Lamar EV Charging - Documented Quote - Appendix G - Construction Drawings.pdf

PDF 2 MB Posted

Attached to
Lamar Electrical Vehicle Charging Electrical Connection
Solicitation number
0002
Issued by
Pitkin County, Colorado

About this file

These construction drawings are for the Lamar EV Station project by the Colorado Department of Transportation (CDOT), located at 2402 S. Main St. in Lamar, Colorado. The project involves installing electrical infrastructure for two new electric vehicle charging stations, specifically two ChargePoint CP6011X-80A-L7 dual-port chargers. The electrical scope includes providing a new 240/120V, 600A, single-phase panelboard (L1), a CT cabinet, conduit, wiring, and associated equipment. The design is prepared by Farnsworth Group and dated 12/18/2023, with the electrical design following the 2021 IBC, 2017 ICC A117.1, 2021 IFC, and 2023 NEC codes.

The electrical design includes a new 100kVA utility transformer, a NEMA 3R panelboard, and detailed specifications for conduit routing, equipment mounting, and electrical connections. The site plan shows the proposed locations for the transformer, meter, CT cabinet, panelboard, and EV charging stations, with specific notes about underground conduit routing, bollard protection, and coordination requirements with Lamar Light and Power utility. The one-line diagram and electrical site plan provide technical details about the electrical infrastructure, including short circuit calculations, feeder schedules, and equipment specifications to support the EV charging station installation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

arnswor

GROUP

COOT

2402 S. MAIN ST, LAMAR, CO 80152

INDEX OF DRAWINGS

ELECTRICAL

SHEET NUMBER SHEET TITLE

E0.1 ELECTRICAL SYMBOLS

E0.2

GENERAL NOTES AND

ABBREVIATIONS

ESl.1 ELECTRICAL SITE PLAN

E2.0

SCHEDULE AND

ONE-LINE

Project No: 0190216.16

I

LOCATION MAP

ENGINEER/DESIGNER INFORMATION

FARNSWORTH GROUP

5613 DTC PARKWAY, SUITE 1100

GREENWOOD VILLAGE, COLORADO 80111

(303) 692-8838 I info@f-w.com

UTILITY CONTACTS

LAMAR LIGHT AND POWER

100 N. 2ND ST.

LAMAR, CO 81052

HOUSSIN HOURIEH

(719) 336-7456

OWNER INFORMATION

CDOT LAMAR

2402 S. MAIN ST, LAMAR, CO 80152

Date: 12/18/2023

PARCEL NO. 0000084851

SCOPE OF PROJECT: SCOPE IS LIMITED TO PROVIDING PANEL, CONDUIT,

WIRING, AND EQUIPMENT FOR NEW EV CHARGING STATION. PROPOSED

CHARGER IS CHARGEPOINT CP6011X-80A-L7, 80A DUAL PORT, PEDESTAL

MOUNT, 23 FT CABLE.

APPLICABLE CODES: 2021 IBC, 2017 ICC A117.1, 2021 IFC, & 2023 NEC

chenerykm Rectangle chenerykm Rectangle

REVIEWED:

DESIGNED:

DRAWN:

SHEET TITLE:

SHEET NUMBER:

FIELD BOOK NO.:

ELECTRICAL

SYMBOLS

E0.1

MP/IM

MP

AC

PROJECT:

DATE:

PROJECT NO.:

CDOT

LAMAR EV STATION

2402 S. Main St, Lamar, CO 80152

12/18/2023

0190216.16

DESCRIPTION:DATE:#

ISSUE:

NOT FOR CONSTRUCTION

99% CODE REVIEW

GROUP

www.f-w.com Engineers | Architects | Surveyors | Scientists

5613 DTC PARKWAY, SUITE 1100

GREENWOOD VILLAGE, COLORADO 80111

(303) 692-8838 / info@f-w.com

1 12/18/2023 PLAN REVIEW REPORT RESPONSE

CONDUIT - CAPPED

CABLE TRAY

SEALING FITTING

EXPANSION FITTING

CONDUIT FITTING (CONDULET)

JUNCTION BOX

CONDUIT - FLEXIBLE

SPECIAL PURPOSE RECEPTACLE - FLOOR MOUNTED

SPECIAL PURPOSE RECEPTACLE - CEILING MOUNTED

SPECIAL PURPOSE RECEPTACLE - MOUNTED 18" AFF

CEILING FAN

QUADRUPLEX RECEPTACLE - FLOOR MOUNTED

DUPLEX RECEPTACLE - FLUSH FLOOR MOUNTED

SINGLE RECEPTACLE - MOUNTED 18" AFF

QUADRUPLEX RECEPTACLE - MOUNTED 18" AFF

CONDUIT - CONTINUED

CONDUIT - TURNING UP

CONDUIT - EXPOSED

CONDUIT - TURNING DOWN

REVISION CALL-OUT

ROOM NUMBER

FEEDER CALL-OUT

KEYED NOTE

GENERAL SYMBOLS

UTILITY KILOWATT-HOUR METER

DUPLEX RECEPTACLE - EMERGENCY POWER - MOUNTED 18" AFF

DUPLEX RECEPTACLE - CEILING MOUNTED

DUPLEX RECEPTACLE - SPLIT WIRED - MOUNTED 18" AFF

DUPLEX RECEPTACLE - MOUNTED 6" ABOVE COUNTER

DUPLEX RECEPTACLE (NEMA 5-20R) - MOUNTED 18" AFF

MAGNETIC STARTER

COMBINATION STARTER

SAFETY SWITCH - FUSIBLE

SAFETY SWITCH - NON-FUSIBLE

EQUIPMENT - MOTOR

BRANCH CIRCUIT PANELBOARD - FLUSH MOUNTED

DISTRIBUTION PANELBOARD OR SWITCHBOARD

MOTOR CONTROL CENTER

BRANCH CIRCUIT PANELBOARD - SURFACE MOUNTED

T

CONTROL PANEL

TRANSFORMER

POWER SYMBOLS

COMPUTER OUTLET - CEILING MOUNTED

COMPUTER OUTLET - FLOOR MOUNTED

COMPUTER OUTLET - WALL MOUNTED 18" AFF

TELEPHONE OUTLET - CEILING MOUNTED

TELEPHONE OUTLET - FLOOR MOUNTED

TELEPHONE OUTLET - WALL MOUNTED

TELEPHONE TERMINAL BACKBOARD (PROVIDE WITH 3/4"

FIRERATED PLYWOOD)

JUNCTION BOX - EMERGENCY POWER

FOOD SERVICE EQUIPMENT DESIGNATION

TTB

HAND DRYER

WIRING AND CONDUITS

NEW EQUIPMENT (TYPICAL)

EXISTING EQUIPMENT (TYPICAL)

DEMOLITION EQUIPMENT (TYPICAL)

PUSH BUTTON

WALL MOUNT BRACKET (TYPICAL)

ABOVE COUNTER COMMUNICATIONS OUTLET

ABOVE COUNTER DATA OUTLET

ABOVE COUNTER TELEPHONE OUTLET

AHU

J

J

B

M

F

H

VFD

GWH1

MECHANICAL EQUIPMENT CALL-OUT: REFER TO

THE EQUIPMENT DATA SCHEDULE FOR DETAILS

PLUMBING EQUIPMENT CALL-OUT: REFER TO THE

EQUIPMENT DATA SCHEDULE FOR DETAILS

###A#G

AC

AC

AC

COMBINATION TELEPHONE/DATA OUTLET -

WALL MOUNTED 18" A.F.F

COMBINATION TELEPHONE/DATA OUTLET -

FLOOR MOUNTED

COMBINATION TELEPHONE/DATA OUTLET -

CEILING MOUNTED

COMMUNICATIONS SYMBOLS (FOR ROUGH-IN ONLY

WITH 1"CONDUIT TO ACCESSIBLE CEILING)

CONDUIT - UP AND DOWN

(CHANGE IN ELEVATION)

CONDUIT - CONCEALED BELOW

SLAB OR GRADE

CONDUIT - CONCEALED IN

SUSPENDED CEILING OR WALL

T POLE MOUNTED TRANSFORMER

GROUND BAR

AC

QUADRUPLEX RECEPTACLE - MOUNTED 6" ABOVE COUNTER

AC

J FLOOR BOX - SEE SPECS OR KEYED NOTES ON PLAN

FOR DETAILS

PP

POWER POLE

ONE-LINE DIAGRAM SYMBOLS

SERVICE DROP

PANEL

### PANELBOARD

T-1

45 KVA 3Ø

208Y/120VAC

G # KVA/KW

480Y/277V, 3Ø, 4W

DELTA-WYE TRANSFORMER

GENERATOR

# A

# POLES

AUTOMATIC TRANSFER SWITCH

GROUND

# AF

# AT CIRCUIT BREAKER

# AF

# AT

DRAWOUT CIRCUIT BREAKER

METER

CURRENT TRANSFORMER

M # A

POTENTIAL TRANSFORMER

G

ST

GROUND FAULT PROTECTED BREAKER

SHUNT TRIP BREAKER

# A SWITCH

FUSE

CONTACTOR

SPD

VFD

DPM

K

THERMAL OVERLOAD

ELECTRONIC OVERLOAD

SURGE PROTECTION DEVICE

VARIABLE FREQUENCY DRIVE

KIRK KEY INTERLOCK

DIGITAL POWER METER

WIFI WIRELESS ACCESS POINT

GFI GROUND FAULT CIRCUIT INTERRUPTER

SS SURGE SUPPRESSOR (ISOLATED GROUND TYPE)

WP WEATHERPROOF

H HOSTPITAL GRADE

TP TAMPER PROOF

D DEDICATED

USB STANDARD DUPLEX WITH 2 USB PORTS

VFD VARIABLE FREQUENCY DRIVE

- WALL MOUNTED 18" AFF

T TOUCH TONE DEVICE FOR THE DEAF

W WALL PHONE (MOUNTED 54" AFF)

D DEDICATED TELEPHONE OUTLET

QUADRUPLEX RECEPTACLE - CEILING MOUNTED

SYMBOLS LEGEND

NOTE: NOT ALL SYMBOLS ARE USED IN CONSTRUCTION DOCUMENTS.

http://www.f-w.com

DRAWN:

SHEET TITLE:

SHEET NUMBER:

FIELD BOOK NO.:

GENERAL NOTES

AND ABBREVIATIONS

E0.2

MP/IM

MP

AC

PROJECT:

DATE:

PROJECT NO.:

CDOT

LAMAR EV STATION

2402 S. Main St, Lamar, CO 80152

12/18/2023

0190216.16

DESCRIPTION:DATE:#

ISSUE:

NOT FOR CONSTRUCTION

99% CODE REVIEW

GROUP

www.f-w.com Engineers | Architects | Surveyors | Scientists

5613 DTC PARKWAY, SUITE 1100

GREENWOOD VILLAGE, COLORADO 80111

(303) 692-8838 / info@f-w.com

1 12/18/2023 PLAN REVIEW REPORT RESPONSE

(E) EXISTING (ALSO COVERED BY TEXT

WEIGHT)

(F) FUTURE

(PART) PARTIAL CIRCUIT

(R) RELOCATE

2S1W TWO SPEED, SINGLE WINDING

2S2W TWO SPEED, DOUBLE WINDING

A AMPERES

AC 6" ABOVE COUNTER

ADA AMERICANS WITH DISABILITIES ACT

AF AMPERES FRAME

AFCI ARC FAULT CIRCUIT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERES INTERRUPTING CAPACITY

AL ALUMINUM

AT AMPERES TRIP

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAM CAMERA

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CCW COUNTER CLOCKWISE

CKT CIRCUIT

CL CENTER LINE

CLG CEILING

CO CONDUIT ONLY

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CU COPPER

CW CLOCKWISE

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DPDT DOUBLE POLE DOUBLE THROW

DPST DOUBLE POLE SINGLE THROW

DR DUPLEX RECEPTACLE

DWG DRAWING(S)

EC ELECTRICAL CONTRACTOR

ELC ELEVATOR CONTRACTOR

ELEC ELECTRIC/ELECTRICAL

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXP EXPLOSION PROOF

F FUSED

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FLA FULL LOAD AMPERES

FMC FLEXIBLE METAL CONDUIT

FO FIBER OPTIC

FPC FIRE PROTECTION CONTRACTOR

FS FUSED SWITCH

FSD FIRE/SMOKE DAMPER

FT FOOT/FEET

FVNR FULL VOLTAGE, NON-REVERSING

FVR FULL VOLTAGE, REVERSING

G GROUND

GC GENERAL CONTRACTOR

GEN GENERATOR

GF GROUND FAULT

GFI/GFCI GROUND FAULT INTERRUPTER

GND GROUND/GROUNDING

H HORIZONTALLY MOUNTED

HH HANDHOLE

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTO

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HZ FREQUENCY

I/O INPUT/OUTPUT

IC INTERRUPTING CAPACITY

ID INSIDE DIAMETER

IDF INTERMEDIATE DISTRIBUTION FRAME

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

JB JUNCTION BOX

K KELVIN (COLOR TEMPERATURE)

KCMIL THOUSAND CIRCULAR MILS

KV KILOVOLTS

KVA KILOVOLT-AMPERES

KW KILOWATTS

KWH KILOWATT-HOUR

LAN LOCAL AREA NETWORK

LC LIGHTING CONTACTOR

LCP LIGHTING CONTROL PANEL

LED LIGHT EMITTING DIODE

LF LINEAR FOOT

LFMC LIQUID-TIGHT FLEXIBLE METAL

CONDUIT

LM LUMEN

LTG LIGHTING

LV LOW VOLTAGE

MAN MANUAL MOTOR STARTER WITH

OVERLOADS

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPERES

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MDF MAIN DISTRIBUTION FRAME

MDP MAIN DISTRIBUTION PANEL

MEPFP MECHANICAL, ELECTRICAL, PLUMBING,

FIRE PROTECTION

MGB MASTER GROUND BAR

MH MANHOLE

MH METAL HALIDE

MIN MINIMUM

MLO MAIN LUG ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MSB MAIN SWITCHBOARD

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MVA MEGAVOLT-AMPERES

MW MEGAWATTS

MWH MEGAWATT-HOURS

N NEUTRAL

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NF NONFUSED

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NP NAMEPLATE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OWN OWNER

P POLE

PA PUBLIC ADDRESS

PB PULL BOX

PC PHOTOCELL

PC PLUMBING CONTRACTOR

PDT PASSIVE DUAL TECHNOLOGY

PF POWER FACTOR

PH PHASE

PIR PASSIVE INFRARED

PLC PROGRAMMABLE LOGIC CONTROLLER

PNL PANEL

PR PAIR

PRI PRIMARY

PT POTENTIAL TRANSFORMER

PV PHOTOVOLTAIC

PVC POLYVINYL CHLORIDE

PWC PRE-WIRED CONTROLS

PWR POWER

RCPT RECEPTACLE

REQD REQUIRED

RF RADIO FREQUENCY

RM ROOM

RMC RIGID METAL CONDUIT

RNC RIGID NON-METALLIC CONDUIT (SCH 40)

RVAT REDUCED VOLTAGE -

AUTOTRANSFORMER

SC SHORT CIRCUIT

SCC SHORT CIRCUIT CURRENT RATING

SDP SUBDISTRIBUTION PANEL

SEC SECONDARY

SHLD SHIELD(ED) (AS IN CABLE)

SHT SHEET

SPD SURGE-PROTECTIVE DEVICE

SPDT SINGLE POLE DOUBLE THROW

SPST SINGLE POLE SINGLE THROW

SR SINGLE RECEPTACLE

ST SHUNT TRIP

SW MOTOR RATED SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TBD TO BE DETERMINED

TC TIMECLOCK

TCC TEMPERATURE CONTROLS

CONTRACTOR

TEMP TEMPERATURE

TT THERMAL TRIP SWITCH

TTB TELEPHONE TERMINAL BOARD

TYP TYPICAL

U UTILITY

UG UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERUPTABLE POWER SUPPLY

V VOLTS

VA VOLT-AMPERES

VAC VOLTS ALTERNATING CURRENT

VDC VOLTS DIRECT CURRENT

VFD VARIABLE FREQUENCY DRIVE

VND VENDOR

W WATTS

W WIRE

WHM WATTHOUR METER

WP WEATHERPROOF

XFMR TRANSFORMER

XP EXPLOSION PROOF

Z IMPEDANCE

ABBREVIATIONSGENERAL NOTES

GENERAL NOTES:

A. PRIOR TO ROUGH-IN AND FINAL CONNECTION, VERIFY ELECTRICAL REQUIREMENTS AND EXACT LOCATION OF EQUIPMENT BEING PROVIDED BY OTHER TRADES. REFERENCE ENTIRE SET OF CONSTRUCTION DOCUMENTS AS

WELL AS FINALIZED SHOP DRAWINGS.

B. COORDINATE SCHEDULE OF CONSTRUCTION WITH THE OWNER, OTHER TRADES AND UTILITIES INVOLVED BEFORE TRENCHING AND INSTALLATION OF UNDERGROUND CONDUIT. USE EXTREME CAUTION DURING EXCAVATION TO LOCATE EXISTING UNDERGROUND PIPING, CONDUITS, ETC. LOCATE AND PROTECT ANY BURIED UTILITIES IN AREAS

OF EXCAVATION.

C. DRAWINGS SHOW EXISTING CONDITIONS OF THE SITE. AN ATTEMPT HAS BEEN MADE TO SHOW EXISTING BUILDING, SITE DETAILS, ETC., BUT ACCURACY CANNOT BE GUARANTEED. VERIFY EXACT LOCATIONS OF ALL CIRCUITS, CONDUITS, PIPING, EQUIPMENT, ETC. VERIFY ALL SITE AND BUILDING DETAILS.

D. THE ELECTRICAL CONTRACTOR SHALL BE HELD FINANCIALLY RESPONSIBLE FOR ANY AND ALL COSTS OF THE ENGINEERS TIME REQUIRED TO REVIEW AND RESEARCH NON-SPECIFIED EQUIPMENT SUBMITTED FOR SUBSTITUTION BY THE ELECTRICAL CONTRACTOR. THESE COSTS SHALL BE AUTOMATICALLY INVOICED TO THE CONTRACTOR UNLESS SUCH SUBSTITUTIONS FOLLOW THE GUIDELINES FOR SUBSTITUTION AND ARE WITHIN THE PROPER TIME

FRAME AS OUTLINED IN OTHER SECTIONS OF THIS SPECIFICATION.

E. PROVIDE AND INSTALL IN EACH PANEL, TYPEWRITTEN NEAT TWO-COLUMN CIRCUIT INDEX CARD SET UNDER PLASTIC COVERS ON INSIDE OF DOORS. EACH ODD-NUMBERED CIRCUIT SHALL BE IN SEQUENCE ON ONE COLUMN AND THE EVEN-NUMBERED CIRCUITS ON THE OTHER COLUMN (E.G. 1,3,5...,2,4,6...). EACH CIRCUIT SHALL BE IDENTIFIED AS TO THE USE AND ROOM NAME(S) OR AREA(S). THE CONTRACTOR SHALL CONFIRM ROOM NAMES AND/OR ROOM

NUMBERS WITH THE ARCHITECT PRIOR TO PROJECT COMPLETION.

F. PRIOR TO SUBMITTING BID PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS AND VISIT CONSTRUCTION SITE TO BE FAMILIAR WITH EXISTING CONDITIONS UNDER WHICH HE WILL HAVE TO OPERATE AND WHICH WILL IN ANY WAY AFFECT THE WORK UNDER THIS CONTRACT. NO SUBSEQUENT ALLOWANCE WILL BE MADE IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR FOR ANY ERROR OR NEGLIGENCE ON HIS PART.

G. UNLESS INDICATED IN SOME MANNER THAT ELECTRICAL EQUIPMENT IS EXISTING, ALL EQUIPMENT SHALL BE NEW.

H. CONTRACTOR SHALL NOT SCALE DRAWING FOR QUANTITIES. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING

ALL MEASUREMENTS.

I. WHERE CONDUIT AND WIRING RUNS ARE NOT SHOWN ON FLOOR PLANS, THE CONTRACTOR SHALL DETERMINE AND PROVIDE THE REQUIRED CONDUIT AND WIRING FOR SPECIFIED CIRCUITING IN ACCORDANCE WITH NEC AND THE

FOLLOWING MINIMUM REQUIREMENTS:

1. MINIMUM CONDUIT SIZE SHALL BE 3/4".

2. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG. #10 AWG SHALL BE USED FOR HOME RUNS OF 20 AMP BRANCH

CIRCUITS OVER 100 FEET IN LENGTH.

3. EACH RACEWAY SHALL CONTAIN AN INSULATED EQUIPMENT GROUNDING CONDUCTOR PER NEC.

4. DERATING OF CONDUCTOR AMPACITY SHALL BE APPLIED PER NEC.

5. NO SHARING OF NEUTRALS ALLOWED. CIRCUIT SHALL HAVE DEDICATED NEUTRAL CONDUCTORS. ONE CIRCUIT, ONE NEUTRAL.

6. MAXIMUM SIX FOOT FLEXIBLE LUMINAIRE WHIP SHALL BE USED FOR FINAL CONNECTIONS TO LUMINAIRES

INSTALLED IN LAY-IN CEILINGS. MAXIMUM FOUR LUMINAIRE WHIPS SHALL BE CONNECTED FROM ONE JUNCTION

BOX. FEED THRU BETWEEN LUMINAIRES SHALL NOT BE ALLOWED.

J

J

T

M

PANELBOARD

L1L1-2

GFI

WP

CT CABINET

L1-1,3 L1-4,6

L1-5,7 L1-8,10

1'- 0"

5'- 0"

2"

FINISHED

GRADE

1'- 0"

FI

EL

D

VE

RI

FY

(T

YP

IC

AL

)6'- 3"

2" M

AX

(TYPICAL)

FIELD VERIFY

(TYPICAL)

METER

CT

CABINET PANEL

1.

2.

3.

4.

KEYNOTES:

3-INCH NOMINAL GALVANIZED STEEL SCHEDULE 40 PIPE OR RIGID

METAL CONDUIT SUPPORT POST. TYPICAL OF TWO. CLOSE OPEN

ENDS OF ALL POSTS WITH GALVANIZED STEEL CAP.

GALVANIZED PIPE/CONDUIT CLAMP P1119 OR P2558-35, TYPICAL.

TIGHTEN BOLTS TO MANUFACTURER'S RECOMMENDED TORQUE

VALUES.

18-INCH DIAMETER CONCRETE PIER, TYPICAL OF TWO.

SLOTTED-METAL CHANNEL, UNISTRUT P5000, AS REQUIRED TO

SUPPORT AND BRACE THE EQUIPMENT AND CONDUITS. ALL

SUPPORTS, FITTINGS, AND HARDWARE SHALL BE OF CORROSION-

RESISTANT MATERIAL OR PAINTED WITH A FACTORY APPLIED

CORROSION INHIBITING PAINT.

GFI SERVICE

RECEPTACLE

WITH

WEATHERPROOF

COVER

REVIEWED:

DESIGNED:

DRAWN:

SHEET TITLE:

SHEET NUMBER:

FIELD BOOK NO.:

ELECTRICAL SITE

PLAN

ES1.1

MP/IM

MP

AC

PROJECT:

DATE:

PROJECT NO.:

CDOT

LAMAR EV STATION

2402 S. Main St, Lamar, CO 80152

12/18/2023

0190216.16

DESCRIPTION:DATE:#

ISSUE:

NOT FOR CONSTRUCTION

99% CODE REVIEW

GROUP

www.f-w.com Engineers | Architects | Surveyors | Scientists

5613 DTC PARKWAY, SUITE 1100

GREENWOOD VILLAGE, COLORADO 80111

(303) 692-8838 / info@f-w.com

1 12/18/2023 PLAN REVIEW REPORT RESPONSE

U.S. SURVEY FEET

15 30 60

1 SCALE:

ELECTRICAL SITE PLAN

1"=30' NORTH

GENERAL NOTES

A. REFER TO ONE-LINE DIAGRAM (E2.0) FOR ADDITIONAL INFORMATION.

KEYNOTES

1. RUN CONDUIT UNDERGROUND AT A MINIMUM OF 24" BELOW GRADE FROM NEW

PANEL L1 LOCATION TO NEW EV CHARGING LOCATIONS. COORDINATE ROUTE WITH

OWNER ON THE FIELD.

2. APPROXIMATE LOCATION OF NEW EV CHARGING STATION. CONTRACTOR SHALL

VERIFY EXACT LOCATION WITH THE OWNER IN THE FIELD.

3. VERIFY NETWORK CONNECTIONS WITH OWNER. IF A WIRELESS CONNECTION IS NOT

AVAILABLE, PROVIDE 2" UNDERGROUND CONDUIT BETWEEN SERVICE POINT AND

STATION.

4. CONTRACTOR SHALL PROVIDE 4' IMPACT RESISTANT BOLLARD IN FRONT OF EV

STATION.

5. PROPOSED LOCATION OF NEW 240/120V SECONDARY UTILITY TRANSFORMER.

COORDINATE TRANSFORMER LOCATION WITH UTILITY COMPANY AND OWNER

PRIOR TO INSTALLATION.

6. PLACE METER, CT CABINET, AND PANEL ON UNISTRUT STRUCTURE. SEE DETAIL 2

ON SHEET ES1.1. CONTRACTOR SHALL PROVIDE 4' IMPACT RESISTANT BOLLARD TO

PROTECT ELECTRICAL EQUIPMENT.

7. RUN CONDUIT OVERHEAD FROM NEW UTILITY TRANSFORMER LOCATION TO NEW

METER, CT CABINET AND PANEL L1. COORDINATE ROUTE WITH OWNER ON THE

FIELD.

8. PLAQUE SHALL BE INSTALLED ON CHARGER DENOTING EXACT LOCATION OF PANEL

L1 WITH LOCKABLE DISCONNECTING MEANS PER NEC 625.43.

2 3

(TYP. 2)

2 SCALE:

PANELBOARD UNISTRUT MOUNTING

NOT TO SCALE

http://www.f-w.com chenerykm Stamp

DRAWN:

SHEET TITLE:

SHEET NUMBER:

FIELD BOOK NO.:

SCHEDULE AND

ONE-LINE

E2.0

MP/IM

MP

AC

PROJECT:

DATE:

PROJECT NO.:

CDOT

LAMAR EV STATION

2402 S. Main St, Lamar, CO 80152

12/18/2023

0190216.16

DESCRIPTION:DATE:#

ISSUE:

NOT FOR CONSTRUCTION

99% CODE REVIEW

GROUP

www.f-w.com Engineers | Architects | Surveyors | Scientists

5613 DTC PARKWAY, SUITE 1100

GREENWOOD VILLAGE, COLORADO 80111

(303) 692-8838 / info@f-w.com

1 12/18/2023 PLAN REVIEW REPORT RESPONSE

GENERAL NOTES

A. ONE-LINE DIAGRAM PREPARED BASED ON LIMITED SITE OBSERVATION. NOT ALL

EXISTING SYSTEM GROUNDING CONNECTIONS MAY EXIST.

NEW UTILITY

TRANSFORMER

240/120V XFMR 1PH

100KVA

1 SCALE:

ONE-LINE DIAGRAM

NOT TO SCALE

100A/2P 100A/2P

NEW PANELBOARD L1

240/120V, 600A, 1PH

NEMA 3R

NEW CT CABINET

NEMA 3R

N G

NEW 80A

CP6000 EV

CHARGER 1,

PORT1

600A/2P

MCB

100A/2P

100A2G 100A2G

NEW 80A

CP6000 EV

CHARGER 1,

PORT2

600A3

M 600A

U

100A2G

NEW 80A

CP6000 EV

CHARGER 2,

PORT1

100A/2P

100A2G

NEW 80A

CP6000 EV

CHARGER 2,

PORT2

FEEDER SCHEDULE

MARK CONDUIT & CONDUCTORS

(SEE NOTE 1)

REMARKS

100A2G 2#1, 1#8G, 1-1/4"C

600A3 2 SETS (3#350, 2-1/2"C)

REMARKS:

1. THIS FEEDER SCHEDULE IS BASED ON 60 DEGREE CENTIGRADE (TYPE TW) WIRE

AND TERMINATIONS FOR SIZES #12 TO #1, AND 75 DEGREE CENTIGRADE (TYPE

THHN/THWN) WIRE AND TERMINATIONS FOR SIZES #1/0 AND LARGER. UNLESS

NOTED OTHERWISE, CONDUIT IS SIZED BASED ON TYPE EMT CONDUIT. USE OF

OTHER CONDUIT TYPES REQUIRES RESIZING OF CONDUIT.

PANELBOARD L1

VOLTAGE: 240/120V CONNECTED LOAD PER

PHASE

ISOLATED GROUND BUS (Y/N): N

PHASE / WIRE: 1Ø / 3W BUSSING: SEE SPEC

RATED AMPERAGE: 600 A A B MOUNTING: SURFACE

MAIN: 600 A MCB MCB GROUND FAULT PROTECTION (Y/N): N

SCC RATING (SYM): 35 KA 38580 VA 38400 VA MCB SHUNT TRIP (Y/N): N

322 A 320 A MCB 100% RATED (Y/N): N

CKT IDENTIFICATION TYPE

BKR

SIZE POLES A B POLES BKR

SIZE

TYPE

(*) IDENTIFICATION CKT

1 CP6000 EV CHARGER 1 PORT 1 5 100A 2

9600 180 1 20A SERVICE RECEPT. 2

3 9600 9600

2 100A 5 CP6000 EV CHARGER 1 PORT 2 4

CP6000 EV CHARGER 2 PORT 1 5 100A 2

9600 9600 6 7 9600 9600

2 100A 5 CP6000 EV CHARGER 2 PORT 2

9 SPARE 20A 1 0 9600 10

11 SPARE 20A 1 0 0 1 20A SPARE 12

Load Classification Connected Load Demand Factor Demand Load PANEL TOTALS Lighting - Continuous 0 VA 125% 0 VA Receptacle - First 10 kVA 180 VA 100% 180 VA TOTAL CONNECTED LOAD: 76980 VA

Remainder 0 VA 50% 0 VA TOTAL DEMAND: 96180 VA Motor - Largest 0 VA 125% 0 VA TOTAL CONNECTED CURRENT: 321 A

Remainder 0 VA 100% 0 VA TOTAL DEMAND CURRENT: 401 A Kitchen Equip - Non-Dwelling Unit 0 VA **** #VALUE!

Electric Heat 0 VA 125% 0 VA Other Continuous Load 76800 VA 125% 96000 VA Other Non-Continuous Load 0 VA 100% 0 VA

NOTES:

1. ALL BREAKERS ARE STANDARD UNLESS OTHERWISE NOTED

2. (*) NUMBER INDICATES BREAKER TYPE: 1 = AFCI, 2 = CLASS A 5mA GFCI, 3 = 30mA GFPE, 4 = SHUNT TRIP ACTIVATED, 5 = PANELBOARD FEEDER SERVING UNIT

SHALL BE LOCKABLE USING A PADLOCK, IN ACCORDANCE WITH OSHA LOCK-OUT-TAG RULES.

SHORT CIRCUIT SCHEDULE

Required Short Line-Line Length Xfmer Xfmer

Short Circuit Circuit Voltage of run Rated Imped

POINT DESCRIPTION Bracing ISC SYM RMS V (Note 1) kVA %Z

U SERVICE TRANSFORMER

SECONDARY 100KVA ----- 29,761 240 ----- 100 1.4

1 CT CABINET 35,000 29,120 240 21 ----- -----

2 PANEL L1 35,000 29,060 240 2 ----- -----

3 CP6000 EV CHARGER 1 10,000 5,797 240 39 ----- -----

NOTES:

1. CONTRACTOR IS RESPONSIBLE FOR ALL QUANTITIES, FEEDER ROUTING AND INSTALLATION.

INDICATED FEEDER LENGTH WAS USED TO CALCULATE FAULT CURRENT AND IS AN APPROXIMATE LENGTH. IF THE INSTALLED FEEDER LENGTH IS 10% SHORTER OR LONGER THAN THE INDICATED

FEEDER LENGTH THE FAULT CURRENT MUST BE RE-EVALUATED AND REQUIRED BRACING

RESIZED.

600A3

#2/0G

File details come from the government source that posted it. Updated .