KUA_040123Steel_PackageREV108.04.2026.pdf

PDF 3 MB Posted

Attached to
Marydia to Hansel 69kV Storm Hardening Project-Tubular Steel Transmission Poles
Solicitation number
IFB 26-042-JG
Issued by
Florida

About this file

This file comprises technical assembly drawings and specifications for tubular steel transmission poles for the Kissimmee Utility Authority's Marydia to Hansel 69kV Storm Hardening Project in Florida. The solicitation (IFB 26-042-JG) requests eight transmission structures: Structure 264 (H9 class, 100 feet height with 23-foot embedment), Structures 21360 and 21361 (H11 class, 105-110 feet height with 23-24 foot embedment), Structures 9199 and 9287 (Custom class, 80 feet height), and Structures 9194 and 9195 (Custom class, 100-105 feet height with 24-27 foot embedment). All structures are designed for 69kV transmission line applications with various tangent and deadend configurations, including poles, insulator assemblies, grounding systems, cathodic protection, and identification plates. Bids are due August 11, 2026, with delivery required by July 1, 2027. Bidders unable to meet the delivery deadline must state required lead time in weeks.

Pricing must be submitted on a fixed-price basis with freight charges listed separately and excluded from unit prices. Bidders must specify whether freight pricing is firm or estimated and confirm FOB Destination compliance. All pricing submissions must include company name, contact information, phone number, email address, authorized signature, transmission structure manufacturer information, plant location, and shipment method. The solicitation was posted July 9, 2026, and KUA reserves the right to modify quantities during contract performance based on service protocols and engineering determinations. Incomplete submissions may be invalidated. No estimated contract value, evaluation criteria, incumbent contractor information, or pre-bid meeting details are specified in the available solicitation materials.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A A 6"

'H

SE

E

TA

BL

E)

7' -6

5'

-0

6' -0

-1

2' -1

0" 3'

-8

5' -5

"D

" S

EE

TA

BL

E

B B

GROUND LINE

1'-0" TYP.

10" TYP.

1' -0

4'

-0

8" 2'

-1 1"

CC

DATE

CHECKED

ENGINEER

DATE

DRAWN CODE

SCALE

PROJECT DRAWING NUMBER REV

REVISIONS AND RECORD OF ISSUENO

STEEL POLE

STRUCTURE INFORMATION

STRUCTURE

NUMBER CLASS

STRUCTURE

HEIGHT 'H'

(FT.)

EMBEDMENT

DEPTH 'D'

(FT.)

264 H9 100' 23

04-0123 STRUCTURE REPLACEMENTS

69KV TRANSMISSION LINE

STRUCTURE 264 ASSEMBLY

CLL/GAI

IAP/GAI

JNR/GAI

01/16/2026

04-0123 AS7501

ASSEMBLY INFORMATION

Assembly Number

Quantity Assembly Name

1 1 Pole

2 1 OPGW Suspension Assembly

3 3 69kV Suspension Insulator Assembly

4 3 Distribution Suspension Insulator Assembly

5 1 Ground Sleeve

6 1 Identification Plate

7 1 Cathodic Protection

SEE SECTION 5 FOR

FOUNDATION DETAILS

SECTION B-B

TRANSMISSION

TANGENT ASSEMBLY

SECTION B1-B1

TRANSMISSION

TANGENT ASSEMBLY

A1

SECTION A1-A1

POLE CAP & OPGW

TANGENT ASSEMBLY

HOLE SCHEDULE AND GROUND WIRE DATA

Distance From Top Size or Type Flats Function

0'-6" 7/8" Dia. Hole FLAT 4 Shield Wire 2'-0" Grounding Pad FLAT 1 2 Hole Pad 7'-6" 7/8" Dia. Hole FLAT 4 Insulator Base, Transmission8'-6" 7/8" Dia. Hole FLAT 4 13'-6" 7/8" Dia. Hole FLAT 10 Insulator Base, Transmission14'-6" 7/8" Dia. Hole FLAT 10 19'-6" 7/8" Dia. Hole FLAT 4 Insulator Base, Transmission20'-6" 7/8" Dia. Hole FLAT 4 29'-7" 3/4" Dia. Hole FLAT 10 Insulator Brkt, Distribution30'-5" 3/4" Dia. Hole FLAT 10 30'-9" 3/4" Dia. Hole FLAT 10 TAN, Distribution 33'-3" 3/4" Dia. Hole FLAT 10 Insulator Brkt, Distribution34'-1" 3/4" Dia. Hole FLAT 10 34'-5" 3/4" Dia. Hole FLAT 10 TAN, Distribution 36'-11" 3/4" Dia. Hole FLAT 10 Insulator Brkt, Distribution37'-9" 3/4" Dia. Hole FLAT 10 38'-1" 3/4" Dia. Hole FLAT 10 TAN, Distribution 38'-9" 3/4" Dia. Hole FLAT 1 CO/LA

BRACKET39'-5" 3/4" Dia. Hole FLAT 1 42'-4" 3/4" Dia. Hole FLAT 4 Neutral/Xfmr

42'-10" Grounding Pad FLAT 1 2 Hole Pad 43'-4" 3/4" Dia. Hole FLAT 1 DE/ Xfmr 44'-4" 3/4" Dia. Hole FLAT 4 ADSS/ Alt N

48'-10" Grounding Sleeve FLAT 1 2 Hole Pad

B1 B1

FLAT 1

A 01/16/2026 ISSUE FOR 90% REVIEW

10 4

7 4 10

PLAN VIEW

FOR STRUCTURE

*DESIGN FOR FUTURE

DISTRIBUTION

*DESIGN FOR FUTURE

DISTRIBUTION

*DESIGN FOR FUTURE

DISTRIBUTION

N.T.S.

*COMMUNICATION SHALL BE BANDED IF

NEEDED AND HAS BEEN ACCOUNTED

FOR IN POLE DESIGN

C1 C14 10

SECTION C-C

DISTRIBUTION

TANGENT ASSEMBLY

A1

SECTION A-A

POLE CAP & OPGW

TANGENT ASSEMBLY

SECTION C1-C1

DISTRIBUTION

TANGENT ASSEMBLY

STREETLIGHT

DETAIL F

STRUCTURE ID

DETAIL

4-7/8"

3/

4"

KUA

STR TYPE

TOTAL LENGTH (FT)

EMBEDMENT LENGTH (FT)

BENDING MOMENT (F-K)

VENDOR NAME

YEAR OF MANUFACTURE

SE

E

ST

R

U C

TU

R

E D

R

AW

IN

G

F O

R

LO

C

AT

IO

N

C L

SPARE SPACE

FOR FIELD

STAMPING (STR.

NUMBER)

STENCIL MARK

WITH LETTER

1/2" HEIGHT

1/8"

STRUCTURE ID

SEE DETAIL "F"

0 02/19/2026 ISSUED FOR BID

1 08/04/2026 ISSUED FOR BID

02/19/2026

GROUND LINE

A A

'H

SE

E

TA

BL

E)

'D ' S

EE

TA

BL

E

B B

7' -6

6'

-0

'-1

2'

-1 0"

3' -8

5'

-5

1'-0" TYP.

10" TYP.

6"

5' -0

1' -0

4'

-0

8" 2'

-1 1"

C C

DATE

CHECKED

ENGINEER

DATE

DRAWN CODE

SCALE

PROJECT DRAWING NUMBER REV

REVISIONS AND RECORD OF ISSUENO

STEEL POLE

STRUCTURE INFORMATION

Structure Number Class

Structure Height 'H'

(FT.)

Embedment Depth 'D'

(FT.)

21360 H11 105' 24

21361 H11 110' 23

04-0123 STRUCTURE REPLACEMENTS

69KV TRANSMISSION LINE

TANGENT ASSEMBLY

CLL/GAI

IAP/GAI

JNR/GAI

01/16/2026

04-0123 AS7502

ASSEMBLY INFORMATION

Assembly Number

Quantity Assembly Name

1 1 Pole

2 1 OPGW Suspension Assembly

3 3 69kV Suspension Insulator Assembly

4 3 Distribution Suspension Insulator Assembly

5 1 Steel Pole Grounding Assembly

6 1 Identification Plate

7 1 Cathodic Protection

SEE SECTION 5 FOR

FOUNDATION DETAILS

SECTION B1-B1

TRANSMISSION

TANGENT ASSEMBLY

SECTION C1-C1

DISTRIBUTION

TANGENT ASSEMBLY

SECTION A1-A1

POLE CAP & OPGW

TANGENT ASSEMBLY

HOLE SCHEDULE AND GROUND WIRE DATA

Distance From Top Size or Type Flats Function

0'-6" 7/8" Dia. Hole FLAT 4 Shield Wire 2'-0" Grounding Pad FLAT 1 2 Hole Pad 7'-6" 7/8" Dia. Hole FLAT 4 Insulator Base, Transmission8'-6" 7/8" Dia. Hole FLAT 4 13'-6" 7/8" Dia. Hole FLAT 10 Insulator Base, Transmission14'-6" 7/8" Dia. Hole FLAT 10 19'-6" 7/8" Dia. Hole FLAT 4 Insulator Base, Transmission20'-6" 7/8" Dia. Hole FLAT 4 29'-7" 3/4" Dia. Hole FLAT 10 Insulator Brkt, Distribution30'-5" 3/4" Dia. Hole FLAT 10 30'-9" 3/4" Dia. Hole FLAT 10 TAN, Distribution 33'-3" 3/4" Dia. Hole FLAT 10 Insulator Brkt, Distribution34'-1" 3/4" Dia. Hole FLAT 10 34'-5" 3/4" Dia. Hole FLAT 10 TAN, Distribution 36'-11" 3/4" Dia. Hole FLAT 10 Insulator Brkt, Distribution37'-9" 3/4" Dia. Hole FLAT 10 38'-1" 3/4" Dia. Hole FLAT 10 TAN, Distribution 38'-9" 3/4" Dia. Hole FLAT 1 CO/LA

BRACKET39'-5" 3/4" Dia. Hole FLAT 1 42'-4" 3/4" Dia. Hole FLAT 4 Neutral/Xfmr

42'-10" Grounding Pad FLAT 1 2 Hole Pad 43'-4" 3/4" Dia. Hole FLAT 1 DE/ Xfmr 44'-4" 3/4" Dia. Hole FLAT 4 ADSS/ Alt N

48'-10" Grounding Sleeve FLAT 1 2 Hole Pad

SECTION A-A

POLE CAP & OPGW

TANGENT ASSEMBLY

A1 A1

SECTION B-B

TRANSMISSION

TANGENT ASSEMBLY

B1 B110 4

A 01/16/2026 ISSUE FOR 90% REVIEW

4 10

PLAN VIEW

FOR STRUCTURES

21360 & 21361

FLAT 1

*DESIGN FOR FUTURE

DISTRIBUTION

*DESIGN FOR FUTURE

DISTRIBUTION

*DESIGN FOR FUTURE

DISTRIBUTION

N.T.S.

*COMMUNICATION SHALL BE BANDED IF

NEEDED AND HAS BEEN ACCOUNTED

FOR IN POLE DESIGN

NOTES:

1. CONSTRUCTION SHALL BE RESPONSIBLE FOR ANY SIDEWALK

DAMAGE NEAR POLE 21360

C1 C110 4

SECTION C-C

DISTRIBUTION

TANGENT ASSEMBLY

STREETLIGHT

STRUCTURE ID

SEE DETAIL "F"

DETAIL F

STRUCTURE ID

DETAIL

4-7/8"

3/

4"

KUA

STR TYPE

TOTAL LENGTH (FT)

EMBEDMENT LENGTH (FT)

BENDING MOMENT (F-K)

VENDOR NAME

YEAR OF MANUFACTURE

SE

E

ST

R

U C

TU

R

E D

R

AW

IN

G

F O

R

LO

C

AT

IO

N

C L

SPARE SPACE

FOR FIELD

STAMPING (STR.

NUMBER)

STENCIL MARK

WITH LETTER

1/2" HEIGHT

1/8"

0 02/19/2026 ISSUED FOR BID

1 08/04/2026 ISSUED FOR BID

02/19/2026

9"

'H

SE

E

TA

BL

E)

9' -0

6'

-0

6' -0

'-2

3' -8

3'

-8

6' -0

1' -0

"B B

6' -0

2'-0"

2'-0"

A A

C C

4' -6

TY

P

1' -0

1'

-0

DATE

CHECKED

ENGINEER

DATE

DRAWN CODE

SCALE

PROJECT DRAWING NUMBER REV

REVISIONS AND RECORD OF ISSUENO

STEEL POLE

STRUCTURE INFORMATION

Structure Number Class

Structure Height 'H'

(FT.)

9199 Custom 80' 9287 Custom 80'

04-0123 STRUCTURE REPLACEMENTS

69KV TRANSMISSION LINE

DEADEND ASSEMBLY

CLL/GAI

IAP/GAI

JNR/GAI

02/19/2026

04-0123 1S7403

6"

2' -0

"GROUNDING PAD

SEE DETAIL "D"

SECTION A-A

POLE CAP & OPGW

DE ASSEMBLY

DETAIL "D"

2-HOLE

GROUNDING PAD

2" 1" 1"

1/

8"

3/ 4"

1/

8"

B1

SECTION B-B

TRANSMISSION

DE ASSEMBLY

B1

SECTION B1-B1

JUMPER POST

INSULATOR

SECTION C1-C1

DISTRIBUTION

DE ASSEMBLY

ASSEMBLY INFORMATION

Assembly Number

Quantity Assembly Name

1 1 Pole

2 2 OPGW Dead-end Assembly

3 12 69kV Dead-end Insulator Assembly

4 3 69kV Post Insulator Assembly

5 12 Davit Arm Dead-end Insulator Assembly

6 1 Anchor Bolt Assembly

7 2 Grounding Pad

8 1 Identification Plate

SEE SECTION 5 FOR

FOUNDATION DETAILS

INSULATOR BRACKET

SEE DETAIL "E"

DETAIL E

POST INSULATOR

MOUNTING

BRACKET

NOTE:

1. FLAT 1 & FLAT 10 WILL BE IDENTIFIED BY VENDOR

POST INSULATOR

MOUNTING BRACKET

SEE DETAIL "E"

FLAT 1

4 10

PLAN VIEW

FOR STRUCTURE

4 10

PLAN VIEW

FOR STRUCTURE

*DESIGN FOR FUTURE

DISTRIBUTION

N.T.S.

DISTIBUTION DE ASSEMBLY

SEE DETAIL "C"

0 02/19/2026 ISSUED FOR BID

SECTION C-C

DISTRIBUTION

DE ASSEMBLY

C1 C1

4' 4'

GROUNDING PAD

SEE DETAIL "D"

COMMUNICATION

COMMUNICATION

COMMUNICATION

DETAIL F

STRUCTURE ID

DETAIL

STRUCTURE ID

SEE DETAIL "F"

4-7/8"

3/

4"

KUA

STR TYPE

TOTAL LENGTH (FT)

EMBEDMENT LENGTH (FT)

BENDING MOMENT (F-K)

VENDOR NAME

YEAR OF MANUFACTURE

SE

E

ST

R

U C

TU

R

E D

R

AW

IN

G

F O

R

LO

C

AT

IO

N

C L

SPARE SPACE

FOR FIELD

STAMPING (STR.

NUMBER)

STENCIL MARK

WITH LETTER

1/2" HEIGHT

1/8"

1 08/04/2026 ISSUED FOR BID

1"

1" 9" 1"

1"

23/25"

HOLES

TYP.

STEEL POLE

INSULATOR

BASE

6"

9"

'H

SE

E

TA

BL

E)

9' -0

6'

-0

6' -0

'-2

3' -8

3'

-8

6' -0

1' -0

"B B

6' -0

2'-0"

2'-0"

A A

C C

4' -6

TY

P

1' -0

1'

-0

NOTES:

1. CUSTOM STEEL DAVIT ARMS ARE TO BE DESIGNED AND SUPPLIED BY VENDOR.

2. ALL DISTRIBUTION ARMS ARE TO BE DESIGNED WITH ALL VANGS.

SECTION A-A

STRUCTURE 9287

POLE CAP & OPGW DETAIL

SECTION B-B

STRUCTURE 9287

69KV CONDUCTOR

SECTION C-C

STRUCTURE 9287

12KV DISTRIBUTION ARM

AHEAD SPAN

(+) TR

AN

SVER

SE

AXIS

0°

(+) LONGITUDINAL

AXIS

34.53°

.74

72.74

SECTION A-A

STRUCTURE 9199

POLE CAP & OPGW DETAIL

AHEAD SPAN

(+) TR

AN

SVER

SE

AXIS

0°

(+) LONGITUDINAL

AXIS

34.53°

.74

72.74°

(+) TR

AN

SVER

SE

AXIS

(+) LONGITUDINAL

AXIS

STRUCTURE 9199

12KV DISTRIBUTION ARM

BACK SPAN

BACK SPAN

(+) TR

AN

SVER

SE

AXIS

SECTION B-B

STRUCTURE 9199

69KV CONDUCTOR

SECTION C-C

0°

AHEAD SPAN

34.53°

.74

72.74°

BACK SPAN

AHEAD SPAN

34.53°

.74

72.74°

BACK SPAN

(+) LONGITUDINAL

AXIS

(+) TRANSVERSE

AXIS

62.3°

.8

5°

58.85°

0°

AHEAD SPAN

BACK SPAN

(+) LONGITUDINAL

AXIS

(+) TRANSVERSE

AXIS

62.3°

.8

5°

58.85°

0°

AHEAD SPAN

BACK SPAN

(+) TRANSVERSE

AXIS

0°

AHEAD SPAN

BACK SPAN

62.3°

.8

5°

58.85°

AHEAD SPAN

62.3°

.8

5°

58.85°

(+) LONGITUDINAL

AXIS

BACK SPAN

DATE

CHECKED

ENGINEER

DATE

DRAWN CODE

AREA

PROJECT DRAWING NUMBER REV

REVISIONS AND RECORD OF ISSUENO

STEEL POLE

STRUCTURE INFORMATION

Structure Number Class

Structure Height 'H'

(FT.)

9199 Custom 80' 9287 Custom 80'

04-0123 STRUCTURE REPLACEMENTS

69KV TRANSMISSION LINE

DEADEND ASSEMBLY

CLL/GAI

IAP/GAI

JNR/GAI

02/19/2026

04-0123 1

S7504

ASSEMBLY INFORMATION

Assembly Number

Quantity Assembly Name

1 1 Pole

2 2 OPGW Dead-end Assembly

3 12 69kV Dead-end Insulator Assembly

4 3 69kV Post Insulator Assembly

5 12 Distribution Dead-end Insulator Assembly

6 1 Anchor Bolt Assembly

7 2 Grounding Pad

8 1 Identification Plate

6"

2' -0

GROUNDING PAD

SEE DETAIL "D"

SEE SECTION 5 FOR

FOUNDATION DETAILS

COMMUNICATION

COMMUNICATION

COMMUNICATION

1 08/04/2026 ISSUED FOR BID

0 02/19/2026 ISSUED FOR BID

STRUCTURE 9199 LOADS

DATE

CHECKED

ENGINEER

DATE

DRAWN CODE

AREA

PROJECT DRAWING NUMBER REV

REVISIONS AND RECORD OF ISSUENO

04-0123 STRUCTURE REPLACEMENTS

69KV TRANSMISSION LINE

DEADEND ASSEMBLY

CLL/GAI

IAP/GAI

JNR/GAI

02/19/2026

04-0123 1S7505

0 02/19/2026 ISSUED FOR BID

LOAD DIAGRAM

VERT. (+)

TRANS. (+)

LO

NG. (+

1 08/04/2026 ISSUED FOR BID

NA, NB

C1A, C1B C2A, C2B C3A, C3B

D2A, D2BD1A, D1B

PA, PB

PA, PB

PA, PB

SA, SB

NOTE:

1. WTRANS IS THE WIND LOAD APPLIED TO THE

STRUCTURE IN PSF. A SHAPE FACTOR OF 1.0

SHALL BE APPLIED.

2. THE DEAD LOAD OF THE STRUCTURE SHALL BE

MULTIPLIED BY K.

3. LIMIT POLE DEFLECTION TO 1% OF STRUCTURE

HEIGHT AT DEFLECTION LOAD CASE. LIMIT POLE

DEFLECTION TO 7% FOR ALL OTHER LOAD CASES.

4. CAMBERING IS NOT A PERMITTED METHOD TO

MEET THE ABOVE STATED DEFLECTION CRITERIA.

5. NO STRUCTURAL MEMBER SHALL BE DESIGNED

TO MORE THAN 90% CAPACITY BASED ON THE

DESIGN LOADS PROVIDED.

OUT OF PAGE

1.5

1.5

1.5 1.5

STRUCTURE 9287 LOADS

DATE

CHECKED

ENGINEER

DATE

DRAWN CODE

AREA

PROJECT DRAWING NUMBER REV

REVISIONS AND RECORD OF ISSUENO

04-0123 STRUCTURE REPLACEMENTS

69KV TRANSMISSION LINE

DEADEND ASSEMBLY

CLL/GAI

IAP/GAI

JNR/GAI

02/19/2026

04-0123 1

0 02/19/2026 ISSUED FOR BID

S7506

LOAD DIAGRAM

1 08/04/2026 ISSUED FOR BID

VERT. (+)

TRANS. (+)

NA, NB

C1A, C1B C2A, C2B C3A, C3B

D2A, D2BD1A, D1B

PA, PB

PA, PB

PA, PB

SA, SB

NOTE:

1. WTRANS IS THE WIND LOAD APPLIED TO THE

STRUCTURE IN PSF. A SHAPE FACTOR OF 1.0

SHALL BE APPLIED.

2. THE DEAD LOAD OF THE STRUCTURE SHALL BE

MULTIPLIED BY K.

3. LIMIT POLE DEFLECTION TO 1% OF STRUCTURE

HEIGHT AT DEFLECTION LOAD CASE. LIMIT POLE

DEFLECTION TO 7% FOR ALL OTHER LOAD CASES.

4. CAMBERING IS NOT A PERMITTED METHOD TO

MEET THE ABOVE STATED DEFLECTION CRITERIA.

5. NO STRUCTURAL MEMBER SHALL BE DESIGNED

TO MORE THAN 90% CAPACITY BASED ON THE

DESIGN LOADS PROVIDED.

LO

NG. (+

OUT OF PAGE

A A

'H

SE

E

TA

BL

E)

"D " S

EE

TA

BL

E

B B

GROUND LINE

1 6

9"

8' -4

3'

-6

3' -6

'-2

3' -8

3'

-8

5' -0

2'-0" 2'-0"

C C

5' -0

DATE

CHECKED

ENGINEER

DATE

DRAWN CODE

SCALE

PROJECT DRAWING NUMBER REV

REVISIONS AND RECORD OF ISSUENO

STEEL POLE

STRUCTURE INFORMATION

STRUCTURE

NUMBER CLASS

STRUCTURE

HEIGHT 'H'

(FT.)

Embedment Depth 'D'

(FT.)

9194 Custom 100' 27'

9195 Custom 105' 24'

04-0123 STRUCTURE REPLACEMENTS

69KV TRANSMISSION LINE

TANGENT ASSEMBLY

CLL/GAI

IAP/GAI

JNR/GAI

02/19/2026

04-0123 1S7404

ASSEMBLY INFORMATION

Assembly Number

Quantity Assembly Name

1 1 Pole

2 1 OPGW Suspension Assembly

3 3 69kV Suspension Insulator Assembly

4 6 Distribution Suspension Insulator Assembly

5 1 Steel Pole Grounding Assembly

6 1 Identification Plate

7 1 Cathodic Protection

SEE SECTION 5 FOR

FOUNDATION DETAILS

SECTION A-A

POLE CAP & OPGW

TANGENT ASSEMBLY

B1

SECTION B-B

TRANSMISSION

TANGENT ASSEMBLY

B1

SECTION B1-B1

TRANSMISSION

TANGENT ASSEMBLY

SECTION C1-C1

DISTRIBUTION

TANGENT ASSEMBLY

A1 A1

SECTION A1-A1

POLE CAP & OPGW

TANGENT ASSEMBLY

INSULATOR BRACKET

SEE DETAIL "E"

NOTE:

1. FLAT 10 WILL BE IDENTIFIED BY VENDOR

POST INSULATOR

MOUNTING BRACKET

SEE DETAIL "E"

4 10

PLAN VIEW

FOR STRUCTURES

9194 & 9195

FLAT 1

*DESIGN FOR FUTURE

DISTRIBUTION

*DESIGN FOR FUTURE

DISTRIBUTION

*DESIGN FOR FUTURE

DISTRIBUTION

N.T.S.

DETAIL F

DISTRIBUTION

INSULATOR

MOUNTING BRACKET

C1

SECTION C-C

TRANSMISSION

TANGENT ASSEMBLY

C1

INSULATOR BRACKET

SEE DETAIL "F"

8"

COMMUNICATION

COMMUNICATION

COMMUNICATION

DETAIL G

STRUCTURE ID

DETAIL

STRUCTURE ID

SEE DETAIL "G" 4-7/8"

3/

4"

KUA

STR TYPE

TOTAL LENGTH (FT)

EMBEDMENT LENGTH (FT)

BENDING MOMENT (F-K)

VENDOR NAME

YEAR OF MANUFACTURE

SE

E

ST

R

U C

TU

R

E D

R

AW

IN

G

F O

R

LO

C

AT

IO

N

C L

SPARE SPACE

FOR FIELD

STAMPING (STR.

NUMBER)

STENCIL MARK

WITH LETTER

1/2" HEIGHT

1/8"

1"

1" 9" 1"

1"

23/25"

HOLES

TYP.

STEEL POLE

INSULATOR

BASE

6"

DETAIL E

POST INSULATOR

MOUNTING

BRACKET

A A

'H

SE

E

TA

BL

E)

"D " S

EE

TA

BL

E

B B

GROUND LINE

1 6

9"

8' -4

3'

-6

3' -6

'-2

3' -8

3'

-8

5' -0

2'-0" 2'-0"

C C

5' -0

SECTION A-A

POLE CAP& OPGW DETAIL

SECTION B-B

69KV CONUDCTOR

AHEAD SPAN

BACK SPAN

SECTION C-C

13KV DISTRIBUTION

AHEAD SPAN

BACK SPAN

AHEAD SPAN

BACK SPAN

(+) TRANSVERSE

AXIS

(+) LONGITUDINAL

AXIS

(+) TRANSVERSE

AXIS

(+) LONGITUDINAL

AXIS

(+) TRANSVERSE

AXIS

(+) LONGITUDINAL

AXIS

DATE

CHECKED

ENGINEER

DATE

DRAWN CODE

AREA

PROJECT DRAWING NUMBER REV

REVISIONS AND RECORD OF ISSUENO

04-0123 STRUCTURE REPLACEMENTS

69KV TRANSMISSION LINE

TANGENT ASSEMBLY

CLL/GAI

IAP/GAI

JNR/GAI

02/19/2026

04-0123 1

S7508

ASSEMBLY INFORMATION

Assembly Number

Quantity Assembly Name

1 1 Pole

2 1 OPGW Suspension Assembly

3 3 69kV Suspension Insulator Assembly

4 6 Distribution Suspension Insulator Assembly

5 1 Steel Pole Grounding Assembly

6 1 Identification Plate

7 1 Cathodic Protection

SEE SECTION 5 FOR

FOUNDATION DETAILS

STEEL POLE

STRUCTURE INFORMATION

STRUCTURE

NUMBER CLASS

STRUCTURE

HEIGHT 'H'

(FT.)

Embedment Depth 'D'

(FT.)

9194 Custom 100' 27'

9195 Custom 105' 24'

STRUCTURE 9194 LOADS

STRUCTURE 9195 LOADS

DATE

CHECKED

ENGINEER

DATE

DRAWN CODE

AREA

PROJECT DRAWING NUMBER REV

REVISIONS AND RECORD OF ISSUENO

04-0123 STRUCTURE REPLACEMENTS

69KV TRANSMISSION LINE

TANGENT ASSEMBLY

CLL/GAI

IAP/GAI

JNR/GAI

02/19/2026

04-0123 1S7509

LOAD DIAGRAM

VE

RT

TRANS. (+)

S

P

P

P

D1 D2

C1 C2 C3

LONG. (+)

OUT OF PAGE

N NOTE:

1. WTRANS IS THE WIND LOAD APPLIED TO THE

STRUCTURE IN PSF. A SHAPE FACTOR OF 1.0

SHALL BE APPLIED.

2. THE DEAD LOAD OF THE STRUCTURE SHALL BE

MULTIPLIED BY K.

3. LIMIT POLE DEFLECTION TO 1% OF STRUCTURE

HEIGHT AT DEFLECTION LOAD CASE. LIMIT POLE

DEFLECTION TO 7% FOR ALL OTHER LOAD CASES.

4. CAMBERING IS NOT A PERMITTED METHOD TO

MEET THE ABOVE STATED DEFLECTION CRITERIA.

5. NO STRUCTURAL MEMBER SHALL BE DESIGNED

TO MORE THAN 90% CAPACITY BASED ON THE

DESIGN LOADS PROVIDED.

File details come from the government source that posted it. Updated .