Mechanical Calculations 100 percent.pdf

PDF 761 KB Posted

Attached to
Renovate Interventional Radiology Suites (Construction Services)
Solicitation number
Not on record
Issued by

About this file

This file is a comprehensive HVAC load calculation and system sizing report for a hospital renovation project (Gainesville IR, Project 0122093) prepared by Above Group for VAMC Gainesville. The document provides detailed engineering analysis for multiple air handling systems, terminal units, and plant equipment at 100% construction document phase.

The project includes five primary HVAC systems: 1-AHU-2-69 (7.9 tons cooling capacity, 3,072 CFM, serving 2,904 square feet with six zones including angiography rooms and control rooms); CRAC-1 and CRAC-2 (19.1 MBH and 9.0 MBH cooling capacity respectively, serving equipment rooms); EX AHU-2 (13.9 tons, 7,484 CFM, serving 37,577 square feet across basement, first floor, and second floor with ten zones); EX AHU-4 (3.0 tons, 654 CFM, serving 1,051 square feet with three zones); and DAC_DCU (0.7 tons, 453 CFM for electrical room). Central chilled water plant sizing indicates maximum load of 27.1 tons occurring at August 17:00, with coincident loads detailed for each system. Hot water plant sizing shows maximum load of 38.6 MBH at design heating conditions. All systems are VAV or constant volume with preheat coils, terminal reheat capability where required, and detailed psychrometric analysis for both summer cooling and winter heating design conditions. Supply air temperatures are designed at 55°F for cooling systems, with outdoor ventilation requirements ranging from 0 CFM to 664 CFM depending on system function and occupancy classifications.

View the file

Other files

File Type Posted
Reports.zip ZIP file
VA 573-22-103 Gainesville - Interventional Radiology - Addendum 01.pdf PDF
Updated Parking Policy.pdf PDF
36C24826R0038 0002 Responses to RFI_s.pdf PDF
Pre-bid RFIs 573-22-103.xlsx XLSX spreadsheet
Cutsheets.zip ZIP file
Elevator Modernization.zip ZIP file
Basis of Design.zip ZIP file
573-22-103 Renovate Interventional Radiology Suites Site Visit Presentation.pptx PPTX presentation
Stryker CAD.zip ZIP file
Philips CAD.zip ZIP file
RFI Documents.zip ZIP file
Wage Determination FL20250194 dated 01-02-2026.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Air System Sizing Summary for 1-AHU-2-69 (In Alternative: GAINESVILLE IR)

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Air System Information Air System Name 1-AHU-2-69 Equipment Class CW AHU Air System Type VAV

Number of zones 6 Floor Area 2903.9 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data Total coil load 7.9 Tons Total coil load 95.4 MBH Sensible coil load 70.6 MBH Coil CFM at peak load 3072 CFM Sum of peak zone CFM 3072 CFM Sensible heat ratio 0.741 CFM/Ton 386.5 sqft/Ton 365.4 BTU/(hr sqft) 32.8 Water flow @ 12.0 F rise 15.90 gpm

Peak coil load occurs at August 16:00

OA DB / WB 93.8 / 75.9 F

Entering DB / WB 73.9 / 63.5 F Leaving DB / WB 53.0 / 52.9 F Resulting RH 58 % Design supply temp. 55.0 F Zone T-stat Check 6 of 6 OK Max zone temperature deviation 0.0 F

Preheat Coil Sizing Data Max coil load 9.4 MBH Coil CFM at Design Heating 3072 CFM Max coil CFM 3072 CFM Water flow @ 20.0 F drop 0.94 gpm

Load occurs at Design Heating Ent. DB / Lvg DB 47.2 / 50.0 F

Supply Fan Sizing Data Design CFM 3072 CFM Design CFM occurs at January 0:00 Design CFM/sqft 1.06 CFM/sqft Sum of peak zone CFM 3072 CFM VAV Fan Diversity 0.0 %

Fan motor BHP 2.52 BHP Fan motor kW 2.00 kW Fan total static 3.00 in wg

Return Fan Sizing Data Actual max CFM at January 0:00 3072 CFM Standard CFM 3058 CFM Actual max CFM/sqft 1.06 CFM/sqft

Fan motor BHP 2.52 BHP Fan motor kW 2.00 kW Fan total static 3.00 in wg

Outdoor Ventilation Air Data Design airflow CFM 664 CFM CFM/sqft 0.23 CFM/sqft

CFM/person 66.38 CFM/person

Hourly Analysis Program 6.2 Page 1 of 39

Zone Sizing Summary for 1-AHU-2-69

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Air System Information Air System Name 1-AHU-2-69 Equipment Class CW AHU Air System Type VAV

Number of zones 6 Floor Area 2903.9 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

1-TU-69-01 121 121 1.03 5.2 0.52 0.0 0.00 0

1-TU-69-02 1291 1291 1.59 55.5 5.56 0.0 0.00 0

1-TU-69-03 1292 1292 1.59 55.6 5.56 0.0 0.00 0

1-TU-69-04 120 120 1.05 5.2 0.52 0.0 0.00 0

1-TU-69-05 148 148 0.18 6.4 0.64 0.0 0.00 0

1-TU-69-06 100 100 0.41 4.3 0.43 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

1-TU-69-01 2.6 July 7:00 0.1 117.3

1-TU-69-02 15.3 July 21:00 -0.6 812.5

1-TU-69-03 15.3 July 21:00 -0.6 814.3

1-TU-69-04 2.6 July 7:00 0.1 114.3

1-TU-69-05 3.2 July 21:00 0.7 800.6

1-TU-69-06 0.5 July 22:00 0.2 244.9

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

1-TU-69-01

CONTROL RM D365A 2.6 July 7:00 121 0.1 117.3 1.03

1-TU-69-02

ANGIO RM 1 D365 15.3 July 21:00 1291 -0.6 812.5 1.59

1-TU-69-03

ANGIO RM 2 D364 15.3 July 21:00 1292 -0.6 814.3 1.59

1-TU-69-04

CONTROL RM D364A 2.6 July 7:00 120 0.1 114.3 1.05

1-TU-69-05

CORRIDOR C366 (1) 0.8 July 21:00 36 0.3 384.9 0.09

CORRIDOR C366 (2) 0.6 July 21:00 28 0.2 297.4 0.09

PUBLIC TOILET D363C 0.1 July 22:00 6 0.1 63.3 0.09

PYXIS D363G 1.7 July 7:00 79 0.1 55.0 1.43

1-TU-69-06

CLEAN SUPPLY D363F 0.2 July 22:00 47 0.1 120.0 0.40

SOILED UTILITY D363D 0.1 July 22:00 29 0.1 71.2 0.41

STAFF TOILET D363E 0.1 July 22:00 23 0.1 53.7 0.44

Hourly Analysis Program 6.2 Page 2 of 39

Ventilation Sizing Summary for 1-AHU-2-69

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

1. Summary Ventilation Sizing Method Sum of Space OA Airflows Design Ventilation Airflow Rate 664 CFM

2. Space Ventilation Analysis

Zone Name / Space Name

Floor Area

(sqft) Maximum

Occupants

Maximum Supply Air

(CFM)

Required Outdoor Air

(CFM/person)

Required Outdoor Air

(CFM/sqft)

Required Outdoor Air

(CFM)

Required Outdoor Air

(% of supply)

Required Outdoor Air

(ACH)

Uncorrected Outdoor Air

(CFM)

Direct Exhaust Air

(CFM)

1-TU-69-01

CONTROL RM D365A 117.3 2.0 120.8 5.00 0.06 0.0 0.0 0.00 17.0 0.0

1-TU-69-02

ANGIO RM 1 D365 812.5 3.0 1291.1 0.00 0.00 0.0 0.0 2.00 0.0 0.0

1-TU-69-03

ANGIO RM 2 D364 814.3 3.0 1291.8 0.00 0.00 0.0 0.0 2.00 0.0 0.0

1-TU-69-04

CONTROL RM D364A 114.3 2.0 120.4 5.00 0.06 0.0 0.0 0.00 16.9 0.0

1-TU-69-05

CORRIDOR C366 (1) 384.9 0.0 35.7 0.00 0.06 0.0 0.0 0.00 23.1 0.0

CORRIDOR C366 (2) 297.4 0.0 27.8 0.00 0.06 0.0 0.0 0.00 17.8 0.0

PUBLIC TOILET D363C 63.3 0.0 5.9 0.00 0.00 0.0 0.0 0.00 0.0 100.0

PYXIS D363G 55.0 0.0 78.8 0.00 0.00 0.0 0.0 2.00 0.0 0.0

1-TU-69-06

CLEAN SUPPLY D363F 120.0 0.0 47.5 0.00 0.00 0.0 0.0 2.00 0.0 0.0

SOILED UTILITY D363D 71.2 0.0 29.0 0.00 0.00 0.0 0.0 2.00 0.0 0.0

STAFF TOILET D363E 53.7 0.0 23.5 0.00 0.00 0.0 0.0 0.00 0.0 100.0

Totals 3072.3 663.8

Hourly Analysis Program 6.2 Page 3 of 39

Air System Heat Balance Summary for 1-AHU-2-69

Table 1. System Loads

DESIGN COOLING - AUGUST 16:00 DESIGN HEATING

OA DB / WB 93.8 F / 75.9 F OA DB / WB 29.6 F / 25.0 F

COMPONENT LOADS Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Zone Conditioning - 39527 3424 - 7570 0

Plenum Load - 0 0 - 0 0

Return Fan Load 2872 CFM 6435 - 2872 CFM -6435 -

Ventilation Load 664 CFM 17159 20576 664 CFM 14981 0

Supply Fan Load 3072 CFM 6836 - 3072 CFM -6836 -

Zone Fan Coil Fans Load - 0 - - 0 -

>> Total System Loads - 69957 24001 - 9280 0

Central Cooling Coil - 70633 24734 - 0 0

Preheat Coil - 0 - - 9359 -

Terminal Reheat Coils - 0 - - 0 -

>> Total Conditioning - 70633 24734 - 9359 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Table 2. Zone Heat Balance Loads

DESIGN COOLING - AUGUST 16:00 DESIGN HEATING

OA DB / WB 93.8 F / 75.9 F OA DB / WB 29.6 F / 25.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 0 sqft 0 - 0 sqft 0 -

Roof Convection 0 sqft 0 - 0 sqft 0 -

Window Convection 0 sqft 0 - 0 sqft 0 -

Skylight Convection 0 sqft 0 - 0 sqft 0 -

Door Convection 0 sqft 0 - 0 sqft 0 -

Floor Convection 2904 sqft 5297 - 2904 sqft -436 -

Interior Wall Convection 6642 sqft 6147 - 6642 sqft -18 -

Ceiling Convection 2904 sqft 7940 - 2904 sqft 283 -

Overhead Lighting Convection 1162 W 912 - 0 W 0 -

Task Lighting Convection 0 W 0 - 0 W 0 -

Electric Equipment Convection 0 W 0 - 0 W 0 -

People Convection 10 825 3550 0 0 0

Infiltration 0 CFM 0 0 0 CFM 0 0

Miscellaneous Equipment - 18000 0 - 0 0

Air Internal Energy Change - 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 39120 3550 - -172 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room air. Therefore, the effect of solar heat gain is found in the surface convection line items.

Hourly Analysis Program 6.2 Page 4 of 39

System Psychrometrics for 1-AHU-2-69

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

DESIGN COOLING DAY AT AUGUST 16:00

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 93.6 0.01525 664 400 17159 20576

Vent - Return Mixing Outlet 73.9 0.01016 3072 609 - -

Preheat Coil Outlet 73.9 0.01016 3072 609 0 -

Central Cooling Coil Outlet 53.0 0.00851 3072 609 70633 24734

Supply Fan Outlet 55.0 0.00851 3072 609 6836 -

Cold Supply Duct Outlet 55.0 0.00851 3072 609 - -

Zone Air - 68.9 0.00869 2872 651 39527 3424

Zone Direct Exhaust Outlet 72.3 0.00851 200 609 - -

Return Air Outlet 66.4 0.00876 2872 667 - -

Return Fan Outlet 68.4 0.00876 2872 667 6435 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.075 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4725.5 BTU/(hr-CFM) Site Altitude = 123.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

1-TU-69-01 1727 Cooling 2528 74.1 121 803 0 0

1-TU-69-02 12027 Cooling 14841 65.5 1291 655 0 0

1-TU-69-03 12032 Cooling 14849 65.5 1292 655 0 0

1-TU-69-04 1731 Cooling 2520 74.1 120 804 0 0

1-TU-69-05 1656 Cooling 3153 74.5 148 609 0 0

1-TU-69-06 0 Deadband 1657 70.1 100 609 0 0

Hourly Analysis Program 6.2 Page 5 of 39

System Psychrometrics for 1-AHU-2-69

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 29.6 0.00158 664 400 -14981 0

Vent - Return Mixing Outlet 47.2 0.00158 3072 400 - -

Preheat Coil Outlet 50.0 0.00158 3072 400 9359 -

Central Cooling Coil Outlet 50.0 0.00158 3072 400 0 0

Supply Fan Outlet 52.1 0.00158 3072 400 6836 -

Cold Supply Duct Outlet 52.1 0.00158 3072 400 - -

Zone Air - 49.0 0.00158 2872 400 -7570 0

Zone Direct Exhaust Outlet 47.2 0.00158 200 400 - -

Return Air Outlet 50.0 0.00158 2872 400 - -

Return Fan Outlet 52.0 0.00158 2872 400 6435 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.075 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4725.5 BTU/(hr-CFM) Site Altitude = 123.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

1-TU-69-01 -18823 Heating -389 49.1 121 400 0 0

1-TU-69-02 -85562 Heating -2746 50.1 1291 400 0 0

1-TU-69-03 -85617 Heating -2748 50.1 1292 400 0 0

1-TU-69-04 -18522 Heating -385 49.1 120 400 0 0

1-TU-69-05 -65630 Heating -817 46.9 148 400 0 0

1-TU-69-06 -33370 Heating -488 47.5 100 400 0 0

Hourly Analysis Program 6.2 Page 6 of 39

DOAS Sizing Summary for CRAC-1

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Air System Information Air System Name CRAC-1 Equipment Class TERM Air System Type 4P-FC

Number of zones 1 Floor Area 182.1 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 6.2 Page 7 of 39

Zone Sizing Summary for CRAC-1

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Air System Information Air System Name CRAC-1 Equipment Class TERM Air System Type 4P-FC

Number of zones 1 Floor Area 182.1 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time

Coil Coil Entering Leaving Flow of

Load Load DB / WB DB / WB @ 10.0 F Peak Coil Zone

Zone Name (MBH) (MBH) (F) (F) (gpm) Load CFM/sqft

CRAC-1 19.1 19.1 70.2 / 59.7 58.4 / 55.2 3.82 July 21:00 8.10

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil

Heating Coil Water Fan OA Vent

Coil Ent/Lvg Flow Design Fan Fan Design

Load DB @20.0 F Airflow Motor Motor Airflow

Zone Name (MBH) (F) (gpm) (CFM) (BHP) (kW) (CFM)

CRAC-1 0.0 0.0 / 0.0 0.00 1476 0.109 0.087 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

CRAC-1 19.0 July 7:00 0.0 182.1

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

CRAC-1

EQUIPMENT/UPS 19.0 July 7:00 1476 0.0 182.1 8.10

Hourly Analysis Program 6.2 Page 8 of 39

Ventilation Sizing Summary for CRAC-1

2. Space Ventilation Analysis

2.1 Zone: CRAC-1

Zone Name / Space Name

Floor Area

(sqft) Maximum

Occupants

Maximum Supply Air

(CFM)

Required Outdoor Air

(CFM/person)

Required Outdoor Air

(CFM/sqft)

Required Outdoor Air

(CFM)

Required Outdoor Air

(% of supply)

Required Outdoor Air

(ACH)

Uncorrected Outdoor Air

(CFM)

Direct Exhaust Air

(CFM)

CRAC-1

EQUIPMENT/UPS 182.1 0.0 1476.3 0.00 0.00 0.0 0.0 0.00 0.0 0.0

Totals 1476.3 0.0 0.0

Hourly Analysis Program 6.2 Page 9 of 39

Air System Heat Balance Summary for CRAC-1

DESIGN COOLING - JULY 21:00 DESIGN HEATING

OA DB / WB 84.8 F / 73.5 F OA DB / WB 29.6 F / 25.0 F

COMPONENT LOADS Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Zone Conditioning - 18805 0 - 297 0

Plenum Load - 0 0 - 0 0

Exhaust Fan Load 0 CFM 0 - 0 CFM 0 -

Ventilation Load 0 CFM 0 0 0 CFM 0 0

Ventilation Fan Load 0 CFM 0 - 0 CFM 0 -

Zone Fan Coil Fans Load - 295 - - -295 -

>> Total System Loads - 19100 0 - 2 0

Terminal Unit Cooling - 19100 0 - 0 0

Terminal Unit Heating - 0 - - 0 -

>> Total Conditioning - 19100 0 - 0 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Table 2. Zone Heat Balance Loads

DESIGN COOLING - JULY 21:00 DESIGN HEATING

OA DB / WB 84.8 F / 73.5 F OA DB / WB 29.6 F / 25.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 0 sqft 0 - 0 sqft 0 -

Roof Convection 0 sqft 0 - 0 sqft 0 -

Window Convection 0 sqft 0 - 0 sqft 0 -

Skylight Convection 0 sqft 0 - 0 sqft 0 -

Door Convection 0 sqft 0 - 0 sqft 0 -

Floor Convection 182 sqft 355 - 182 sqft -4 -

Interior Wall Convection 488 sqft 511 - 488 sqft -5 -

Ceiling Convection 182 sqft 511 - 182 sqft 8 -

Overhead Lighting Convection 37 W 29 - 0 W 0 -

Task Lighting Convection 0 W 0 - 0 W 0 -

Electric Equipment Convection 0 W 0 - 0 W 0 -

People Convection 0 0 0 0 0 0

Infiltration 0 CFM 0 0 0 CFM 0 0

Miscellaneous Equipment - 17500 0 - 0 0

Air Internal Energy Change - 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 18905 0 - 0 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 10 of 39

System Psychrometrics for CRAC-1

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

DESIGN COOLING DAY AT JULY 21:00

TABLE 1: SYSTEM DATA

No data available. This system does not include a Dedicated Outdoor Air System (DOAS)

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

CRAC-1 ( Cooling )

Ventilation Air - - - 0 - - -

Cooling Coil Inlet - 70.2 0.00858 1476 400 - -

Cooling Coil Outlet - 58.4 0.00858 1476 400 19100 0

Heating Coil Inlet - 58.4 0.00858 1476 400 - -

Heating Coil Outlet - 58.4 0.00858 1476 400 0 -

Zone Air - 70.0 0.00858 1476 400 18805 -

Hourly Analysis Program 6.2 Page 11 of 39

System Psychrometrics for CRAC-1

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

No data available. This system does not include a Dedicated Outdoor Air System (DOAS)

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

CRAC-1 ( Heating )

Ventilation Air - - - 0 - - -

Cooling Coil Inlet - 47.3 0.00158 1476 400 - -

Cooling Coil Outlet - 47.3 0.00158 1476 400 0 0

Heating Coil Inlet - 47.3 0.00158 1476 400 - -

Heating Coil Outlet - 47.3 0.00158 1476 400 0 -

Zone Air - 47.2 0.00158 1476 400 -298 -

Hourly Analysis Program 6.2 Page 12 of 39

DOAS Sizing Summary for CRAC-2

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Air System Information Air System Name CRAC-2 Equipment Class TERM Air System Type 4P-FC

Number of zones 1 Floor Area 71.5 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 6.2 Page 13 of 39

Zone Sizing Summary for CRAC-2

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Air System Information Air System Name CRAC-2 Equipment Class TERM Air System Type 4P-FC

Number of zones 1 Floor Area 71.5 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time

Coil Coil Entering Leaving Flow of

Load Load DB / WB DB / WB @ 10.0 F Peak Coil Zone

Zone Name (MBH) (MBH) (F) (F) (gpm) Load CFM/sqft

CRAC-2 9.0 9.0 70.2 / 59.8 58.4 / 55.2 1.80 July 21:00 9.75

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil

Heating Coil Water Fan OA Vent

Coil Ent/Lvg Flow Design Fan Fan Design

Load DB @20.0 F Airflow Motor Motor Airflow

Zone Name (MBH) (F) (gpm) (CFM) (BHP) (kW) (CFM)

CRAC-2 0.0 0.0 / 0.0 0.00 697 0.052 0.041 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

CRAC-2 9.0 July 7:00 0.0 71.5

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

CRAC-2

EQUIPMENT D364B 9.0 July 7:00 697 0.0 71.5 9.75

Hourly Analysis Program 6.2 Page 14 of 39

Ventilation Sizing Summary for CRAC-2

2. Space Ventilation Analysis

2.1 Zone: CRAC-2

Zone Name / Space Name

Floor Area

(sqft) Maximum

Occupants

Maximum Supply Air

(CFM)

Required Outdoor Air

(CFM/person)

Required Outdoor Air

(CFM/sqft)

Required Outdoor Air

(CFM)

Required Outdoor Air

(% of supply)

Required Outdoor Air

(ACH)

Uncorrected Outdoor Air

(CFM)

Direct Exhaust Air

(CFM)

CRAC-2

EQUIPMENT D364B 71.5 0.0 697.0 0.00 0.00 0.0 0.0 0.00 0.0 0.0

Totals 697.0 0.0 0.0

Hourly Analysis Program 6.2 Page 15 of 39

Air System Heat Balance Summary for CRAC-2

OA DB / WB 84.8 F / 73.5 F OA DB / WB 29.6 F / 25.0 F

COMPONENT LOADS Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Zone Conditioning - 8846 0 - 140 0

Plenum Load - 0 0 - 0 0

Exhaust Fan Load 0 CFM 0 - 0 CFM 0 -

Ventilation Load 0 CFM 0 0 0 CFM 0 0

Ventilation Fan Load 0 CFM 0 - 0 CFM 0 -

Zone Fan Coil Fans Load - 139 - - -139 -

>> Total System Loads - 8985 0 - 1 0

Terminal Unit Cooling - 8985 0 - 0 0

Terminal Unit Heating - 0 - - 0 -

>> Total Conditioning - 8985 0 - 0 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Table 2. Zone Heat Balance Loads

DESIGN COOLING - JULY 21:00 DESIGN HEATING

OA DB / WB 84.8 F / 73.5 F OA DB / WB 29.6 F / 25.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 0 sqft 0 - 0 sqft 0 -

Roof Convection 0 sqft 0 - 0 sqft 0 -

Window Convection 0 sqft 0 - 0 sqft 0 -

Skylight Convection 0 sqft 0 - 0 sqft 0 -

Door Convection 0 sqft 0 - 0 sqft 0 -

Floor Convection 71 sqft 139 - 71 sqft -1 -

Interior Wall Convection 350 sqft 342 - 350 sqft -2 -

Ceiling Convection 71 sqft 195 - 71 sqft 3 -

Overhead Lighting Convection 15 W 11 - 0 W 0 -

Task Lighting Convection 0 W 0 - 0 W 0 -

Electric Equipment Convection 0 W 0 - 0 W 0 -

People Convection 0 0 0 0 0 0

Infiltration 0 CFM 0 0 0 CFM 0 0

Miscellaneous Equipment - 8200 0 - 0 0

Air Internal Energy Change - 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 8888 0 - 0 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 16 of 39

System Psychrometrics for CRAC-2

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

DESIGN COOLING DAY AT JULY 21:00

TABLE 1: SYSTEM DATA

No data available. This system does not include a Dedicated Outdoor Air System (DOAS)

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

CRAC-2 ( Cooling )

Ventilation Air - - - 0 - - -

Cooling Coil Inlet - 70.2 0.00859 697 400 - -

Cooling Coil Outlet - 58.4 0.00859 697 400 8985 0

Heating Coil Inlet - 58.4 0.00859 697 400 - -

Heating Coil Outlet - 58.4 0.00859 697 400 0 -

Zone Air - 70.0 0.00859 697 400 8846 -

Hourly Analysis Program 6.2 Page 17 of 39

System Psychrometrics for CRAC-2

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

No data available. This system does not include a Dedicated Outdoor Air System (DOAS)

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

CRAC-2 ( Heating )

Ventilation Air - - - 0 - - -

Cooling Coil Inlet - 47.3 0.00158 697 400 - -

Cooling Coil Outlet - 47.3 0.00158 697 400 0 0

Heating Coil Inlet - 47.3 0.00158 697 400 - -

Heating Coil Outlet - 47.3 0.00158 697 400 0 -

Zone Air - 47.1 0.00158 697 400 -141 -

Hourly Analysis Program 6.2 Page 18 of 39

Air System Sizing Summary for EX AHU-2

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Air System Information Air System Name EX AHU-2 Equipment Class CW AHU Air System Type VAV

Number of zones 10 Floor Area 37576.7 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data Total coil load 13.9 Tons Total coil load 167.0 MBH Sensible coil load 159.4 MBH Coil CFM at peak load 6689 CFM Sum of peak zone CFM 7628 CFM Sensible heat ratio 0.954 CFM/Ton 480.6 sqft/Ton 2699.6 BTU/(hr sqft) 4.4 Water flow @ 10.0 F rise 33.42 gpm

Peak coil load occurs at July 18:00

OA DB / WB 91.3 / 75.2 F

Entering DB / WB 75.4 / 61.4 F Leaving DB / WB 53.6 / 52.5 F Resulting RH 44 % Design supply temp. 55.0 F Zone T-stat Check 10 of 10 OK Max zone temperature deviation 0.0 F

Preheat Coil Sizing Data Max coil load 20.4 MBH Coil CFM at Design Heating 2928 CFM Max coil CFM 7484 CFM Water flow @ 20.0 F drop 2.04 gpm

Load occurs at Design Heating Ent. DB / Lvg DB 43.5 / 50.0 F

Supply Fan Sizing Data Design CFM 7484 CFM Design CFM occurs at July 18:00 Design CFM/sqft 0.20 CFM/sqft Sum of peak zone CFM 7628 CFM VAV Fan Diversity 1.9 %

Fan motor BHP 4.10 BHP Fan motor kW 3.25 kW Fan total static 2.00 in wg

Outdoor Ventilation Air Data Design airflow CFM 180 CFM CFM/sqft 0.00 CFM/sqft

CFM/person 25.73 CFM/person

Hourly Analysis Program 6.2 Page 19 of 39

Zone Sizing Summary for EX AHU-2

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Air System Information Air System Name EX AHU-2 Equipment Class CW AHU Air System Type VAV

Number of zones 10 Floor Area 37576.7 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

1-TU-61-1B-05 43 43 0.30 1.8 0.18 0.0 0.00 0

1-TU-61-1B-06 31 31 0.30 1.3 0.13 0.0 0.00 0

1-TU-61-1B-07 25 7 0.16 0.3 0.03 0.0 0.00 0

1-TU-61-1B-08 58 17 0.56 0.8 0.08 0.0 0.00 0

1-TU-61-1B-09 51 38 0.41 1.6 0.16 0.0 0.00 0

1-TU-61-1B-10 53 41 0.39 1.7 0.17 0.0 0.00 0

1-TU-61-1B-11 50 15 0.43 0.6 0.06 0.0 0.00 0

BASEMENT 1668 637 0.11 27.4 2.74 0.0 0.00 0

FIRST FLOOR SURROUNDING 1767 600 0.19 25.8 2.58 0.0 0.00 0

SECOND FLOOR 3883 1500 0.31 64.5 6.46 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

1-TU-61-1B-05 0.3 July 22:00 0.1 141.9

1-TU-61-1B-06 0.2 July 22:00 0.1 102.9

1-TU-61-1B-07 0.5 July 21:00 0.1 158.1

1-TU-61-1B-08 1.3 July 21:00 0.1 104.8

1-TU-61-1B-09 1.1 July 21:00 0.1 126.3

1-TU-61-1B-10 1.1 July 21:00 0.1 135.4

1-TU-61-1B-11 1.1 July 21:00 0.1 114.8

BASEMENT 35.9 July 22:00 17.1 14902.2

FIRST FLOOR SURROUNDING 38.0 July 19:00 16.1 9115.7

SECOND FLOOR 83.5 August 17:00 40.3 12674.6

Hourly Analysis Program 6.2 Page 20 of 39

Zone Sizing Summary for EX AHU-2

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

1-TU-61-1B-05

SOILED UTILITY D171-1 0.3 July 22:00 43 0.1 141.9 0.30

1-TU-61-1B-06

CLEAN UTILITY D167-1 0.2 July 22:00 31 0.1 102.9 0.30

1-TU-61-1B-07

READING ROOM D363B (1) 0.5 July 21:00 25 0.1 158.1 0.16

1-TU-61-1B-08

TECH WORKROOM D363K 1.3 July 21:00 58 0.1 104.8 0.56

1-TU-61-1B-09

PATIENT RECOVERY D363J 1.1 July 21:00 51 0.1 126.3 0.41

1-TU-61-1B-10

PATIENT RECOVERY D363H 1.1 July 21:00 53 0.1 135.4 0.39

1-TU-61-1B-11

DOCTOR'S OFFICE D363A 1.1 July 21:00 50 0.1 114.8 0.43

BASEMENT

BASEMENT LEVEL 35.9 July 22:00 1668 17.1 14902.2 0.11

FIRST FLOOR SURROUNDING

FIRST FLOOR SPACE 38.0 July 19:00 1767 16.1 9115.7 0.19

SECOND FLOOR

SECOND FLOOR 83.5 August 17:00 3883 40.3 12674.6 0.31

Hourly Analysis Program 6.2 Page 21 of 39

Ventilation Sizing Summary for EX AHU-2

Design Ventilation Airflow Rate 180 CFM

2. Space Ventilation Analysis

Zone Name / Space Name

Floor Area

(sqft) Maximum

Occupants

Maximum Supply Air

(CFM)

Required Outdoor Air

(CFM/person)

Required Outdoor Air

(CFM/sqft)

Required Outdoor Air

(CFM)

Required Outdoor Air

(% of supply)

Required Outdoor Air

(ACH)

Uncorrected Outdoor Air

(CFM)

Direct Exhaust Air

(CFM)

1-TU-61-1B-05

SOILED UTILITY D171-1 141.9 0.0 42.6 0.00 0.00 0.0 0.0 2.00 0.0 0.0

1-TU-61-1B-06

CLEAN UTILITY D167-1 102.9 0.0 30.9 0.00 0.00 0.0 0.0 2.00 0.0 0.0

1-TU-61-1B-07

READING ROOM D363B (1) 158.1 0.0 24.5 0.00 0.00 0.0 0.0 0.00 0.0 0.0

1-TU-61-1B-08

TECH WORKROOM D363K 104.8 2.0 58.2 5.00 0.06 0.0 0.0 0.00 16.3 0.0

1-TU-61-1B-09

PATIENT RECOVERY D363J 126.3 2.0 51.4 0.00 0.00 0.0 0.0 2.00 0.0 0.0

1-TU-61-1B-10

PATIENT RECOVERY D363H 135.4 2.0 52.5 0.00 0.00 0.0 0.0 2.00 0.0 0.0

1-TU-61-1B-11

DOCTOR'S OFFICE D363A 114.8 1.0 49.5 5.00 0.06 0.0 0.0 0.00 11.9 0.0

BASEMENT

BASEMENT LEVEL 14902.2 0.0 1668.0 0.00 0.00 0.0 0.0 0.00 0.0 0.0

FIRST FLOOR SURROUNDING

FIRST FLOOR SPACE 9115.7 0.0 1767.1 0.00 0.00 0.0 0.0 0.00 0.0 0.0

SECOND FLOOR

SECOND FLOOR 12674.6 0.0 3882.7 0.00 0.00 0.0 0.0 0.00 0.0 0.0

Totals 7627.5 180.1

Hourly Analysis Program 6.2 Page 22 of 39

Air System Heat Balance Summary for EX AHU-2

DESIGN COOLING - JULY 18:00 DESIGN HEATING

OA DB / WB 91.3 F / 75.2 F OA DB / WB 29.6 F / 25.0 F

COMPONENT LOADS Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Zone Conditioning - 146090 1374 - 22476 0

Plenum Load - 0 0 - 0 0

Return Fan Load 6689 CFM 0 - 2928 CFM 0 -

Ventilation Load 180 CFM 3126 5985 180 CFM 2882 0

Supply Fan Load 6689 CFM 10018 - 2928 CFM -5046 -

Zone Fan Coil Fans Load - 0 - - 0 -

>> Total System Loads - 159234 7359 - 20312 0

Central Cooling Coil - 159386 7645 - 0 0

Preheat Coil - 0 - - 20369 -

Terminal Reheat Coils - 0 - - 0 -

>> Total Conditioning - 159386 7645 - 20369 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Table 2. Zone Heat Balance Loads

DESIGN COOLING - JULY 18:00 DESIGN HEATING

OA DB / WB 91.3 F / 75.2 F OA DB / WB 29.6 F / 25.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 15505 sqft 24459 - 15505 sqft 26710 -

Roof Convection 12683 sqft 23002 - 12683 sqft 17611 -

Window Convection 0 sqft 0 - 0 sqft 0 -

Skylight Convection 0 sqft 0 - 0 sqft 0 -

Door Convection 0 sqft 0 - 0 sqft 0 -

Floor Convection 37577 sqft 30567 - 37577 sqft 17524 -

Interior Wall Convection 19333 sqft 9944 - 19333 sqft 6184 -

Ceiling Convection 24902 sqft 18952 - 24902 sqft 6300 -

Overhead Lighting Convection 29306 W 52022 - 0 W 0 -

Task Lighting Convection 0 W 0 - 0 W 0 -

Electric Equipment Convection 0 W 0 - 0 W 0 -

People Convection 7 497 1095 0 0 0

Infiltration 0 CFM 0 0 0 CFM 0 0

Miscellaneous Equipment - 1500 0 - 0 0

Air Internal Energy Change - 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 160942 1095 - 74329 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 23 of 39

System Psychrometrics for EX AHU-2

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

DESIGN COOLING DAY AT JULY 18:00

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 91.1 0.01525 180 400 3126 5985

Vent - Return Mixing Outlet 75.4 0.00840 6689 660 - -

Preheat Coil Outlet 75.4 0.00840 6689 660 0 -

Central Cooling Coil Outlet 53.6 0.00817 6689 660 159386 7645

Supply Fan Outlet 55.0 0.00817 6689 660 10018 -

Cold Supply Duct Outlet 55.0 0.00817 6689 660 - -

Zone Air - 75.0 0.00819 6689 661 146090 1374

Return Air Outlet 75.0 0.00821 6689 667 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.075 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4725.5 BTU/(hr-CFM) Site Altitude = 123.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

1-TU-61-1B-05 0 Deadband 753 71.2 43 659 0 0

1-TU-61-1B-06 0 Deadband 560 71.6 31 659 0 0

1-TU-61-1B-07 468 Cooling 468 75.0 21 657 0 0

1-TU-61-1B-08 1188 Cooling 1189 75.0 54 1090 0 0

1-TU-61-1B-09 1007 Cooling 1008 75.0 46 1055 0 0

1-TU-61-1B-10 1023 Cooling 1024 75.0 47 1049 0 0

1-TU-61-1B-11 995 Cooling 996 75.0 45 917 0 0

BASEMENT 31106 Cooling 31107 75.0 1422 655 0 0

FIRST FLOOR SURROUNDING 31088 Cooling 31089 75.0 1421 657 0 0

SECOND FLOOR 77898 Cooling 77899 75.0 3560 658 0 0

Hourly Analysis Program 6.2 Page 24 of 39

System Psychrometrics for EX AHU-2

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 29.6 0.00158 180 400 -2882 0

Vent - Return Mixing Outlet 43.6 0.00158 2928 400 - -

Preheat Coil Outlet 50.0 0.00158 2928 400 20369 -

Central Cooling Coil Outlet 50.0 0.00158 2928 400 0 0

Supply Fan Outlet 51.6 0.00158 2928 400 5046 -

Cold Supply Duct Outlet 51.6 0.00158 2928 400 - -

Zone Air - 44.0 0.00158 2928 400 -22476 0

Return Air Outlet 44.5 0.00158 2928 400 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.075 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4725.5 BTU/(hr-CFM) Site Altitude = 123.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

1-TU-61-1B-05 -14768 Heating -201 47.2 43 400 0 0

1-TU-61-1B-06 -12160 Heating -153 47.0 31 400 0 0

1-TU-61-1B-07 -9776 Heating -29 47.9 7 400 0 0

1-TU-61-1B-08 -6854 Heating -87 47.0 17 400 0 0

1-TU-61-1B-09 -13343 Heating -180 47.2 38 400 0 0

1-TU-61-1B-10 -14157 Heating -192 47.2 41 400 0 0

1-TU-61-1B-11 -7395 Heating -78 46.7 15 400 0 0

BASEMENT -968023 Heating -6763 41.8 637 400 0 0

FIRST FLOOR SURROUNDING -531870 Heating -3710 45.9 600 400 0 0

SECOND FLOOR -1113788 Heating -11128 44.7 1500 400 0 0

Hourly Analysis Program 6.2 Page 25 of 39

Air System Sizing Summary for EX AHU-4

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Air System Information Air System Name EX AHU-4 Equipment Class CW AHU Air System Type VAV

Number of zones 3 Floor Area 1051.2 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data Total coil load 3.0 Tons Total coil load 36.5 MBH Sensible coil load 23.3 MBH Coil CFM at peak load 654 CFM Sum of peak zone CFM 927 CFM Sensible heat ratio 0.638 CFM/Ton 215.1 sqft/Ton 345.7 BTU/(hr sqft) 34.7 Water flow @ 10.0 F rise 7.30 gpm

Peak coil load occurs at June 15:00

OA DB / WB 92.8 / 75.9 F

Entering DB / WB 85.9 / 71.0 F Leaving DB / WB 53.6 / 53.6 F Resulting RH 52 % Design supply temp. 55.0 F Zone T-stat Check 3 of 3 OK Max zone temperature deviation 0.0 F

Preheat Coil Sizing Data Max coil load 8.9 MBH Coil CFM at Design Heating 512 CFM Max coil CFM 654 CFM Water flow @ 20.0 F drop 0.89 gpm

Load occurs at Design Heating Ent. DB / Lvg DB 33.8 / 50.0 F

Supply Fan Sizing Data Design CFM 654 CFM Design CFM occurs at July 21:00 Design CFM/sqft 0.62 CFM/sqft Sum of peak zone CFM 927 CFM VAV Fan Diversity 29.5 %

Fan motor BHP 0.36 BHP Fan motor kW 0.28 kW Fan total static 2.00 in wg

Outdoor Ventilation Air Data Design airflow CFM 393 CFM CFM/sqft 0.37 CFM/sqft

CFM/person 65.48 CFM/person

Hourly Analysis Program 6.2 Page 26 of 39

Zone Sizing Summary for EX AHU-4

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

Air System Information Air System Name EX AHU-4 Equipment Class CW AHU Air System Type VAV

Number of zones 3 Floor Area 1051.2 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

1-TU-4-01 60 18 0.27 0.8 0.08 0.0 0.00 0

1-TU-4-02 333 333 0.60 14.3 1.43 0.0 0.00 0

1-TU-4-03 535 160 1.96 6.9 0.69 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

1-TU-4-01 1.3 July 21:00 0.2 223.8

1-TU-4-02 1.3 July 21:00 0.4 555.3

1-TU-4-03 11.5 July 21:00 0.2 272.1

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

1-TU-4-01

CORRIDOR 0.1 July 22:00 6 0.1 72.0 0.08

OFFICE 1.2 July 21:00 54 0.1 151.8 0.35

1-TU-4-02

CLEAN STORAGE D337-1 1.3 July 21:00 333 0.4 555.3 0.60

1-TU-4-03

LOUNGE C265B-1 11.5 July 21:00 535 0.2 272.1 1.96

Hourly Analysis Program 6.2 Page 27 of 39

Ventilation Sizing Summary for EX AHU-4

Design Ventilation Airflow Rate 393 CFM

2. Space Ventilation Analysis

Zone Name / Space Name

Floor Area

(sqft) Maximum

Occupants

Maximum Supply Air

(CFM)

Required Outdoor Air

(CFM/person)

Required Outdoor Air

(CFM/sqft)

Required Outdoor Air

(CFM)

Required Outdoor Air

(% of supply)

Required Outdoor Air

(ACH)

Uncorrected Outdoor Air

(CFM)

Direct Exhaust Air

(CFM)

1-TU-4-01

CORRIDOR 72.0 0.0 6.0 0.00 0.06 0.0 0.0 0.00 4.3 0.0

OFFICE 151.8 1.0 53.5 5.00 0.06 0.0 0.0 0.00 14.1 0.0

1-TU-4-02

CLEAN STORAGE D337-1 555.3 0.0 333.1 0.00 0.00 0.0 0.0 4.00 0.0 0.0

1-TU-4-03

LOUNGE C265B-1 272.1 5.0 534.6 5.00 0.06 0.0 0.0 0.00 41.3 0.0

Totals 927.3 392.9

Hourly Analysis Program 6.2 Page 28 of 39

Air System Heat Balance Summary for EX AHU-4

DESIGN COOLING - JUNE 15:00 DESIGN HEATING

OA DB / WB 92.8 F / 75.9 F OA DB / WB 29.6 F / 25.0 F

COMPONENT LOADS Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Zone Conditioning - 14657 773 - 1836 0

Plenum Load - 0 0 - 0 0

Return Fan Load 654 CFM 0 - 512 CFM 0 -

Ventilation Load 393 CFM 7295 12052 393 CFM 7803 0

Supply Fan Load 654 CFM 970 - 512 CFM -770 -

Zone Fan Coil Fans Load - 0 - - 0 -

>> Total System Loads - 22922 12825 - 8869 0

Central Cooling Coil - 23263 13221 - 0 0

Preheat Coil - 0 - - 8911 -

Terminal Reheat Coils - 0 - - 0 -

>> Total Conditioning - 23263 13221 - 8911 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Table 2. Zone Heat Balance Loads

DESIGN COOLING - JUNE 15:00 DESIGN HEATING

OA DB / WB 92.8 F / 75.9 F OA DB / WB 29.6 F / 25.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 0 sqft 0 - 0 sqft 0 -

Roof Convection 0 sqft 0 - 0 sqft 0 -

Window Convection 0 sqft 0 - 0 sqft 0 -

Skylight Convection 0 sqft 0 - 0 sqft 0 -

Door Convection 0 sqft 0 - 0 sqft 0 -

Floor Convection 1051 sqft 766 - 1051 sqft 100 -

Interior Wall Convection 2618 sqft 1320 - 2618 sqft 356 -

Ceiling Convection 1051 sqft 1002 - 1051 sqft 365 -

Overhead Lighting Convection 426 W 334 - 0 W 0 -

Task Lighting Convection 0 W 0 - 0 W 0 -

Electric Equipment Convection 0 W 0 - 0 W 0 -

People Convection 6 419 805 0 0 0

Infiltration 0 CFM 0 0 0 CFM 0 0

Miscellaneous Equipment - 10100 0 - 0 0

Air Internal Energy Change - 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 13942 805 - 820 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 29 of 39

System Psychrometrics for EX AHU-4

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

DESIGN COOLING DAY AT JUNE 15:00

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 92.7 0.01548 393 400 7295 12052

Vent - Return Mixing Outlet 85.9 0.01289 654 458 - -

Preheat Coil Outlet 85.9 0.01289 654 458 0 -

Central Cooling Coil Outlet 53.6 0.00874 654 458 23263 13221

Supply Fan Outlet 55.0 0.00874 654 458 970 -

Cold Supply Duct Outlet 55.0 0.00874 654 458 - -

Zone Air - 73.2 0.00903 654 548 14657 773

Return Air Outlet 75.5 0.00899 654 544 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.075 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4725.5 BTU/(hr-CFM) Site Altitude = 123.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

1-TU-4-01 1586 Cooling 956 75.7 42 736 0 0

1-TU-4-02 0 Deadband 3640 69.1 235 458 0 0

1-TU-4-03 18996 Cooling 10072 79.4 377 577 0 0

Hourly Analysis Program 6.2 Page 30 of 39

System Psychrometrics for EX AHU-4

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 29.6 0.00158 393 400 -7803 0

Vent - Return Mixing Outlet 33.9 0.00158 512 400 - -

Preheat Coil Outlet 50.0 0.00158 512 400 8911 -

Central Cooling Coil Outlet 50.0 0.00158 512 400 0 0

Supply Fan Outlet 51.4 0.00158 512 400 770 -

Cold Supply Duct Outlet 51.4 0.00158 512 400 - -

Zone Air - 47.7 0.00158 512 400 -1836 0

Return Air Outlet 48.1 0.00158 512 400 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.075 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4725.5 BTU/(hr-CFM) Site Altitude = 123.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

1-TU-4-01 -14519 Heating -102 46.3 18 400 0 0

1-TU-4-02 -69898 Heating -1158 48.2 333 400 0 0

1-TU-4-03 -35875 Heating -576 48.1 160 400 0 0

Hourly Analysis Program 6.2 Page 31 of 39

Air System Sizing Summary for DAC_DCU

Project: 0122093 Gainesville IR

Prepared by: Above Group

Air System Information Air System Name DAC_DCU Equipment Class SPLT AHU Air System Type SZCAV

Number of zones 1 Floor Area 29.5 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data Total coil load 0.7 Tons Total coil load 8.8 MBH Sensible coil load 8.8 MBH Coil CFM at peak load 453 CFM Sum of peak zone CFM 453 CFM Sensible heat ratio 1.000 CFM/Ton 616.1 sqft/Ton 40.1 BTU/(hr sqft) 299.3 Water flow @ 10.0 F rise N/A

Peak coil load occurs at July 21:00

OA DB / WB 84.8 / 73.5 F

Entering DB / WB 75.0 / 61.9 F Leaving DB / WB 57.2 / 55.3 F Resulting RH 48 % Design supply temp. 58.0 F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 F

Central Heating Coil Sizing Data Max coil load 0.8 MBH Coil CFM at Design Heating 453 CFM Max coil CFM 453 CFM Water flow @ 20.0 F drop N/A

Load occurs at Design Heating BTU/(hr sqft) 27.1 Ent. DB / Lvg DB 70.0 / 71.6 F

Supply Fan Sizing Data Design CFM 453 CFM Design CFM/sqft 15.37 CFM/sqft

Fan motor BHP 0.25 BHP Fan motor kW 0.20 kW Fan total static 2.00 in wg

Outdoor Ventilation Air Data Design airflow CFM 0 CFM CFM/sqft 0.00 CFM/sqft

CFM/person 0.00 CFM/person

Hourly Analysis Program 6.2

Zone Sizing Summary for DAC_DCU

Project: 0122093 Gainesville IR

Prepared by: Above Group

Air System Information Air System Name DAC_DCU Equipment Class SPLT AHU Air System Type SZCAV

Number of zones 1 Floor Area 29.5 sqft Location Gainesville Regional, FL, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

DAC 453 453 15.37 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

DAC 8.3 July 7:00 0.1 29.5

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

DAC

ELECTRICAL 8.3 July 7:00 453 0.1 29.5 15.37

Ventilation Sizing Summary for DAC_DCU

Design Ventilation Airflow Rate 0 CFM

2. Space Ventilation Analysis

Zone Name / Space Name

Floor Area

(sqft) Maximum

Occupants

Maximum Supply Air

(CFM)

Required Outdoor Air

(CFM/person)

Required Outdoor Air

(CFM/sqft)

Required Outdoor Air

(CFM)

Required Outdoor Air

(% of supply)

Required Outdoor Air

(ACH)

Uncorrected Outdoor Air

(CFM)

Direct Exhaust Air

(CFM)

DAC

ELECTRICAL 29.5 0.0 453.2 0.00 0.00 0.0 0.0 0.00 0.0 0.0

Totals 453.2 0.0

Hourly Analysis Program 6.2 Page 34 of 39

Air System Heat Balance Summary for DAC_DCU

OA DB / WB 84.8 F / 73.5 F OA DB / WB 29.6 F / 25.0 F

COMPONENT LOADS Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Zone Conditioning - 8154 0 - 1472 0

Plenum Load - 0 0 - 0 0

Return Fan Load 453 CFM 0 - 453 CFM 0 -

Ventilation Load 0 CFM 0 0 0 CFM 0 0

Supply Fan Load 453 CFM 672 - 453 CFM -672 -

Zone Fan Coil Fans Load - 0 - - 0 -

>> Total System Loads - 8826 0 - 800 0

Central Cooling Coil - 8826 0 - 0 0

Central Heating Coil - 0 - - 800 -

>> Total Conditioning - 8826 0 - 800 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Table 2. Zone Heat Balance Loads

DESIGN COOLING - JULY 21:00 DESIGN HEATING

OA DB / WB 84.8 F / 73.5 F OA DB / WB 29.6 F / 25.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 0 sqft 0 - 0 sqft 0 -

Roof Convection 0 sqft 0 - 0 sqft 0 -

Window Convection 0 sqft 0 - 0 sqft 0 -

Skylight Convection 0 sqft 0 - 0 sqft 0 -

Door Convection 0 sqft 0 - 0 sqft 0 -

Floor Convection 29 sqft 20 - 29 sqft 3 -

Interior Wall Convection 331 sqft 105 - 331 sqft 46 -

Ceiling Convection 29 sqft 28 - 29 sqft 9 -

Overhead Lighting Convection 13 W 27 - 0 W 0 -

Task Lighting Convection 0 W 0 - 0 W 0 -

Electric Equipment Convection 0 W 0 - 0 W 0 -

People Convection 0 0 0 0 0 0

Infiltration 0 CFM 0 0 0 CFM 0 0

Miscellaneous Equipment - 8000 0 - 0 0

Air Internal Energy Change - 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 8180 0 - 58 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 35 of 39

System Psychrometrics for DAC_DCU

Project: 0122093 Gainesville IR 04/07/2025

Prepared by: Above Group 9:17 AM

DESIGN COOLING DAY AT JULY 21:00

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 84.7 0.01524 0 400 0 0

Vent - Return Mixing Outlet 75.0 0.00887 453 400 - -

Central Cooling Coil Outlet 57.2 0.00887 453 400 8826 0

Central…