Drawn By: Serial No.
Page No.
Scale:
THIS DRAWING AND ALL INFORMATION
CONTAINED HEREON IS THE
PROPERTY OF WHITLEY MFG. CO. INC.,
AND IS NOT TO BE REPRODUCED
WITHOUT THE EXPRESS PERMISSION
OF WHITLEY MFG. CO., INC.
WHITLEY MFG. CO. INC., ASSUMES NO
RESPONSIBILITY FOR UNAUTHORIZED
USE OF THIS DRAWING.
Quote No.
Model No.
Job No.
Date:
Rev:
Checked By:
No. Description Date Whitley East, LLC
64 HESS ROAD
LEOLA, PA 17540
PHONE: 717.656.2081
www.whitleyman.com
C U
ST
O
M
ER
A
PP
R O
VA
L
SE
T
6/
/2
7:
:3
AM
As indicated
6/30/2022
7:00:35 AM
E1.02022-072-WP
EP 2696-97
49675-99
DL/CZ
(2) 10'-0" x 52'-0" MODULES
ELECTRICAL NOTES AND DETAILS
SUSTAINABLE MODULAR MANAGEMENT
NAVAL UNDERSEA WARFARE CENTER
CONDUIT FILL NOTES:
1.) ALL ELECTRICAL WORK SHALL BE COMPLIANT WITH THE 2020 NFPA 70 NATIONAL ELECTRICAL CODE.
2.) ELECTRICAL DRAWINGS ARE DIAGRAMMATICAL ONLY; REFER TO THE NOTES BELOW FOR MOUNTING REQUIREMENTS.
3.) CONDUITS ARE TO BE MOUNTED IN A NEAT AND WORKMAN-LIKE FASHION; EXPOSED CONDUITS ARE TO BE PARALLEL WITH BUILDING STRUCTURAL COMPONENTS AND/OR WALLS; EXPOSED CONDUITS ARE NOT TO BE MOUNTED BELOW 8'-6"
ABOVE THE FINISHED FLOOR.
4.) CONDUIT AND CABLE UTILIZATION SHALL CONFORM TO THE FOLLOWING:
A. ELECTRICAL METALLIC TUBING (EMT) - INDOOR MAIN FEEDERS; FITTINGS SHALL BE STEEL AND COMPRESSION OR SET SCREW TYPES; EMT TO BE SECURED 3 FEET AWAY FROM OUTLET, JUNCTION, WIRE PULL, OR OTHER BOXES/TERMINATION POINTS AND 10 FEET O.C. INTERMITTENTLY TO FRAMING MEMBERS.
B. NON-METALLIC SHEATHED CABLE (NM-B CABLE) - INDOOR BRANCH CIRCUITING IN WALL CAVITIES;
FITTINGS SHALL BE LISTED FOR USE WITH NM-B CABLE; NM-B CABLE TO BE
SECURED 1 FOOT AWAY FROM OUTLET, JUNCTION, WIRE PULL, OR OTHER BOXES/TERMINATIONS
AND 4.5 FEET O.C. INTERMITTENTLY TO FRAMING MEMBERS.
C. METAL-CLAD CABLE (MC CABLE) - INDOOR BRANCH CIRCUITING IN CEILING CAVITIES
AND CONCEALED LOCATIONS; FITTINGS SHALL BE LISTED FOR USE WITH MC CABLE; MC CABLE TO BE SECURED 1 FOOT AWAY FROM OUTLET, JUNCTION, WIRE PULL, OR OTHER BOXES/TERMINATIONS
AND 6 FEET O.C. INTERMITTENTLY TO FRAMING MEMBERS.
D. FLEXIBLE METALLIC TUBING (FMT) - FOR INDOOR MATELINE CROSS OVER CONNECTIONS; FITTINGS SHALL BE LISTED FOR USE WITH FMT; FMT TO BE SECURED 1 FOOT AWAY FROM OUTLET, JUNCTION, WIRE PULL, OR OTHER BOXES/TERMINATION POINTS AND 6 FEET O.C. INTERMITTENTLY TO FRAMING MEMBERS.
5.) JUNCTION, OUTLET, DEVICE, AND WIRE PULL BOXES AND CONDUIT BODIES SHALL BE METALLIC, LISTED FOR USE IN ELECTRICAL SYSTEMS 0 - 1,000 VOLTS, AND SHALL CONTAIN A BONDING GROUND WIRE, AND A COMPATIBLE COVER.
6.) JUNCTION BOXES THAT ARE FLUSH-MOUNTED (BEHIND WALL FINISH) SHALL BE EQUIPPED WITH APPROPRIATE SURFACE EXTENSIONS AND SHALL BE MOUNTED TO A FRAMING MEMBER WITH APPROVED FASTENERS AND/OR SUPPORTS.
7.) JUNCTION BOXES THAT ARE SURFACE MOUNTED (ON TOP OF WALL FINISH) SHALL BE SECURELY FASTENED TO
FRAMING MEMBERS AND/OR BLOCKING.
8.) FLOOR JUNCTION BOXES SHALL BE LISTED SPECIFICALLY FOR THIS APPLICATION.
9.) JUNCTION BOXES MOUNTED IN CEILING CAVITIES OF A SUSPENDED CEILING SHALL BE SECURELY FASTENED TO
STRUCTURAL FRAMING MEMBERS.
10.) JUNCTION BOXES MOUNTED IN FRAMING MEMBERS OF AN ENCLOSED CEILING (GYPSUM BOARD OR OTHER) SHALL
COMPLY WITH NOTE #6.
11.) CONDUIT BODIES SHALL BE ACCESSIBLE AND SHALL NOT EXCEED THE WIRE FILL OF THE NOMINAL CONDUIT TRADE SIZE.
12.) ALL METAL BOXES AND CONDUIT BODIES ARE TO BE CORROSION RESISTANT AND CONFORM TO THE FOLLOWING:
A. SHEET STEEL BOXES NOT OVER 100 in.3 SHALL BE MADE FROM STEEL NOT LESS THAN 0.0625 in. THICK.
B. SHEET STEEL BOXES OVER 100 in.3 SHALL BE MADE FROM STEEL NOT LESS THAT 0.053 in. THICK.
C. CONDUIT BODIES MADE OF MALLEABLE IRON, DIE-CAST ALUMINUM, BRASS, BRONZE OR ZINC SHALL NOT HAVE A WALL THICKNESS LESS THAN 3/32 in.
D. CONDUIT BODIES OR METAL BOXES NOT MADE OF MATERIALS LISTED ABOVE ARE TO HAVE A WALL THICKNESS OF NOT LESS THAN 1/8 in.
E. SHEET STEEL JUNCTION BOXES NOT OVER 16 in² THAT ARE LOCATED IN A FIRE-RATED WALL
ASSEMBLY SHALL BE COVERED WITH LISTED PUTTY PADS.
13.) ALL WIRING TO BE TYPE THHN COPPER UNLESS NOTED OTHERWISE.
14.) ALL WIRING SHALL BE STRANDED CONDUCTOR.
15.) 20 AMP CIRCUITS WITH DEVELOPED LENGTHS 100 FEET AND GREATER SHALL HAVE A HOMERUN
CONDUCTOR OF #10 AWG MINIMUM
16.) CONDUCTORS SHALL CONFORM TO THE FOLLOWING COLOR CODES:
A. 120/208V THREE PHASE
i. PHASE A = BLACK
ii. PHASE B = RED
iii. PHASE C = BLUE
iv. SWITCHLEG = PURPLE
v. TRAVELER = PINK
vi. NEUTRAL = WHITE
vii. GROUND = GREEN
17.) WIRE FILLS PER CONDUIT TYPE SHALL CONFORM TO INFORMATIVE ANNEX C AS PER BELOW:
A. EMT - TABLE C.1
B. FMC - TABLE C.3
18.) NOT MORE THAN NINE CURRENT CARRYING CONDUCTORS SHALL BE PERMITTED IN A SINGLE
CONDUIT FOR CIRCUITS 30 AMPS OR LESS.
19.) ALL CONDUCTORS IN ACCESSIBLE BOXES OR CONDUIT BODIES ARE TO BE LABELED PER
LOADCENTER AND CIRCUIT WITH TYPE-WRITTEN LABELS.
20.) CONDUIT ROUGH-INS ARE TO INCLUDE A 200 LB. RATED NYLON OR EQUAL PULL STRING.
21.) ALL ELECTRICAL EQUIPMENT IS TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS AND THE 2020 NFPA 70 NATIONAL ELECTRICAL CODE.
22.) ALL PANELBOARDS TO HAVE COPPER NEUTRAL BUS AND LUGS. LUGS SHALL BE SIZED TO
ACCOMMODATE INDICATED CONDUCTOR SIZES.
23.) ALL PANELBOARD ENCLOSURES TO BE NEMA RATED FOR LOCATION(S) MOUNTED, AND SHALL
INCLUDE LOCKABLE DOORS.
24.) ALL PANELBOARDS TO HAVE TYPE-WRITTEN BREAKER DIRECTORIES MOUNTED TO THE INSIDE
OF THE DOOR IN ACCORDANCE WITH WHITLEY EAST LLC QUALITY CONTROL MANUAL.
25.) MAIN DISTRIBUTION PANELBOARD TO BE MARKED "SUITABLE FOR USE AS SERVICE EQUIPMENT"
AND HAVE BREAKER / FUSE TYPE OVERCURRENT PROTECTION.
26.) PROPER THERMAL OVERLOAD PROTECTION TO BE PROVIDED FOR ALL MOTORS.
27.) DISCONNECTING MEANS WITHIN SIGHT REQUIRED FOR ALL MOTORS.
28.) WEATHERPROOF PROTECTION REQUIRED FOR ALL OUTDOOR LIGHTS
AND / OR RECEPTACLES.
29.) PROPER WORKING CLEARANCES TO BE PROVIDED AND MAINTAINED ABOUT
ALL ELECTRICAL EQUIPMENT.
30.) ALL FLUORESCENT ONLY FIXTURES REQUIRE THERMAL PROTECTION.
31.) COMBINATION EXHAUST FAN/LIGHT AND RECESSED INCANDESCENT FIXTURES
TO HAVE THERMAL PROTECTION.
32.) ALL EMERGENCY LIGHTING (IF REQUIRED) AND EXIT SIGNS WILL BE CONNECTED
AHEAD OF ANY LOCAL SWITCHES PER 2020 NPFA 70 NATIONAL ELECTRICAL CODE,
ARTICLE 700.20.
33.) ALL EMERGENCY LIGHTING SHALL HAVE A BATTERY PACK TO ASSURE CONTINUED ILLUMINATION.
34.) GROUNDING ELECTRODE SHALL BE INSTALLED IN ACCORDANCE WITH 2020 NFPA 70
NATIONAL ELECTRICAL CODE, ARTICLE 250
35.) MAIN DISTRIBUTION PANEL OR DISCONNECT SWITCHES(S) SHALL BE INSTALLED ON SITE
PER CONTRACTUAL AGREEMENT
36.) SERVICE ENTRANCE CONDUCTORS TO BE TYPE THWN COPPER.
37.) HEAT TAPE RECEPTACLES TO BE PROTECTED BY A DEDICATED GFEP CIRCUIT
BREAKER PER 2020 NFPA 70 NATIONAL ELECTRICAL CODE, ARTICLE 426.28; RECEPTACLE
TO BE WEATHER-RESISTANT WITH A WEATHERPROOF COVER PER 2020 NFPA 70
NATIONAL ELECTRICAL CODE, ARTICLE 406.9(A).
38.) WATER HEATER TO HAVE LOCKABLE BREAKER OR PROVIDE DISCONNECTING
MEANS WITHIN SIGHT OF WATER HEATER PER 2020 NFPA 70 NATIONAL ELECTRICAL CODE,
ARTICLE 422.
1" = 1'-0"1 Electrical Detail - Extension Rings
3/4" = 1'-0"2 Electrical Detail - Data Rough-In
3/4" = 1'-0"3 Mateline Connection - Electrical
PCE
EX/EM
G
FC
I R
H T
W P
O
M F
S
T
R ef rig er at or
W P
GFCI
+18"
R
GFCI
+44"
EX/EM
EX
/E
M
PCE
T T
G
FC
I +18"
O S
S
FF
F
F MMPC
E
H T
J
J
J
80 CFM
G
FC
I +44" G
FC
I
+44" G
FC
I +44"
WP
W P
PNL
ITEMS REPRESENTED BY DASHED LINES TO BE
SHIPPED LOOSE FOR INSTALL ON SITE BY OTHERS
Legend
120/208V 3-PH
PANELBOARD
5-PIN 120/208V 3-PH
PIN AND SLEEVE
RECEPTACLE
2'x4' L.E.D. LAY-IN PANEL LIGHT w/
LENSE
2'x4' L.E.D. LAY-IN PANEL LIGHT w/
LENSE AND BATTERY
BACK-UP
EXTERIOR LIGHT w/
PHOTOCELL CONTROLS
AND BATTERY BACK-UP
EXIT/EMERGENCY LIGHT
w/ BATTERY BACK-UP
125V/20A DUPLEX
RECEPTACLE - UP
18" A.F.F., UNO
125V/20A GFCI DUPLEX
RECEPTACLE - UP
18" A.F.F., UNO
125V/20A GFCI BREAKER
PROTECTED DUPLEX
RECEPTACLE FOR REFRIGERATOR
UP 18" A.F.F., UNO
125V/20A GFEP BREAKER
PROTECTED DUPLEX
RECEPTACLE FOR HEAT TAPE
125V/20A WEATHER-RESISTANT
GFCI DUPLEX RECEPTACLE w/
WEATHER-PROOF IN-USE COVER
UP 6" A.F.F.
120V/20A 3-WAY SWITCH
UP 44" A.F.F.
120V/20A OCCUPANCY/VACANCY
SENSOR; WALL MOUNTED
UP 44" A.F.F.
120V/20A OCCUPANCY/VACANCY
SENSOR; CEILING MOUNTED
D PB 24"x24"x8"D DATA PULL
BOX - UP 60" A.F.F. TO TOP
DATA ROUGH-IN
UP 18" A.F.F.
MANUAL PULL STATION
FIRE ALARM ROUGH-IN
UP 44" A.F.F.
AUDIO/VISUAL DEVICE
FIRE ALARM ROUGH-IN
UP 44" A.F.F.
SMOKE DETECTOR
FIRE ALARM ROUGH-IN
GRAB BAR; SEE FLOOR PLAN
AND INTERIOR ELEVATIONS
18" x 36" STAINLESS STEEL
FRAMED MIRROR
TOILET PAPER
DISPENSER
24" x 24" SUPPLY AIR
DIFFUSER (LAY-IN)
12" x 12" SUPPLY AIR
DIFFUSER (LAY-IN)
W R
G WALL RETURN GRILLE
AT PLENUM WALL
80 CFM 80 CFM CEILING-
MOUNTED EXHAUST FAN
PROGRAMMABLE
THERMOSTAT
UP 48" A.F.F.
125V/20A QUADRUPLEX
RECEPTACLE - UP
18" A.F.F., UNO
125V/20A L5-20R "TWIST-LOCK"
RECEPTACLE - CELING MOUNTED
PN
L-
PN
L-
2.
5T
/9 kW
SP
VA
C 2.
5T /9 kW
SP
VA
C
D
PB
1-
,1 5, 2-8
1-2
1-1
1-1, b
1-1, b
1-1, b
1-1, b
1-1, b
2-1, c ab b a
1-1
2-1
2-1, a
2-1, a
2-1, a
2-1, a
1-3 1-3 1-3 1-3
2- 1, a S
/L
1-10 1-10
1-
1-
1-12
1-1
1-1
1-
1-
1-
2-2
2-
2-52-5
2-10
2-
2-6
2-52-52-8 2-8
1-19
1-20
1-20 1-23 1-23 1-23
2-182-18
2-18
2-18
E2.1
Typ
2-1, c
2-1, c
1-2
1-
2-8
2-
2-3
2-7
2-9
2-11
1-18
1-7
PANEL #1
125 AMP MCB
120/208V THREE PHASE
30 SPACE PANEL
2" DIA. EMT CONDUIT; FACTORY-
INSTALLED TO BELOW FLOOR
#4 CU AWG THWN GROUND WIRE;
BOLTED TO STEEL FRAME; FRAME TO
BE GROUNDED TO GROUNDING LUG
BY ELECTRICAL CONTRACTOR
ON SITE PER CONTRACTUAL AGREEMENT
PANEL #2
100 AMP MCB
120/208V THREE PHASE
30 SPACE PANEL
2" DIA. EMT CONDUIT; FACTORY-
INSTALLED TO BELOW FLOOR
(4) 2/0 CU AWG THWN WIRES WITH #4 CU GROUND WIRE
IN A 2" DIA EMT CONDUIT; FIELD-
PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR
PIN AND SLEEVE RECEPTACLE w/
30° ANGLE COVER PLATE, AND
BACK BOX; INSTALLED IN FACTORY
2" EMT CONDUIT; INSTALLED
BY FACTORY
2" LL CONDUIT BODY;
INSTALLED BY FACTORY
(4) 2/0 THWN CU WIRES w/
(1) #4 AWG THWN CU GROUND WIRE
INSTALLED IN CONDUIT BY FACTORY
FACTORY-INSTALLED
SERVICE ENTRANCE
CONDUIT
COUPLING AND CONDUIT
TO BE PROVIDED AND
INSTALLED BY CERTIFIED
INSTALLER
FACTORY-INSTALLED
THWN GROUND WIRE
FACTORY-INSTALLED
CONDUIT SLEEVE FOR
GROUND WIRE
MECHANICAL TWO-
CONDUCTOR GROUNDING
LUG FASTENED TO STEEL
FRAME OF MODULE w/ SELF-
DRILLING SCREW
FACTORY-INSTALLED
THWN GROUND WIRE
CONNECTED TO
GROUNDING LUG
BY FACTORY
THWN GROUND WIRE TO
GROUND ELECTRODE;
GROUND WIRE AND
GROUND ELECTRODE
PROVIDED AND INSTALLED
BY CERTIFIED INSTALLER
NOTE:
SET SCREWS FOR GROUNDING LUG
TO BE TORQUED PER ANNEX I OF
THE NATIONAL ELECTRICAL CODE
DATA PULL BOX
4" DIA. EMT CONDUIT
4" LB CONDUIT
BODY
EXTERIOR WALL
4" EMT IN CEILING CAVITY;
STUB INTO STRUCTURE 9" MIN.
4" EMT PUSH-ON BUSHING
MIN
9"
1st- floor12 1st- w alls- columns24 1st- flel- drs10 1st- flel9 1st-flme- p11 1st- walls23 common27 1st-common1 1st- floor- dim130 0
Drawn By: Serial No.
Page No.
Scale:
THIS DRAWING AND ALL INFORMATION
CONTAINED HEREON IS THE
PROPERTY OF WHITLEY MFG. CO. INC.,
AND IS NOT TO BE REPRODUCED
WITHOUT THE EXPRESS PERMISSION
OF WHITLEY MFG. CO., INC.
WHITLEY MFG. CO. INC., ASSUMES NO
RESPONSIBILITY FOR UNAUTHORIZED
USE OF THIS DRAWING.
Quote No.
Model No.
Job No.
Date:
Rev:
Checked By:
No. Description Date Whitley East, LLC
64 HESS ROAD
LEOLA, PA 17540
PHONE: 717.656.2081
www.whitleyman.com
C U
ST
O
M
ER
A
PP
R O
VA
L
SE
T
6/
/2
7:
:4
AM
As indicated
6/30/2022
7:00:42 AM
E2.12022-072-WP
EP 2696-97
49675-99
DL/CZ
(2) 10'-0" x 52'-0" MODULES
ELECTRICAL PLAN
SUSTAINABLE MODULAR MANAGEMENT
NAVAL UNDERSEA WARFARE CENTER
3/8" = 1'-0"1 Electrical Plan
1" = 1'-0"3…