60025306 M-5 Rev.pdf
PDF 174 KB Posted
- Attached to
- RENOVATE M602 Federal contract opportunity
- Solicitation number
- N4008520R4049
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 60025281 C-1 Rev.pdf | ||
| 60025289 A6 Rev.pdf | ||
| 60025324 E-16 Rev.pdf | ||
| 60025283 C-3 Rev.pdf | ||
| 60025285 A2 Rev..pdf | ||
| 60025314 E-6 Rev.pdf | ||
| 60025300 P-4 Rev.pdf | ||
| 60025282 C-2 Rev.pdf | ||
| 60025286 A3 Rev.pdf | ||
| 60025283A C-4 Rev.pdf | ||
| 60025322 E-14 Rev.pdf | ||
| 60025304 M-3 Rev.pdf | ||
| 60025295 FA-2 Rev.pdf | ||
| 60025309 E-1 Rev.pdf | ||
| 60025299 P-3 Rev.pdf | ||
| 60025278 LS-1 Rev.pdf | ||
| 60025279 LS-2 Rev.pdf | ||
| 60025288 A5 Rev.pdf | ||
| 32 31 13.53 High Security Chain Link Fences.pdf | ||
| Amnd 0002 20R4049.pdf | ||
| Amnd 0001 20R4049.pdf | ||
| Master PPI Form Template.xls | XLS spreadsheet | |
| RFP 19-0063 Renovate M602.pdf | ||
| N4008519B0063 SPECs.pdf | ||
| N4008519B0063 DWGs.pdf | ||
| 19-0063 ACM-LBP Report - FINAL.pdf |
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
09.30.19
DIFFUSERS, REGISTERS AND GRILLES SCHEDULE
DRAWING
CODE
TYPE SERVICE NECK
SIZE (IN.)
BRANCH
CONN.
SIZE
(IN.)
MODULE
SIZE
(IN.)
MATERIAL FINISH MOUNTING NOTES ACCESSORIES
S1 SQUARE CEILING DIFFUSER SUPPLY 6Ø 24 X 24 ALUMINUM WHITE T-BAR 1,2 A
S2 SQUARE CEILING DIFFUSER SUPPLY 8Ø 24 X 24 ALUMINUM WHITE T-BAR 1,2 A
S3 SQUARE CEILING DIFFUSER SUPPLY 10Ø 24 X 24 ALUMINUM WHITE T-BAR 1,2 A
S4 SPIRAL DUCT GRILLE SUPPLY - - 18 X 6 ALUMINUM WHITE DUCT SURFACE 1 B
S5 VARIABLE COOLING AND HEATING DIFFUSER SUPPLY 8Ø 24 X 24 ALUMINUM WHITE T-BAR 1,2,3 - S6 SQUARE CEILING DIFFUSER SUPPLY 6Ø 16 X 16 ALUMINUM WHITE CEILING SURFACE 1,2 A
R1 FIXED FACE GRILLE RETURN 20 X 20 24 X 24 ALUMINUM WHITE T-BAR 1,2
R2 FIXED FACE GRILLE RETURN - - 24 X 10 ALUMINUM WHITE DUCT SURFACE 1 B
R3 FIXED FACE GRILLE RETURN 12 X 12 16 X 16 ALUMINUM WHITE CEILING SURFACE 1,2
E1 FIXED FACE GRILLE EXHAUST 20 X 20 24 X 24 ALUMINUM WHITE T-BAR 1,2
E2 FIXED FACE GRILLE EXHAUST 10 X 10 12 X 12 ALUMINUM WHITE CEILING SURFACE 1,2
NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.
2. DUCT BRANCH CONNECTION SIZE TO BE EQUAL TO THE NECK SIZE OF DIFFUSER UNLESS NOTED OTHERWISE ON PLANS.
3. CONTRACTOR SHALL PROVIDE AND INSTALL 24v TRANSFORMER TO POWER DIFFUSER.
ACCESSORIES: A. VOLUME DAMPER.
B. CONCEALED MOUNTING BRACKET.
SPLIT SYSTEM SCHEDULE
DRAWING CODE
(IDU/ODU)
SYSTEM
TYPE
COOLING (AHRI STANDARD) HEATING (AHRI STANDARD) INDOOR UNIT ELECTRICAL WEIGHT (LBS.) NOTES ACCESSORIES
TOTAL
(MBH)
SENSIBLE
(MBH)
EFFICIENCY TOTAL
(MBH)
EFFICIENCY SUPPLY AIRFLOW
(CFM)
OUTSIDE AIRFLOW
(CFM)
ESP
(IN. WG.)
AUX HEAT INDOOR UNIT OUTDOOR UNIT INDOOR
UNIT
OUTDOOR
UNITCAP (KW) (V/PH/HZ) (MCA) (MOCP) (V/PH/HZ) (MCA) (MOCP)
AH01/HP01 HEAT PUMP 48.2 35.4 EER 12.0 42.5 COP 3.4 1600 125 0.5 0.0 208/1/60 5.0 15 208/1/60 26.0 45 166 266 1,3,4 A,B,C,D,E,F
AH02/HP02 HEAT PUMP 73.8 54.2 EER 12.7 38.9 COP 3.3 2400 275 0.5 0.0 208/3/60 7.0 15 208/3/60 27.0 35 360 413 1,2,3,4,5 A,B,C,D,E,F,G,H
NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.
2. 2-STAGE/DUAL CIRCUIT UNIT.
3. FILTER VELOCITY NOT TO EXCEED 350 FPM.
4. HEAT PUMP COILS TO BE COATED FOR EXPOSURE TO ASTM B117-90 3000 HOUR SALT SPRAY RESISTANCE TEST WITH NO DEGRADATION.
5. MECHANICAL CONTRACTOR SHALL INSTALL DUCT SMOKE DETECTOR PROVIDED BY FIRE ALARM CONTRACTOR.
ACCESSORIES: A. HAIL-/VANDAL-PROOF COIL GUARD FOR OUTDOOR UNIT
B. BACNET MSTP DDC SYSTEM INTERFACE
C. RETURN AIR PLENUM WITH INTEGRAL FILTER RACK
D. REMOVABLE DRAIN PAN WITH FLOAT SWITCH INTERLOCKED TO SHUT DOWN UNIT. SWITCH SHALL BE MONITORED BY BAS
E. CONCRETE SUPPORT PAD FOR OUTDOOR UNIT
F. SINGLE POINT POWER SUPPLY
G. PHASE MONITOR FOR 3-PHASE EQUIPMENT
H. SINGLE ZONE VAV WITH VARIABLE FREQUENCY DRIVE ON MOTOR
DUCTLESS SPLIT SYSTEM SCHEDULE
DRAWING CODE ARI COOLING
80/67/95
ARI HEATING
70/47
MIN
SEER
MIN
HSPF
INDOOR UNIT OUTDOOR UNIT REFRIGERANT PIPING NOTES ACCESSORIES
FAN ELECTRICAL WEIGHT ELECTRICAL WEIGHT MAXIMUM
LENGTH (FT.)
MAXIMUM HEIGHT
DIFFERENTIAL (FT.)TOTAL MIN. TOTAL SA MIN-MAX VOLTAGE MCA VOLTAGE MCA MOCP
(IDU / ODU) (MBH) (MBH) (MBH) (CFM) (V/PH/HZ) (AMPS) (LBS) (V/PH/HZ) (AMPS) (AMPS) (LBS)
DAH01 / DHP01 12.0 1.5 14.4 23.1 12.5 145-399 208/1/60 1 22 208/1/60 9 15 81 65 40 1 A,B,C,D,E,F
NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.
ACCESSORIES: A. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT AND CONDUCTOR FROM OUTDOOR UNIT TO INDOOR UNIT.
B. HEAT PUMP COILS TO BE COATED FOR EXPOSURE TO ASTM B117-90 3000 HOUR SALT SPRAY RESISTANCE TEST WITH NO DEGRADATION.
C. CONCRETE SUPPORT PAD FOR OUTDOOR UNIT
D. BACNET MSTP DDC CONTROL SYSTEM INTERFACE
E. PROVIDE CONDENSATE PUMP AND RESERVOIR WITH CAPACITY OF 1.6 GAL/HR AT 33 FT OF HEAD. INTERLOCK TO SHUTDOWN UNIT.
F. WIRED WALL-MOUNTED REMOTE CONTROLLER WITH VANDAL PROOF ENCLOSURE.
LOUVER SCHEDULE
DRAWING CODE TYPE FRAME DESCRIPTION MATERIAL LOUVER
DEPTH
SIZE (W x H) SERVICE AIRFLOW (CFM) PERFORMANCE RATINGS NOTES ACCESSORIES
FREE AREA S.P. LOSS WATER PENETRATION
(IN.) (IN.) (SF) (IN.H20) (OZ./SF)
L1 FIXED CHANNEL HORIZONTAL, DRAINABLE-BLADE ALUMINUM 4 13 x 12 EXHAUST 290 0.38 0.06 0 1,2 A L2 FIXED CHANNEL HORIZONTAL, DRAINABLE-BLADE ALUMINUM 4 16 x 12 INTAKE 395 0.49 0.07 0 1,2 A, B
NOTES: 1. REFER TO SPECIFICATION FOR FURTHER INFORMATION.
ACCESSORIES: A. BIRD SCREENING (MATERIAL TO MATCH LOUVER MATERIAL).
B. PROVIDE MOTORIZED DAMPER WITH END PROVING SWITCH.
ELECTRIC DUCT HEATER SCHEDULE
DRAWING CODE HEATING
CAPACITY
(KW)
STEPS SUPPLY
AIRFLOW
(CFM)
ELECTRICAL NOTES ACCESSORIES
(V/PH/HZ) (MCA) (MOCP)
EDH01 10.0 SCR 1,400 208/3/60 34.7 45 1,2 A
EDH02 16.0 SCR 2,400 208/3/60 55.5 70 1,2 A
NOTES: 1. REFER TO SPECIFICATIONS FOR FURTHER INFORMATION.
2. OPEN COIL SLIP-IN DUCT SIZE.
ACCESSORIES: A. SCR CONTROL WITH DUCT MOUNTED DISCHARGE AIR TEMPERATURE SENSOR.
POWER VENTILATOR SCHEDULE
DRAWING CODE FAN TYPE SERVICE CAPACITIES ELECTRICAL SONES WEIGHT
(LBS.)
NOTES ACCESSORIES
AIRFLOW
(CFM)
ESP
(IN. WG.)
DRIVE
ARRANGEMENT
FAN
RPM
MOTOR
TYPE
MOTOR
SIZE (HP)
V/PH/HZ MCA MOCP
PV01 IN-LINE CENTRIFUGAL FANS EXHAUST 290 1.00 DIRECT 1707 ECM 1/4 115/1/60 5.8 15 11.8 47 1,2 A NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.
2. CONTINUOS OPERATION DURING OCCUPIED TIMES. REFER TO CONTROL SEQUENCE FOR FURTHER INFORMATION.
ACCESSORIES: A. MOTORIZED DAMPER WITH END PROVING SWITCH.
09.30.19