MILITARY SEALIFT COMMAND
N32205-17-R-4703
QUESTIONS AND ANSWERS #2
The following are answers to questions received from potential offerors. The answers provide clarification only and do not constitute an amendment to the solicitation.
1. Item 0901: Two versions of Work Item 901 were provided, one dated 29 April 2016 and the other dated 24 Jan 2017. Please clarify which is to be used.
ANSWER: WI 901 dated 29 April 2016 has been revised. Utilize revised WI 901; to be provided via AMRDEC Safe.
2. Item 0601 paragraph 4.1 and 7.3: Statement of work in paragraph 7.3 states that the contractor shall take delivery of GFM listed in section 4.1 and install it in place of the deployed MES unit. However, section 4.0 states that there is no GFM. Is there or is there not any GFM? If so, please specify what will be provided.
ANSWER: There is no GFM for this work item. Contractor not to perform services at 7.3. Contractor to perform requirements listed in paragraph 7.3.1 and 7.3.2.
3. Item 0506: Are the requirements for insulation and heat tracing as stated in paragraphs 7.8 & 7.8.1 in addition to the insulation and heat tracing installed by work items 304 and 305?
ANSWER: Yes.
4. Item 0307 paragraph 7.2.1: Can a size, type, design etc. information be provided for the two (2) junction boxes required by paragraph 7.2.1? Paragraph 7.2.1 also requires calibration of system upon completion. Is this work to be accomplished by Wartsila?
ANSWER: Work to be accomplished by Wartsila. Junction box specifications to be provided via AMRDEC Safe.