N33005.D_Maintenance Procedure Card.pdf

PDF 236 KB Posted

Attached to
52000QR260028280-CGC PIKE Fire System Inspection
Solicitation number
52000QR260028280
Issued by

About this file

This document is a U.S. Coast Guard Computerized Maintenance System (CMS) form (WPB-87, N33005.D, Revision 05/15/23) used to record scheduled and unscheduled maintenance performed on Coast Guard aircraft and surface assets.

The form documents the inspection of a contractor fire system (CMS Code N33005, CEINUM P1-B000-001) and requires completion by authorized Coast Guard personnel or contractor maintenance personnel. Key data fields include asset number, operating activity, maintenance accomplished date with asset hours, and maintenance due date with asset hours. The form captures whether maintenance was scheduled or unscheduled, identifies any discrepancies found, and documents man-hours expended by technician type (MK, DC, EM, ET, IT, GM, BM, FN, SN, ME, and other). Technician signature and ID are required, and Quality Assurance (QA) review is mandatory as indicated by asterisks. The maintenance procedure involves preliminary steps including equipment lockout/tagout per COMDTINST 9077.1, verification that an authorized marine fire extinguishing system inspector performs the work, installation of a new 360-degree fusible link (P/N: 302810), verification of contractor test completion, CO2 cylinder hydrostatic test date checks with Condition Finding Documentation (CFD) requirements, and compliance verification of CO2 discharge hoses. The form requires notification of the Engineer Petty Officer (EPO) if QA findings are unsatisfactory and completion of appropriate sign-off with pertinent remarks. References include DC MPC documents R-S-1570, R-S-1646, R-S-8844, MPC M00060.0, and COMDTINST 9077.1 (series).

View the file

Other files

File Type Posted
PIKE_SOW_Revised.docx DOCX document
Smart Matrix Acquisition.GOV.pdf PDF
PIKE_SOW.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U.S. COAST GUARD

COMPUTERIZED MAINTENANCE SYSTEM

WPB-87

N33005.D

REV'D 05/15/23

ASSET NUMBER OPERATING ACTIVITY MAINTENANCE ACCOMPLISHED MAINTENANCE DUE

DATE ASSET HOURS DATE ASSET HOURS

MO DAY YEAR MO DAY YEAR

ZULU DATE ZULU TIME

MO DAY YEAR

ITEM 1

DUE

CMS CODE ACTION DESCRIPTION CEINUM

N33005 INSPECT CONTRACTOR FIRE SYSTEM P1-B000-001

SCHEDULED UNSCHEDULED

DISCREPANCIES FOUND: NO_____ YES_____

MAN HOURS: MK___.___DC___.___EM___.___ET___.___IT___.___GM___.___BM___.___FN___.___SN___.___ME___.___OTHER___.___

IF DISCREPANCIES ARE FOUND REMARKS ARE REQUIRED

TECHNICIAN'S

SIGNATURE

TECHNICIAN'S

ID

* ASTERISK INDICATES QA REQUIRED *QA (2)

REFERENCES:

DC MPC R-S-1570

DC MPC R-S-1646

DC MPC R-S-8844

REVIEWED

BY

LOG YN DATA

ENTRY

COMPLETED

Distribution Statement D: Distribution authorized to the DHS/CG/DoD and their contractors Administrative/Operational use, 04/27/23. Other requests shall be referred to the appropriate asset product line.

WARNING: This document contains technical data whose export is restricted by the Arms Export-Control Act (Title 22, U.S.C., Sec 2751, et. seq.) or the Export Administration Act of 1979, as amended, Title 50, U.S.C. App 2401 et. seq. Violations of these export laws are subject to severe criminal penalties. Disseminate in accordance with provisions of DoD Directive 5230.25.

DESTRUCTION NOTICE: For classified documents, follow the procedures in DoD 5200.22-M, National Industrial Security Program Operating Manual, Section 5-705 or DoD 5200.1-R, Information Security Program Regulation, Chapter VI, Section 7. For unclassified, limited documents, destroy by any method that will prevent disclosure of contents or reconstruction of the document.

PRIVACY ACT STATEMENT

Authority: 44 U.S.C. 3101; 44 U.S.C. 3534; 5 U.S.C. §552a (e)(3); and Executive Order 9397.

Purpose: To account for scheduled and unscheduled maintenance performed on CG aircraft and surface assets.

Routine Uses: Authorized CG personnel will use this information to document scheduled and unscheduled maintenance, man-hours expended, and the technician respon-sible for tasks performed on CG aircraft and surface assets. Any external disclosures of data within this record will be made in accordance with DHS/ALL-004, General Information Technology Access Account Records, 77 Federal Register 70792, November 27, 2012.

Disclosure: Furnishing your Tech ID is voluntary; however, the inability to collect this information could result in untimely or incomplete Asset Computerized Maintenance System reports or the inability for the CG to make informed decisions regarding manpower analysis.

WPB-87

N33005.D

REV'D 05/15/23

ASSET NUMBER OPERATING ACTIVITY MAINTENANCE ACCOMPLISHED MAINTENANCE DUE

DATE ASSET HOURS DATE ASSET HOURS

MO DAY YEAR MO DAY YEAR

FIRST/LAST NAME: ______________________ TECH ID/TH: ________/________

FIRST/LAST NAME: ______________________ TECH ID/TH: ________/________

REVIEWED

BY

LOG YN DATA

ENTRY

COMPLETED

DESTRUCTION NOTICE - Destroy by any method that will prevent disclosure of contents or reconstruction of the document. Page 2 of 4

WPB-87

N33005.D

REV'D 05/15/23

1 TRACTOR FIRE SYSTEM INSPECT

REFERENCES:

COMDTINST 9077.1 (series) Equipment Lockout/Tags-Plus Instruction

MPC M00060.0

TOOLS/TESTEQUIPMENT:

NONE

EXPENDABLES:

NONE

CONSUMABLES:

Link, Fusible, Fire, P/N: 302810, CAGE: 05646, NIIN: 004433526

A PRELIMINARY STEPS

WARNING

VARIOUS STEPS IN THIS PROCEDURE EMPLOY ITEMS ON

THE HAZARDOUS MATERIALS LIST. BEFORE EXECUTING

THIS MPC, REFER TO THE APPLICABLE MSDS/SDS FOR

FULL SAFETY AND HANDLING PROCEDURES.

NOTE: EPOs shall submit service request through their Sector EO to the SFLC Asset Manager inbox 60 days prior to required due date for annual inspection. Asset Managers will forward properly submitted service request to the cutter’s APM. APM will complete PR for ser-vice and unit will receive notification from SK when purchase order is complete and unit may schedule service.

NOTE: This MPC is completed by a Depot repair activity or requires Depot level assistance.

1. Contact the Product Line to schedule Depot level work.

2. Complete this procedure in conjunction with CO2 cylinder test delay and cables while contractor is on site.

WARNING

ENSURE EQUIPMENT IS PROPERLY TAGGED OUT. FAILURE

TO COMPLY MAY RESULT IN SERIOUS PERSONAL INJURY

OR DEATH.

3. Complete Equipment Lockout/Tags-Plus Process IAW COMDTINST 9077.1 (series).

DESTRUCTION NOTICE - Destroy by any method that the document. Page 3 of 4

WPB-87

N33005.D

REV'D 05/15/23

WARNING

AVOID EYE CONTACT, SKIN CONTACT, AND INHALATION

WITH GAS. USE IN A WELL VENTILATED AREA. ENSURE

CYLINDER IS SECURE. FAILURE TO COMPLY MAY RESULT

IN SERIOUS PERSONAL INJURY.

NOTE: Ensure that the company who performs maintenance on this system is an authorized marine fire extinguishing system inspector.

4. Check that a new 360 degree fusible link, P/N: 302810, is provided to or by the contractor and installed during this test procedure.

5. Verify that the contractor completes all required tests.

* QA REQUIRED (1)

6. Check the CO2 cylinders for hydrostatic test dates.

a. Write a CFD in the Electronic Asset Logbook (EAL) if the hydrostatic test date is within 12 months of being due.

* QA REQUIRED (2)

7. Check that the following hoses are in compliance:

a. CO2 cylinder inboard discharge hose MPC M00060.0 (CMS Code M00062).

b. CO2 cylinder outboard discharge hose MPC M00060.0 (CMS Code M00063).

(1) Notify the Engineer Petty Officer (EPO) if the above QAs are unsatisfactory.

8. Reconnect necessary Operating Components and Remove Lockout/Tags-plus Material and Hardware IAW COMDTINST 9077.1 (series).

9. Restore equipment to its normal condition of readiness.

10. Notify EO, EPO, or Supervisor of any discrepancies, repairs, or future actions.

11. Record maintenance action by completing appropriate sign-off and adding pertinent remarks.

DESTRUCTION NOTICE - Destroy by any method that the document. Page 4 of 4