M-004 - MECHANICAL - AHU SCHEDULES.pdf
PDF 325 KB Posted
- Attached to
- Y1DA--Upgrade AHU's and Water-Cooled Equipment
- Solicitation number
- 36C24221B0040
About this file
This document includes an air handling unit (AHU) schedule and specifications for upgrading AHUs and water-cooled equipment at the VA New Jersey Healthcare System East Orange Campus. Key details include:
-
Replacing deficient HVAC equipment in Buildings 1 and 7 including new AHUs, water-cooled equipment, and all related connections.
-
Scope of work covers general construction, alterations, asbestos abatement, HVAC, plumbing and electrical work to remove existing finishes and construct new.
-
Project completion is 328 calendar days from notice to proceed.
-
Solicitation number 36C24221B0040 will be posted on SAM.gov on or around June 4, 2021 and include the response address, date and time.
-
The estimated cost is between $2-5 million.
-
The opportunity is a Service-Disabled Veteran Owned Small Business set-aside for the Department of Veterans Affairs Veterans Health Administration VISN 2.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24221B0040 0001.docx | DOCX document | |
| 36C24221B0040_1.docx | DOCX document | |
| Drawings MEPF - 561-19-130.pdf | ||
| MD-7-R-01 - MECHANICAL - DEMOLITION - BUILDING 7 - ROOF.pdf | ||
| VHA MASTER SPECIFICATIONS.pdf | ||
| MH-7-R-01 - MECHANICAL - NEW WORK - BUILDING 7 - ROOF.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROVIDE SUPPLY AIR SMOKE DAMPER, OUTSIDE
AIR INTAKE SMOKE DAMPER, RETURN AIR
OPENING DAMPER AS SMOKE DAMPER.
EACH DAMPER SHALL COMPLY
WITH UL 555S, CLASS 1.
GENERAL NOTES:
1.
2. FILTERS SHALL BE PROVIDED BY THE UNIT
MANUFACTURER. ONE SET OF NEW FILTERS
SHALL BE INSTALLED IN EACH FILTER BANK
WHEN BUILDING IS TURNED OVER TO OWNER
AND ONE COMPLETE SET SHALL BE PROVIDED
FOR OWNER'S STOCK.
3. REFER TO UNIT PLANS FOR ARRANGEMENT OF
UNITS, ACCESS DOORS, ETC.
4. REFER TO SPECIFICATIONS FOR SPECIFIC
REQUIREMENTS FOR ACCESSORIES AND DETAILS
OF CONSTRUCTION FOR THE AIR HANDLING
UNITS.
5. ALL UNITS SHALL BE
PROVIDED WITH REMOTE MOUNTED ELECTRICAL
PANELS, LIGHTING FOR EACH SECTION AND UV
LIGHTING FOR COOLING COIL
SECTION.
6. ROOFTOP UNITS SHALL HAVE STRUCTURAL,
SEISMIC ROOF SUPPORTS.
MANUFACTURER
REMARKS:
SERVES
GPM (CHILLED WATER ONLY)
WHEEL DIAMETER (IN)
FILTER PRESSURE DROP (INWG) (CLEAN)
FILTER AREA (SQUARE FEET)
FILTER MINIMUM EFFICIENCY
FILTER TYPE
REMARKS:
TYPE UNIT
LOCATION
SYSTEM NO.
VFD
REMARKS:
FAN TYPE
REMARKS:
REMARKS:
VFD
REMARKS:
FAN TYPE
SQ. FT. FACE AREA MIN.
PREFILTER MIN. EFF.
FINAL FILTER MIN. EFF.
FINAL FILTER TYPE
FINAL FILTER (SF)
ACCESS SECTION W/AD
SUPPORT BASE
VIBRATION ISOLATORS (FANS)
MOTOR OPER. SMOKE DAMPERS
DISCHARGE AIR PLENUM W/AD
RETURN AIR PLENUM W/AD
MIXING SECTION W/AD
SENSIBLE LOAD (MBH)
E.A.T. D.B./W.B. (°F)
L.A.T. D.B./W.B. (°F)
FINS PER INCH MIN.
SQ. FT. FACE AREA MAX.
FACE VELOCITY MAX.
AIR PRESSURE DROP INWG
INPUT HEATING CAPACITY
L.A.T. D.B. °F
E.A.T. D.B. °F
TYPE COIL
TOTAL CFM
ROWS MIN.
TYPE COIL
WHEEL DIAMETER MIN. (in.)
RPM APPROX.
TYPE DRIVE
HP MIN/VOLT/PH
ARRANGEMENT
RPM APPROX.
HP MIN/VOLT/PH
TYPE DRIVE
EXTERNAL STATIC PRESSURE
TOTAL CFM (CFM PER FAN)
TOTAL LOAD (MBH)
ARRANGEMENT
TOTAL CFM
TOTAL CFM (CFM PER FAN)
EXTERNAL STATIC PRESSURE (IN W.G.)
TOTAL AIRFLOW (SUPPLY) CFM
ECONOMIZER
OUTSIDE AIR CFM (MINIMUM/ECONOMIZER)
REMARKS:
RATED CAPACITY (lbs/hr)
AIRFLOW, CFM
MODEL NUMBER
WATER PRESSURE DROP (FTWG) CHILLED WAT.
ELECTRICAL CHARACTERISTICS (MOP/MCA)
AHU-7
BLDG 1 / PENTHOUSE
INDOOR
C O
O L
IN
G C
O
IL
A C
C E
S S
S
U P
P L Y
F A
N F
IN
A
L F
IL
T
E R
P R
E -H
E A
T
IN
G C
O
IL
P R
E F
IL
T
E R
R E
T U
R N
F A
N
CUSTOM AIR HANDLING UNIT SCHEDULE
H U
M
ID
IF
IE
R
FLUID FLOW RATE (GPM)
MAX WATER P.D. (FT.)
ABSORBTION DISTANCE (in)
REMARKS:
SQ. FT. FACE AREA MIN.
INPUT HEATING CAPACITY
L.A.T. D.B. °F
E.A.T. D.B. °F
TYPE COIL
TOTAL CFM
R E
-H E
A T
IN
G
C O
IL
FLUID FLOW RATE (GPM)
MAX WATER P.D. (FT.)
7. PROVIDE NEMA 3R ENCLOSURES ON VFDs.
LOCATED OUTDOORS.
8. PROVIDE UV LIGHTS DOWNSTREAM OF COOLING COIL.
AHU-11
BLDG 1 / LEVEL C
AHU-12
BLDG 1 / LEVEL C
AHU-13
BLDG 1 / LEVEL C
MORGUE AHU-10A
BLDG 1 / LEVEL C
INDOOR INDOOR INDOOR INDOOR
AHU-A-LEVEL-LAB
BLDG 1 / LEVEL A
INDOOR
AHU-CANTEEN
BLDG 1 / LEVEL 3
INDOOR
9. PROVIDE STAINLESS STEEL COIL CASINGS FOR
COOLING COILS.
PROVIDE SUPPORT BENEATH UNIT WITH EITHER 6"
ALUMINUM I BEAM OR CONCRETE CURB, SEE UNIT
DRAWINGS FOR DETAILS, TO FACILITATE
INSTALLATION
OF DRAIN AND TRAP FROM COIL SECTIONS.
10.
5,000
REMARKS:
UV LIGHTS
TRANE TRANE TRANE TRANE TRANE
18,000 7,000 13,000 13,000 2,200 18,000
15,500 (7,750)
1.0
22.25
1,200
DIRECT
5HP/460/3Ø (EACH)
PLENUM
PER FAN
1X2
2,500
CSAA035
13TH FLOOR
SUPPLY:51/90 RETURN:22/35
18,000 (9,000)
2.0
22.25
1,800
DIRECT
15HP/460/3Ø (EACH)
PLENUM
PER FAN
1X2
PLEATED MEDIA
MERV 8
18,000
880 MBH
45.00
90.00
HOT WATER
15.00
430.5
18,000
12" MIN
18,000
80/67
55/54.5
0.646
19.18
18,000
554.28
HOT WATER
55.5
6.08
BAG/CARTRIDGE
RIGHT SIDE LOAD
12IN
0.782
A LEVEL
CSAA014
7,000
SUPPLY:18.15/30
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
PLEATED MEDIA
MERV 8
7,000
342 MBH
45.00
90.00
12.5
34.5
3.70
7,000
7,000
95/78
55/54.9
13.5
0.945
15.40
7,000
207MBH
HOT WATER
12.5
20.7
1.40
7,000
2.5
22.25
1,800
DIRECT
10HP/460/3Ø
PLENUM
PER FAN
1X1
BAG/CARTRIDGE
13.5
RIGHT SIDE LOAD
12IN
0.782
CSAA025 CSAA025
A & B LEVELS A & B LEVELS
1,500
SUPPLY:34.4/60 RETURN:12.5/30
11,500
1.0
24.5
DIRECT
10HP/460/3Ø
PLENUM
1X1
PER FAN
PLEATED MEDIA
MERV 8
13,000
13,000
13,000
80/67
55/54.35
24.75
0.76
10.24
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
13,000
2.5
24.5
2,034
DIRECT
20HP/460/3Ø
PLENUM
PER FAN
1X1
95% MERV 15
BAG/CARTRIDGE
26.00
RIGHT SIDE LOAD
12IN
0.773
95% MERV 1595% MERV 15
1,500
SUPPLY:34.4/60 RETURN:12.5/30
11,500
1.0
24.5
DIRECT
10HP/460/3Ø
PLENUM
1X1
PER FAN
PLEATED MEDIA
MERV 8
13,000
13,000
80/67
55/54.35
24.75
0.76
10.24
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
13,000
2.5
24.5
2,034
DIRECT
20HP/460/3Ø
PLENUM
PER FAN
1X1
95% MERV 15
BAG/CARTRIDGE
26.00
RIGHT SIDE LOAD
12IN
0.773
MORGUE
CSAA004
2,200
SUPPLY:10.90/15
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
PLEATED MEDIA
MERV 8
2,200
96.23 MBH
45.00
85.33
4.00
105.01LB/HR
0.31
NA
NA
2,200
95/78
55/54.79
CHILLED WATER
11.5
4.51
0.915
13.92
2,200
96.23 MBH
85.33
45 PSIG MED STEAM
4.00
105 LB/HR
1.97
CHILLED WATERCHILLED WATERCHILLED WATERCHILLED WATER
2,200
2.5
13.5
3,670
DIRECT
5HP/460/3Ø
PLENUM
PER FAN
1X1
95% MERV 15
BAG/CARTRIDGE
5.56
RIGHT SIDE LOAD
12IN
0.730
2" PLEATED MERV 8
18,000
SUPPLY: 47.5/80
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
PLEATED MEDIA
MERV 8
18,000
599 MBH
45.00
75.65
623.96 LB/HR
0.077
HOT WATER 45PSIG MED STEAM 5 PSI STEAM
430.5
18,000
18,000
1,474
801.74
95/78
55/54.90
CHILLED WATER
11.5
38.54
0.915
9.37
18,000
1144.43 MBH
103.63
5 PSI STEAM
35.00
1188.96 LB/HR
17.33
18,000
2.5
1,705
BELT
30HP/460/3Ø
FORWARD CURVE
PER FAN
1X1
95% MERV 15
BAG/CARTRIDGE
SIDE LOAD
12IN
0.730
2" PLEATED MERV 8
TRANE TRANE
CSAA040 CSAA014
5,000
SUPPLY: 14.4/25
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
PLEATED MEDIA
MERV 8
5,000
162.8 MBH
45.00
12.50
1.00
GLYC HOT WATER
119.6
5,000
5,000
95/78
55/54.90
CHILLED WATER
8.5
38.54
0.451
14.18
5,000
2.5
2,432
BELT
7.5HP/460/3Ø
FORWARD CURVE
PER FAN
1X1
A LEVEL CANTEEN
95% MERV 15
BAG/CARTRIDGE
SIDE LOAD
12IN
0.72
2" PLEATED MERV 8
MANUFACTURER
SERVES
FILTER PRESSURE DROP (INWG) (CLEAN)
FILTER AREA (SQUARE FEET)
FILTER MINIMUM EFFICIENCY
FILTER TYPE
REMARKS:
LOCATION
SYSTEM NO.
REMARKS:
REMARKS:
REMARKS:
FAN TYPE
REMARKS:
SQ. FT. FACE AREA MIN.
VIBRATION ISOLATORS (FANS)
MOTOR OPER. SMOKE DAMPERS
DISCHARGE AIR PLENUM W/AD
RETURN AIR PLENUM W/AD
MIXING SECTION W/AD
SENSIBLE LOAD (MBH)
E.A.T. D.B./W.B. (°F)
L.A.T. D.B./W.B. (°F)
FINS PER INCH MIN.
SQ. FT. FACE AREA MAX.
FACE VELOCITY MAX.
STEAM PRESSURE (PSI)
L.A.T. D.B. °F
E.A.T. D.B. °F
TYPE COIL
OUTPUT HEATING CAPACITY (MBH)
TOTAL CFM
ROWS MIN.
TYPE COIL
RPM APPROX.
TYPE DRIVE
HP MIN/VOLT/PH
TOTAL LOAD (MBH)
TOTAL CFM
TOTAL CFM (CFM PER FAN)
EXTERNAL STATIC PRESSURE (IN W.G.)
SYSTEM TYPE
ECONOMIZER
OUTSIDE AIR CFM (MINIMUM/ECONOMIZER)
MODEL NUMBER
ELECTRICAL CHARACTERISTICS (MOP/MCA)
NO
NO
NO
YES
YES
NORTEK
VARIABLE VOLUME
TBD
BLDG 7/ROOF
AHU-7B
YES
5,200
FORWARD CURVED
2,650
BELT
5,200
2.0
12.00
93/74
52.3/52
DX
373.5
STEAM
5.0
68.8
MERV 8
77.8
0.25
5,200
2" CARTRIDGE
5,200
1 @ 7.5/208/3Ø
PACKAGED CONDENSING
UNIT
A-1-05e-PX-SC-ACCU0302-X-P
225/184
C O
O L
IN
G C
O
IL
A C
C E
S S
S
U P
P L Y
F A
N H
E A
T
IN
G C
O
IL
P R
E F
IL
T
E R
PACKAGED AIR HANDLING UNIT SCHEDULE
WEIGHT (LBS) TBD
TBD
GENERAL NOTES:
1. PROVIDE SUPPLY AIR SMOKE DAMPER, OUTSIDE
AIR INTAKE SMOKE DAMPER, RETURN AIR
OPENING DAMPER AND RETURN AIR (MIXED AIR)
SMOKE DAMPER. EACH DAMPER SHALL COMPLY
WITH UL 555S, CLASS 1.
2. FILTERS SHALL BE PROVIDED BY THE UNIT
MANUFACTURER. ONE SET OF NEW FILTERS
SHALL BE INSTALLED IN EACH FILTER BANK
WHEN BUILDING IS TURNED OVER TO OWNER
AND ONE COMPLETE SET SHALL BE PROVIDED
FOR OWNER'S STOCK.
3. REFER TO UNIT PLANS FOR ARRANGEMENT OF
UNITS, ACCESS DOORS, ETC.
4. REFER TO SPECIFICATIONS FOR SPECIFIC
REQUIREMENTS FOR ACCESSORIES AND DETAILS
OF CONSTRUCTION FOR THE AIR HANDLING
UNITS.
5. ALL CUSTOM ROOF TOP UNITS SHALL BE
PROVIDED WITH REMOTE MOUNTED ELECTRICAL
PANELS, LIGHTING FOR EACH SECTION AND UV
LIGHTING FOR COOLING COIL SECTION.
6. UNIT DIMENSIONS SHALL MATCH EXISTING
CURB DIMENSIONS SO THAT EXISTING ROOF
CURB MAY BE REUSED. IF NECESSARY, A
CURB ADAPTER SHALL BE PROVIDED.
8. UNITS WILL BE PROVIDED WITH DOUBLE WALL
CONSTRUCTION.
9. UNITS WILL BE PROVIDE WITH INSULATED
STAINLESS STEEL DRAIN PANS.
PREFILTER MIN. EFF.
FINAL FILTER MIN. EFF.
FINAL FILTER TYPE
ACCESS SECTION W/AD
F
IN
A L
F
IL
T E
R MERV 8
MERV 14
CARTRIDGE
YES
AHU-7C
BLDG 7/ROOF
BELT GUARD AND THRUST
RESTRAINT
NO
NO
NO
YES
YES
NORTEK
VARIABLE VOLUME
YES
5,200
FORWARD CURVED
2,650
BELT
4,000
2.0
12.00
93/74
52.3/52
DX
373.5
STEAM
5.0
68.8
MERV 8
77.8
0.25
4,000
2" CARTRIDGE
5,200
1 @ 7.5/208/3Ø
PACKAGED CONDENSING
UNIT
A-1-05e-PX-SC-ACCU0302-X-P
225/184
TBD
BELT GUARD AND THRUST
RESTRAINT
634 MBH
45.00
90.00
HOT WATER
24.08
63.5
7.90
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
35.00
1.1 BI-POLAR IONIZATION SYSTEM
A. DESCRIPTION:
1. PROVIDE A MODULAR NEEDLEPOINT BIPOLAR IONIZATION SYSTEM THAT IS FIELD
ASSEMBLED TO ANY LENGTH REQUIRED UP TO 240 INCHES IN 6-INCH INCREMENTS. THE
COMPOSITE AND CARBON FIBER CONSTRUCTION THAT ALLOWS UNIT TO BE MOUNTED IN
CORROSIVE ENVIRONMENTS.
2. FACTORY INSTALLED AND PRE-ENGINEERED.
3. MANUFACTURED BY GPS SOLUTIONS (OR EQUAL).
B. STANDARD: UL LISTED, UL 2998 COMPLIANT. PRODUCTS WITHOUT UL 2998 ARE NOT ACCEPTABLE.
ASHRAE 62 NOW REQUIRES ALL ELECTRONIC AIR CLEANERS TO BE UL 2998 CERTIFIED AS AN OZONE FREE DEVICE AND SUPPLIER MUST SUBMIT UL 2998 ENVIRONMENTAL CLAIM CERTIFICATE PROVING
NO OZONE OUTPUT.
C. BAR: COMPOSITE AND CARBON FIBER CONSTRUCTION. OUTPUT FROM EACH BAR SHALL BE A
MINIMUM OF 120 MILLION IONS/CC PER INCH OF BAR WHEN TESTED AT 1” FROM THE IONIZATION
BAR. BARS WITH NEEDLES SPACED FURTHER APART THAN 0.5” AND DC BARS SHALL NOT BE
ACCEPTABLE.
D. ACCESS DOOR : INSTALL UNIT UPSTREAM OF COOLING COILS DOWNSTREAM OF PRE-
FILTER. INSTALL IN AREA WITH ACCESS DOOR TO ALLOW FOR UNIT SERVICE. INSTALL CONTROL PANEL OUTSIDE OF AIR HANDLING UNIT ON WALL OR ON AHU HOUSING (IF AMPLE SPACE PERMITS –
THAT DOES NOT INHIBIT ACCESS TO OTHER COMPONENTS).
E. POWER SUPPLY: UL-LISTED, SINGLE-POINT ELECTRICAL CONNECTION WITH SERVICE DISCONNECT.
F. TESTING: PRODUCT SHOULD HAVE IONIZATION TESTING RESULTS, DEMONSTRATING A 99.4%
REDUCTION RATE ON A SARS-COV-2 (COVID-19) SURFACE STRAIN WITHIN 30 MINUTES
BI-POLAR IONIZATION
EACH AHU SHALL BE PROVIDED WITH BI-POLAR
IONZATION UNITS BY GLOBAL PLASMA SOLUTIONS OR
EQUAL. SEE SPECIFICATION NOTES.
11.
6. EACH AHU SHALL BE PROVIDED WITH BI-
POLAR IONIZATION UNITS BY GLOBAL
PLASMA SOLUTIONS OR EQUAL. SEE
SPECIFICAITON.
FILTER ASSEMBLY NON-
STANDARD, OFFSET FILTER
BANKS 40"x72" (2)
YES
YES
SEE GENERAL NOTES
YES
YES
YES
SEE SEQUENCE
YES
YES
SEE GENERAL NOTES
YES
YES
YES
SEE SEQUENCE
YES
YES
SEE GENERAL NOTES
YES
YES
YES
SEE SEQUENCE
YES
YES
SEE GENERAL NOTES
YES
YES
YES
SEE SEQUENCE
YES
YES
SEE GENERAL NOTES
YES
YES
YES
SEE SEQUENCE
YES
YES
SEE GENERAL NOTES
YES
YES
YES
SEE SEQUENCE
YES
YES
SEE GENERAL NOTES
YES
YES
YES
SEE SEQUENCE
12" MIN 12" MIN 12" MIN 12" MIN 12" MIN 12" MIN
13,000
634 MBH
45.00
90.00
HOT WATER
24.08
63.5
7.90
EACH AHU SHALL BE INSTALLED TO ALLOW ACCESS
TO COILS FOR FUTURE REPLACEMENT.
12.
AS CONTRACTOR DEVELOPS PLAN FOR CONSTRUCTION AND REPLACEMENT
OF AIR HANDLING UNITS, IT IS CRITICAL THAT THE FOLLOWING AIR HANDLING
UNITS ARE INSTALLED BETWEEN THE MONTHS OF OCTOBER & FEBRUARY:
• AHU-7
• AHU-CANTEEN (AHU-10)
• AHU-A-LEVEL LAB
• MORGUE AHU-10A
CONSTRUCTION NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
ENGINEER OF RECORD
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves
M L o c a l R e v it F ile s \R e v it
\4
C
E C e n tr a l M o d e l.
rv t
/1
/2
:0
:3
A
M
M-004
MECHANICAL - AHU SCHEDULES VAMC EAST ORANGE AHU &
WATER-COOLED EQUIPMENT
UPGRADES
EAST ORANGE, NEW JERSEY
561-19-130
3/11/2021 GAT DON
FULLY SPRINKLERED
Revisions: Date:
ADDENDUM 1 5/10/2021
| Sheets |
| M-004 - MECHANICAL - AHU SCHEDULES |
| MD-7-R-01 - MECHANICAL - DEMOLITION - BUILDING 7 - ROOF |
| MH-7-R-01 - MECHANICAL - NEW WORK - BUILDING 7 - ROOF |