MOUNT ISABEL_ECSO_BID_11-13-23_reduced.pdf
PDF 10 MB Posted
- Solicitation number
- S-X15022-00008745
- Issued by
- Jackson County, Oregon
About this file
This document is a Request for Proposal (RFP) for Communication Facilities Projects issued by Jackson County, Oregon. The RFP seeks proposals for the construction, installation, and maintenance of communication facilities and related infrastructure within the county. The project overview includes the construction of communication towers, equipment shelters, access roads, and the installation of cabling, antennas, and other supporting equipment. The RFP specifies the quantities of various items required, such as tower heights, shelter sizes, and cable lengths. Responses to the RFP are due on November 13, 2023, and a mandatory bidder's conference is scheduled for October 23, 2023. The contract term is for three years with two optional one-year renewals.
The RFP outlines the pricing terms, including the requirement for fixed-price bids. It also indicates that this procurement is set aside for small businesses. The current incumbent contractor is not eligible to submit a proposal. The project is funded through a combination of state and local government sources, with the total available funding amount specified in the RFP. Respondents must demonstrate their ability to meet the funding requirements and provide detailed pricing information as part of their proposals.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. PROPOSED MODIFICATION OF AN EXISTING
TELECOMMUNICATIONS FACILITY FOR ECSO 911.
2. PROPOSED INSTALLATION OF THE FOLLOWING EQUIPMENT ON A
NEW 120' TOWER:
* ANTENNAS W/ ASSOCIATED ANCILLARY EQUIPMENT
3. PROPOSED INSTALLATION OF THE FOLLOWING WITHIN GROUND:
* 12'x24' EQUIPMENT SHELTER
* 10'x10' GENERATOR SHELTER
* 500 GAL. PROPANE TANK
* GENERATOR
SHEET INDEX
SCALE: NTS
FROM ECSO 911 BUILDING
1. HEAD EAST ON PECH RD TOWARD CIRRUS DR
0.1 MI
2. TURN RIGHT ONTO CIRRUS DR
0.3 MI
3. TURN LEFT ONTO BIDDLE RD
0.4 MI
4. TURN RIGHT ONTO AIRPORT RD
0.3 MI
5. TURN LEFT ONTO TABLE ROCK RD
1.6 MI
6. CONTINUE ONTO N CENTRAL AVE
0.1 MI
7. KEEP RIGHT TO STAY ON N CENTRAL AVE
0.2 MI
8. TURN RIGHT ONTO OR-238 W/ROSSANLEY DR
2.2 MI
9. TURN LEFT ONTO OR-238 W
2.8 MI
10. TURN RIGHT ONTO OR-238 W/E CALIFORNIA ST
5.0 MI
11. TURN RIGHT ONTO FOREST CREEK RD
2.5 MI
12. TURN LEFT TO STAY ON FOREST CREEK RD
1.8 MI
13. TURN LEFT ONTO ISABELLE MOUNTAIN RD
2.4 MI
14. TURN RIGHT TO STAY ON ISABELLE MOUNTAIN RD
1.4 MI
EST. TIME: 41 MINS.
EST. MILEAGE: 21.1 MI
COVER
SHEET
SHEET NUMBER:
SHEET TITLE:
PROJECT INFORMATION PROJECT INFORMATION CONTINUED DRIVING DIRECTIONS
VICINITY MAP
PROPERTY OWNER:
BLM- MEDFORD DISTRICT
3040 BIDDLE RD
MEDFORD, OR 97504
CONTACT:
NICKY SMITH
N3SMITH@BLM.GOV
JURISDICTION:
JACKSON COUNTY
COUNTY:
JACKSON
ZONING:
FR (FOREST RESOURCE)
PARCEL NUMBER(S) & AREA:
TAX LOT#: 373W12400
ACCOUNT ID#: 10468145
24,316,063.2 SQ FEET±
558.22 ACRES±
PROJECT LOCATION:
*LAT: N 42° 18'11.69" (42.303247)
*LONG: W 123°6'16.21" (-123.104503)
*ELEVATION (ASML): 4,494'±
*INFORMATION OBTAINED FROM BLM DOCUMENT
UTILITY PROVIDERS:
TELCO PROVIDER: TBD
POWER PROVIDER: PACIFICORP
GENERAL INFORMATION:
1. TRAFFIC IS UNAFFECTED
2. SIGNAGE AT SITE IS PROPOSED
3. SITE IS UNMANNED AND HANDICAP ACCESS IS NOT REQUIRED
CODE INFORMATION:
1. IBC-2018 INTERNATIONAL BUILDING CODE
2. 2019 OREGON FIRE CODE
3. NEC-2017 NATIONAL ELECTRIC CODE
4. 2019 OREGON STRUCTURAL SPECIALITY CODE
5. 2017 NFPA 58 CODE
6. OCCUPANCY GROUP: U
7. CONSTRUCTION TYPE: II-B
SITE NAME:
MOUNT ISABELLE
T-1
PROJECT AREA:
TOTAL COMPOUND AREA - 3,600 SQ FEET
ACCESS DRIVE AND PARKING - EXISTING ACCESS ROAD
TOTAL - 3,600 SQ FEET ±
LOCATOR MAP
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
6701 FOREST CREEK RD, JACKSONVILLE, OR 97530
APPLICANT:
ECSO 911 (EMERGENCY COMMUNICATIONS OF SOUTHERN OREGON)
400 PECH ROAD
CENTRAL POINT, OR 97502
CONTACT:
JODY HATHAWAY
541-774-5062
PROJECT MANAGER:
TBD
CONSTRUCTION
MANAGER:
TBD
ZONING CONTACT:
CUSHING CIVIL ENGINEERS
12725 SW MILLIKAN WAY, STE 300
BEAVERTON, OR 97005
ROB HOWE
503-387-5331
ENGINEER OF RECORD:
CUSHING CIVIL ENGINEERS
12725 SW MILLIKAN WAY, STE 300
BEAVERTON, OR 97005
KENNY MCMANAWAY
503-387-5331
SURVEYEOR
ORION GEOMATICS
1724 23RD AVE
FOREST GROVE, OR 97116
JOHN PUTNAM
503-359-1688
PROJECT DESCRIPTION
SCALE: NTS
T-1 COVER SHEET
V-1 EXISTING CONDITIONS (SURVEY)
G-1 GENERAL NOTES
ER-1 GRADING & EROSION CONTROL PLAN
ER-2 GRADING & EROSION CONTROL DETAILS
C-1 OVERALL SITE PLAN I
C-2 OVERALL SITE PLAN II
C-3 ENLARGED SITE PLAN
C-4 ELEVATIONS
C-5 COMPOUND DETAILS I
C-6 COMPOUND DETAILS II
C-7 GENERATOR & PROPANE TANK DETAILS
C-8 EQUIPMENT SHELTER FOUNDATION PLAN
C-9 GENERATOR SHELTER FOUNDATION PLAN
E-1 SITE GROUNDING PLAN
E-2 GROUNDING DETAILS I
E-3 GROUNDING DETAILS II
E-4 GROUNDING DETAILS III
RF-1.0 RF TOWER APPURTENANCES I
RF-1.1 MICROWAVE ANTENNA DETAIL I
RF-1.2 MICROWAVE ANTENNA DETAIL II
RF-1.3 MICROWAVE ICE-SHIELD DETAIL
RF-1.4 ANTENNA MOUNT DETAILS
RF-2.0 RF TOWER APPURTENANCES II
RF-3.0 RF TOWER APPURTENANCES III
CONSTRUCTION SUBMITTAL:
BID
D
RAWIN
GS
KamalThapa Text Box
WUT PRELIMINARY TOWER AND FOUNDATION DRAWINGS:
T1 SHEET
S1 SHEET
F1 SHEET
jdpor
CENTER LINE
PROPERTY LINE
NUMBER
OTHERWISE
WATERPROOF
VERIFY IN FIELD
WITHOUT
WINDOW
VINYL TILE
VERTICAL
UNLESS NOTED
TOP OF MASONRY
TOP OF CONCRETE
SHEET VINYL
TYPICAL
THROUGH
SUSPENDED
STRUCTURAL
STAINLESS STEEL
SPECIFICATION
ROUGH OPENING
SQUARE
SIMILAR
REQUIRED
W/O
GA
GC
GALV
FT
FLR
FLUOR
FIN
EXT
EX
GAUGE
GENERAL CONTRACTOR
GALVANIZE(D)
FLUORESCENT
FOOT
FLOOR
FINISH
EXTERIOR
EXISTING
PRESSURE TREATED
OUTSIDE DIAMETER
PAIRPR
PROP
PROJ
PT
PROPERTY
PROJECT
OPP
OC, o/c
OPG
OD
OPPOSITE
OPENING
ON CENTER
AT
WP
C P L L
AND
ANGLE
GROUNDGRND
AIR CONDITIONINGA/C
REQ'D
CONTINUOUSCONT
DWG
EL, ELEV
E.W.
EQUIP
EQ
ELECT
EA
E
DIAG
DIM
DN
DTL, DETL
DIA, Ø
DBL
DRAWING
ELEVATION
EACH WAY
EQUIPMENT
EQUAL
ELECTRICAL
EACH
EAST
DIAGONAL
DETAIL
DOWN
DIMENSION
DIAMETER
DOUBLE
CONST
CONC
CLR
CLG
BLK
B/S
BMR
BLDG
AWG
ASTM
APPROX
AFF
ADJ
CONSTRUCTION
BUILDING STANDARD
BASE MOBILE RADIO
CONCRETE
CLEAR
CEILING
BLOCK
AMERICAN WIRE GAUGE
TESTING & MATERIALS
AMERICAN SOCIETY FOR
APPROXIMATELY
ABOVE FINISH FLOOR
BUILDING
ADJUSTABLE
T.O.C.
NOT IN CONTRACT
NOT APPLICABLE
MINIMUMMIN
N
NTS
NIC
NA
MISC
NORTH
NOT TO SCALE
MISCELLANEOUS
MET, MTL
MECH
MGR
MFR
LB(S)
MAX
MANAGER
MANUFACTURER
MECHANICAL
METAL
MAXIMUM
POUND(S)
VERT
WIN
W/ W
VT
VIF
WEST
WITH
U.N.O.
T.O.M.
TYP
GYPSUM WALL BOARD
HVAC
IN
INSUL
INT
INFO
I.D.
INCH
INTERIOR
INSULATION
INFORMATION
INSIDE DIA.
HORIZ
HARD'WD
HT
HR
GYP BD
GWB
HORIZONTAL
HARDWOOD
HEIGHT
HOUR
GYPSUM BOARD
SQ
TNND
THRU
SUSP
STRUCT
S.V.
SS
STL
TINNED
STEEL
SPEC
S
SHT
SIM
RM
R.O.
SOUTH
SHEET
ROOM
ANTENNA AMPLIFIERLNA
OVERHEAD POWEROHP
UNDRGRND POWERUGP
OVERHEAD TELCOOHT
UNDRGRND TELCOUGT
HEATING, VENTING AND
AIR CONDITIONING
1. DRAWINGS ARE NOT TO BE SCALED, WRITTEN DIMENSIONS TAKE PRECEDENCE, THIS SET OF
DOCUMENTS IS INTENDED TO BE USED FOR DIAGRAMMATIC PURPOSED ONLY, UNLESS
NOTED OTHERWISE. THE GENERAL CONTRACTOR'S SCOPE OF WORK SHALL INCLUDE
FURNISHING ALL MATERIALS, EQUIPMENT, LABOR AND ANY REQUIREMENTS DEEMED
NECESSARY TO COMPLETE INSTALLATION AS DESCRIBED IN THE DRAWINGS AND OWNER'S
PROJECT MANUAL.
2. THE CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS AND STANDARDIZED DETAILS THAT
REQUIRE MODIFICATIONS DUE TO ACTUAL FIELD CONDITIONS AND REQUIREMENTS MUST BE
SUBMITTED TO AND APPROVED BY OWNERS REPRESENTATIVE PRIOR TO START OF WORK.
3. PRIOR TO THE SUBMISSION OF BIDS, CONTRACTORS INVOLVED SHALL VISIT THE JOB SITE TO
FAMILIARIZE THEMSELVES WITH ALL CONDITIONS AFFECTING THE PROPOSED PROJECT.
CONTRACTORS SHALL VISIT THE CONSTRUCTION SITE WITH THE CONSTRUCTION/CONTRACT
DOCUMENTS TO VERIFY FIELD CONDITIONS AND CONFIRM THAT THE PROJECT WILL BE
ACCOMPLISHED AS SHOWN. PRIOR TO PROCEEDING WITH CONSTRUCTION, ANY ERRORS,
OMISSIONS, OR DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER VERBALLY AND IN WRITING.
4. THE GENERAL CONTRACTOR SHALL RECEIVE WRITTEN AUTHORIZATION TO PROCEED WITH
CONSTRUCTION PRIOR TO STARTING WORK ON ANY ITEM NOT CLEARLY DEFINED BY THE
CONSTRUCTION DRAWINGS/CONTRACT DOCUMENTS.
5. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE PROJECT DESCRIBED IN THE
CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL
CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, SAFETY, AND PROCEDURES
FOR COORDINATING ALL PORTIONS OF THE WORK UNDER THE CONTRACT.
6. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS ACCORDING TO
MANUFACTURER'S/VENDOR'S SPECIFICATIONS UNLESS NOTED OTHERWISE OR WHERE
LOCAL CODES OR ORDINANCES TAKE PRECEDENCE.
7. ALL WORK PERFORMED ON THE PROJECT AND MATERIALS INSTALLED SHALL BE IN STRICT
ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS, AND ORDINANCES.
CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES,
REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY, MUNICIPAL AND UTILITY
COMPANY SPECIFICATIONS, AND LOCAL AND STATE JURISDICTIONAL CODES BEARING ON THE
PERFORMANCE OF THE WORK.
8. THE CONTRACTOR SHALL PROVIDE, AT THE PROJECT SITE, A FULL SET OF CONSTRUCTION
DOCUMENTS UPDATED WITH THE LATEST REVISIONS INVOLVED WITH THE PROJECT. THIS
SET IS A VALID CONTRACT DOCUMENT ONLY IF THE TITLE SHEET IS STAMPED IN RED INK "FOR
CONSTRUCTION" AND EACH SUCCESSIVE SHEET BEARS THE ARCHITECT'S/ENGINEER'S
SIGNED WET STAMP.
9. THE CONTRACTOR IS RESPONSIBLE FOR ADEQUATELY BRACING AND PROTECTING ALL WORK
DURING CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, ETC. ACCORDING TO
APPLICABLE CODES, STANDARDS, AND GOOD CONSTRUCTION PRACTICES. THE
STRUCTURAL COMPONENTS OF ADJACENT CONSTRUCTION OR FACILITIES ARE NOT TO BE
ALTERED BY THE CONSTRUCTION PROJECT UNLESS NOTED OTHERWISE.
10. THE CONTRACTOR SHALL MEET ALL OSHA REQUIREMENTS FOR ALL INSTALLATIONS.
11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGES TO THE EXISTING
CONSTRUCTION AND REPAIR ALL DAMAGES TO EQUAL OR BETTER NEW CONSTRUCTION. THE
CONTRACTOR SHALL NOTIFY THE PROJECT MANAGER OF ANY DAMAGE TO THE BUILDING
SITE OR ANY ADJACENT STRUCTURES AROUND THE PROJECT. THE OWNERS
REPRESENTATIVE SHALL BE SOLE AND FINAL JUDGE AS TO THE QUALITY OF THE REPAIRED
CONSTRUCTION. ANY ADDITIONAL MODIFICATIONS WHICH MUST BE MADE SHALL BE MADE AT
THE CONTRACTOR'S EXPENSE.
12. WHERE NEW PAVING, CONCRETE SIDEWALKS OR PATHS MEET EXISTING CONSTRUCTION, THE
CONTRACTOR SHALL MATCH THE EXISTING PITCH, GRADE, AND ELEVATION SO THE ENTIRE
STRUCTURE SHALL HAVE A SMOOTH TRANSITION.
13. THE CONTRACTOR SHALL MODIFY THE EXISTING FLOORS, WALL, CEILING, OR OTHER
CONSTRUCTION AS REQUIRED TO GAIN ACCESS TO AREAS FOR ALL MECHANICAL, PLUMBING,
ELECTRICAL, OR STRUCTURAL MODIFICATIONS. WHERE THE EXISTING CONSTRUCTION
DOORS, PARTITIONS, CEILING, ETC., ARE TO BE REMOVED, MODIFIED, OR REARRANGED OR
WHERE THE EXPOSED OR HIDDEN MECHANICAL, ELECTRICAL, SYSTEMS ARE ADDED OR
MODIFIED, THE GENERAL CONTRACTOR SHALL REPAIR, PATCH AND MATCH ALL EXISTING
CONSTRUCTION AND FINISHES OF ALL FLOORS WALLS AND CEILINGS. WHERE CONCRETE
MASONRY CONSTRUCTION IS MODIFIED, THE CONTRACTOR SHALL TOOTH IN ALL NEW
CONSTRUCTION TO MATCH THE EXISTING BOND. WHERE CONCRETE CONSTRUCTION IS
MODIFIED, THE CONTRACTOR SHALL VERIFY THE EXACT DETAILS TO BE USED FOR
CONSTRUCTION. ALL WORK SHALL BE COVERED UNDER THE GENERAL CONTRACT.
14. IF CONTRACTOR OR SUBCONTRACTOR FIND IT NECESSARY TO DEVIATE FROM ORIGINAL
APPROVED PLANS, THEN IT IS THE CONTRACTOR'S AND THE SUBCONTRACTOR'S
RESPONSIBILITY TO PROVIDE THE PROJECT MANAGER WITH 4 COPIES OF THE PROPOSED
CHANGES FOR HIS APPROVAL BEFORE PROCEEDING WITH THE WORK. IN ADDITION THE
CONTRACTOR AND SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROCURING ALL
NECESSARY APPROVALS FROM THE BUILDING AUTHORITIES FOR THE PROPOSED CHANGES
BEFORE PROCEEDING WITH THE WORK. THE CONTRACTOR AND SUBCONTRACTORS SHALL
BE RESPONSIBLE FOR PROCURING ALL NECESSARY INSPECTIONS AND APPROVALS FROM
BUILDING AUTHORITIES DURING THE EXECUTION OF THE WORK.
15. CONTRACTOR TO PROVIDE A PORTABLE FIRE EXTINGUISHER WITH A RATING OF NOT LESS
THAN 2-A OR 2-A10BC WITHIN 75 FEET TRAVEL DISTANCE TO ALL PORTIONS OF PROJECT
AREA DURING CONSTRUCTION.
16. THIS IS AN ESSENTIAL FACILITY THEREFORE SHALL STRICTLY MEET ALL APPLICABLE CODE
AND JURISDICTIONAL REQUIREMENTS.
1. RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER REFUSE SHALL BE REMOVED
FROM THE SITE AND DISPOSED OF LEGALLY UNLESS OTHERWISE REQUIRED TO BE LEFT AS
DEFINED BY LAND/PROPERTY OWNER.
2. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE
EQUIPMENT, EQUIPMENT SHELTER, GENERATOR, FUEL TANK, TOWER AREAS, AND
ADJACENT BUILDINGS, ETC.
3. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN
MATERIALS, SNOW OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT.
4. THE SUBGRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE
PRIOR TO THE CRUSHED STONE APPLICATION. FABRIC USE AS REQUIRED.
5. ALL APPLICABLE LOCATES SHALL BE PERFORMED PRIOR TO TO ANY EXCAVATION OR SITE
GRADING. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES
WHERE ENCOUNTERED IN THE WORK, SHALL BE PROTECTED AT ALL TIMES, AND WHERE
REQUIRED FOR THE PROPER EXECUTION OF THE WORK, SHALL BE RELOCATED AS
DIRECTED BY ENGINEERS. EXTREME CAUTION SHOULD BE USED BY THE CONTRACTOR
WHEN EXCAVATING OR PIER DRILLING AROUND OR NEAR UTILITIES. CONTRACTOR SHALL
PROVIDE SAFETY TRAINING FOR THE WORKING CREW.
6. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES, WHICH
INTERFERE WITH THE EXECUTION OF THE WORK, SHALL BE REMOVED AND SHALL BE
CAPPED, PLUGGED OR OTHERWISE DISCONTINUED AT POINTS WHICH WILL NOT INTERFERE
WITH THE EXECUTION OF THE WORK, SUBJECT TO THE APPROVAL OF ENGINEERING.
7. THE AREAS OF THE PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE
BUILDING, DRIVEWAY OR CRUSHED STONE, SHALL BE GRADED TO A UNIFORM SLOPE,
FERTILIZED, SEEDED, AND COVERED WITH MULCH AS SPECIFIED IN THE SPECIFICATION
LANDSCAPE WORK..
8. BEDDING MATERIAL FOR UTILITY LINES, CULVERTS AND PIPING: CLEAN SAND, MEDIUM TP
COARSE, SUB ROUNDED NATURAL RIVER OR BANK SAND, WASHED, FREE OF SILT OR CLAY,
LOAM, FRIABLE OR SOLUBLE MATERIALS, AND ORGANIC MATTER; GRADED IN
ACCORDANCE WITH THE FOLLOWING GRAIN SIZE DISTRIBUTION:
9. BMP'S FOR TEMPORARY EROSION/SEDIMENTATION CONTROL SHALL BE IMPLEMENTED PER
LOCAL, CITY OR COUNTY GUIDELINES AND PER PLAN IF APPLICABLE.
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301, ACI 318 AND THE
SPECIFICATION CAST-IN-PLACE CONCRETE.
2. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS
(UNO).
3. REINFORCING STEEL SHALL CONFORM TO ASTM A 615, GRADE 60, DEFORMED UNLESS NOTED
OTHERWISE. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A 185 WELDED STEEL WIRE
FABRIC UNLESS NOTED OTHERWISE. SPLICES CLASS "B" AND ALL HOOKS SHALL BE
STANDARD (UNO).
4. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL
UNLESS SHOWN OTHERWISE ON DRAWINGS: CONCRETE CAST AGAINST EARTH - 3 IN.
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 AND LARGER ..........................2 IN.
#5 AND SMALLER & WWF ...........1-1/2 IN.
5. A 1/2" TROWELED RADIUS SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE (UNO).
HOLES TO RECEIVE EXPANSION/WEDGE ANCHORS SHALL BE 1/8" LARGER IN DIAMETER THAN
THE ANCHOR BOLT, DOWEL OR ROD AND SHALL CONFORM TO MFR RECOMMENDATION FOR
EMBEDMENT DEPTH OR AS SHOWN ON THE DRAWINGS. AVOID CUTTING EXISTING REBAR
WHEN DRILLING HOLES IN THE ELEVATED SLAB.
6. INSTALLATION OF CONCRETE EXPANSION AND WEDGE ANCHOR, SHALL BE PER
MANUFACTURER'S WRITTEN RECOMMENDED PROCEDURES.
7. FLOAT SURFACE SHALL BE A SMOOTH FINISH. SURFACE SHALL BE FREE OF ALL OBVIOUS
DEPRESSIONS. SURFACE SHALL BE SLOPED AT 2% TO PROMOTE DRAINAGE AWAY FROM
EQUIPMENT.
17. THE CONTRACTOR SHALL PERFORM WORK DURING SITE/PROPERTY OWNER'S PREFERRED
HOURS TO AVOID DISTURBING NORMAL BUSINESS.
18. SEAL ALL PENETRATIONS THROUGH FIRE-RATED AREAS WITH U.L. LISTED OR FIRE MARSHAL
APPROVED MATERIALS AS APPLICABLE TO THIS FACILITY AND OR PROJECT SITE.
19. CONTRACTOR SHALL BE RESPONSIBLE FOR UTILITY LOCATES, SCHEDULING, COORDINATING
SPECIAL AND BUILDING DEPARTMENT INSPECTIONS.
21. ROUTING OF ALL CONDUITS, CABLES, CABLE TRAYS ETC ARE INDICATED AS PROPOSED
LOCATION ONLY. CONFIRM THE EXACT LOCATION AND ROUTING WITH THE ON SITE PROJECT
MANAGER PRIOR TO STARTING WORK.
AGL ABOVE GRADE LEVEL
GENERAL NOTES CONTINUED:
CONCRETE NOTES:
GENERAL NOTES:
SITE WORK NOTES:
60-90
0-45 0-25 0-2
0-2NO. 200 MESH
NO. 100 MESH
NO. 16 MESH
NO. 8 MESH
NO. 4 MESH
PERCENT PASSINGSIEVE SIZE
SYMBOLS LEGEND
WATER
CENTERLINE
COAX
POWER/TELCO
TELCO
COAX COAX
EASEMENT
PROPERTY LINE
GAS
UNDERGROUND POWER
CEDAR FENCE
CHAINLINK FENCE
ABBREVIATIONS LEGEND
GENERAL
NOTES
G-1
SHEET NUMBER:
SHEET TITLE:
C-4
REVISION
KEY NOTE DETAIL
REFERENCE ELEVATION
SECTION REFERENCE
ELEVATION DATUM POINT
A C-3
GA
GC
GALV
FT
FLR
FIN
EXT
DWG
E.W.
EQ
EA
E
DIAG
DIM
DN
DBL
CLR
CLG
BLK
B/S
BMR
BLDG
AWG
LB(S)
MAX
IN
INT
INFO
I.D.
HT
HR
GWB
LNA
SYMBOLS LEGEND
DESIGN LOADS:
W W
OVERHEAD POWER
G G G G G G
10. ALL SITE DESIGN AND CONSTRUCTION MUST COMPLY WITH INDUSTRY STANDARDS AND BE
ALIGNED WITH BMP GUIDELINES AS TECHNICALLY APPLICABLE. EACH SITE MUST BE PM
APPROVED BEFORE IT SHALL BE CONSIDERED COMPLETE AND ACCEPTED.
11. IF INADVERTENT DISCOVERIES OF NATIVE AMERICAN CULTURAL MATERIALS OR HUMAN
REMAINS ARE MADE DURING CONSTRUCTION, ALL WORK SHOULD CEASE AND POTENTIALLY
AFFECTED TRIBES, AS WELL AS THE STATE HISTORIC PRESERVATION OFFICE, SHOULD BE
NOTIFIED IMMEDIATELY.
1. ALL ANTENNAS, LINES AND RELATED INSTALLATION HARDWARE TO BE PROVIDED BY THE
LAND MOBILE COMMUNICATIONS PROVIDER.
2. ALL HARDWARE (NUTS AND BOLTS) BE TIGHTENED AND TORQUED IN ACCORDANCE WITH
THE TOWER MANUFACTURER'S AND STRUCTURAL ENGINEER'S SPECIFICATIONS.
3. VERIFICATION THAT THE TOWER/POLE CAN SUPPORT THE PROPOSED ANTENNA LOADING
IS TO BE DONE BY OTHERS.
4. PROVIDE SUPPORTS FOR THE ANTENNA COAX CABLES TO THE ELEVATION OF ALL INITIAL
AND FUTURE ANTENNAS. ANTENNA COAX CABLES ARE TO BE SUPPORTED AND
RESTRAINED AT THE CENTERS SUITABLE TO THE MANUFACTURER'S REQUIREMENTS.
SITE WORK NOTES CONTINUED:
TOWER/POLE NOTES:
CALL 1-800-332-2344 48 HOURS BEFORE YOU DIG. OREGON LAW REQUIRES YOU TO FOLLOW
OAR 952-001-0010 THRU 952-001-0090. COPIES ARE AVAILABLE AT THE OREGON UTILITY
NOTIFICATION CENTER 503-232-1987
ATTENTION (OREGON SITES ONLY):
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
P PROPOSED
OHP OHP OHP OHP OHP
LPG LPG LPG LPGPROPANE
ROOF SNOW LOAD DATA - GROUND SNOW LOAD: 137 PSF*
FLAT-ROOF SNOW LOAD: 105 PSF***
SNOW EXPOSURE FACTOR: **
SNOW LOAD IMPORTANCE FACTOR: **
THERMAL FACTOR: **
WIND DESIGN DATA - ULTIMATE DESIGN WIND SPEED: 105 MPH*
RISK CATEGORY: IV
WIND EXPOSURE: C*
INTERNAL PRESSURE COEFFICIENT: **
DESIGN WIND PRESSURES;
WIND LOAD HORIZONTAL (MWFRS):**
WIND LOAD (UPLIFT) (MWFRS): **
EARTHQUAKE DESIGN DATA - RISK CATEGORY: IV
SEISMIC IMPORTANCE FACTOR: **
MAPPED SPECTRAL RESPONSE ACCEL-
ERATION PARAMETERS;
SS 0.89*
S1 0.4*
SITE CLASS: B
DESIGN SPECTRAL RESPONSE ACCEL-
ERATION PARAMETERS;
SDS 0.49*
SD1 0.24*
SEISMIC DESIGN CATEGORY: D*
BASIC SEISMIC FORCE-RESISTING
SYSTEM: BEARING WALL
DESIGN BASE SHEAR: **
SEISMIC RESPONSE COEFFICIENT: **
RESPONSE MODIFICATION COEFFICIENT: **
ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL
FORCE PROCEDURE
GEOTECHNICAL INFORMATION - ALLOWABLE BEARING CAPACITY: NA
*INFORMATION OBTAINED FROM ASCE 7 HAZARD TOOL
**PER MANUFACTURER
***INFORMATION OBTAINED FROM OREGON SNOW LOAD MAP
BID
D
RAWIN
GS
4,500
4,490
4,495
4,485
4,485
GRADING & EROSION
CONTROL PLAN
ER-1
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
11X17 SCALE: 1" = 12' 22X34 SCALE: 1" = 6' GRADING & EROSION CONTROL PLAN 1
EROSION CONTROL NOTES:
1. OWNER OR DESIGNATED PERSON SHALL BE RESPONSIBLE FOR PROPER INSTALLATION AND MAINTENANCE OF ALL EROSION AND SEDIMENT CONTROL MEASURES, IN ACCORDANCE WITH LOCAL, STATE, AND FEDERAL REGULATIONS.
2. THE IMPLEMENTATION OF THESE ESC PLANS AND CONSTRUCTION, MAINTENANCE, REPLACEMENT, AND UPGRADING OF THESE ESC FACILITIES IS THE RESPONSIBILITY OF THE CONTRACTOR UNTIL ALL CONSTRUCTION IS COMPLETED AND APPROVED BY THE LOCAL JURISDICTION, AND VEGETATION/LANDSCAPING IS ESTABLISHED. THE DEVELOPER SHALL BE RESPONSIBLE FOR MAINTENANCE AFTER THE PROJECT IS APPROVED UNTIL THE LOTS ARE SOLD.
3. THE BOUNDARIES OF THE CLEARING LIMITS SHOWN ON THIS PLAN SHALL BE CLEARLY MARKED IN THE FIELD PRIOR TO CONSTRUCTION. DURING THE CONSTRUCTION PERIOD, NO DISTURBANCE BEYOND THE CLEARING LIMITS SHALL BE PERMITTED. THE MARKINGS SHALL BE MAINTAINED BY THE APPLICANT/CONTRACTOR FOR THE DURATION OF
CONSTRUCTION.
4. THE ESC FACILITIES SHOWN ON THIS PLAN MUST BE CONSTRUCTED IN CONJUNCTION WITH ALL CLEARING AND GRADING ACTIVITIES, AND IN SUCH A MANNER AS TO INSURE THAT SEDIMENT AND SEDIMENT LADEN WATER DOES
NOT ENTER THE DRAINAGE SYSTEM, ROADWAYS, OR VIOLATE APPLICABLE WATER STANDARDS.
5. THE ESC FACILITIES SHOWN ON THIS PLAN ARE MINIMUM REQUIREMENTS FOR ANTICIPATED SITE CONDITIONS.
DURING CONSTRUCTION PERIODS, THESE ESC FACILITIES SHALL BE UPGRADED AS NEEDED FOR UNEXPECTED STORM EVENTS AND TO ENSURE THAT SEDIMENT AND SEDIMENT LADEN WATER DOES NOT LEAVE THE SITE.
6. THE ESC FACILITIES SHALL BE INSPECTED DAILY BY THE APPLICANT/CONTRACTOR AND MAINTAINED AS NECESSARY
TO ENSURE THEIR CONTINUED FUNCTIONING.
7. AT NO TIME SHALL SEDIMENT BE ALLOWED TO ACCUMULATE MORE THAN 1/3 THE BARRIER HEIGHT. ALL CATCH BASINS AND CONVEYANCE LINES SHALL BE CLEANED PRIOR TO PAVING. THE CLEANING OPERATIONS SHALL NOT
FLUSH SEDIMENT-LADEN WATER INTO THE DOWNSTREAM SYSTEM.
8. STABILIZED GRAVEL ENTRANCES SHALL BE INSTALLED AT THE BEGINNING OF CONSTRUCTION AND MAINTAINED FOR THE DURATION OF THE PROJECT. ADDITIONAL MEASURES MAY BE REQUIRED TO INSURE THAT ALL PAVED AREAS
ARE KEPT CLEAN FOR THE DURATION OF THE PROJECT.
9. STORM DRAIN INLETS, BASINS, AND AREA DRAINS SHALL BE PROTECTED UNTIL PAVEMENT SURFACES ARE
COMPLETED AND/OR VEGETATION IS RE-ESTABLISHED.
10. PAVEMENT SURFACES AND VEGETATION ARE TO BE PLACED AS RAPIDLY AS POSSIBLE.
11. SEEDING SHALL BE PERFORMED NO LATER THAN SEPTEMBER 1 FOR EACH PHASE OF CONSTRUCTION.
12. IF THERE ARE EXPOSED SOILS OR SOILS NOT FULLY ESTABLISHED FROM OCTOBER 1ST THROUGH APRIL 30TH, THE
WET WEATHER EROSION PREVENTION MEASURES WILL BE IN EFFECT. SEE THE EROSION PREVENTION AND
SEDIMENT CONTROL PLANNING AND DESIGN MANUAL (CHAPTER 4) FOR REQUIREMENTS.
13. NO EXPOSED, BARE SOILS SHALL REMAIN UNSTABILIZED FOR MORE THAN TWO DAYS DURING THE PERIOD OCTOBER 1 THROUGH APRIL 30 OR FOR MORE THAN SEVEN DAYS DURING THE PERIOD OF MAY 1 THROUGH SEPTEMBER 30.
ALL DISTURBED SOIL SURFACES SHALL BE STABILIZED BY A SUITABLE APPLICATION OF "BEST MANAGEMENT
PRACTICES".
14. WHERE FEASIBLE, NO MORE THAN 500 FEET OF TRENCH SHALL BE OPEN AT ONE TIME. EXCAVATED MATERIAL SHALL BE PLACED ON THE UPHIL SIDE OF TRENCHES PROVIDED IT DOES NOT CONFLICT WITH SAFETY
REQUIREMENTS.
15. THE DEVELOPER SHALL REMOVE ESC MEASURES WHEN VEGETATION IS FULLY ESTABLISHED.
4 GENERAL NOTES SCALE: NTS
2SCALE: NTS
3SCALE: NTS CUT/ FILL QUANTITIES
UNADJUSTED CUT/ FILL QUANTITIES
STRIPPING ORGANICS FOR COMPOUND;
CUT = 122.5 CU. YD.
STRIPPING FOR ACCESS ROAD AND PARKING;
CUT = NA
PROPOSED COMPOUND AREA;
CUT = 122.5 CU. YD.
FILL = 3.31 CU. YD.
PROPOSED ACCESS ROAD AND PARKING;
CUT = 0 CU. YD.
FILL = 0 CU. YD.
PROPOSED TOWER FOUNDATION;
EXCAVATION = TBD CU. YD.
APPROX. TOTAL AREA OF DISTURBANCE OF PROPOSED GRADING = 2,318.97 SQ. FT.
REFER TO GEO-TECHNICAL ENGINEERING EVALUATION BY BLACK MOUNTAIN DATED XX/XX/XX.
IMPERVIOUS AREAS
TOTAL PARCEL AREA = 24,381,879.64 SQ. FT.
PRE-DEVELOPMENT AREA; EXISTING IMPERVIOUS:
EXISTING COMPOUND = 22.57 SQ. FT.
EXISTING ACCESS & PARKING = 0 SQ. FT.
TOTAL = 22.57 SQ. FT.
POST-DEVELOPMENT AREA; NEW IMPERVIOUS:
NEW COMPOUND = 1,012 SQ. FT.
NEW ACCESS & PARKING = 0 SQ. FT.
TOTAL = 1,012 SQ. FT.
PERVIOUS = 2,588 SQ. FT
EXISTING GRADE
PROPOSED GRADE
TEMPORARY SILT FENCE
CONSTRUCTION ENTRANCE
FLOW DIRECTION
GROUND ELEVATION250'
LEGEND
FLOW DIRECTION, TYP
4,490'
4,495'
4,500'
4,485'
4,485'
EG 4,495.2'
FG 4,497.0'
EG 4,497.1'
FG 4,497.0'
EG 4,497.9'
FG 4,497.0'
EG 4,495.4'
FG 4,497.0'
EG 4,497.1'
FG 4,497.0'
EG 4,495.7'
FG 4,497.0'
EG 4,495.5'
FG 4,497.0'
EG 4,497.5'
FG 4,497.0'
EG 4,495.9'
FG 4,497.0'
TOP OF SHELTER FOUNDATION
FG 4,497.5' TOP OF SHELTER FOUNDATION
FG 4,497.5'
TOP OF PAD
FG 4,497.5'
(P) BLM OUTDOOR
CABINET TO BE REMOVED
BID
D
GRADING &
EROSION CONTROL
PLAN DETAILS
ER-2
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
SEDIMENT FENCE NOTES:
1. THE FILTER FABRIC FENCE SHALL BE INSTALLED TO FOLLOW THE CONTOURS WHERE FEASIBLE. THE FENCE POSTS SHALL BE SPACED A MAXIMUM OF 6' APART AND DRIVEN
SECURELY INTO THE GROUND A MINIMUM OF 24”.
2. THE FILTER FABRIC SHALL BE PURCHASED IN A CONTINUOUS ROLL CUT TO THE LENGTH OF THE BARRIER TO AVOID USE OF JOINTS. WHEN JOINTS ARE NECESSARY, FILTER CLOTH SHALL BE SPLICED TOGETHER ONLY AT A SUPPORT POST, WITH A MINIMUM 6” OVERLAP, AND BOTH ENDS SECURELY FASTENED TO THE POST, OR OVERLAP 2” X 2”
POSTS AND ATTACH AS SHOWN ON DETAIL SHEET 4-3A OF THE EROSION CONTROL MANUAL.
3. THE FILTER FABRIC SHALL HAVE A MINIMUM VERTICAL BURIAL OF 6”. ALL EXCAVATED MATERIAL FROM FILTER FABRIC INSTALLATION SHALL BE BACKFILLED AND COMPACTED
ALONG THE ENTIRE DISTURBED AREA.
4. STANDARD OR HEAVY-DUTY FILTER FABRIC FENCES SHALL HAVE MANUFACTURED STITCHED LOOPS FOR 2” X 2” POST INSTALLATION. STITCHED LOOPS SHALL BE INSTALLED
ON THE UP HILLSIDE OF THE SLOPED AREA.
5. FILTER FABRIC FENCES SHALL BE REMOVED WHEN THEY HAVE SERVED THEIR USEFUL PURPOSE, BUT NOT BEFORE THE UPSLOPE AREA HAS BEEN PERMANENTLY
PROTECTED AND STABILIZED.
6. FILTER FABRIC FENCES SHALL BE INSPECTED BY APPLICANT/CONTRACTOR IMMEDIATELY AFTER EACH RAINFALL AND AT LEAST DAILY DURING PROLONGED RAINFALL. ANY
REQUIRED REPAIRS SHALL BE MADE IMMEDIATELY.
3SCALE: NTS
2SCALE: NTS
4SCALE: NTS
1SCALE: NTS
TOE OF
SLOPE
PL
PL
H/5 BUT 2' MINIMUM
AND NEED NOT EXCEED
20' MAXIMUM
TOE OF
SLOPE
H/5 BUT 2'
MINIMUM
AND NEED
NOT
EXCEED 10'
MAXIMUM
NATURAL OR
FINISH GRADE
INTERCEPTOR DRAIN
(IF REQUIRED)
H
NATURAL OR
FINISH GRADE
CUT OR
FILL SLOPE
GRAVEL CONSTRUCTION ENTRANCE TEMPORARY SEDIMENT FENCE
PLASTIC SHEETING SETBACKS AND DRAINAGE DIMENSIONS
BID
D
© 2023 Microsoft Corporation © 2023 Maxar ©CNES (2023) Distribution Airbus DS © 2023 TomTom
22X34 SCALE: 1" = 350' OVERALL SITE PLAN 1
OVERALL
SITE PLAN I
C-1
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
NOTE:
THIS IS NOT A SURVEY ALL
EXISTING INFORMATION IS
PROVIDED BY GIS.
ACCOUNT: 10305148
11X17 SCALE: 1" = 700'
ZONING
FR (COUNTY-FOREST RESOURCE)
ACCOUNT: 10291541
ZONING
FR (COUNTY-FOREST RESOURCE)
ACCOUNT: 10305229
ZONING
FR (COUNTY-FOREST RESOURCE)
ACCOUNT: 10468145
ZONING
FR (COUNTY-FOREST RESOURCE)
PROPOSED PROJECT AREA
SEE SHEET C-2 FOR DETAILS
ACCOUNT: 10291841
ZONING
FR (COUNTY-FOREST RESOURCE)
ACCOUNT: 10291532
ZONING
FR (COUNTY-FOREST RESOURCE)
ACCOUNT: 10291524
ZONING
FR (COUNTY-FOREST RESOURCE)
ACCOUNT: 10291516
ZONING
FR (COUNTY-FOREST RESOURCE)
ACCOUNT: 10468160
ZONING
FR (COUNTY-FOREST RESOURCE)
ACCOUNT: 10305845
ZONING
FR (COUNTY-FOREST RESOURCE)
(E) SITE ACCESS ROAD
(E) SITE ACCESS GATE
±3318'-9"
±3
7'- 8"
±1880'-2"
±2
'-1
(P) PRIMARY FUEL BREAK
(50' OFFSET FROM NEW SHELTER)
CONTRACTOR TO MAINTAIN PER JACKSON
COUNTY REQ. IN SECTION 8.7.1.B OF LDO
(P) SECONDARY FUEL BREAK
(100' OFFSET FROM NEW SHELTER)
CONTRACTOR TO MAINTAIN PER
JACKSON COUNTY REQ. IN SECTION
8.7.1.B OF LDO
BID
D
P
LPG
NOTES:
1. TOWER INFO SHOWN FOR CONCEPTUAL USE ONLY.
2. EXISTING INFORMATION IS PROVIDED BY GIS, SITE
SURVEY & SITE WALK NOTES.
11X17 SCALE: 1" = 24' 22X34 SCALE: 1" = 12' SITE PLAN 1
OVERALL
SITE PLAN II
C-2
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
(P) 120' SELF-SUPPORT TOWER
(P) POWER ROUTE FROM
(P) METER, ROUTE TBD
(P) 200 A METER
W/ DISCONNECT
(P) POWER ROUTE TBD
(EX) SHELTER BY OTHERS, TYP
(EX) TOWER BY OTHERS
(EX) PROPANE
TANK BY OTHERS
(EX) UTILITY RACK TO BE
EXTENDED TO ACCOMMODATE
NEW EQUIPMENT
(P) 60'x60' SITE PAD AREA
SEE SHEET C-3 FOR
ENLARGED SITE PLAN
(P) UTILITY RACK EXTENSION
(EX) VEGETATION, TYP
(EX) GRAVEL DRIVE
(P) PRIMARY FUEL BREAK
(50' OFFSET FROM NEW SHELTER)
CONTRACTOR TO MAINTAIN PER
JACKSON COUNTY REQ. IN
SECTION 8.7.1.B OF LDO
(EX) TREELINE, TYP
(P) SECONDARY FUEL BREAK
(100' OFFSET FROM NEW SHELTER)
CONTRACTOR TO MAINTAIN PER JACKSON
COUNTY REQ. IN SECTION 8.7.1.B OF LDO
BID
D
LPG
LPG
LPG
NOTES:
1. TOWER INFO SHOWN FOR CONCEPTUAL USE ONLY.
2. EXISTING INFORMATION IS PROVIDED BY GIS, SITE
SURVEY & SITE WALK NOTES.
11X17 SCALE: 1" = 12' 22X34 SCALE: 1" = 6' ENLARGED SITE PLAN 1
ENLARGED
SITE PLAN
C-3
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
C-3
±3 '-6
±2 0'
IC
E-
BR
ID
GE
±60'
SITE PAD
±6 0'
SI
TE
P
AD
(P) 120' SELF-SUPPORT TOWER
SEE SHEET C-4 FOR ELEVATIONS
(P) 500 GAL. PROPANE TANK
ON 12'x4' CONCRETE PAD
(P) BOLLARD,
TYP OF (10)
(P) POWER ROUTE FROM
(P) METER, ROUTE TBD (EX) SHELTER BY OTHERS, TYP
(EX) TOWER BY OTHERS
(P) GENERATOR
INSIDE SHELTER
(P) 10'x10' GENERATOR
SHELTER
(P) 12'x24' EQUIPMENT SHELTER
C-3
COMPOUND ROCK SECTION
(P) LED SHELTER LIGHT
(P) GAS AND TELCO LINE
TO (P) GENERATOR
(P) POWER/TELCO LINE FROM
TO (P) EQUIPMENT SHELTER
±1 0'
±10'
(P) 60'x60' SITE PAD AREA
(EX) GRAVEL DRIVE
±1 0'
IC
E-
BR
ID
GE
±9'
±13'-10"
±16'TYP
±4
TY
P
±20'
±1 2'
±30'
±20'
BID
D
C O
AX
C
O
AX
C O
AX
C
O
AX
C O
AX
C
O
AX
C O
AX
C
O
AX
C O
AX
C
O
AX
C O
AX
C
O
AX
C O
AX
C
O
AX
C O
AX C
O
AX
C
O
AX
C O
AX
C
O
AX
C O
AX
C
O
AX
C O
AX
COAX COAX
NOTES:
· ELEVATION FOR SCHEMATIC PURPOSES ONLY
· EXISTING TREES NOT SHOWN FOR CLARITY
· PROPOSED ANTENNAS TO BE LIGHT GRAY OR
LIGHT BLUE IN COLOR
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
11X17 SCALE: 1" = 16' 22X34 SCALE: 1" = 8'PROPOSED SOUTH ELEVATION 1 11X17 SCALE: 1" = 16'PROPOSED EAST ELEVATION 222X34 SCALE: 1" = 8'
ELEVATIONS
C-4
SHEET NUMBER:
SHEET TITLE:
(P) TOWER TOP ±120.0' AGL
(BY OTHERS)
GROUND LEVEL (GL)
(P) ANTENNA BASE ±93.0' AGL
(BY OTHERS)
(P) ANTENNA CL ±65.0' AGL
(BY OTHERS)
(P) SHELTER TOP ±12.0' AGL
(P) ANTENNA BASE ±75.0' AGL
(BY OTHERS)
(P) ANTENNA BASE ±50.0' AGL
(BY OTHERS)
(P) ANTENNA CL ±55.0' AGL
(P) ANTENNA CL ±85.0' AGL
(BY OTHERS)
(P) LIGHTNING ROD TOP ±135.0' AGL
(BY OTHERS)
(P) ANTENNA CL ±105.0' AGL
(P) ANTENNA BASE ±120.0' AGL
(P) 6'Ø MICROWAVE ANTENNA;
MODEL# VHLP6-6W
AZIMUTH = 90.99°
(TO BALDY)
(P) VHF RX OMNI ANTENNA;
MODEL# OA40-41-T3-P
(P) MICROWAVE ANTENNA;
MODEL# VHLP4-11W
AZIMUTH = 194.27°
(TO TALLOWBOX)
(P) 120' SELF-SUPPORT TOWER
(P) ICE-BRIDGE
(P) GENERATOR SHELTER
(P) PROPANE TANK
(P) CABLE LADDER
(P) COAX CABLE
(P) TOWER TOP ±120.0' AGL
(BY OTHERS)
GROUND LEVEL (GL)
(P) ANTENNA BASE ±93.0' AGL
(BY OTHERS)
(P) ANTENNA CL ±65.0' AGL
(BY OTHERS)
(P) SHELTER TOP ±12.0' AGL
(P) ANTENNA BASE ±75.0' AGL
(BY OTHERS)
(P) ANTENNA BASE ±50.0' AGL
(BY OTHERS)
(P) ANTENNA CL ±55.0' AGL
(P) ANTENNA CL ±85.0' AGL
(BY OTHERS)
(P) LIGHTNING ROD TOP ±135.0' AGL
(BY OTHERS)
(P) ANTENNA CL ±105.0' AGL
(P) ANTENNA BASE ±120.0' AGL
(P) 120' SELF-SUPPORT TOWER
(P) EQUIPMENT SHELTER
(P) GENERATOR SHELTER
(P) PROPANE TANK
(P) COAX CABLE
(P) EQUIPMENT SHELTER
(P) ICE-BRIDGE
(P) ANTENNA BASE ±75.0' AGL
(P) VHF TX OMNI ANTENNA;
MODEL# RFI EA40-41-P
(P) ANTENNA BASE ±75.0' AGL
(P) 6'Ø MICROWAVE ANTENNA;
MODEL# VHLP6-6W
AZIMUTH = 90.99°
(TO BALDY)
(P) MICROWAVE ANTENNA;
MODEL# VHLP4-11W
AZIMUTH = 194.27°
(TO TALLOWBOX)
(P) VHF TX OMNI ANTENNA;
MODEL# RFI EA40-41-P
(P) VHF RX OMNI ANTENNA;
MODEL# OA40-41-T3-P
(P) MICROWAVE ICE SHIELD
MODEL# MIS6
(P) MICROWAVE ICE SHIELD
MODEL# MIS6
BID
D
COMPOUND
DETAILS I
C-5
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
SCALE: NTS
SCALE: NTS
NOT USED SCALE: NTS
NOT USED SCALE: NTS
SCALE: NTS
ICE BRIDGE DETAIL SCALE: NTS
SIGN DETAILSNOT USED
NOT USED
SIGN NOTES:
1. SIGN MATERIAL: 18GA
ALUMINUM
2. LETTERING COLOR =
BLACK / WHITE
3. BACKGROUND COLOR =
WHITE / BLUE
7"
SIGN NOTES:
1. SIGN MATERIAL: 18GA
ALUMINUM
2. LETTERING COLOR =
BLACK
3. BACKGROUND COLOR =
WHITE / RED
12"
SIGN NOTES:
1. SIGN MATERIAL: 18GA
ALUMINUM
2. LETTERING COLOR =
BLACK
3. BACKGROUND COLOR =
YELLOW
7"
ECSO 911
2 3
36" OC MAX
10'-0" OC MAX
FIELD VERIFY
12"
2"CLR.
2'-0"
CLR MIN.
COAX BRIDGE: 14 GA.
GALV. GRIPSTRUT 24"
WIDTH, 2" PLANK 14 GA.
SUPPORT COLUMN: 4"Ø
O.D. GALV. SCHED. 40
POST @ 10'-0" O.C. MAX
CROWN TO DRAIN; TYP.
FOOTING
MUST BE 6"
BELOW
FROST LINE,
TYP.
SIDE ELEVATIONFRONT ELEVATION
NOTE: GROUND COAX BRIDGE PER THE REQUIREMENTS
OF THE NEC STANDARDS - SEE DETAIL 1/E-2
COAX SUPPORT BLOCKS
AT 3'-0" MAX O.C.
EDGE OF
SHELTER
20" UNISTRUT W/ NUT
AND WASHER EACH
SIDE/ EACH LEVEL AS
REQUIRED
12"Ø X 48" DEEP CONC.
FOOTING; TYPICAL
COAX BRIDGE-(2) 24" WIDE
SAFETY GRATED WAVE
GUIDE BRIDGE CHANNEL,
OR APPROVED EQUAL
DUAL POST 24" ICE
BRIDGE KIT SITE PRO1
PART# 4B24D OR
APPROVED EQUAL
8"
2-1/2"
1-1/2"
8" x 8" x 1/2" PLATE
SUPPORT PIPE
1/2"Ø HILTI-KWIK-BOLT-TZ
SS EXPANSION ANCHOR
MIN 2" EMBED (TYP. OF 4)
5/16 TYP
8" x 8" x 1/2" PLATE
CONC. SLAB (IF
REQUIRED)
B
ICE-BRIDGE
SUPPORT POST
SECTION B
BASE PLATE -
OPTIONAL PIPE TO
CONC ATTACHMENT
24" WIDE WELDED STEEL
BAR GRATING
ASTM A123 HOT DIP
GALVANIZED 24" WIDE
WELDED STEEL BAR
GRATING
BID
D
COMPOUND
DETAILS II
C-6
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
4" OF 3/4" CHIP ROCK;
NO FINES
GEOTEXTILE FABRIC,
TYPAR-3401
OR EQUIVALENT
4" OF 3/4"-MINUS
CRUSHED ROCK
COMPACTED 95%
SUBSOIL COMPACTED TO 92% OF
MAXIMUM DRY DENSITY MIN. PER
ASTM-D1557
NOTE: STRIP ALL ORGANICS
3" MIN OF 3/4" MINUS CRUSHED
ROCK COMPACTED TP 95% IN
ACCORDANCE WITH ASTM-D698
GEOTEXTILE FABRIC,
MIRAFI 500X (12"
OVERLAP AT SEAMS)SUBSOIL COMPACTED TO 92% OF
MAXIMUM DRY DENSITY MIN PER
ASTM-D1557
NOTES:
1. CONTRACTOR SHALL STRIP SUPERFICIAL, SOFT, WET, ORGANIC OR DELETERIOUS SOILS TO EXPOSE FIRM AND UNYIELDING SOIL (BETWEEN 6" & 12"). IF STRIPPING IS REQUIRED DEEPER THAN 12", CONTRACTOR SHALL CONTACT THE SITE CONSTRUCTION MANGER TO DETERMINE THE APPROPRIATE STRIPPING DEPTH AT THE TIME
OF CONSTRUCTION.
2. MATERIAL AND INSTALLATION SHALL CONFORM TO CURRENT ODOT/APWA STANDARD SPECIFICATIONS AND
MANUFACTURERS RECOMMENDATIONS.
12" MIN OF 3" MINUS
CRUSHED ROCK COMPACTED
TO 95% IN ACCORDANCE WITH
ASTM-D698
3"
6" MI
N
3"
1/4" PER FOOT SLOPE
(BROOM FINISH)
6" CONCRETE SLAB
(2,500 PSI) W/
#4 BARS @ 12" O.C.
EACH WAY 3" CLR
SHELTER
DOOR &
FLOOR BY
OTHERS
4'x4' CONCRETE
STOOP
FINISH GRADE
3/4" CHAMFER
ON EDGES
CRUSHED AGGREGATE
EXISTING GROUND
1/2" NEOPRENE FILLER W/ BACKER ROD
SHELTER FOUNDATION BY OTHERS
POWER LINE TRENCH
SCALE: NTS STOOP SECTION DETAIL ACCESS ROAD SECTION DETAIL SCALE: NTS
SCALE: NTS COMPOUND ROCK SECTION DETAILSCALE: NTSSCALE: NTS GRAVEL ROAD SECTION DETAIL
SCALE: NTSNOT USED
" E
LE
CT
RI
CA
L P
RI
MA
RY
" E
LE
CT
RI
CA
L S
EC
ON
DA
RY
2'- 6"
T O
3'- 6"
±4
±4
12" MIN
CLEAR
24"±
WARNING TAPE
FINISH GRADE
UNEXCAVATED EARTH
COMPACTED FILL
(85% IN LANDSCAPED AREAS,
95% IN PAVED AREAS)
ELECTRICAL CONDUIT(S); 3"Ø
MIN, SCHEDULE 40 PVC, OR
AS SHOWN ON PLAN
COMPACTED SANDNOTES:
1. EXCAVATE TO REQUIRED DEPTH.
2. VERIFY ALL TRENCHING REQUIREMENTS PER LOCAL UTILITIES.
3. CONTRACTOR TO PROVIDE (1) 300 POUND NYLON PULL CORD
AND CONDUCTORS AS REQUIRED PER CONDUIT.
CONTRACTOR TO VERIFY WITH
ECSO PM IF SPARE CONDUIT TO BE
PLACED IN TRENCH FOR FUTURE
1 2 3
4 5
BID
D
GENERATOR &
PROPANE TANK
DETAILS
C-7
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
G
AS
G
AS
G
AS
G
AS
10'-0" REQUIRED PROPANE
TANK SETBACK BUFFER;
NO IGNITION SOURCES
WITHIN SETBACK
NOTE:
ALL CONDUIT INSIDE THE BUILDING MUST BE METAL AND BE GROUNDED PER R-56 STANDARDS.
INTERIOR SHELTER LAYOUT IS FOR REFERENCE ONLY.
THIS GENERATOR & PROPANE LAYOUT IS FOR INFORMATION ONLY AND IS PRESENTED AS A GUIDELINE. VERIFY SITE CONDITIONS AND LAYOUT PRIOR TO INSTALLATION OF ALL EQUIPMENT. INSTALL ALL EQUIPMENT PER MANUFACTURER'S
INSTRUCTIONS.
FUEL LINE SIZE PER MANUFACTURERS
RECOMMENDATION
1-CAT-5 FOR HALL EFFECT FUEL
SENSOR WIRE SUPPLIED BY
OTHERS IN 3/4" RIGID PVC
CONDUIT FROM GENERATOR TO
PROPANE TANK
3-#2 THHN PLUS #8
GROUND IN 2" RIGID
PVC CONDUIT FROM
GENERATOR TO
TRANSFER SWITCH
EQUIPMENT SHELTER
10'
LIQUID PROPANE FUEL TANK
OR EQUAL ON CONCRETE PAD
2-CAT-5 CONTROL WIRING IN 3/4"
RIGID PVC CONDUIT
AUTOMATIC TRANSFER SWITCH
CIRCUIT BREAKER PANEL
POWER CONDUIT TO STUB UP AT
METER
BORE AND WEATHERPROOF NEW PENETRATIONS
INTO SHELTER FOR NEW CONDUIT ROUTING, TYP.
LIQUID WITHDRAWL
DOME
RELIEF VALVE
2-#12 THHN PLUS #12 GROUND IN
1" RIGID METAL CONDUIT FROM
GENERATOR TO DEDICATED
CIRCUIT BREAKER @ BREAKER
PANEL, RATING 20A
MANUAL TRANSFER SWITCH
35 KW 60 HZ 44KVA AC
BACKUP GENERATOR
MANUFACTURER TBD
GENERATOR TO BE PROVIDED
BY ECSO
SEE DETAIL 5
SCALE: NTS
SCALE: NTS
SCALE: NTS GENERATOR PLAN
GENERATOR FUEL SYSTEM ELEVATION
SIDE
FRONT
SIDE
TRENCH SECTION NOT USED
SCALE: NTS GENERATOR ELEVATION NOT USED
TYPICAL GENERATOR LAYOUT
NOTE: DOCUMENTATION FOR THE GENERATOR IS TO BE PROVIDED BY THE SUPPLIER CERTIFYING THAT ALL HAZARDOUS CONTENTS WILL REMAIN CONTAINED FOLLOWING THE DESIGN EARTHQUAKE FOR THIS SITE. CERTIFICATION OF CONTAINMENT IS TO BE PROVIDED BY 1) ANALYSIS, 2) APPROVED SHAKE TABLE TESTING IN ACCORDANCE WITH SECTION 13.2.5 OF ASCE 7, OR 3) EXPERIENCE DATA IN ACCORDANCE WITH ASCE 7 SECTION 13.2.6. EVIDENCE DEMONSTRATING COMPLIANCE OF THIS REQUIREMENT SHALL BE SUBMITTED TO THE LOCAL JURISDICTION AFTER REVIEW AND APPROVAL BY THE ENGINEER OF RECORD.
NOTE: SEE GENERATOR SPEC SHEET FOR DIMENSIONS AND WEIGHTS
SCALE: NTS GENERAL NOTES
1. CONTRACTOR TO VERIFY AND CONFIRM ALL DIMENSIONS
AND CONDITIONS AND NOTIFY ENGINEER OF RECORD OF
ANY DISCREPANCIES PRIOR TO START OF WORK.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
STRUCTURAL STABILITY DURING CONSTRUCTION. THE
STRUCTURE SHOWN ON THE DRAWINGS HAS BEEN
DESIGNED FOR STABILITY UNDER THE FINAL
CONFIGURATION ONLY.
3. CODE: 2018 INTERNATIONAL BUILDING CODE (IBC).
4. THE FOOTINGS HAVE BEEN DESIGNED FOR AN ALLOWABLE
SOIL BEARING PRESSURE OF 1,500 PSF.
5. CONCRETE: FOOTINGS, F'C = 3,000 PSI MINIMUM
COMPRESSIVE STRENGTH AT 28 DAYS.
6. REINFORCING STEEL: FY = 60,000 PSI
7. STRUCTURAL AND MISCELLANEOUS STEEL SHALL BE IN
ACCORDANCE WITH AISC SPECIFICATION FOR THE DESIGN,
FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR
BUILDINGS AND SHALL BE ASTM A-36 U.O.N. ALL BOLTS
HOLES SHALL BE PUNCHED OR DRILLED; BURNING OF
HOLES SHALL NOT BE PERMITTED. ALL STRUCTURAL STEEL
SHALL HAVE ONE SHOP COAT OF PAINT.
ALL MATERIALS SHALL CONFORM TO THE FOLLOWING
STANDARDS:
PIPE: A53 GR. B (MIN. FY = 35 KSI)
SHAPES: ASTM A36/ ASTM A572 GR. 50
WIDE FLANGE: ASTM A992
TUBES: A500 GR. B, FY = 46 KSI
PLATES: A36
WELDS: E70XX ELECTRODES
STRUCTURAL BOLTS: ASTM A325N
NON-STRUCTURAL BOLTS: SAE J429 GR. 5 / F1554-36
U-BOLTS: ASTM A36
THREADED ROD: ASTM A307
SPECIAL INSPECTION BY OWNERS TESTING AGENCY
SPECIAL INSPECTIONS AND TESTING SHALL BE PERFORMED BY
AN APPROVED AGENCY IN ACCORDANCE WITH INTERNATIONAL
BUILDING CODE (IBC) CHAPTER 17 SECTIONS 1703 AND
SECTIONS 1704, AND WITH THE STATEMENT OF SPECIAL
INSPECTIONS AS REQUIRED BY IBC SECTIONS 1704.2.3 AND 1705
FOR BUILIDNG STRUCTURAL ELEMENTS SUMMARIZED AS
FOLLOWS:
1. STRUCTURAL STEEL CONSTRUCTION PER IBC SECTIONS
1705.3 AND TABLE 1705.3 INCLUDING MATERIAL
IDENTIFICATION, AND SHOP WELDING.
1'-4"1' 4"
NONVEHICULAR AREAS:
BACKFILL WITH CLEAN NATIVE
BACKFILL AND COMPACT TO
90% MAX. DRY DENSITY.
VEHICULAR AREAS: BACKFILL
WITH GRANULAR 'A' AND
COMPACT TO 95% MDD
2'
WARNING TAPE
CONDUIT, TYPICAL
BRICK SAND
FUEL LINE SIZE AND TRACE
WIRE PER MANUFACTURERS
RECOMMENDATION
NOT USED
FUEL LINE CONNECTION
PER MANUFACTURER
RECOMMENDATION
35 KW 60 HZ 44KVA AC
BACKUP GENERATOR
MANUFACTURER TBD
GENERATOR TO BE
PROVIDED BY ECSO
2-CAT-5 CONTROL WIRING
IN 3/4" RIGID PVC
CONDUIT
3-#2 THHN PLUS #8
GROUND IN 2" RIGID PVC
CONDUIT
1-CAT-5 HALL EFFECT
FUEL SENSOR WIRING IN
3/4" RIGID PVC CONDUIT
2-#12 THHN PLUS #12
GROUND IN 3/4" RIGID PVC
CONDUIT (BLOCK HEATER
AND BATTERY CHARGER)
FUEL LINE CONNECTION PER
MANUFACTURER RECOMMENDATION
35 KW 60 HZ 44KVA AC
BACKUP GENERATOR
MANUFACTURER TBD
GENERATOR TO BE
PROVIDED BY ECSO
(4) 1/2"Ø X 5" EMBED.
TITEN HD ANCHORS,
SEE DETAIL #3 THIS
SHEET
FRONT
SHELTER FLOOR
STRUCTURE
(4) 3/4"Ø X 5" EMBED.
TITEN HD SS
ANCHORS
35 KW 60 HZ 44KVA AC
BACKUP GENERATOR
MANUFACTURER TBD
GENERATOR TO BE
PROVIDED BY ECSO
1 2 3
9SCALE: NTS 6 SCALE: NTS 7 SCALE: NTS 8 SCALE: NTS
SHUT-OFF VALVE
LEGEND
UNION
PRESSURE REGULATOR
SOLENOID VALVE
FLEXIBLE CONNECTION
3/4" DIA. CONDUIT W/ 1-4/18 AWG
1/4" FLEX FUEL LINE FROM PROP
TANK TO REG
SOLENOID VALVE AND
REGULATOR TO COME
WITH GENSET
TO CARBURETOR
NOTES:
1. GROUND SYSTEM SHOULD COMPLY WITH INDUSTRY STANDARDS
2. CONFIRM CONNECTIONS PROVIDED WITH FUEL TANK
3. USE GASEOUS LP VAPOR WITHDRAWAL SYSTEM
4. TO CODE OFFICIAL, PAD IS FOR EQUIPMENT ONLY (NO BUILDINGS)
5. CONTRACTOR IS TO VERIFY THAT ALL PROPOSED ANCHORS WILL PROVIDE ADEQUATE FIT
PRIOR TO POURING CONCRETE PADS, NOTIFY DON CUSHING ASSOCIATES IF ANY
DISCREPANCIES EXIST
C-9
NOTES:
1. PROPANE TANK REGISTERED WITH
NATIONAL BOARD AND COMPLIES
AND INSTALLED PER NFPA 58 CODE
2. PROPANE TANK INSTALLED AT LEAST
10 FT FROM EXTERNAL SOURCE OF
IGNITION
TRINITY LIQUID
PROPANE FUEL
TANK OR EQUAL
SEE PROPANE TANK SPEC SHEET
FOR DIMENSIONS AND WEIGHTS
# 4 X 25"X12" @
12" O.C. TYP.
8" 4"
12"
1ST STAGE REG; LV4403TR96 14" IN
AND 3/4 " OUT
2ND STAGE REG LV5503B8;
4" IN AND 1" OUT
SNAP2IT NON-METALLIC CONN 34"
NM LIQUID TIGHT CONN CAT 5
GALV. 1 12" Ø STAND PIPE POST
(1.9" OD) W/ CAP
SHUT-OFF VALVE W/ DRIP LEG
HOR. UNI-STR W/ NON
CORR PIPE CLAMP
SERVI-SERT TOP-CON RISER
5'-0" X 10'-0" X 8" CONCRETE
PAD W/ #4 @ 12" O.C. EA WAY
GROUND PROPANE TANK
PER NEC REQUIREMENTS
DOME
PLUG
RELIEF VALVE
VAPOR WITHDRAWAL
# 4 CONT. IN
TURNED-DOWN EDGE
FOOTING
FINISHED GRADE
6" MIN. COMPACTED GRAVEL
BASE UNDER PERIMETER
FOOTING AND SLAB
FUEL GAUGE, R3D
3/4" ULTRATITE LIQUIDTIGHT FLEX
NON-MET PVC COND FOR 1-4/18 AWG
FOR HALL EFFECT FUEL SENSOR,
DS_1318
CUSTOM PROPANE TANK
CANOPY GENERATOR CANOPY NOT
SHOWN FOR CLARITY
UFER GROUND
5/8" X 5" SS TITEN HD
ANCHORAGE, TYP
18"
BACKUP GENERATOR
MANUFACTURER TBD
SHELTER FLOOR
STRUCTURE
BID
D
EQUIPMENT
SHELTER
FOUNDATION PLAN
C-8
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
N
(2) #5 CONT. @
MID HT. OF FTG.
SCALE: NTS EQUIPMENT SHELTER FOUNDATION PLAN
#5 @ 12" O.C., EA. TYP.
CONCRETE SLAB
SEC
A
22"
TROWELED FINISH
#5 @ 12" EW
(BOTH DIRECTIONS)
#5 BARS @
5" O.C. @ TOP
& BOTT., (TYP)
2'-0"
(SEE NOTE 9)
3/4" MINUS CRUSHED
ROCK (COMPACTED 95%)
(SEE NOTE 8)
±6
GEOTEXTILE FABRIC
(SEE NOTE 8)
1"
CHAMFER
STRUCTURAL FILL UNDER SHELTER
SLAB AND UNDER GRADE BEAMS
(SEE NOTE 5 AND NOTE 10)
6"
1/2" PREFORMED JOINT FILLER & SEALER, TYP
2-3/8"
CLR
3" CLR
(TYP)
8" CLR
(TYP)
2-3/8"
CLR
#3 TIES @
12" O.C. (TYP)
3/4" MINUS CRUSHED
ROCK (COMPACTED 95%)
(SEE NOTE 8)
5"
PROPOSED VAPOR BARIER
(SEE NOTE 7)
NOTES:
1. ULTIMATE COMPRESSIVE STRENGTH OF CONCRETE AT 28 DAYS SHALL BE 3000 PSI, UNLESS
OTHERWISE SPECIFIED.
2. REINFORCING BARS SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 "DEFORMED
AND PLAIN BILLET STEEL BARS FOR CONCRETE REINFORCEMENT," LATEST EDITION, GRADE
60.
3. LAP LENGTH FOR SPLICES SHALL NOT BE LESS THAN CLASS B SPLICE, UNLESS OTHERWISE
SPECIFIED. WELDING OF REINFORCEMENT WILL NOT BE PERMITTED.
4. CONTRACTOR MAY USE EARTH FORMS FOR UNEXPOSED CONCRETE WHERE SOIL IS FIRM
AND STABLE. EARTH FORMS SHALL BE TRENCHED NEATLY AND ACCURATELY. SIDES OF
FOUNDATIONS, WHERE EARTH SLOUGHS, SHALL BE FORMED. EARTH FORMS SHALL BE
TAMPED FIRM, AND CLEANED OF ALL DEBRIS AND LOOSE MATERIAL, BEFORE DEPOSITING
CONCRETE.
5. STRUCTURAL FILL USED FOR SITE GRADING SHALL BE FREE FROM TOP SOIL, ORGANIC
CONTAMINATED SOIL, AND ROCK FRAGMENTS HAVING A MAXIMUM DIMENSION GREATER
THAN 3 INCHES. MATERIAL SHALL BE CLEAN AND SHALL BE SUBJECT TO THE FOLLOWING
RESTRICTIONS.
SILT CLAYS OR SANDY CLAY
PLASTICITY INDEX 10 TO 24
LIQUID LIMIT <45
CLAYEY SANDS OR SLIGHTLY CLAYEY SILTY SANDS
PLASTICITY INDEX 3 TO 15
LIQUID LIMIT <35
6. MINIMUM CONCRETE COVER FOR REINFORCEMENT SHALL BE 3 INCHES FOR CONCRETE
CAST AGAINST AND PERMANENTLY EXPOSED EARTH AND 1-1/2 INCHES FOR TOP BARS ON
SIDEWALK AND SHELTER FOUNDATIONS.
7. VAPOR BARRIER SHALL BE VAPORBLOCK 10, OR APPROVED EQUAL.
8. CRUSHED ROCK AND GEOTEXTILE FABRIC IN THE COMPOUND AREA SHALL MEET THE
REQUIREMENTS OF DETAIL 3 ON DWG C-5 AND ALL APPLICABLE GRADING NOTES.
9. IN INSTANCES WHERE ROCK IS ENCOUNTERED AT LESS THAN 2'-0", CONCRETE MAY BEAR
ON THE ROCK.
10. PAINT SHEAR PLATES WITH COLD GALV.
SECTION A
FOUNDATION PLAN
UFER GROUND, SEE
ELECTRICAL SHEETS
FINISH GRADE
SAW CUT CONTROL JOINTS
1/8" WIDE AND 1 1/4" DEEP,
JUST AFTER SET FIRM
USING EARLY ENTRY SAW
GRADE BEAM (TYP)
24'
SHELTER TIE-DOWN, TYP
PER MANUFACTURER REQUIREMENTS
BID
D
GENERATOR
SHELTER
FOUNDATION PLAN
C-9
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
04-19-23 SITE SKETCH
07-19-23 PRELIMINARY ZONING DRAWINGS
07-21-23 REVISED PRELIMINARY ZONING DRAWINGS
09-25-23 FINAL ZONING DRAWINGS
11-13-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
MOUNT ISABELLE
6701 FOREST CREEK RD
JACKSONVILLE, OR 97530
12725 SW MILLIKAN WAY
STE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing Civil Engineers
Civil Engineers
NOT F
OR
CONSTR
UCTIO
This is the start of the file's text. The full file is on GovTribe.