60025306 M-5 Rev.pdf

PDF 174 KB Posted

Attached to
RENOVATE M602 Federal contract opportunity
Solicitation number
N4008520R4049
Issued by
Department of the Navy Naval Facilities Engineering Command

View the file

Other files for this federal contract opportunity

Other files attached to RENOVATE M602, newest first.
File Type Posted
60025281 C-1 Rev.pdf PDF
60025289 A6 Rev.pdf PDF
60025324 E-16 Rev.pdf PDF
60025283 C-3 Rev.pdf PDF
60025285 A2 Rev..pdf PDF
60025314 E-6 Rev.pdf PDF
60025300 P-4 Rev.pdf PDF
60025282 C-2 Rev.pdf PDF
60025286 A3 Rev.pdf PDF
60025283A C-4 Rev.pdf PDF
60025322 E-14 Rev.pdf PDF
60025304 M-3 Rev.pdf PDF
60025295 FA-2 Rev.pdf PDF
60025309 E-1 Rev.pdf PDF
60025299 P-3 Rev.pdf PDF
60025278 LS-1 Rev.pdf PDF
60025279 LS-2 Rev.pdf PDF
60025288 A5 Rev.pdf PDF
32 31 13.53 High Security Chain Link Fences.pdf PDF
Amnd 0002 20R4049.pdf PDF
Amnd 0001 20R4049.pdf PDF
Master PPI Form Template.xls XLS spreadsheet
RFP 19-0063 Renovate M602.pdf PDF
N4008519B0063 SPECs.pdf PDF
N4008519B0063 DWGs.pdf PDF
19-0063 ACM-LBP Report - FINAL.pdf PDF
Show all 26

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2246 Yaupon Drive

Wilmington, NC 28401

Phone: 910.791.4000

Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2019 CBHF Engineers, PLLC

Engineers, PLLC

NC# P-0506

09.30.19

DIFFUSERS, REGISTERS AND GRILLES SCHEDULE

DRAWING

CODE

TYPE SERVICE NECK

SIZE (IN.)

BRANCH

CONN.

SIZE

(IN.)

MODULE

SIZE

(IN.)

MATERIAL FINISH MOUNTING NOTES ACCESSORIES

S1 SQUARE CEILING DIFFUSER SUPPLY 6Ø 24 X 24 ALUMINUM WHITE T-BAR 1,2 A

S2 SQUARE CEILING DIFFUSER SUPPLY 8Ø 24 X 24 ALUMINUM WHITE T-BAR 1,2 A

S3 SQUARE CEILING DIFFUSER SUPPLY 10Ø 24 X 24 ALUMINUM WHITE T-BAR 1,2 A

S4 SPIRAL DUCT GRILLE SUPPLY - - 18 X 6 ALUMINUM WHITE DUCT SURFACE 1 B

S5 VARIABLE COOLING AND HEATING DIFFUSER SUPPLY 8Ø 24 X 24 ALUMINUM WHITE T-BAR 1,2,3 - S6 SQUARE CEILING DIFFUSER SUPPLY 6Ø 16 X 16 ALUMINUM WHITE CEILING SURFACE 1,2 A

R1 FIXED FACE GRILLE RETURN 20 X 20 24 X 24 ALUMINUM WHITE T-BAR 1,2

R2 FIXED FACE GRILLE RETURN - - 24 X 10 ALUMINUM WHITE DUCT SURFACE 1 B

R3 FIXED FACE GRILLE RETURN 12 X 12 16 X 16 ALUMINUM WHITE CEILING SURFACE 1,2

E1 FIXED FACE GRILLE EXHAUST 20 X 20 24 X 24 ALUMINUM WHITE T-BAR 1,2

E2 FIXED FACE GRILLE EXHAUST 10 X 10 12 X 12 ALUMINUM WHITE CEILING SURFACE 1,2

NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.

2. DUCT BRANCH CONNECTION SIZE TO BE EQUAL TO THE NECK SIZE OF DIFFUSER UNLESS NOTED OTHERWISE ON PLANS.

3. CONTRACTOR SHALL PROVIDE AND INSTALL 24v TRANSFORMER TO POWER DIFFUSER.

ACCESSORIES: A. VOLUME DAMPER.

B. CONCEALED MOUNTING BRACKET.

SPLIT SYSTEM SCHEDULE

DRAWING CODE

(IDU/ODU)

SYSTEM

TYPE

COOLING (AHRI STANDARD) HEATING (AHRI STANDARD) INDOOR UNIT ELECTRICAL WEIGHT (LBS.) NOTES ACCESSORIES

TOTAL

(MBH)

SENSIBLE

(MBH)

EFFICIENCY TOTAL

(MBH)

EFFICIENCY SUPPLY AIRFLOW

(CFM)

OUTSIDE AIRFLOW

(CFM)

ESP

(IN. WG.)

AUX HEAT INDOOR UNIT OUTDOOR UNIT INDOOR

UNIT

OUTDOOR

UNITCAP (KW) (V/PH/HZ) (MCA) (MOCP) (V/PH/HZ) (MCA) (MOCP)

AH01/HP01 HEAT PUMP 48.2 35.4 EER 12.0 42.5 COP 3.4 1600 125 0.5 0.0 208/1/60 5.0 15 208/1/60 26.0 45 166 266 1,3,4 A,B,C,D,E,F

AH02/HP02 HEAT PUMP 73.8 54.2 EER 12.7 38.9 COP 3.3 2400 275 0.5 0.0 208/3/60 7.0 15 208/3/60 27.0 35 360 413 1,2,3,4,5 A,B,C,D,E,F,G,H

NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.

2. 2-STAGE/DUAL CIRCUIT UNIT.

3. FILTER VELOCITY NOT TO EXCEED 350 FPM.

4. HEAT PUMP COILS TO BE COATED FOR EXPOSURE TO ASTM B117-90 3000 HOUR SALT SPRAY RESISTANCE TEST WITH NO DEGRADATION.

5. MECHANICAL CONTRACTOR SHALL INSTALL DUCT SMOKE DETECTOR PROVIDED BY FIRE ALARM CONTRACTOR.

ACCESSORIES: A. HAIL-/VANDAL-PROOF COIL GUARD FOR OUTDOOR UNIT

B. BACNET MSTP DDC SYSTEM INTERFACE

C. RETURN AIR PLENUM WITH INTEGRAL FILTER RACK

D. REMOVABLE DRAIN PAN WITH FLOAT SWITCH INTERLOCKED TO SHUT DOWN UNIT. SWITCH SHALL BE MONITORED BY BAS

E. CONCRETE SUPPORT PAD FOR OUTDOOR UNIT

F. SINGLE POINT POWER SUPPLY

G. PHASE MONITOR FOR 3-PHASE EQUIPMENT

H. SINGLE ZONE VAV WITH VARIABLE FREQUENCY DRIVE ON MOTOR

DUCTLESS SPLIT SYSTEM SCHEDULE

DRAWING CODE ARI COOLING

80/67/95

ARI HEATING

70/47

MIN

SEER

MIN

HSPF

INDOOR UNIT OUTDOOR UNIT REFRIGERANT PIPING NOTES ACCESSORIES

FAN ELECTRICAL WEIGHT ELECTRICAL WEIGHT MAXIMUM

LENGTH (FT.)

MAXIMUM HEIGHT

DIFFERENTIAL (FT.)TOTAL MIN. TOTAL SA MIN-MAX VOLTAGE MCA VOLTAGE MCA MOCP

(IDU / ODU) (MBH) (MBH) (MBH) (CFM) (V/PH/HZ) (AMPS) (LBS) (V/PH/HZ) (AMPS) (AMPS) (LBS)

DAH01 / DHP01 12.0 1.5 14.4 23.1 12.5 145-399 208/1/60 1 22 208/1/60 9 15 81 65 40 1 A,B,C,D,E,F

NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.

ACCESSORIES: A. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT AND CONDUCTOR FROM OUTDOOR UNIT TO INDOOR UNIT.

B. HEAT PUMP COILS TO BE COATED FOR EXPOSURE TO ASTM B117-90 3000 HOUR SALT SPRAY RESISTANCE TEST WITH NO DEGRADATION.

C. CONCRETE SUPPORT PAD FOR OUTDOOR UNIT

D. BACNET MSTP DDC CONTROL SYSTEM INTERFACE

E. PROVIDE CONDENSATE PUMP AND RESERVOIR WITH CAPACITY OF 1.6 GAL/HR AT 33 FT OF HEAD. INTERLOCK TO SHUTDOWN UNIT.

F. WIRED WALL-MOUNTED REMOTE CONTROLLER WITH VANDAL PROOF ENCLOSURE.

LOUVER SCHEDULE

DRAWING CODE TYPE FRAME DESCRIPTION MATERIAL LOUVER

DEPTH

SIZE (W x H) SERVICE AIRFLOW (CFM) PERFORMANCE RATINGS NOTES ACCESSORIES

FREE AREA S.P. LOSS WATER PENETRATION

(IN.) (IN.) (SF) (IN.H20) (OZ./SF)

L1 FIXED CHANNEL HORIZONTAL, DRAINABLE-BLADE ALUMINUM 4 13 x 12 EXHAUST 290 0.38 0.06 0 1,2 A L2 FIXED CHANNEL HORIZONTAL, DRAINABLE-BLADE ALUMINUM 4 16 x 12 INTAKE 395 0.49 0.07 0 1,2 A, B

NOTES: 1. REFER TO SPECIFICATION FOR FURTHER INFORMATION.

ACCESSORIES: A. BIRD SCREENING (MATERIAL TO MATCH LOUVER MATERIAL).

B. PROVIDE MOTORIZED DAMPER WITH END PROVING SWITCH.

ELECTRIC DUCT HEATER SCHEDULE

DRAWING CODE HEATING

CAPACITY

(KW)

STEPS SUPPLY

AIRFLOW

(CFM)

ELECTRICAL NOTES ACCESSORIES

(V/PH/HZ) (MCA) (MOCP)

EDH01 10.0 SCR 1,400 208/3/60 34.7 45 1,2 A

EDH02 16.0 SCR 2,400 208/3/60 55.5 70 1,2 A

NOTES: 1. REFER TO SPECIFICATIONS FOR FURTHER INFORMATION.

2. OPEN COIL SLIP-IN DUCT SIZE.

ACCESSORIES: A. SCR CONTROL WITH DUCT MOUNTED DISCHARGE AIR TEMPERATURE SENSOR.

POWER VENTILATOR SCHEDULE

DRAWING CODE FAN TYPE SERVICE CAPACITIES ELECTRICAL SONES WEIGHT

(LBS.)

NOTES ACCESSORIES

AIRFLOW

(CFM)

ESP

(IN. WG.)

DRIVE

ARRANGEMENT

FAN

RPM

MOTOR

TYPE

MOTOR

SIZE (HP)

V/PH/HZ MCA MOCP

PV01 IN-LINE CENTRIFUGAL FANS EXHAUST 290 1.00 DIRECT 1707 ECM 1/4 115/1/60 5.8 15 11.8 47 1,2 A NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.

2. CONTINUOS OPERATION DURING OCCUPIED TIMES. REFER TO CONTROL SEQUENCE FOR FURTHER INFORMATION.

ACCESSORIES: A. MOTORIZED DAMPER WITH END PROVING SWITCH.

09.30.19