This is an Approved Products List for Transmission Systems maintained by Orange County, Florida, revised October 10, 2021, covering water, reclaimed water, and wastewater infrastructure components. The document provides comprehensive specifications and manufacturer approvals for materials and equipment used in the County's water distribution and wastewater collection systems, including ductile iron pipe, PVC pipe, HDPE pipe, fittings, valves, hydrants, joint restraints, coatings, and appurtenances. The list includes numerous manufacturers with specific model numbers, performance specifications, and application requirements for each product category. Items are categorized by utility type (water, reclaimed water, and wastewater) with detailed technical requirements such as pressure ratings, material compositions, stainless steel specifications, and color-coding standards per utility type and system function.
The approved products span multiple infrastructure categories including casing seals, exterior coatings, valve boxes, service saddles, tapping valves, valve actuators, precast concrete structures, pump station equipment, and electrical control components. All manufacturers listed must maintain membership in good standing with relevant industry organizations such as DIPRA, Uni-Bell, and PPI to maintain approval status. Specifications incorporate AWWA and ASTM standards throughout, with particular emphasis on corrosion protection through coating systems, material durability, and compatibility with the County's utility infrastructure standards. The document establishes mandatory requirements for NSF certification, stainless steel hardware specifications, proper grounding systems, and equipment ratings to ensure system reliability and longevity across the County's transmission infrastructure.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sewer_Pipes_and_Fittings_(Addendum_#2_Revision).pdf | ||
| Sewer_Pipes_and_Fittings.pdf | ||
| Scope_of_Services.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Desc Manufacturer
Model # Comments Model # Comments Model # Comments
131632 H30-B Blue 44" Tall 131632 H30-P Pantone 44" 131632 H-30 Green 44" Tall 171730 H40-B Blue 30" Tall 171730 H40-P Pantone 30" 171730 H-40 Green 30" Tall
N/A N/A N/A N/A 182635 H-65 (Wide model for 6” ARV) Green 38” Tall
AVG2036 Encl AVG2036 Encl GP3232 Base GP3232 Base
AVG2041 Encl GP3232 Base
AVG2448 Encl Blue 48" Tall AVG2448 Encl Pantone 48" Tall AVG2448 Encl Green 48" Tall
Safety-Guard/Hydro Guard 15100 Encl Blue 34" Tall 15100 Encl Pantone 34" Tall 15100 Encl Green 34" Tall
ARI D-040-ST ST Combination D-040-ST ST Combination N/A N/A H-TEC 993 (316SS) 0-250 PSI 993 (316SS) 0-250 PSI 986 (316SS) Combination Vent-O-Mat Series RBX DN50 2" Series RBX DN50 2" N/A N/A Dezurik / APCO ASU Combination ASU Combination N/A N/A
HG-1, HG1ST02018T1NF00 Automatic
HG-5 With air gap to sewer lateral.
Kupferle Foundry Co Eclipse #9800WC With air gap to sewer lateral. N/A N/A N/A N/A
Oldcastle 1527 1527 N/A N/A DFW Plastics, Inc. DFW65C-14-AF1M DFW65C-14-AF1M N/A N/A
Blow Off Valve box – Shall be 15” X 27” X 12” and AASHTO H-20 loading. Shall have OCU “WATER” or OCU “RECLAIM” on the lid. Logo to match OCU lid STANDARD DRAWING, powder coat not required.
B lo w O ff
A ut o B lo w
O ff
B lo w O ff V al ve b ox
Air Release Valves shall be Combination Type, 316 SS. All ARV’s shall be installed with ¼ turn valve on flush port.
Automatic Blow Off Valve.
Hydro Guard N/A N/A N/A N/A
A ir
R el ea se
A R
V E nc lo su re
All ARV above ground enclosures shall be vented with tamper proof locking device.
Water Plus Polyethylene Enclosure
Hot Box Vent Guard Fiberglass Enclosure
AVG2036 Encl Green 36" Tall
Blue 41" Tall Green 41" Tall
A ir
R el ea se
V al ve s
Appendix D
C at
. Water Reclaimed Water
Blue 36" Tall Pantone 36" Tall
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
AVG2041 Encl AVG2041 Encl GP3232 Base Pantone 41" Tall
Appendix D D103 Page 1 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Advance Products Model AC and AW Model AC and AW Model AC and AW BWM Company Model WR and PO Model WR and PO Model WR and PO Cascade Water Works Model CCES Model CCES Model CCES CCI Pipeline Model ESW and ESC Model ESW and ESC Model ESW and ESC
Pipeline Seal & Insulator, Inc. (PSI) Model C and W Model C and W Model C and W
Power Seal Model 4810ES Model 4810ES Model 4810ES
Advance Products SSI8 / SSI12 SSI8 / SSI12 SSI8 / SSI12 BWM Company BWM-SS-8 / SS-12 BWM-SS-8 / SS-12 BWM-SS-8 / SS-12 Cascade Water Works Series CCS 8" / 12" Series CCS 8" / 12" Series CCS 8" / 12" CCI Pipeline Model CCS8 / CSS12 Model CCS8 / CSS12 Model CCS8 / CSS12
Pipeline Seal & Insulator, Inc (PSI) Series S8G-2 / S12G-2 Series S8G-2 / S12G-2 Series S8G-2 / S12G-2
Carbozinc 859 3.0 - 8.0 mils Carbozinc 859 3.0 - 8.0 mils Carbozinc 859 3.0 - 8.0 mils Carbothane 133 HB 3.0 - 5.0 mils Carbothane 133 HB 3.0 - 5.0 mils Carbothane 133 HB 3.0 - 5.0 mils Carboxane 950 2.0 - 3.0 mils Carboxane 950 2.0 - 3.0 mils Carboxane 950 2.0 - 3.0 mils
2.5 - 3.5 mils
4.0 - 14.0 mils
EnduraShield Series73 2.0 - 3.0 mils EnduraShield Series73 2.0 - 3.0 mils EnduraShield Series73 2.0 - 3.0 mils Hydroflon Series 700 2.0 - 3.0 mils Hydroflon Series 700 2.0 - 3.0 mils Hydroflon Series 700 2.0 - 3.0 mils Corothane 1 Zinc 3.0 - 4.0 mils Corothane 1 Zinc 3.0 - 4.0 mils Corothane 1 Zinc 3.0 - 4.0 mils Acrolon 218 HS Urethane 3.0 - 6.0 mils Acrolon 218 HS Urethane 3.0 - 6.0 mils Acrolon 218 HS Urethane 3.0 - 6.0 mils Fluorokem HS 2.0 - 3.0 mils Fluorokem HS 2.0 - 3.0 mils Fluorokem HS 2.0 - 3.0 mils
Ex te rio r C oa tin gs fo r Ex po se d M et al
A ss et s (
Sy st em
Coatings: Above ground piping, fittings, valves and appurtenances - System 1 Zinc / Urethane / Fluoropolymer application and color code per Section 3119 "Coatings & Linings".
Coating shall not be in contact with Potable water unless NSF-61 approved.
Carboline
Tnemec
Zinc Series 90-97 Typoxy Series 27WB
2.5 - 3.5 mils
4.0 - 14.0 mils
Zinc Series 90-97 Typoxy Series 27WB
2.5 - 3.5 mils
4.0 - 14.0 mils
Zinc Series 90-97 Typoxy Series 27WB
Sherwin Williams
C as in g
Se al s / S pa ce rs
C as in g
En d
Se al s
Casing End Seals. Annular space between pipe and steel casing shall be brick and mortar with end seals to secure ends.
C as in g sp ac er
Casing spacers shall be a min. 8-inches wide for pipe 12" Dia or less or min. 12-inches wide for pipe 16” Dia or greater, shall have a minimum 14 gauge 304 stainless steel shell/band, minimum 10 gauge 304 reinforced risers; minimum thickness of 0.090 EPDM or PVC interior liners, glass reinforces polymer or ultra high molecular weight polyethylene and 304 stainless bolts, nuts and washers.
C oa tin gs
Appendix D D103 Page 2 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Carbozinc 859 3.0 - 8.0 mils N/A N/A N/A N/A Carboguard 890 4.0 -6.0 mils N/A N/A N/A N/A Carboxane 950 2.0 - 3.0 mils N/A N/A N/A N/A Zinc Series 90-97 Typoxy Series 27WB
2.5 - 3.5 mils
4.0 -14.0 mils N/A N/A N/A N/A
Hi-Build Epoxoline II Series N69 4.0 - 10.0 mils N/A N/A N/A N/A
EnduraShield Series73 2.0 - 3.0 mils N/A N/A N/A N/A Corothane 1 Zinc 3.0 - 4.0 mils N/A N/A N/A N/A Epoxy Mastic Aluminum 4.0 - 6.0 mils N/A N/A N/A N/A Hi-Solid Polyurethane 3.0 - 5.0 mils N/A N/A N/A N/A
Protecto 401 / Permox-CTF Protecto 401 / Permox-CTF Protecto 401 / Permox-CTF Protecto 401 / Permox-CTF Protecto 401 / Permox-CTF
In Fact Corp Foster Adapter MJ restraint Foster Adapter MJ restraint Foster Adapter MJ restraint Star Series 100 MJ x MJ adapter Series 100 MJ x MJ adapter Series 100 MJ x MJ adapter SIP Industries EZ GRIP MJ adapter EZ GRIP MJ adapter EZ GRIP MJ adapter
George Fischer Central Plastics Min. DR11 Min. DR11 Min. DR11 Plasson USA Min. DR11 Min. DR11 Min. DR11 IPEX Min. DR11 Min. DR11 Min. DR11 Specified Fittings Min. DR11 Min. DR11 Min. DR11 Strongbridge International Inc. Min. DR11 Min. DR11 Min. DR11
Sherwin Williams
Ex te rio r C oa tin gs fo r Ex po se d M et al
A ss et s (
Sy st em
FBE / Cement
SIP Industries
Fi tti ng s B ol t th ru
M J
R es tra in t Ductile Iron fittings shall be FBE coating.
Fu si on F itt in fo r H
D
PE
ASTM D2683. Electrofusion Fittings shall meet ASTM F1055 and installed per F1290. Per AWWA C906, the DR of HDPE fittings shall be the same or greater than the pipe to which the fitting will be joined.
Tyler Union & Clow
30" & up FBE / Cement 30" & up
FBE / Cement
Star FBE / Cement FBE / Cement
FBE / Cement FBE / Cement
FBE / Cement FBE / Cement
Coatings: Hydrants - System 2 Zinc / Epoxy / Urethane application and color code per Section 3119 "Coatings & Linings".
Carboline
Tnemec
Fi tt in gs
Fi tti ng s
Ductile Iron Fittings C153 SSB / C110 FLG: (Water & Reclaimed Water fittings shall cement lined or holiday free fusion bonded epoxy lined per NACE standard RP0490). (Wastewater fittings interior shall be holiday free and coated with Protecto 401, or Permox-CTF )
American 30" & up FBE / Cement
Sigma
C oa tin
Appendix D D103 Page 3 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Siemens N/A N/A N/A N/A 5100 with MAG 6000 Remote Transmitter
ABB N/A N/A N/A N/A Water Master FEW
American Flow Control / American Darling B-84-B-5 (6”) N/A N/A N/A N/A
Clow Medallion 2545 (5-1/4”) N/A N/A N/A N/A Mueller Super Centurion 250 (5-1/4”) N/A N/A N/A N/A
GradeLok Swivel x Swivel N/A N/A N/A N/A Star MJ x Swivel N/A N/A N/A N/A Tyler Union MJ x Swivel N/A N/A N/A N/A SIP Industries MJ – Swivel Offset – C153 N/A N/A N/A N/A
EBAA Iron Inc Megalug Series 1100 Megalug Series 1100 Megalug Series 1100 Ford / Uni-Flange UFR-1400 UFR-1400 UFR-1400 Sigma OneLok Series SLD/SLDE OneLok Series SLD/SLDE OneLok Series SLD/SLDE Smith Blair Cam Lok Series 111 Cam Lok Series 111 Cam Lok Series 111 Star Star Grip Series 3000 Star Grip Series 3000 Star Grip Series 3000 Tyler Union TufGrip Series TLD TufGrip Series TLD TufGrip Series TLD
EBAA Iron Inc Tru-Dual Series 1500TD Tru-Dual Series 1500TD Tru-Dual Series 1500TD Ford / Uni-Flange Uni-Flange Series 1390C Uni-Flange Series 1390C Uni-Flange Series 1390C Sigma PV-Lok Series PWP-C PV-Lok Series PWP-C PV-Lok Series PWP-C Smith Blair Bell-Lock Series 165 Bell-Lock Series 165 Bell-Lock Series 165 Star StarGrip Series 3100S StarGrip Series 3100S StarGrip Series 3100S Tyler Union TufGrip-Series 300C TufGrip-Series 300C TufGrip-Series 300C
D uc til e
Ir on p ip e B el l J oi nt
R es tra in ts (4
(N ew
E xi st in
g) Bell Joint Restraints for Ductile Iron Pipe (4"-12") (New & Existing) - All restraints split serrated on bell and spigot ends. Pipe 16" and greater shall have restraint gaskets or locking bells. (Wastewater only for restraint of existing DIP FM).
Fl ow
Fl ow
M et er
Flow Meters
H yd ra nt s H yd ra nt s H yd ra nt M
J O ff se t S w ee ps da pt er s
Hydrants shall use MJ Swivel adapter to ensure hydrant is at proper grade. Risers shall not be permitted.
D uc til e iro n pi pe
M J
R es tra in ts
Mechanical Joint Wedge-action Restraining Gland, Epoxy Coated Restrain ductile iron pipe to mechanical joint fittings, pipe and appurtenances.
Hydrants Shall open left, 1-1/2" Pentagon operating nut, NST hose & pumper thread, rotate 360 degrees, closed drains, epoxy on shoe in & out and 304 SS nuts & bolts below ground.
Hydrant sizes shall be 36”, 42”, 48”, or 54” only.
Jo in t R es tr ai nt s
Appendix D D103 Page 4 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
EBAA Iron Inc Series 1100HD Existing Only Series 1100HD Existing Only Series 1100HD Existing Only Sigma Series SSLDH Existing Only Series SSLDH Existing Only Series SSLDH Existing Only Star Series 3100S Existing Only Series 3100S Existing Only Series 3100S Existing Only
Fast Grip Gasket Gasket Fast Grip Gasket Gasket N/A N/A Flex-Ring Joint Bell Lock Flex-Ring Joint Bell Lock N/A N/A Lok-Ring Joint Bell Lock Lok-Ring Joint Bell Lock N/A N/A Talon RJ Gasket Gasket Talon RJ Gasket Gasket N/A N/A Snap-Lok Bell Lock Snap-Lok Bell Lock N/A N/A Sure Stop 350 Gasket Gasket Sure Stop 350 Gasket Gasket N/A N/A TR-Flex Bell Lock TR-Flex Bell Lock N/A N/A Field Lok 350 Gasket Gasket Field Lok 350 Gasket Gasket N/A N/A Field Lok Gasket Gasket Field Lok Gasket Gasket N/A N/A TR-Flex Bell Lock TR-Flex Bell Lock N/A N/A HP Lok Restraint Joint Bell Lock HP Lok Restraint Joint Bell Lock N/A N/A
Mega-lug Series 2000PV Mega-lug Series 2000PV Mega-lug Series 2000PV N/A N/A N/A N/A Megalug Series 2200 (42"-48")
Ford / Uni-Flange UFR 1500 Series UFR 1500 Series UFR 1500 Series Sigma One Lok Series SLC/SLCE One Lok Series SLC/SLCE One Lok Series SLC/SLCE Smith Blair Cam Lok Series 120 Cam Lok Series 120 Cam Lok Series 120 Star Star Grip Series 4000 Star Grip Series 4000 Star Grip Series 4000 Tyler Union TufGrip Series TLP TufGrip Series TLP TufGrip Series TLP
EBAA Iron Inc Tru-Dual Series 1500TD Tru-Dual Series 1500TD Tru-Dual Series 1500TD Ford / Uni-Flange Uni-Flange Series 1390 Uni-Flange Series 1390 Uni-Flange Series 1390 Sigma PV-Lok Series PWP PV-Lok Series PWP PV-Lok Series PWP Smith Blair Bell-Lock Series 165 Bell-Lock Series 165 Bell-Lock Series 165 Star Series 1100 Series 1100 Series 1100 Tyler Union TufGrip 300C TufGrip 300C TufGrip 300C
D uc til e
Ir on
B el l Jo in t R es tra in ts
(1 6"
G re at er
PV
C
B el l J oi nt
R es tra in ts (4
- 1
2"
(N ew
E xi st in g)
PVC Bell Joint Restraints: PVC pipe Split Serrated on Bell End and Spigot End. (4" - 12") (New & Existing).
PV
C
P ip e M
J R es tra in ts Mechanical Joint Wedge-action Restraining Gland, Epoxy Coated Restrain PVC pipe to mechanical joint fittings, and appurtenances.
EBAA Iron Inc
Ductile Iron Pipe Bell Joint Restraints for Ductile Iron Pipe (16" & Greater) - All restraints shall have a split back-up ring for the bell and a serrated or wedge action gland for the spigot end. New installation for water & reclaimed water piping 16" and greater shall have restraint gaskets or locking bells.
D uc til e iro n pi pe
B el l J oi nt R es tra in t G as ke ts an d
Lo ck in g
B el l ( 4"
A bo ve
Bell Joint Restraint Gaskets and Locking Bell (4" & Above) Stainless Steel locking wedges built into the gasket-rubber. ANSI/AWWA C111/A21.11 Standard for Rubber-Gasket Joints for Ductile Iron Pressure Pipe. Ductile Iron Bell Joint Restraint for Push-On Pipe- Locking bell joint system that prevents joint separation and allows for joint deflection. Bells shall be painted red to verify restrained gasket.
American
Griffin
McWane Ductile
US Pipe
Jo in t R es tr ai nt
Appendix D D103 Page 5 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Ford / Uni-Flange Series 1390 Existing Only Series 1390 Existing Only Series 1390 JCM Sur-Grip Series 621 Existing Only Sur-Grip Series 621 Existing Only Sur-Grip Series 621 Sigma PV-Lok PWP Existing Only PV-Lok PWP Existing Only PV-Lok PWP Smith Blair Bell-Lock Series 165 Existing Only Bell-Lock Series 165 Existing Only Bell-Lock Series 165 Star Series 1100 Existing Only Series 1100 Existing Only Series 1100 Tyler Union TufGrip Series 3000 Existing Only TufGrip Series 3000 Existing Only TufGrip Series 3000
Diamond Plastics Corp C-900 Blue C-900 Pantone Purple Diamond C900/Trans-21 DR18 Green
Ipex Inc C-900 Blue Brute Blue C-900 Pantone Purple C900 Blue Brute / IPEX Centurion Green
JM Eagle C-900 Blue C-900 Pantone Purple C-900 Green National Pipe & Plastics Inc C-900 Dura-Blue Blue C-900 Pantone Purple C-900 / C905 Green
North American Pipe Corp (NAPCO) C-900 Blue C-900 Pantone Purple C-900 / C905 Green
North American Pipe Corp (NAPCO) 4” to 12”
Certa-Lok C900/ RJ DR18 (Directional Drill Only)
Blue NSF (Joint Coupled)
Certa-Lok C900/ RJ DR18 (Directional Drill Only)
Pantone Purple (Joint Coupled)
Certa-Lok C900/ RJ DR18 (Directional Drill Only)
Green (Joint Coupled)
Sanderson Pipe Corp C-900 Blue C-900 Pantone Purple C-900 Green
Charter Plastics, Inc Blue Stripes Pantone Stripes Green Stripes
Flying W Plastics Blue Stripes Pantone Stripes Green Stripes
JM Eagle Blue Stripes Pantone Stripes Green Stripes
Performance Pipe (Chevron) Blue Stripes Pantone Stripes Green Stripes
Pipeline Plastics Blue Stripes Pantone Stripes Green Stripes
WL Plastics Corp Blue Stripes Pantone Stripes Green Stripes
TUBI Blue Stripes Pantone Stripes Green Stripes
HDPE Pipe DR11 AWWA C906 shall be Ductile Iron Pipe Size, PE 4710 DIPS manufactured in accordance with ASTM F-714 and listed with NSF. Pipe shall be marked in accordance with either AWWA C901, AWWA C906. Compression type connections are not acceptable in new installations. Pipe joints shall be butt fusion or electro-fusion with flange or adapter.
All HDPE shall be color coded to the Utility. Color identifications are in accordance with the APWA/ULCC Uniform Color Code. Manufacturers shall be members in good standing with PPI to maintain approval status.
H D
PE
C
D R
PV
C B el l J oi nt
R es tra in ts
(1 6"
G re at er
PVC Bell Joint Restraints: (16" & Greater) PVC pipe Split Serrated on Bell End and Spigot End. Water & Reclaimed Water Existing pipe only. Wastewater shall be new and existing pipe.
AWWA C-900 Bell & Spigot PVC Pipe: Minimum DR18 for water and reclaimed water. 4”, 6”, & 8” Dia only. Minimum DR18 for wastewater forcemains 4” to 24”. Minimum DR21 for wastewater forcemains 30” and greater. Manufacturers shall be members in good standing with Uni-Bell to maintain approval status.
PV
C
C
B el l &
S pi go t
Jo in t R es tr ai nt s
Pi pe
Appendix D D103 Page 6 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
American Cement Lined Blue Cement Lined Pantone Purple Protecto 401 / Permox-CTF Pump Station McWaneDuctile Cement Lined Blue Cement Lined Pantone Purple Protecto 401 / Permox-CTF Pump Station US Pipe Cement Lined Blue Cement Lined Pantone Purple Protecto 401 / Permox-CTF Pump Station
Trumbull V-Bio ® Blue PE tape V-Bio ® Purple PE tape N/A N/A American V-Bio ® Blue PE tape V-Bio ® Purple PE tape N/A N/A McWane Ductile V-Bio ® Blue PE tape V-Bio ® Purple PE tape N/A N/A US Pipe V-Bio ® Blue PE tape V-Bio ® Purple PE tape N/A N/A
Safety-Guard SG-BSS-05 with pedestal #77 Green Enclosure N/A N/A N/A N/A
Water Plus Corp Model 5000 Green N/A N/A N/A N/A
Ford Series S-70, S-90 4"-12" Series S-70, S-90 4"-12" N/A N/A
AY McDonald Model 3891 / 3895,3801 / 3805 4"-12" Model 3891 / 3895,3801 / 3805 4"-12" N/A N/A
Mueller Series S-13000 / H-13000 4"-12" Series S-13000 / H-13000 4"-12" N/A N/A
Ford Series FC202 16" & greater Series FC202 16" & greater Series FC202 4" & greater JCM Series 406 16" & greater Series 406 16" & greater Series 406 4" & greater Mueller DR2S 16" & greater DR2S 16" & greater DR2S 4" & greater Romac Series 202NS 16" & greater Series 202NS 16" & greater Series 202NS 4" & greater Smith Blair Series 317 16" & greater Series 317 16" & greater Series 317 4" & greater
Brass Service Saddles for 1" & 2" water & reclaimed water services on 4" through 8” (existing 12") PVC Mains - Service saddles shall be hinge or bolt controlled OD saddles to be used on C-900 and existing IPS OD PVC pipe. Shall be no lead brass.
Se rv ic e
Sa dd le s
Service Saddles for 1" (CC) & 2" (Iron pipe threads) Water & Reclaimed Water services on mains greater than 12". Service saddles for 2” taps (iron pipe threads) on 4" mains and greater for Wastewater: Epoxy or nylon coated stainless steel 18-8-type 304 double straps, controlled O.D. saddles to be used on C-900 / C905 and DIP for all 1" and 2" taps on pipes over 12". Shall be no lead brass.
D uc til e
Ir on
P ip e Ductile iron/Cast iron: (4" to 12" = Class 350, 16" to 24" - Class 250, 30" to 64" = Class 200). Water and Reclaimed water shall be cement lined. Exterior coatings shall be Asphaltic or Zinc coating. Wastewater Piping shall be Holiday Free Protecto 401 or Permox-CTF. Exterior coatings as specified. Wastewater DIP piping shall be for pump station piping only.
Manufacturers shall be members in good standing with DIPRA to maintain approval status.
Po ly et hy le ne
En ca se m en t Polyethylene encasement: Shall be required for all ductile iron pipe 24 inches and greater and installed in accordance with ANSI/AWWA A21.51/C105.
Sa m pl e
St at io n
Sample Stations - Bacteriological Sample Station with built in flush system, all internal piping to be 2", brass and includes lockable green enclosures.
B ra ss S er vi ce
Sa dd le s P
V C
P ip e
Pi pe
Se rv ic es
Sa m pl e
St at io ns
Appendix D D103 Page 7 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
George Fischer Central Plastics Min. DR11 Min. DR11 Min. DR11 Plasson USA Min. DR11 Min. DR11 Min. DR11 IPEX Min. DR11 Min. DR11 Min. DR11 Specified Fittings Min. DR11 Min. DR11 Min. DR11 Strongbridge International Inc. Min. DR11 Min. DR11 Min. DR11
Ford FB1000 FB1000 N/A N/A AY McDonald 74701B-22 74701B-22 N/A N/A Mueller P25008 P25008 N/A N/A
American Series 2500 Series 2500 N/A N/A Clow C509 THRD X THRD C509 THRD X THRD N/A N/A Mueller A-2362 RWGV - THDXTHD A-2362 RWGV - THDXTHD N/A N/A Dezurk N/A N/A N/A N/A Eccentric Plug Henry Pratt Company N/A N/A N/A N/A Ballcentric Plug Val-Matic N/A N/A N/A N/A Eccentric Plug
Ford B41-777W B41-777W N/A N/A AY McDonald 76102W-22 76102W-22 N/A N/A Mueller P25172 P25172 N/A N/A
Ford B44-444W B44-444W N/A N/A AY McDonald 76100W-22 76100W-22 N/A N/A Mueller P25146 P25146 N/A N/A
Endot Endopure Blue Blue Endocore Lavender Purple N/A N/A JM Eagle Pure-Core Blue N/A N/A N/A N/A Advanced Drainage Systems, Inc. PolyFlex 4710 Blue PolyFlex 4710 Purple N/A N/A REHAU Municipex Blue Municipex Purple N/A N/A
2” V al ve s
Polyethylene tubing: AWWA C901 or C904. UV protection (SDR-9) 1-inch and 2-inch only. PE 4710
PE
tu bi ng
Valves shall have a 2” operating nut. Water and Reclaimed water valve shall be resilient wedge gate valve with threaded ends. Wastewater valve shall be 316 SST plug valve with threaded ends.
C ur b St op s Curb Stops - Straight Valves: Ball type compression 2" cts O.D. tubing by 2" FIP. Shall be no lead brass.
C ur b St op s Curb Stops - Straight Valves: ball type compression x compression. Shall be no lead brass.
Se rv ic e
Sa dd le s f or
H D
PE
(F us io n fit tin gs
) Service Saddles for 1" (CC) & 2" (Iron Pipe threads) Water and Reclaimed Water Services: Electrofusion service saddles to be used on HDPE for all 1-in and -2in taps. Taps to HDPE pipe shall be approved on a case by case basis. Shall be no lead brass.
1” C or po ra tio n St op s B al l T yp e
Corporation Stops Ball Type (1-inch with AWWA taper C threads only/pack joint outlet for CTS). Shall be no lead brass.
Se rv ic
Appendix D D103 Page 8 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Team InsertValve 4”-12” MJ DI Resilient Wedge Gate Valve
4”-12” MJ DI Resilient Wedge Gate Valve
N/A N/A
JCM 440 Series 440 Series 440 Series Fabricated 316
SST
Smith Blair 680 Series 680 Series N/A N/A
American Flow Control Series 2800 FBE Series 2800 FBE N/A N/A
JCM 414 Series FBE 414 Series FBE 414 Series Fabricated 316
SST
Series H-615 DIP/PVC Series H-615 DIP/PVC N/A N/A Series H-619 A/C Pipe Series H-619 A/C Pipe N/A N/A
Smith Blair Style 624 FBE Style 624 FBE N/A N/A Ford MJTS-xxxx style FBE MJTS-xxxx style FBE N/A N/A
American Flow Control Series 2500 Alignment Lip Series 2500 Alignment Lip Series 2500 Alignment Lip Clow Series F-6114 Alignment Lip Series F-6114 Alignment Lip Series F-6114 Alignment Lip Mueller Series T2361 (4"-12") Alignment Lip Series T2361 (4"-12") Alignment Lip Series T2361 (4"-12") Alignment Lip
American Flow Control Series 2500 Alignment Lip & flushing port Series 2500 Alignment Lip & flushing port Series 2500 Alignment Lip & flushing port
Clow Series F-6114 Alignment Lip & flushing port Series F-6114 Alignment Lip & flushing port Series F-6114 Alignment Lip & flushing port
Mueller Series T2361 (14"&up) Alignment Lip & flushing port Series T2361 (14"&up) Alignment Lip & flushing port Series T2361 (14"&up) Alignment Lip & flushing port
Ta pp in g
V al ve s:
an d sm al le r Tapping Valves: 12" and smaller - Tapping Valves shall be furnished with an alignment lip and installed in the vertical position for Water and Reclaim Water. Wastewater shall be installed horizontally and abandoned in the open position. Tapping valves shall be resilient seated only and meet the requirements of AWWA C509 or C515 All hardware for valve construction shall be 304 SS nuts and bolts.
Ta pp in g
V al ve s:
an d
La rg er
Tapping Valves: 16" and Larger - Tapping valves shall be furnished with an alignment lip and be installed in the vertical position for Water and Reclaimed Water. No tapping valve shall be installed horizontally for Water and Reclaim Water unless approved by the engineer. Tapping Valves 16" and larger AWWA C515 resilient seated only (16" and 24" no gearing required) above 24" shall be installed vertically with a spur gear actuator unless noted by the engineer. All tapping valves above 24” shall be furnished with NPT pipe plugs for flushing the tracks when valves are installed horizontally. Tapping valves for Wastewater shall be installed horizontally and abandoned in open position. All hardware for valve construction shall be 304 SS nuts and bolts
Li ne
S to ps
Line Stops with stainless steel nuts and bolts. Working pressure shall be minimum 150 psi.
Ta pp in g
Sl ee ve s
Tapping Sleeves: (Mechanical joint for taps on cast iron, ductile iron, PVC & AC pipe, including size on size) with stainless steel nuts and bolts. Working Pressure shall be minimum 150 psi. Wastewater tapping sleeves shall be fabricated 316SST. MJ gland ends shall meet AWWA C-110/C-111.
Mueller
T ap pi ng
S le ev es a nd
V al ve
Appendix D D103 Page 9 of 21 October 10, 2021
Appendix D C at . Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Dezurik BAW BAW N/A N/A Mueller / Pratt LINSEAL III / Groundhog LINSEAL III / Groundhog N/A N/A
American Flow Control N/A N/A N/A N/A Series 600 or 50 line Clow / M&H / Kennedy N/A N/A N/A N/A 106 Mueller N/A N/A N/A N/A Series 2600 Dezurik / APCO N/A N/A N/A N/A 250LW Series
American Flow Control Series 2500 Series 2500 N/A N/A Clow Series F-6100 (2638) Series F-6100 (2638) N/A N/A Mueller Series A-2361 Series A-2361 N/A N/A
American Flow Control Series 2500 Series 2500 N/A N/A Clow Series F-6100 (2638) Series F-6100 (2638) N/A N/A Mueller Series A-2361 Series A-2361 N/A N/A
Clow / M&H / Kennedy N/A N/A N/A N/A Eccentric (FLG / MJ) 4" & up Dezurik N/A N/A N/A N/A Series PEF or PEC (FLG / MJ) 4"& up Val-Matic N/A N/A N/A N/A 5600F or 5700F (FLG / MJ) 4" & up
HBC HBC HBC
WG series (300)(IP68-50) Modified to OCU spec WG series (300)(IP68-50) Modified to
OCU spec WG series (300)(IP68-50) Modified to OCU spec
Rotork IW-RL-MD-RAW Modified to OCU spec IW-RL-MD-RAW Modified to
OCU spec IW-RL-MD-RAW Modified to OCU spec
AUMA GS-OCU Modified to OCU spec GS-OCU Modified to
OCU spec GS-OCU Modified to OCU spec
V al ve s
Limitorque
G at e V al ve s (1
2" a nd le ss ) Gate Valves 12" and smaller - resilient seated only AWWA C509 or C515. Valve seat shall be leak-tight in both directions at 150 psi. All hardware for valve construction shall be 304 SS nuts and bolts.
V al ve A ct ua to rs
(P lu g
B ut te rf ly V al ve s)
Valve actuators are required for all plug (4” and greater) and butterfly valves. Shall be modified at minimum to OCU specs including, IP68 rated at 50' for buried service and IP67 for above ground installation. Actuator designed to withstand, without damage, an input torque of 300 ft. lbs. Actuator name plate or ID tag shall include “OCU spec”. Gear box shall be AWWA certified. A torque limiting / over-torque protector device shall be permanently mounted to valves 16” and larger.
G at e V al ve s (V er tic al an d
U p
Gate Valves 16" and larger (Vertical Installation) AWWA C515 resilient seated only (16" and 24" no gearing required) above 24" shall be installed vertically with a gear actuator unless noted by the engineer. Valve seat shall be leak-tight in both directions at 150 psi. All hardware for valve construction shall be 304 SS nuts and bolts.
Pl ug
V al ve s
Plug Valves - Bi-directional, MJ & Flanged (min. 8mil epoxy with stainless steel bolts), gear operator to be sized for rated pressure of the valve. Plug valves shall be eccentric, 100% port rectangular plug. Valves up to 12" shall be factory tested to minimum 175PSI in both directions. Valves larger than 12" shall be factory tested to 160 psi in both directions. Only approved valve actuators shall be accepted. Gear box shall be AWWA certified. A torque limiting / over-torque protector device shall be permanently mounted to valves 16” and larger. Actuator name plate or ID tag shall include “OCU spec”.
B ut te rf ly V ve an d A bo ve
Butterfly Valves 42"and above. AWWA C504. Actuators input torques based on 150 psi valve pressure and 16 fps velocity with a maximum input of 80 ft-lb on 2” nuts and shall withstand 250 ft-lbs. Valve seats shall be leak-tight in both directions at 150 psi. Horizontal shaft and no rubber seat on disc. Only approved valve actuators shall be accepted.
C he ck V al ve s Valves (Check) 4-inch and Larger (8 mil epoxy lined)
Appendix D D103 Page 10 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Series 4905 Box Series 4905 Box Series 4905 Box 4905-X Extension 4905-X Extension 4905-X Extension
CUL5LHVTSK4OCW-B Blue WATER Lid CUL5LHVTSK4OCR-P Purple
RECLAIM Lid CUL5LHVTSK4OCS-G Green SEWER Lid
EJ 6800 series Blue WATER Lid 6800 series Purple
RECLAIM Lid 6800 series Green SEWER Lid
Series VB 261X-268X Box Series VB 261X-268X Box Series VB 261X-268X Box VB 6302 Extension VB-6302 Extension VB 6302 Extension Series VB462SHD35 Box Series VB462SHD35 Box Series VB462SHD35 Box VBEX 12-24S Extension VBEX 12-24S Extension VBEX 12-24S Extension VBLIDOCUW (Water) VBLIDOCUWFH (Hydrant)
Blue or Silver WATER Lid VBLIDOCUR Purple
RECLAIM Lid VBLIDOCUS Green SEWER Lid
Series 6850 Box Series 6850 Box Series 6850 Box 58, 59, 60 Extension 58, 59, 60 Extension 58, 59, 60 Extension
V al ve B ox es w ith
H ea vy D ut y
Li ds
C as t I ro n)
Two piece standard screw type Heavy Duty Valve Boxes with Heavy Duty Lids (Cast Iron) and type of service cast in heavy duty traffic lid (H20 loading) ASTM A48. Lids shall be powder coated and have OCU Logo per STANDARD DRAWING. Heavy duty lids shall be min. 5” length including a min. 4” skirt/vane length and minimum 22 lbs.
Bingham/Taylor
Sigma
Star
Tyler Union
V al ve B ox
Appendix D D103 Page 11 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
American Building Restoration Products N/A N/A N/A N/A Polyshield Graffiti Preventer for
Unpainted Masonry Type B Super Bio Strip or Strip it all
Tnemec / Chemprobe N/A N/A N/A N/A 626 DUR A PEL 680 Mark A Way
Professional Products of Kansas, Inc N/A N/A N/A N/A Professional Water Seal & Anti- Graffitiant (PWS-15 Super Strength)
Professional Phase II Cleaner
Sherwin Williams N/A N/A N/A N/A 1K Siloxane
Kerneos Aluminate Technologies N/A N/A N/A N/A Sewpercoat min 1,000 mils (1")
Raven 171 Primer min 8 mils Raven 405 min 125 mils 210 Series min 125 mils Topcoat Glaze 210G min 20 mils Series 434 min 125 mils Topcoat Glaze 435 15-20 mils
Sprayroq N/A N/A N/A N/A SprayWall min 250 mils
Diamond Plastics Corp N/A N/A N/A N/A Sani-21 SDR-26 JM Eagle N/A N/A N/A N/A Gravity Sewer National Pipe & Plastics, Inc. N/A N/A N/A N/A Ever-Green Sewer Pipe
North American Pipe Corp (NAPCO) N/A N/A N/A N/A Gravity Sewer
Sanderson Pipe Corp N/A N/A N/A N/A Gravity Sewer
3M N/A N/A N/A N/A
PV
C
P ip e an d fit tin gs
Lo ca te
B ls Locating Marker Systems - Wastewater Locator balls placed at all sanitary sewer cleanouts 3M™ EMS 4" Extended Range 5' Ball Marker 1404-
XR
N/A N/A
Sauereisen N/A
A nt i-G ra ff iti
P ai nt Pi pe S
D R
G ra vi ty
M ai ns
PVC Pipe for Gravity (including service laterals) SDR26 (Green in color) ASTM D3034 and ASTM F679. Manufacturers shall be members in good standing with Uni-Bell to maintain approval status.
C oa tin gs fo r
Ex is tin g
M an ho le s
Rehabilitation corrosion protection system per Section 3119 "Coatings & Linings". Interior coating for force main connections to existing concrete manholes only. New precast structures and existing pump stations shall be lined.
Raven Lining System
N/A N/A
Tnemec N/A N/A
N/A
N/A N/A N/A N/A
Block Walls-Anti-Graffiti Paint per Section 3119 "Coatings & Linings".
C oa tin
Appendix D D103 Page 12 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
GPK Products, Inc. N/A N/A N/A N/A Harrington Corporation (HARCO) N/A N/A N/A N/A Multi Fittings Corp. N/A N/A N/A N/A JM Eagle N/A N/A N/A N/A Plastic Trends Inc N/A N/A N/A N/A TIGRE USA, Inc. N/A N/A N/A N/A
Maxadapter N/A N/A N/A N/A Universal Shielded Sewer coupling 6"-12"
EJ N/A N/A N/A N/A 08107127A01
Neenah Foundry N/A N/A N/A N/A R-1225 USF Fabrication Inc. N/A N/A N/A N/A USF 225-AS
Halliday Products N/A N/A N/A N/A S1R or S2R Series USF Fabrication Inc. N/A N/A N/A N/A APS or APD Series EJ N/A N/A N/A N/A CLS Series
Allied Precast N/A N/A N/A N/A Dyed Admix Atlantic Concrete Products, Inc. N/A N/A N/A N/A Dyed Admix Delzotto Products, Inc. N/A N/A N/A N/A Dyed Admix Forterra Pipe & Precast N/A N/A N/A N/A Dyed Admix Mack Concrete N/A N/A N/A N/A Dyed Admix Oldcastle Precast N/A N/A N/A N/A Dyed Admix Standard Precast Inc. N/A N/A N/A N/A Dyed Admix
N/A N/A N/A N/A Xypex Admix C-1000 Red 3.0 - 3.5% N/A N/A N/A N/A Xypex Admix C-500 NF Red 2.0 - 2.5%
Master Builders Solutions N/A N/A N/A N/A MasterLife 300D Red 2.5 - 3.0%
PV
C
P ip e an d fit tin gs
Pr ec as t C on cr et e
St ru ct ur es
Precast Manhole and Wetwell Structures ASTM C478. Precast concrete shall be batched with integral colorant crystalline waterproofing admixture with corrosion resistance. Concrete without admixture or without color tint /tracer shall be rejected. Minimum wall thickness shall be 6”.
C on cr et e A dm ix
SDR26/SDR35 Gasketed sewer fittings
G ra vi ty
Pi
Tr si tio n Connectors and Transitions for differential pipe.
Crystalline Waterproofing Concrete Admix with color dye shall be added to all concrete structures (precast and cast-in-place) to provide waterproofing and corrosion resistance.
Concrete without admixture or without color tint / tracer shall be rejected. % concentration of admix with “RED” colored dye added to the mix shall be based on weight of cement.
Xypex Chemical Corp
M H
L id s Frame and Cover
H at ch es
Wet Well Access Frames and Covers (Include the term "Confined Space" etched or cast into the cover with recessed lock & hasp. Frames and covers per manufacturers’ specifications.
(6’ wet well hatch shall encompass entire top)
Pr ec as t C on cr et e
St ru ct ur es Fi tti ng s S D
R
6/
Fittings, Adapters and Plugs - Gravity PVC ASTM-D3034, Min SDR26 / SDR 35 SDR26/SDR35 Gasketed sewer fittings SDR26/SDR35 Gasketed sewer fittings SDR26/SDR35 Trench Tough sewer fittings SDR26/SDR35 Gasketed sewer fittings SDR26/SDR35 Gasketed sewer fittings
Appendix D D103 Page 13 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
AFE N/A N/A N/A N/A Fiberglass Liner
AGRU Liner N/A N/A N/A N/A HDPE Liner (Min 2 mm for Manhole / Min 5 mm for Pump Station)
Containment Solutions Inc. (Flowtite) N/A N/A N/A N/A Fiberglass Liner
GSE Studliner N/A N/A N/A N/A HDPE Liner (Min 2 mm for Manhole / Min 5 mm for Pump Station)
L&F Manufacturing N/A N/A N/A N/A Fiberglass Liner
Canusa-CPS N/A N/A N/A N/A Wrapid Seal with WrapidSeal Primer (Canusa G Primer )
GPT N/A N/A N/A N/A Riser Wrap with Polyken 1027 or 1039 primer
Henry Company N/A N/A N/A N/A Ram-Nek RN100 Series Martin Asphalt Company / Del Zotto Products N/A N/A N/A N/A Evergrip 990
Trelleborg Pipe Seals N/A N/A N/A N/A NPC – Bidco C-56 ConSeal, Concrete Sealants Inc. N/A N/A N/A N/A CS-102 Joint Sealant
H ea t S hr in k
Se al
Heat Shrink Seal - Precast structures shall be primed with manufacturer approved primer prior to application of heat shrunk encapsulation.
Jointing Material Min. 2" width for all products to ensure squeeze out with manufacturer approved primer.
Li ne rs Jo in tin g M at er ia l
Pr ec as t C on cr et e
St ru ct ur es
Interior Liner for new or existing Precast Manhole and Precast Wetwell Structures per Section 3119 "Coatings & Linings"
Appendix D D103 Page 14 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Atlantic Concrete N/A N/A N/A N/A A-Lok STM (cast-in-place) Vertex, Inc N/A N/A N/A N/A Star Seal (cast-in-place) IPS N/A N/A N/A N/A Wedge Style NPC / Trelleborg N/A N/A N/A N/A Kor-N-Seal Model WS Press-Seal Corporation N/A N/A N/A N/A PSX Direct Drive
Atlantic Concrete N/A N/A N/A N/A A-Lok, STM Press-Seal Corporation N/A N/A N/A N/A Cast-A-Seal 12-08 Vertex, Inc N/A N/A N/A N/A Star Seal
CCI Pipeline Systems N/A N/A N/A N/A Wrap-It Link WL-SS Series Pipeline Seal & Insulator, Inc / Link Seal N/A N/A N/A N/A Link-Seal S-316 Modular Seal
Proco Products, Inc N/A N/A N/A N/A PenSeal ES-PS Series
Modular Pipe Seals for Wetwell penetrations and for all forcemain connections to existing and new precast concrete structures. EPDM Rubber with 316 SS HardwarePr ec as t C on cr et e
St ru ct ur es
C as t i n
Pl ac e Pi pe S ea ls
M an ho le
G ra vi ty
R es ili en t C on ne ct or
Pi
S ea ls . M an ho le
G ra vi ty
Resilient Connector Pipe Seals, Manhole - Gravity less than 12-inch and less than 15-ft deep
Cast in Place Pipe Seals, Manhole - Gravity Greater Than or Equal to 12-inch and all pipe sizes greater than 15-ft deep
M od ul ar
P ip e Se al s.
W et w el l, M an ho le
Fo rc em ai n
Appendix D D103 Page 15 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Caterpillar N/A N/A N/A N/A CAT Diesel Generator Set Cummins Power Generation N/A N/A N/A N/A Diesel Generator Set
Modern Welding N/A N/A N/A N/A Fireguard UL-2085 Phoenix N/A N/A N/A N/A Envirovault UL-2085 Envirosafe N/A N/A N/A N/A Fireguard UL-2085
Cooper Crouse-Hinds N/A N/A N/A N/A AR2042 (230V, 200A, 3P, 4W) With AJA1 Angle Adaptor
Cooper Crouse-Hinds N/A N/A N/A N/A AR2042-S22 (460V, 200A, 3P, 4W)
With AJA1 Angle Adaptor
Pyle National N/A N/A N/A N/A JRE-4100 (230V, 100A, 3P, 4W)
Russelectric N/A N/A N/A N/A RMTD Series with model 2000 controller
NEMA 12/3R
316SS Enclosure
BioAir N/A N/A N/A N/A EcoPure® Bio Trickling Filter Biorem N/A N/A N/A N/A Biosorbens BTF
Calgon N/A N/A N/A N/A Pure Air Filtration N/A N/A N/A N/A Evoqua N/A N/A N/A N/A
Perry Fiberglass Products, Inc. N/A N/A N/A N/A Perry Fiberglass H (horizontal) and V (vertical) series
Grease Filter / Mist Eliminator Units
G en er at or
G R
Generator Receptacle (GR)
A
TS
Generator Transfer Switch
O do r C on tr ol U ni ts
C ar bo n
A ds or pt io n
U ni ts
Carbon Adsorption Units
G en er at or Generator Systems, Fixed Shall be UL 2200 Certified. Monitoring equipment shall be Pneumercator, Veeder-Root, or Omntec only.
Fu el
T an ks Generator Fuel Tanks. Shall be UL2085 certified and Fireguard rated.
G re as e
Fi lte r /
M is t El im in at or
B io tri ck lin g
Fi lte rs Biotrickling filters
Appendix D D103 Page 16 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Ametek 375 AG375FB0100GLSVX40FT N/A N/A N/A N/A
ABB N/A N/A N/A N/A AB 266HRHPRRA
Siemens P200
7MF1565-4BG00-5GD1NA N/A N/A 7MF 4033 / 7MF4860
ABS N/A N/A N/A N/A
Flygt N/A N/A N/A N/A
Anchor Scientific N/A N/A N/A N/A Roto-Float
Sitrans LR560 Quadplex and above
Sitrans LR120 Duplex and Triplex
Pulsar N/A N/A N/A N/A DBI10 Duplex and Triplex
Square D N/A N/A N/A N/A
Current Technology (Power & Systems Innovations) N/A N/A N/A N/A
Josyln AKA (Total Protection Solutions) N/A N/A N/A N/A
Surge Suppressors, Inc N/A N/A N/A N/A
Hoffman N/A N/A N/A N/A Schaefer N/A N/A N/A N/A Universal enclosure systems N/A N/A N/A N/A
LSE Series or SHL Series
Su b
Pa ne l
Su b
Pa ne l Sub-Panel Enclosure - NEMA 12/3R Enclosure 316SS, white polyester powder coated finish inside and out, with 3 Point Pad lockable Handle, and Door Stop
N/A N/A
Pu m p St at io n M ai n
Se rv ic e
M ai n Se rv ic e D is co nn ec t
Main Service Disconnect Breaker
H or J Frame 3 Pole 600 Volt (HGL or JGL determined by amperage)
Su rg e Pr ot ec to r
D ev ic e Surge Protector - UL 1449, 3rd Edition listed and labeled, minimum 10 year warranty, NEMA LS-1 and IEEEC62, 41/45 tested with NEMA 4X enclosure, internal fusing, voltage and phase to match service. Rated 80,000 amps per mode for Duplex & Triplex stations and 150,000 Amperes per mode for Master Stations. All devices shall be provided with a NEMA 4X Plastic enclosure which is approved in lieu of stainless steel.
XN-80, TG-150 or CurrentGuard 150 Plus Series TSS-ST 160 Series, ST 300 Series or JSP-300 Series
Pu m ps
Pu m ps
Submersible Pumps
Fl oa ts Float Regulator (FR) - Duplex and Triplex Pump Stations
Le ve l T ra ns du ce r Level Transducer
Siemens N/A N/A
Pr es su re
T ra ns m itt er
Pr es su re
Tr sm itt er
Pressure Transmitter
Appendix D D103 Page 17 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
ECS N/A N/A N/A N/A
Sta-Con Inc N/A N/A N/A N/A
Hoffman N/A N/A N/A N/A Schaefer N/A N/A N/A N/A Universal enclosure systems N/A N/A N/A N/A
Unistrut Stainless Steel N/A N/A N/A N/A 1" 5/8 x 1" 5/8 316 SS
Cooper Crouse-Hinds N/A N/A N/A N/A EYSR
MPE N/A N/A N/A N/A 025-120-105
SSAC N/A N/A N/A N/A FS-126
Federal Signal N/A N/A N/A N/A 141ST-120-R
Wheelock N/A N/A N/A N/A 3IT-115-R
Bussmann N/A N/A N/A N/A FNQ-R or KTK-R
Square D N/A N/A N/A N/A 9001-SKS43B
Square D N/A N/A N/A N/A 9001-SKR1RH5
Square D N/A N/A N/A N/A S29354
H SS Horn Silence Button (HSS)
In te r-lo ck Mechanical Interlock
Fu se Fuses (F)
H O
A Hand-Auto-Off Selector (HOA)
A H Alarm Horn (AH)
Mounting Channel for Enclosures
Se al of f
Explosion-Proof Sealoff
FL
Flasher (FL)
A L Alarm Light / With Base and Globe (AL)
SC
A
D
C on tro l
Pa ne l SCADA &Control Panel Supplier
Pu m p St at io n C on tr ol P an el
En cl os ur e Enclosure - NEMA 12/3R Enclosure 316SS, white polyester powder coated finish inside and out, with 3 Point Pad lockable Handle, and Door Stop
M nt
Appendix D D103 Page 18 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Square D N/A N/A N/A N/A H or J Frame 3 Pole 600 Volt (HGL or JGL determined by amperage)
Square D N/A N/A N/A N/A H or J Frame 3 Pole 600 Volt (HGL or JGL determined by amperage)
Square D N/A N/A N/A N/A H or J Frame 3 Pole 600 Volt (HGL or JGL determined by amperage)
Square D N/A N/A N/A N/A QOU120
Square D N/A N/A N/A N/A Type S Class 8536 or IEC
Square D N/A N/A N/A N/A
Square D N/A N/A N/A N/A 9066-RA1
Square D N/A N/A N/A N/A 9070TF75D23 120/24 Volt .075
KVA
Square D N/A N/A N/A N/A 9070T2000D1 480/120 2KVA
Square D N/A N/A N/A N/A Mini power zone, 316 SS
Square D N/A N/A N/A N/A MG24532
Square D N/A N/A N/A N/A 9001 SKS11B
SP
B Supplemental Protector Breaker - 3 pole, 1-amp for Phase Monitor
Sw itc h Control Panel Lighting, 2 position switch
Tr an sf or m er
Control Circuit Transformer (XMFR)
Main Circuit Transformer (MCT)
Combination Transformer and Panel
Control Circuit Breaker / GFCI Receptacle Breaker / SCADA Breaker
M S Motor Starter (MS)
O R Overload Reset
B re ak er s
Control Panel Main Circuit Breaker (MCB) With S29450 Circuit Breaker Auxiliary Switch
Emergency Circuit Breaker (ECB) With S29450 Circuit Breaker Auxiliary Switch
O L Overload Heater(OL)
Part number will vary with size needed
Motor Circuit Breaker (MB)
Pu m p St at io n C on tr ol P an el
Appendix D D103 Page 19 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
MPE 240 & 480V. N/A N/A N/A N/A 001-DVM-118-ORCO
Diversified Duplex N/A N/A N/A N/A ARB-120-ACA Diversified Triplex N/A N/A N/A N/A ARA-120-AME MPE Duplex N/A N/A N/A N/A 008-120-13SP MPE Triplex N/A N/A N/A N/A 009-120-23P MPE Triplex Socket N/A N/A N/A N/A SD-12-PC
Carling Technologies N/A N/A N/A N/A 6GG5E-78 Honeywell N/A N/A N/A N/A 2TL1-50
Potter Brumfield 24 Volt N/A N/A N/A N/A KRPA-11AN-24 Potter Brumfield 120 Volt N/A N/A N/A N/A KRPA-11AN-120 Square D 24 Volt N/A N/A N/A N/A 8501KP12P14V14 Square D 120Volt N/A N/A N/A N/A 8501KP12P14V20
IEDC 8 Pin Relay Base 600 Volt N/A N/A N/A N/A SR2P-06
Hubbell N/A N/A N/A N/A GFTR20BK Pass & Seymour N/A N/A N/A N/A 2095TRBK
Reddington N/A N/A N/A N/A 711-0160
Marathon N/A N/A N/A N/A Neutral Isolation Block 1421570
Panduit N/A N/A N/A N/A Ground Lug LAM2A 1/0 - 014 - 6Y
Square D N/A N/A N/A N/A Ground Buss PK7GTA
Marathon N/A N/A N/A N/A Series 200 Square D N/A N/A N/A N/A 9080GR6
D up le x
R ec ep ta cl e
/ G
FC
I Duplex Receptacle/GFCI (DR) Upgraded to 20 Amp
R ay
B as e Relay Base
TS
Terminal Strip (TS)
Pu m p A lte rn at or
Pump Automatic Alternator (PAA)
ET
M Elapse Time Meter (ETM)
G ro un di ng
Grounding System
A lt.
T es t Sw itc h Alt. Test Switch
R el ay
Relay
PM
Phase Monitor (PM)
Pu m p St at io n C on tr ol P an
Appendix D D103 Page 20 of 21 October 10, 2021
Appendix D
C at
. Water Reclaimed Water
LIST OF APPROVED PRODUCTS - TRANSMISSION SYSTEMS
Wastewater
Revised: October 10, 2021
Square D N/A N/A N/A N/A 9080GM6B & 9080GH10
IDEC N/A N/A N/A N/A APP22M-2Q4A
IDEC N/A N/A N/A N/A APP22M-2QHG
IDEC N/A N/A N/A N/A APP22M-2Q4R
Rodney Hunt N/A N/A N/A N/A Series A - 113 SS Fontaine N/A N/A N/A N/A Model 20 - 316 SS
Square D N/A N/A N/A N/A
Below 25 HP – Altistart 22 25 HP and above – Altistart 48So ft S ta rt s
So ft
St ar ts
Soft Starts
Square D N/A N/A N/A N/A
Sl ui ce
Sl ui ce G at e Sluice Gate for Wet Well with Motorized Operator
V
FD
V
FD
Variable Frequency Drives
PL
Pilot Light (PL) 24 Volt
R L Run Indicator Light (RL) 120 Volt
M T Moisture and Temperature Failure Light (MT) 120 Volt with 120MB Bulb
TS
Terminal Strip End Blocks and End Clamps
Pu m p St at io n C on tr ol P an
Appendix D D103 Page 21 of 21 October 10, 2021
File details come from the government source that posted it. Updated .