Replace NFPC Compound Perimeter Fencing 1585933 Replace NFPC B546 Perimeter Fencing 1599026
2.4 ACCESS CONTROL SYSTEM (ACS)
a. The ACS card credentials are Common Access Cards (CAC). CAC cards are provided by the Government.
b. System is to grant or deny access or exit based upon:
(1) Keypad identification data
(2) CAC card identification data
2.4.1 Access Control Unit(ACU)
a. Door Reader Interface Module: Lenel 1320 Dual Reader Interface Module.
Provide and connect Lenel 1320 Door Reader Interface Modules to existing Lenel Intelligent Controller as indicated on drawings.
b. Powered by a 12 or 24 VDC power source rated at a minimum of 4 amperes with a battery back-up for complete system operation in the event of power failure. Provide battery backup for all ACU(s) to sufficiently power the ACU for 12 hours continuous service.
2.4.2 Access Control Devices
2.4.2.1 Card Readers
Provide weatherproof mountable card readers as indicated for each individual location.
a. Access Control Card Reader: Bridgepoint Entry Point Reader Dual Interface 2 factor (Card +PIN) Product code 74-01-2003.
For exterior card reader locations, provide a Bridgepoint Reader Accessory
- Weather and Security Shield. Product code 74-40-1001.
2.4.2.2 Sally Port Control Devices
Sally Port Control Devices (Electric strikes) must be integral with sally port gate product.
2.4.3 Warranty
Include a minimum 3-year warranty.
2.5 WIRE AND CABLE
Provide all wire and cable for Electronic Security Systems. Wiring must meet NFPA 70 standards.
2.5.1 Cable Construction
Provide all cable components that will withstand the environment in which the cable is installed for a minimum of 20 years. Access Control System power and signal cable installed in underground conduit shall be rated for direct burial applications.
SECTION 28 10 05 Page 7