PPI Reponses -0001.pdf

PDF 73 KB Posted

Attached to
REPLACE CONDENSER WATER LOOP PIPING AT STRIKE WEAPONS SCHOOL BLDG 137, NAS OCEANA
Solicitation number
N4008521R0138
Issued by

View the file

Other files

File Type Posted
PPI Reponses -0002.pdf.pdf PDF
21R0138_AMENDMENT 0003.pdf PDF
21R0138_AMENDMENT 0002.pdf PDF
Revised PPI Spreadsheet.xlsx XLSX spreadsheet
21R0138_AMENDMENT 0001.pdf PDF
52.204-24.pdf PDF
General Requirements 21R0138.pdf PDF
Price Schedule Form.pdf PDF
SECNAV 5512.pdf PDF
BASE ACCESS INSTRUCTION.pdf PDF
Wage Determination.pdf PDF
1662105 Final Specifications.pdf PDF
PPI Spreadsheet.xlsx XLSX spreadsheet
BLANK SPONSOR VERIFICATION SPREADSHEET.xls XLS spreadsheet
1662105 Final Drawings.pdf PDF
252.223-7999.pdf PDF
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page Section Para. Dwg #

1 TST Construction 12/13/2021 M-002 M-002

The intent of the phasing is to provide partial heating/cooling to the "Annex" or "Original" Buildings while the other is loop being worked on. Is the intent to also provide temporary heating/cooling the same phase where New Work will be occuring? Example: do we provide temp cooling in "Annex" building while condenser pipe is being replaced in "Annex" building.

The intent is not to provide temporary heating/cooling in the same phase in which new construction is being performed.

2 TST Construction 12/13/2021 M-002 M-002

There appears to be an unsettled chemical treatment note regarding responsibiltly. Please advise if the mechanical contractor is to provide chemical treatment for the newly installed condenser loops. If so, please provide chemical treatment spec and quantities (especially if chem treatment is to be introduced in Building 230)

Chemical teratment for the newly installed condenser loop piping is not required for this project. Chemical treatment for the closed circuit cooler and the primary geothermal/condenser water loop is part of another previous construction contract referenced on sheet M-401. 0001

3 TST Construction 12/13/2021 Is containerization of condenser water a requirement prior to condenser pipe demo? Yes. 0001

4 TST Construction 12/13/2021 M-401 M-401

Will NAVFAC be responsible for operating all exsiting to remain isolation valves, control valves, globe valves in support of "Annex" and "Original" Bldg construction phasing? (M-401/Notes-4,5,6,7)

Intent is for the mechanical contractor to perform this work with assistance from NAVFAC DDC control personnel. 0001

5 TST Construction 12/13/2021

During the site visit, it was mentioned that Bldg 137 would be unoccupied during the project. Will this be the case? Intent is for the building to be unoccupied. 0001

6 TST Construction 12/13/2021 If the building is unoccupied, will temp conditioning still be required?

No. Intent is to maintain partial heating and cooling based on the loop phasing as indicated on M-002. 0001

7 TST Construction 12/13/2021 M-401

Can you confirm the other " Geothermal Project " work, as mentioned on Page M-401, General Notes # 2, has been completed in the Bldg.137 Mechanical Room and no work on this Page M-401 is necessary.

Appears based on our 12/08/2021 site visit this work has been accomplished. 0001

8 TST Construction 12/13/2021

Does Bldg. 137 Condenser System Loop have any Glycol added into the System ? If so, what percentages of Glycol is required for this Loop ?

Glycol is not required for this condenser loop system. 0001

9 TST Construction 12/13/2021

If no Glycol is in the System, Does the Govt. want us to provide them with a Water Treatment Cost for this System after we complete the project ?

Do not provide any cost for water treatment or glycol. 0001

Project Title: REPLACE CONDENSER WATER LOOP PIPING AT STRIKE WEAPONS

SCHOOL BLDG 137, NAS OCEANA

Solicitation / RFP#: N4008521R0138 - PPI Cut Off Date: 14 DEC 2021