2246 Yaupon Drive Wilmington, NC 28401 Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
GENERAL NOTES
1. ALL ELECTRICAL WORK SHALL BE IN FULL COMPLIANCE WITH NFPA 70, ALL APPLICABLE UNITED FACILITIES CRITERA, ALL LOCAL CODES AND ORDINANCES AND
IN ACCORDANCE WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION.
2. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR SHALL BE LISTED AND LABELED BY A NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL MATERIAL, EQUIPMENT AND DEVICES SHALL BE NEW CURRENT PRODUCTS OF MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH PRODUCTS. EQUIPMENT SHALL BE SUITABLE FOR ITS APPLICATION (E.G. WHEN
INSTALLED OUTDOORS, IT SHALL BE WEATHERPROOF, ETC.)
3. THE CONTRACTOR SHALL REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR WORK REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL
EQUIPMENT, AND LAYOUT HIS WORK IN A COMPATIBLE AND COMPLEMENTARY MANNER.
4. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR THOROUGHLY FAMILIARIZING HIMSELF WITH ANY CONTRACTUAL REQUIREMENTS AS MAY BE SET FORTH
IN THE OTHER DIVISIONS OF THE PROJECT SPECIFICATIONS.
5. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED BY THE ELECTRICAL CONTRACTOR SHALL BE COMPLETE AND FULLY-FUNCTIONING AFTER INSTALLATION. INCIDENTAL COMPONENTS MAY NOT BE SHOWN, AND ALL WORK WHICH MAY BE REASONABLY IMPLIED AS BEING INCIDENTAL TO THIS WORK, BUT REQUIRED FOR THE PROPER OPERATION OF THE EQUIPMENT OR SYSTEM, SHALL BE PROVIDED BY THE CONTRACTOR AND INCLUDED IN THE BID. ADDITIONAL CIRCUITS SHALL BE INSTALLED WHEREVER NEEDED TO CONFORM TO THE SPECIFIC REQUIREMENTS OF EQUIPMENT.
6. TEMPORARY POWER CONNECTIONS AS REQUIRED SHALL BE PROVIDED BY THE CONTRACTOR AND INCLUDED IN THE BID. ALL TEMPORARY EQUIPMENT WIRING SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. THE CONTRACTOR SHALL PROVIDE DETAILS, METHODS, MATERIALS, ETC. FOR REVIEW PRIOR TO MAKING TEMPORARY CONNECTIONS. FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS INCLUDING CONTROL EQUIPMENT, MOTOR STARTERS, BRANCH AND FEEDER CIRCUIT BREAKERS, PANELBOARDS, TRANSFORMERS, ETC. FOR TEMPORARY POWER. COORDINATE WITH THE ELECTRICAL UTILITY
COMPANY AS REQUIRED.
7. THE WORK SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING AT THE COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR
ADJUSTMENTS NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM AND EQUIPMENT.
8. ALL EQUIPMENT SHOWN DOTTED OR DASHED IS BY OTHERS OR IS EXISTING, AS NOTED.
9. ALL ELECTRICAL EQUIPMENT SHALL, AT ALL TIMES DURING CONSTRUCTION, BE ADEQUATELY PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER AND/OR THE ELEMENTS. ELECTRICAL EQUIPMENT SHALL NOT BE STORED OUT OF DOORS, BUT SHALL BE STORED IN DRY PERMANENT SHELTERS. IF AN APPARATUS HAS BEEN DAMAGED, OR HAS BEEN SUBJECT TO POSSIBLE INJURY BY WATER OR THE ELEMENTS, SUCH DAMAGE SHALL BE REPLACED AT NO
ADDITIONAL COST.
10. DO NOT SCALE ELECTRICAL DRAWINGS. REFER TO THE ARCHITECTURAL DRAWINGS FOR DIMENSIONS.
11. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR OTHER INSTALLATION DETAILS. UNLESS NOTED OTHERWISE, THE EXACT ROUTING OF FEEDER AND BRANCH CIRCUIT RACEWAYS AND CABLES IS THE RESPONSIBILITY OF THE CONTRACTOR. RISER AND GENERAL CIRCUIT ARRANGEMENTS ARE SHOWN SCHEMATICALLY/DIAGRAMMATICALLY ONLY. THE CONTRACTOR SHALL ROUTE CONDUITS AS REQUIRED BY THE CONDITIONS OF
THE INSTALLATION.
12. UNLESS DIMENSIONED, DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE. ADJUST EXACT LOCATIONS AS REQUIRED TO SERVE THE INTENDED PURPOSE AND TO AVOID CONFLICTS AND INTERFERENCES WITH OTHER TRADES. EXACT DEVICE LOCATIONS SHALL BE AS INDICATED ON THE ARCHITECTURAL DRAWINGS OR AS DIMENSIONED. IF NOT SHOWN ON THE ARCHITECTURAL DRAWINGS OR DIMENSIONED ON THE ELECTRICAL DRAWINGS, VERIFY EXACT
LOCATION WITH THE ARCHITECT/ENGINEER PRIOR TO ROUGH-IN.
13. CONDUIT TERMINATING IN PRESSED STEEL BOXES SHALL HAVE DOUBLE LOCKNUTS AND INSULATED BUSHINGS. CONDUITS TERMINATING IN GASKETED
ENCLOSURES SHALL BE TERMINATED WITH GROUNDING TYPE CONDUIT HUBS.
14. DEVICE BOXES SHOWN BACK-TO-BACK SHALL BE OFFSET A MINIMUM OF TWELVE (12) INCHES TO REDUCE SOUND TRANSMISSION BETWEEN ROOMS.
15. BRANCH CIRCUIT HOMERUNS SHOWN ON DRAWINGS INDICATE PHASE CONDUCTORS, NEUTRAL, EQUIPMENT GROUND CONDUCTORS AS REQUIRED.
ADDITIONAL CONDUCTORS REQUIRED FOR CONTROL SHALL BE INCLUDED EVEN IF NOT EXPLICITLY SHOWN.
16. SEAL ALL CONDUIT OPENINGS THROUGH EXTERIOR BUILDING WALLS WATERTIGHT.
17. IN WET LOCATIONS AND EXTERIOR, ALL WIRING DEVICES SHALL BE WEATHER-RESISTANT LISTED WITH WEATHERPROOF WHILE IN USE COVER. LIGHTING FIXTURES SHALL BE APPROPRIATELY RATED AND LISTED FOR THE ENVIRONMENT INCLUDING 0 DEGREE BALLASTS FOR FLUORESCENT.
18. RACEWAYS PENETRATING FLOORS, CEILINGS OR WALLS SHALL BE PROPERLY SEALED SMOKETIGHT.
19. RACEWAYS PENETRATING RATED FLOOR, CEILING OR WALL ASSEMBLIES SHALL BE PROPERLY SEALED IN ACCORDANCE WITH THE CORRESPONDING UNDERWRITERS LABORATORIES (OR OTHER APPROVED THIRD PARTY TESTING AGENCY) APPROVED AND LISTED FIRESTOPPING MATERIALS AND MANUFACTURER APPROVED INSTALLATION TECHNIQUES COMPLYING WITH ALL APPLICABLE CODES. SEE ARCHITECTURAL DRAWINGS FOR IDENTIFICATION OF
RATED WALLS AND CEILINGS.
20. LIGHTING FIXTURES, SPEAKER ASSEMBLIES, ETC. MOUNTED IN FIRE-RATED CEILINGS SHALL BE PROVIDED WITH UL-LISTED, PRE-FABRICATED OR FIELD
FABRICATED SHROUDS/ACCESSORIES NECESSARY TO MAINTAIN THE CEILING FIRE RATING.
21. ALL RACEWAYS SHALL BE CONCEALED WHERE POSSIBLE. IF APPLICABLE, MATCH EXISTING RACEWAY INSTALLATION METHODS AND ROUTINGS AT OR NEAR
EXISTING FACILITIES.
22. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY SURFACES OR STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS AS MUCH AS POSSIBLE. NO DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS SHALL BE RUN STRAIGHT AND TRUE. RUN PARALLEL OR BANKED RACEWAYS TOGETHER ON COMMON SUPPORTS WHERE PRACTICAL. MAKE BENDS IN PARALLEL OR BANKED RUNS FROM SAME CENTERLINE TO MAKE BENDS PARALLEL.
23. PROVIDE AND PLACE ALL SLEEVES FOR CONDUITS PENETRATING WALLS, FLOORS, PARTITIONS, ETC. LOCATE ALL NECESSARY SLOTS FOR ELECTRICAL WORK
AND FORM BEFORE CONCRETE IS POURED.
24. PATCHING OF WATERPROOFED SURFACES SHALL RENDER THE AREA OF THE PATCHING COMPLETELY WATERPROOF.
25. ALL MOTORS, DRY TYPE TRANSFORMERS AND OTHER VIBRATING EQUIPMENT SHALL BE CONNECTED TO THE CONDUIT SYSTEM BY MEANS OF A SHORT SECTION (18 INCH MINIMUM) OF FLEXIBLE CONDUIT UNLESS OTHERWISE INDICATED. AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED INSIDE THE FLEXIBLE
CONDUIT AND TERMINATE AT THE LOAD END WITH AN APPROVED GROUNDING CLAMP OR LUG.
26. SURFACE MOUNTED PANELBOARDS, JUNCTION, OUTLET AND PULL BOXES, RACEWAYS, ETC., INSTALLED ON EXTERIOR SURFACES OR INSIDE ON EXTERIOR WALLS SHALL BE SUPPORTED BY SPACERS TO PROVIDE A 1/4" MINIMUM CLEARANCE BETWEEN THE WALL AND EQUIPMENT.
27. CEILING MOUNTED DEVICES INSTALLED IN ACOUSTICAL TILE CEILING AREAS SHALL BE SUPPORTED FROM THE STRUCTURE ABOVE WITH RODS OF SUFFICIENT SIZE TO PREVENT VERTICAL MOVEMENT OF THE OUTLET BOX. BRIDGES ALONE ARE NOT ADEQUATE UNLESS SPECIFICALLY APPROVED. CEILING MOUNTED EXIT LIGHT FIXTURES SHALL BE INSTALLED LEVEL. DO NOT SUPPORT DEVICES FROM ACCOUSTICAL CEILING TILE.
28. EXCAVATION AND TRENCHING REQUIRED FOR THE INSTALLATION OF ELECTRICAL POWER AND TELECOMMUNICATIONS RACEWAYS SHALL BE PROVIDED BY THE CONTRACTOR IN ACCORDANCE WITH THE REQUIREMENTS OF DIVISION 26 OF THE PROJECT SPECIFICATIONS.
29. PRIOR TO TRENCHING IN ANY AREA, THE CONTRACTOR SHALL CONTACT ELECTRICAL, COMMUNICATIONS/DATA/FIBER, CABLE TELEVISION, GAS AND WATER UTILITY PROVIDERS AND HAVE ALL UTILITIES IN THE AREA IDENTIFIED. DAMAGE TO ANY UNDERGROUND UTILITIES OR STRUCTURES SHALL BE REPAIRED BY
THE CONTRACTOR AT NO ADDITIONAL COST TO THE PROJECT.
30. ALL UNDERGROUND RACEWAYS SHALL BE IDENTIFIED BY UNDERGROUND LINE MARKING TAPE LOCATED DIRECTLY ABOVE THE RACEWAY AT 6 TO 8 INCHES
BELOW FINISHED GRADE. SEE SPECIFICATIONS.
31. WHERE UNDERGROUND RACEWAYS ARE REQUIRED TO TURN UP INTO CABINETS, EQUIPMENT, ETC., AND ON TO POLES, THE ELBOW REQUIRED AND THE
STUB-UP OUT OF THE SLAB OR EARTH SHALL BE OF PLASTIC-COATED RIGID STEEL.
32. PROVIDE 200% RATED NEUTRAL FEEDERS AND NEUTRAL BARS FOR PANELBOARDS FED BY K-RATED TRANSFORMERS.
33. PROVIDE ADHESIVE BACKED RECEPTACLE DEVICE PLATE LABELS IDENTIFYING THE CIRCUIT FEEDING THE DEVICE. LABELS SHALL INDICATE PANEL AND CIRCUIT NUMBER. ALSO PROVIDE IDENTIFICATION FOR MULTIWIRE BRANCH CIRCUIT PHASE CONDUCTORS IN PANELBOARD.
34. FINAL TYPED PANELBOARD DIRECTORIES INSTALLED IN THE PANELBOARD DOOR POCKET SHALL INCLUDE FINAL ACTUAL ROOM NAMES AND NUMBERS IN ADDITION TO THE GENERAL DESCRIPTION SHOWN ON THE PANEL SCHEDULES ON THE DRAWINGS.
35. CONDUCTOR SIZING IS BASED ON 75 DEGREE C. COPPER NEC RATINGS, UNLESS NOTED OTHERWISE. THE CONTRACTOR SHALL VERIFY, PRIOR TO INSTALLATION OF CONDUCTORS OR CONDUIT FEEDING ANY EQUIPMENT, THE ELECTRICAL EQUIPMENT IS RATED FOR USE WITH 75 DEGREE C. WIRING. IF ANY EQUIPMENT IS RATED FOR USE WITH LESS THAN 75 DEGREE C. CONDUCTORS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY FOR
EVALUATION/CORRECTION.
36. DO NOT PULL CONDUCTORS UNTIL THE CONDUIT SYSTEM IS COMPLETE IN EVERY DETAIL. IN THE CASE OF CONCEALED WORK, "COMPLETE" MEANS UNTIL ALL
ROUGH PLASTERING OR MASONRY HAS BEEN COMPLETED.
37. WHERE SIZE IS NOT SHOWN ON THE DRAWINGS, BRANCH CIRCUITS SHALL CONSIST OF #12 OR #10 AWG MINIMUM PHASE, NEUTRAL AND EQUIPMENT GROUND
CONDUCTORS IN 3/4" MINIMUM RACEWAY.
38. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS WITH A TOTAL INSTALLED LENGTH GREATER THAN 75 FEET AND/OR BRANCH CIRCUIT HOMERUNS LONGER THAN 50 FEET, I.E.; #12 AWG INCREASED TO #10 AWG FOR RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH (INCLUDING THE
HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET.
39. ALTERNATE MULTIWIRE (COMMON NEUTRAL) RECEPTACLE CIRCUITS SUCH THAT ADJACENT RECEPTACLES ARE ON DIFFERENT CIRCUITS.
40. PROVIDE SEPARATE, INDIVIDUAL NEUTRAL CONDUCTORS FOR RECEPTACLE CIRCUITS MARKED FOR COMPUTER OR PRINTER USE. SEE LEGEND AND/OR
DRAWINGS FOR DEFINITION.
41. KEEP CONDUCTOR SPLICES TO A MINIMUM. INSTALL SPLICES AND TAPES THAT POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION RATINGS THAN CONDUCTORS BEING SPLICED. USE SPLICE AND TAP CONNECTORS COMPATIBLE WITH CONDUCTOR MATERIAL. INSTALL CONDUCTORS AT EACH OUTLET WITH AT LEAST 12 INCHES OF SLACK. CONNECT OUTLETS AND COMPONENTS TO WIRING AND TO GROUND AS INDICATED AND INSTRUCTED BY THE
MANUFACTURER.
42. DO NOT SPLICE BRANCH CIRCUIT HOMERUNS WITHOUT THE PERMISSION OF THE ARCHITECT/ENGINEER. HOMERUNS SHALL BE CONTINUOUS FROM THE LAST
OUTLET BOX TO THE SERVING PANELBOARD.
43. DO NOT COMBINE BRANCH CIRCUIT HOMERUNS UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
44. DO NOT CHANGE CIRCUITING SHOWN WITHOUT PERMISSION OF THE ARCHITECT/ENGINEER.
45. TROUGH TAPS SHALL BE AT SWITCH AMPACITY, UNLESS NOTED OTHERWISE.
46. INSTALL WIRING DEVICES AT HEIGHTS AS SHOWN ON THE DRAWINGS. ALSO COORDINATE MOUNTING HEIGHTS WITH THE ARCHITECTURAL DRAWINGS AND CASEWORK DETAILS. IF CONFLICTING, ARCHITECTURAL DRAWINGS AND DETAILS SHALL GOVERN.
47. PROVIDE GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL IN ACCORDANCE WITH THE NEC INCLUDING ALL ELECTRIC WATER COOLERS, EXTERIOR RECEPTACLES AND RECEPTACLES IN AREAS SUBJECT TO POSSIBLE WET CONDITIONS. ALL RECEPTACLES INSTALLED WITHIN 6 FEET OF A SINK SHALL BE GFI PROTECTED. ALL RECEPTACLES IN NON-RESIDENTIAL KITCHENS SHALL BE GFI PROTECTED.
48. IN AREAS IN WHICH DUAL LEVEL SWITCHING IS INDICATED (TYPICALLY BY 2 OR MORE ADJACENT, GANGED SWITCHES), PROVIDE THE APPROPRIATE NUMBER OF
CONDUCTORS TO FACILITATE THIS FUNCTION (AS TYPICALLY SHOWN).
49. CONNECT BATTERY PACK TYPE EMERGENCY AND EXIT LIGHTING TO THE UNSWITCHED LIGHTING CIRCUIT SERVING THE SPACE LIGHTED BY THE EMERGENCY AND EXIT FIXTURES. THESE CONNECTIONS ARE INTENTIONALLY NOT SHOWN TO MAINTAIN DRAWING FOR CLARITY.
50. COORDINATE LIGHTING FIXTURE LOCATIONS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN. IF CONFLICTS ARE NOTED, REQUEST CLARIFICATION FROM
THE ARCHITECT/ENGINEER BEFORE PROCEDING.
51. ADJACENT SWITCHES SHALL BE GANGED. INSTALL BARRIERS BETWEEN UNLIKE VOLTAGE SECTIONS.
52. SEPARATE NEUTRALS ARE REQUIRED FOR ALL DIMMED LIGHTING CIRCUITS.
53. WHERE THE DRAWINGS INDICATE A LIGHTING FIXTURE IS TO BE PROVIDED WITH SPECIAL FEATURES/SWITCHING (DIMMING, EMERGENCY BATTERY BALLAST, MULTI-LEVEL, ETC), THE CONTRACTOR SHALL PROVIDE THESE FIXTURES WITH THE APPROPRIATE BALLASTING TO ACCOMMODATE THE SPECIAL FEATURE. THE CONTRACTOR SHALL PROVIDE THE FIXTURES AS INDICATED IN THE LIGHTING FIXTURE SCHEDULE WITH MODIFICATIONS AS REQUIRED BY DRAWING NOTES.
54. COORDINATE LOCATIONS OF MECHANICAL, DATA AND GOVERNMENT-PROVIDED EQUIPMENT WITH THE RESPECTIVE SUPPLIERS AND VENDORS AND THE GOVERNMENT BEFORE ROUGH-IN. ADJUST LIGHTING FIXTURES, RECEPTACLES AND ELECTRICAL EQUIPMENT TO ACCOMMODATE THIS EQUIPMENT. ADVISE THE
ARCHITECT/ENGINEER OF CONFLICTS BEFORE ROUGH-IN.
55. BEFORE COMMENCING WORK OR ORDERING MATERIALS, THE CONTRACTOR SHALL COORDINATE WITH OTHER TRADES AND VERIFY THE NAMEPLATE RATINGS OF ALL EQUIPMENT (MOTORS, HEATERS, COMPRESSORS, ETC.) AND ADJUST THE RATINGS OF THE ELECTRICAL EQUIPMENT (SWITCHES, FUSES, CIRCUIT
BREAKERS, FEEDERS, ETC.) AS APPROPRIATE TO SERVE THIS EQUIPMENT.
56. ENERGIZE EQUIPMENT ONLY AFTER OBTAINING PERMISSION FROM THE CONTRACTOR PROVIDING THE EQUIPMENT.
57. THE MECHANICAL CONTRACTOR SHALL FURNISH ALL STARTERS AND CONTROLS FOR THEIR EQUIPMENT. THE ELECTRICAL CONTRACTOR SHALL MOUNT STARTERS FURNISHED BY THE MECHANICAL CONTRACTOR, THE ELECTRICAL CONTRACTOR PROVIDE ALL SAFETY SWITCHES, WIRING AND CONNECTIONS TO LINE SIDE AND LOAD SIDE OF STARTERS AND SAFETY SWITCHES COMPLETE TO MECHANICAL EQUIPMENT. FOR RESISTANCE TYPE LOADS WHERE STARTERS OR CONTACTORS ARE NOT REQUIRED, THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL POWER WIRING AND CONNECTIONS COMPLETE TO EQUIPMENT. THE MECHANICAL AND PLUMBING CONTRACTORS SHALL PROVIDE ALL CONTROL WIRING AND CONNECTIONS AND DEVICES FOR THEIR EQUIPMENT. .Non SCO projects]
58. THE CONTRACTOR SHALL COORDINATE ALL EQUIPMENT TERMINATIONS, PLUGS AND CORDSETS WITH VENDOR EQUIPMENT AND VERIFY ALL DEVICE LOCATIONS
FOR SPECIALITY EQUIPMENT WITH CASEWORK PRIOR TO ROUGH-IN.
59. THE LAYOUT AND PLACEMENT OF ELECTRICAL DISTRIBUTION EQUIPMENT IN ELECTRICAL AND MECHANICAL EQUIPMENT ROOMS IS BASED ON PUBLISHED EQUIPMENT SIZES AND SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE. DEVIATIONS FROM CONFIGURATIONS SHOWN IS THE RESPONSIBILITY OF THE CONTRACTOR. PROVIDE NATIONAL ELECTRIC CODE REQUIRED CLEARANCES FOR ALL ELECTRICAL EQUIPMENT, PANELBOARDS, TRANSFORMERS, SAFETY SWITCHES, SWITCHBOARDS, ETC. COORDINATE RESOLUTION OF CONFLICTS WITH OTHER TRADES. ADVISE THE ARCHITECT/ENGINEER OF CONFLICTS BEFORE
ROUGH-IN.
60. COORDINATION WITH THE UTILITY FOR PLACEMENT OF THE UTILITY'S FACILITIES AND THE CONTRACTOR'S SERVICE ENTRANCE RACEWAYS AND CONNECTIONS TO THE CONTRACTOR'S SERVICE ENTRANCE CONDUCTORS IS THE RESPONSIBILITY OF CONTRACTOR.
61. TELECOMMUNICATIONS AND DATA CABLES WILL BE PROVIDED AND INSTALLED BY THE CONTRACTOR. LEAVE PULL WIRES OR ROPES OF ADEQUATE TENSILE
STRENGTH IN ALL EMPTY CONDUITS.
62. PROVIDE TELEPHONE, CABLE TELEVISION, FIBER AND DATA SERVICE ENTRANCE CONDUIT IN SIZES AND LOCATIONS AS SHOWN ON THE DRAWINGS AND AS REQUIRED BY THE GOVERNMENT AND THE SERVICE UTILITIES. LEAVE PULL WIRES OR ROPES OF ADEQUATE TENSILE STRENGTH IN ALL EMPTY CONDUITS.
63. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR FIRE ALARM WORK ON THIS PROJECT. THIS INCLUDES BUT NOT LIMITED TO DE-PROGRAMMING REMOVED DEVICES, PUTTING SYSTEM ON TEST, PROTECTING EXISTING DEVICES DURING CONSTRUCTION, ETC. EC SHALL INCLUDE IN BID THE COST FOR THE SCHOOL'S FIRE ALARM VENDOR TO PERFORM THIS WORK. THE CURRENT NHCS FIRE ALARM VENDOR IS KELLER'S INC. THE EC SHALL BE RESPONSIBLE FOR PAYING FOR
ANY FALSE ALARMS CAUSED BY THE CONSTRUCTION FOR THIS PROJECT.
64. INSTALLATION INFORMATION PACKED WITH LIGHTING FIXTURES, DEVICES AND EQUIPMENT SHALL BE RETAINED FOR INCLUSION IN THE OPERATIONS AND
MAINTENANCE MANUALS.
65. SAFETY: COMPLY WITH OSHA AND NEC ARC FLASH PROTECTION REQUIREMENTS.
SYSTEM NO. W-J-2274
JUNE 04, 2015
ANSI/UL1479 (ASTM E814)
F RATING — 2 HR
T RATING — 2 HR
CAN/ULC S115
F RATING — 2 HR
FT RATING — 2 HR
FH RATING — 2 HR
FTH RATING — 2 HR
SYSTEM TESTED WITH A PRESSURE DIFFERENTIAL OF 50 PA BETWEEN THE EXPOSED AND THE UNEXPOSED SURFACES WITH THE HIGHER PRESSURE ON
THE EXPOSED SIDE.
1. WALL ASSEMBLY — MIN 6 IN. (152 MM) THICK LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE.
WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. DIAM OF OPENING SHALL BE MAX 1-11/16 IN. (43 MM) LARGER THAN OUTER DIAMETER (OD) OF THROUGH PENETRANT. MAX DIAM OF OPENING IS 8 IN. (203 MM).
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS.
2. THROUGH PENETRANTS — ONE NONMETALLIC PIPE TO BE INSTALLED CONCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN THE PIPE AND PERIPHERY OF OPENING SHALL BE MAX 7/8 IN. (22 MM). PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES MAY BE USED:
A. POLYPROPYLENE (PP-R) PIPE — NOM 6 IN. DIAM - 160 MM OD (OR SMALLER) SDR 17.6 MF AQUATHERM BLUE PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT)
PIPING SYSTEMS.
3. FIRESTOP SYSTEM — THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. FIRESTOP DEVICE* — GALV STEEL SLEEVE LINED WITH AN INTUMESCENT MATERIAL SIZED TO FIT THE SPECIFIC DIAM OF THE THROUGH PENETRANT. DEVICE TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS ALONG WITH THE FOLLOWING: DEVICE TO BE WRAPPED AROUND OUTER CIRCUMFERENCE OF THROUGH PENETRANT AND INSTALLED THROUGH THE ANNULAR SPACE OF THE OPENING. THE DEVICE MAY BE TEMPORARILY SECURED BY MEANS OF TAPE OR TIE WIRES AROUND THE OUTER CIRCUMFERENCE OF THROUGH PENETRANT TO ALLOW FOR INSTALLATION OF THE FILL MATERIAL (ITEM 3B). THE DEVICE SHALL BE CENTERED WITHIN THE WALL AND EXTEND EQUALLY BEYOND EACH SURFACE OF THE WALL.
RECTORSEAL — FLAMESAFE® INTUMESCENT SLEEVE 68, METACAULK INTUMESCENT SLEEVE 68 OR
BIOSTOP INTUMESCENT SLEEVE 68
B. FILL, VOID OR CAVITY MATERIAL* - SEALANT — MIN 1/2 IN. (13 MM) THICKNESS OF FILL MATERIAL
APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL.
RECTORSEAL — METACAULK 1000, METACAULK 150+, BIOSTOP 500+, BIOSTOP 150+, FLAMESAFE
* INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR JURISDICTIONS EMPLOYING THE UL OR CUL CERTIFICATION (SUCH
AS CANADA), RESPECTIVELY.
NOT TO SCALE1 UL Detail W-J-2274
Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
LUMINAIRE REQUIREMENTS:
LED EXTERIOR / EGRESS SURFACE FIXTURE
FLUSH OR BACKBOX MOUNT
12-3/4
14-1/2
75-1/2
1. HOUSING - CAST ALUMINUM HOUSING.
2. FINISH - THERMOSET POWDER COAT FINISH.
3. LENS - CLEAR GLASS.
4. LAMPS - LEDs.
5. DRIVER - ELECTRONIC >90% POWER FACTOR.
6. ELECTRICAL - 120/277V
7. CERTIFICATION - UL LISTED AND LABELED.
8. INTEGRAL PHOTOCELL
NOT TO SCALE3 TYPE C DETAIL
LUMINAIRE REQUIREMENTS:
LED COMBO/EXIT SIGN
12"
NOMINAL
NOMINAL
8"
19"
NOMINAL
1. THERMOPLASTIC HOUSING, IMPACT-RESISTANT, SCRATCH-RESISTANT AND
CORROSION-PROOF. UL94V-0 FLAME RATING. UV-STABLE RESIN. RUGGED UNIBODY HOUSING
SNAPS TOGETHER WITH NO ADDITIONAL FASTENERS. UNIVERSAL, DIRECTIONAL CHEVRON
INSERTS ARE EASILY REMOVED AND REINSERTED. LETTERS ARE 6" HIGH WITH 3/4" STROKE,
WITH 100 FT. VIEWING DISTANCE RATING BASED UPON UL924 STANDARD. LEDs MOUNTED ON
PRIMARY CIRCUIT BOARDS FOR SIGN ILLUMINATION. LOW-ENERGY LED LAMP IN SIGN
OPERATES IN NORMAL (AC INPUT) AND EMERGENCY (DC INPUT) MODES. LOW-PROFILE,
INTEGRATED TEST SWITCH/PILOT LIGHT. RED STATUS INDICATOR. UNIQUE TRACK-AND-SWIVEL
ARRANGEMENT PERMITS FULL RANGE OF DIRECTION OF LAMP HEAD ADJUSTMENT. TOOL-LESS
ACCESS FOR MAINTENANCE.
2. OPTICS - TWIN LED LAMP HEADS OPERATE IN EMERGENCY (DC INPUT) MODE WITH 12
SERIES-PARALLEL WHITE LEDS IN EACH HEAD.
3. ELECTRICAL - DUAL-VOLTAGE INPUT CAPABILITY (120/277V). CURRENT-LIMITING CHARGER.
SHORT-CIRCUIT PROTECTION. SINGLE MULTI-COLOR LED INDICATOR TO DISPLAY TWO-STATE
CHARGING, TEST ACTIVATION AND THREE-STATE DIAGNOSTIC TEST. TEST SWITCH.
SELF-DIAGNOSTIC TESTING FOR 30 SECONDS EVERY 30 DAYS, 30 MINUTES AT 180-DAY
INTERVAL, AND 90 MINUTES ANNUALLY. DIAGNOSTIC EVALUATION OF LED LIGHT SOURCE,
AC-TO-DC TRANSFER, CHARGING AND BATTERY CONDITION. BATTERY: SEALED,
MAINTENANCE-FREE NICKEL-CADMIUM BATTERY. DELIVERS 90-MINUTE CAPACITY TO
EMERGENCY LAMPS.
4. INSTALLATION - TOP, END OR BACK MOUNTING. HOUSING SNAPS TO CANOPY WITH
POSITIVE-LOCKING TABS. CAM LOCKING PIN SECURES HOUSING TO CANOPY.
5. LISTINGS - UL DAMP LOCATION LISTED STANDARD 50°-104°F (10°-40°C). MEETS UL 924, NFPA
101 (CURRENT LIFE SAFETY CODE), NEC AND OSHA ILLUMINATION STANDARDS.
NOT TO SCALE6 TYPE X DETAIL
WALL-MOUNTED LED AREA FIXTURE
(PER ANSI/IEEE C62.41.2)
DRIVER IS MOUNTED IN DIRECT CONTACT WITH THE CASTING. DIE-CAST DOOR FRAME FULLY
4000K, 70CRI
THD <20%, SERVICEABLE SURGE PROTECTION DEVICE MEETS A MINIMUM CATEGORY B
CERTIFICATION - LIGHT ENGINES ARE IP66 RATED, LUMINAIRE IS IP65 RATED,
LAMPS - LEDS, PERFORMANCE PACKAGE 10A700/40K, NOMINAL LUMENS 3,851 TO 4,028,
IT IS CONSISTANT WITH THE LEED AND GREEN GLOBES CRITERIA.
DIFFUSER - PRECISION-MOLDED CLEAR ACRYLIC LENS. ZERO UPLIGHT WHICH MEANS
LED DRIVER - (2) 700mA, CLASS 2 ELECTRONIC DRIVERS EACH WITH POWER FACTOR >90%, HOUSING - ONE-PIECE, DIE-CAST ALUMINUM HOUSING WITH INTEGRATED HEAT SINKS, LUMINAIRE REQUIREMENTS:
GASKET - ONE-PIECE, SOLID SILICONE GASKET TO KEEP OUT MOISTURE AND DUST.
GASKETED, ZINC-INFUSED 3 MIL THICK
THERMOSET POWER COAT FINISH.
UL LISTED SUITABLE FOR WET LOCATIONS WHEN MOUNTED WITH LENS DOWN, OPTION OF
UL LISTED SUITABLE FOR WET LOCATIONS WHEN MOUNTED WITH LENS UP.
NOT TO SCALE4 TYPE D DETAIL
OPTIONAL INTEGRAL PHOTOCELL.
DIRECT/INDIRECT RECESSED 2' X 2' LED
7.
LUMINAIRE REQUIREMENTS:
6.
5.
4.
3.
2.
1.
2.38
NOMINAL
24"
NOMINAL
CONSTRUCTION - COMPONENTS ARE DIE-FORMED FOR DIMENSIONAL CONSISTENCY AND PAINTED
AFTER FABRICATION WITH A POLYESTER POWDER PAINT FOR IMPROVED PERFORMANCE AND
PROTECTION. THE REFLECTOR IS FINISHED WITH A HIGH REFLECTIVE MATTE WHITE POWDER PAINT
FOR IMPROVED AESTHETICS AND INCREASED LIGHT DIFFUSION. END PLATES CONTAIN
EASY-TO-POSITION INTEGRAL T-BAR CLIPS FOR SECURELY ATTACHING THE LUMINAIRE TO THE T-GRID. FOR ADDITIONAL T-GRID SECURITY, OPTIONAL SCREW ON T-BAR CLIPS ARE AVAILABLE.
DIFFUSERS ARE EXTRUDED FROM IMPACT MODIFIED ACRYLIC FOR INCREASED DURABILITY. LED
BOARDS AND DRIVERS ARE ACCESSIBLE FROM THE PLENUM.
OPTICS - VOLUMETRIC ILLUMINATION IS ACHIEVED BY CREATING AN OPTIMAL MIX OF LIGHT TO WALLS, PARTITIONS AND VERTICAL AND HORIZONTAL WORK SURFACES - RENDERING THE INTERIOR SPACE, OBJECTS AND OCCUPANTS IN A MORE BALANCED, COMPLIMENTARY LUMINOUS ENVIRONMENT. HIGH PERFORMANCE EXTRUDED ACRYLIC DIFFUSERS CONCEAL LEDS AND EFFERENTLY DELIVER LIGHT IN A VOLUMETRIC DISTRIBUTION. FOUR DIFFUSER CHOICES AVAILABLE - CURVED AND SQUARE DESIGNS
WITH LINEAR PRISMS OR A SMOOTH FROSTED FINISH.
ELECTRICAL - LONG-LIFE LEDS, COUPLED WITH HIGH-EFFICENCY DRIVERS, PROVIDE SUPERIOR QUANTITY AND QUALITY OF ILLUMINATION FOR EXTENDED SERVICE LIFE. FIXTURE SHALL BE RATED TO
DELIVER L80 PERFORMANCE FOR 50,000 HOURS.
LED DRIVER - DRIVER DELIVERS FULL RANGE DIMMING FROM 0 - 10V CONTROL SIGNAL.
INSTALLATION - GRID INTERFACING ARRANGEMENT PROVIDES MOUNTING INTO STADARD 1" AND 9/16" TEE BAR OR SCREW SLOT GRIDS. 9/16" ALLOWS FIXTURE TRIM TO HANG LEVEL WITH ARCHITECTURAL
CEILING TILES. DRYWALL CEILING ADAPTORS AVAILABLE. SUITABLE FOR DAMP LOCATION.
LISTINGS - CSA CERTIFIED TO MEET US AND CANADIAN STANDARDS. PATENTS PENDING. DLC
CERTIFIED TEST TO LM80 STANDARDS.
SEE SCHEDULE FOR DELIVERED LUMEN PACKAGE, 4000K
NOT TO SCALE2 TYPE B DETAIL
LED SUSPENDED FIXTURE
NOT TO SCALE1 TYPE A DETAIL
LIGHTING FIXTURE SCHEDULE
MARK DESCRIPTION NOM. SIZE TEMP(oK) LAMPS VOLTS DELIVERED
LUMENS WATTS LENS COLOR MOUNTING
HEIGHT
BALLAST/
DRIVER REMARKS
INDUSTRIAL HIGH BAY 14" x 24" 4000 LED UNIV 12,000 87.5 N/A N/A 13'-0" LED DRIVER
A TYPE LED FIXTURE 0-10V
DIMMING
DIRECT / INDIRECT RECESSED 2'x4' 4000 LEDs 120 5,500 49 N/A N/A RECESSED LED DRIVER 5
B LED FIXTURE 0-10V
DIMMING
WALL MOUNTED EMERGENCY 7.5"x 4000 LEDs 120 700 NORMAL 24 N/A WHITE WALL MTD LED DRIVER 3,5,6,7,8 C FIXTURE WITH 90 MINUTE EM. 11"x 500 EM 12" ABOVE
BATTERY, FULL CUT OFF 3" DOOR
EXTERIOR WALL MOUNTED LED FIXTURE 16" x 9" 4000 LEDs UNIV 10,800 104 N/A WHITE 12'-0" AFF LED DRIVER 3,8
D TYPE 4 OPTICS
EMERGENCY LIGHTING UNIT 15"x4"x6" N/A LEDS 120 N/A 5 N/A WHITE 8'-6" AFF 3,6
E WITH 90 MINUTE EMERGENCY
BATTERY BACKUP, WET LOCATION
COMBINATION EXIT SIGN AND 19"x8" N/A LEDS 120 N/A 5 N/A WHITE REFER TO 6
X LIGHTING UNIT WITH 90 MINUTE DETAIL 1/E-1
EMERGENCY BATTERY
REMARKS:
1. BI-LEVEL SWITCHING 4. WIREGUARD 7. FINAL COLOR SELECTION BY ARCHITECT
2. DAMP LOCATION 5. LED REQUIRED SURGE PROTECTION 8. INTEGRAL PHOHTCELL
3. WET LOCATION 6. VERIFY FINAL MOUNTING HEIGHT WITH ARCHITECT 9. USER DEFINED
GENERAL NOTES:
A. THE CONTRACTOR SHALL VERIFY THE LEAD TIME OF ALL PRODUCTS SPECIFIED IN THIS SCHEDULE AT THE TIME OF PACKAGE QUOTE.
B. DURING THE BID PROCESS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER OF ANY DELIVERY/SCHEDULING ISSUES.
C. NO SUBSTITUTIONS WILL BE ALLOWED DUE TO THE LACK OF COORDINATION OF DELIVERY DATES AND CONSTRUCTION SCHEDULE AFTER BID.
D. ALL EXPEDITED EXPENSES SHALL BE THE RESPONSIBILITY OF THE CONTRACTORS.
E. FIXTURES TO BE INSTALLED IN CEILINGS, INDICATE ON THE ARCHITECTURAL PLANS AS HAVING INSULATION IN CONTACT WITH THE CEILING
SURFACE, SHALL BE IC RATED BY MANUFACTURER.
F. LIGHTING FIXTURES SHALL MEET THE AESTHETICS, DESCRIPTION AND SPECIFICATIONS, SUBSTITUTIONS SHALL INCLUDE PT. BY PT. CALCULATIONS.
G. LIGHTING FIXTURES, AS SPECIFIED, HAVE BEEN SO SELECTED TO ACHIEVE REQUIRED/DESIRED FOOTCANDLE LEVELS IN THEIR RESPECTIVE AREA.
HENCE SPECIFIC FIXTURE CHARACTERISTICS WHICH MAY CREATE PARTICULAR ILLUMINATION RESULTS ARE ESSENTIAL. ANY DEVIATIONS FROM SPECIFIED FIXTURES SHALL DEEM THE SUBMITTING AGENT AND CONTRACTORS RESPONSIBLE IN PROVIDINGSUCH DEVIATION FOR THE ARCHITECT/
ENGINEER AND OWNER TO MAKE AN INFORMED DECISION.
H. SUBSTITUTIONS ARE ACCEPTABLE AS LONG AS THEY ARE EQUAL TO THE FIXTURE SPECIFIED, UNLESS OTHERWISE NOTED THIS INCLUDES LENS, COLORS, REFLECTORS, PHOTOMETRICS, HOUSING MATERIAL, FINISHES, ETC. ALL
J. ALL EXIT AND EMERGENCY FIXTURES SHALL COMPLY WITH NCSBC STANDARDS AND HAVE AUTOMATIC TESTING DEVICES.
K. LED MODULES SHALL BE REPLACEABLE.
L. ELECTRICAL CONTRACTOR SHALL RECEIVE APPROVAL FOR ALL LIGHTING FIXTURES FROM ARCHITECT/OWNER PRIOR TO PURCHASE AND ROUGH-IN.
REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL RATINGS.
M. THE ABOVE FIXTURE TYPES ARE LISTED AS THE DESIGN BASIS. THE ACTUAL FIXTURES SUBMITTED SHALL BE MANUFACTURED IN THE UNITED STATES.
REVISED: AUGUST 2004 NL-67LIGHTING PLATE:
DECORATIVE EMERGENCY LIGHTING UNIT
ILLUMINATION STANDARDS. DAMP LOCATION 32°F TO 122°F (0°C TO 50°C) LISTED STANDARD.
HOUSING - INJECTION-MOLDED, FAME-RETARDANT, HIGH-IMPACT, THERMOPLASTIC HOUSING
WITH SNAP-FIT DESIGN COMPONENTS. TRACK AND SWIVEL ARRANGEMENT PERMITS FULL
OPTICS - TWO 1.8W LED LAMPS FOR EMERGENCY LIGHT.
ELECTRICAL - DUAL-VOLTAGE INPUT 120V OR 277V AC. EMERGENCY UNIT PROVIDED WITH
LISTINGS - UL LISTED. MEETS UL 924, NFPA 101, NFPA 70-NEC AND OSHA
LUMINAIRE REQUIREMENTS:
1.
3.
4.
2.
14"
NOMINAL
NOMINAL
4"MAX. DEPTH
3 3/4" NOMINAL
RANGE OF LAMP ADJUSTMENT.
TEST SWITCH, STATUS INDICATOR AND RECHARGEABLE BATTERY. MAINTENANCE-FREE
NICKEL-CADMIUM BATTERY, 90 MINUTES OF EMERGENCY POWER.
NOT TO SCALE5 TYPE E DETAIL
Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
ON BACKBOARD - PROTECTOR / BUILDING ENTRANCE (BEP), TMGB
PROPER BONDING & GROUNDING, CABLE MANAGEMENT AND SLACK ON LADDER RACK. LADDER
RACK SHOULD BE ANCHORED FROM COMM. RACK TO AT LEAST TWO WALLS.
TMGB
EGB
#1/0 AWG GREEN-
1"CND
EGB LOCATED AT PANEL MDP
11mm DIA (7/16 in) MOUNTING HOLES, TYPICAL
TYPICAL GROUND CONDUCTOR AND COMPRESSION
LUG, TYPICAL
#6 AWG GREEN TO EQUIPMENT RACK
BOLT TO WALL
STAND-OFF INSULATOR,
TYPICAL
PROVIDE PRE-DRILLED SPACES, QUANTITY AND
SIZES PER SPECIFICATIONS
100mm (4in)
16mm (5/8in) TYPICAL
29mm (1 1/8in) TYPICAL
GROUND BAR SHALL BE PER TIA-607,
13mm (1/2in)
25mm (1in)
8mm DIA (5/16 in) TYPICAL DIA
50mm (2 in)
#6 AWG GREEN TO
LADDER RACK
MOUNTING
BRACKET,
TYPICAL
#6 AWG GREEN TO CABLE
TRAY
ALL DATA CONDUITS SHALL BE
INSTALLED WITH AN INSULATING
BUSHING AT EACH END
NOT TO SCALE
1 TELECOMMUNICATION RISER NOT TO SCALE
2 TELECOMMUNICATIONS GROUND BAR (TMGB) DETAIL
#1/0 AWG GREEN-
1"CND TO SERVICE ENTRANCE
GROUND (EGB)
4'X 8' FIRE RETARDANT
PLYWOOD BACKBOARD
MDP-11
MDP-13
(X)6 PAIR COPPER
(X)PEDESTAL RP8-1
2 1/2" MINIMUM
M
I N
I M
U M
MACHINE SCREW WITH
ACORN NUT AND
LOCKWASHER, TYP.
PANEL DESIGNATION 1/4"
BLACK ENGRAVED LETTERS
SOURCE DESIGNATION 1/4"
BLACK ENGRAVED LETTERS
RATING DESIGNATION 1/4"
BLACK ENGRAVED LETTERS
VOLTAGE & PHASE
DESIGNATION 1/4" BLACK
ENGRAVED LETTERS
PANEL: "MDP"
VOLTAGE: 240120V, 1Ø, 3W
RATING: 200 AMPS
FEED: UTILITY TRANSFORMER
AT LOCATION: EAST OF BLDG. 3767
2 1/2" MINIMUM
PANEL DESIGNATION 1/4"
BLACK ENGRAVED LETTERS
FEED DESIGNATION 1/4"
BLACK ENGRAVED LETTERS
RATING DESIGNATION 1/2"
BLACK ENGRAVED LETTERS
VOLTAGE & PHASE
DESIGNATION 1/4" BLACK
ENGRAVED LETTERS
M
I N
I M
U M
MACHINE SCREW WITH
ACORN NUT AND
LOCKWASHER, TYP.
AT LOCATION 1/4" BLACK
ENGRAVED LETTERS
WHITE PLASTIC NAMEPLATE
WITH BLACK ENGRAVED
LETTERS
WHITE PLASTIC NAMEPLATE
WITH BLACK ENGRAVED
LETTERS
NOT TO SCALE
3 PANELBOARD NAMEPLATE DETAIL
NOT TO SCALE
4 TYPICAL EQUIPMENT NAMEPLATE DETAIL
AF-1APRIL 2015
GENERAL ARC FLASH WARNING LABEL
SKETCH DATE STYLE
NOTES:
1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO WARN OF ARC
FLASH HAZARDS.
2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE.
3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO QUALIFIED
PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE
EQUIPMENT.
4. THE SIZE OF THE LABEL SHALL BE MINIMUM:
EQUIPMENT TYPE HEIGHT WIDTH
INDOOR 2" 3"
OUTDOOR 3" 4.5"
5. A DOWNLOADABLE WINDOWS METAFILE IS AVAILABLE ON THE WHOLE BUILDING DESIGN GUIDE
WEBSITE (WWW.WDBG.ORG) FOR USE IN A LABEL MAKING MACHINE.
A. THE FILE IS LOCATED ON THE "NAVFAC CADD DETAILS" PAGE. TO NAVIGATE TO THIS
LOCATION, FOLLOW: HOME > DOCUMENTS & REFERENCES > CCB > CADD LIBRARY >
NAVFAC CADD RESOURCES > NAVFAC CADD DETAILS.
B. ALTERNATIVELY, TYPE IN THE FOLLOWING ADDRESS IN INTERNET EXPLORER:
HTTP://WWW.WBDG.ORG/CCB/BROWSE_CAT.PHP?C=232
WIDTH
H E
I G
H T
NOT TO SCALE
5 WARNING LABEL DETAIL
SERVICE EQUIPMENT
GROUND BAR
EQUIPMENT GROUND
CONDUCTORS SIZED PER
NEC 250-122
GROUNDING BUSHING ON
METALLIC CONDUITS,
TYPICAL
TO SERVICE EQUIPMENT
ENCLOSURES-SIZE PER NEC
250-102(C)(1)
JUMPER SIZED PER NEC
TABLE 250-102(C)(1)
BRAZED
CONNECTION
3/4" X 10' GROUND
ROD IN WELL W/
COVER.
10'-0"
(MIN.)
SYSTEM GROUND "DO NOT REMOVE"
#2/0 CU
CONDUCTORS PER NEC OR
AS SPECIFIED, WHICHEVER IS
LARGER
GROUNDING BUSHING
FOR METALLIC
RACEWAYS, TYPICAL
PANEL "MDP"
EQUIPMENT GROUND
BAR
1/4"x2"x LENGTH AS REQUIRED (12" MIN.), COPPER BAR SUPPORTED BY HEAVY DUTY
STANDOFF INSULATORS BOLTED TO WALL
BOLT, NUT & BELLEVILLE
WASHER, TYPICAL
BLACK LAMICORE LABEL, WHITE CORE,
TY-WRAPPED TO GROUND CONDUCTORS,
TYPICAL
CONDUCTORS PER NEC,
TYP.
TELE/COM
GND BAR
(TMGB)
NOT TO SCALE
6 SERVICE GROUND DETAIL
NOT TO SCALE
7 SERVICE EQUIPMENT GROUND BAR (EGB) DETAIL
CONDUIT AND GROUNDING
BUSHING
COMPRESSION LUG, TYPICAL
CONDUIT AND GROUNDING
BUSHING
Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
1/8" = 1'-0"
0 8' 16'4'
1 DEMOLITION FLOOR PLAN
PLAN
NORTH
S S
S
S
S
RECEPTACLES: CONTRACTOR MUST REMOVE DEVICE, BOX, CONDUIT, CONDUCTORS, FITTINGS ECT. IN
ENTIRETY TO SOURCE.
LIGHTING: CONTRACTOR MUST REMOVE DEVICE, BOX, CONDUIT, CONDUCTORS, FITTINGS, SWITCHES, ECT. IN
ENTIRETY TO SOURCE.
HVAC EQUIPMENT: CONTRACTOR MUST REMOVE BOX, CONDUIT, CONDUCTORS, FITTINGS, SWITCHES, ECT. IN
ENTIRETY TO SOURCE.
AIR COPMRESSOR: CONTRACTOR MUST REMOVE DISCONNECT SWITCH, BOX, CONDUIT, CONDUCTORS, FITTINGS, ECT. IN ENTIRETY TO SOURCE.
MAIN DISTRIBUTION PANEL: CONTRACTOR MUST REMOVE PANEL, DISTRIBUTION CONDUIT AND CONDUCTORS
AND FEED CONDUIT, WEATHERHEAD AND CONDUCTORS IN ENTIRETY. PROTECT OVERHEAD SECONDARY FOR
RECONNECTION.
DATA/COMM BACKBOARD: CONTRACTOR MUST REMOVE DATA/COMM SYSTEM COMPLETE TO SOURCE
INCLUDING BUT NOT LIMITED TO DEVICE PLATES, CABLES, CONDUIT, PATCH PANELS, FITTINGS ECT.
DATA/COMM OSP: CONTRACTOR SHALL REMOVE IN ENTIRTY TO PEDESTAL #M100/#31.
PUMP: CONTRACTOR MUST REMOVE DISCONNECT SWITCH, BOX, CONDUIT, CONDUCTORS, FITTINGS, ECT. IN
ENTIRETY TO SOURCE.
DEMOLITION KEYED NOTES
2 2 2 2 2
2 2 2 2 2
DEMOLITION NOTES
1. THE INTENTION OF THIS PROJECT IS TO DEMOLISH ALL ELECTRICAL DEVICES, WIRING, CONDUIT, SUPPORTS
AND ETC. IN BUILDING. ALL DEVICES MAY NOT BE SHOWN.
2. DEMOLITION SHALL BE PROVIDED BY THE CONTRACTOR AS DESCRIBED HEREIN AND AS SHOWN ON THE
CONTRACT DRAWINGS. GROSS DEMOLITION WILL BE PROVIDED BY THE GENERAL CONTRACTOR. IDENTIFY
ACTIVE UTILITIES, AND AT THE APPROPRIATE TIME, DISCONNECT AND CAP OFF SUCH UTILITIES AND PROVIDE
EXPERIENCED PERSONNEL ON SITE DURING GENERAL CONTRACTOR DEMOLITION OPERATIONS TO PERFORM
SUCH OPERATIONS AND RESOLVE ISSUES.
3. THE ELECTRICAL CONTRACTOR SHALL REVIEW THE ARCHITECTURAL, MECHANICAL, PLUMBING AND
ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR DEMOLITION REQUIREMENTS AND CARRY OUT HIS WORK
IN A COMPATIBLE AND COMPLEMENTARY MANNER. REMOVE ALL WIRING DEVICES, BOXES, FIXTURES, ABANDONED RACEWAYS, HANGARS, ETC., MADE OBSOLETE BY THESE ALTERATIONS AND AS SHOWN ON THE
ELECTRICAL DRAWINGS. ALL ITEMS TO BE REMOVED MAY NOT BE SHOWN, HOWEVER, THIS CONTRACTOR
SHALL REMOVE ANY ELECTRICAL WORK AS REQUIRED BY THE CONSTRUCTION OR AS DIRECTED BY THE
GOVERNMENT. SURVEY THE AFFECTED AREAS BEFORE SUBMITTING A BID AS ALL EXISTING CONDITIONS
CANNOT BE COMPLETELY DEPICTED ON THE DRAWINGS AND SOME UNUSUAL CONDITIONS MAY EXIST.
4. REMOVE EXISTING INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION.
5. VERIFY FIELD MEASUREMENTS AND CIRCUITING ARRANGEMENTS ARE AS SHOWN ON DRAWINGS.
6. VERIFY THAT ABANDONED WIRING AND EQUIPMENT SERVE ONLY ABANDONED FACILITIES.
7. DISCONNECT AND/OR DE-ENERGIZE ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS SCHEDULED
FOR REMOVAL.
8. EXISTING ELECTRICAL SERVICE: COORDINATE POWER OUTAGES WITH THE GOVERNMENT. MAINTAIN
EXISTING SYSTEMS IN SERVICE. OBTAIN PERMISSION FROM THE GOVERNMENT AT LEAST 24 HOURS BEFORE
PARTIALLY OR COMPLETELY DISABLING SYSTEM. MINIMIZE OUTAGE DURATION.
9. ENDS OF ALL CONDUITS TO REMAIN SHALL BE TIGHTLY PLUGGED TO EXCLUDE DUST AND MOISTURE WHILE
THE BUILDING IS UNDER RENOVATION.
10. SECURE ALL CIRCUITS, RACEWAYS, CABLE AND CONDUCTORS THAT, AS A RESULT FROM THIS
CONSTRUCTION, ARE ABANDONED OR UNUSED. REMOVE UNUSED EXPOSED CONDUIT AND WIRING BACK TO
POINT OF CONCEALMENT INCLUDING ABANDONED CONDUIT ABOVE ACCESSIBLE CEILINGS. REMOVE
UNUSED WIRING IN CONCEALED CONDUITS BACK TO SOURCE OR NEAREST POINT OF USAGE. BLANK
ABANDONED KNOCKOUTS IN REMAINING BOXES. INSTALL BLANK PLATES FOR ALL UNUSED OUTLETS THAT
WILL REMAIN AS A RESULT OF THIS CONSTRUCTION. ALL SUCH WORK SHALL BE IN STRICT ACCORDANCE
WITH ALL APPLICABLE CODES AND ORDINANCES.
11. TRACE OUT EXISTING WIRING THAT IS TO BE RELOCATED OR REMOVED AND PERFORM THE RELOCATION OR
REMOVAL WORK AS REQUIRED FOR A COMPLETE OPERATING AND SAFE SYSTEM.
12. DELIVER ALL REMOVED AND SALVAGED LIGHTING FIXTURES, WIRING DEVICES, FIRE ALARM DEVICES, SPEAKERS, ETC., TO THE OWNER, OR AT THE OWNER'S OPTION, DISPOSE OF PROPERLY OFF SITE IN
ACCORDANCE WITH LOCAL, STATE AND FEDERAL ENVIRONMENTAL REGULATIONS. FEES ASSOCIATED WITH
DISPOSAL SHALL BE INCLUDED IN THE CONTRACTOR'S BASE BID.
13. COORDINATE WITH THE OTHER TRADES, PRIOR TO BID, AND INCLUDE IN THE BASE BID THE ELECTRICAL
DISCONNECTION OF ANY EQUIPMENT BEING DEMOLISHED, EVEN IF NOT EXPLICITLY SHOWN. UNLESS NOTED
OTHERWISE, REMOVE ALL DEMOLISHED EQUIPMENT FROM THE PROPERTY AND IDENTIFIED IN THE
ELECTRICAL DRAWINGS.
14. THESE DRAWINGS ARE COMPILED BY THE ARCHITECT/ENGINEER FROM THE GOVERNMENT'S RECORD
DRAWINGS AND LIMITED FIELD VERIFICATION OF EXISTING CONDITIONS FOR THE PURPOSE OF INDICATING
THE WORK REQUIRED AND ARE BELIEVED TO BE CORRECT. NOTWITHSTANDING, THE CONTRACTOR SHALL
VERIFY ALL CIRCUITS, WIRING, CONDUIT, DIMENSIONS, POINTS OF ACCESS AND ALL FIELD CONDITIONS
AFFECTING HIS WORK. BEGINNING OF DEMOLITION MEANS THE CONTRACTOR ACCEPTS EXISTING
CONDITIONS.
15. THE CONTRACTOR IS RESPONSIBLE FOR DISPOSAL OF ALL LAMPS CONTAINING MERCURY IN A LINED
LANDFILL IN ACCORDANCE WITH NC GEN STATUTE 309.10M.
16. SEE GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.
t t t t t t t t t t t t t t t t t
S
D 3
S
D 3
S
D 3
S
D
OS OS
OS
OS
OS
OS
OS
OS
OS
OS
S
S
S
MDP-2
MDP-4
MDP-6 MDP-8
PANEL MDP
S
MDP-26
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
1/8" = 1'-0"
0 8' 16'4'
1 LIGHTING PLAN
PLAN
NORTH
X
X
XX
XX
A A A A A A A
A A A
A A A
E
E
CC
CCCC
A A AA A
A
A A AA A
A
A
X
C
E
E
E
E
E
D D
D
D
14.1
17.8
22.2
26.8
32.1
37.0
39.1
39.2
37.3
32.8
27.8
23.1
18.2
13.6
10.5
15.2
19.7
25.1
31.1
38.0
41.2
41.1
41.2
41.4
38.8
32.1
25.9
20.0
14.7
11.5
16.4
21.5
27.7
34.9
41.1
41.7
40.6
40.6
41.8
41.6
35.7
28.3
21.7
15.9
12.2
17.4
23.0
29.8
37.1
43.9
45.4
44.7
44.7
45.4
44.3
37.8
30.3
23.2
16.9
12.9
18.2
24.2
31.2
38.1
45.8
50.9
52.1
52.1
51.0
46.3
38.6
31.6
24.3
17.7
13.4
18.7
25.1
32.1
38.9
46.0
52.8
57.3
57.4
53.2
46.4
39.3
32.3
25.0
18.3
13.8
14.9
18.9
23.6
28.1
33.1
38.0
40.1
40.3
39.2
35.4
30.1
25.6
21.5
18.5
17.2
21.6
26.5
33.2
40.1
47.7
54.2
57.1
57.2
54.5
48.1
40.4
33.1
25.6
18.6
14.0
15.3
20.4
26.4
32.7
39.8
43.2
42.9
42.7
43.0
41.4
34.9
28.4
23.2
20.4
20.0
22.1
27.2
34.0
41.7
49.7
53.2
53.3
53.3
53.2
50.0
42.0
33.9
26.0
18.9
14.1
16.4
21.9
28.5
35.8
42.9
44.2
42.8
42.5
43.4
43.7
38.7
31.3
25.4
21.5
20.6
22.4
27.5
34.5
42.8
49.7
50.7
49.6
49.6
50.5
49.8
43.1
34.4
26.2
19.0
14.1
17.2
23.2
30.2
37.5
45.1
48.2
47.6
47.5
47.8
47.0
40.7
33.3
27.1
22.5
21.2
22.8
27.8
34.7
42.7
50.4
52.6
52.1
52.0
52.4
50.6
43.0
34.5
26.4
19.1
14.2
17.9
24.1
31.3
38.3
45.9
52.3
54.5
54.7
53.5
49.0
41.4
34.5
28.2
23.4
21.8
23.3
28.0
34.7
41.9
50.0
55.7
57.3
57.3
55.7
50.3
42.1
34.4
26.4
19.2
14.3
18.4
24.7
31.9
38.9
46.1
53.1
58.4
59.4
55.7
49.1
42.0
35.3
28.8
24.0
22.3
23.6
28.1
34.6
41.6
48.8
55.7
60.4
60.5
56.0
49.1
41.6
34.2
26.4
19.3
14.5
18.7
25.2
32.7
40.1
47.9
54.9
57.9
58.3
56.6
51.3
43.4
36.2
29.5
24.4
22.5
23.8
28.3
35.0
42.2
50.1
56.3
58.7
58.8
56.5
50.4
42.3
34.6
26.6
19.4
14.5
18.8
25.6
33.4
41.5
49.9
54.1
54.2
54.3
54.4
52.6
45.3
37.1
30.0
24.6
22.6
23.8
28.6
35.5
43.4
51.4
54.4
54.3
54.3
54.3
51.6
43.5
35.1
26.9
19.4
14.4
18.9
25.7
33.8
42.3
50.2
52.2
51.3
51.1
51.9
51.8
46.3
37.7
30.2
24.7
22.7
23.8
28.7
35.7
44.1
51.0
52.1
51.1
51.0
51.8
51.0
44.3
35.4
26.9
19.5
14.5
19.0
25.8
33.7
41.9
50.5
54.5
54.4
54.5
54.6
53.1
45.8
37.5
30.3
24.9
22.8
24.0
28.7
35.6
43.6
51.6
54.5
54.3
54.2
54.3
51.8
43.8
35.3
27.0
19.6
14.5
18.9
25.6
33.3
40.9
49.2
56.2
59.4
59.8
58.1
52.7
44.5
37.0
30.1
24.8
22.8
24.0
28.5
35.1
42.4
50.6
57.0
59.5
59.5
57.2
51.0
42.6
34.8
26.8
19.5
14.6
18.7
25.2
32.7
40.0
47.7
55.5
61.0
61.9
58.4
51.2
43.4
36.3
29.5
24.4
22.5
23.6
27.9
34.4
41.4
49.0
56.6
61.3
61.5
57.1
49.5
41.6
34.2
26.3
19.2
14.4
18.2
24.5
31.8
39.1
47.3
53.3
55.0
55.3
54.5
50.7
42.8
35.4
28.8
23.7
21.7
22.8
27.1
33.5
40.6
48.6
53.7
55.0
55.0
53.9
49.2
40.9
33.3
25.7
18.7
14.0
17.3
23.3
30.4
37.9
45.6
48.2
47.6
47.6
48.1
47.8
41.9
34.1
27.5
22.5
20.6
21.5
25.8
31.9
39.3
46.4
47.9
47.3
47.4
48.0
46.9
40.0
32.1
24.5
17.8
13.4
16.3
21.7
28.2
35.4
42.9
45.0
44.0
44.0
44.8
45.0
39.7
32.1
25.7
21.1
19.3
20.1
24.0
29.6
36.8
43.5
44.6
43.7
43.8
44.7
44.2
37.9
30.2
23.0
16.7
12.6
15.3
20.0
25.6
31.5
38.7
43.5
44.0
44.0
44.1
42.0
35.7
29.4
23.9
19.8
18.1
18.8
22.0
26.8
32.7
39.6
43.3
43.7
43.7
43.8
40.8
34.1
27.8
21.5
15.6
11.7
33.3
38.0
41.0
42.9
43.4
42.6
42.3
42.3
42.5
43.2
42.7
40.8
37.7
33.2
38.8
41.4
42.3
44.4
47.4
48.6
47.4
47.4
48.5
47.3
44.2
42.1
41.0
38.1
40.5
40.0
39.4
41.7
46.3
50.7
50.4
50.4
50.6
46.2
41.5
39.1
39.5
39.7
40.5
40.0
39.3
41.6
46.2
50.7
50.5
50.5
50.6
46.2
41.4
39.0
39.4
39.7
39.0
41.5
42.3
44.4
47.5
48.8
47.6
47.6
48.7
47.4
44.2
42.0
41.0
38.3
33.6
38.3
41.3
43.1
43.7
43.0
42.6
42.6
42.8
43.6
43.0
41.1
38.0
33.5
17.8
23.0
28.9
35.2
42.4
45.3
44.6
44.6
45.1
44.6
38.8
32.1
26.7
22.8
21.3
22.0
25.4
30.3
36.4
43.1
45.2
44.5
44.5
45.2
44.1
37.7
31.0
24.8
19.1
14.5
18.5
24.3
31.0
38.5
45.8
47.5
46.5
46.3
47.2
47.5
42.6
34.9
28.6
24.0
22.3
23.1
26.9
32.6
39.7
46.3
47.2
46.2
46.2
47.4
47.2
41.4
33.5
26.3
19.8
14.7
19.3
25.6
32.8
40.2
48.3
52.4
52.6
52.7
52.7
51.0
44.1
36.5
30.0
25.0
23.0
24.0
28.2
34.2
41.3
49.0
52.4
52.5
52.5
52.6
50.3
42.8
35.1
27.6
20.7
15.3
19.9
26.4
33.8
41.0
48.7
55.7
58.9
59.3
57.6
52.3
44.5
37.4
30.9
25.8
23.9
24.8
29.0
35.2
42.0
49.7
56.2
58.9
59.1
57.0
51.2
43.2
36.0
28.4
21.4
15.8
20.3
27.0
34.5
41.7
49.1
56.2
61.7
62.8
59.0
52.3
45.1
38.1
31.4
26.4
24.4
25.4
29.6
35.9
42.7
50.0
57.0
62.0
62.4
58.1
51.2
43.8
36.6
29.0
21.9
16.2
20.6
27.5
35.3
42.9
51.1
57.8
60.2
60.5
59.3
54.5
46.5
39.0
32.0
26.7
24.6
25.7
30.2
36.8
44.0
52.1
58.2
60.2
60.3
58.8
53.4
45.1
37.4
29.5
22.2
16.3
20.8
27.8
35.9
44.2
52.6
56.2
55.9
56.0
56.2
55.1
48.2
39.8
32.4
26.9
24.7
25.8
30.5
37.4
45.5
53.4
56.2
55.8
55.8
56.1
54.3
46.7
38.2
29.9
22.3
16.3
20.8
27.9
36.1
44.7
52.8
54.8
54.0
53.8
54.5
54.4
48.8
40.1
32.6
27.0
24.8
25.9
30.7
37.7
46.0
53.3
54.7
53.8
53.7
54.5
53.8
47.3
38.4
30.0
22.4
16.4
20.9
28.0
36.0
44.1
52.8
57.6
58.0
58.1
58.0
55.6
48.0
39.8
32.6
27.1
24.9
26.0
30.7
37.5
45.3
53.7
57.7
58.0
57.9
57.8
54.7
46.5
38.2
30.1
22.5
16.5
20.8
27.7
35.5
43.1
51.1
58.6
62.7
63.3
60.8
54.7
46.6
39.2
32.2
27.0
24.9
26.0
30.4
37.0
44.2
52.2
59.3
62.9
63.1
60.1
53.5
45.3
37.6
29.7
22.3
16.4
20.5
27.2
34.8
42.2
49.9
57.6
62.4
63.3
60.2
53.5
45.6
38.5
31.7
26.5
24.6
25.6
29.8
36.3
43.2
50.9
58.3
62.7
63.0
59.4
52.3
44.3
37.0
29.2
22.0
16.2
19.9
26.5
33.9
41.3
49.5
54.8
55.8
55.9
55.6
52.6
45.0
37.5
30.9
25.8
23.7
24.7
29.0
35.3
42.3
50.4
54.9
55.7
55.8
55.3
51.7
43.7
36.0
28.5
21.4
15.8
19.1
25.2
32.3
39.9
47.4
49.4
48.6
48.5
49.2
49.2
43.9
36.1
29.6
24.7
22.7
23.6
27.7
33.7
41.0
47.8
49.1
48.3
48.4
49.2
48.8
42.6
34.6
27.2
20.4
15.1
18.1
23.6
30.1
37.1
44.6
47.1
46.2
46.1
46.8
46.8
41.2
33.9
27.9
23.5
21.7
22.5
26.1
31.5
38.3
45.1
46.7
45.9
46.0
46.9
46.3
40.1
32.5
25.6
19.3
14.4
17.4
22.2
27.6
33.2
39.8
44.6
45.5
45.5
45.3
42.6
36.4
30.8
25.8
22.1
20.7
21.4
24.4
28.9
34.2
40.5
44.6
45.4
45.4
45.1
41.9
35.5
29.7
23.9
18.5
14.2
15.5
19.1
23.0
26.8
30.5
33.7
36.2
36.8
35.2
32.3
29.0
25.4
22.0
19.4
18.2
18.6
20.7
23.9
27.4
31.0
34.0
36.3
36.6
34.8
31.8
28.3
24.6
20.6
16.8
13.4
16.1
20.6
25.8
30.9
36.6
41.9
44.3
44.6
43.7
39.9
34.4
29.4
24.8
21.3
19.7
20.2
22.9
27.2
32.0
37.4
42.3
44.2
44.5
43.3
39.1
33.4
28.1
22.7
17.6
13.5
17.4
22.8
29.0
35.4
42.6
46.5
46.4
46.4
46.7
45.7
39.7
33.1
27.4
23.1
21.2
21.9
25.3
30.5
36.6
43.4
46.5
46.2
46.3
46.6
44.9
38.4
31.6
25.1
19.1
14.3
18.7
24.8
31.8
39.1
46.5
48.4
47.4
47.2
48.0
48.4
43.7
36.1
29.7
24.8
22.7
23.4
27.4
33.2
40.3
47.1
48.3
47.2
47.1
48.0
47.8
42.3
34.5
27.3
20.6
15.2
19.8
26.4
33.9
41.6
49.9
54.0
54.0
54.1
54.1
53.0
46.3
38.3
31.5
26.2
24.0
24.8
29.1
35.4
42.8
50.8
54.0
53.9
53.9
53.9
52.2
44.8
36.7
29.0
21.8
16.0
20.4
27.3
35.3
43.1
51.7
59.8
64.0
64.6
62.5
56.4
47.6
39.8
32.7
27.2
24.9
25.8
30.1
36.8
44.2
52.9
60.5
64.1
64.4
61.8
55.1
46.1
38.2
30.1
22.5
16.4
20.7
27.7
35.9
43.8
52.6
60.8
65.1
65.8
63.7
57.4
48.3
40.4
33.1
27.5
25.2
26.1
30.5
37.4
44.9
53.7
61.5
65.3
65.6
62.9
56.0
46.9
38.8
30.6
22.8
16.6
20.6
27.6
35.6
43.8
52.7
57.1
57.2
57.4
57.3
55.9
48.7
40.1
32.9
27.2
24.9
25.8
30.3
37.1
45.0
53.5
57.1
57.1
57.2
57.1
55.0
47.2
38.5
30.4
22.7
16.5
20.2
27.0
34.9
43.3
51.4
53.7
52.8
52.5
53.3
53.4
48.1
39.5
32.1
26.6
24.2
25.1
29.7
36.4
44.5
52.0
53.6
52.6
52.4
53.2
52.8
46.6
37.9
29.7
22.2
16.2
19.6
26.2
33.9
41.7
49.9
54.3
54.4
54.4
54.5
53.0
46.2
38.3
31.2
25.8
23.5
24.4
28.7
35.3
42.8
50.7
54.3
54.3
54.2
54.3
52.2
44.8
36.7
28.8
21.5
15.8
19.1
25.4
32.6
39.6
46.6
53.0
55.9
56.3
54.9
50.3
43.3
36.6
30.1
25.0
22.9
23.8
27.8
33.9
40.5
47.4
53.5
55.9
56.0
54.4
49.2
42.1
35.1
27.8
20.9
15.4
18.8
24.7
31.3
37.7
43.8
48.9
52.7
53.5
51.2
46.7
41.0
35.0
29.1
24.4
22.5
23.2
27.0
32.6
38.5
44.4
49.4
52.8
53.3
50.5
45.7
39.9
33.6
26.9
20.5
15.2
18.5
24.4
30.9
37.2
43.1
48.7
52.6
53.4
51.1
46.1
40.4
34.5
28.7
24.1
22.1
22.9
26.6
32.1
38.0
43.8
49.2
52.8
53.2
50.4
45.2
39.3
33.2
26.5
20.2
15.1
18.4
24.3
31.1
37.6
44.6
50.3
52.3
52.4
51.7
48.1
41.2
34.8
28.7
23.9
21.9
22.7
26.5
32.3
38.5
45.4
50.7
52.2
52.3
51.3
47.0
40.0
33.4
26.5
20.1
14.9
18.4
24.2
31.0
38.2
45.8
48.8
47.8
47.7
48.3
48.3
42.5
34.9
28.6
23.8
21.9
22.6
26.5
32.3
39.3
46.5
48.6
47.6
47.5
48.2
47.6
41.1
33.5
26.4
20.0
14.9
18.4
24.2
30.9
38.3
45.8
47.2
45.6
45.2
46.4
47.3
42.7
34.9
28.5
23.8
21.9
22.6
26.4
32.1
39.4
46.2
47.0
45.3
45.1
46.4
46.8
41.3
33.4
26.3
20.0
14.9
18.3
24.1
30.8
37.7
45.2
49.2
49.1
49.0
49.3
48.0
41.7
34.6
28.4
23.7
21.8
22.5
26.3
32.0
38.6
45.9
49.2
48.9
48.8
49.1
47.2
40.4
33.2
26.3
19.9
14.9
18.2
23.9
30.4
36.6
42.9
49.0
52.0
52.4
51.0
46.4
39.9
34.0
28.2
23.6
21.6
22.5
26.1
31.6
37.4
43.7
49.5
52.0
52.2
50.4
45.3
38.8
32.7
26.1
19.8
14.8
18.2
23.8
30.0
35.8
41.4
46.3
49.9
50.8
48.4
44.1
38.8
33.3
27.9
23.5
21.7
22.4
25.9
31.1
36.6
42.0
46.7
50.1
50.5
47.7
43.2
37.8
32.0
25.8
19.7
14.8
18.2
23.8
30.1
36.1
41.8
47.3
51.2
51.9
49.7
44.7
39.1
33.5
27.9
23.5
21.7
22.4
25.9
31.3
36.8
42.5
47.8
51.3
51.7
49.0
43.8
38.1
32.2
25.9
19.8
14.8
18.3
24.0
30.6
37.1
43.9
49.5
51.3
51.4
50.8
47.4
40.6
34.2
28.3
23.6
21.7
22.5
26.2
31.8
37.9
44.8
49.8
51.2
51.3
50.4
46.4
39.4
32.9
26.2
19.9
14.8
18.3
24.1
30.9
38.0
45.5
48.3
47.3
47.1
47.8
47.9
42.2
34.7
28.4
23.7
21.8
22.5
26.3
32.1
39.0
46.2
48.1
47.1
47.0
47.7
47.2
40.9
33.3
26.3
20.0
14.9
18.4
24.2
30.9
38.3
45.7
47.2
45.6
45.2
46.4
47.3
42.6
34.8
28.5
23.8
21.9
22.6
26.4
32.1
39.3
46.2
47.0
45.4
45.1
46.4
46.8
41.3
33.4
26.3
20.0
14.9
18.3
24.1
30.9
37.8
45.3
49.5
49.5
49.4
49.6
48.2
41.8
34.7
28.5
23.8
21.8
22.6
26.4
32.1
38.7
46.1
49.5
49.4
49.2
49.4
47.4
40.5
33.3
26.4
20.0
14.9
18.3
24.1
30.7
37.0
43.3
49.5
52.6
53.0
51.5
46.8
40.3
34.3
28.4
23.8
21.7
22.6
26.3
31.9
37.8
44.1
49.9
52.6
52.8
50.9
45.7
39.2
33.0
26.3
20.0
14.9
18.4
24.1
30.5
36.6
42.3
47.3
50.9
51.8
49.4
45.1
39.7
34.0
28.3
23.8
22.0
22.7
26.3
31.7
37.3
43.0
47.7
51.1
51.5
48.7
44.2
38.6
32.7
26.3
20.0
15.0
18.6
24.4
31.1
37.4
43.4
49.2
53.1
53.9
51.6
46.5
40.6
34.7
28.8
24.1
22.2
23.0
26.7
32.3
38.2
44.1
49.7
53.2
53.6
50.9
45.5
39.5
33.3
26.6
20.3
15.1
18.9
25.0
32.1
39.1
46.5
52.2
53.9
54.0
53.5
50.1
42.9
36.0
29.6
24.6
22.5
23.4
27.3
33.4
40.0
47.4
52.5
53.8
53.8
53.1
49.0
41.7
34.6
27.3
20.6
15.3
19.2
25.6
33.0
40.8
48.8
51.8
50.9
50.8
51.4
51.3
45.3
37.3
30.3
25.1
23.0
23.8
28.0
34.3
41.9
49.5
51.6
50.7
50.7
51.3
50.6
43.9
35.7
28.0
21.0
15.5
19.6
26.1
33.7
41.7
49.6
51.8
50.7
50.4
51.2
51.5
46.3
38.0
31.0
25.7
23.5
24.3
28.6
35.0
42.8
50.1
51.6
50.5
50.3
51.2
50.9
44.9
36.5
28.6
21.5
15.8
19.9
26.5
34.1
41.6
49.9
55.2
56.0
56.1
55.9
53.4
46.0
38.2
31.4
26.1
23.9
24.7
29.0
35.4
42.7
50.8
55.4
55.9
55.9
55.6
52.5
44.6
36.7
29.1
21.8
16.0
19.9
26.4
34.0
41.2
48.8
56.5
61.3
62.2
59.5
53.0
45.2
38.1
31.4
26.2
24.1
24.9
29.0
35.3
42.1
49.8
57.2
61.5
61.9
58.6
51.8
43.9
36.6
29.0
21.8
16.0
19.6
26.1
33.5
40.6
48.2
55.6
59.9
60.7
58.3
52.4
44.6
37.6
31.0
25.9
23.8
24.6
28.6
34.9
41.6
49.2
56.2
60.0
60.4
57.6
51.2
43.3
36.1
28.7
21.6
15.9
19.2
25.4
32.6
39.7
47.6
52.3
52.7
52.8
52.8
51.0
44.1
36.7
30.3
25.2
23.1
23.9
27.9
33.9
40.8
48.5
52.4
52.6
52.6
52.6
50.1
42.7
35.2
27.9
21.0
15.5
18.3
24.1
30.9
38.1
45.3
47.0
45.9
45.7
46.6
47.2
42.7
35.2
28.9
24.1
22.1
22.8
26.6
32.2
39.2
45.8
46.8
45.7
45.6
46.6
46.7
41.3
33.6
26.6
20.1
14.9
17.2
22.4
28.5
35.0
42.2
45.2
44.5
44.5
45.1
45.1
39.7
32.8
27.0
22.7
20.9
21.5
24.9
30.0
36.2
43.0
45.1
44.3
44.3
45.0
44.5
38.4
31.3
24.8
18.8
14.1
16.0
20.4
25.6
30.9
37.0
42.4
44.1
44.3
44.0
41.0
35.0
29.7
24.9
21.2
19.6
20.2
22.9
27.2
32.1
38.1
42.7
44.0
44.2
43.7
40.1
34.0
28.4
22.8
17.5
13.3
15.5
19.1
23.1
27.0
31.1
35.1
38.1
38.8
37.0
33.6
29.7
26.0
22.4
19.6
18.4
18.8
20.9
24.3
27.9
31.7
35.5
38.2
38.6
36.6
33.0
29.0
25.1
20.9
16.8
13.2
1/8" = 1'-0"
0 8' 16'4'
1 PHOTOMETRIC PLAN
PLAN
NORTH
A t t t t t t t t t t t t t t t t
S
M
PV01
PV03
GUH1
GUH2
GUH3
EUH1
PV02
PV04
S
M
S
O
S
M
S
O
S
O
M M MM
S
M
S
M
S
M
S
M
S
M
GUH4
S
M
DAMPER
FOR L2
DAMPER
FOR L3
DAMPER
FOR L4
DAMPER
FOR L1
MDP-3
MDP-1
MDP-39,41
MDP-10
MDP-7
MDP-5
MDP-12
MDP-14
MDP-16
2#12 & 1#12G, 3/4"CND
2#12 & 1#12G, 3/4"CND
2#12 & 1#12G, 3/4"CND
2#12 & 1#12G, 3/4"CND
2#12 & 1#12G, 3/4"CND
2#12 & 1#12G, 3/4"CND
2#12 & 1#12G, 3/4"CND
2#12 & 1#12G, 3/4"CND
2#12 & 1#12G, 3/4"CND
(INTERLOCK)
2#12 & 1#12G, 3/4"CND
(INTERLOCK)
2#12 & 1#12G, 3/4"CND
(INTERLOCK)
1 1 1
PANEL MDP
MDP-9
MDP-15
MDP-17
MDP-19
MDP-21
MDP-18
MDP-20
MDP-22
WP,GFIWP,GFI
WP,GFI WP,GFI
+54
+54
+54
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
1/8" = 1'-0"
0 8' 16'4'
1 POWER PLAN
PLAN
NORTH
DEMOLITION KEYED NOTES
ALL DEVICE IN ROOMS R102, R103, & R104 ARE SURFACE MOUNTED UNLESS NOTED.
E-4
EUH1 DISC.
30/2/1
W/20AF
Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
EXISTING O.H.
PRIMARY
EXISTING POLE SHALL
REMAIN
'NAME'
'WARNING'
ROOF
(X)PANEL A
208/120V, 3Ø, 4W
DEMOLITION KEYED NOTES
PANELBOARD: REMOVE SERVICE ENTRANCE CONDUCTORS AND WEATHERHEAD. REMOVE SECONDARY
FROM POLE MOUNTED TRANSFORMER.
METER: REMOVE EXISTING METER, CONDUIT AND CONDUCTORS TO CTs.
EXISTING O.H.
PRIMARY
EXISTING POLE,
TRANSFORMERS AND
METERING SHALL
REMAIN
'NAME'
'WARNING'
ROOF
PANEL MDP
240/120V, 1Ø, 3W
LOAD SUMMARY
VOLTAGE PHASE
240 1
LARGEST MOTOR APPROX. AMPS 2 AMPS
LARGEST MOTOR APPROX. AMPS x .25 1 AMPS
HVAC
EUH1
3,480
VA
GUH01 384 VA
GUH02 384 VA
GUH03 384 VA
GUH04 384 VA
PV01 420 VA
PV02 420 VA
PV03 420 VA
PV04 420 VA
SUB-TOTAL HVAC DEMAND
6,696
VA
SUB-TOTAL HVAC DEMAND 28 AMPS
EQUIPMENT
ADD FOR LARGEST MOTOR 1 AMPS
TOTAL EQUIPMENT DEMAND
1 AMPS
LIGHTING
LIGHTS (INTERIOR, BASED ON NEC 220.12)
2,317
VA
LIGHTS (EXTERIOR)
584 VA
TOTAL LIGHTING LOAD
2,901
VA
LIGHTING LOAD x 1.25
3,626
VA
TOTAL DEMAND FOR LIGHTING 15 AMPS
RECEPTACLES
RECEPTACLES
6,840
VA
RECEPTACLES
6,840
VA
TOTAL DEMAND FOR RECEPTACLE/POWER PANELS
6,840
VA
TOTAL DEMAND FOR RECEPTACLE/POWER PANELS 29 AMPS
TOTAL DEMAND BUILDING AMPS 72 AMPS
TOTAL DEMAND BUILDING AMPS
17,282
VA
TOTAL BUILDING CONNECTED LOAD
16,437
VA
PANEL MDP SERVICE EQUIPMENT LISTED
TYPE: NEMA 1 240 120
V, PH,
3 WIRE PROVIDE IF XX EQUIP. GROUND BUS
BOLT-ON MOUNT: SURFACE CHECKED: XX NEUTRAL BUS
DOOR-IN-DOOR WITH-IN HINGED TRIM FRONT COVER FEED: TOP GUTTER TAPS
SUB-FEED LUGS
LOAD CKT CKT CKT CKT LOAD
LOAD SERVED VA BKR # A B # BKR VA LOAD SERVED
PV01 420 15/1 1 591 2 20/1 171 LTGS: R101
PV02 420 15/1 3
1,081
4 20/1 661 LTGS: R102
PV03 420 15/1 5 993 6 20/1 573 LTGS: R103
PV04 420 15/1 7
1,518
8 20/1 1,098
LTGS: R104
RCP: RM R101 720 20/1 9
1,104
10 20/1 384 GUH1
RCP: TELECOMM BACKBOARD 360 20/1 11 744 12 20/1 384 GUH2
RCP: TELECOMM BACKBOARD 360 20/1 13 744 14 20/1 384 GUH3
RCP: RM R102 720 20/1 15
1,104
16 20/1 384 GUH4
RCP: RM R102 720 20/1 17
1,440
18 20/1 720 RCP: RM 104
RCP: RM R103 720 20/1 19
1,620
20 20/1 900 RCP: RM 104
RCP: RM R103 720 20/1 21
1,620
22 20/1 900 RCP: RM 104
SPARE 20/1 23 300 24 20/1 300 FMCP
SPARE 20/1 25 416 26 20/1 416 LTGS: EXTERIOR
SPARE 20/1 27 28 20/1 SPARE
SPARE 20/1 29 30 20/1 SPARE
SPARE 20/1 31 32 20/1 SPARE
SPARE 20/1 33 34 20/1 SPARE
SPARE 20/1 35 36 20/1 SPARE
SPARE 20/1 37 38 20/1 SPARE
EUH-1
1,740
20/2 39 1,740
40 30/2 SPD
| 1,740 |
1,740
NOTE:
8,648 8,107
TOTAL VOLT AMPS 200
A. BUS (COPPER)
1. HVAC & REFRIGERATION EQUIPMENT SHALL USE TYPE HACR BREAKERS. 72 68 CONN. AMPS 200 A. MAIN CIRCUIT BREAKER
2. PROVIDE CIRCUIT BREAKER LOCKING DEVICE FOR FACU ALONG WITH
IDENTIFYING CIRCUIT BREAKER IN ACCORDANCE WITH NEC 760.41
22 KAIC MIN.
3#3/0, 2"CND
3#3/0
E-4
GROUND PER
NEC 250
SPD
NOTE:
1. SURGE PROTECTION DEVICE (SPD) SHALL BE MOUNTED TO KEEP
LEADS AS SHORT AS POSSIBLE.
2. SPD SHOWN WITH A 30A, 3 POLE BREAKER IN PANELBOARD BEING
PROTECTED, MAKE CONNECTION WITH 4#10AWG CONDUCTORS,
IF SPD MANUFACTURER RECOMMENDS LARGER BREAKER OR
LEADS, PROVIDE AT NO ADDITIONAL COST TO OWNER.
E-4
EGB
#4 COPPER
GROUND
NOTE:
1. SHORT CIRCUIT CALCULATION COMPLETED ON 12/20/2019. BASED ON A 50KVA
POLE MOUNTED TRANSFORMER @ 1.5% IMPEDANCE, AND 1.83 X/R. VERIFY
ACTUAL PARAMETERS WITH UTILITY COMPANY AND EQUIPMENT
CHARACTERISTICS PRIOR TO INSTALLATION
2.…