This is Addendum #2 issued by Virginia's Community Colleges (VCCS) and Mountain Empire Community College (MECC) for Project Code 260-B3260-105 (M23ME173) regarding the Phillip-Taylor-Goodloe Roof Replacement project. The addendum adds Section 16670 Lightning Protection System specifications, requiring the existing lightning system to be removed, safely stored, re-installed and re-certified by a LPI-certified contractor or UL listed lightning protection installation company to meet original installation requirements. The specifications detail requirements for a functional and unobtrusive lightning protection system that must comply with NFPA 780 and UL 96A standards.
The contractor must coordinate with other trades for proper installation, with the roofing contractor responsible for sealing and flashing all lightning protection roof penetrations per manufacturer recommendations. Upon completion, the system must be inspected by Underwriters Laboratories Inc. or another ANSI certified testing agency for compliance, and the contractor must obtain a UL Master Label Certificate of Inspection. The system must bond to the structure, electrode system, and gas piping as required by code (NEC 250.106, NFPA 54:7.13.4), with the lightning protection system label including all services without exceptions.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
16670 - 1
DIVISION 16 - SECTION 16670
LIGHTNING PROTECTION SYSTEM
PART I - GENERAL
1.01 SUMMARY
1. To provide safety for the building and occupants by preventing damage to building structure caused by lightning.
2. The work covered under this section of the specification consists of furnishing labor, materials and services required for the removal, protected storage, re-installation and re-certification of a functional and unobtrusive lightning protection system.
3. Existing lightning system to be removed, safely stored, re-installed and re-certified by a LPI-certified contractor or as a UL listed lightning protection installation company to the requirements of the original installation.
4. Reinstalled lightning protection system shall Bond to the structure, the electrode system, and gas piping as required by code. NEC 250.106, NFPA 54:7.13.4
5. The lightning protection system label shall include all services with no exceptions
6. The inspection shall certify the final installation to obtain a master label for all elements to include the facility and services entering the facility.
1.02 STANDARDS
Standards: The completed lightning protection system shall comply with the latest issue of the following standards which form a part of this specification. Where conflicts occur between the two standards, the requirements of NFPA®780 shall apply.
1. NFPA® 780, Standard for the Installation of Lightning Protection Systems.
2. UL 96A, Installation Requirements for Lightning Protection Systems
1.03 SYSTEM DESIGN
The work covered by this section of the specifications consists of furnishing all labor, Materials and items of service required for the completion of a functional and unobtrusive lightning protection system in strict accordance with this Section of the specifications and the applicable contract drawings. If any departure from the contract drawings or submittal drawings covered below are deemed necessary by the Contractor, details of such departures and reasons therefore shall be submitted as soon as practical to the architect and engineer for approval.
1.05 QUALITY ASSURANCE
1. The lightning protection system shall conform to the requirements and standards for lightning protection systems of UL and NFPA. Upon completion, application shall be made to the Underwriters Laboratories, Inc. for inspection and issuance of the UL Master Label.
2. The installing contractor shall apply for inspection of the completed system by UL field representatives. The system is to be inspected by Underwriters Laboratories Inc, or other ANSI certified testing agency for compliance with NFPA® 780. The system shall be without deviation and the UL field representative will issue a UL Master Label® Certificate of Inspection for
16670 - 2
Lightning Protection Systems or Letter of Findings at completion of the installation.
PART 2 - PRODUCTS
2.01 This section not used
PART 3 - EXECUTION
3.01 Installation: The installation shall be accomplished by an experienced installation company that is listed with Underwriters Laboratories for lightning protection installation. All equipment shall be re-installed in a neat, workmanlike manner. The re-installed system shall consist of a complete conductor network at the roof and include air terminals, connectors, splicers, bonds, down leads and proper ground terminals.
3.02 Coordination: The lightning protection installer will work with other trades to ensure a correct, neat and unobtrusive installation. The roofing contractor will be responsible for sealing and flashing all lightning protection roof penetrations as per the roof Manufacturer’s recommendations.
Note: Lightning Protection penetrations and/or attachment procedures should be addressed in the roofing section of the specifications.
3.03 INSPECTION AND CERTIFICATION
1. Upon completion of the installation, the contractor shall re-certify the re-installed lightning protection system by a LPI-certified contractor or as a UL listed lightning protection installation company to the requirements of the original installation. Submit lightning protection system UL Master Label.
END OF SECTION 16670
| 260-B3260-105 (M23ME173) Phillip-Taylor-Goodloe ADDENDUM # 2 |
| 16670 - Lightning Protection System |
| PART I - GENERAL |
| PART 2 - PRODUCTS |
| PART 3 - EXECUTION |
END OF SECTION 16670