Lamar EV Charging - Documented Quote - Appendix G - Construction Drawings.pdf
PDF 2 MB Posted
- Solicitation number
- 0002
- Issued by
- Pitkin County, Colorado
About this file
These construction drawings are for the Lamar EV Station project by the Colorado Department of Transportation (CDOT), located at 2402 S. Main St. in Lamar, Colorado. The project involves installing electrical infrastructure for two new electric vehicle charging stations, specifically two ChargePoint CP6011X-80A-L7 dual-port chargers. The electrical scope includes providing a new 240/120V, 600A, single-phase panelboard (L1), a CT cabinet, conduit, wiring, and associated equipment. The design is prepared by Farnsworth Group and dated 12/18/2023, with the electrical design following the 2021 IBC, 2017 ICC A117.1, 2021 IFC, and 2023 NEC codes.
The electrical design includes a new 100kVA utility transformer, a NEMA 3R panelboard, and detailed specifications for conduit routing, equipment mounting, and electrical connections. The site plan shows the proposed locations for the transformer, meter, CT cabinet, panelboard, and EV charging stations, with specific notes about underground conduit routing, bollard protection, and coordination requirements with Lamar Light and Power utility. The one-line diagram and electrical site plan provide technical details about the electrical infrastructure, including short circuit calculations, feeder schedules, and equipment specifications to support the EV charging station installation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
arnswor
GROUP
COOT
2402 S. MAIN ST, LAMAR, CO 80152
INDEX OF DRAWINGS
ELECTRICAL
SHEET NUMBER SHEET TITLE
E0.1 ELECTRICAL SYMBOLS
E0.2
GENERAL NOTES AND
ABBREVIATIONS
ESl.1 ELECTRICAL SITE PLAN
E2.0
SCHEDULE AND
ONE-LINE
Project No: 0190216.16
I
LOCATION MAP
ENGINEER/DESIGNER INFORMATION
FARNSWORTH GROUP
5613 DTC PARKWAY, SUITE 1100
GREENWOOD VILLAGE, COLORADO 80111
(303) 692-8838 I info@f-w.com
UTILITY CONTACTS
LAMAR LIGHT AND POWER
100 N. 2ND ST.
LAMAR, CO 81052
HOUSSIN HOURIEH
(719) 336-7456
OWNER INFORMATION
CDOT LAMAR
2402 S. MAIN ST, LAMAR, CO 80152
Date: 12/18/2023
PARCEL NO. 0000084851
SCOPE OF PROJECT: SCOPE IS LIMITED TO PROVIDING PANEL, CONDUIT,
WIRING, AND EQUIPMENT FOR NEW EV CHARGING STATION. PROPOSED
CHARGER IS CHARGEPOINT CP6011X-80A-L7, 80A DUAL PORT, PEDESTAL
MOUNT, 23 FT CABLE.
APPLICABLE CODES: 2021 IBC, 2017 ICC A117.1, 2021 IFC, & 2023 NEC
chenerykm Rectangle chenerykm Rectangle
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
ELECTRICAL
SYMBOLS
E0.1
MP/IM
MP
AC
PROJECT:
DATE:
PROJECT NO.:
CDOT
LAMAR EV STATION
2402 S. Main St, Lamar, CO 80152
12/18/2023
0190216.16
DESCRIPTION:DATE:#
ISSUE:
NOT FOR CONSTRUCTION
99% CODE REVIEW
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
5613 DTC PARKWAY, SUITE 1100
GREENWOOD VILLAGE, COLORADO 80111
(303) 692-8838 / info@f-w.com
1 12/18/2023 PLAN REVIEW REPORT RESPONSE
CONDUIT - CAPPED
CABLE TRAY
SEALING FITTING
EXPANSION FITTING
CONDUIT FITTING (CONDULET)
JUNCTION BOX
CONDUIT - FLEXIBLE
SPECIAL PURPOSE RECEPTACLE - FLOOR MOUNTED
SPECIAL PURPOSE RECEPTACLE - CEILING MOUNTED
SPECIAL PURPOSE RECEPTACLE - MOUNTED 18" AFF
CEILING FAN
QUADRUPLEX RECEPTACLE - FLOOR MOUNTED
DUPLEX RECEPTACLE - FLUSH FLOOR MOUNTED
SINGLE RECEPTACLE - MOUNTED 18" AFF
QUADRUPLEX RECEPTACLE - MOUNTED 18" AFF
CONDUIT - CONTINUED
CONDUIT - TURNING UP
CONDUIT - EXPOSED
CONDUIT - TURNING DOWN
REVISION CALL-OUT
ROOM NUMBER
FEEDER CALL-OUT
KEYED NOTE
GENERAL SYMBOLS
UTILITY KILOWATT-HOUR METER
DUPLEX RECEPTACLE - EMERGENCY POWER - MOUNTED 18" AFF
DUPLEX RECEPTACLE - CEILING MOUNTED
DUPLEX RECEPTACLE - SPLIT WIRED - MOUNTED 18" AFF
DUPLEX RECEPTACLE - MOUNTED 6" ABOVE COUNTER
DUPLEX RECEPTACLE (NEMA 5-20R) - MOUNTED 18" AFF
MAGNETIC STARTER
COMBINATION STARTER
SAFETY SWITCH - FUSIBLE
SAFETY SWITCH - NON-FUSIBLE
EQUIPMENT - MOTOR
BRANCH CIRCUIT PANELBOARD - FLUSH MOUNTED
DISTRIBUTION PANELBOARD OR SWITCHBOARD
MOTOR CONTROL CENTER
BRANCH CIRCUIT PANELBOARD - SURFACE MOUNTED
T
CONTROL PANEL
TRANSFORMER
POWER SYMBOLS
COMPUTER OUTLET - CEILING MOUNTED
COMPUTER OUTLET - FLOOR MOUNTED
COMPUTER OUTLET - WALL MOUNTED 18" AFF
TELEPHONE OUTLET - CEILING MOUNTED
TELEPHONE OUTLET - FLOOR MOUNTED
TELEPHONE OUTLET - WALL MOUNTED
TELEPHONE TERMINAL BACKBOARD (PROVIDE WITH 3/4"
FIRERATED PLYWOOD)
JUNCTION BOX - EMERGENCY POWER
FOOD SERVICE EQUIPMENT DESIGNATION
TTB
HAND DRYER
WIRING AND CONDUITS
NEW EQUIPMENT (TYPICAL)
EXISTING EQUIPMENT (TYPICAL)
DEMOLITION EQUIPMENT (TYPICAL)
PUSH BUTTON
WALL MOUNT BRACKET (TYPICAL)
ABOVE COUNTER COMMUNICATIONS OUTLET
ABOVE COUNTER DATA OUTLET
ABOVE COUNTER TELEPHONE OUTLET
AHU
J
J
B
M
F
H
VFD
GWH1
MECHANICAL EQUIPMENT CALL-OUT: REFER TO
THE EQUIPMENT DATA SCHEDULE FOR DETAILS
PLUMBING EQUIPMENT CALL-OUT: REFER TO THE
EQUIPMENT DATA SCHEDULE FOR DETAILS
###A#G
AC
AC
AC
COMBINATION TELEPHONE/DATA OUTLET -
WALL MOUNTED 18" A.F.F
COMBINATION TELEPHONE/DATA OUTLET -
FLOOR MOUNTED
COMBINATION TELEPHONE/DATA OUTLET -
CEILING MOUNTED
COMMUNICATIONS SYMBOLS (FOR ROUGH-IN ONLY
WITH 1"CONDUIT TO ACCESSIBLE CEILING)
CONDUIT - UP AND DOWN
(CHANGE IN ELEVATION)
CONDUIT - CONCEALED BELOW
SLAB OR GRADE
CONDUIT - CONCEALED IN
SUSPENDED CEILING OR WALL
T POLE MOUNTED TRANSFORMER
GROUND BAR
AC
QUADRUPLEX RECEPTACLE - MOUNTED 6" ABOVE COUNTER
AC
J FLOOR BOX - SEE SPECS OR KEYED NOTES ON PLAN
FOR DETAILS
PP
POWER POLE
ONE-LINE DIAGRAM SYMBOLS
SERVICE DROP
PANEL
### PANELBOARD
T-1
45 KVA 3Ø
208Y/120VAC
G # KVA/KW
480Y/277V, 3Ø, 4W
DELTA-WYE TRANSFORMER
GENERATOR
# A
# POLES
AUTOMATIC TRANSFER SWITCH
GROUND
# AF
# AT CIRCUIT BREAKER
# AF
# AT
DRAWOUT CIRCUIT BREAKER
METER
CURRENT TRANSFORMER
M # A
POTENTIAL TRANSFORMER
G
ST
GROUND FAULT PROTECTED BREAKER
SHUNT TRIP BREAKER
# A SWITCH
FUSE
CONTACTOR
SPD
VFD
DPM
K
THERMAL OVERLOAD
ELECTRONIC OVERLOAD
SURGE PROTECTION DEVICE
VARIABLE FREQUENCY DRIVE
KIRK KEY INTERLOCK
DIGITAL POWER METER
WIFI WIRELESS ACCESS POINT
GFI GROUND FAULT CIRCUIT INTERRUPTER
SS SURGE SUPPRESSOR (ISOLATED GROUND TYPE)
WP WEATHERPROOF
H HOSTPITAL GRADE
TP TAMPER PROOF
D DEDICATED
USB STANDARD DUPLEX WITH 2 USB PORTS
VFD VARIABLE FREQUENCY DRIVE
- WALL MOUNTED 18" AFF
T TOUCH TONE DEVICE FOR THE DEAF
W WALL PHONE (MOUNTED 54" AFF)
D DEDICATED TELEPHONE OUTLET
QUADRUPLEX RECEPTACLE - CEILING MOUNTED
SYMBOLS LEGEND
NOTE: NOT ALL SYMBOLS ARE USED IN CONSTRUCTION DOCUMENTS.
http://www.f-w.com
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
GENERAL NOTES
AND ABBREVIATIONS
E0.2
MP/IM
MP
AC
PROJECT:
DATE:
PROJECT NO.:
CDOT
LAMAR EV STATION
2402 S. Main St, Lamar, CO 80152
12/18/2023
0190216.16
DESCRIPTION:DATE:#
ISSUE:
NOT FOR CONSTRUCTION
99% CODE REVIEW
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
5613 DTC PARKWAY, SUITE 1100
GREENWOOD VILLAGE, COLORADO 80111
(303) 692-8838 / info@f-w.com
1 12/18/2023 PLAN REVIEW REPORT RESPONSE
(E) EXISTING (ALSO COVERED BY TEXT
WEIGHT)
(F) FUTURE
(PART) PARTIAL CIRCUIT
(R) RELOCATE
2S1W TWO SPEED, SINGLE WINDING
2S2W TWO SPEED, DOUBLE WINDING
A AMPERES
AC 6" ABOVE COUNTER
ADA AMERICANS WITH DISABILITIES ACT
AF AMPERES FRAME
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERES INTERRUPTING CAPACITY
AL ALUMINUM
AT AMPERES TRIP
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAM CAMERA
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CCW COUNTER CLOCKWISE
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CO CONDUIT ONLY
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CU COPPER
CW CLOCKWISE
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DPDT DOUBLE POLE DOUBLE THROW
DPST DOUBLE POLE SINGLE THROW
DR DUPLEX RECEPTACLE
DWG DRAWING(S)
EC ELECTRICAL CONTRACTOR
ELC ELEVATOR CONTRACTOR
ELEC ELECTRIC/ELECTRICAL
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXP EXPLOSION PROOF
F FUSED
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FLA FULL LOAD AMPERES
FMC FLEXIBLE METAL CONDUIT
FO FIBER OPTIC
FPC FIRE PROTECTION CONTRACTOR
FS FUSED SWITCH
FSD FIRE/SMOKE DAMPER
FT FOOT/FEET
FVNR FULL VOLTAGE, NON-REVERSING
FVR FULL VOLTAGE, REVERSING
G GROUND
GC GENERAL CONTRACTOR
GEN GENERATOR
GF GROUND FAULT
GFI/GFCI GROUND FAULT INTERRUPTER
GND GROUND/GROUNDING
H HORIZONTALLY MOUNTED
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTO
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HZ FREQUENCY
I/O INPUT/OUTPUT
IC INTERRUPTING CAPACITY
ID INSIDE DIAMETER
IDF INTERMEDIATE DISTRIBUTION FRAME
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
JB JUNCTION BOX
K KELVIN (COLOR TEMPERATURE)
KCMIL THOUSAND CIRCULAR MILS
KV KILOVOLTS
KVA KILOVOLT-AMPERES
KW KILOWATTS
KWH KILOWATT-HOUR
LAN LOCAL AREA NETWORK
LC LIGHTING CONTACTOR
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LF LINEAR FOOT
LFMC LIQUID-TIGHT FLEXIBLE METAL
CONDUIT
LM LUMEN
LTG LIGHTING
LV LOW VOLTAGE
MAN MANUAL MOTOR STARTER WITH
OVERLOADS
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPERES
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MDF MAIN DISTRIBUTION FRAME
MDP MAIN DISTRIBUTION PANEL
MEPFP MECHANICAL, ELECTRICAL, PLUMBING,
FIRE PROTECTION
MGB MASTER GROUND BAR
MH MANHOLE
MH METAL HALIDE
MIN MINIMUM
MLO MAIN LUG ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MSB MAIN SWITCHBOARD
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MVA MEGAVOLT-AMPERES
MW MEGAWATTS
MWH MEGAWATT-HOURS
N NEUTRAL
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NF NONFUSED
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NP NAMEPLATE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OWN OWNER
P POLE
PA PUBLIC ADDRESS
PB PULL BOX
PC PHOTOCELL
PC PLUMBING CONTRACTOR
PDT PASSIVE DUAL TECHNOLOGY
PF POWER FACTOR
PH PHASE
PIR PASSIVE INFRARED
PLC PROGRAMMABLE LOGIC CONTROLLER
PNL PANEL
PR PAIR
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE
PWC PRE-WIRED CONTROLS
PWR POWER
RCPT RECEPTACLE
REQD REQUIRED
RF RADIO FREQUENCY
RM ROOM
RMC RIGID METAL CONDUIT
RNC RIGID NON-METALLIC CONDUIT (SCH 40)
RVAT REDUCED VOLTAGE -
AUTOTRANSFORMER
SC SHORT CIRCUIT
SCC SHORT CIRCUIT CURRENT RATING
SDP SUBDISTRIBUTION PANEL
SEC SECONDARY
SHLD SHIELD(ED) (AS IN CABLE)
SHT SHEET
SPD SURGE-PROTECTIVE DEVICE
SPDT SINGLE POLE DOUBLE THROW
SPST SINGLE POLE SINGLE THROW
SR SINGLE RECEPTACLE
ST SHUNT TRIP
SW MOTOR RATED SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBD TO BE DETERMINED
TC TIMECLOCK
TCC TEMPERATURE CONTROLS
CONTRACTOR
TEMP TEMPERATURE
TT THERMAL TRIP SWITCH
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
U UTILITY
UG UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERUPTABLE POWER SUPPLY
V VOLTS
VA VOLT-AMPERES
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
VFD VARIABLE FREQUENCY DRIVE
VND VENDOR
W WATTS
W WIRE
WHM WATTHOUR METER
WP WEATHERPROOF
XFMR TRANSFORMER
XP EXPLOSION PROOF
Z IMPEDANCE
ABBREVIATIONSGENERAL NOTES
GENERAL NOTES:
A. PRIOR TO ROUGH-IN AND FINAL CONNECTION, VERIFY ELECTRICAL REQUIREMENTS AND EXACT LOCATION OF EQUIPMENT BEING PROVIDED BY OTHER TRADES. REFERENCE ENTIRE SET OF CONSTRUCTION DOCUMENTS AS
WELL AS FINALIZED SHOP DRAWINGS.
B. COORDINATE SCHEDULE OF CONSTRUCTION WITH THE OWNER, OTHER TRADES AND UTILITIES INVOLVED BEFORE TRENCHING AND INSTALLATION OF UNDERGROUND CONDUIT. USE EXTREME CAUTION DURING EXCAVATION TO LOCATE EXISTING UNDERGROUND PIPING, CONDUITS, ETC. LOCATE AND PROTECT ANY BURIED UTILITIES IN AREAS
OF EXCAVATION.
C. DRAWINGS SHOW EXISTING CONDITIONS OF THE SITE. AN ATTEMPT HAS BEEN MADE TO SHOW EXISTING BUILDING, SITE DETAILS, ETC., BUT ACCURACY CANNOT BE GUARANTEED. VERIFY EXACT LOCATIONS OF ALL CIRCUITS, CONDUITS, PIPING, EQUIPMENT, ETC. VERIFY ALL SITE AND BUILDING DETAILS.
D. THE ELECTRICAL CONTRACTOR SHALL BE HELD FINANCIALLY RESPONSIBLE FOR ANY AND ALL COSTS OF THE ENGINEERS TIME REQUIRED TO REVIEW AND RESEARCH NON-SPECIFIED EQUIPMENT SUBMITTED FOR SUBSTITUTION BY THE ELECTRICAL CONTRACTOR. THESE COSTS SHALL BE AUTOMATICALLY INVOICED TO THE CONTRACTOR UNLESS SUCH SUBSTITUTIONS FOLLOW THE GUIDELINES FOR SUBSTITUTION AND ARE WITHIN THE PROPER TIME
FRAME AS OUTLINED IN OTHER SECTIONS OF THIS SPECIFICATION.
E. PROVIDE AND INSTALL IN EACH PANEL, TYPEWRITTEN NEAT TWO-COLUMN CIRCUIT INDEX CARD SET UNDER PLASTIC COVERS ON INSIDE OF DOORS. EACH ODD-NUMBERED CIRCUIT SHALL BE IN SEQUENCE ON ONE COLUMN AND THE EVEN-NUMBERED CIRCUITS ON THE OTHER COLUMN (E.G. 1,3,5...,2,4,6...). EACH CIRCUIT SHALL BE IDENTIFIED AS TO THE USE AND ROOM NAME(S) OR AREA(S). THE CONTRACTOR SHALL CONFIRM ROOM NAMES AND/OR ROOM
NUMBERS WITH THE ARCHITECT PRIOR TO PROJECT COMPLETION.
F. PRIOR TO SUBMITTING BID PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS AND VISIT CONSTRUCTION SITE TO BE FAMILIAR WITH EXISTING CONDITIONS UNDER WHICH HE WILL HAVE TO OPERATE AND WHICH WILL IN ANY WAY AFFECT THE WORK UNDER THIS CONTRACT. NO SUBSEQUENT ALLOWANCE WILL BE MADE IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR FOR ANY ERROR OR NEGLIGENCE ON HIS PART.
G. UNLESS INDICATED IN SOME MANNER THAT ELECTRICAL EQUIPMENT IS EXISTING, ALL EQUIPMENT SHALL BE NEW.
H. CONTRACTOR SHALL NOT SCALE DRAWING FOR QUANTITIES. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING
ALL MEASUREMENTS.
I. WHERE CONDUIT AND WIRING RUNS ARE NOT SHOWN ON FLOOR PLANS, THE CONTRACTOR SHALL DETERMINE AND PROVIDE THE REQUIRED CONDUIT AND WIRING FOR SPECIFIED CIRCUITING IN ACCORDANCE WITH NEC AND THE
FOLLOWING MINIMUM REQUIREMENTS:
1. MINIMUM CONDUIT SIZE SHALL BE 3/4".
2. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG. #10 AWG SHALL BE USED FOR HOME RUNS OF 20 AMP BRANCH
CIRCUITS OVER 100 FEET IN LENGTH.
3. EACH RACEWAY SHALL CONTAIN AN INSULATED EQUIPMENT GROUNDING CONDUCTOR PER NEC.
4. DERATING OF CONDUCTOR AMPACITY SHALL BE APPLIED PER NEC.
5. NO SHARING OF NEUTRALS ALLOWED. CIRCUIT SHALL HAVE DEDICATED NEUTRAL CONDUCTORS. ONE CIRCUIT, ONE NEUTRAL.
6. MAXIMUM SIX FOOT FLEXIBLE LUMINAIRE WHIP SHALL BE USED FOR FINAL CONNECTIONS TO LUMINAIRES
INSTALLED IN LAY-IN CEILINGS. MAXIMUM FOUR LUMINAIRE WHIPS SHALL BE CONNECTED FROM ONE JUNCTION
BOX. FEED THRU BETWEEN LUMINAIRES SHALL NOT BE ALLOWED.
J
J
T
M
PANELBOARD
L1L1-2
GFI
WP
CT CABINET
L1-1,3 L1-4,6
L1-5,7 L1-8,10
1'- 0"
5'- 0"
2"
FINISHED
GRADE
1'- 0"
FI
EL
D
VE
RI
FY
(T
YP
IC
AL
)6'- 3"
2" M
AX
(TYPICAL)
FIELD VERIFY
(TYPICAL)
METER
CT
CABINET PANEL
1.
2.
3.
4.
KEYNOTES:
3-INCH NOMINAL GALVANIZED STEEL SCHEDULE 40 PIPE OR RIGID
METAL CONDUIT SUPPORT POST. TYPICAL OF TWO. CLOSE OPEN
ENDS OF ALL POSTS WITH GALVANIZED STEEL CAP.
GALVANIZED PIPE/CONDUIT CLAMP P1119 OR P2558-35, TYPICAL.
TIGHTEN BOLTS TO MANUFACTURER'S RECOMMENDED TORQUE
VALUES.
18-INCH DIAMETER CONCRETE PIER, TYPICAL OF TWO.
SLOTTED-METAL CHANNEL, UNISTRUT P5000, AS REQUIRED TO
SUPPORT AND BRACE THE EQUIPMENT AND CONDUITS. ALL
SUPPORTS, FITTINGS, AND HARDWARE SHALL BE OF CORROSION-
RESISTANT MATERIAL OR PAINTED WITH A FACTORY APPLIED
CORROSION INHIBITING PAINT.
GFI SERVICE
RECEPTACLE
WITH
WEATHERPROOF
COVER
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
ELECTRICAL SITE
PLAN
ES1.1
MP/IM
MP
AC
PROJECT:
DATE:
PROJECT NO.:
CDOT
LAMAR EV STATION
2402 S. Main St, Lamar, CO 80152
12/18/2023
0190216.16
DESCRIPTION:DATE:#
ISSUE:
NOT FOR CONSTRUCTION
99% CODE REVIEW
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
5613 DTC PARKWAY, SUITE 1100
GREENWOOD VILLAGE, COLORADO 80111
(303) 692-8838 / info@f-w.com
1 12/18/2023 PLAN REVIEW REPORT RESPONSE
U.S. SURVEY FEET
15 30 60
1 SCALE:
ELECTRICAL SITE PLAN
1"=30' NORTH
GENERAL NOTES
A. REFER TO ONE-LINE DIAGRAM (E2.0) FOR ADDITIONAL INFORMATION.
KEYNOTES
1. RUN CONDUIT UNDERGROUND AT A MINIMUM OF 24" BELOW GRADE FROM NEW
PANEL L1 LOCATION TO NEW EV CHARGING LOCATIONS. COORDINATE ROUTE WITH
OWNER ON THE FIELD.
2. APPROXIMATE LOCATION OF NEW EV CHARGING STATION. CONTRACTOR SHALL
VERIFY EXACT LOCATION WITH THE OWNER IN THE FIELD.
3. VERIFY NETWORK CONNECTIONS WITH OWNER. IF A WIRELESS CONNECTION IS NOT
AVAILABLE, PROVIDE 2" UNDERGROUND CONDUIT BETWEEN SERVICE POINT AND
STATION.
4. CONTRACTOR SHALL PROVIDE 4' IMPACT RESISTANT BOLLARD IN FRONT OF EV
STATION.
5. PROPOSED LOCATION OF NEW 240/120V SECONDARY UTILITY TRANSFORMER.
COORDINATE TRANSFORMER LOCATION WITH UTILITY COMPANY AND OWNER
PRIOR TO INSTALLATION.
6. PLACE METER, CT CABINET, AND PANEL ON UNISTRUT STRUCTURE. SEE DETAIL 2
ON SHEET ES1.1. CONTRACTOR SHALL PROVIDE 4' IMPACT RESISTANT BOLLARD TO
PROTECT ELECTRICAL EQUIPMENT.
7. RUN CONDUIT OVERHEAD FROM NEW UTILITY TRANSFORMER LOCATION TO NEW
METER, CT CABINET AND PANEL L1. COORDINATE ROUTE WITH OWNER ON THE
FIELD.
8. PLAQUE SHALL BE INSTALLED ON CHARGER DENOTING EXACT LOCATION OF PANEL
L1 WITH LOCKABLE DISCONNECTING MEANS PER NEC 625.43.
2 3
(TYP. 2)
2 SCALE:
PANELBOARD UNISTRUT MOUNTING
NOT TO SCALE
http://www.f-w.com chenerykm Stamp
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
SCHEDULE AND
ONE-LINE
E2.0
MP/IM
MP
AC
PROJECT:
DATE:
PROJECT NO.:
CDOT
LAMAR EV STATION
2402 S. Main St, Lamar, CO 80152
12/18/2023
0190216.16
DESCRIPTION:DATE:#
ISSUE:
NOT FOR CONSTRUCTION
99% CODE REVIEW
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
5613 DTC PARKWAY, SUITE 1100
GREENWOOD VILLAGE, COLORADO 80111
(303) 692-8838 / info@f-w.com
1 12/18/2023 PLAN REVIEW REPORT RESPONSE
GENERAL NOTES
A. ONE-LINE DIAGRAM PREPARED BASED ON LIMITED SITE OBSERVATION. NOT ALL
EXISTING SYSTEM GROUNDING CONNECTIONS MAY EXIST.
NEW UTILITY
TRANSFORMER
240/120V XFMR 1PH
100KVA
1 SCALE:
ONE-LINE DIAGRAM
NOT TO SCALE
100A/2P 100A/2P
NEW PANELBOARD L1
240/120V, 600A, 1PH
NEMA 3R
NEW CT CABINET
NEMA 3R
N G
NEW 80A
CP6000 EV
CHARGER 1,
PORT1
600A/2P
MCB
100A/2P
100A2G 100A2G
NEW 80A
CP6000 EV
CHARGER 1,
PORT2
600A3
M 600A
U
100A2G
NEW 80A
CP6000 EV
CHARGER 2,
PORT1
100A/2P
100A2G
NEW 80A
CP6000 EV
CHARGER 2,
PORT2
FEEDER SCHEDULE
MARK CONDUIT & CONDUCTORS
(SEE NOTE 1)
REMARKS
100A2G 2#1, 1#8G, 1-1/4"C
600A3 2 SETS (3#350, 2-1/2"C)
REMARKS:
1. THIS FEEDER SCHEDULE IS BASED ON 60 DEGREE CENTIGRADE (TYPE TW) WIRE
AND TERMINATIONS FOR SIZES #12 TO #1, AND 75 DEGREE CENTIGRADE (TYPE
THHN/THWN) WIRE AND TERMINATIONS FOR SIZES #1/0 AND LARGER. UNLESS
NOTED OTHERWISE, CONDUIT IS SIZED BASED ON TYPE EMT CONDUIT. USE OF
OTHER CONDUIT TYPES REQUIRES RESIZING OF CONDUIT.
PANELBOARD L1
VOLTAGE: 240/120V CONNECTED LOAD PER
PHASE
ISOLATED GROUND BUS (Y/N): N
PHASE / WIRE: 1Ø / 3W BUSSING: SEE SPEC
RATED AMPERAGE: 600 A A B MOUNTING: SURFACE
MAIN: 600 A MCB MCB GROUND FAULT PROTECTION (Y/N): N
SCC RATING (SYM): 35 KA 38580 VA 38400 VA MCB SHUNT TRIP (Y/N): N
322 A 320 A MCB 100% RATED (Y/N): N
CKT IDENTIFICATION TYPE
BKR
SIZE POLES A B POLES BKR
SIZE
TYPE
(*) IDENTIFICATION CKT
1 CP6000 EV CHARGER 1 PORT 1 5 100A 2
9600 180 1 20A SERVICE RECEPT. 2
3 9600 9600
2 100A 5 CP6000 EV CHARGER 1 PORT 2 4
CP6000 EV CHARGER 2 PORT 1 5 100A 2
9600 9600 6 7 9600 9600
2 100A 5 CP6000 EV CHARGER 2 PORT 2
9 SPARE 20A 1 0 9600 10
11 SPARE 20A 1 0 0 1 20A SPARE 12
Load Classification Connected Load Demand Factor Demand Load PANEL TOTALS Lighting - Continuous 0 VA 125% 0 VA Receptacle - First 10 kVA 180 VA 100% 180 VA TOTAL CONNECTED LOAD: 76980 VA
Remainder 0 VA 50% 0 VA TOTAL DEMAND: 96180 VA Motor - Largest 0 VA 125% 0 VA TOTAL CONNECTED CURRENT: 321 A
Remainder 0 VA 100% 0 VA TOTAL DEMAND CURRENT: 401 A Kitchen Equip - Non-Dwelling Unit 0 VA **** #VALUE!
Electric Heat 0 VA 125% 0 VA Other Continuous Load 76800 VA 125% 96000 VA Other Non-Continuous Load 0 VA 100% 0 VA
NOTES:
1. ALL BREAKERS ARE STANDARD UNLESS OTHERWISE NOTED
2. (*) NUMBER INDICATES BREAKER TYPE: 1 = AFCI, 2 = CLASS A 5mA GFCI, 3 = 30mA GFPE, 4 = SHUNT TRIP ACTIVATED, 5 = PANELBOARD FEEDER SERVING UNIT
SHALL BE LOCKABLE USING A PADLOCK, IN ACCORDANCE WITH OSHA LOCK-OUT-TAG RULES.
SHORT CIRCUIT SCHEDULE
Required Short Line-Line Length Xfmer Xfmer
Short Circuit Circuit Voltage of run Rated Imped
POINT DESCRIPTION Bracing ISC SYM RMS V (Note 1) kVA %Z
U SERVICE TRANSFORMER
SECONDARY 100KVA ----- 29,761 240 ----- 100 1.4
1 CT CABINET 35,000 29,120 240 21 ----- -----
2 PANEL L1 35,000 29,060 240 2 ----- -----
3 CP6000 EV CHARGER 1 10,000 5,797 240 39 ----- -----
NOTES:
1. CONTRACTOR IS RESPONSIBLE FOR ALL QUANTITIES, FEEDER ROUTING AND INSTALLATION.
INDICATED FEEDER LENGTH WAS USED TO CALCULATE FAULT CURRENT AND IS AN APPROXIMATE LENGTH. IF THE INSTALLED FEEDER LENGTH IS 10% SHORTER OR LONGER THAN THE INDICATED
FEEDER LENGTH THE FAULT CURRENT MUST BE RE-EVALUATED AND REQUIRED BRACING
RESIZED.
600A3
#2/0G
File details come from the government source that posted it. Updated .