The document is a project drawing file related to a state and local contract opportunity for the Godwin Hall Sprinkler, Exit and Emergency Lights, and Generators project at Mountain Empire Community College in Big Stone Gap, Virginia. The project, identified as PC#260-18279-002, involves the installation of a new fire protection (wet) sprinkler system throughout Godwin Hall, as well as the provision of a new generator for Godwin and Holton Halls. Sealed bids will be received electronically through eVA or at the Virginia Community College System office in Richmond, Virginia, with a deadline of 2:00 P.M. sharp on Monday, April 8, 2024. A pre-bid conference will be held on Wednesday, March 13, 2024, at Mountain Empire Community College, and attendance is optional but highly recommended.
The contract will require a Standard Commonwealth Bid Bond (form CO-10.2) and Contract Security, regardless of the bid amount. The bidder or offeror must be a registered vendor in eVA. The project is located in Wise County, Virginia, and the contract will be awarded by the Virginia Community College System.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CAMPUS MAP
BIG STONE GAP, VA.
MOUNTAIN EMPIRE COMMUNITY COLLEGE
GODWIN HALL SPRINKLER, EXIT AND
EMERGENCY LIGHTS, AND GENERATORS
3441 MOUNTAIN EMPIRE ROAD,
BIG STONE GAP, VA, 24219
BID DOCUMENTS
PROJECT CODE: 260-18279-002
OWNER: VIRGINIA COMMUNITY COLLEGE SYSTEM
INDEX OF DRAWINGS
T-1 TITLE SHEET
E-001 - ELECTRICAL LEGEND, GENERAL NOTES, DETAILS AND ABBREVIATIONS
E-GH1 - GODWIN HALL - GROUND FLOOR PLAN - ELECTRICAL DEMOLITION
E-GH2 - GODWIN HALL - FIRST FLOOR PLAN - ELECTRICAL DEMOLITION
E-GH3 - GODWIN HALL - GROUND FLOOR PLAN - ELECTRICAL NEW WORK
E-GH4 - GODWIN HALL - FIRST FLOOR PLAN - ELECTRICAL NEW WORK
E-GH5 - GODWIN HALL - PANELBOARD SCHEDULES AND VOLTAGE DROP CALCULATIONS
E-GH6 - GODWIN HALL - ONE-LINE DIAGRAM AND GROUNDING SCHEMATICS
E-GH7 - GODWIN HALL - GROUND FLOOR PLAN - EMERGENCY EGRESS PHOTOMETRICS
E-GH8 - GODWIN HALL - FIRST FLOOR PLAN - EMERGENCY EGRESS PHOTOMETRICS
SP-1 GODWIN HALL - LEGEND AND DETAILS - SUPPRESSION
SP-2 GODWIN HALL - GROUND FLOOR PLAN - SUPPRESSION
SP-3 GODWIN HALL - FIRST FLOOR PLAN - SUPPRESSION
CODE GOVERNING NEW WORK: 2018 VIRGINIA EXISTING BUILDING CODE (VEBC), 2018 VIRGINIA
CONSTRUCTION CODE (VCC)
CODE GOVERNING EXISTING WORK:
ORIGINAL BUILDING - VIRGINIA FIRE SAFETY REGULATIONS (VFSR), PART ONE FOR BUILDINGS
CONSTRUCTED BETWEEN 1949 AND 1973 - GODWIN HALL
CODE MODIFICATIONS FOR EXISTING WORK: NONE KNOWN
T-1
T
IT
LE
S
H E
E T
JTO/DRR CAD/DRR
WAM/RDF LPA
DESIGNED DRAWN
APPROVEDCHECKED
COMM. NO. DATE
SHEET
18147 03/01/2024
M O
U N
T A
IN
E
M P
IR
E
C O
M M
U N
IT
Y
C O
LL
E
G E
G
O D
W
IN
H A
LL
S
P R
IN
K
LE
R
, E X
IT
A
N D
E M
E R
G E
N C
Y L
IG
H
T S
, A N
D G
E N
E R
A T
O R
S B
IG
S
T O
N E
G A
P , V
IR
G
IN
IA
P
R O
JE
C
T C
O D
E
0-
9-
REVISION DATE
SUBMITTAL DATE
8 8 16 324
1/8" = 1'-0"
( IN FEET )
GRAPHIC SCALE
C O M M O
N W
EA
LTH OF
V
IR
G I N I A
P R O
F E
SS IONAL E
N G
IN
E R E
C O M M O
N W
EA
LTH OF
V
IR
G I N I A
P R O
F E
SS IONAL E
N G
IN
E R E
03/01/24 03/01/24
2018, Virginia Uniform Statewide Building Code (VUSBC)
2010, ADA Standards For Accessible Design (ASAD) Dated September 15, 2010
2022, Commonwealth of Virginia Construction and Professional Service Manual (CPSM), Revision 1
OWNER: Virginia Community College System
ADDRESS: 3441 Mountain Empire Road, Big Stone Gap, VA, 24219
BUILDING NUMBER: 1 - GODWIN HALL
CONSTRUCTION TYPE: 2B
OCCUPANT USE GROUP: B
BUILDING AREA GROSS: 44,349 SF
RENOVATION AREA GROSS: 44,349 SF
NUMBER OF STORIES: 2
FIRE SUPPRESSION: NONE
FIRE ALARM: MANUAL
VICINITY MAP
BIG STONE GAP
BIG STONE GAP VA.
AN ASBESTOS INSPECTION WAS PERFORMED AND ACM WAS FOUND
GENERALLY IN THE AREAS INDICATED. HOWEVER, THE WORK IN THIS
PROJECT IS NOT INTENDED TO DISTURB THE EXISTING ACM. THE
ASBESTOS INSPECTION REPORT IS INCLUDED WITH THE DRAWING/BID
PACKAGE.
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED
COMPONENTS HAS BEEN CONDUCTED AND WILL BE PROVIDED WITH THE
DRAWING/BID PACKAGE. THIS REPORT IS PROVIDED FOR THE
CONTRACTOR'S USE AND MAY NOT BE ALL INCLUSIVE. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA
OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY
PERTAIN TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND
LEAD-COATED BUILDING COMPONENTS SHALL BE RECYCLED TO THE
EXTENT POSSIBLE.
GENERAL CONSTRUCTION SAFETY NOTES:
1. THE CONTRACTOR SHALL ADDRESS THE PHASING AND TIMING OF THE WORK
ASSOCIATED WITH THIS PROJECT WITH THE OWNER'S BUILDING OCCUPANCY
SCHEDULES TO ENSURE EXISTING LIFE SAFETY SYSTEMS AND COMPONENTS
REMAIN OPERATIONAL AT ALL TIMES THE BUILDING IS OCCUPIED.
2. INTERIM SAFETY MEASURES SHALL BE IMPLEMENTED DURING CONSTRUCTION
TO PROVIDE CONTINUAL FUNCTIONALITY OF THE BUILDING FIRE PROTECTION
SYSTEMS AND MAINTENANCE OF THE MEANS OF EGRESS. WHERE TEMPORARY
DOWNTIME OF FIRE ALARM SYSTEMS IS REQUIRED IN ORDER TO RECONNECT
THE EXISTING CONTROL PANELS TO NEW CIRCUITS, THE DOWNTIME SHALL BE
SCHEDULED WITH THE OWNER AND SHALL BE KEPT TO AN ABSOLUTE MINIMUM.
3. IF TEMPORARY ALTERATIONS TO THE MEANS OF EGRESS ARE REQUIRED, THE
ALTERATIONS SHALL BE REVIEWED BY THE STATE FIRE MARSHAL'S OFFICE
PRIOR TO IMPLEMENTATION.
4. MAINTAIN MEANS OF EGRESS FREE OF OBSTRUCTIONS DURING CONSTRUCTION,
INCLUDING CONSTRUCTION PERSONNEL, MATERIALS, EQUIPMENT, DEBRIS, ETC.
DESIGNED DRAWN
APPROVEDCHECKED
COMM. NO. DATE
SHEET
18147 03/01/2024
M O
U N
T A
IN
E
M P
IR
E
C O
M M
U N
IT
Y
C O
LL
E
G E
G
O D
W
IN
H A
LL
S
P R
IN
K
LE
R
, E X
IT
A
N D
E M
E R
G E
N C
Y L
IG
H
T S
A N
D G
E N
E R
A T
O R
S B
IG
S
T O
N E
G A
P , V
IR
G
O
JE
C
T C
O D
E
0-
9-
REVISION DATE
SUBMITTAL DATE
C O M M O
N W
EA
LTH OF
V
IR
G I N I A
P R O
F E
SS IONAL E
N G
IN
E R E
03/01/24
E-001
E
LE
C T
R
IC
A L
LE
G
E N
D , G
E N
E R
A L
N O
T E
S , D
E T
A
IL
S A
N D
A
B B
R E
V
IA
T
IO
N S
JTO JTO
WAM LPA
MTG. HGT. SYMBOL DESCRIPTION
ELECTRICAL LEGEND
PLAN NOTE DESIGNATION.1
REVISION DESIGNATION.1
NEW CONNECTED TO EXISTING AT THIS POINT.
EXISTING REMOVED FROM THIS POINT.
LIGHTING FIXTURE, LED OR FLUORESCENT, CEILING MOUNTED. SYMBOL SIZE VARIES
WITH LIGHTING FIXTURE TYPE.
LIGHTING FIXTURE, LED OR FLUORESCENT, CEILING MOUNTED WITH INTEGRAL
EMERGENCY LED DRIVER OR BATTERY BALLAST OR CONNECTED ON EMERGENCY
CIRCUIT. (TYPICAL FOR ALL LIGHTING FIXTURES)
LIGHTING FIXTURE, LED OR FLUORESCENT, WALL MOUNTED. SYMBOL SIZE VARIES WITH
LIGHTING FIXTURE TYPE.
LIGHTING FIXTURE, LED, INCANDESCENT, FLUORESCENT OR HID, CEILING MOUNTED.
LIGHTING FIXTURE, LED, INCANDESCENT, FLUORESCENT OR HID, WALL MOUNTED.
(12)
LIGHT TRACK. SYMBOL " " INDICATES QUANTITY OF TRACK LIGHT FIXTURES PER TRACK.
NUMBER INDICATES NOMINAL LENGTH IN FEET. TRACK LIGHT SYMBOL MAY VARY.
7'-6" TO CENTER EMERGENCY LIGHTING UNIT, SELF-CONTAINED, SURFACE WALL MOUNTED WITH INTEGRAL
BATTERY AND UNIT MOUNTED LIGHTING HEADS.
EXIT SIGN, CEILING MOUNTED. SHADED QUADRANT(S) INDICATES FACE(S). PROVIDE
ARROWS AS INDICATED ON DRAWINGS. LIGHTING FIXTURE TYPE "X1", UNO.
7'-6" TO CENTER EXIT SIGN, WALL MOUNTED. SHADED QUADRANT(S) INDICATES FACE(S). PROVIDE
ARROWS AS INDICATED ON DRAWINGS. LIGHTING FIXTURE TYPE "X1", UNO.
GENERAL USE SWITCH, SINGLE POLE. LOWER CASE ALPHABETIC SUBSCRIPT, WHERE
SHOWN, INDICATES LOADS CONTROLLED. (TYPICAL FOR ALL SWITCHES)
a4'-0" S
GENERAL USE SWITCH, THREE WAY.34'-0" S
OCCUPANCY SENSOR, STANDARD ON/OFF SWITCHING, CEILING MOUNTED. NUMBER
INDICATES TYPE AS SCHEDULED ON DRAWINGS OR IN SPECIFICATIONS.
O1
RECEPTACLE, DUPLEX, WALL. ALPHA-NUMERIC OR NUMERIC SUBSCRIPT, WHERE SHOWN,
INDICATES CIRCUIT. (TYPICAL FOR ALL RECEPTACLES)
1'-4" TO BOT
GROUND CONNECTION.
GROUND ROD.GR
ELECTRIC MOTOR CONNECTION.M
208/120 VOLT PANELBOARD.6'-0"
480/277 VOLT PANELBOARD.6'-0"
NON-FUSIBLE SAFETY SWITCH, WALL OR EQUIPMENT MOUNTED. NUMBER INDICATES
NON-FUSED/3-POLE/60 AMP RATING.N/3/60
5'-0"
FUSIBLE SAFETY SWITCH, WALL OR EQUIPMENT MOUNTED. NUMBER INDICATES
FUSED/3-POLE/60 AMP RATING/45 AMP FUSES.F/3/60/45
5'-0"
CIRCUIT DESIGNATION. DESIGNATION SHOWN INDICATES PANEL 2HB1 AND CIRCUIT
NUMBER 24.
2HB1-24
CONDUIT EXPOSED.
CONDUIT CONCEALED IN OR BELOW FLOOR SLAB OR BELOW GRADE.
CONDUIT CONCEALED IN WALL OR ABOVE CEILING.
EXISTING CONDUIT TO REMAIN.ER
EXISTING CONDUIT TO BE REMOVED.
NOTES (ELECTRICAL LEGEND):
1. THESE ARE STANDARD ELECTRICAL SYMBOLS AND MAY NOT ALL APPEAR ON THE PROJECT DRAWINGS.
HOWEVER, WHEREVER AN ELECTRICAL SYMBOL APPEARS ON THE PROJECT DRAWINGS, THE ITEM SHALL BE
FURNISHED AND INSTALLED.
2. MOUNTING HEIGHTS ARE FROM FINISHED FLOOR TO TOP OF OUTLET OR EQUIPMENT, UNO. WHERE THE
MOUNTING HEIGHT INDICATED ON THE DRAWINGS IS DIFFERENT FROM THE LEGEND, THE DRAWING TAKES
PRECEDENT. SEE DRAWINGS FOR MOUNTING HEIGHTS NOT INDICATED IN THE LEGEND.
3. SEE ELECTRICAL ABBREVIATIONS FOR ALPHABETIC SUBSCRIPT WITH SYMBOL, UNO.
ELECTRIC WATER COOLEREWC
SCCR SHORT CIRCUIT CURRENT RATING
1. ALL ABBREVIATIONS LISTED MAY NOT APPLY TO THIS PROJECT. REFER TO OTHER ABBREVIATION LISTS
NOTE (ELECTRICAL ABBREVIATIONS):
ELSEWHERE IN THESE DOCUMENTS FOR ABBREVIATIONS NOT LISTED HERE.
IG
IMC INTERMEDIATE METAL CONDUIT
ISOLATED GROUND
GF,GFI,GFCI
FLUORFLUOR
HPF
HZ
HW
HPS
HTR
HP
HID
HOA
HG
H OR HOR
GND
FC
GEN
FXTRFXTR
FSD
FSS
FACPFACP
FDR
FA
EXIST
EXT
HIGH INTENSITY DISCHARGE
HORSEPOWER OR HEAT PUMP
HIGH PRESSURE SODIUM
HIGH POWER FACTOR
HAND-OFF-AUTOMATIC
HOT WATER
HERTZ
HEATER
HORIZONTAL
HOSPITAL GRADE
GROUND
FIRE/SMOKE DAMPER
FUSIBLE SAFETY SWITCH
FIRE ALARM CONTROL PANELFIRE ALARM CONTROL PANEL
FOOTCANDLE
GENERATOR
FLUORESCENTFLUORESCENT
GROUND FAULT CIRCUIT INTERRUPTER
FIXTURE
EXISTING
EXTERIOR
FIRE ALARM
FEEDER
WP WEATHERPROOF
TRANSFORMER
TRANSFER
XFMR
XFER
TC TIME CLOCK
VOLT-AMPERE
UNDERGROUND
WATT OR WIRE
VOLT-AMPERE REACTIVE
UNLESS NOTED OTHERWISE
VOLT
VOLTMETER
W
VM
V
VAR
VA
UNDERFLOOR
TYPICAL
TELEVISION
TELEPHONE
UG
UNO
UF
TYP
TV
TEL
MOTOR OPERATED SMOKE DAMPER
SURGE SUPPRESSOR
SYMMETRICAL
SWITCHBOARD
SURFACE RACEWAY
SOLID NEUTRAL
SURFACE METAL RACEWAY
STR STARTER
SWITCHGEAR
SWITCH
SYM
SN
SWGR
SWBD
SW
SECONDARY
SPEAKERSPKR
SS
SR
SMD
SEC
SMR
COMB
E OR EMER
ENG
ER
EQUIP
EP
ENCL
EMT
EML
EM
EMN
ELEC
EL
CTRL
DC
DR
DISC
CW
CU
COND
CONT
CT
CONN
CND
CNTR
EXIST RELOCATED TO THIS LOCATION
EXIST REMOVED
EXIST REMOVED AND NEW INSTALLED
ELECTRICAL METALLIC TUBING
EXIST TO REMAIN
EQUIPMENT
ENCLOSURE
EXPLOSIONPROOF
ENGINE
EMERGENCY
ELECTRIC OR ELECTRICAL
DOOR RELEASE SERVICE
CURRENT TRANSFORMER
CONTROL
DISCONNECT
DIRECT CURRENT
COLD WATER
COPPER
CONTACTOR
CONNECTION
CONDUCTOR
COMBINATION
CENTER
CONDUIT
BRKR
ASYM
AWG
CATV
CCTV
CF
CKT
CLG
CB
CAB
CA
BD
BEL
AM
ATS
AMPL
AIC
AL
AFF
ABV
AFD
AC
ACB
A OR AMP
AMERICAN WIRE GAGE
COMPACT FLUORESCENT
CLOSED CIRCUIT TELEVISION
CABLE TV
CIRCUIT BREAKER
CIRCUIT
CEILING
BUS DUCT
BREAKER
CABINET
CABLE
BELOW
ADJUSTABLE FREQUENCY DRIVE
ABOVE FINISHED FLOOR
ALTERNATING CURRENT
ABOVE COUNTER BACKSPLASH
AMPERES INTERRUPTING CAPACITY
AUTOMATIC TRANSFER SWITCH
AMMETER
ALUMINUM
AMPLIFIER
ASYMMETRICAL
ABOVE
AMPERE
MS
PBS PUSHBUTTON STATION
PANELBOARD
POLYVINYL CHLORIDE
RIGID GALVANIZED STEEL CONDUIT
POTENTIAL TRANSFORMER
RECEPTACLE
QUANTITY
REC
RGS
QTY
POWER
PANEL OR PANELBOARD
PHASE
PRIMARY
PT
PVC
PWR
PRI
PNLBRD
PH
PNL
PULL BOX OR PUSHBUTTON
MOUNTED OR MOUNTING
MAGNETIC STARTER
MERCURY VAPOR
NON-FUSIBLE SAFETY SWITCH
NATIONAL ELECTRICAL CODE
NFSS
OVERHEAD
POLE
NUMBER
PB
P
OH
NO
NEUTRAL
METER
NEUT
NEC
MTG
MV
MTR
LTG LIGHTING
MAIN DISTRIBUTION FRAME
MAIN LUGS ONLY
THOUSAND CIRCULAR MILS
MOTOR CONTROL CENTER
METAL HALIDE OR MOUNTING HEIGHT
MOTOR OPERATED DAMPER
MASTER ANTENNA TELEVISION
MAIN CIRCUIT BREAKER
MOTOR
MOD
MOT
MLO
MCM
MDF
MH
LUMENS OR LUMINAIRE
MANUAL
MAGNETIC
MAN
MATV
MCC
MCB
MAG
LUM
JUNCTION BOX
LIGHTNING ARRESTER
LOW PRESSURE SODIUM
KILOWATT-HOUR
KILOVOLT-AMPERE
KILOVOLT-AMPERE REACTIVE
KILOWATT
KWH
LPS
LA
KVAR
KW
KVA
KILOVOLT
THOUSAND CIRCULAR MILS
JB
KCMIL
KV
DB DOOR BELL
DS DOOR SWITCH
GD GARAGE DOOR
C COUNTERTOP
ERC ELEVATOR RECALL
ELEV ELEVATOR
UNDERWRITERS' LABORATORIESUL
HGT HEIGHT
REFRIGERATORREFRIG
BOT BOTTOM
DIM DIMENSION
MINIMUMMIN
DWG DRAWING
ARC FAULT INTERRUPTERAF OR AFI
FACU FIRE ALARM CONTROL UNIT
SURGE PROTECTIVE DEVICESPD
EXIST REMOVED AND RELOCATED
VERTICALVERT
ELECTRICAL ABBREVIATIONS
NIGHT LIGHTNL
SB SOUNDER BASE
RELAY BASERB
MASS NOTIFICATION SYSTEMMNS
KNOCKOUTKO
IC INTERCOM OR INTERRUPTING CAPACITY
TAMPER RESISTANTT
LRP LIGHTING RELAY PANEL
CR CORROSION RESISTANT
NORMALN OR NORM
SL SINGLE STATION
UNDERCOUNTERUC
S/O SPACE ONLY
LIGHT EMITTING DIODELED
SPECIAL PURPOSESP
MANUAL MOTOR STARTERMMS
ECNC EXIST CND AND NEW CONDS
ABD ABANDONED
AIP ABANDONED IN PLACE
INITIALINIT
GFP GROUND FAULT PROTECTION/PROTECTED
INCANDESCENTINC
BAS BUILDING AUTOMATION SYSTEM
MAXIMUM OVER CURRENT PROTECTIONMOCP
MINIMUM CIRCUIT AMPACITY MCA
IDF INTERMEDIATE DISTRIBUTION FRAME
MOTOR/GENERATORM/G
WIRE GUARDWG
GTD GENERATOR TRANSFER DEVICE
VARIABLE FREQUENCY DRIVEVFD
EGC EQUIPMENT GROUNDING CONDUCTOR
GEC GROUNDING ELECTRODE CONDUCTOR
EC EMPTY CONDUIT
G RECEPTACLE GUARD
USB CHARGERU
GENERAL NOTES:
1. LOAD SIDE CONDUCTOR AND CONDUIT SIZES FROM DISCONNECT SWITCHES TO EQUIPMENT SHALL BE THE SAME AS LINE SIDE CONDUCTORS AND CONDUIT UNLESS NOTED
OTHERWISE.
2. CAREFULLY COORDINATE ALL ELECTRICAL EQUIPMENT LOCATIONS WITH DUCTWORK, PIPING AND MECHANICAL EQUIPMENT. MAINTAIN ALL CLEARANCES AND SPACES REQUIRED
BY THE NEC.
3. WHERE MULTIPLE CIRCUITS ARE COMBINED IN A SINGLE CONDUIT, DERATE CONDUCTORS PER THE NEC.
4. SEE SPECIFICATION SECTION 26 0519 FOR REQUIREMENTS REGARDING OVERSIZING CONDUCTORS FOR 1-POLE 15- AND 20-AMP CIRCUITS TO REDUCE VOLTAGE DROP - THESE
OVERSIZING REQUIREMENTS TAKE PRECEDENCE OVER THE WIRE AND CONDUIT SIZES SHOWN IN THE PANEL SCHEDULES. OVERSIZED CONDUCTORS FOR VOLTAGE DROP ON
OTHER CIRCUITS ARE INDICATED IN THE PANEL SCHEDULES.
5. UNLESS INDICATED OTHERWISE, ALL EXIT SIGNS AND THE VOLTAGE SENSING TERMINALS OF ALL EMERGENCY BATTERY PACKS AND GTD'S SHALL BE CONNECTED AHEAD OF ALL
SWITCHES, RELAYS, SENSORS AND POWER PACKS WITH 2-#12 AND 1-#12 GROUND IN 1/2" CONDUIT.
6. ALL EMERGENCY LIGHTING FIXTURES SHALL BE MARKED SO AS TO BE IDENTIFIED BY VISUAL INSPECTION FOR TESTING PURPOSES. IDENTIFICATION SHALL BE BY ONE 1/2" RED
SELF-STICK DOT ON THE VERTICAL PORTION OF LOUVER OR ON THE TOP OF THE LENS.
7. EXACT LOCATION AND ORIENTATION OF OCCUPANCY SENSORS SHALL BE AS RECOMMENDED BY MANUFACTURER TO OBTAIN COMPLETE COVERAGE. IF THE CONTRACTOR USES
A SENSOR THAT HAS A COVERAGE PATTERN DIFFERENT FROM THAT WHICH IS SPECIFIED, AND AS A RESULT ADDITIONAL SENSORS ARE REQUIRED TO COMPLETELY COVER A
SPACE, THE CONTRACTOR SHALL PROVIDE ADDITIONAL SENSORS AS REQUIRED (CONNECTED IN PARALLEL WITH EACH OTHER) AT NO ADDITIONAL COST TO THE OWNER. ALL
OCCUPANCY SENSOR TIME DELAYS SHALL BE SET TO NO MORE THAN 30 MINUTES.
8. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ALL PANELBOARD AND SWITCHBOARD FEEDER ENTRANCE LOCATIONS (TOP, BOTTOM, SIDE).
9. PROVIDE ALL 120-VOLT POWER NEEDED FOR THE FIRE ALARM SYSTEM, FED FROM THE NEW LIFE SAFETY PANELBOARD BEING PROVIDED. PROVIDE CIRCUIT BREAKER LOCKS AND
CLEARLY INDICATE IN THE DIRECTORY THAT THEY ARE FIRE ALARM CIRCUITS. PROVIDE RED BREAKER, RED BREAKER LOCK OR RED DOT ON DEAD FRONT COVER BESIDE
BREAKER.
10. CAREFULLY COORDINATE LOCATIONS OF NEW OCCUPANCY SENSORS WITH SPRINKLER HEADS AND HVAC CEILING DEVICES.
11. WHERE NEW RECEPTACLES ARE SHOWN ON EXISTING WALLS AND CEILINGS AND THERE ARE NO EXISTING CONCEALED OUTLET BOXES OR CONDUITS TO REUSE, USE SURFACE
RACEWAY (SINGLE-CHANNEL EXCEPT WHERE SPECIFICALLY INDICATED OTHERWISE), EXCEPT EXPOSED CONDUIT AND BOXES MAY BE USED IN UNFINISHED AREAS
(MECHANICAL/ELECTRICAL/IT ROOMS, STORAGE AND HOUSEKEEPING CLOSETS, ETC.).
12. WHERE RE-USE OF EXISTING CONDUIT, WIRING AND/OR OUTLET BOXES IS INDICATED, ALSO PROVIDE NEW MATERIALS IF NECESSARY. IF NEW EXPOSED MATERIALS ARE NEEDED, USE SURFACE RACEWAY (SINGLE-CHANNEL EXCEPT WHERE SPECIFICALLY INDICATED OTHERWISE), EXCEPT EXPOSED CONDUIT AND BOXES MAY BE USED IN UNFINISHED AREAS
(MECHANICAL/ELECTRICAL/IT ROOMS, STORAGE AND HOUSEKEEPING CLOSETS, ETC.).
13. WHERE SURFACE RACEWAY IS USED, COORDINATE WITH OTHER WALL MOUNTED APPURTENANCES IN ORDER TO AVOID INTERFERENCE WITH RACEWAY.
14. MODIFY EXISTING PANEL SCHEDULES TO ACCURATELY REFLECT ALL CHANGES MADE AS PART OF THIS CONTRACT. ALL NEW BREAKERS IN EXISTING PANELS SHALL MATCH
EXISTING AIC. PROVIDE NEW "TYPED" AS-BUILT PANEL SCHEDULES, HANDWRITTEN PANEL SCHEDULES WILL NOT BE ACCEPTED.
15. FOR ALL EXTERIOR UNDERGROUND CONDUIT AND WIRING, CAREFULLY COORDINATE ALL WORK WITH EXISTING SOIL CONDITIONS AND WITH EXISTING UTILITIES IN ORDER TO
AVOID CONFLICTS. NOTIFY ENGINEER IF ROUTING MUST BE DIFFERENT FROM WHAT IS SHOWN ON THE DRAWINGS.
16. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING BID IN ORDER TO VERIFY ALL EXISTING CONDITIONS, TO DETERMINE THE FULL EXTENT OF DEMOLITION WORK
REQUIRED, AND TO DETERMINE THE FULL EXTENT OF RELOCATION AND MODIFICATION WORK REQUIRED FOR ELECTRICAL WORK (DUE TO OTHER DISCIPLINES INTERFERING OR
ANY OTHER REASON). EXISTING SPACE IS TIGHT IN MANY AREAS (PARTICULARLY ABOVE CEILINGS), AND THE CONTRACTOR SHALL BE FULLY RESPONSIBLE TO COORDINATE ALL
ELECTRICAL WORK WITH BOTH NEW AND EXISTING PIPING, DUCTWORK, CONDUIT, ETC. NO CHANGE ORDERS WILL BE APPROVED FOR ADDITIONAL WORK DUE TO THE
CONTRACTOR NEGLECTING TO VISIT THE SITE AND GATHER ALL NECESSARY INFORMATION.
EQUIPMENT GROUNDING
CONDUCTOR FROM
PRIMARY FEEDER
SYSTEM BONDING JUMPER
SIZED PER NEC TABLE
250.102 (C)(1) AND 250.28(D)
NEAREST GROUNDING
ELECTRODE PER 2011 NEC
250.30(A)(4), INCLUDING
EXCEPTION NO. 1
GROUNDING ELECTRODE
CONDUCTOR (IN CONDUIT WHEN
REQUIRED BY NEC 250.64(B))
TRANSFORMER
ENCLOSURE
NEUTRAL
FIRST SECONDARY
DISCONNECTING MEANS
ENCLOSURE
PRIMARY
A B C
N
A B C
SECONDARY
GROUND
SUPPLY-SIDE BONDING JUMPER
SIZED PER NEC TABLE 250.102
(2)(1) AND 250.102 (C)
3-PHASE DRY-TYPE TRANSFORMER
CONNECTION SCHEMATIC
NO SCALE
GENERAL DEMOLITION NOTES:
1. SCOPE: THE SCOPE OF ELECTRICAL DEMOLITION IS DEFINED IN THE FOLLOWING NOTES AND ON THE DRAWINGS;
THE DRAWINGS ARE ONLY INTENDED TO BE A PARTIAL REPRESENTATION OF THE ACTUAL DEMOLITION WORK
REQUIRED. THESE NOTES ONLY APPLY TO THE AREAS OF RENOVATION. IN GENERAL, THE DEMOLITION SCOPE IS
THE REMOVAL AND/OR MODIFICATION OF PORTIONS OF THE EXISTING ELECTRICAL SYSTEMS AS INDICATED ON
THE DEMOLITION FLOOR PLANS TO FACILITATE RECONNECTION OF EQUIPMENT AND FIXTURES TO NEW
ELECTRICAL EQUIPMENT.
2. RECEPTACLES AND SWITCHES: EXCEPT WHERE INDICATED OTHERWISE, EXISTING RECEPTACLES AND SWITCHES
AND CIRCUITS SHALL REMAIN. WHERE FLUSH MOUNTED SWITCHES TO BE REMOVED (NOT REPLACED IN PLACE)
OCCUR IN EXISTING WALLS TO REMAIN, REMOVE DEVICE AND COVER PLATE, CUT WIRES AS SHORT AS POSSIBLE, AND PROVIDE BLANK COVER PLATE. COVER PLATE SHALL MATCH THE EXISTING TO REMAIN COVER PLATES IN THE
SPACE. WHERE SURFACE MOUNTED SWITCHES AND RECEPTACLES TO BE REMOVED OCCUR ON EXISTING WALLS
TO REMAIN, ALSO REMOVE ASSOCIATED EXPOSED BOXES, CONDUIT AND SURFACE RACEWAY.
3. DATA, PHONE, CATV AND A/V: ALL EXISTING DATA, PHONE, CATV AND A/V OUTLETS SHALL REMAIN.
4. FIRE ALARM SYSTEM: THE EXISTING FIRE ALARM SYSTEMS SHALL REMAIN AS INSTALLED, EXCEPT THE EXISTING
FIRE ALARM CONTROL PANELS, REMOTE ANNUNCIATORS, AND ANY OTHER EXISTING PORTIONS OF THE FIRE
ALARM SYSTEM REQUIRING 120V POWER SHALL BE DISCONNECTED FROM THE EXISTING 120V CIRCUITS AND
RECONNECTED TO THE NEW LIFE SAFETY PANELBOARDS AS INDICATED ON THE FLOOR PLANS.
5. MECHANICAL EQUIPMENT: THE EXISTING MECHANICAL EQUIPMENT SHALL REMAIN AS INSTALLED UNLESS
OTHERWISE INDICATED ON THE FLOOR PLANS.
6. ELECTRICAL SERVICE: THE EXISTING ELECTRICAL SERVICES SHALL BE RE-USED, BUT SOME DOWNTIME WILL
LIKELY STILL BE REQUIRED FOR INSTALLATION OF NEW CONNECTIONS TO NEW EQUIPMENT. ALL ELECTRICAL
SERVICE DOWNTIME REQUIRED SHALL BE COORDINATED WITH OWNER AND SHALL BE AT THE OWNER'S
CONVENIENCE. DOWNTIME SHALL BE KEPT TO A MINIMUM. ALL EXTENDED DOWNTIME REQUIRED SHALL BE
COORDINATED WITH OWNER AND SHALL BE OUTSIDE OF NORMAL HOURS OF OPERATION.
7. PANELBOARDS: ALL EXISTING PANELBOARDS SHALL REMAIN AS INSTALLED UNLESS OTHERWISE INDICATED ON
THE FLOOR PLANS. UPDATE THE CIRCUIT DIRECTORIES TO REFLECT ALL CIRCUIT CHANGES (CIRCUITS NO LONGER
BEING USED AFTER DEMOLITION WORK, CIRCUITS ADDED, NEW HVAC UNIT ON CIRCUIT, ETC.). PROVIDE NEW
TYPED CIRCUIT DIRECTORIES FOR ALL PANELBOARDS MODIFIED AS PART OF THIS PROJECT. ALL SPARE CIRCUIT
BREAKERS SHALL BE PLACED IN THE 'OFF' POSITION.
8. EXTERIOR LIGHTING: EXCEPT WHERE SPECIFICALLY INDICATED OTHERWISE, ALL EXISTING EXTERIOR
BUILDING-MOUNTED AND CANOPY LIGHTING, ASSOCIATED CONTROLS (TIMECLOCKS, PHOTOSENSORS, ETC.) AND
WIRING SHALL REMAIN. REFER TO THE FLOOR PLANS FOR MODIFICATION WORK REQUIRED FOR THE EXISTING
EXTERIOR LIGHTING SYSTEMS.
9. INTERIOR LIGHTING: ALL EXISTING INTERIOR LIGHTING FIXTURES SHALL REMAIN, EXCEPT WHERE SPECIFICALLY
INDICATED OTHERWISE. EXISTING EMERGENCY LIGHTING FIXTURES SHALL BE MODIFIED AS INDICATED ON THE
FLOOR PLANS (THESE FIXTURES WILL BE RECONNECTED TO THE NEW LIFE SAFETY PANELBOARDS BEING
PROVIDED).
10. EMERGENCY LIGHTING: REFER TO THE FLOOR PLANS FOR THE EXTENT OF DEMOLITION AND MODIFICATION WORK
REQUIRED FOR THE EXISTING EMERGENCY LIGHTING SYSTEMS. IN GENERAL, THE EXISTING EMERGENCY BATTERY
PACKS ARE TO BE REMOVED, AND THE EXISTING EMERGENCY LIGHTING FIXTURES SHALL BE RECONNECTED TO
THE NEW LIFE SAFETY PANELBOARDS BEING PROVIDED.
11. CONDUIT: ALL ACCESSIBLE UNUSED CONDUIT SHALL BE REMOVED; ALL INACCESSIBLE UNUSED CONDUIT SHALL BE
ABANDONED. ALL CONDUIT TO NEW DEVICES AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE.
12. WIRING: ALL WIRING TO DEMOLISHED DEVICES AND EQUIPMENT SHALL BE REMOVED, UNLESS NOTED OTHERWISE.
ALL EXISTING WIRING TO EXISTING-TO-REMAIN DEVICES AND EQUIPMENT SHALL REMAIN, UNLESS NOTED
OTHERWISE. ALL ACCESSIBLE UNUSED WIRING SHALL BE REMOVED; ALL INACCESSIBLE UNUSED WIRING SHALL BE
ABANDONED. ALL WIRING TO NEW DEVICES AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE.
13. MAINTAIN CIRCUIT CONTINUITY AS NECESSARY IN ALL DEMOLITION WORK.
14. THE CONTRACTOR SHALL INFORM THE OWNER'S REPRESENTATIVE OF ELECTRICAL EQUIPMENT REMOVED FROM
THE BUILDING. IF THE OWNER DESIRES TO RETAIN EQUIPMENT, HE WILL REMOVE IT FROM THE SITE. ALL
EQUIPMENT NOT RETAINED BY THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM THE SITE. DISPOSAL OF ALL EQUIPMENT CONTAINING HAZARDOUS MATERIALS SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR, AND THE COST OF DISPOSAL SHALL BE INCLUDED.
15. INFORMATION ON DEMOLITION DRAWINGS DOES NOT NECESSARILY INDICATE ALL EXISTING EQUIPMENT AND
DEVICES. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING BID AND SHALL VERIFY ALL DEMOLITION
REQUIRED. ADDITIONAL COMPENSATION WILL NOT BE ALLOWED FOR DEMOLITION DUE TO CONTRACTOR NOT
VISITING SITE AND DETERMINING FULL SCOPE OF DEMOLITION REQUIRED.
16. SEE THE DEMOLITION FLOOR PLANS FOR ADDITIONAL DEMOLITION REQUIREMENTS. ON THE DEMOLITION FLOOR
PLANS AND RISERS, ALL DASHED ITEMS SHALL BE REMOVED AND ALL SOLID ITEMS SHALL REMAIN, UNLESS NOTED
OTHERWISE. NEW WORK FLOOR PLANS MAY CONTAIN ADDITIONAL DEMOLITION INFORMATION IN SOME
LOCATIONS.
CONDUIT PENETRATION FIRESTOPPING DETAIL
NO SCALE
System No. W-L-1054
SECTION A-A
A
A
1A
2 1B
C
C
LA
SS I F IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F RATINGS —1 AND 2 HR (SEE ITEMS 1 AND 3) F RATINGS — 1 AND 2 HR (SEE ITEMS 1 AND 3)
T RATING — 0 HR FT RATING — 0 HR
L RATING AT AMBIENT — LESS THAN 1 CFM/SQ FT FH RATINGS —1 AND 2 HR (SEE ITEMS 1 AND 3)
L RATING AT 400 F — LESS THAN 1 CFM/SQ FT FTH RATING — 0 HR
FTH RATING — 0 HR
L RATING AT AMBIENT — LESS THAN 1 CFM/SQ FT
L RATING AT 400 F — LESS THAN 1 CFM/SQ FT
1. WALL ASSEMBLY — THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF
THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN
THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS — WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST
OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC. STEEL STUDS TO BE MIN 2-1/2 IN. (64 MM) WIDE
AND SPACED MAX 24 IN. (610 MM) OC. WHEN STEEL STUDS ARE USED AND THE DIAM OF OPENING EXCEEDS THE WIDTH
OF STUD CAVITY, THE OPENING SHALL BE FRAMED ON ALL SIDES USING LENGTHS OF STEEL STUD INSTALLED BETWEEN
THE VERTICAL STUDS AND SCREW-ATTACHED TO THE STEEL STUDS AT EACH END. THE FRAMED OPENING IN THE WALL
SHALL BE 4 TO 6 IN. (102 TO 152 MM) WIDER AND 4 TO 6 IN. (102 TO 152 MM) HIGHER THAN THE DIAM OF THE
PENETRATING ITEM SUCH THAT, WHEN THE PENETRATING ITEM IS INSTALLED IN THE OPENING, A 2 TO 3 IN. (51 TO 76 MM)
CLEARANCE IS PRESENT BETWEEN THE PENETRATING ITEM AND THE FRAMING ON ALL FOUR SIDES.
B. GYPSUM BOARD* — 5/8 IN. (16 MM) THICK, 4 FT (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM BOARD
TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE
INDIVIDUAL U300 OR U400 SERIES DEMVSIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 32-1/4
IN. (819 MM) FOR STEEL STUD WALLS. MAX DIAM OF OPENING IS 14-1/2 IN. (368 MM) FOR WOOD STUD WALLS. THE F AND
FH RATINGS OF THE FIRESTOP SYSTEM ARE EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY.
2. THROUGH-PENETRANTS — ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR
ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE SHALL BE MIN 0 IN. TO MAX 2-1/4 IN. (57 MM). PIPE MAY
BE INSTALLED WITH CONTINUOUS POINT CONTACT. PIPE, CONDUIT OR TUBING MAY BE INSTALLED AT AN ANGLE NOT
GREATER THAN 45 DEGREES FROM PERPENDICULAR. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES
OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE — NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE — NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. CONDUIT — NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR 6 IN. (152 MM) . DIAM STEEL
CONDUIT.
D. COPPER TUBING — NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
E. COPPER PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
3. FILL, VOID OR CAVITY MATERIAL* — SEALANT — MIN 5/8 IN. (16 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN THE
ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. AT THE POINT OR CONTINUOUS CONTACT LOCATIONS BETWEEN PIPE AND
WALL, A MIN 1/2 IN. (13 MM) DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE PIPE WALL INTERFACE ON BOTH
SURFACES OF WALL.
* INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR JURISDICTIONS EMPLOYING THE UL OR CUL
CERTIFICATION (SUCH AS CANADA), RESPECTIVELY.
CONDUIT PENETRATION FIRESTOPPING DETAIL
NO SCALE
System No. C-AJ-1630
SECTION A-A
1. Floor or Wall Assembly — See Configuration A above. Reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/cu meter) concrete as specified in the Table in Item 4 below. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of sleeved opening is 32
in. (813 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
1A. Floor Assembly — See Configuration B above. Min 6 in. (152 mm) thick UL Classified hollow-core Precast Concrete Units*. Max diam of opening is 7 in. (178 mm).
See Precast Concrete Units (CFTV) category in the Fire Resistance Directory for names of manufacturers.
2. STEEL SLEEVE (OPTIONAL) — NOM 32 IN. (813 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE SLEEVE CAST OR
GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH BOTH SURFACES OF FLOOR OR WALL. AS AN OPTION, SLEEVE MAY
EXTEND MAX 2 IN. ABOVE TOP SURFACE OF FLOOR OR BEYOND ONE OR BOTH SURFACES OF WALL. STEEL SLEEVE MAY BE USED
IN 2 AND 3 HR F RATED SYSTEMS ONLY.
3. THROUGH PENETRANTS — ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR
ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF
FLOOR OR WALL ASSEMBLY. SEE TABLE IN ITEM 4 FOR SIZES OF PENETRANTS A, B, D AND E THAT MAY BE USED. SEE ITEM 3C
BELOW FOR SIZE OF CONDUIT THAT MAY BE USED. THE ANNULAR SPACE SHALL BE AS SPECIFIED IN TABLE IN ITEM 4 BELOW. THE
FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE — SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE — CAST OR DUCTILE IRON PIPE.
C. CONDUIT — NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR NOM 6 IN. (152 MM) DIAM (OR
SMALLER) STEEL CONDUIT.
D. COPPER TUBING — TYPE L (OR HEAVIER) COPPER TUBING.
E. COPPER PIPE — REGULAR (OR HEAVIER) COPPER PIPE.
4. FIRESTOP SYSTEM — THE F RATING OF THE SYSTEM IS DEPENDENT UPON THE TYPE OF CONCRETE, THICKNESS OF CONCRETE, ANNULAR SPACE, FILL AND PACKING MATERIAL THICKNESS, PACKING MATERIAL DENSITY AND PENETRANT SIZE AS SHOWN IN
THE TABLE BELOW. W RATING APPLIES TO ANNULAR SPACES OF MIN 0 IN. (POINT CONTACT) TO MAX 1-7/8 IN. AND TO
CONFIGURATION A DETAIL ONLY.
A
C
C
LA
SS I F IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings — 2, 3 & 4 Hr (See Item 4) F Rating — 2, 3 & 4 Hr (See Item 4)
T Rating — 0 Hr FT Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM/sq ft FH Rating — 2, 3 & 4 Hr (See Item 4)
L Rating At 400 F — Less Than 1 CFM/sq ft FTH Rating — 0 Hr
W Rating — Class 1 (See Item 4) L Rating At Ambient — Less Than 1 CFM/sq ft
L Rating At 400 F — 4 CFM/sq ft
F
Rating hr
Min
Thick
Concrete
In. (mm)
Annular
Space
In. (mm)
Min
Thick
Packing
Mtl
In. (mm)
Min
Density
Packing
Mtl pcf
(kg/cu meter)
Min
Thick
Fill
Mtl, In. (mm)
Penetrant
Size, In. (mm)
Diam
(or Smaller)
D, E
Copper
A, B
(Steel Iron)
2 5-1/2 (140) 0 to 1-7/8 (0 to 48) 5 (127) 4 (64) 1/2 (13) 4 (102) 16 (406)
3 4-1/2 (114) 0 to 2-1/8 (0 to 54) 4-1/4 (108) 4 (64) 1/4 (6) 6 (152) 30 (762)
4 5-1/2 (140) 0 to 1-7/8 (0 to 48) 5 (127) 4 (64) 1/2 (13) 4 (102) 8 (203)
A. Packing Material — Min 4-1/4 or 5 in. (108 or 127 mm) thickness of min 4.0 pcf (64 kg/cu meter) mineral wool batt insulation firmly packed into opening as a permanent form as specified in the Table above. Packing material to be recessed from top surface of floor or top end of sleeve, or from both surfaces of wall or ends of sleeve, as required to accommodate the required thickness of fill material. For hollow-core floor applications as shown in Configuration B, one half of the required thickness of mineral wool packing material shall be installed flush with the bottom surface of the floor and the remaining half of the mineral wool packing material installed at the top of the opening and recessed from the top surface of the floor to accommodate the required thickness of the fill material.
B. Fill, Void or Cavity Material* — Caulk — Min 1/4 or 1/2 in. (6 or 13 mm) thickness of fill material as specified in the Table above applied within the annulus, flush with top surface of floor or top end of sleeve, or with both surfaces of wall or ends of sleeve. At the point contact location between pipe and concrete or sleeve, a min 1/2 in. (13 mm) diam bead of fill material shall be applied. As an option, for hollow-core floors, the packing material (Item 4A) on the bottom surface of the floor may be recessed to accommodate a 1/4 in. (6 mm) depth of fill material installed flush with bottom surface of floor.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-S SIL GG (floors or walls) and CFS-S SIL SL (floors only)
*Bearing the UL Classification Mark
A
A
A
SECTION A-A
CONFIGURATION A
CONFIGURATION B
4B
4A
4B
4B
4A
SUPPLY-SIDE BONDING JUMPER
SIZED PER NEC TABLE 250.102
(2)(1) AND 250.102 (C)
POINTS OF CONTACT:
OWNER'S REPRESENTATIVE:
PRESTON LAYNE
PROJECT MANAGER
MOUNTAIN EMPIRE COMMUNITY COLLEGE
(276) 523-2400 EXT. 248
E-MAIL: PLAYNE@MECC.EDU
POWER COMPANY:
OLD DOMINION POWER COMPANY
(800) 383-5582
FIRE RATED SLEEVES:
WHERE INDICATED ON THE FLOOR PLANS TO PROVIDE "FIRE RATED
SLEEVES" OR WHERE SLEEVES ARE REQUIRED, THEY SHALL BE
PROVIDED WITH PENETRATIONS THROUGH WALLS, CEILINGS, AND
FLOOR ASSEMBLIES THAT ARE TO BE PROTECTED USING TESTED
THROUGH-PENETRATION ASSEMBLIES. ALL PENETRATION
ASSEMBLIES SHALL BE EQUAL TO THE RATING OF THE ASSEMBLY
BEING PENETRATED. PENETRATION ASSEMBLIES SHALL NOT
REDUCE THE F AND T RATINGS.
CLEARANCE MARKINGS:
WHERE CLEARANCE OUTLINES ARE SHOWN ON THE ELECTRICAL
DRAWINGS IN UNFINISHED SPACES WITH CONCRETE FLOORS,
PROVIDE A 2" WIDE YELLOW LINE PAINTED ON THE EXPOSED
CONCRETE FLOOR INDICATING THE ELECTRICAL WORKING SPACE.
STENCIL "NO STORAGE -ELECTRICAL WORKING SPACE" IN 2" HIGH
YELLOW LETTERS CENTERED IN THE OUTLINED AREA. WHERE
CLEARANCE OUTLINES ARE NOT SHOWN ON THE ELECTRICAL
DRAWINGS AND THERE IS NEW ELECTRICAL EQUIPMENT BEING
PROVIDED IN A SPACE, PROVIDE PERMANENT SIGNAGE READING
'NO STORAGE' IN LETTERS LARGER THAN THE ROOM
IDENTIFICATION LETTERS.
SCOPE OF WORK:
THE PRIMARY PURPOSE OF THIS PROJECT IS TO PROVIDE
EMERGENCY POWER TO EXISTING EGRESS LIGHTING
FIXTURES, FIRE ALARM SYSTEMS, AND OTHER LIFE SAFETY
EQUIPMENT IN GODWIN HALL AT MOUNTAIN EMPIRE
COMMUNITY COLLEGE. NO EXISTING LIGHTING FIXTURES
ARE BEING REPLACED IN THIS PROJECT; ONLY THE POWER
SOURCE TO THE EGRESS FIXTURES IS BEING ALTERED.
IN ADDITION TO PROVIDING EMERGENCY POWER FOR LIFE
SAFETY FIXTURES AND SYSTEMS, THIS PROJECT ALSO
INCLUDES THE ADDITION OF 'EQUIPMENT POWER'
BRANCHES FED FROM THE GENERATORS BEING PROVIDED
TO SERVE GODWIN HALL. THESE 'EQUIPMENT BRANCHES'
WILL POWER OWNER-DESIGNATED LOADS UPON LOSS OF
NORMAL POWER.
MODIFICATIONS TO THE EXISTING POWER DISTRIBUTION
SYSTEMS WILL BE REQUIRED IN EACH BUILDING FOR
CONNECTION OF THE STANDBY GENERATORS AND
ASSOCIATED EMERGENCY POWER DISTRIBUTION
EQUIPMENT.
VOLTAGE DROP CALCULATIONS:
REFER TO SHEET E-GH5 FOR VOLTAGE DROP CALCULATIONS FOR
GODWIN HALL.
EQUIPMENT IDENTIFICATION:
• ALL NEW EQUIPMENT LABELED WITH THE PREFIX 'L' IS
PART OF THE LIFE SAFETY BRANCH OF THE EMERGENCY
POWER SYSTEM IN ACCORDANCE WITH NEC 700. PROVIDE
SIGNAGE ON NEC 700 SERVICE-ENTRANCE EQUIPMENT
INDICATING THE TYPE AND LOCATION OF THE
EMERGENCY POWER SOURCE FEEDING THE EQUIPMENT.
• ALL NEW EQUIPMENT LABELED WITH THE PREFIX 'E' IS
PART OF THE EQUIPMENT BRANCH (I.E. OPTIONAL
STANDBY) OF THE EMERGENCY POWER SYSTEM IN
ACCORDANCE WITH NEC 702. PROVIDE SIGNAGE ON NEC
702 SERVICE-ENTRANCE EQUIPMENT INDICATING THE
TYPE AND LOCATION OF THE EMERGENCY POWER
SOURCE FEEDING THE EQUIPMENT.
• TO COMPLY WITH NEC 230.2 (E), PROVIDE A PERMANENT
PLAQUE AT EACH SERVICE DISCONNECTING MEANS
LOCATION AT EACH BUILDING THAT INDICATES ALL OTHER
SERVICES, FEEDERS AND BRANCH CIRCUITS SUPPLYING
THAT BUILDING OR STRUCTURE. THE PLAQUE SHALL
INDICATE THE LOCATION OF THE OTHER SERVICE
DISCONNECTS THAT FEED THE BUILDING.
FIRE ALARM SYSTEM CONTINUITY:
THIS PROJECT INCLUDES RE-WIRING OF THE EXISTING TO
REMAIN FIRE ALARM SYSTEM IN GODWIN HALL. SOME DOWNTIME
WILL BE REQUIRED TO RECONNECT THE EXISTING FIRE ALARM
PANELS TO NEW LIFE SAFETY CIRCUITS. ALL FIRE ALARM
SYSTEM DOWNTIME SHALL BE COORDINATED WITH THE OWNER
AND SHALL BE KEPT TO THE ABSOLUTE MINIMUM.
PHASING:
CONTRACTOR SHALL COORDINATE WITH MECC, VCCS AND THE
ENGINEER TO PROVIDE A PHASING PLAN WHICH ALLOW FOR
INSTALLATION OF THE WORK SUCH THAT IT ACCOMMODATES
THE COLLEGE'S SCHOOL CALENDAR AND CLASS SCHEDULING
REQUIREMENTS.
GODWIN HALL - GROUND FLOOR PLAN - ELECTRICAL DEMOLITION
SCALE: 1/8" = 1'-0"
STOR
MECHANICAL
MAIL ROOM
ELEC
PHYSICAL
PLANT
OFFICE
ELEV
STAIR NO. 1
WORKROOM
MAIL ROOM
STOR.
COMPUTER ROOM
STOR
106WORKRM
CORRIDOR
DATA
HARDWARE ROOM
120A
ODU CLASSROOM
COPY
STOR.
CORRIDOR
DATA / COMM
CLOSET
OFFICE-4
OFFICE-10
OFFICE-3
PHYSICAL PLANT
SHIPPING & RECEIVING
COUN.
ENTRY LOBBY
FILES ROOM
OFFICE-5
OFFICE-4
OFFICE-2
MULTIPURPOSE RM
CLOSET
CLASSROOM
STAIR NO. 2
MEN WOMEN
BUSINESS OFFICE
WORK STATION
147COUN.
OFFICE
OFFICE
STOR
TEL EQUIP
OFFICE
FINANCIAL
AID
OFFICE
COUN.
MEN
EQUIP
WOMEN
CORRIDOR
CLOSET
136A
OFFICE-1
SEC/ RECEPTION
OFFICE
OFFICE
CORRIDOR
OFFICE
HSKG SUPPLIES
CORRIDOR
ODU
CLASSROOM
VENDING ROOM
MULTI-PURPOSE CLASSROOM
OFFICE-8
OFFICE-7
OFFICE-9
WAITING
OFFICE-6
OFFICE-5
DIV. CHAIR
OFFICE-3
OFFICE-1
OFFICE-2
TOOL/ SHOP RM
1111 1 1 1
WAITING/
RECEPT.
ARTS &
SCIENCE LAB
OFFICE-6
1 1
1 5
ADMISSIONS
1 1
CLASSROOM
ODU OFFICE
EXISTING FIRE ALARM
ANNUNCIATOR PANEL
ER
EXISTING FIRE ALARM
ANNUNCIATOR PANEL
ER
EXISTING PANEL-X
EXISTING DISTRIBUTION
PANEL NO. 1
EXISTING
DISTRIBUTION
PANEL NO. 2
EXISTING PANEL-I
EXISTING PANEL-F
EXISTING XFMR
ER
ER
ERER
ER
ER
ER
ER
ER
ER
ER
ER
EXISTING PANEL-E
EXISTING PANEL-DEXISTING PANEL-A
OFFICE
STOR
JAN
7 7 7 7 7
ER ER
ER ER
ER
ER
EM
ER ER
ER
ER
ER ER
ER ER
ER ER
ER
ER
ERERER
ER
ER
ER
ER
ER
ER ER
ER
ER
ER ER
ER
ER
7 7
ER ER ER
ERERER
ER ER ER
ER ER
ER
ER ER ER ER
ERER EM
ER
ERER
ER
ER ER ER
ERERER
ER ER ER
ER
ER
ER
ER ER
ER
ER
ER
ER ER ER
ER
ER
ERERER
ER
ER
ER
ER
ERERERERERERERER
ER
ER
ERER
ER
ER
EM ER
ER
ER
ER
ERERERERERERERERERERER
ER
ERERERERERERERERER
ER ER
ER ER
ER
ER
ER ER
ER ER
ER ERER
ERER
ERER
ERERER
ER
ER
ER
ER
ER 2
ER
ER
ER
ER
ER ER
ERERER
ER
ER
ER
ER ER
ER
ER
EM
EM
ER
ER
ER
ER
DESIGNED DRAWN
APPROVEDCHECKED
COMM. NO. DATE
SHEET
18147 03/01/2024
M O
U N
T A
IN
E
M P
IR
E
C O
M M
U N
IT
Y
C O
LL
E
G E
G
O D
W
IN
H A
LL
S
P R
IN
K
LE
R
, E X
IT
A
N D
E M
E R
G E
N C
Y L
IG
H
T S
A N
D G
E N
E R
A T
O R
S B
IG
S
T O
N E
G A
P , V
IR
G
O
JE
C
T C
O D
E
0-
9-
REVISION DATE
SUBMITTAL DATE
8 8 16 324
1/8" = 1'-0"
( IN FEET )
GRAPHIC SCALE
C O M M O
N W
EA
LTH OF
V
IR
G I N I A
P R O
F E
SS IONAL E
N G
IN
E R E
03/01/24
PLAN NOTES:
1. DISCONNECT THE EMERGENCY LIGHTING FIXTURE FROM EXISTING CIRCUIT AND SWITCH
CONTROL. FIXTURE WILL BE CONNECTED TO NEW LIFE SAFETY CIRCUIT UNDER NEW
WORK. MAINTAIN CONTINUITY OF EXISTING CIRCUIT TO OTHER FIXTURES CONNECTED
TO CIRCUIT. THE EXISTING BATTERY BALLAST SHALL REMAIN AS INSTALLED.
2. DISCONNECT EXISTING EXIT SIGN FROM EXISTING CIRCUIT. FIXTURE WILL BE
CONNECTED TO NEW LIFE SAFETY CIRCUIT UNDER NEW WORK. MAINTAIN CONTINUITY
OF EXISTING CIRCUIT TO OTHER FIXTURES CONNECTED TO CIRCUIT.
3. DISCONNECT THIS FIXTURE FROM EXISTING SWITCH CONTROL. THIS FIXTURE WILL BE
CONNECTED TO A NEW LIFE SAFETY CIRCUIT WITH OCCUPANCY SENSOR CONTROL
UNDER NEW WORK.
4. REMOVE WALL MOUNTED BATTERY PACK UNIT. MAINTAIN CIRCUIT CONTINUITY AFTER
FIXTURE IS REMOVED.
5. DISCONNECT AND REMOVE REMOTE EMERGENCY BATTERY ASSEMBLY. REMOVE
CONNECTING CABLE FROM REMOTE BALLAST TO FIXTURE WHERE IT IS ACCESSIBLE.
FIXTURE WILL BE CONNECTED TO A NEW LIFE SAFETY CIRCUIT UNDER NEW WORK.
6. DISCONNECT THE EXISTING CIRCUIT FROM THE FIRE ALARM CONTROL PANEL AND
RECONNECT TO NEW LIFE SAFETY SHOWN UNDER NEW WORK.
7. NO EXISTING EGRESS LIGHTING IN THIS ROOM.
8. WHERE THE EXISTING FIRE ALARM ANNUNCIATOR IS POWERED BY A 120 VOLT CIRCUIT,
DISCONNECT THE EXISTING CIRCUIT AND RECONNECT THE PANEL TO THE SAME LIFE
SAFETY CIRCUIT THAT IS POWERING THE FIRE ALARM CONTROL PANEL INDICATED ON
THE NEW WORK FLOOR PLANS.
FIRE RATED WALL LEGEND
1-HOUR FIRE SEPARATION
GENERAL NOTES:
1. WHEN EXISTING CEILINGS IN GODWIN ARE REMOVED, THE CONTRACTOR SHALL PROVIDE
COVERPLATES ON ALL EXISTING JUNCTION BOXES ABOVE THE ACCESSIBLE CEILING
SPACES AND ANY WALL MOUNTED BOXES IN THE AREA OF RENOVATIONS WHERE
EXISTING COVERPLATES ARE MISSING. THE CONTRACTOR SHALL ALSO PROVIDE
ADDITIONAL SUPPORTS FOR EXISTING CONDUIT AND JUNCTION BOXES IN THE AREA OF
RENOVATIONS THAT CURRENTLY DO NOT MEET CODE REQUIREMENTS.
2. NOTE THAT THE EXISTING LIGHT FIXTURES IN THE CEILINGS OF GODWIN ARE NOT
PROPERLY SUPPORTED FROM THE BUILDING STRUCTURAL FRAMING ABOVE THE
ACOUSTICAL CEILINGS. PRIOR TO REMOVAL OF EXISTING CEILINGS IN GODWIN THE
CONTRACTOR HAS THE OPTION OF:
2.1. EITHER DISCONNECTING POWER/CONTROLS TO ALL EXISTING LIGHT FIXTURES,
TEMPORARY REMOVING THEM FROM THE CEILINGS AND STORING THE LIGHT
FIXTURES TILL THE NEW CEILINGS ARE IN PLACE AND THEN REINSTALLING AND
RECONNECTING POWER. NOTE THAT WHEN RE-INSTALLING ALL THE EXISTING
LIGHT FIXTURES THEY WILL BE REQUIRED TO BE RE-INSTALLED WITH THE CODE
REQUIRED SUPPORTS TO THE BUILDING STRUCTURAL FRAMING. ALSO NOTE THAT
REMOVING THE EXISTING LIGHT FIXTURES WOULD REQUIRE PROVIDING
TEMPORARY WORK LIGHTING IN THE SPACES.
2.2. OR INSTALLING THE SUPPORTS TO ALL EXISTING LIGHT FIXTURES AS NOTED BELOW.
THE SUPPORTS WILL ALLOW THE LIGHT FIXTURES TO HANG FROM THE BUILDING
STRUCTURAL FRAMING SO THAT DISCONNECTING POWER/CONTROLS TO THE
FIXTURES WOULD NOT BE REQUIRED. NOR WOULD HAVING TO PROVIDE
TEMPORARY WORK LIGHTS.
2.2.1. SUPPORT ALL CEILING MOUNTED LUMINAIRES THAT MATCH THE SIZE OF THE
LAYOUT OF THE CEILING GRID FROM THE BUILDING STRUCTURAL FRAMING
MEMBERS OR THE CEILING FRAMING SYSTEM UTILIZING CONDUIT STEMS,
FIXTURE STUDS, SUPPORT CLIPS, STEEL RODS OR BAR HANGERS. IF THE
CEILING FRAMING SYSTEM IS USED FOR SUPPORT, INSTALL A MINIMUM OF TWO
CEILING SUPPORT SYSTEM RODS OR WIRES FOR EACH LUMINAIRE (ON
DIAGONALLY OPPOSITE CORNERS OF THE FIXTURE). LOCATE NOT MORE THAN
6 INCHES FROM FIXTURE CORNERS.
2.3. NOTE THERE ARE SOME SURFACE MOUNTED LIGHT FIXTURES INSTALLED DIRECTLY
TO THE BOTTOM OF THE ACOUSTICAL CEILING TILES, WHICH THESE FIXTURES WILL
NEED TO FOLLOW 2.1 ABOVE.
3. NOTE THAT NOT ALL LOW-VOLTAGE WIRING IS PROPERLY SUPPORTED TO THE BUILDING
STRUCTURAL FRAMING, MOST OF THE WIRING IS LAYING ON TOP OF THE ACOUSTICAL
CEILING TILES/GRID. PRIOR TO REMOVAL OF THE EXISTING CEILINGS IN GODWIN ALL OF
THE LOW-VOLTAGE WIRING SHALL BE SUPPORTED FROM THE BUILDING STRUCTURAL
FRAMING. COORDINATE WITH OWNER FOR ANY WIRING
4. THE REMOVAL OF THE CEILINGS IN GODWIN HALL WILL REQUIRE REMOVAL OF ALL
EQUIPMENT/DEVICES/ITEMS ON THE ACOUSTICAL CEILING TILES OR PASSING THROUGH
THE CEILING TILES. SUCH AS, BUT NOT LIMITED TO, LIGHT FIXTURES, CEILING MOUNTED
SENSORS, HVAC DIFFUSERS, HVAC EQUIPMENT, LOW-VOLTAGE DEVICES (CAMERAS,
WIRELESS ACCESS POINTS, PROJECTORS, ETC.), ETC. NOTE THAT THE CONTRACTOR
SHALL INCLUDE HANDLING AND OR REWORKING THIS EQUIPMENT/DEVICES/ITEMS TO
REINSTALL BACK INTO THE NEW CEILINGS.
E-GH1
G O
D W
IN
H
A
LL
G
R O
U N
D F
LO
O
R P
LA
N
E
LE
C
T R
IC
A
L D
E M
O
LI
T
IO
N
JTO JTO
WAM LPA
GODWIN HALL - FIRST FLOOR PLAN - ELECTRICAL DEMOLITION
STOR
VESTIBULE
STAIR
STORAGE
ELEV
CHEMISTRY
PHYSICS
A / V WORK
OFFICE
STOR
MULTIPURPOSEMULTIPURPOSE
PHYSICS PREP
TALENT SEARCH
LECTURE HALL
OFFICE
OFFICE
ELEV. LOBBY
CLOSET
NURSING
WOMEN
MEN
OFFICE
ENGLISH LAB
CLASSROOM CLASSROOM
BIOLOGY LAB
MATH LAB
STAIR
LEARNING /
COMPUTER LAB
BIOLOGY LAB
OFFICE
MULTIPURPOSE
MULTIPURPOSE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CORRIDOR CORRIDOR
1 1 1 1 1 1 1 1
JAN
BIOLOGY PREP
3 3
EXISTING PANEL-G
EXISTING PANEL-B EXISTING PANEL-H
EXISTING PANEL-L
5 5 5
OFFICE
OFFICE
OFFICE
OFFICE
5 5
ER
ER
ER ER ER ER ER ER ER ER
ER
ER ER
ER
ER ER ER ER
ER
ER ER ER ER ER ER ER ER ER ER ER ER
ER
ER
ER
ER
ER ER
ER
ER
ER
ER
ERER
ER
44 4
ER ER
ER
ER
ER
ER ER
ERER
ER ER
ER
ER
ER
ER
ER ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ERER
ER
ER
ER
ER
ER
ER
ER
ERER
ER
ER
ER
ER
ER
ER
ER
ERER
ER
ER
ER
ER
ER
ER
ER ER
ER
ER
ER
ER
ER
ER
ERER
ER
ER
ER
ER
ER
ER
ER
EM
EMEMEM
EM
EM
ER
ER
ER ER
ER
ER
ER ER
ER
ER
ER ER
ER ER
ER
ER
ER
ER
ER
ER
ERER
ER
ER
ER
ER
ER
EM
ER
ER
EM
ER
EM
ER
DESIGNED DRAWN
APPROVEDCHECKED
COMM. NO. DATE
SHEET
18147 03/01/2024
M O
U N
T A
IN
E
M P
IR
E
C O
M M
U N
IT
Y
C O
LL
E
G E
G
O D
W
IN
H A
LL
S
P R
IN
K
LE
R
, E X
IT
A
N D
E M
E R
G E
N C
Y L
IG
H
T S
A N
D G
E N
E R
A T
O R
S B
IG
S
T O
N E
G A
P , V
IR
G
O
JE
C
T C
O D
E
0-
9-
REVISION DATE
SUBMITTAL DATE
8 8 16 324
1/8" = 1'-0"
( IN FEET )
GRAPHIC SCALE
C O M M O
N W
EA
LTH OF
V
IR
G I N I A
P R O
F E
SS IONAL E
N G
IN
E R E
03/01/24
E-GH2
G O
D W
IN
H
A
LL
F
IR
S
T F
LO
O
R P
LA
N
E
LE
C
T R
IC
A
L D
E M
O
LI
T
IO
N
JTO JTO
WAM LPA
PLAN NOTES:
1. DISCONNECT FIXTURE FROM EXISTING CIRCUIT AND SWITCH CONTROL. FIXTURE WILL BE
CONNECTED TO NEW LIFE SAFETY CIRCUIT UNDER NEW WORK. MAINTAIN CONTINUITY OF
EXISTING CIRCUIT TO OTHER FIXTURES CONNECTED TO CIRCUIT. THE EXISTING BATTERY
BALLAST SHALL REMAIN AS INSTALLED.
2. DISCONNECT EXISTING EXIT SIGN FROM EXISTING CIRCUIT. FIXTURE WILL BE CONNECTED TO
NEW LIFE SAFETY CIRCUIT UNDER NEW WORK. MAINTAIN CONTINUITY OF EXISTING CIRCUIT
TO OTHER FIXTURES CONNECTED TO CIRCUIT.
3. DISCONNECT THIS FIXTURE FROM EXISTING SWITCH CONTROL. MAINTAIN SWITCH CONTROL
TO OTHER FIXTURES CONNECTED TO SWITCH. FIXTURE WILL BE CONNECTED TO LIFE SAFETY
CIRCUIT UNDER NEW WORK.
4. REMOVE WALL MOUNTED BATTERY PACK UNIT. MAINTAIN CIRCUIT CONTINUITY AFTER
FIXTURE IS REMOVED.
5. NO EXISTING EGRESS LIGHTING IN THIS ROOM.
6. DISCONNECT AND REMOVE REMOTE EMERGENCY BATTERY ASSEMBLY. REMOVE
CONNECTING CABLE FROM REMOTE BALLAST TO FIXTURE WHERE IT IS ACCESSIBLE. FIXTURE
WILL BE CONNECTED TO A NEW LIFE SAFETY CIRCUIT UNDER NEW WORK.
FIRE RATED WALL LEGEND
1-HOUR FIRE SEPARATION
GENERAL NOTES:
1. WHEN EXISTING CEILINGS IN GODWIN ARE REMOVED, THE CONTRACTOR SHALL PROVIDE
COVERPLATES ON ALL EXISTING JUNCTION BOXES ABOVE THE ACCESSIBLE CEILING
SPACES AND ANY WALL MOUNTED BOXES IN THE AREA OF RENOVATIONS WHERE
EXISTING COVERPLATES ARE MISSING. THE CONTRACTOR SHALL ALSO PROVIDE
ADDITIONAL SUPPORTS FOR EXISTING CONDUIT AND JUNCTION BOXES IN THE AREA OF
RENOVATIONS THAT CURRENTLY DO NOT MEET CODE REQUIREMENTS.
2. NOTE THAT THE EXISTING LIGHT FIXTURES IN THE CEILINGS OF GODWIN ARE NOT
PROPERLY SUPPORTED FROM THE BUILDING STRUCTURAL FRAMING ABOVE THE
ACOUSTICAL CEILINGS. PRIOR TO REMOVAL OF EXISTING CEILINGS IN GODWIN THE
CONTRACTOR HAS THE OPTION OF:
2.1. EITHER DISCONNECTING POWER/CONTROLS TO ALL EXISTING LIGHT FIXTURES,
TEMPORARY REMOVING THEM FROM THE CEILINGS AND STORING THE LIGHT
FIXTURES TILL THE NEW CEILINGS ARE IN PLACE AND THEN REINSTALLING AND
RECONNECTING POWER. NOTE THAT WHEN RE-INSTALLING ALL THE EXISTING
LIGHT FIXTURES THEY WILL BE REQUIRED TO BE RE-INSTALLED WITH THE CODE
REQUIRED SUPPORTS TO THE BUILDING STRUCTURAL FRAMING. ALSO NOTE THAT
REMOVING THE EXISTING LIGHT FIXTURES WOULD REQUIRE PROVIDING
TEMPORARY WORK LIGHTING IN THE SPACES.
2.2. OR INSTALLING THE SUPPORTS TO ALL EXISTING LIGHT FIXTURES AS NOTED BELOW.
THE SUPPORTS WILL ALLOW THE LIGHT FIXTURES TO HANG FROM THE BUILDING
STRUCTURAL FRAMING SO THAT DISCONNECTING POWER/CONTROLS TO THE
FIXTURES WOULD NOT BE REQUIRED. NOR WOULD HAVING TO PROVIDE
TEMPORARY WORK LIGHTS.
2.2.1. SUPPORT ALL CEILING MOUNTED LUMINAIRES THAT MATCH THE SIZE OF THE
LAYOUT OF THE CEILING GRID FROM THE BUILDING STRUCTURAL FRAMING
MEMBERS OR THE CEILING FRAMING SYSTEM UTILIZING CONDUIT STEMS,
FIXTURE STUDS, SUPPORT CLIPS, STEEL RODS OR BAR HANGERS. IF THE
CEILING FRAMING SYSTEM IS USED FOR SUPPORT, INSTALL A MINIMUM OF TWO
CEILING SUPPORT SYSTEM RODS OR WIRES FOR EACH LUMINAIRE (ON
DIAGONALLY OPPOSITE CORNERS OF THE FIXTURE). LOCATE NOT MORE THAN
6 INCHES FROM FIXTURE CORNERS.
2.3. NOTE THERE ARE SOME SURFACE MOUNTED LIGHT FIXTURES INSTALLED DIRECTLY
TO THE BOTTOM OF THE ACOUSTICAL CEILING TILES, WHICH THESE FIXTURES WILL
NEED TO FOLLOW 2.1 ABOVE.
3. NOTE THAT NOT ALL LOW-VOLTAGE WIRING IS PROPERLY SUPPORTED TO THE BUILDING
STRUCTURAL FRAMING, MOST OF THE WIRING IS LAYING ON TOP OF THE ACOUSTICAL
CEILING TILES/GRID. PRIOR TO REMOVAL OF THE EXISTING CEILINGS IN GODWIN ALL OF
THE LOW-VOLTAGE WIRING SHALL BE SUPPORTED FROM THE BUILDING STRUCTURAL
FRAMING. COORDINATE WITH OWNER FOR ANY WIRING
4. THE REMOVAL OF THE CEILINGS IN GODWIN HALL WILL REQUIRE REMOVAL OF ALL
EQUIPMENT/DEVICES/ITEMS ON THE ACOUSTICAL CEILING TILES OR PASSING THROUGH
THE CEILING TILES. SUCH AS, BUT NOT LIMITED TO, LIGHT FIXTURES, CEILING MOUNTED
SENSORS, HVAC DIFFUSERS, HVAC EQUIPMENT, LOW-VOLTAGE DEVICES (CAMERAS,
WIRELESS ACCESS POINTS, PROJECTORS, ETC.), ETC. NOTE THAT THE CONTRACTOR
SHALL INCLUDE HANDLING AND OR REWORKING THIS EQUIPMENT/DEVICES/ITEMS TO
REINSTALL BACK INTO THE NEW CEILINGS.
GODWIN HALL - GROUND FLOOR PLAN - ELECTRICAL NEW WORK
WORKRM
STOR
MECHANICAL
MAIL ROOM
ELEC
PHYSICAL
PLANT
OFFICE
ELEV
STAIR NO. 1
WORKROOM
MAIL ROOM
STOR.
COMPUTER ROOM
STOR
CORRIDOR
DATA
HARDWARE ROOM
120A
ODU CLASSROOM
COPY
STOR.
CORRIDOR
DATA / COMM
CLOSET
OFFICE-4
OFFICE-10
OFFICE-3
PHYSICAL PLANT
SHIPPING & RECEIVING
COUN.
ENTRY LOBBY
FILES ROOM
OFFICE-5
OFFICE-4
139 OFFICE-2
MULTIPURPOSE RM
CLOSET
CLASSROOM
STAIR NO. 2
MEN WOMEN
BUSINESS OFFICE
WORK STATION
COUN.
OFFICE
OFFICE
STOR
TEL EQUIP
OFFICE
FINANCIAL
AID
OFFICE
COUN.
MEN
EQUIP
WOMEN
CORRIDOR
CLOSET
136A
OFFICE-1
SEC/ RECEPTION
OFFICE
OFFICE
OFFICE
HSKG SUPPLIES
CORRIDOR
ODU
CLASSROOM
VENDING ROOM
MULTI-PURPOSE CLASSROOM
OFFICE-8
OFFICE-7
OFFICE-9
WAITING
OFFICE-6
OFFICE-5
DIV. CHAIR
OFFICE-3
OFFICE-1
OFFICE-2
TOOL/ SHOP RM
WAITING/
RECEPT.
ARTS &
SCIENCE LAB
OFFICE-6
ADMISSIONS
CLASSROOM
ODU OFFICE
CORRIDOR
4 4 4
4444444
4 4
SIDEWALK
SIDEWALK
FORMER CHILLER YARD
NEW XFMR T-LLG
NEW PANEL-LHG
NEW PANEL-LLG
22222
2 2
OFFICE
STOR
2 2
2 2
EXISTING FIRE ALARM
ANNUNCIATOR PANEL
ER
EXISTING PANEL-E
EXISTING PANEL-DEXISTING PANEL-A
EXISTING PANEL-I
EXISTING PANEL-F
ER
ER
EXISTING PANEL-X
EXISTING DISTRIBUTION
PANEL NO. 1
EXISTING
DISTRIBUTION
PANEL NO. 2
EXISTING XFMR
ER
ER
ERER
EXISTING FACP
ER 5
ER
ER
ER
ERER
ER
ER
ER
ER
ER
ER
ER
ER
ER ER ER ER
ER
ER
EM
ER ER
ER
ER
ER ER
ER ER
ER ER
ER
ER
ERERER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER ER
ER
ER
ER ER ER
ERERER
ER ER ER
ER ER
ER
ER ER ER ER
ERER
ER
ERER
ER
ER ER ER
ERERER
ER ER ER
ER
ER
ER
ER ER
ER
ER
ER
ER ER ER
ER
ER
ER
ERER
ER
ER
ER
ER
ERERERERER
ER
ERER
ER
ER
ERER
ER
ER
ER
ER
ER
ER
ERERERERERERERERERERER
ER
ERERERERERERERERER
ER ER
ER ER
ER
ER
ER ER
ER ER
ER ERER
ERER
ER
ERERERER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER ER
ERERER
ER
ER
ER
ER ER
ER
ER
ER
ER
ER
ER
NEW ATS-LG
NEW ATS-MDPG
CAP END OF CONDUITS
FOR FUTURE EXTENSION
OF NORMAL AND
EMERGENCY FEEDERS TO
HOLTON HALL
EXISTING POWER COMPANY
TRANSFORMER SERVING
GODWIN AND HOLTON HALLS
FEEDER TO GENERATOR
DISTRIBUTION PANEL
NEW QUAZITE
PULL BOX FOR
CONNECTION TO
EXISTING SERVICE
CONDUCTORS
GENERATOR 'GH' REMOTE
ANNUNCIATOR PANEL
750 KW GENERATOR WITH
SUBBASE DIESEL TANK
6" HIGH CONCRETE
PAD 6" WIDER THAN
GENERATOR ALL
AROUND.
GENERATOR EXHAUST
GEN-GH
GENERATOR 'GH' REMOTE STOP
STATION - COORDINATE EXACT
LOCATION WITH MANUFACTURER.
6" HIGH CONCRETE PAD
6" WIDER THAN
MTS-GDP ALL AROUND.
MTS-GDP
GENERATOR
SWITCHBOARD (GDP) -
SEE ONE-LINE DIAGRAM
ON SHEET E-GH6
EXISTING GAS PROPANE TANK
TO REMAIN AS INSTALLED.
CONTRACTOR TO COORDINATE FINAL LOCATION OF NEW
GENERATOR AND MANUAL TRANSFER SWITCH WITH EXISTING
SITE CONDITIONS/UTILITIES AND WITH GET FINALLY APPROVAL
OF LOCATIONS FROM MECC BEFORE PROCEEDING.
INSTALL GENERATOR AT
A MINIMUM OF 15 FEET
FROM THE EXHAUST OF
THE GENERATOR TO THE
SIDE OF THE BUILDING.
DESIGNED DRAWN
APPROVEDCHECKED
COMM. NO. DATE
SHEET
18147 03/01/2024
M O
U N
T A
IN
E
M P
IR
E
C O
M M
U N
IT
Y
C O
LL
E
G E
G
O D
W
IN
H A
LL
S
P R
IN
K
LE
R
, E X
IT
A
N D
E M
E R
G E
N C
Y L
IG
H
T S
A N
D G
E N
E R
A T
O R
S B
IG
S
T O
N E
G A
P , V
IR
G
O
JE
C
T C
O D
E
0-
9-
REVISION DATE
SUBMITTAL DATE
8 8 16 324
1/8" = 1'-0"
( IN FEET )
GRAPHIC SCALE
C O M M O
N W
EA
LTH OF
V
IR
G I N I A
P R O
F E
SS IONAL E
N G
IN
E R E
03/01/24
E-GH3
G O
D W
IN
H
A
LL
G
R O
U N
D F
LO
O
R P
LA
N
E
LE
C
T R
IC
A
L N
E W
W O
R K
JTO JTO
WAM LPA
PLAN NOTES:
1. ROUTE INDICATED CIRCUIT THROUGH THE EXISTING EXTERIOR LIGHTING CONTROL
DEVICE.
2. REFER TO DEMOLITION PLANS, THERE WAS NO EXISTING EGRESS LIGHTING IN THIS
EXISTING ROOM, THEREFORE NO NEW EGRESS LIGHTING HAS BEEN PROVIDED.
3. CONNECT THIS EXISTING LIGHT FIXTURE TO LIFE SAFETY CIRCUIT LHG-5.
4. CONNECT THIS EXISTING LIGHT FIXTURE TO LIFE SAFETY CIRCUIT LHG-1.
5. CONNECT THIS EXISTING EXIT SIGN TO LIFE SAFETY CIRCUIT LHG-3.
6. PROVIDE A NEW CEILING MOUNTED OCCUPANCY SENSOR TO TURN THE EGRESS LIGHTS
ON WHEN THE ROOM IS OCCUPIED AND OFF 15 MINUTES AFTER THE ROOM IS VACANT.
7. DISCONNECT THE EXISTING CIRCUIT FROM THE FIRE ALARM CONTROL PANEL AND
RECONNECT TO NEW LIFE SAFETY CIRCUIT LLG-1.
8. WHERE THE EXISTING FIRE ALARM ANNUNCIATOR IS POWERED BY A 120 VOLT CIRCUIT,
DISCONNECT THE EXISTING CIRCUIT AND RECONNECT THE ANNUNCIATOR TO THE SAME
LIFE SAFETY CIRCUIT THAT IS POWERING THE FIRE ALARM CONTROL PANEL, WHICH IS
LLG-1.
9. THERE IS NO EXISTING EGRESS LIGHTING IN THIS ROOM. NEW EGRESS LIGHTING SHALL
BE PROVIDED AS INDICATED.
10. PROVIDE ONE (1) NEW 36" X 36" QUAZITE PULL BOX FOR CONNECTION OF THE NEW
FEEDER CONDUCTORS ORIGINATING FROM ATS-MDPG TO THE EXISTING SERVICE
ENTRANCE CONDUCTORS FEEDING DISTRIBUTION PANEL NO. 1 IN GODWIN HALL.
COORDINATE THE EXACT LOCATION OF THIS PULL BOX WITH THE EXACT LOCATIONS OF
THE EXISTING SERVICE ENTRANCE FEEDERS IN THE FIELD. REFER TO THE ONE-LINE
DIAGRAM ON SHEET E-GH6 FOR MORE INFORMATION.
GENERAL NOTES:
1. ALL EGRESS LIGHTING AND EXIT SIGN CIRCUITS ORIGINATING FROM PANEL 'LHG' SHALL BE UNSWITCHED UNLESS OTHERWISE NOTED.
2. ALL LIGHT FIXTURES ARE EXISTING.
3. ALL LIGHTING CIRCUITS SHALL BE 2-#12 AND 1-#12 GROUND IN 3/4" CONDUIT UNLESS OTHERWISE NOTED.
4. IN STAIRWELLS, PROVIDE ONE (1) UL1008 LISTED GENERATOR TRANSFER DEVICE FOR EMERGENCY OPERATION OF THE STAIRWELL LIGHTING FIXTURES. CONNECT THE NORMAL
SIDE OF THE GTD TO THE EXISTING NORMAL POWER CIRCUIT PREVIOUSLY SERVING THE STAIRWELL LIGHTING FIXTURES. CONNECT THE EMERGENCY POWER SIDE OF THE GTD
TO THE NEW LIFE SAFETY CIRCUIT INDICATED. THE EXISTING STAIRWELL LIGHTING FIXTURE CONTROLS SHALL REMAIN OPERATIONAL AFTER INSTALLATION OF THE GTD. UPON
LOSS OF NORMAL POWER, THE STAIRWELL LIGHTING FIXTURES SHALL TURN 'ON' TO 100% LIGHT OUTPUT.