M-004 - MECHANICAL - AHU SCHEDULES.pdf

PDF 325 KB Posted

Attached to
Y1DA--Upgrade AHU's and Water-Cooled Equipment
Solicitation number
36C24221B0040
Issued by

About this file

This document includes an air handling unit (AHU) schedule and specifications for upgrading AHUs and water-cooled equipment at the VA New Jersey Healthcare System East Orange Campus. Key details include:

  • Replacing deficient HVAC equipment in Buildings 1 and 7 including new AHUs, water-cooled equipment, and all related connections.

  • Scope of work covers general construction, alterations, asbestos abatement, HVAC, plumbing and electrical work to remove existing finishes and construct new.

  • Project completion is 328 calendar days from notice to proceed.

  • Solicitation number 36C24221B0040 will be posted on SAM.gov on or around June 4, 2021 and include the response address, date and time.

  • The estimated cost is between $2-5 million.

  • The opportunity is a Service-Disabled Veteran Owned Small Business set-aside for the Department of Veterans Affairs Veterans Health Administration VISN 2.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROVIDE SUPPLY AIR SMOKE DAMPER, OUTSIDE

AIR INTAKE SMOKE DAMPER, RETURN AIR

OPENING DAMPER AS SMOKE DAMPER.

EACH DAMPER SHALL COMPLY

WITH UL 555S, CLASS 1.

GENERAL NOTES:

1.

2. FILTERS SHALL BE PROVIDED BY THE UNIT

MANUFACTURER. ONE SET OF NEW FILTERS

SHALL BE INSTALLED IN EACH FILTER BANK

WHEN BUILDING IS TURNED OVER TO OWNER

AND ONE COMPLETE SET SHALL BE PROVIDED

FOR OWNER'S STOCK.

3. REFER TO UNIT PLANS FOR ARRANGEMENT OF

UNITS, ACCESS DOORS, ETC.

4. REFER TO SPECIFICATIONS FOR SPECIFIC

REQUIREMENTS FOR ACCESSORIES AND DETAILS

OF CONSTRUCTION FOR THE AIR HANDLING

UNITS.

5. ALL UNITS SHALL BE

PROVIDED WITH REMOTE MOUNTED ELECTRICAL

PANELS, LIGHTING FOR EACH SECTION AND UV

LIGHTING FOR COOLING COIL

SECTION.

6. ROOFTOP UNITS SHALL HAVE STRUCTURAL,

SEISMIC ROOF SUPPORTS.

MANUFACTURER

REMARKS:

SERVES

GPM (CHILLED WATER ONLY)

WHEEL DIAMETER (IN)

FILTER PRESSURE DROP (INWG) (CLEAN)

FILTER AREA (SQUARE FEET)

FILTER MINIMUM EFFICIENCY

FILTER TYPE

REMARKS:

TYPE UNIT

LOCATION

SYSTEM NO.

VFD

REMARKS:

FAN TYPE

REMARKS:

REMARKS:

VFD

REMARKS:

FAN TYPE

SQ. FT. FACE AREA MIN.

PREFILTER MIN. EFF.

FINAL FILTER MIN. EFF.

FINAL FILTER TYPE

FINAL FILTER (SF)

ACCESS SECTION W/AD

SUPPORT BASE

VIBRATION ISOLATORS (FANS)

MOTOR OPER. SMOKE DAMPERS

DISCHARGE AIR PLENUM W/AD

RETURN AIR PLENUM W/AD

MIXING SECTION W/AD

SENSIBLE LOAD (MBH)

E.A.T. D.B./W.B. (°F)

L.A.T. D.B./W.B. (°F)

FINS PER INCH MIN.

SQ. FT. FACE AREA MAX.

FACE VELOCITY MAX.

AIR PRESSURE DROP INWG

INPUT HEATING CAPACITY

L.A.T. D.B. °F

E.A.T. D.B. °F

TYPE COIL

TOTAL CFM

ROWS MIN.

TYPE COIL

WHEEL DIAMETER MIN. (in.)

RPM APPROX.

TYPE DRIVE

HP MIN/VOLT/PH

ARRANGEMENT

RPM APPROX.

HP MIN/VOLT/PH

TYPE DRIVE

EXTERNAL STATIC PRESSURE

TOTAL CFM (CFM PER FAN)

TOTAL LOAD (MBH)

ARRANGEMENT

TOTAL CFM

TOTAL CFM (CFM PER FAN)

EXTERNAL STATIC PRESSURE (IN W.G.)

TOTAL AIRFLOW (SUPPLY) CFM

ECONOMIZER

OUTSIDE AIR CFM (MINIMUM/ECONOMIZER)

REMARKS:

RATED CAPACITY (lbs/hr)

AIRFLOW, CFM

MODEL NUMBER

WATER PRESSURE DROP (FTWG) CHILLED WAT.

ELECTRICAL CHARACTERISTICS (MOP/MCA)

AHU-7

BLDG 1 / PENTHOUSE

INDOOR

C O

O L

IN

G C

O

IL

A C

C E

S S

S

U P

P L Y

F A

N F

IN

A

L F

IL

T

E R

P R

E -H

E A

T

IN

G C

O

IL

P R

E F

IL

T

E R

R E

T U

R N

F A

N

CUSTOM AIR HANDLING UNIT SCHEDULE

H U

M

ID

IF

IE

R

FLUID FLOW RATE (GPM)

MAX WATER P.D. (FT.)

ABSORBTION DISTANCE (in)

REMARKS:

SQ. FT. FACE AREA MIN.

INPUT HEATING CAPACITY

L.A.T. D.B. °F

E.A.T. D.B. °F

TYPE COIL

TOTAL CFM

R E

-H E

A T

IN

G

C O

IL

FLUID FLOW RATE (GPM)

MAX WATER P.D. (FT.)

7. PROVIDE NEMA 3R ENCLOSURES ON VFDs.

LOCATED OUTDOORS.

8. PROVIDE UV LIGHTS DOWNSTREAM OF COOLING COIL.

AHU-11

BLDG 1 / LEVEL C

AHU-12

BLDG 1 / LEVEL C

AHU-13

BLDG 1 / LEVEL C

MORGUE AHU-10A

BLDG 1 / LEVEL C

INDOOR INDOOR INDOOR INDOOR

AHU-A-LEVEL-LAB

BLDG 1 / LEVEL A

INDOOR

AHU-CANTEEN

BLDG 1 / LEVEL 3

INDOOR

9. PROVIDE STAINLESS STEEL COIL CASINGS FOR

COOLING COILS.

PROVIDE SUPPORT BENEATH UNIT WITH EITHER 6"

ALUMINUM I BEAM OR CONCRETE CURB, SEE UNIT

DRAWINGS FOR DETAILS, TO FACILITATE

INSTALLATION

OF DRAIN AND TRAP FROM COIL SECTIONS.

10.

5,000

REMARKS:

UV LIGHTS

TRANE TRANE TRANE TRANE TRANE

18,000 7,000 13,000 13,000 2,200 18,000

15,500 (7,750)

1.0

22.25

1,200

DIRECT

5HP/460/3Ø (EACH)

PLENUM

PER FAN

1X2

2,500

CSAA035

13TH FLOOR

SUPPLY:51/90 RETURN:22/35

18,000 (9,000)

2.0

22.25

1,800

DIRECT

15HP/460/3Ø (EACH)

PLENUM

PER FAN

1X2

PLEATED MEDIA

MERV 8

18,000

880 MBH

45.00

90.00

HOT WATER

15.00

430.5

18,000

12" MIN

18,000

80/67

55/54.5

0.646

19.18

18,000

554.28

HOT WATER

55.5

6.08

BAG/CARTRIDGE

RIGHT SIDE LOAD

12IN

0.782

A LEVEL

CSAA014

7,000

SUPPLY:18.15/30

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

PLEATED MEDIA

MERV 8

7,000

342 MBH

45.00

90.00

12.5

34.5

3.70

7,000

7,000

95/78

55/54.9

13.5

0.945

15.40

7,000

207MBH

HOT WATER

12.5

20.7

1.40

7,000

2.5

22.25

1,800

DIRECT

10HP/460/3Ø

PLENUM

PER FAN

1X1

BAG/CARTRIDGE

13.5

RIGHT SIDE LOAD

12IN

0.782

CSAA025 CSAA025

A & B LEVELS A & B LEVELS

1,500

SUPPLY:34.4/60 RETURN:12.5/30

11,500

1.0

24.5

DIRECT

10HP/460/3Ø

PLENUM

1X1

PER FAN

PLEATED MEDIA

MERV 8

13,000

13,000

13,000

80/67

55/54.35

24.75

0.76

10.24

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

13,000

2.5

24.5

2,034

DIRECT

20HP/460/3Ø

PLENUM

PER FAN

1X1

95% MERV 15

BAG/CARTRIDGE

26.00

RIGHT SIDE LOAD

12IN

0.773

95% MERV 1595% MERV 15

1,500

SUPPLY:34.4/60 RETURN:12.5/30

11,500

1.0

24.5

DIRECT

10HP/460/3Ø

PLENUM

1X1

PER FAN

PLEATED MEDIA

MERV 8

13,000

13,000

80/67

55/54.35

24.75

0.76

10.24

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

13,000

2.5

24.5

2,034

DIRECT

20HP/460/3Ø

PLENUM

PER FAN

1X1

95% MERV 15

BAG/CARTRIDGE

26.00

RIGHT SIDE LOAD

12IN

0.773

MORGUE

CSAA004

2,200

SUPPLY:10.90/15

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

PLEATED MEDIA

MERV 8

2,200

96.23 MBH

45.00

85.33

4.00

105.01LB/HR

0.31

NA

NA

2,200

95/78

55/54.79

CHILLED WATER

11.5

4.51

0.915

13.92

2,200

96.23 MBH

85.33

45 PSIG MED STEAM

4.00

105 LB/HR

1.97

CHILLED WATERCHILLED WATERCHILLED WATERCHILLED WATER

2,200

2.5

13.5

3,670

DIRECT

5HP/460/3Ø

PLENUM

PER FAN

1X1

95% MERV 15

BAG/CARTRIDGE

5.56

RIGHT SIDE LOAD

12IN

0.730

2" PLEATED MERV 8

18,000

SUPPLY: 47.5/80

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

PLEATED MEDIA

MERV 8

18,000

599 MBH

45.00

75.65

623.96 LB/HR

0.077

HOT WATER 45PSIG MED STEAM 5 PSI STEAM

430.5

18,000

18,000

1,474

801.74

95/78

55/54.90

CHILLED WATER

11.5

38.54

0.915

9.37

18,000

1144.43 MBH

103.63

5 PSI STEAM

35.00

1188.96 LB/HR

17.33

18,000

2.5

1,705

BELT

30HP/460/3Ø

FORWARD CURVE

PER FAN

1X1

95% MERV 15

BAG/CARTRIDGE

SIDE LOAD

12IN

0.730

2" PLEATED MERV 8

TRANE TRANE

CSAA040 CSAA014

5,000

SUPPLY: 14.4/25

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

PLEATED MEDIA

MERV 8

5,000

162.8 MBH

45.00

12.50

1.00

GLYC HOT WATER

119.6

5,000

5,000

95/78

55/54.90

CHILLED WATER

8.5

38.54

0.451

14.18

5,000

2.5

2,432

BELT

7.5HP/460/3Ø

FORWARD CURVE

PER FAN

1X1

A LEVEL CANTEEN

95% MERV 15

BAG/CARTRIDGE

SIDE LOAD

12IN

0.72

2" PLEATED MERV 8

MANUFACTURER

SERVES

FILTER PRESSURE DROP (INWG) (CLEAN)

FILTER AREA (SQUARE FEET)

FILTER MINIMUM EFFICIENCY

FILTER TYPE

REMARKS:

LOCATION

SYSTEM NO.

REMARKS:

REMARKS:

REMARKS:

FAN TYPE

REMARKS:

SQ. FT. FACE AREA MIN.

VIBRATION ISOLATORS (FANS)

MOTOR OPER. SMOKE DAMPERS

DISCHARGE AIR PLENUM W/AD

RETURN AIR PLENUM W/AD

MIXING SECTION W/AD

SENSIBLE LOAD (MBH)

E.A.T. D.B./W.B. (°F)

L.A.T. D.B./W.B. (°F)

FINS PER INCH MIN.

SQ. FT. FACE AREA MAX.

FACE VELOCITY MAX.

STEAM PRESSURE (PSI)

L.A.T. D.B. °F

E.A.T. D.B. °F

TYPE COIL

OUTPUT HEATING CAPACITY (MBH)

TOTAL CFM

ROWS MIN.

TYPE COIL

RPM APPROX.

TYPE DRIVE

HP MIN/VOLT/PH

TOTAL LOAD (MBH)

TOTAL CFM

TOTAL CFM (CFM PER FAN)

EXTERNAL STATIC PRESSURE (IN W.G.)

SYSTEM TYPE

ECONOMIZER

OUTSIDE AIR CFM (MINIMUM/ECONOMIZER)

MODEL NUMBER

ELECTRICAL CHARACTERISTICS (MOP/MCA)

NO

NO

NO

YES

YES

NORTEK

VARIABLE VOLUME

TBD

BLDG 7/ROOF

AHU-7B

YES

5,200

FORWARD CURVED

2,650

BELT

5,200

2.0

12.00

93/74

52.3/52

DX

373.5

STEAM

5.0

68.8

MERV 8

77.8

0.25

5,200

2" CARTRIDGE

5,200

1 @ 7.5/208/3Ø

PACKAGED CONDENSING

UNIT

A-1-05e-PX-SC-ACCU0302-X-P

225/184

C O

O L

IN

G C

O

IL

A C

C E

S S

S

U P

P L Y

F A

N H

E A

T

IN

G C

O

IL

P R

E F

IL

T

E R

PACKAGED AIR HANDLING UNIT SCHEDULE

WEIGHT (LBS) TBD

TBD

GENERAL NOTES:

1. PROVIDE SUPPLY AIR SMOKE DAMPER, OUTSIDE

AIR INTAKE SMOKE DAMPER, RETURN AIR

OPENING DAMPER AND RETURN AIR (MIXED AIR)

SMOKE DAMPER. EACH DAMPER SHALL COMPLY

WITH UL 555S, CLASS 1.

2. FILTERS SHALL BE PROVIDED BY THE UNIT

MANUFACTURER. ONE SET OF NEW FILTERS

SHALL BE INSTALLED IN EACH FILTER BANK

WHEN BUILDING IS TURNED OVER TO OWNER

AND ONE COMPLETE SET SHALL BE PROVIDED

FOR OWNER'S STOCK.

3. REFER TO UNIT PLANS FOR ARRANGEMENT OF

UNITS, ACCESS DOORS, ETC.

4. REFER TO SPECIFICATIONS FOR SPECIFIC

REQUIREMENTS FOR ACCESSORIES AND DETAILS

OF CONSTRUCTION FOR THE AIR HANDLING

UNITS.

5. ALL CUSTOM ROOF TOP UNITS SHALL BE

PROVIDED WITH REMOTE MOUNTED ELECTRICAL

PANELS, LIGHTING FOR EACH SECTION AND UV

LIGHTING FOR COOLING COIL SECTION.

6. UNIT DIMENSIONS SHALL MATCH EXISTING

CURB DIMENSIONS SO THAT EXISTING ROOF

CURB MAY BE REUSED. IF NECESSARY, A

CURB ADAPTER SHALL BE PROVIDED.

8. UNITS WILL BE PROVIDED WITH DOUBLE WALL

CONSTRUCTION.

9. UNITS WILL BE PROVIDE WITH INSULATED

STAINLESS STEEL DRAIN PANS.

PREFILTER MIN. EFF.

FINAL FILTER MIN. EFF.

FINAL FILTER TYPE

ACCESS SECTION W/AD

F

IN

A L

F

IL

T E

R MERV 8

MERV 14

CARTRIDGE

YES

AHU-7C

BLDG 7/ROOF

BELT GUARD AND THRUST

RESTRAINT

NO

NO

NO

YES

YES

NORTEK

VARIABLE VOLUME

YES

5,200

FORWARD CURVED

2,650

BELT

4,000

2.0

12.00

93/74

52.3/52

DX

373.5

STEAM

5.0

68.8

MERV 8

77.8

0.25

4,000

2" CARTRIDGE

5,200

1 @ 7.5/208/3Ø

PACKAGED CONDENSING

UNIT

A-1-05e-PX-SC-ACCU0302-X-P

225/184

TBD

BELT GUARD AND THRUST

RESTRAINT

634 MBH

45.00

90.00

HOT WATER

24.08

63.5

7.90

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

35.00

1.1 BI-POLAR IONIZATION SYSTEM

A. DESCRIPTION:

1. PROVIDE A MODULAR NEEDLEPOINT BIPOLAR IONIZATION SYSTEM THAT IS FIELD

ASSEMBLED TO ANY LENGTH REQUIRED UP TO 240 INCHES IN 6-INCH INCREMENTS. THE

COMPOSITE AND CARBON FIBER CONSTRUCTION THAT ALLOWS UNIT TO BE MOUNTED IN

CORROSIVE ENVIRONMENTS.

2. FACTORY INSTALLED AND PRE-ENGINEERED.

3. MANUFACTURED BY GPS SOLUTIONS (OR EQUAL).

B. STANDARD: UL LISTED, UL 2998 COMPLIANT. PRODUCTS WITHOUT UL 2998 ARE NOT ACCEPTABLE.

ASHRAE 62 NOW REQUIRES ALL ELECTRONIC AIR CLEANERS TO BE UL 2998 CERTIFIED AS AN OZONE FREE DEVICE AND SUPPLIER MUST SUBMIT UL 2998 ENVIRONMENTAL CLAIM CERTIFICATE PROVING

NO OZONE OUTPUT.

C. BAR: COMPOSITE AND CARBON FIBER CONSTRUCTION. OUTPUT FROM EACH BAR SHALL BE A

MINIMUM OF 120 MILLION IONS/CC PER INCH OF BAR WHEN TESTED AT 1” FROM THE IONIZATION

BAR. BARS WITH NEEDLES SPACED FURTHER APART THAN 0.5” AND DC BARS SHALL NOT BE

ACCEPTABLE.

D. ACCESS DOOR : INSTALL UNIT UPSTREAM OF COOLING COILS DOWNSTREAM OF PRE-

FILTER. INSTALL IN AREA WITH ACCESS DOOR TO ALLOW FOR UNIT SERVICE. INSTALL CONTROL PANEL OUTSIDE OF AIR HANDLING UNIT ON WALL OR ON AHU HOUSING (IF AMPLE SPACE PERMITS –

THAT DOES NOT INHIBIT ACCESS TO OTHER COMPONENTS).

E. POWER SUPPLY: UL-LISTED, SINGLE-POINT ELECTRICAL CONNECTION WITH SERVICE DISCONNECT.

F. TESTING: PRODUCT SHOULD HAVE IONIZATION TESTING RESULTS, DEMONSTRATING A 99.4%

REDUCTION RATE ON A SARS-COV-2 (COVID-19) SURFACE STRAIN WITHIN 30 MINUTES

BI-POLAR IONIZATION

EACH AHU SHALL BE PROVIDED WITH BI-POLAR

IONZATION UNITS BY GLOBAL PLASMA SOLUTIONS OR

EQUAL. SEE SPECIFICATION NOTES.

11.

6. EACH AHU SHALL BE PROVIDED WITH BI-

POLAR IONIZATION UNITS BY GLOBAL

PLASMA SOLUTIONS OR EQUAL. SEE

SPECIFICAITON.

FILTER ASSEMBLY NON-

STANDARD, OFFSET FILTER

BANKS 40"x72" (2)

YES

YES

SEE GENERAL NOTES

YES

YES

YES

SEE SEQUENCE

YES

YES

SEE GENERAL NOTES

YES

YES

YES

SEE SEQUENCE

YES

YES

SEE GENERAL NOTES

YES

YES

YES

SEE SEQUENCE

YES

YES

SEE GENERAL NOTES

YES

YES

YES

SEE SEQUENCE

YES

YES

SEE GENERAL NOTES

YES

YES

YES

SEE SEQUENCE

YES

YES

SEE GENERAL NOTES

YES

YES

YES

SEE SEQUENCE

YES

YES

SEE GENERAL NOTES

YES

YES

YES

SEE SEQUENCE

12" MIN 12" MIN 12" MIN 12" MIN 12" MIN 12" MIN

13,000

634 MBH

45.00

90.00

HOT WATER

24.08

63.5

7.90

EACH AHU SHALL BE INSTALLED TO ALLOW ACCESS

TO COILS FOR FUTURE REPLACEMENT.

12.

AS CONTRACTOR DEVELOPS PLAN FOR CONSTRUCTION AND REPLACEMENT

OF AIR HANDLING UNITS, IT IS CRITICAL THAT THE FOLLOWING AIR HANDLING

UNITS ARE INSTALLED BETWEEN THE MONTHS OF OCTOBER & FEBRUARY:

• AHU-7

• AHU-CANTEEN (AHU-10)

• AHU-A-LEVEL LAB

• MORGUE AHU-10A

CONSTRUCTION NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

ENGINEER OF RECORD

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves

M L o c a l R e v it F ile s \R e v it

\4

C

E C e n tr a l M o d e l.

rv t

/1

/2

:0

:3

A

M

M-004

MECHANICAL - AHU SCHEDULES VAMC EAST ORANGE AHU &

WATER-COOLED EQUIPMENT

UPGRADES

EAST ORANGE, NEW JERSEY

561-19-130

3/11/2021 GAT DON

FULLY SPRINKLERED

Revisions: Date:

ADDENDUM 1 5/10/2021

Sheets
M-004 - MECHANICAL - AHU SCHEDULES
MD-7-R-01 - MECHANICAL - DEMOLITION - BUILDING 7 - ROOF
MH-7-R-01 - MECHANICAL - NEW WORK - BUILDING 7 - ROOF

File details come from the government source that posted it. Updated .