Attachment_1_(AC_Equip_Info).docx
DOCX document 20 KB Posted
- Attached to
- A/C Preventive Maintenance Services
- Solicitation number
- M00318-19-Q-0008
- Issued by
-
United States Marine Corps
About this file
Attachment 1
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment_2_(WD).docx | DOCX document | |
| M00318-19-Q-0008_AC_Prev_Maint_Svcs_Combined_Synopsis_Solicitation.docx | DOCX document | |
| AC_Maint_PWS.DOCX | DOCX document | |
| M00318-19-Q-0008_AC_Prev_Maint_Svcs_Combined_Synopsis_Solicitation.docx | DOCX document | |
| AC_Maint_PWS.DOCX | DOCX document | |
| Attachment_1_(AC_Equip_Info).docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PAR (Songbird 5 Ton AC)
| MODEL NUMBER: | A/E32E-45A/1559AS400-1 | ||
| CAGE: | 0V5R4 | ||
| CONTRACT: | B25-45182516 | ||
| DATE OF MFG: | 07/2017 | ||
| REFRIGERANT: | R-134A | ||
| CHARGE: | 9LB | ||
| UNIT SERIAL DESIGNATION: | SN0W-2516-01 |
UNIT TEST SHEET
| PSIG GAGE SET#: | 737 | ||
| AMBIENT TEMP: | 79 | ||
| START-UP (FAN MODE ONLY): | 4.0 | ||
| VOLTAGE: | 186 |
COOL MODE
| VOLTAGE: | 206/205/205 | |
| AMPERAGE: | 21.4/16.7/16.3 | |
| SIGHT GLASS: | ACCEPTED |
HEAT MODE:
| VOLTAGE: | 205/204/204 |
| AMPERAGE: | 24.7/20.0/19.7 |
| HEATER CUT OUT: | ACCEPT |
INDOOR COIL TEMP:
| INLET: | 79 |
| OUTLET: | 59 |
| LEAKAGE TEST: | ACCEPT |
| DEFORST TEST: | ACCEPT |
PRESSURE CUTOUT:
| HIGH PRESS | 410 |
| COOL MODE: | 55/48 |
| HEAT MODE: | 215/57 |
TACAN (36K BTU Mitsubishi Mini-Split AC)
MITSUBISHI ELECTRIC
MODEL NUMBER: MSY-D36NA-8
SERIAL NUMBER: 7 001329 T
UNIT SUPPLY (EVAP UNIT AS WELL):
| VOLTS: | 208/230 | |
| MAX: | 253 | |
| MIN: | 187 | |
| PHASE: | 1 | |
| HZ: | 60 |
APPROVED FOR HACR BREAKERS
OR TIME DELAY FUSES (EVAP UNIT AS WELL)
| MAX FUSE: | 25A | |
| MIN. CURCUIT AMPACITY: | 21 |
FAN MOTOR:
| F.L.A. | 0.93 | |
| W/(OUTPUT): | 77 |
COMPRESSOR:
| R.L.A. | 16.0 |
| L.R.A | 20.0 |
REFRIGERANT: R410A
FACTORY CHARGE: 4LB
IF THE LIQUID EXEEDS 25FT PLYS 1.08OZ
PER ADDITIONAL 5FT LIQUID LINE
DESIGN PRESSURE PSIG
| HI SIDE: | 601 |
| LO SIDE: | 320 |
SUITABLE FOR OUTDOOR INSTALLATION
WEIGHT: 125LB
EVAPORATING UNIT
DISCONNECT SWITCH: 15A
MIN CKT AMPS: 1.0
FAN MOTOR:
| FLA: | 0.76 | |
| W/(OUTPUT) | 56 |
| REFRIGERANT: | R410A | |
| DESIGN PRESSURE: | 320PSIG |
THIS UNIT IS INTENDED ONLY FOR FREE-AIR DISCHARGE
WEIGHT: 40LB
SERIAL NUMBER: 7001372 T
COMPATIBILITY CHART
COOL (BTU/H): 32,600
Heat (BTU/H): N/A
SEER: 15.1
HSPF: N/A
ENERGY STAR: NO
SOUND LEVEL AS LOW AS DB(A): 32
i-See Sensor™ OPTION: NO
CONTROL OPTIONS AVAILABLE: ALL
FILTER TYPE: A, C
FAN SPEED: 4Spd
TIMER: 24H
ATCMD AC UNIT SPECIFICATION/PART INFORMATION
ALL INFORMATION FOUND USING RESPECTIVE LABELS ON AC UNITS
DASR (Bard 5 Ton AC)
| Model: | W60L1-C09EPXXXV | |||
| SERIAL NUMBER: | 326L092650706-02 | |||
| APPROVED HEATER PACKAGE: | EHWA05A-C09L | |||
| VAC: | 460 | |||
| HZ: | 60 | |||
| PHASE: | 3 | |||
| MIN CIRCUIT AMP: | 18 | |||
| CIRC MAX FUSE OR CIRC BREAKER: | 20 | |||
| BRANCH CIRC SELECT CURRENT: | 7.8 |
OPERATING VOLTAGE RANGE
| MIN: | 414VAC |
| MAX: | 506VAC |
COMPRESSOR:
| VAC: | 460 |
| HZ: | 60 |
| PHASE: | 3 |
| LRA: | 52 |
| RLA: | 7.6 |
OUTDOOR MOTOR:
| VAC: | 460 |
| HZ: | 1 |
| HP: | 1/3 |
| FLA: | 1.3 |
INDOOR MOTOR:
| VAC: | 460 |
| HZ: | 60 |
| PH: | 1 |
| HP: | ½ |
| FLA: | 1.9 |
WERV-C5A:
| VAC: | 460 |
| HZ: | 60 |
| PH: | 1 |
| FLA: | 1.2 |
HEATER PACKAGE:
| HP: | KW |
| FLA: | FLA |
EHWA05A-C09L:
| VAC: | 480 |
| HZ: | 60 |
| PHASE: | 3 |
| HP: | 9 |
| FLA: | 10.8 |
EHWA05A-C15L
| VAC: | 480 |
| HZ: | 60 |
| PHASE: | 3 |
| HP: | 15 |
| FLA: | 18.0 |
| REFRIGERANT: | R410A |
| AMOUNT: | 150 OZ |
DESIGN PRESSURE PSIG:
| HI: | 449 |
| LOW: | 238 |
DASR(Bard 5 Ton AC)
| Model: | WA602-C09EPXXXV | |||
| SERIAL NUMBER: | 155K072390358-02 | |||
| APPROVED HEATER PACKAGE: | EHWA05A-C09L | |||
| VAC: | 460 | |||
| HZ: | 60 | |||
| PHASE: | 3 | |||
| MIN CIRCUIT AMP: | 17 | |||
| CIRC MAX FUSE OR CIRC BREAKER: | 20 | |||
| BRANCH CIRC SELECT CURRENT: | 9 |
OPERATING VOLTAGE RANGE
| MIN: | 414VAC |
| MAX: | 506VAC |
COMPRESSOR:
| VAC: | 460 |
| HZ: | 60 |
| PHASE: | 3 |
| LRA: | 62 |
| RLA: | 6.8 |
OUTDOOR MOTOR:
| VAC: | 460 |
| HZ: | 1 |
| HP: | 1/3 |
| FLA: | 1.3 |
INDOOR MOTOR:
| VAC: | 460 |
| HZ: | 60 |
| PH: | 1 |
| HP: | ½ |
| FLA: | 1.9 |
WERV-C5A:
| VAC: | 460 |
| HZ: | 60 |
| PH: | 1 |
| FLA: | 1.2 |
HEATER PACKAGE:
| HP: | KW |
| FLA: | FLA |
EHWA05A-C09L:
| VAC: | 480 |
| HZ: | 60 |
| PHASE: | 3 |
| HP: | 9 |
| FLA: | 10.8 |
EHWA05A-C15L
| VAC: | 480 |
| HZ: | 60 |
| PHASE: | 3 |
| HP: | 15 |
| FLA: | 18.0 |
| REFRIGERANT: | R22 |
| AMOUNT: | 140 OZ |
DESIGN PRESSURE PSIG:
| HI: | 306 |
| LOW: | 150 |
File details come from the government source that posted it.