Kirtland AFB Comm Division Specs 06 Sept 2023.pdf
PDF 808 KB Posted
- Attached to
- MHMV 210010, Site Preparation for Temporary Squad Operations Facility Federal contract opportunity
- Solicitation number
- FA940124B0002
About this file
This document appears to be a set of communications specifications for Kirtland Air Force Base. The key details are:
The specifications provide design criteria for planning telecommunications cabling and distribution systems for building construction and renovation efforts at Kirtland AFB. It covers requirements for the exterior communications plant, underground copper and fiber installations, manholes and duct systems, building entrances, telecommunications rooms, and interior wiring. Specific requirements are provided for items like conduit sizing, manhole placement and construction, cable types and terminations, and room sizing and layout. The document also outlines the roles and responsibilities of various stakeholders including the customer, Base Civil Engineering, the project manager, and the communications division. Certification requirements for installers and designers are also detailed. This document serves as a standard to promote common skills, interoperability, and maintainability of the telecommunications infrastructure across Kirtland AFB.
View the file
Other files for this federal contract opportunity
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Kirtland Air Force Base
Communications Specifications
September 2023
Kirtland AFB Communications Specifications
Contents
1. Background/Overview
2. General Purpose
3. Roles and Requirements
4. Exterior Communications Plant
5. Underground Copper Installation
6. Underground Fiber Installation
7. Manholes and Duct Systems
8. Building/Vault Entrance
9. Telecommunications (Comm) Rooms
10. Interior/Premise Wiring- General Requirements
11. Interior/Premise Wiring- Copper (CAT 6)
12. Interior/Premise Fiber
13. Switches
14. Telecom Outlets
15. Other Considerations
Appendixes……………………………………………………………….32
1. Background/Overview
1.1 These local standards have been established to minimize the long-term cost of the infrastructure, ensure interoperability and interface capability, and may only be changed when approved in writing by the Communications/Computer Systems Officer (CSO). These standards are intended to promote common skills among maintenance personnel throughout Kirtland Air Force Base and to minimize the necessity for excessive spare parts and variations in telecommunications equipment.
Revisions to this document will be prepared and distributed by the 377 Communications Division
(377 MSG/SC) when higher headquarters guidance, United States Air Force (USAF) communications standards, or other contributing agency standards warrant changes. Additionally, 377 MSG/SC recognizes the inherent need to maintain close interaction with Base Civil
Engineering and the Army Corps of Engineers on all project issues and invite comments or recommendations for changes to this document. Any reference obtained from this document to a specific product, process, or service does not constitute or imply an endorsement by the 377
ABW, the US Air Force, or the United States Government of the product, process, or service, or its producer or provider. All product and company names are trademarks™ or registered® trademarks of their respective holders. Use of them does not imply any affiliation with or endorsement by them.
2. General Purpose
2.1 The purpose of this instruction is to provide design criteria for planning telecommunications cabling and distribution systems for building construction and renovation efforts. Pre-wiring must be included in all Renovation/Repair and Military Construction (MILCON) projects to include.
All pre- wiring must comply with industry regulatory standards, UFC 3-580-01, and this instruction. Compliance with these instructions will improve maintenance by establishing a standard for communications systems facility. Department of Defense (DOD) publications direct the use of commercial standards whenever they meet DOD needs. The commercial standards referenced in UFC 3-580-01 must be followed along with this instruction.
2.1.1 This guidance is for all MILCON, Cabling Infrastructure, and Building
Renovation/Remodel/Repurpose projects within Kirtland AFB boundaries, whether managed/funded by Base Civil Engineering or Base Communications. DOE and other
(Kirtland AFB) partners are encouraged to adopt these standards to the maximum extent possible to ensure government investments are maintainable for the entire lifespan of the project/building/cabling.
2.1.2 The base CSO (377 MSG/SC) or designated authority should be contacted for approval/disapproval of any deviations to the criteria defined in this document.
3. Roles and Requirements
3.1 Customer Must:
3.1.1 The Customer is defined as the organization requesting the facility work which leads to the changes to the facility telecommunications cabling.
3.1.2 Share ideas with Base Comm as customers develop long range plans for mission requirements and building utilization- Cyber Plans & Programs (377 MSG/SCXP) so that the supporting infrastructure can be engineered. Communication regarding plan development can be shared through various modes of communication, such as AF332 submitted through Base CE or ECSRD 3215 requesting Comm support.
3.1.2 Identify work that will affect facility or infrastructure telecommunications cabling as early as possible and submit an ECSRD 3215 for Base Comm outlining any Comm requirements. At a minimum, this review should be accomplished before AF 332 submission to Base CE (377 MSG/CE). Base Comm is available to assist the customer with this task.
3.1.3 Brief changes in project scope at all design reviews, making sure to include Comm in at the earliest identification that Comm coordination will be required. Instances that will require Comm coordination may include planning of security or fire alarms, as well as office requirements for computers, faxes or printers, etc.
3.1.4 Tests must be conducted by the installer, reviewed, and accepted by Comm for any installed communications lines. Customers must not occupy facilities until AFTO form 747 is signed by all parties upon completion of the project.
3.2 Base Civil Engineering (CE) [377 MSG/CE] Must:
3.2.1 Ensure that submitted AF 332s are reviewed by 377 MSG/SC before final approval for the following types of work orders: New Buildings, Office Renovations, Repurposed/Rearranged Work Areas, Building Additions, Addition/Movement of facility walls, projects involving extensive digging/trenching, and Addition/Movement of Cubicles.
3.2.2 These types of work orders have a higher chance of requiring changes to building telecommunications cabling and distribution systems, and potentially require new cabling to be brought to the building.
3.2.3 If performing project management duties for the customer, CE must also have the duties outlined in section 3.3 – otherwise, CE must ensure that the duties outlined in section
3.3 are documented as responsibilities of the chosen project management agency.
3.3 Project Manager Must:
3.3.1 The Project Manager is defined as the individual from the project management agency having the responsibility of the planning, procurement and execution of ALL tasks of the project.
3.3.2 Provide all communications requirements to 377 MSG/SC once identified in the
Requirements Document stage. All project modifications which bring new communications requirements must be emphasized at the next design review. Status updates to Comm are required throughout the duration of the project.
3.3.3 Submit an ECSRD Work Order (WO or 3215) once personnel occupying the facility/renovation is determined - requesting a determination of necessary infrastructure to support customer requirements.
3.3.4 Project Manager assigned to the 377 MSG/CE Construction/Renovation project, must submit an ECSRD WO by 10% design review.
3.3.5 Ensure that the Final Design includes a set of dedicated draft drawings relevant to
Telecommunications. These drawings must depict telecommunications systems ONLY.
3.3.6 Dedicated draft drawings as defined above include:
• Man-Hole butterfly drawings
• Rack elevations
• Backboard design/layout
• Premise wiring layout
• Installation layouts for telecommunication systems
3.3.7 Allow 10 business days for the communications division personnel to review all design packages.
3.4 377 Mission Support Group, Communications Division, Plans/Programs (377 MSG/SCXP)
Project Manager(s) must:
3.4.1 Continuingly review Construction/Renovation Design Packages as the project progresses.
3.4.2 Coordinate with the Base Network Control Center (NCC) and Mission System teams to provide subject matter expertise with the incorporation of new infrastructure.
3.4.3 Coordinate with the Cyberspace System Integrator-Base (CSI-B) to provide communications assistance.
3.4.4 Inspect telecommunications system installations to verify compliance within specifications guidance.
3.5 Installer/ Contractor Certification requirements
3.5.1 Per UFC-3-580-01, Design and Engineering of Telecommunications Cabling and
Distribution systems must be performed and stamped by a Registered Communications
Distribution Designer (RCDD) for all projects.
3.5.2 Dedicated draft drawings utilizing electronic drawings, which are unable to be physically stamped, must be documented to be attributable to the RCDD. Design contractor must submit a copy of the RCDD’s certification to COR / contracting officer. Documents must be submitted in Visio and/or PDF.
3.5.3 Before cabling and distribution systems installation, companies must submit to the government project representative information documenting installer certification(s).
Submitters/Bidders are required to meet industry standards as part of the bidding process.
Bidders will be required to meet specifications outlined by Base Contracting (PK).
3.5.4 Certification(s) must be specialized in the installation of the type of cabling and equipment the installer will be working on.
3.5.5 Telecommunications contractor must submit certifications to COR/Contracting Officer for all personnel performing installations of telecommunications infrastructure and related equipment.
3.5.6 Telecommunications contractor must submit certifications to demonstrate their personnel meet BICSI (Building Industry Consulting Service International) or New Mexico
Construction Industries ES-7 Journeyman Certificate equivalency to the COR/Contracting
Officer who will utilize 377 SCXP to review submitted certifications.
3.5.7 A qualified installer must be onsite during all telecommunications cabling installation.
4. Exterior Communications Plant
4.1 For all construction or remodel; design installation, and related costs must be included in the project package. Customers will need to reach out to Comm to request identification of any buried cables before the project starts. Multiple service entrance locations are required for all facilities housing command and control systems to provide diverse, redundant, survivable service.
4.2 A burial marking tape must be laid in the backfill over the conduit bank, in accordance with
TIA 569B. This tape should be at least twelve inches below the finished grade and 24 inches above the conduit bank. The tape must be rated for at least 50 years direct burial. The tape must be at least 3 inches wide and marked every five feet with 2-inch-high wording similar to the following: WARNING: COMMUNICATIONS CONDUIT BURIED BELOW. Digging cannot occur within 4 feet of buried cable, only hand digging is allowed within 4-foot range either side of buried cable.
4.3 All cables must be tagged with all pertinent identification information at splice points, all traversing manholes and termination points.
5. Underground Copper Installation
5.1 To ensure protected, easily maintainable infrastructure, outside copper cable design must use conduit to the maximum extent possible.
5.2 When direct buried copper infrastructure is prudent, it must be identified and approved by 377
MSG/S at the earliest possible design phase. Customer is required to have a digging permit before digging can begin.
5.3 All splices must use 710 modules.
5.4 All splice cases must be bonded and grounded.
5.5 All splice cases must be stainless steel.
5.6 All copper splice cases must be pressure tested to not less 10 PSI.
5.7 Copper cable splices in manholes must remain pressurized after testing.
5.8 All copper cable splices must be re-enterable / gel filled in buried cases.
5.9 End plates in splice cases must be put together and installed properly according to assembly instructions.
6. Underground Fiber Installation
6.1 Single mode fiber optic cable (SM FOC) must be used. Building network connectivity must be supplied in accordance with the “Base Information Transport Infrastructure Wired Base Area
Network Technical Requirements Document”. Typically, a minimum of 12 strands SM FOC
(8.3/125 micron or better). Facility use and user requirements will dictate whether more fiber optic cable is required. All interior fiber connections must be LC connectors or match connectors to existing Light Interface Unit (LIU).
6.2 All FOC must be run directly, or “home run” from the closest ITB to the new facility.
6.3 Splice cases must meet the criteria established in sections 5.4 – 5.8.
6.4 All new fiber must be installed in multicell fabric innerduct and must include tracer wire.
6.5 For all base fiber optic cables between ITBs (backbone fiber), use a minimum of shielded 36
Strand Single Mode Fiber 8.3 micron with diverse routing to at least two other ITBs, consistent with long distance transport 10 Gigabit Ethernet protocol transmission equipment.
6.6 Fiber optic cable terminations must be performed by the installer and must provide manufacturer test results IAW TIA/EIA 568C.
7. Manholes and Duct Systems
7.1 All manholes must be designed and constructed to meet the requirements of all applicable commercial manuals.
7.1.1 The manhole numerical designation must be provided by 377 MSG/SC to ensure standardization and no duplication in designations with current infrastructure.
7.1.2 Manholes must provide a clear inside floor space measurement of 8’x12’. An alternate size of 6’x8’ may be approved only when no primary backbone cable passes through the manhole (lateral or dead-end service only). All manholes must provide a clear height no less than 7’. Conduit penetration banks must be at least 12” from the adjacent manhole wall and must not be centered. Conduits must enter the manhole 36-60 inches above the finish floor on the end and be perpendicular to the wall in approximate location. Mandatory items include grounding bus bar & rod, related conductors and wiring, a ladder or step, cable rack supports, a 50ft sump (French drain), pull in iron/anchor. See 7.5 and appendix A for more information on internal manhole preparations.
7.1.3 Manholes are to be located wherever a significant change in direction of the main conduit bank is needed, or a building feeder is to intersect the existing duct system. A
"significant change of direction" is defined as a change in alignment that would exceed the maximum total bend parameter allowed.
7.1.4 The manhole must be set on 6 inches of level. 90% compacted granular fill, ¾ to 1 inch size extending 12 inches beyond the manhole on each vertical side. Granular fill must be compacted by a minimum of four passes with a plate type vibrator.
7.1.5 Drain sumps must be provided for precast manholes, as required. Installation also must conform to the manufacturer's instructions. When required, the sump hole must drain through 2 feet of pea gravel to allow the manhole to completely drain into the ground.
7.1.6 Minimum Ground Cover. The top of the manhole chamber must be least 12 inches below grade.
7.2 Manhole Entrance
7.2.1 Access to the manhole is to be provided by a minimum 30-inch diameter opening centered over the top of the vault with the manhole cover having the stenciled numbering designation on the side that is exposed to the service.
7.2.2 The removable metal cover (aka LID) should be round, in accordance with specifications reliant on the estimated traffic/weight loads of the area. See Appendix A for an appropriate Manhole Neck/Lid.
7.2.3 All Neck/Lids must be of equivalent specifications to Appendix A.
7.2.4 Top access may require variable extension of the “neck” to reach ground surface level.
The manhole hatchway must be even with the finished grade of the surrounding terrain and must be no more than 3/8” above any highway surface, see Appendix A.
7.2.5 Locking manhole lids requirement specifications will be approved by 377 MSG/SC.
Round manhole lids should utilize Durashield-type locking mechanisms. Handholes requirement specifications will be approved by 377 MSG/SC.
7.3 Conduit/ Duct Systems
7.3.1 Manholes conduit penetrations are to be sealed against water seepage and finished inside the manhole to present a smooth, tapered entry. Unused conduits must be capped or plugged to prevent gases or wildlife from migrating between manholes. Planned conduit penetrations, such as for the main conduit bank or building feeder conduits, should be accommodated via "knock out panels" precast into the sides of the manhole.
7.3.2 Schedule 40 or better polyvinyl chloride (PVC) conduit must be used. A #10 AWG copper tracer wire or tracer tape must be installed 6" above the duct bank to assist in future location efforts. WTracer wire must be secured inside each manhole and securely fastened at the Primary Telecommunications Room (PTR). If steel pipe conduit is used, boring procedures must be followed that ensures protection of existing resources.
7.3.3 Conduit must be encased in concrete when minimum conduit depth of 24 inches cannot be attained, passing under paved roads/parking lots or high traffic area, driveways, railroad tracks or bend points that are subject to movement. These conduits must be extended an additional 3 feet on each side of the crossing for protection.
7.3.4 If the conduit must be curved, gentle sweeps must be used while maintaining a minimum radius of 25 feet. No section of conduit must contain more than two 90-degree bends between Manholes. All conduits must be sloped toward each opposing manhole at a slope of 3" per 100' of run to promote drainage of liquids.
7.4 Manhole Location
7.4.1 The maximum spacing requirement for manhole location is derived from ANSI/TIA
758-B. The design of conduit runs potentially sporting larger copper cables, will require less spacing.
7.4.1 Manholes installation is not preferred under roadways or other normal traffic ways. It is preferred that manholes be installed under walkways or under landscaped areas if they don't interfere with tree roots, etc.
7.5 Internal Manhole Preparation
7.5.1 Each manhole must be constructed to include common interior fittings. These are intended to support the use and management of the manhole. All exposed metal fittings must be rust resistant, typically galvanized steel. Note: See Appendix A for an example of racing hardware common to communications manhole.
7.5.2 A removable metal ladder is to be provided inside each manhole. The ladder must be used by staff to enter the manhole. It should be held in place at the top by metal loops or similar anchors and must rest on the bottom of the manhole. The ladder must be easily removable to facilitate cable installation and routing within the manhole.
7.5.3 Anchors for cable installation pulleys must be provided on all four sides of manhole walls.
7.5.4 Permanently installed lighting is not required in the manhole. At least 2 hanger loops are to be provided in the manhole ceiling to accommodate temporary utility lighting.
7.6 Grounding Rod
7.6.1 All manholes must have a 10 foot long by 3/4" diameter copper plated grounding rod installed through the floor of the manhole near one corner. The rod must protrude no more than 4 inches above the floor. The hole through the manhole floor must be sealed against seepage with either epoxy filler or Room Temperature Vulcanizing caulking.
7.7 The Conduit Banks
7.7.1 All primary backbone conduit locations must be reviewed by 377 MSG/SC, to ensure there are no conflicts with existing infrastructure or upcoming projects and plans.
7.7.2 The cables enter the Manhole near the sidewalls, allowing the incoming cable to align with the cable racks (splayed configuration). Manholes must be watertight through the use of appropriate seals/caps/bores.
7.7.3 The conduit banks (manhole-to-manhole) consist of a minimum of six (each) four-inch diameter conduits, arranged in a pattern 2 wide and 3 deep. The center-to-center spacing of the conduits is 6 inches, in both directions.
7.7.4 Manhole-to-Building conduits are to be sealed with foam sealant or capped airtight to prevent water from entering the Primary Telecommunications Room (PTR).
7.7.5 If a diverse path is required for fiber or copper, a minimum of four (each) 4” conduits, per diverse path, is required.
8. Building/Vault Entrance
8.1 The Building/Vault Entrance and PTR are often the same room. Appendix C displays a typical Entrance/PTR arrangement. Note: the connections between the BET and the distribution blocks are missing.
8.1.1 All cross-connections directly from the BET must be made by 377 MSG/SCO.
8.2 The contractor must provide underground exterior service gel filled cable, IAW Rural
Electrical Association (REA) standard PE-39, Specifications for Filled Telephone Cable, or PE-
89, Specifications for Filled Telephone Cable with Expanded Insulation, from main communications Building Entrance Terminal (BET) to the nearest manhole tie in point or splice case, which can provide sufficient vacant pairs to accommodate each facility with required circuits, plus 100% spare pairs, as determined by 377 MSG/SC.
8.2.1 Splice cases must meet the criteria established in sections 5.3-5.8.
8.2.2 A transition splice must be made between the exterior copper gel-filled cable and dry-filled intra-building cable in the PTR in accordance with TIA/EIA 569A.
8.2.3 In accordance with Underwriters Laboratories (UL) 497, all Building Entrance
Terminals (BET’s) must be provided with three-electrode gas tube or solid-state type 5-pin rated for the application. Provide gas tube protection modules in accordance with RUS
Bulletin 345-83 and must be heavy duty, A>10kA, B>400A, C>65A where A is the maximum single impulse discharge current in accordance with National Electrical
Manufacturers Association (NEMA) C62.61. The gas modules must shunt high voltage to ground, fail short, and be equipped with an external spark gap and heat coils, in accordance with UL 497. The number of surge protection modules must equal the number of pairs of exterior cable of the building protector assembly.
8.2.4 New Construction: Install a minimum of 25 pair #24 American Wire Gauge (AWG) copper outside plant cable. All splices for 24 AWG copper wire must be spliced using 710 modular splicing method. All splices must have a single (1) fold back (no inline splices).
8.2.5 Each building needing any form of network access must be supplied with a minimum of 12 Strand Single Mode (SM) Fiber in accordance with section 6.
8.3 Building Entrance Terminals (BET)
8.3.1 BETs must be stenciled according to designations provided by 377 MSG/SC.
8.3.2 All BETs must be provided with 5-pin element, 3B1E type gas tube protective modules and must provide equal protection to REA-PE-80, Specifications for Gas Tube
Surge Arrestors, specifications. All BETs must be mounted in a vertical arrangement but must not be stacked more than three high. Depending on pair count of the outside TP cables, a different BET size/style may be required.
8.3.3 BET used for the termination of outside TP cables, 300 pair and less in size, must have a built-in splice chamber with 710 type splice modules with 66B output with blocks
Circa model 1890ECS or equivalent.
8.3.4 BET used for the termination of outside TP cables, 301 to 600 pairs, must have cable stub input with 66B output with blocks Circa model 1890BC1-100K or equivalent. The stubs must be spliced to the incoming OP cable using a stainless-steel closure utilizing factory drilled end plates. See Appending D for examples of “typical” Vault Closure End-Plate
Designs.
8.3.5 BET used for the termination of outside TP cables, larger than 600 pair, must be 24
AWG stubbed central office protectors Circa model 4486 type blocks or equivalent. Frame verticals must be mounted to the backboard to support central office type blocks.
8.3.6 Plenum rated cabling is not required for OSP cable but is required once transition to building interior has been made.
8.3.7 The contractor must conduct appropriate testing to provide 100% continuity and pair-test results documenting opens, shorts, and grounded pairs through the Contracting
Officer/Representative to the 377MSG/SCXP office OPR.
8.3.8 FOC entering the building must terminate in the PTR in a 19” cabinet floor mounted
FOC or on a wall mounted patch panel with LC connectors or matching connectors to existing.
9. Telecommunications (Comm) Rooms
9.1 A Primary Telecommunications Room (PTR) must be provided by building occupants nearest the entrance of the fiber/copper run to the building for solely communications equipment.
Equipment can include Computer System (C-CS) switching and transmission equipment, (gateways, power supplies, etc.) main distribution frame(s), equipment racks, ladder racks, fiber optic cable terminations, patch panels, and other equipment needed for termination of the building's interior wiring systems and to interface the local service equipment with the exterior base cable system.
9.1.1 In accordance with Industry Best Practices, AF Design Requirements, Safety Instructions (AFI 91-203 / 30.1.1) and DISA Security requirements (STIGS IA-
12.02.01 & PH- 03.02.01) -- Telecommunication rooms must be a dedicated space, not shared with other functions, and must not be used for storage.
9.1.2 As a dedicated space, no other equipment, such as mechanical, plumbing equipment, and electrical panels must be placed in the Telecommunications Room (or TR), the TR must be free and clear of all obstructions to the height of 8’0” to provide adequate ventilation and cooling. General purpose storage is prohibited in all TRs.
9.1.3 The PTR must be located on the first floor with an interior door only and provide uninterrupted access by authorized personnel. All TR doors must be installed so the door will open out, must be solid core, and directly accessible. A controlled and secured access cypher keypad lock on all TRs is required to allow 24-hour uninterrupted access by authorized technicians See TRs Security section for additional information.
9.1.4 TRs other than the PTR will serve as a secondary interconnection point between the
CAT 6 outlets and the main communications frame in the PTR. Wall and floor space must be provided for installation and maintenance of equipment such as frames or backerboards.
9.1.5 Appendix C displays a typical entrance/PTR arrangement.
9.1.6 All station cable/patch panels in the TR must be tagged/labeled according to room and jack number to indicate its associated jack number and location. All LAN runs must be continuous from wall outlet to patch panels in the TRs.
9.2 Telecommunications Room Interconnections
9.2.1 For Horizontal cable connections between the PTR and other Telecommunications
Rooms within the same building, a minimum of 12 Strand Single Mode (SM) Fiber 8.3 microns must be used – along with a CAT 3 telephone tie cable.
9.2.2 For special situations requiring interconnections between TRs, in addition to the PTR connection, single-mode (SM) fiber optic cable must also be utilized. Cables must be labeled to document origin and destination of cable. Specifications for labelling requirements will be provided by 377 MSG/SC.
9.2.3 Tie cables must connect the PTR 66M1-50 blocks to the other TRs.
9.2.4 Tie cables must be sized based on the TR user’s phone requirements in accordance with 2 pairs/ user with 100% growth. For example: A TR supplying 50 traditional phones should have a tie cable of 200 pairs (2 pairs *50 Users * 2).
9.2.5 All interior fiber connections will use LC connectors or matching connectors to existing Light Interface Unit (LIU).
9.3 Telecommunications Room(s) Sizing and Location
9.3.1 The quantity and size of building TRs must comply with the standards and guidelines as shown below.
Table 1: TR Size Requirements
Building Usable Area
(Square Feet)
TR Size (Square Feet) Number of 4”
Entrance Conduits
<20,000 400 3
20,000 to 100,000 500 4
100,000 to 200,000 900 5
Every additional 200,000 600+ +1
9.3.2 More than one telecommunications room per floor is required if distance to a work area exceeds 295 feet, or if floor area served exceeds 10,000 square feet. Recommended room sizing is
10' x 11' for each 10,000 square-foot area served. Best practice is for this room to be designed with a 2:1 ratio in length to width.
9.3.3 TRs will be provided with space as required and must be situated in a centralized location within the building unless the cable distance exceeds 295 ft. (90M) from the TR to the desktop/wall jacks.
9.4 TR Operational Environment and Equipment
9.4.1 Connectivity from the telecommunications outlet jacks to the TR must be provided through conduit, painted to match CE building standards based on customer requirement, stubbed to above the finished ceiling using the most direct route available, complete with pull cords. A 6 inch wide by 2 inch deep, minimum, above the ceiling cable through/raceway may be used to connect rooms. Where cable trays are provided, conduits must be extended to the cable tray and be terminated. The through/raceway will run above the ceiling on the top of proper support structures using the most direct route between the TRs. Conduit fill must not exceed the 40% rule as stipulated in the National Fire Protection Association (NFPA) 70 and TIA/EIA.
9.4.2 Cabinets housing equipment must be seismically braced, IAW local Seismic Standard
4, and have a minimum of 3 feet of clearance along all sides to facilitate equipment installation and maintenance.
9.4.2.1 Cabinets that are placed side by side must maintain the clearance as outlined above, around the row of cabinets. Type 630B-8 wall plate or equivalent, containing a CAT 6 jack must be provided to support a wall mounted telephone in the PTR, other TRs, and all electrical/mechanical rooms. This wall plate must be mounted 60" above the finished floor.
9.4.2.2 New cabinets must have a Power Distribution Unit (PDU) with the following attributes/capabilities: provide a minimum of 20A to the rack equipment and have a minimum of TEN NEMA L5-20R output receptacles.
9.4.2.3 If designer chooses a horizontal PDU, PDU should be a maximum 1 RU.
9.5 TR Security
9.5.1 A controlled and secured access cypher keypad lock on the TR is required to allow 24- hour uninterrupted access by facility managers and authorized technicians.
9.5.2 For TR storing inspectable SIPRNET, the installed exterior door lock must meet the latest revision of Federal Specification FF-L-2740.
9.5.3 DoD and USAF Communications security specifications require 377 MSG/SC to limit communications equipment access to 377 MSG/SC personnel and designated contractors – therefore, the use of “open” racks is not acceptable. All TR cabinets must be lockable and contain only equipment owned/operated by 377 MSG/SC.
9.5.4 Customer network equipment, supporting networks other than NIPR/SIPR, cannot be stored within the same cabinet.
9.5.5 Building designs must incorporate additional rack(s)/cabinet(s) for customer networking equipment.
9.6 Backerboards
9.6.1 BETs are required for all primary TRs. All required BETs or block terminations must be mounted on an 8’ x4’ x ¾” exterior plywood backerboard. The backerboard must be flame retardant or covered with flame retardant coating. The backerboard must be installed vertically, a minimum of 9” above the finished floor.
9.7 Power Requirements
9.7.1 A dedicated four-gang 115V, 60 Hertz power outlets on separate Ampere (A) circuit with isolated ground must be installed on each wall and also placed within equipment cabinets for use to power telecommunication devices. Additionally, a minimum of two-gang, 220-240 VAC 30-
Amp power outlet circuit with isolated ground for use in powering uninterruptable power supply
(UPS) must also be provided. Depending on customer UPS requirements, additional outlets may be required.
9.7.2 Ground all devices, cable sheaths, protectors and other equipment in accordance with applicable T.O.s, ANSI/TIA/EIA 607, MIL Standard 188-124B, and the NFPA 70. Provide a single-point ground for all communications/electronic equipment for the building within the TR.
9.7.3 Provide a telecommunications main grounding bus bar (TMGB) at a minimum of 6 inches high by 24 inches long. The ground riser from the ground plate to the single main electrical service entrance ground must be a #1 AWG or larger copper conductor directly connected to the ground plate with no taps. Per Mil standard, 188-124B, the resistance of the ground riser must be
10 ohms or less measured from the main building ground point. All connections of wire-to- wire and/or wire-to-ground rod must be exothermic-welded. Extend #6 AWG or larger copper ground wires from the TR ground plate to each secondary TR within the building and connect a telecommunications grounding bus bar (TGBB) in the TR.
9.8 Operational Environment
9.8.1 Temperature/humidity: A temperature-controlled environment is required in all TRs. Provide heating, cooling, and fresh air appropriate for the equipment housed. Maintain a positive pressure inside the room to reduce the entry of dust. Normal operating ranges should be as locally established for employee comfort, typically between 65°F to 78°F. There are no special relative humidity requirements. However, in order to minimize static discharge and condensation it is recommended that the relative humidity be between 20% and 60%.
9.8.2 Lighting: Sufficient lighting must be provided in all TR areas to promote a safe and acceptable work area. Switched lighting must be provided in all TR areas, adequate to promote work with small fiber items and miniature lettering devices. Maintain a minimum of 12" clearance between fluorescent “ballasted” light fixtures and all cable runs and cable devices. Provide a minimum of 538 lux (50 foot-candles) of illumination measured 1 meter (39 inches) above the finished floor.
10. Interior/Premise Wiring
10.1 Regardless of the interior wiring cable used, the following requirements apply to ALL
Interior/Premise Wiring:
10.1.1 Distribution frames and interior conduits/cable trays must be of sufficient size to allow for 100% growth and must not exceed the 40% fill rule stipulated in the NEC NFPA
70, National Electrical Code.
10.1.2 Installation of all interior pre-wiring to include the TRs, must be performed to ensure termination as required back to the PTR.
10.1.3 Each cable must be marked with an adhesive type strip marker at both ends. Affix a permanent label to the outlet jack cover to clearly identify the outlet with the corresponding termination jack on the patch panel or termination block. Handwritten or manual embossing labels are NOT permitted. Automated embossed labels are preferred, such as Brothers P-touch systems utilizing 1/4-inch labels, with 1/8-inch lettering.
10.2 Premise wiring supporting the following networks should utilize the color code identified in
Table 3. *Note- uncommon color wiring may have extensive lead times, purchasing parties should plan accordingly.
Table 3 Building Cabling/Drop Color Designation
Network Cabling Color
NIPR/VOICE Green
SIPR Red
JWICS Yellow
DREN Purple
Special Access Networks Orange
Audio-Visual (AV) White
Commercial / Internet (non-Gov owned) Black
10.3 Conduits and Cable Trays (Interior)
10.3.1 For new installations, and renovations, circuit connectivity from the telecommunications outlet jacks to the TR must be routed through conduit sufficient in size as not to exceed the 40% rule as stipulated in the National Electrical Code (NEC), National Fire Protection Association
(NFPA) 70. Conduits must be installed above the finished ceiling, using the most direct route.
Cable trays/raceways may be used to connect rooms provided that plenum type cable is used. If cable trays are used, conduits must be extended to and terminated at the cable tray; empty conduit must have pull strings installed. The cable tray/raceway must run above the ceiling, using an independent support structure, and using the most direct route between points. "J" hooks may be used with prior approval from 377 MSG/SC for distribution of wiring.
10.3.2 Where multiple TR rooms are required, attention must be given to their strategic placement to support interconnection via 4-inch conduit or 6 inch wide by 2- in ch -d eep minimum cable trays between each room as well as to the PTR in which the cable head/fiber connections are to be located. In existing buildings, plenum jacketed cables may be used, where allowed by national building codes, without the noted conduits, if properly supported.
11. Interior/Premise Wiring- Copper (CAT 6)
11.1 Interior CAT 6 wiring must be four pair, 24 American Wire Gauge (AWG), solid copper conductor, CAT 6, Underwriters Laboratories (UL) tested and certified.
11.2 Each cable must be dedicated to one device or outlet only and must be terminated on the TR patch panel in accordance with T-568B.
11.3 Cables must be terminated in a 110 style, 48 port, 19-inch, cabinet mounted, CAT 6 patch panel located in the appropriate TR.
11.4 The patch rack(s) will contain two sets of patch panels. One larger group (Set A) supporting connections to all wall jacks, and a smaller group (Set B) for interconnection to the CAT 3 telephone tie cable.
11.4.1 Set A patch panels must be terminated on the panel in accordance with T-568B.
11.4.2. Set B panels consist of 48 port, 19-inch cabinet mounted, CAT 6, RJ45 voice grade, patch panels containing a minimum number of jacks equal to 75% of the pair count of the tie cable supplying the TR.
11.4.2.1. Set B panel jacks must be wired with both dual-pair and single-pair jacks. 50% of the cable pair count must be allocated to dual-pair jacks. The second half of the cable pair count will be allocated to single-pair jacks.
11.4.2.1.1. Dual-Pair jacks must utilize two pairs from the telephone tie cable connected to the terminals corresponding to pair 1 and pair 3 of T-568B.
These are the “inner” pairs of the RJ-45 jack.
11.4.2.1.2. Single-Pair jacks must utilize one pair from the telephone tie cable connected to the terminals corresponding to pair 1 of T-568B.
11.5 Suitable patch cords for user end equipment must be provided by the installer as part of the project.
12. Interior/Premise Fiber
12.1. Single mode fiber optic cable (SM FOC) must be used for outside and inside premise. All interior fiber connections will use LC connectors or matching connectors to existing Light Interface Unit (LIU).
12.1.1. Fiber optic cable terminations must be performed by the contractor and must provide manufacturer test results IAW TIA/EIA 568C. Testing equipment must have passed calibration within five calendar years prior to date of testing. Project acceptance will be contingent on “pass” results of testing.
13. Switches/ Network Equipment
13.1. Switching needs are highly dependent on the location and specialized systems being used.
Early coordination with 377 MSG/SC will ensure that areas and customer needs are properly understood, so that an accurate switching solution can be provided.
13.2. Customers are required to purchase network switching equipment. Projects may require additional switching capability if more personnel will occupy facility.
14. Telecom Outlets
14.1. In general office areas, use a dual modular telecommunications outlet at minimum, with two 8pin/8 position CAT 6 modular Uniform Service Order Code RJ-45 type jacks mounted in a single face plate (one for voice/one for data) in a factory-made assembly. All wall outlet components must have a removable outer bezel with molded labeling and coloring to match wiring identifying the outlet usage (see Figure 1). Communication jacks installed in or under the floor must have dust covers installed on the individual jacks. Enclosure covers with seals must be used to prevent moisture and debris from entering the enclosure. All inside wire used for telecommunications outlets must be four pair, 24 American Wire Gauge (AWG), solid copper conductor, CAT 6, Underwriters Laboratories (UL) tested and certified.
14.2 All fiber optic jacks must accommodate LC connector.
14.2.1. Fiber is not required to be installed to the desktop at this time due to increased equipment cost, maintenance complexity, with no overall increase in performance.
14.3 Each cable must be dedicated to one device or outlet only.
14.4 Only plenum rated cable may be used whenever cable is installed and exposed within air circulation areas.
14.4.1 Telecommunication outlets must be mounted 18" above the finished floor, to the centerline of the cover plate, unless noted otherwise.
14.4.2 Place phone/data/Local Area Network (LAN) outlet jacks along every wall or one every 8 feet apart or for every 40 square feet; whichever provides a higher outlet density. All other locations must be provided with an outlet density as determined and approved by 377
MSG/SCXP.
14.4.3 Outlet Jacks must be labeled in accordance with Figure 1 to provide critical information for maintenance actions.
Figure 1. Four-Gang Wall Plate Numbering
15. Other Considerations
15.1 Security
15.1.1 See section 9.5.4 for information specific to TR security.
15.1.2 Classified requirements may vary and shall be taken on a case-by-case basis.
15.1.3 Special attention will be given to the space, security, ability to inspect conduit containing comm wiring and separation required for placement of classified systems to ensure security countermeasures are met.
15.1.4 For customers requiring a Protected Distribution System (PDS), they must coordinate with the 377 ABW Information Protection Office (377 ABW/ IP).
15.2 Critical End Buildings
15.2.1 Critical End Buildings, or CEBs supporting the highest priority missions require a
CEB designation by the 377 MSG/SC Director. Customers must submit a ECSRD 3215 outlining their requirement for CEB designation and provide a mission brief for the 377
MSG/SC Director.
15.2.2 CEBs require multiple design considerations. CEBs shall be designed in accordance with the latest Base Information Transport Infrastructure (BITI) Wired Base
Area Network (BAN) Technical Requirements Document (TRD) which outlines all
USAF expectations.
15.3 Geospatial Mapping/ Surveying
15.3.1 Geospatial Mapping/Surveying data is required to be submitted for all work outside the bounds of footprints of buildings. This includes all outside plant infrastructure features and communications pathways that are installed/modified.
15.3.2 Example of Outside Plant features include manholes, vaults, pedestals, underground cables, marked direct buried splices, terminals etc.
15.3.3 Examples of communications pathways include duct routes, direct-buried cable, and communication pathway entry points on building exterior walls that lead to interior building entry terminals, etc.
15.3.4 Geospatial Mapping / Surveying must be accomplished in accordance with
Appendix B - GUIDANCE FOR GEOSPATIAL DATA
15.4 Classified Systems (Secure Internet Protocol Router Network (SIPERNET) and Defense
Red Switch Network (DRSN))
15.4.1 Customers must assign a supply custodian (CA/CRL) for all unit cryptographic devices used in support of their secure systems.
15.4.2. Customers must identify classified message traffic or telephone requirements and coordinate all requirements with the 377 MSG/SC Plans and the Information
Assurance Flights to ensure proper compliance measures are attained.
15.5 Modular Furniture
15.5.1. Telecommunications jacks must be direct run without intermediate connections.
There should only be one CAT 6 jack between the TR and the customer’s equipment.
15.5.2. Each Modular Furniture cubicle must have a four-gang jack configuration for standard CAT6 RJ-45 jacks. Label these jacks under the same standard as wall jacks
(See Figure 1).
15.5.3. Suitable patch cords for user end equipment must be provided by the installer.
15.6 Periodic, Final Inspections, Testing and Documentation
15.6.1. All telecommunications cable must be certified and tested utilizing test equipment in accordance with TIA/EIA standards with Microsoft compatible soft-copy test result to be provided to the 377 MSG/SC. Certified testing equipment is required to complete testing, with calibration of testing equipment to have been completed within five calendar years prior to date of testing. Project acceptance is contingent upon “pass” of testing. Where deficiencies of any type are discovered upon testing, the contractor must make all necessary repairs, including replacement, if necessary, at no cost to the government.
15.6.2 Two groups of acceptable digital records must be provided to 377 MSG/SC prior to final acceptance: (1) cable certification records (2) revised drawings which reflect the actual “as built” conditions.
15.6.3 All communications drawings must be geospatially referenced and include the conduit, innerduct, cable types, cable count, cable size, and length. All manholes and pull boxes must have complete butterfly details to include geospatially referenced location, entry points, grounding, bonding, racks/ladders, or other equipment installed.
See Appendix B for more information on GPS survey requirements.
15.6.4 377 MSG/SC personnel will conduct in-progress inspections during construction.
The general contractor performing the work is solely responsible for scheduling inspections and providing response to the government for inspection findings. These inspections must be scheduled with 377 MSG/SC before backfilling or installation of walls. Trenches may be inspected to verify conduit size, quantity, cable type, earth cover compliance, and updated "red line" cable record or contract drawings.
15.6.5 All installed cables must be tested by the installer and may be in the presence of
377 MSG/SC personnel or its representatives. Baseline test records must be provided to the 377 MSG/SC in printed and digital format.
15.6.6. The Communications Division shall not assume maintenance responsibility until
AFTO form 747 is signed by all parties.
Appendix A – Example Manhole & Neck/Lid Specifications
Any reference obtained from this document to a specific product, process, or service does not constitute or imply an endorsement by the 377 ABW, the US Air Force, or the United States Government of the product, process, or service, or its producer or provider. All product and company names are trademarks™ or registered® trademarks of their respective holders. Use of them does not imply any affiliation with or endorsement by them.
Neck/Lid Specifications
Appendix B – Guidance for Geospatial Data
Geospatial/mapping data is required to be submitted for all work outside the bounds of footprints of buildings and structures. Contract deliverables that involve maps or other geospatial data must be delivered in a geo-referenced GIS (Geographic Information System) format. For vector data, this will be an ESRI personal geodatabase format (10.x) unless otherwise approved by the IGI&S (Installation
Geospatial Information and Services). For raster data, this must be an ESRI compatible format.
All contract deliverables listed below that involve mapping or other geospatial data must meet the following requirements:
These deliverables include, but are not limited to:
• Site plans
• Record drawings
• Engineering designs, plans or surveys
• Topographic surveys or studies
• Boundary or Cadastral surveys
• Master Plan drawings
• Utility (water, sewer, power, storm, etc.) designs, plans, surveys and studies
• Pavement, Grading, or Excavation plans
• Soil/Geology studies or surveys
• Environmental assessments, surveys, studies, or plans
• Historical or Archaeological surveys, studies, or plans
A. SDSFIE Data Standards/Structure
All geospatial and associated data must comply with the latest version of Spatial Data Standards for
Facilities, Infrastructure, and Environment (SDSFIE) available from the CADD/GIS Technology
Center at http://tsc.wes.army.mil/products/TSSDS-TSFMS/tssds/html/. These data must be organized using the most recent SDSFIE specifications for entity naming conventions, attribute fields, domain names, and topology.
B. Data Structure (GIS ESRI format)
1) The Contractor must provide a quality control (QC) report that must state whether all inconsistencies in the data generated were corrected, or it must detail the remaining errors by case. The Contractor must utilize topology ArcGIS 10.X or later to assure that there are no overshoots or undershoots in the line work, slivers or dangles in polygons. The quality report must identify the software (name and version) and satisfy these conditions:
a. The edges of all digitized vector data or raster imagery must exactly match digitally with those of all adjacent maps.
b. The digital representation of the common boundaries for all graphic features must be exactly the same, regardless of feature layer. Each feature within a theme must be represented by a single graphic element (e.g., polygon, line).
c. Lines, which represent the same graphic element, must be continuous (i.e., not broken or segmented), unless that segmentation reflects a specific visual line type. Lines representing the same type of data must not cross except at intersections.
d. Polygons must be closed (i.e., the first x- and y-coordinates must exactly match the last x- and y-coordinates). Polygons of the same layer must not overlap and must cover the area of interest completely (i.e., have no gaps in coverage).
e. Straight lines must be represented by only the beginning and ending x- and y-coordinate points.
Line strings must not cross back on themselves or be of zero length.
f. All symbol libraries, font libraries, text size, text format, and text placement must be prepared in accordance with and conform to the Spatial Data Standards for Facilities, Infrastructure and
Environment (SDSFIE) Release 3.0.
g. The Contractor must not develop new libraries without prior written approval from the
Government.
2) Survey
Global Position Systems (GPS) or comparable traditional survey methods will be used to collect geospatial data (e.g., northing, easting, and elevation above or below the Earth's surface) for all contract activities where geospatial data is involved. For construction purposes this data must be obtained at the time of construction and prior to burial in the case of underground utilities. Survey methods must meet accuracy standards for actual results.
3) Accuracy
Information must be collected at no less than 1:1200 scale (1”=100ft) for base areas and 1:4800
(1”=400ft) for areas outside of the base boundary. All data must be collected within submeter accuracy, except for utilities underground data, which must be collected at survey grade accuracy of 1 foot or less. This data must meet or exceed National Map Accuracy Standards at the corresponding scales. Delivered data must meet these accuracy standards at no less than 95%.
4) Projection/Coordinate System
Geospatial data must be delivered in a georeferenced GIS (Geographic Information System) format.
All geospatial data must be delivered in the…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .