RFC_003.pdf
PDF 16 KB Posted
- Attached to
- USNS MERCY (T-AH 19) Mid-Term Availability Federal contract opportunity
- Solicitation number
- N32205-19-R-6502
About this file
Responses to Requests for Clarification (RFC 003)
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| N32205-19-R-6502-0005.pdf | ||
| RFC_004.pdf | ||
| N32205-19-R-6502-0004.pdf | ||
| 0703__(REV_A)_PRC_REPIR_02-52-0_SCULLERY_Specifiction.pdf | ||
| 0518__(REV_A)FWD_GLLEY_STEM_TBLE_DRIN_PIPE_REPIR_(18-008).pdf | ||
| 0702__(REV_A)_PRC_REPIRS_02_LEVEL_FR42-62_Specifiction.pdf | ||
| RFC_002.pdf | ||
| 0701__(REV_A)_MIN_LB_DECK_REFURBISHMENT_Specifiction.pdf | ||
| N3220519R6502-0003.pdf | ||
| J-8_RFC_(001).pdf | ||
| Solicitation_Amendment_(0002).pdf | ||
| N3220519R6502_0001.pdf | ||
| MERCY_FY-19_MTA_JA__.pdf | ||
| J-Attachments_.zip | ZIP file | |
| N3220519R6502_USNS_MERCY_.pdf | ||
| SYNOPSIS_N3220519R6502.docx | DOCX document |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Request for Clarification (RFC) 003
SPECIFICATION ITEM NO.: 01XX General
PARAGRAPH / SECTION NO: N/A
TITLE: SHIP-CHECK STATEMENTS MADE, PLEASE ADVISE.
QUESTION:
At the Ship-Check, Contractors were advised that 3 of the “100” Group Work Items were in-progress and subject to cancellation on this contract. Please formally define which items. Item 0199 cancellation per RFC #2 was noted.
ANSWER: Work Items 101, 102 and 103 have been deleted from the solicitation as per Amendment 0004.
SPECIFICATION ITEM NO.: 0107
PARAGRAPH / SECTION NO: 3.1.1 & 7.3
TITLE: MTF LAUNDRY DECK DRAIN REPAIR
QUESTION:
Paragraph 3.1.1 Location: Per drawings 528-5980084 there are 9 deck drains that run independently with up to 30 feet of downstream piping to the flanged 2”check valve in 3.1.2 Service Area #1. Please define which deck drain piping run needs to be replaced (by frame and location relative to the centerline).
ANSWER: For estimating purposes plan for replacement 200 ft. of 2” Steel Drain Piping and Fittings. Revised Work Item 107 (Rev A) has been issued under Amendment 0004.
SPECIFICATION ITEM NO: 0107
PARAGRAPH / SECTION NO: 7.3
TITLE: MTF LAUNDRY DECK DRAIN REPAIR
QUESTION:
Per drawings 528-5980084, a Standing Water Test is possible if the check valve is blanked.
Configuration does not provide for over-pressurization Hydrostatic test (included in the paragraph). Please advise.
ANSWER: The intent of Paragraph 7.3 is to accomplish a Standing Water test of the Drain Piping to prove the repairs.
SPECIFICATION ITEM NO.: 0402
PARAGRAPH / SECTION NO: 2.1.1
TITLE: TELEPHONE SYSTEM SERVICE
QUESTION:
Paragraph 2.1.1 Specification does not identify a Technical Representation. The system manufacturer, Nortel has been out of business since 2008. The Meridian 1 system is dated.
Contractor found a remaining certified technical services contractor for model 61C. However, in an attempt to help define the work, Contractor could not provide any further information as requested by the Tech Sub because the System Technical Manual is listed as “available on the ship”. Request minimum of system parameters and schematics (scanned and forwarded).
ANSWER: The following is a potential source to accomplish the requirements of Work Item 402:
VOX Network Solutions 8000 Marine Blvd, Suite 130 Brisbane, California 94005 Phone: (877) 869-8111 E-mail: service@voxns.com
SPECIFICATION ITEM NO.: 0401
PARAGRAPH / SECTION NO: 7.10
TITLE: COMMUNICATIONS SYSTEMS GROOM AND SERVICE
QUESTION:
Please provide a point of contact for known acceptable provider capable of meeting the requirements of 7.10.
ANSWER:
A possible source to complete the requirements of Work Item 0401 is:
Mid Atlantic Engineering Technical Services (MAETS) 1501 Crossways Blvd., Suite E Chesapeake, Virginia, 23320 POC: Danny Henderson Phone: 757-512-6864 mailto:service@voxns.com