Questions_6-3-15.pdf
PDF 94 KB Posted
- Attached to
- Leasing of Portable Air Cooled Water Chiller
- Solicitation number
- M00146-15-T-S009
- Issued by
-
United States Marine Corps
About this file
Response to Questions 6-3-15
View the file
Other files
| File | Type | Posted |
|---|---|---|
| M00146-15-T-S009-0001.pdf | ||
| Attachment_1.pdf | ||
| M00146-15-T-S009.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFQ M00146-15-T-S009 Portable Air Cooled Water Chiller
QUESTIONS
1. QUESTION: The flow rate of 445 gpm is suited more for a 200 ton chiller unit. Are you looking for a 200 ton unit with this rate, or will a 250 ton Chiller with higher gpm?
ANSWER: The flow rate is appropriate for a 250 ton chiller. The required chiller capacity is 250 tons.
2. QUESTION: Could you tell us the average water temperature leaving and water temp entering?
ANSWER: The leaving chilled water temperature is specified in paragraph 3.0 in the Statement Of Work.
Given the specified flow rate of 445 gpm and the specified tonnage the return water temperature is approximately 57.5 degrees F.
3. QUESTION: What size fused disconnects are being furnished?
ANSWER: The fused disconnect switch specified in Paragraph 3.1 b is an error. The intent is to furnish a chiller with integral fusing/overload protection. The Government is furnishing a 800A enclosed circuit breaker as a disconnecting means.
File details come from the government source that posted it. Updated .