MEP_SPECIFICATION_9-15-2025.pdf
PDF 1 MB Posted
- Attached to
- B026-09 Station 5 Boiler Replacement
- Solicitation number
- B026-09
- Issued by
- New Haven County, Connecticut
About this file
This is a Project Manual and specification document for the City of Meriden, Connecticut, detailing the comprehensive replacement of the boiler system at Fire Station #5, located at 1075 East Main Street in Meriden, Connecticut. The project requires furnishing all labor, materials, equipment, and services to replace the existing boiler with a new gas-fired condensing boiler (Lochinvar Knight XL Model FTXL1000N-120 or approved equivalent such as Viessmann or Buderus), along with all associated mechanical, electrical, and plumbing systems necessary for complete installation and operation. The work encompasses mechanical demolition and new work, electrical systems, plumbing installations including hot and cold water lines, fuel gas piping, vibration isolation and seismic restraints, mechanical insulation, heating equipment installation, and comprehensive testing and balancing of HVAC systems. All work must comply with the 2022 Connecticut State Building Code, 2021 IBC, 2021 IPC, 2021 IMC, 2021 NFPA 101, Connecticut Public Health Code, NEC, ASME standards, and all applicable local codes and regulations. The contractor must provide temporary domestic hot water during the construction period. A mandatory site inspection was scheduled for November 19, 2025, at 10:00 a.m., with questions due by December 3, 2025, at 4:00 p.m. Sealed electronic bids must be submitted via the City eProcurement Portal no later than 11:00 a.m. on December 10, 2025. The contract includes an 18-month guarantee period from the date of acceptance, with all defective materials or workmanship to be repaired or replaced at no additional cost to the City of Meriden.
The project budget is listed at $1,001, with account number 00543. Each bid must include a bid bond equal to ten percent of the bid amount, along with a Non-Collusive Statement, Bidders' Qualification Statement, and Surety Guaranty Form. The successful contractor will be required to provide both a Labor and Material Payment Bond and a Performance Bond for 100% of the contract price. Contractors must maintain comprehensive insurance coverage, including General Liability ($1,000,000 to $2,000,000), Auto Liability ($1,000,000), and Workers' Compensation at statutory limits. Prevailing wage rates apply, with hourly rates ranging from $21.42 to $66.72 depending on worker classification. Liquidated damages are set at $250 per calendar day for failure to complete work within the stipulated timeline. The City of Meriden applies a local preference policy allowing Meriden-based businesses submitting bids within ten percent of the lowest bid to potentially accept the award. No specific set-asides or restrictions on bidder types are designated for this procurement.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CITY OF MERIDEN
PROJECT MANUAL
for
MERIDEN FIRE STATION #5
BOILER REPLACEMENT
EAST MAIN AND POMEROY AVENUE
MERIDEN, CONNECTICUT 06451
PROJECT #
Bemis Associates LLC 185 Main Street
Farmington, Connecticut
September 15, 2025
MERIDEN FIRE STATION #5
BOILER REPLACEMENT
MERIDEN, CONNECTICUT
SECTION 00020 LIST OF DRAWINGS
COVER
MECHANICAL
M1.1 BOILER ROOM - MECHANICAL DEMOLITION AND NEW WORK PART PLANS
M1.2 MECHANICAL DEMOLITION AND SCHEMATIC PIPING DIAGRAM
ELECTRICAL
E1.1 BOILER ROOM - ELECTRICAL DEMOILITION AND NEW WORK PART PLANS
END OF LIST OF DRAWINGS
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 1
SECTION 20 00 50 - GENERAL CONDITIONS FOR MECHANICAL AND ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS:
A. The General provisions of the Contract, including General and Supplementary Conditions, and Division 1, General Requirements apply to the work specified in this Section.
B. Scope of Work: This Section contains special provisions for Divisions 22,23 and 26.
1.2 EXAMINATION OF SITE AND DRAWINGS:
A. Before submitting his bid, Contractor shall visit site with plans and specifications in hand, shall consult with the Engineer and shall become thoroughly familiar with all conditions under which his work will be done since he will be held responsible for any assumptions he may make in regard thereto.
B. The Contractor shall verify and obtain all necessary dimensions at the building.
C. Certain present building clearances are available for handling equipment.
1.3 INTENT:
A. Finished Work: The intent of the specifications and drawings is to call for finished work, completed, tested and ready for operation.
B. Good Practice: It is not intended that the drawings show every pipe, fitting or minor detail and it is understood that while the drawings must be followed as closely as circumstances will permit, the systems shall be installed according to the intent and meaning of the Contract Documents and in accordance with good practice.
C. Work under each Section shall include giving written notice to the City of Meriden within 15 days after the Award of the Contract of any materials of apparatus believed inadequate or unsuitable or in violation of any laws or codes, or items of work omitted. In the absence of such written notice, it is mutually agreed that work under each Section has included the cost of all required items and labor for the satisfactory functioning of the entire system without extra compensation.
D. Any apparatus, appliance, material or work not shown on drawings but mentioned in specifications or vice versa, or any incidental accessories necessary to make the work complete and perfect in all respects and ready for operation, even if not particularly specified, shall be furnished and installed by Contractor at no additional cost to the City of Meriden.
E. Prior to receipt of bids, Contractors shall give written notice to Engineer of any materials or apparatus believed inadequate, unsuitable or in violation of laws, ordinances, rules or regulations of authorities having jurisdiction and any necessary items or work omitted. In the absence of such written notice, it is mutually agreed that Contractor has included the
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 2 cost of all required items in his proposal and that he will be responsible for approved satisfactory functioning of systems without further compensation.
F. In all cases where apparatus is herein referred to in singular number, it is intended that such reference include as many such items as are required to complete work.
G. If not otherwise specified or shown on plans, apparatus and materials shall be installed in accordance with manufacturer's published recommendations and instructions and to the complete satisfaction of the Engineer.
H. It is the intent of these specifications for Mechanical and Electrical Contractors and/or their subcontractors or equipment suppliers to furnish all equipment complete with all accessories.
1.4 REGULATIONS:
A. Codes: All work shall be done in strict accordance with the 2022 Connecticut State Building Code, 2022 Connecticut State Fire Safety Code, 2021 IBC, 2021 IPC, 2021 IMC, Connecticut Public Health Code, 2021 NFPA 101, all applicable NFPA Codes, NEC, UL, NEMA, O.S.H.A., with all requirements of local utility companies and the requirements of all governmental departments having jurisdiction.
B. Precedence: Requirements of the above shall take precedence over plans and specifications.
C. Equipment construction standards shall be as follows: Pressure vessels shall be constructed in accordance with the ASME Code, all electrical equipment shall be UL listed and approved and conform to the N.E.C., gas equipment shall be approved by A.G.A. and conform to N.F.P.A. Codes, piping materials, fittings, valves and accessories shall be constructed in accordance with A.S.T.M. and A.N.S.I. standards for class of work involved.
All equipment and materials shall be new and of domestic manufacture. All the above codes shall be referenced and dated in the Connecticut Basic Building Code.
D. Wherever discrepancies occur between above regulations and agencies and contract drawings and specifications, the requirements of above shall take precedence, except that the contract drawings and specifications shall be minimum requirements and that contractors shall advise engineer of any required changes before proceeding with work.
1.5 APPROVED FITTINGS:
A. No material other than that contained in the "Latest List of Electric Fittings" approved by the Underwriters' Laboratories, Inc., shall be used in any part of the work.
All wiring, conduit, switches and other material for which label service has been established, shall bear the label of the Underwriters' Laboratories, Inc.
1.6 PERMITS, FEES:
A. Include all necessary notices, obtain all permits and pay all governmental taxes, fees, and other costs. File all necessary plans, prepare all documents and obtain all necessary approvals of all governmental departments having jurisdiction. Obtain all required
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 3
Certificates of the City of Meriden before request for acceptance and final payment for the work.
1.7 DEFINITIONS:
A. Words "finish" or "finished" refer to all rooms and areas listed in Finished Schedule on Drawings. All rooms and areas not covered in Schedule, including underground tunnels and areas above ceilings, shall be considered not finished except as otherwise noted.
B. The word "provide" means to "furnish and install" reference item.
1.8 PROTECTION:
A. Work under each section shall include protecting the work and materials of all other sections from damage by work or workmen, and shall include making good any and all damage thus caused.
B. Each section shall be responsible for work and equipment until finally inspected, tested and accepted. Protect work against theft, weather, injury or damage and carefully store material and equipment received on site which is not immediately installed. Close open ends of work with temporary covers or plugs during construction to prevent entry of obstructing materials.
C. If so specified under the respective section, work may include receiving, unloading, uncrating, storing, protecting, setting in place and connecting up completely of any motor starters, control equipment having mechanical/electrical service connections which may be furnished by The City of Meriden or furnished under another section. Work under each section shall include exercising special care in handling and protecting equipment and fixtures. Any of the above equipment and fixtures which are missing or damaged by reason of mishandling or failure to protect shall be replaced at no additional cost to the City of Meriden.
1.9 EQUIPMENT SUBSTITUTIONS AND DEVIATIONS:
A. Wherever more than one manufacturer is mentioned in specifications and drawings, any of these named are considered equally acceptable to that on upon which design was based and, providing all requirements are met, insofar as performance, space requirements, noise levels and special accessories or materials are concerned, any of those named may be included in Contractor's bid.
B. Where Contractor proposes to use an item of equipment which differs from that upon which design was based, which required any redesign of structure, partitions, foundations, piping, wiring or of any other part of Mechanical or Electrical Layout, all such redesign, new drawings or detailing required shall be prepared by Contractor at his own expense for approval of Engineer.
C. Where approved substitutions or deviations require a different quantity, size or arrange of structural supports, wiring, conduit, piping, ductwork, and equipment from that upon which design was based, all additional items required by the systems shall, with the approval of Engineer, be furnished by Contractor at no additional cost to The City of Meriden.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 4
1.10 ELECTRICAL WORK:
A. The Electrical Section includes all power wiring for all electrical switches, motor starters and unmounted motors, furnished at the job site by other sections or furnished under the Electrical Sections as stated in other sections of the specifications.
B. The Electrical Section shall install and wire all starters, switches and controls, as specified and/or shown on drawings. This shall include all operating and safety controls. Refer to sections 260000 and 260500 for additional information.
C. Electrically operated equipment supplied by other sections which will be installed and wired by Electrical Section shall be delivered to him with detailed instructions for their installation and wiring in sufficient time and proper sequence to enable him to meet his work schedule.
D. Control devices that include mechanical elements, such as float switches, shall be installed by the section furnishing them, but be wired by the Electrical Sections.
E. Equipment which includes a number of correlated electrical control devices mounted in a single enclosure or on a common base with equipment shall be supplied for installation completely wired as unit with terminal boxes and ample leads and/or terminal strips, ready for electrical wiring.
F. Electrical Contractor shall furnish local disconnect switch for all equipment and manual motor starter for fractional HP motors.
1.11 DRAWINGS:
A. The mechanical and electrical drawings are intended to supplement each other and are to be considered as a unit which, taken together in conjunction with the specifications, completely describes the work to be done. All drawings shall be checked to verify spaces in which work will be installed. Where headroom or space conditions appear inadequate, notification shall be given to Engineer before proceeding with installation.
B. The Engineer may without charge, make modifications in the layout as needed to prevent conflict with work of other trades or for proper execution of the work.
C. Note that the drawings are diagrammatic and indicate the general arrangement of the Mechanical and Electrical Equipment and systems, without showing every detail and fitting.
D. Where conflicts occur between drawings and specifications or within either, the item or arrangement of better quality, greater quality or highest cost shall be included in Contract price. Engineer shall determine the manner or item with which work shall be installed.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 5
E. Keep one complete set of all drawings, specifications, shop drawings and addenda on the premises at all times in good condition and available to the Engineer and The City of Meriden.
1.12 REVIEWS:
A. The materials, workmanship, design and arrangement of all work installed under the Mechanical and Electrical sections shall be subject to the review of the Engineer.
B. Where any specific material process of method of construction or manufactured article is specified by name or by reference to the catalog number of a manufacturer, the specifications are to be used as a guide and not intended to take precedence over the basic duty and performance specified or noted on drawings. In all cases, the specific characteristics of the equipment offered for approval, shall be indicated on the shop drawings.
C. All component parts of each item of equipment or device shall bear the manufacturer's nameplate, giving name of manufacturer, description, size, type, serial or model number, electrical characteristics, etc. in order to facilitate maintenance or replacement. The nameplate of a subcontractor or distributor will not be acceptable.
D. If material or equipment is installed before it is reviewed, it shall be removed and replaced at no extra charge to the City of Meriden if, in the opinion of the Engineer, the material or equipment does not meet the intent of the drawings and specifications.
1.13 SHOP DRAWINGS:
A. Contractor shall submit for review electronic copies of shop drawings of all new equipment, materials, piping, lighting fixtures, devices, panels and wiring. Engineer's review of shop drawings must be completed before any equipment is purchased or any work is installed.
B. Shop drawings shall consist of manufacturer's certified scale drawings, cuts or catalog, including descriptive literature and complete certified characteristics of equipment, showing dimensions, capacity, code requirements, motor and drive testing as indicated on the drawings or specifications. Also, sheet metal fabrication drawings drawn to scale of 1/4" to the foot or larger.
C. Certified performance curves for all pumping equipment shall be submitted for review.
D. Samples, drawings, specifications, catalogs, etc. submitted for review shall be properly labeled indicating specific service for which material or equipment is to be used, division and article number of specifications governing Contractor's name and name of job.
E. Catalog, pamphlets or other documents submitted to describe items on which review is being requested, shall be specific and identification in catalog, pamphlet, etc. of item submitted shall be clearly made in ink. Data of a general nature will not be accepted.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 6
F. Review stamp rendered on shop drawings shall not be considered as a guarantee of measurements of building conditions.
Where drawings are reviewed, said review does not mean that drawings have been checked in detail. Said review does not in any way relieve the Contractor from his responsibility or necessity of furnishing material or performing work as required by the Contract Drawings and Specifications.
G. Failure by the Contractor to submit shop drawings in ample time for checking shall not entitle him to an extension of Contract and no claim for extension by reason of such default will be allowed.
H. Prior to submission to shop drawings, the Contractor shall thoroughly check each shop drawing, reject those not conforming to the specifications and indicate by his signature that the shop drawings submitted in his opinion meet Contract requirements.
1.14 CUTTING AND PATCHING:
A. All cutting of openings in walls, floors, partitions, etc. must be done by the Electrical and/or Mechanical Contractor as required to install the work including all cutting of existing construction work. Cutting shall be neatly done and limited to the minimum size necessary.
Contractor shall patch and restore to its original condition any work disturbed as a result of work under this Contract.
PART 2 - PRODUCTS
2.1 MATERIALS AND WORKMANSHIP:
A. All materials and apparatus used shall be new, of first class quality and shall be furnished, delivered, erected, connected and finished in every detail. No materials or apparatus used shall be discontinued or about to be discontinued items.
B. The Engineer shall have the right to reject any part of the work in case material or workmanship is not of satisfactory quality.
C. Any unacceptable work and material shall be replaced with acceptable work and material at no additional expense to the City of Meriden.
D. In case there is any doubt of the acceptability of any material, submit samples to the Engineer for approval and only definite approval in writing from the Engineer shall be evidence of such approval.
E. Such approval shall also be subject to the satisfactory installation of the material.
F. The work in each of these sections shall be constantly under the direction of a competent superintendent who shall be on the premises during such period as the work is in progress.
The superintendent shall familiarize himself with the work of all other sections involved insofar as they relate to or in any way affect the work of these sections, and shall coordinate the work.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 7
G. Unless otherwise noted, all equipment and materials shall be installed and/or applied in accordance with the recommendations of the manufacturer of said equipment, including the performance of any tests recommended by the manufacturer.
2.2 EQUIPMENT VARIATIONS:
A. In these specifications and on the accompanying drawings, one or more makes of materials, apparatus or appliances have been specified for use in this installation.
This has been done for convenience in fixing the standard of workmanship performance of any materials, apparatus or appliance which shall be substituted for those mentioned herein shall also conform to these standards.
B. Where no specified make or material, apparatus or appliance is mentioned, any first class product made by a reputable manufacturer may be used, providing it conforms to the requirements of these specifications and meets the approval of the Engineer prior to installation.
C. To substitute other makes of materials, apparatus or appliance, than those mentioned under the mechanical or electrical sections, a request in writing to be allowed to make the substitution shall be made. This request shall be accompanied by complete plans and specifications of the substitution offered. If so requested by the Engineer, also submit samples of both the specified material or appliance and the substitute.
2.3 MOTOR CONTROL:
A. All motors will be fed from a motor starter. Motor starters shall be furnished by each respective trade for motor driven equipment provided by them. The Electrical Contractor shall install the starters and shall provide all power wiring to the starters, and from the starters to the motors they control. Where required, remote pushbuttons, plates and pilots will be furnished with the starter and will be installed by the Electrical Contractor, unless otherwise called for under the Temperature Control Section of these specifications. All starters for motors which are to be interlocked with another motor shall have suitable auxiliary contacts.
B. All small motors without built-in thermal protection shall be furnished with thermal switches. These switches and pilots shall be furnished by the Electrical Contractor.
2.4 ELECTRIC MOTORS:
A. All motors 1/2 h.p. and above shall be integral horsepower polyphase induction motors conforming to NEMA standards MG-1-1967 and shall be T-frame design in sizes 143 T through 445 T. Each shall be NEMA design B with minimum torque valves per MG 1-12.37 and 12.38.
B. Duty shall be continuous, ambient temperature 40 degrees maximum, allowable temperature rise for open drip-proof -90 degrees, TEFC, 80 degrees C with Class B insulation rating all per MG 1-12.42.
C. Horsepower, speed and frame sized per MG 1-10, 32, 13.02 and 13.06a.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 8
D. Enclosures - open drip-proof and TEFC per MG 1-1.25, 1.26 and 1.27.
E. All dimensions per MG 1-11.31a, 11.32a and 11.34a. All motors shall have stainless steel nameplates with NEMA voltage standards shown.
F. Locked rotor KVA per horsepower shall be designated by proper NEMA code letter per
MG 1.10.37.
G. All motors shall be premium efficiency type with a full load efficiency range of 80 percent to 95 percent. High efficiency motor rating shall meet Northeast Utilities Energy Action Program in accordance with the following schedule:
MINIMUM NOMINAL MOTOR EFFICIENCIES
HP OPEN DRIP PROOF HP TOTALLY ENCLOSED
MINIMUM EFFICIENCY MINIMUM EFFICIENCY
1200 1800 3600 1200 1800 3600
1.5 7.5
82.5% 86.5% 87.5% 89.5% 89.5% 91.7% 91.7% 92.4% 92.4% 93.0% 93.6% 94.1% 94.1% 95.0% 95.0% 95.0%
85.5% 86.5% 86.5% 89.5% 89.5% 91.0% 91.7% 93.0% 93.0% 93.6% 94.1% 94.1% 94.5% 95.0% 95.0% 95.4%
80.0% 85.5% 86.5% 86.5% 89.5% 89.5% 90.2% 91.0% 92.4% 93.0% 93.0% 93.6% 93.6% 94.1% 94.5% 94.5%
1.5 7.5
82.5% 87.5% 88.5% 89.5% 89.5% 91.7% 91.7% 92.4% 92.4% 93.0% 93.6% 94.1% 94.1% 94.5% 95.0% 95.4%
85.5% 86.5% 86.5% 89.5% 89.5% 91.7% 91.7% 92.4% 93.0% 93.6% 93.6% 94.1% 94.5% 95.0% 95.4% 95.4%
78.5% 85.5% 86.5% 88.5% 89.5% 91.0% 91.7% 91.7% 92.4% 93.0% 93.0% 93.6% 94.1% 94.1% 94.5% 95.0%
H. Service Factors - open-drip-proof, 1 h.p. through 200-1.15 TEFC all horsepower - 1.0.
I. Noise level within NEMA standard MG 1-12.49.
J. In addition to the above, all motors 1 through 20 h.p. shall be TEFC with drain holes for both horizontal and vertical positions. Each shall be equipped with deep groove double shielded ball bearings prelubricated with provisions for regreasing.
K. Motors smaller than 1/2 h.p. shall be capacitor-start or split-phase type designed for 120 volts, single phase, 60 cycles alternating current.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 9
2.5 ELECTRICAL MOTOR STARTERS:
A. Motor starters shall be furnished by each respective trade for motor driven equipment provided by them. The Electrical Contractor shall install the starters and shall provide all power wiring to the starters, and from the starters to the motors they control.
B. Motor starters shall conform to requirements of NEC, NEMA, UL, CSA, and ANSI and shall be suitable for the required horsepower, duty, voltage, phase, frequency, service, and location. All starters shall be furnished in NEMA enclosures suitable for the environment in which they are to be located.
C. All starters shall be of the same manufacture and shall be furnished in Cutler-Hammer, Square D, General Electric, or Allen Bradley.
D. Thermal Overloads:
1. All motors 1/8 horsepower or larger shall be provided with thermal-overload protection. Thermal overloads shall be melting alloy ambient temperature compensating type.
2. Thermal overloads shall be sized in accordance with NEC requirements for the nameplate data of the motor(s) as actually delivered to the site.
E. Starters for manual control of single phase motors up to one (1) horsepower furnished without integral thermal overloads shall be combination manual disconnect switch and starters with thermal overload protection for each ungrounded leg. Starters shall be inoperable if a thermal unit is removed. These starters shall be 2-pole and shall be provided with green neon pilot light and handle guard/lock-off.
F. Starters for three phase motors shall be full voltage, circuit breaker combination magnetic starters. All circuit breaker combination magnetic starters shall include melting alloy type thermal overload protection, low voltage protection, and two (2) sets of auxiliary normally open and normally closed contacts. Thermal overload protection shall be provided in each ungrounded leg. Starters shall be inoperable if a thermal unit is removed.
All circuit breaker combination magnetic starters shall be equipped with control power circuits. Provide starters with control power transformers of secondary voltage required for the control power circuitry. Provide control power transformers with secondary fusing.
The disconnect handle on circuit breaker combination magnetic starters shall always be in control of the disconnect device with the door opened or closed. The disconnect handle shall be clearly marked as to whether the disconnect device is "on" or "off", and shall include a two-color handle grip, the black side visible in the "off" position, and the red side visible in the "on" position.
1. All circuit breaker combination magnetic starters for manual control of three phase motors shall have start-stop push buttons in the cover and shall be provided with red and green pilot lights.
2. All circuit breaker combination magnetic starters for automatic or interlocking control of three phase motors shall have hand-off-automatic selector switches in the cover and shall be provided with red and green pilot lights.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 10
G. Starters shall be furnished as part of respective equipment furnished under each Division.
PART 3 - EXECUTION
3.1 CONNECTING TO EXISTING UTILITIES:
A. Connections to existing utilities that will interrupt the service to the present buildings shall be made at a time agreed upon by the City of Meriden, B. If it is necessary to make connections to existing utilities outside the regular working hours, this shall be noted on the written work order and the respective Contractor will be paid for the additional cost of labor over and above what it would cost at regular day time rates.
3.2 FREIGHT, CARTING AND RIGGING:
A. Contractor shall pay all freight and carting charges necessary to deliver all equipment furnished under his Contract to the site and furnish all necessary rigging to properly rig and set the apparatus on the foundations, frames, etc.
B. All scaffolding, blocks and tackle, ropes and chains and other equipment necessary to rig and set the apparatus shall be furnished by the Contractor.
C. The Contractor shall set, level and align all equipment before starting operations.
3.3 SEISMIC RESTRAINTS:
A. It is the intent of this seismic restraint portion of the specification to provide restraint of all non-structural building system components provided in Sections 15 and 16 in Seismic Zone II. Restraint systems and devices are intended to withstand, without failure, the "G" forces detailed in the chart below:
Design Level of Acceleration At Equipment Center of Gravity Seismic Zone 2) (Av - >0.1 to 0.19)
Elevation (feet rel. to grade level)
Rigid* Mnt'd Equip
Non-Struct.
Architect Component
Flexible* Mnt'd Equip
Pipe, Duct, Cable trays, Conduit, Etc.
Life Safe.
Equip
Below Grade up to 20 feet above grade
0.125 "g" 0.250 "g" 0.500 "g" 0.350 "g" 1.000 "g"
21 ft. - 300 ft. 0.500 "g" 0.550 "g" 0.750 "g" 0.650 "g" 1.000 "g"
301 ft. - 600 ft. 0.750 "g" 0.900 "g" 1.000 "g" 1.000 "g" 1.000 "g"
* Rigid mounted equipment is any equipment mounted directly to structure. Flexible mounted equipment is any equipment mounted on resilient supports, ceiling suspended, roof supported or mounted on an independent frame with any primary natural frequency below 16 Hz.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 11
B. Seismic restraints shall be as required by 2021 IBC, Chapter 16 and State of Connecticut 2022 Building Code.
C. Seismic Certificate and Analysis
1. Seismic restraint calculations must be provided for all connections of equipment to the structure.
2. Calculations to support seismic restraint designs must be stamped by a registered professional engineer licensed in the State of Connecticut.
3. Analysis must indicate dead loads, derived loads, and materials used for connections to equipment and structure. Analysis must detail anchoring methods, bolt diameters, embedment, and weld length.
4. A seismic design errors and omissions insurance certificate must accompany submittals.
D. Submit drawings showing locations of all seismic restraints for equipment, piping, and conduit provided under Sections 15 and 16:
1. The term EQUIPMENT includes ALL non-structural components. These specifications are applicable within the facility and 5 feet outside of the foundation wall. Equipment buried underground is excluded but entry of services through the foundation wall is included. Equipment referred to below is a partial list;
(equipment not listed is still included in this specification).
Air Separators Water Heater Light Fixtures Bus Ducts Piping Boiler Pumps (All types) Cable Trays Switching Gear Tanks (All types) Conduit All Electrical Panels
E. Submittals shall include a listing of all isolated and non-isolated equipment to be restrained.
F. Seismic restraints shall not be required for the following installations:
1. Piping in mechanical rooms less than l 1/4-inch inside diameter.
2. All other piping less than 2 1/2-inch inside diameter.
3. All electrical conduit less than 2 1/2-inch inside diameter.
4. All rectangular air-handling ducts less than 6 square feet in cross-sectional area.
5. All round air-handling ducts less than 28 inches in diameter.
6. All piping suspended by individual hangers 12 inches or less in length from the top of the pipe to the bottom of the support for the hanger.
7. All ducts suspended by hangers 12 inches or less in length from the top of the duct to the bottom of the support for the hanger.
G. Life safety systems defined:
1. All systems involved with fire protection including sprinkler piping, service water supply piping, fire dampers and smoke exhaust systems.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 12
2. All systems involved with and/or connected to emergency power supply including all generators, transfer switches, transformers and all flowpaths to fire protection and/or emergency lighting systems.
3. Fresh air relief systems on emergency control sequence including air handlers, conduit, duct, dampers, etc.
3.4 COOPERATION WITH OTHER TRADES:
A. No piping, conduit, valves, boxes, etc., shall be installed until the entire run has been checked for clearance and the work has been coordinated between all the trades. Each tradesman shall be responsible for taking his own field measurements and maintaining proper clearance from the City of Meriden's equipment and the work of other trades, and for coordinating his work with that of other Contractors and The City of Meriden. Furnish all necessary information, dimensions, templates, etc. in order that a perfectly coordinated job will result.
B. Contractor shall carry out his work in conjunction with other trades and shall give full cooperation to other trades. Contractor shall furnish all information necessary to permit work of all trades to be installed in a satisfactory manner.
C. Where space is so limited that Contractor's work shall be installed in close proximity to the work of other trades or where it is evident that Contractor's work will interfere with other trades, he shall assist in working out space conditions to make satisfactory adjustments.
If required or directed by Engineer, the Contractor shall prepare composite working drawings and sections of not less than 3/4" -1'-0" scale clearly showing how his work is to be installed in conjunction with other trades; he shall make corrections necessary to satisfactorily complete installation at no additional cost to The City of Meriden.
D. All supports for hanging material to be connected to steel structure shall be installed prior to installation of fire proofing material. Any damage to fireproofing caused by late installation of hanging material shall be repaired by the Fire-proofing Contractor at the expense of the Contractor responsible.
E. The Heating Contractors shall give to the Electrical Contractor all information on switches, controls, pilots, etc. furnished under the Heating Contracts, together with makes and catalog numbers where required to permit the Electrical Contractor to leave the proper boxes to receive same. This information shall be given well in advance so that the Electrical Contractor may install his work as construction progresses. In the event that this information is not given in time to permit the Electrical Contractor to leave proper boxes, etc. as construction progresses, it shall be the responsibility of the Contractor to pay all costs of cutting and patching.
3.6 INFORMATION FOR ELECTRICAL CONTRACTOR:
A. Deliver to the Electrical Contractor all information on motors and controls furnished under the Mechanical Contract, together with makes and catalog numbers, to permit the Electrical Contractor to leave the proper boxes and wiring.
3.7 SLEEVES, INSERTS AND ANCHOR BOLTS:
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 13
A. All pipes and conduits passing through floors, walls or partitions shall be provided with sleeves sized to give a minimum of 1/2" clearance between sleeve and the outside diameter of the pipe, conduit or insulation, enclosing the pipe or conduit.
B. Sleeves through concrete floors or interior masonry walls shall be Schedule 40 steel pipe, set flush with finished wall or ceiling surfaces, but extending 2 inches above finished floors or shall be in accordance with details on drawings. In all mechanical equipment rooms sleeves shall extend 6 inches above finished floor.
C. Inserts shall be individual or strip type of steel or malleable iron construction for removable nuts and threaded rods up to 3/4" diameter, permitting lateral adjustment.
3.8 FIRE STOPPING:
A. General
1. Firestopping: Material or combination of materials used to retain integrity of fire-rated construction by maintaining an effective barrier against the spread of flame, smoke, and hot gases through penetrations in fire rated wall and floor assemblies.
B. General Description of The Work
1. Only tested firestop systems shall be used in specific locations as follows:
Penetrations for the passage of duct, cable, cable tray, conduit, piping, electrical busways and raceways through fire-rated vertical barriers (walls and partitions), horizontal barriers (floor/ceiling assemblies), and vertical service shaft walls and partitions.
C. References
1. Test Requirements: ASTM E-814, "Standard Method of Fire Tests of Through Penetration Fire Stops" (July 1997).
2. Underwriters Laboratories (UL) of Northbrook, IL runs ASTM E-814 under their designation of UL 1479 and publishes the results in their "FIRE RESISTANCE DIRECTORY" that is updated annually.
3. International Firestop Council Guidelines for Evaluating Firestop Systems Engineering Judgments
4. Test Requirements: ASTM E 84-96, "Surface burning characteristics".
5. All major building codes: ICBO, SBCCI, BOCA, and IBC.
6. Test Requirements: ASTM E-119, “Fire Test of Building Construction and
Materials” (UL 263)
D. Quality Assurance
1. Firestop System installation must meet requirements of ASTM E-119, ASTM E- 814, ASTM E-84-96, UL 236, UL 1479 or UL 2079 tested assemblies that provide a fire rating equal to that of construction being penetrated.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 14
2. Firestop Systems do not reestablish the structural integrity of load bearing partitions/assemblies, or support live loads and traffic. Installer shall consult the structural engineer prior to penetrating any load bearing assembly.
E. Submittals
1. Submit Product Data: Manufacturer's specifications and technical data for each material including the composition and limitations, documentation of UL firestop systems to be used and manufacturer's installation instructions to comply with Section 1300.
2. Submit material safety data sheets provided with product delivered to job-site.
F. Installer Qualifications
1. Engage an experienced Installer who is certified, licensed, or otherwise qualified by the firestopping manufacturer as having been provided the necessary training to install manufacture’s products per specified requirements.
G. Products, General
1. Provide firestopping composed of components that are compatible with each other, the substrates forming openings, and the items, if any, penetrating the firestopping under conditions of service and application, as demonstrated by the firestopping manufacturer based on testing and field experience.
2. Provide components for each firestopping system that are needed to install fill material. Use only components specified by the firestopping manufacturer and approved by the qualified testing agency for the designated fire-resistance-rated systems.
3. Firestopping Materials are either “cast-in-place” (integral with concrete placement) or “post installed.” Provide cast-in-place firestop devices prior to concrete placement.
H. Acceptable Manufacturers
1. Subject to compliance with through penetration firestop systems (XHEZ) and joint systems (XHBN) listed in Volume II of the UL Fire Resistance Directory, provide products of the following manufacturers as identified below:
a. Hilti, Inc., Tulsa, Oklahoma 800-879-8000
b. Other manufacturers listed in the U.L. Fire Resistance Directory – Volume
I. Materials
1. Use only firestop products that have been UL 1479, ASTM E-814, or UL 2079 tested for specific fire-rated construction conditions conforming to construction
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 15 assembly type, penetrating item type, annular space requirements, and fire-rating involved for each separate instance.
2. Provide a firestop system with a "F" Rating as determined by UL 1479 or ASTM E814 which is equal to the time rating of construction being penetrated.
3. Provide a firestop system with an Assembly Rating as determined by UL 2079 which is equal to the time rating of construction being penetrated.
J. Preparation
1. Verification of Conditions: Examine areas and conditions under which work is to be performed and identify conditions detrimental to proper or timely completion.
a. Verify penetrations are properly sized and in suitable condition for application of materials.
b. Surfaces to which firestop materials will be applied shall be free of dirt, grease, oil, rust, laitance, release agents, water repellents, and any other substances that may affect proper adhesion.
c. Provide masking and temporary covering to prevent soiling of adjacent surfaces by firestopping materials.
d. Comply with manufacturer's recommendations for temperature and humidity conditions before, during and after installation of firestopping.
e. Do not proceed until unsatisfactory conditions have been corrected.
K Coordination
1. Coordinate location and proper selection of cast-in-place Firestop Devices with trade responsible for the work. Ensure device is installed before placement of concrete.
2. Responsible trade to provide adequate spacing of field run pipes to allow for installation of cast-in-place firestop devices without interferences.
L. Installation
1. Regulatory Requirements: Install firestop materials in accordance with UL Fire Resistance Directory.
2. Manufacturer's Instructions: Comply with manufacturer's instructions for installation of through-penetration and construction joint materials.
a. Seal all holes or voids made by penetrations to ensure an air and water resistant seal.
b. Consult with project manager and damper manufacturer prior to installation of UL firestop systems that might hamper the performance of fire dampers as it pertains to duct work.
c. Protect materials from damage on surfaces subjected to traffic.
M. Field Quality Control
1. Examine sealed penetration areas to ensure proper installation before concealing or enclosing areas.
2. Keep areas of work accessible until inspection by applicable code authorities.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 16
3. Perform under this section patching and repairing of firestopping caused by cutting or penetrating of existing firestop systems already installed by other trades.
N. Adjusting and Cleaning
1. Remove equipment, materials and debris, leaving area in undamaged, clean condition.
2. Clean all surfaces adjacent to sealed holes and joints to be free of excess firestop materials and soiling as work progresses.
3.9 ACCESSIBILITY:
A. Locate all equipment which must be serviced, operated or maintained in fully accessible positions. Equipment shall include but not be limited to motors, controllers, switchgear, drain points, etc.
B. In the event that any equipment is not installed to permit convenient servicing, disassemble, removal of parts, etc. the Contractor shall, at his own expense, make all corrections necessary to accomplish this.
3.10 LUBRICATION:
A. All equipment having moving parts and requiring lubrication which is installed under this Contract, shall be properly lubricated according to manufacturer's recommendations prior to testing and operation. Any such equipment discovered to have been operated before lubrication is subject to rejection and replacement at no cost to the City of Meriden. Units furnished with sealed bearings are accepted.
3.11 TAGS, CHARTS AND NAMEPLATES:
A. Each valve, control, switch, electrical panel, motor and any piece of apparatus installed under these sections shall be properly identified.
B. Each sectional shutoff valve shall have a brass tag with identifying number. Tag shall be secured to valve stem with sufficient length of copper coated jack chain to allow tag to be easily read.
C. All other equipment, including panels and switches, shall be proved with a suitable laminated plastic nameplate fastened with screws or rivets. Small equipment labels may use a pressure sensitive tape.
D. All nameplates and labels shall identify components by proper nomenclature and numbered according to equipment schedule or as designated.
E. Charts shall be furnished in duplicate and shall include the valve identification number, location and purpose. One chart shall be mounted in frame with a clear glass front and secured to wall in location directed.
Second chart shall be for use throughout building and shall be provided with transparent plastic closure for top and attached 8" bead chain for hanging. Holes to be reinforced with
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 17 brass grommets. Tags and closures as manufactured by Seton Name Plate Corp., New Haven, Conn., or approved equal.
3.12 INSTRUCTIONS:
A. Prepare written instructions frames for the proper maintenance and operation of any special equipment furnished and installed under this Contract.
B. Personally instruct the City of Meriden's Custodian or official representative in addition to furnishing all manuals, diagrams, etc. in the proper operation and maintenance of all equipment and piping installed under this Contract.
C. Prepare a portfolio with all tags, operating manuals, parts lists, guarantees, etc. that are packed with all equipment furnished under this Contract and submit same to the Engineer.
3.13 PIPING CODE MARKERS:
A. All service piping which is accessible for maintenance operations shall be identified with vinyl plastic color bands and legends at each branch and riser take-off, at each passage through wall, floor and ceiling, adjacent to each valve and on all pipe runs marked each 20'-0". Pipe markers to conform to A.S.A. Bulletin A-13. Where pipes are too small for legends, brass identification tags 1-1/2" in diameter with depressed 1/2" high black filled letters shall be fastened with chain. Pipe markers and tags as manufactured by the Seton Name Plate Corp., New Haven, Conn., or equal approved.
3.14 CLEANING PIPING, CONDUITS AND EQUIPMENT:
A. Thoroughly clean all piping and equipment of all foreign substances inside and out before being placed in operation.
B. If any part of a system should be stopped by any foreign matter after being placed in operation, the system shall be disconnected, cleaned and reconnected wherever necessary to locate and remove obstructions.
Any work damaged in the course of removing obstructions shall be repaired or replaced when the system is reconnected at no additional cost to the City of Meriden.
C. During the course of construction, all pipe and electrical conduits shall be capped in an approved manner to insure adequate protection against the entrance of foreign matter.
3.15 CLEANING UP:
A. After completion of the work, remove all waste, rubbish and other materials left as a result of operations and leave the premises in clean condition.
B. All fixtures, equipment, etc. installed under the Mechanical and Electrical Sections shall be free of dirt, grease and other foreign material and left in perfectly clean condition and ready to use.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 18
3.16 GUARANTEE:
A. All parts of the work and all equipment shall be guaranteed for a period of 18 months from the date of acceptance of the job by the City of Meriden.
B. If during that period of general guarantee, any part of the work installed fails, becomes unsatisfactory or does not function properly due to any fault in material or workmanship, whether or not manufactured or job built, each section shall upon notice from the City of Meriden, promptly proceed to repair or replace such faulty material or workmanship without expense to the City of Meriden, including cutting, patching and painting or any other work involved and including repair or restoration of any damaged sections of the premises resulting from such faults.
C. In the event, that a repetition of any one defect occurs, indicating the probability of further failure, and which can be traced to faulty design, material or workmanship, then repairs or replacement shall not continue to be made but, the fault shall be remedied by a complete replacement of the entire defective unit.
D. In addition to the general guarantee, obtain and transmit to the City of Meriden any guarantees or warranties from manufacturers of specialties but only as a supplement to the general guarantee which will not be invalidated by same.
3.17 THE CITY OF MERIDEN'S INSTRUCTIONS AND SYSTEM OPERATION:
A. At the time of the job's acceptance by the City of Meriden, Contractor shall furnish maintenance and operating instructions for all equipment including parts list. These instructions shall be written in layman's language and shall be inserted in vinyl covered three-ring loose leaf binder. This information in binder shall be first sent to the approved by the Engineer before turning over to the City of Meriden.
B. Upon completion of all work and of all tests, each Division shall furnish the necessary skilled labor and helpers for operating the system and equipment for a period of one (1) day of eight (8) hours, or in two (4) hours separate sessions. During this period, instruct the The City of Meriden or his representative fully in operation, adjustment and maintenance of all equipment furnished. Give at least forty-eight (48) hours notice to the City of Meriden in advance of this period.
3.18 THE CITY OF MERIDEN'S ACCEPTANCE TEST:
A. After the various systems are complete as determined by preliminary operating tests, the Contractor shall arrange for the City of Meriden's final acceptance tests.
B. The Contractor shall have present at each acceptance test, representatives of the several Contractors whose work is directly or indirectly involved, with instruments as necessary in accordance with the design and to include the following.
1. All equipment installed and operating in accordance with manufacturer's instructions and performance guarantee.
2. All systems operating in accordance with specifications.
MERIDEN, CONNECTICUT
General Conditions For Mechanical And Electrical Systems 20 00 50 – 19
3. All distribution systems properly adjusted for distribution to equipment as specified.
4. The various systems properly flushed, cleaned, and free of entrapped air and dirt.
5. All motors installed with proper thermal overload protection and not operating under overload conditions as determined by ammeter readings.
6. All valve charts, etc. as specified in various parts of the specifications installed or ready for delivery to the City of Meriden.
C. The date of the City of Meriden’ acceptance of the equipment shall be the start of the one year guarantee period.
3.19 TEST:
A. Conducting Tests: Conduct all tests called for under the various sections or as required and repair or replace any defects. Perform all tests in the presence of and to the satisfaction of the Engineer and such other parties as may have legal jurisdiction.
B. Defective Work: The City of Meriden shall have the privilege of stopping any of the work not being properly installed. All such defective work shall be repaired or replaced and the tests shall be repeated.
C. Repair Damaged Work: Repair all damages resulting from tests and replace damaged materials.
END OF SECTION 20 00 50
MERIDEN, CONNECTICUT
Common Work Results for Plumbing 22 05 00 - 1
SECTION 22 05 00 COMMON WORK RESULTS FOR PLUMBING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS:
A. The General Provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply to the work specified in this Section.
B. The General Requirements in Section 200050 shall also govern the work under this section.
1.2 SCOPE OF WORK:
Gas systems Domestic water systems
A. This contract includes all labor, material, equipment, tests and appliances required to furnish and install all plumbing as shown on drawings, implied and herein specified.
B. The location of the building will be as shown on drawings. A visit to the site and examination of other Mechanical trades showing all details of construction is a requirement before submitting a proposal.
C. The drawings are diagrammatic and indicate the general arrangement of piping and equipment, and do not show all minor details and fittings. Such items shall be included, as well as reasonable modifications, in the layout as directed to prevent conflict with other trades.
D. Connect all equipment shown on drawings. Check all Mechanical drawings and coordinate all the work accordingly.
E. Provide seismic restraints in accordance with Section 230548.
1.3 QUALITY ASSURANCE:
A. Codes and Standards: All work shall comply with the…