Kellogg_Park_Nature_Center_-_100%_Electrical_Submittal.pdf
PDF 1 MB Posted
- Attached to
- Kellogg Park Nature Center State and local contract opportunity
- Solicitation number
- 25-07
- Issued by
- Bay County, Florida
About this file
This document is an electrical submittal for the Kellogg Park Nature Center project in Walton County, Florida, prepared by Stokes Architectural, Inc. and HG Engineers. The electrical drawings provide comprehensive details for a new nature center facility, including site electrical plans, floor plans for power and lighting, electrical legends, and technical details for electrical systems and grounding. The plans cover electrical equipment placement, lighting controls, receptacle locations, panel specifications, and electrical distribution infrastructure for the facility.
The electrical submittal includes detailed technical specifications for power distribution, featuring a 120/208V panel with 3-phase, 4-wire service rated at 22,000 AIC, and a grounding system with specific installation requirements. The design incorporates various electrical components such as occupancy sensors, vacancy sensors, wall switches, receptacles, and lighting fixtures, with careful attention to mounting heights, circuit configurations, and compliance with National Electrical Code (NEC) standards. The project appears to be a permit-level design, with drawings stamped as "100% PERMIT DRAWINGS" and signed by licensed professional engineers, indicating it is prepared for final review and construction permitting.
View the file
Other files for this state and local contract opportunity
Show all 46
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E L E C T R I C A L G E N E R A L N O T E S A. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO INSTALLATION. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR EXACT SIZE AND LOCATION OF
EQUIPMENT WHICH IS FURNISHED BY OTHERS AND CONNECTED BY ELECTRICAL.
B. RECEPTACLES, SWITCHES AND COVERPLATES COLOR SHALL BE SELECTED BY THE ARCHITECT FROM STANDARD COLORS.
C. VERIFY ALL DOOR SWINGS WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGHING-IN WALL FOR SWITCHES.
D. LOCATION OF LIGHTING FIXTURES, DISCONNECT SWITCHES, ETC. FOR MECHANICAL EQUIPMENT/ROOM SHALL BE COORDINATED WITH FINAL MECHANICAL EQUIPMENT LOCATION TO
PROVIDE NATIONAL ELECTRIC CODE REQUIRED ACCESS SPACE.
E. FINAL CONNECTION TO ALL MOTORS SHALL BE WITH FLEXIBLE CONDUIT CONNECTION.
F. ALL EXIT AND EMERGENCY FIXTURES SHALL BE CONNECTED TO LIGHT CIRCUIT AHEAD OF LOCAL SWITCH.
G. ALL PANELBOARDS, BACKBOARDS, TERMINAL CABINETS, ETC SHALL HAVE CUSTOM ENGRAVED MICARTA NAMEPLATE MECHANICALLY AFFIXED IDENTIFYING SYSTEM.
H. PROVIDE GREEN GROUND CONDUCTOR IN ALL CIRCUITS - SIZE PER N.E.C.
I. ALL EXPOSED CONDUITS, BOXES, STRAPS AND HANGERS IN THE CONTRACT AREA WHETHER NEW OR EXISTING THAT ARE PART OF THE ELECTRICAL SYSTEM SHALL BE PAINTED TO
MATCH ADJACENT FINISH.
J. PROVIDE CONCRETE MARKER AT END OF ALL CONDUITS STUBBED OUT OF BUILDING FOR FUTURE USE. MARKER SHALL BE 6" DIA X 18" HIGH WITH 2" ABOVE FINISHED GRADE. INSCRIBE IN TOP OF MARKER "E" FOR ELECTRICAL,"T" FOR TELEPHONE,"V" FOR TV CABLE,"F" FOR FIRE ALARM, AND "IC" FOR INTERCOM.
K. GENERAL CONTRACTOR SHALL FIELD-VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING ANY WORK, AND SHALL IMMEDIATELY NOTIFY THE ARCHITECT OF ANY DISCREPANCIES.
FAILURE TO DO SO INDICATES THAT THE CONTRACTOR ACCEPTS THE CONDITIONS AS THEY EXIST, AND SHALL PERFORM THE WORK REQUIRED AS SHOWN AND SPECIFIED.
L. THE ELECTRICAL CONTRACTOR SHALL OBTAIN AND REVIEW THE MECHANICAL AND SPECIAL EQUIPMENT SUBMITTALS PRIOR TO SUBMITTING THE ELECTRICAL SUBMITTALS. ANY ELECTRICAL EQUIPMENT, CONDUIT, AND WIRE SIZE CHANGES RESULTING FROM THIS REVIEW SHALL ALSO BE SUBMITTED FOR APPROVAL.
M. THE ELECTRICAL CONTRACTOR SHALL PROVIDE FAULT CURRENT CALCULATIONS FOR THE SERVICE EQUIPMENT AND SHALL MARK THE EQUIPMENT WITH THE AVAILABLE FAULT CURRENT AND DATE OF THE CALCULATION PER NEC 110.24. REFER TO TYPICAL SERVICE EQUIPMENT FAULT CURRENT LABEL DETAIL.
N. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ARC FAULT LABELS PER NFPA 70E ARTICLE 110.16 FOR NEW EQUIPMENT. THE OWNER SHALL PROVIDE AVAILABLE CALCULATION DATA FOR THE EXISTING EQUIPMENT IN THE ELECTRICAL SYSTEM. REFER TO TYPICAL ARC FLASH HAZARD LABEL DETAIL.
O. PROVIDE NEUTRAL AT ALL LINE VOLTAGE SWITCH LOCATIONS PER N.E.C. 404.2(C).
P. PROVIDE BUSHINGS ON ALL CONDUIT.
Q. COMPLY WITH ALL LOCAL CODE, LAWS, AND ORDINANCES APPLICABLE TO ELECTRICAL WORK, THE STATE BUILDING CODE AND THE NATIONAL ELECTRIC CODE. OBTAIN ALL PERMITS
REQUIRED BY LOCAL ORDINANCES.
R. OBTAIN ARCHITECTS APPROVAL OF ALL LIGHT FIXTURES, SWITCHES, RECEPTACLES, PANELBOARDS, ETC. PRIOR TO PURCHASING.
S. THE ELECTRICAL WORK SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. ALL NOT SO INSTALLED SHALL BE REMOVED AND REPLACED AT NO COST TO THE OWNER.
T. ALL WORK SHALL BE INSTALLED IN CONCEALED TYPE CONSTRUCTION. UNDERGROUND CONDUITS UP TO FIRST BOX IN CONCEALED CONSTRUCTION MAY BE SCH.40 PVC. EXTERIOR EXPOSED WORK SHALL BE I.M.C. BRANCH CIRCUIT CONDUIT RUN IN OPEN SPACES ABOVE CEILING OR IN WALLS MAY BE THINWALL (E.M.T.) CONDUIT 1/2" MIN. SIZE.
U. ALL CONDUCTORS LESS THAN 100A. SHALL BE COPPER #12 & #10 SOLID, #8 AND LARGER STRANDED, #6 AND SMALLER TO BE TYPE THWN, 600 VOLT INSULATION AND TYPE THWN OR THHN FOR #4 AND LARGER. ALUM. CONDUCTORS MAY BE USED FOR 100A. AND LARGER ONLY WHERE USED WITH COMPRESSION TERMINATIONS.
V. PROVIDE GROUNDING PER NATIONAL ELECTRIC CODE.
W. THE CONTRACTOR SHALL LEAVE THE ENTIRE ELECTRICAL SYSTEM INSTALLED IN PROPER WORKING ORDER, AND SHALL REPLACE WITHOUT ADDITIONAL COST, ALL WORK OR MATERIAL WHICH MAY DEVELOP DEFECTS, (ORDINARY WEAR AND TEAR OR DAMAGE RESULTING FROM IMPROPER HANDLING EXCEPTED) WITHIN A PERIOD OF ONE (1) YEAR FROM THE DATE OF
FINAL ACCEPTANCE BY THE OWNER.
EXIT SIGN; BACK MOUNTED; ARROWS AS NOTED; SHADED SECTION INDICATES LIGHTED FACE OF EXIT SIGN
HAND DRYER; MOUNTED FLUSH IN WALL WITH BLANK COVER
A-1 ADJACENT TO ARROW INDICATES HOMERUN OF CIRCUIT NO. 1 TO PANEL A; "B" INDICATES FIXTURE TYPE; MARKS ACROSS RACEWAY RUN INDICATES THE NUMBER OF NO. 12 CONDUCTORS; UNLESS NOTED OTHERWISE NO MARKS INDICATES TWO NO. 12 CONDUCTORS AND ONE NO. 12 GREEN GROUND CONDUCTOR IN 1/2" CONDUIT
1' X 4' FIXTURE; CEILING MOUNTED; ARROW INDICATES LENS DIRECTION
(2#12 & 1#12 GND-1/2"C)
WALL BRACKET FIXTURE
E L E C T R I C A L L E G E N D A-1 'B'
DUPLEX RECEPTACLE; 125V; 20A; 3 POLE GND; MT 18" AFF TO C/L UNLESS NOTED OTHERWISE; NEMA 5-20R; HUBBELL SERIES HBL5352
DUPLEX RECEPTACLE; 125V; 20A; 3 POLE GND; GFI; MT 18" AFF TO C/L UNLESS NOTED OTHERWISE; NEMA GF-5-20R; HUBBELL SERIES GF5362
LETTERS "WP" ADJACENT TO SYMBOL INDICATES GFI WEATHER RESISTANT RECEPTACLE; HUBBELL HBLGFBFHP20 SERIES WITH WEATHERPROOF COVER;
QUAD RECEPTACLE; 125V; 20A; 3 POLE GND; MT 18" AFF TO C/L UNLESS NOTED OTHERWISE; NEMA 5-20R; HUBBELL SERIES HBL5352
LETTERS +XX" ADJACENT TO SYMBOL INDICATES RECEPTACLE MOUNTING HEIGHT.
QUAD RECEPTACLE; 125V; 20A; 3 POLE GND; GFI; MT 18" AFF TO C/L UNLESS NOTED OTHERWISE; NEMA GF-5-20R; HUBBELL SERIES GF5362
HUBBELL/TAYMAC MR420CW COVER.
EXHAUST FAN; FURNISHED BY OTHERS
NON-FUSED DISCONNECT SWITCH; AMP SIZE AS NOTED
RACEWAY INSTALLED CONCEALED IN WALLS AND/OR ABOVE CEILING
RACEWAY INSTALLED CONCEALED IN FLOOR SLAB AND/OR BELOW GRADE
RACEWAY INSTALLED EXPOSED
CONDUIT STUB UP WITH FLEXIBLE CONDUIT CONNECTION TO EQUIPMENT
FLEXIBLE CONDUIT CONNECTION
WALL SWITCH; 120/277V; 20A; 1 POLE; A.C. ONLY; MT 48" AFF TO C/L; HUBBELL SERIES HBL1221
PANEL; 120/208V; MT 72" AFF TO TOP
LOW VOLTAGE WALL SWITCH; CONNECT TO NON-NETWORKED ROOM CONTROLLER; MT 48" AFF TO C/L; REFER TO SPECS; REFER TO LIGHTING CONTROL DETAILS. NUMBER "#" INDICATES BUTTON COUNT; REFER TO LOW VOLTAGE SWITCH MATRIX FOR SPECIFIC INFORMATION.
LIGHTING CONTROLS ROOM CONTROLLER; INSTALL CONCEALED ABOVE CEILING SPACE; REFER TO LIGHTING CONTROLS DETAILS
LOW VOLTAGE OCCUPANCY SENSOR; 360° DUAL-TECHNOLOGY TYPE; CEILING MOUNTED; UNLESS OTHERWISE NOTED; REFER TO LIGHTING CONTROLS DETAILS
LOW VOLTAGE VACANCY SENSOR; 360° DUAL-TECHNOLOGY TYPE; CEILING MOUNTED; UNLESS OTHERWISE NOTED; REFER TO LIGHTING CONTROLS DETAILS
- LIGHTSLTS
- UNLESS NOTED OTHERWISE
- WEATHERPROOF
- CONDENSING UNIT
- AIR CONDITIONER
- WATER HEATER
- RECEPTACLE
WP
COND
A/C
WH
UNO
REC
- CENTERLINE
- EXHAUST FAN
- ABOVE FINISHED FLOOR
ABBREVIATIONS
- GROUND FAULT PROTECTION
- GROUND CONDUCTOR
- ELECTRICAL CONTRACTOR
- CONDUITC.
C/L
EC
GND
LTG
GFI
EF
- LIGHTING
AFF
- INTERMEDIATE METAL CONDUITIMC
- POLYVINYL CHLORIDE CONDUITPVC
- ELECTRICAL METALLIC TUBINGEMT
- NATIONAL ELECTRIC CODE (NFPA-70)NEC
- NATIONAL FIRE PROTECTION ASSOCIATIONNFPA
PHOTOCELL; REFER TO LIGHTING CONTROL DIAGRAM
WALL MOUNT LINEAR FIXTURE
LIGHTING CONTROL GENERAL NOTES
A. THE DIAGRAMS ARE NOT INTENDED TO SHOW EXACT QUANTITIES OF DEVICES. REFER TO PLAN FOR ESTIMATED DEVICE QUANTITIES AND LOCATIONS.
C. THE LOCAL DEVICE INTERCONNECTIONS FOR ALL LIGHTING CONTROL DEVICES SHALL BE OF THE TOPOLOGY FREE TYPE.
D. COLORS FOR ALL DEVICES AND DEVICE COVERS SHALL BE SELECTED BY THE ARCHITECT.
E. ALL DATA LINE SWITCHES SHALL INCLUDE CUSTOM ENGRAVED LABEL INDICATING FUNCTION OF SWITCH. COORDINATE EXACT LABEL DESCRIPTIONS WITH OWNER PRIOR TO INSTALLATION.
F. PROVIDE ADDITIONAL POWER AND CONTROL MODULES AS RECOMMENDED BY THE SYSTEM SUPPLIER.
G. THE DIAGRAMS REPRESENT A TYPICAL SYSTEM AND ARE NOT INTENDED FOR INSTALLATION, SYSTEM SUPPLIER SHALL PROVIDE INSTALLATION DRAWINGS AND WIRING DIAGRAMS.
H. E.C. SHALL COORDINATE FIELD PROGRAMMING OF LIGHTING CONTROL SYSTEM WITH SYSTEM PROGRAMMER, SPECIFYING ENGINEER, AND OWNER TO ENSURE PROPER OPERATION AND TIME
SCHEDULES.
I. ALL EMERGENCY AND EXIT LIGHTING CIRCUITS SHALL BE CONNECTED TO CONTINUOUS POWER SOURCE AHEAD OF RELAY PANEL OR INDIVIDUAL RELAY COMPONENTS.
J. INSTALL ALL CEILING SENSORS MINIMUM OF 6FT CLEAR OF DUCT REGISTERS.
K. THE LIGHTING CONTROL AND EMERGENCY LIGHTING SYSTEMS SHALL BE CAPABLE OF BEING ACCESSED VIA THE LOCAL AREA NETWORK AND REMOTELY VIA AUTHORIZED PERSONNEL ONLY.
L. PROGRAMMER / COMMISSIONING AGENT SHALL BE CERTIFIED BY THE EQUIPMENT MANUFACTURER ON THE SYSTEM INSTALLED.
M. THE MANUFACTURER CERTIFIED TECHNICIAN WILL MEET ONSITE WITH THE ELECTRICAL CONTRACTORS TO COORDINATE INSTALLATION DETAILS, REVIEW BEST PRACTICES, AND DISCUSS PROJECT SPECIFIC CHALLENGES; PRIOR TO THE INSTALLATION BEING STARTED, ENABLING THE CONTRACTORS TO WORK WITH THE TECHNICIAN TO PREPARE AND MAKE CHANGES UP FRONT.
N. THE MANUFACTURER'S LIGHTING SYSTEMS TEAM SHALL WORK ONSITE AFTER FIXTURE AND CONTROLS INSTALLATION IS COMPLETED. THE MANUFACTURER'S AGENT IS TO VERIFY THE PROJECT IS REVIEWED AND CHECKED FOR PROPER WIRING, INSTALLATION AND FUNCTIONALITY OF THE SYSTEM AS A WHOLE. ANY PROBLEMS SHALL BE ADDRESSED AND RESOLVED WITH THE ONSITE
CONTRACTORS.
O. MANUFACTURER'S TECHNICIANS SHALL MAP OUT THE FIXTURE LOCATIONS AND ADDRESSES WITHIN THE LIGHTING CONTROL SOFTWARE. ASTRONOMIC TIMECLOCK EVENTS, SCENES, AND SCHEDULES ARE PROGRAMMED ACCORDING TO A PRE-DEFINED SCRIPT. THESE EVENTS, SCENES, AND SCHEDULES ARE TESTED AND FINALIZED FOR FINAL APPROVAL BY THE PROJECT'S
OWNERSHIP.
P. MANUFACTURER'S TECHNICIANS SHALL PROVIDE TRAINING FOR SYSTEM USERS AND THE SYSTEM MAINTENANCE TEAM. THE DETAILS OF THE TECHNOLOGY SHALL BE COVERED FROM A MAINTENANCE AND TROUBLESHOOTING POINT OF VIEW. THIS COVERS THE LIGHTING CONTROL SYSTEM AND ITS CORE FUNCTIONALITY, WITH A FOCUS ON HOW TO EDIT EXISTING SCENES AND
ASTRONOMIC LIGHTING EVENTS.
Q. THE MANUFACTURER'S REPRESENTATIVE SHALL PROVIDE IN-DEPTH TRAINING TO THE END USER ON MANAGING THE SPECIFIC CONTROL SYSTEM, GIVING THEM THE TOOLS AND KNOWLEDGE TO
OPERATE THEIR SYSTEM.
HD
OS
VS
VALVE BOX
NOT TO SCALE
ONE (1) 3/4" CONDUIT
FOR CONTROL WIRING.
ONE (1) 1" I.M. CONDUIT
WITH THREE 3#8, 1#10 GND
SOOW CORDS.
INSTALL NEW E.Y.S. SEAL-OFF
FITTINGS ON EACH CONDUIT
FROM WELL.
NEMA 3R JUNCTION BOX WITH
TERMINAL STRIP.
KELLUMS TYPE STRAIN RELIEF
GRIPS, TYP. AT EACH CABLE
COIL EXCESS CABLE IN WET
WELL. DO NOT CUT.
INSTALL BELL END
FITTING ON ALL
CONDUIT ENTERING
WET WELL.
LIFTING CABLE
SECURE ELEC. CABLE TO
LIFTING CABLE AT 4' O.C.
TWO 5.0 HP SUBMERSIBLE PUMPS
GRADE
PANEL
GRINDER STATION
SINGLE LINE POWER RISER
3/4" CONDUIT TO
PANELBOARD
3/4" CONDUIT
NOT TO SCALE
GRINDER STATION
CONNECTION DETAIL
SELF-CONTAINED SMOKE/CARBON MONOXIDE ALARM 120V. WITH BATTERY BACK-UP; PUSH-TO-TEST BUTTON & PILOT LIGHT; TANDEM TYPE
(ONE ALARMS-ALL ALARM)
CGCG
Job No.Christopher A. Garick; FL. PE No.53924 Thomas A. Alexander; FL. PE No.73172 Daniel J. White; FL. PE No.73790 Caleb W. Leonard; FL. PE No.91782
HG Engineers 142 Eglin Parkway SE Fort Walton Beach, Florida, 32548 E-mail: office@hgengineers.com Ph: 850.243.6723 Fl. Authorization No.00006680
23046
8/30/2024
DRAWING NUMBER:
DATE: FILE:
SHEET TITLE:
APPROVED BY:
REVISIONS:
21011
St ok es A rc hi te ct ur al
, I nc
St ok es A rc hi te ct ur al
, i nc
. h er eb y ex pr es sl y re se rv es it s co m m on -la w c op yr ig ht a nd o th er p ro pe rty ri gh ts to th es e pl an s.
D ra w in gs a re n ot to b e re pr od uc ed
, c ha ng ed
, o r c op ie d in a ny fo rm w ha ts oe ve r, no r a re th ey to b e as si gn ed to a ny th ird p ar ty w ith ou t f irs t o bt ai ni ng th e ex pr es s w rit te n pe rm is si on a nd c on se nt o f S to ke s
Ar ch ite ct ur al
, i nc
DRAWN BY:
CG
CHECKED BY:
CG
Ar ch ite ct ur e
M as te r P la nn in g
In te rio r D es ig n
C lo ve rd al e
Bo ul ev ar d Fo rt W al to n Be ac h, F lo rid a
Ph on e:
(8
) 6
-2
F ax
0)
-6
FL
L ic en se
: A
R
L C or p
Li ce ns e
A
AC
Architectural Inc.
Stokes
S a n ta
R o sa
B ea ch
Fl o ri d a
Nat ure
Cen ter at K ello gg P ark
- W alto n Co unt y E a st
N u rs er y R o a d
PROFESSIONAL SEAL:
AR0096630
100 % PERMIT DRAWINGS
E0.1
LEGEND AND NOTES
http://www.Humber-Garick.com
EXISTING UTILITY
POWER POLE
NEW PAD MOUNT
TRANSFORMER BY
UTILITY
NEW PANEL P
NEW METER
GRINDER
PUMP GP-1P-32-34-36
KEYNOTES
APPROXIMATE LOCATION OF
SITE FIXTURE, REFER TO
CIVIL DRAWINGS FOR
FIXTURE TYPE AND
LOCATION. EC SHALL
PROVIDE AND INSTALL WIRE
AND CONDUIT.
J
P-16
PROVIDE PULLBOX WITH 1" C TO SITE FIXTURES.
HOMERUN VIA LIGHTING CONTACTOR
NEW SECONDARY
SERVICE ENTRANCE BY
E.C. REFER TO SINGLE
LINE POWER RISER.
REFER TO POWER RISER
FOR UTILITY SERVICE
CONDUIT INFORMATION.
J PROVIDE PULLBOX WITH 3" C WITH
PULLCORD TO TELECOMM
BACKBOARD; MARK AND LABEL FOR
TELECOMM USE
CGCG
Job No.Christopher A. Garick; FL. PE No.53924 Thomas A. Alexander; FL. PE No.73172 Daniel J. White; FL. PE No.73790 Caleb W. Leonard; FL. PE No.91782
HG Engineers 142 Eglin Parkway SE Fort Walton Beach, Florida, 32548 E-mail: office@hgengineers.com Ph: 850.243.6723 Fl. Authorization No.00006680
23046
8/30/2024
DRAWING NUMBER:
DATE: FILE:
SHEET TITLE:
APPROVED BY:
REVISIONS:
21011
St ok es A rc hi te ct ur al
, I nc
St ok es A rc hi te ct ur al
, i nc
. h er eb y ex pr es sl y re se rv es it s co m m on -la w c op yr ig ht a nd o th er p ro pe rty ri gh ts to th es e pl an s.
D ra w in gs a re n ot to b e re pr od uc ed
, c ha ng ed
, o r c op ie d in a ny fo rm w ha ts oe ve r, no r a re th ey to b e as si gn ed to a ny th ird p ar ty w ith ou t f irs t o bt ai ni ng th e ex pr es s w rit te n pe rm is si on a nd c on se nt o f S to ke s
Ar ch ite ct ur al
, i nc
DRAWN BY:
CG
CHECKED BY:
CG
Ar ch ite ct te r P la nn rio r D es ig n
C lo ve rd al e
Bo ul ev ar d Fo rt W al to n Be ac h, F lo rid a
Ph on e:
(8
) 6
-2
0)
-6
FL
L ic en se
: A
R
C or p
Li ce ns e
A
AC
Architectural Inc.
Stokes
S a n ta
R o sa
B ea ch
Fl o ri d a
Nat ure
Cen ter at K ello gg P ark
- W alto n Co unt y E a st
N u rs er y R o a d
PROFESSIONAL SEAL:
AR0096630
100 % PERMIT DRAWINGS
SITE PLAN - ELECTRICAL
1" = 240'_XREF 10' 20' 40' E1.1
SITE PLAN - ELECTRICAL
PORCH
MEETING
ROOM
CLOSET
JANITOR
MEN
ELEC.
WOMEN
GALLERY
OBSERVATION
DECK
HVAC
+DW"
+AC"
+AC"
+AC"
+AC"
+AC"
+AC"
WP
WP
WP
WP
P-3
P-2
P-1 P-6
P-5
P-8
P-7
P-4
P
HD
HD
HD
HD
P-10
P-9
P-11
P-12
P-13
TELECOM BACKBOARD, 3.5 FT. WIDE X 6 FT. HIGH X 3/4" EXTERIOR PLYWOOD. PAINT
TWO COATS FIRE RETARDANT PAINT. INSTALL ONE NO. 6 COPPER GROUND
CONDUCTOR IN 3/4" CONDUIT TO BUILDING GROUND, LEAVE 4 FT. SLACK CONDUCTOR
AT BACKBOARD.
+48"P-17
ELECTRIC UTILITY METER
CGCG
Job No.Christopher A. Garick; FL. PE No.53924 Thomas A. Alexander; FL. PE No.73172 Daniel J. White; FL. PE No.73790 Caleb W. Leonard; FL. PE No.91782
HG Engineers 142 Eglin Parkway SE Fort Walton Beach, Florida, 32548 E-mail: office@hgengineers.com Ph: 850.243.6723 Fl. Authorization No.00006680
23046
8/30/2024
DRAWING NUMBER:
DATE: FILE:
SHEET TITLE:
APPROVED BY:
REVISIONS:
21011
St ok es A rc hi te ct ur al
, I nc
St ok es A rc hi te ct ur al
, i nc
. h er eb y ex pr es sl y re se rv es it s co m m on -la w c op yr ig ht a nd o th er p ro pe rty ri gh ts to th es e pl an s.
D ra w in gs a re n ot to b e re pr od uc ed
, c ha ng ed
, o r c op ie d in a ny fo rm w ha ts oe ve r, no r a re th ey to b e as si gn ed to a ny th ird p ar ty w ith ou t f irs t o bt ai ni ng th e ex pr es s w rit te n pe rm is si on a nd c on se nt o f S to ke s
Ar ch ite ct ur al
, i nc
DRAWN BY:
CG
CHECKED BY:
CG
Ar ch ite ct te r P la nn rio r D es ig n
C lo ve rd al e
Bo ul ev ar d Fo rt W al to n Be ac h, F lo rid a
Ph on e:
(8
) 6
-2
0)
-6
FL
L ic en se
: A
R
C or p
Li ce ns e
A
AC
Architectural Inc.
Stokes
S a n ta
R o sa
B ea ch
Fl o ri d a
Nat ure
Cen ter at K ello gg P ark
- W alto n Co unt y E a st
N u rs er y R o a d
PROFESSIONAL SEAL:
AR0096630
100 % PERMIT DRAWINGS
FLOOR PLAN - POWER
1/4" = 1'-0" 2' 4' 8'
E2.1
FLOOR PLAN - POWER
PORCH
MEETING
ROOM
CLOSET
JANITOR
MEN
ELEC.
WOMEN
GALLERY
OBSERVATION
DECK
HVAC
EF
EF
EF
EF
P
L2L2
L2L2
RC
RC
OS
OS
OS
OS
'L1'
'L1' 'L1'
'L1'
'L1'
'L1'
'L1'
'L1'
'L1'
'L1'
'L1'
'L1'
'L1'
'L1'
'WB' 'WB'
'WB'
'WB'
'WB'
'WB''WB'
L4
L4
RC
'X'
'X'
'X'
'X'
'L2'
'L2'
'L2'
P-14 HOMERUN VIA
LIGHTING CONTACTOR
'F' 'F'
'F' 'F'
5 'DL'
'DL'
'DL'
'DL'
OS
OS
EF
P-15
L3
'F'
CGCG
Job No.Christopher A. Garick; FL. PE No.53924 Thomas A. Alexander; FL. PE No.73172 Daniel J. White; FL. PE No.73790 Caleb W. Leonard; FL. PE No.91782
HG Engineers 142 Eglin Parkway SE Fort Walton Beach, Florida, 32548 E-mail: office@hgengineers.com Ph: 850.243.6723 Fl. Authorization No.00006680
23046
8/30/2024
DRAWING NUMBER:
DATE: FILE:
SHEET TITLE:
APPROVED BY:
REVISIONS:
21011
St ok es A rc hi te ct ur al
, I nc
St ok es A rc hi te ct ur al
, i nc
. h er eb y ex pr es sl y re se rv es it s co m m on -la w c op yr ig ht a nd o th er p ro pe rty ri gh ts to th es e pl an s.
D ra w in gs a re n ot to b e re pr od uc ed
, c ha ng ed
, o r c op ie d in a ny fo rm w ha ts oe ve r, no r a re th ey to b e as si gn ed to a ny th ird p ar ty w ith ou t f irs t o bt ai ni ng th e ex pr es s w rit te n pe rm is si on a nd c on se nt o f S to ke s
Ar ch ite ct ur al
, i nc
DRAWN BY:
CG
CHECKED BY:
CG
Ar ch ite ct te r P la nn rio r D es ig n
C lo ve rd al e
Bo ul ev ar d Fo rt W al to n Be ac h, F lo rid a
Ph on e:
(8
) 6
-2
0)
-6
FL
L ic en se
: A
R
C or p
Li ce ns e
A
AC
Architectural Inc.
Stokes
S a n ta
R o sa
B ea ch
Fl o ri d a
Nat ure
Cen ter at K ello gg P ark
- W alto n Co unt y E a st
N u rs er y R o a d
PROFESSIONAL SEAL:
AR0096630
100 % PERMIT DRAWINGS
FLOOR PLAN - LIGHTING
1/4" = 1'-0" 2' 4' 8'
E2.2
FLOOR PLAN - LIGHTING
P
AHU
HPU
EF
EF
EF
EF
EF
EWH
P
P-37-39-41
P-31-33-35
P-28-30
P-18
KEYNOTES
REFER TO FLOOR PLAN -
LIGHTING FOR EXHAUST FAN
CONNECTIONS.
PORCH
MEETING
ROOM
CLOSET
JANITOR
MEN
ELEC.
WOMEN
GALLERY
OBSERVATION
DECK
HVAC
CGCG
Job No.Christopher A. Garick; FL. PE No.53924 Thomas A. Alexander; FL. PE No.73172 Daniel J. White; FL. PE No.73790 Caleb W. Leonard; FL. PE No.91782
HG Engineers 142 Eglin Parkway SE Fort Walton Beach, Florida, 32548 E-mail: office@hgengineers.com Ph: 850.243.6723 Fl. Authorization No.00006680
23046
8/30/2024
DRAWING NUMBER:
DATE: FILE:
SHEET TITLE:
APPROVED BY:
REVISIONS:
21011
St ok es A rc hi te ct ur al
, I nc
St ok es A rc hi te ct ur al
, i nc
. h er eb y ex pr es sl y re se rv es it s co m m on -la w c op yr ig ht a nd o th er p ro pe rty ri gh ts to th es e pl an s.
D ra w in gs a re n ot to b e re pr od uc ed
, c ha ng ed
, o r c op ie d in a ny fo rm w ha ts oe ve r, no r a re th ey to b e as si gn ed to a ny th ird p ar ty w ith ou t f irs t o bt ai ni ng th e ex pr es s w rit te n pe rm is si on a nd c on se nt o f S to ke s
Ar ch ite ct ur al
, i nc
DRAWN BY:
CG
CHECKED BY:
CG
Ar ch ite ct te r P la nn rio r D es ig n
C lo ve rd al e
Bo ul ev ar d Fo rt W al to n Be ac h, F lo rid a
Ph on e:
(8
) 6
-2
0)
-6
FL
L ic en se
: A
R
C or p
Li ce ns e
A
AC
Architectural Inc.
Stokes
S a n ta
R o sa
B ea ch
Fl o ri d a
Nat ure
Cen ter at K ello gg P ark
- W alto n Co unt y E a st
N u rs er y R o a d
PROFESSIONAL SEAL:
AR0096630
100 % PERMIT DRAWINGS
FLOOR PLAN - MECH POWER
1/4" = 1'-0" 2' 4' 8'
E2.3
FLOOR PLAN - MECH POWER
TYPICAL ELECTRICAL EQUIPMENT NAMEPLATE
NOT TO SCALE
THIS AREA
TYPICAL FLOOR MARKING AT ELECTRICAL PANELS
NOT TO SCALE
ELECTRICAL PANEL
NO STORAGE
DISCONNECT SWITCH
DESCRIPTION NOMENCLATURE
XX/X/XX
TYPICAL SERVICE EQUIPMENT FAULT CURRENT LABEL DETAIL
NOT TO SCALE
MAXIMUM AVAILABLE FAULT CURRENT
/ / DATE OF CALCULATION
SYMMETRICAL RMS AMPERES
EQUIPMENT NAME
COMPANY RESPONSIBLE FOR CALCULATION CONTACT INFORMATION; COMPANY NAME, ADDRESS, PHONE NUMBER
PVC STUB-UP DETAILS
WITHOUT OUTLET BOXWITH OUTLET BOX
NOT TO SCALE
FEEDER CONDUIT
EXPOSED OR
TYPICAL ARC FLASH HAZARD LABEL DETAIL
NOT TO SCALE
Arc Flash and Shock Risks Appropriate PPE Required
WARNING
ARC FLASH RISK PROTECTION MINIMUM PPE
SHOCK PROTECTION
Arc Flash Boundary 19 in Incident Energy: 1.3 cal/cm^2
Shock Risk When 480 VAC Cover is Removed Limited Approach: 42 in Restricted Approach: 12 in
4 cal/sq cm, FR shirt (long-sleeve) plus FR pants (long), or FR coverall, rainwear as needed.
Hardhat + Safety Glasses or Goggles + Ear Canal Inserts Glove Class 00
Leather work shoes Bus ID:
Prot Device ID:
Calculated Fault Current:
Date of Analysis:
Warning: Changes in equipment settings or system configuration may invalidate the calculated results.
WHITE
ORANGE
4"H x 6"W VINYL LABEL WITH
BLACK LETTERING PER ANSI Z535 STANDARDS.
TYPICAL ELECTRICAL EQUIPMENT
ABOVE CEILING NAMEPLATE
SHADED SECTION
INDICATES LIGHTED
FACE OF EXIT SIGN
ARROWS INDICATE
DIRECTION OF ARROWS
ON EXIT SIGN
EXIT SIGN NOMENCLATURE
WHITE
ORANGE
4"H x 6"W VINYL LABEL WITH
BLACK LETTERING PER ANSI Z535 STANDARDS.
MICARTA ENGRAVED NAMEPLATE
WITH WHITE LETTERS ON BLACK
BACKGROUND, MECHANICALLY AFFIXED.
6" HIGH x 1" WIDE
RED LETTERS
3" WIDE YELLOW PAINT
STRIPE - TYPICAL
1/4" LETTERS
1/2" LETTERS
WALL OUTLET
PVC CONDUIT
CONCEALED IN WALL
PVC COUPLER
FINISHED FLOOR
PVC-2 1/2" MAXIMUM
PVC COUPLER
EMT CONDUIT
CONCEALED IN WALL
PVC TO EMT ADAPTER
FINISHED FLOOR
PVC-2 1/2" MAXIMUM
PVC COUPLER
EMT CONDUIT
RIGID TO EMT ADAPTER
FINISHED FLOOR
RIGID CONDUIT
PVC CONDUIT
PVC TO RIGID ADAPTER
MICARTA ENGRAVED NAMEPLATE WITH
BLACK LETTERS ON WHITE BACKGROUND,
MECHANICALLY AFFIXED TO CEILING TILE
OR WALL WITH BOLTS, NUTS AND
WASHERS
1/4" LETTERS IDENTIFYING
ELECTRICAL EQUIPMENT
AMPERE RATING NEMA RATING
NUMBER OF POLES
TYPICAL STUD
TYPICAL STUD
TYPICAL POWER & COMMUNICATIONS
18" AFF C/L
WORKSTATION CABLE
AND PLUG. (TYPICAL)
BOX MOUNTING
BRACKET EQUAL
TO STEEL CITY
SSF-SB16
2-GANG JUNCTION BOX
EQUAL TO STEEL CITY
2G-3/4.
2-GANG BOX COVER
WITH 1-GANG RING
EQUAL TO STEEL CITY
#1-GC. (TYPICAL)
2-GANG JUNCTION BOX
EQUAL TO STEEL CITY
2G-3/4.
EACH END
WALL STUD
ATTACH TO
EXTERIOR LIGHTING CONTROL DIAGRAM
TO
S
IT
E
LIG
HT
IN
G
NOT TO SCALE
UNLATCH
L1
LATCH
L1
NH
PHOTON.O. C.C.N.O
INPUTS
N
H
CKT 2CKT 1
DIGITAL TIMESWITCH WITH
ASTRONOMIC OPTION
EQUAL TO TORK #DGUM100A
PHOTO ELECTRIC CONTROL
TORK MODEL EPCA
LIGHTING CONTACTOR
4-POLE, MECHANICALLY HELD 120V
COIL, LIGHTING CONTACTOR
LA
TC
H
UN
LA
TC
H
SP
AR
E
SP
AR
E
P-
LOW VOLTAGE WALL
SWITCH EQUAL TO
WATTSTOPPER
LMSW-102-W
Wattstopper
NOT TO SCALE
TYPICAL LIGHTING (SWITCHING) CONTROL
WITH VACANCY SENSOR, AND SWITCH INPUT CEILING MOUNT
VACANCY SENSOR
EQUAL TO
WATTSTOPPER
LMDC-100
NORMAL SWITCH LEG
TYPICAL
NORMAL
FIXTURE
NORMAL
LIGHTING
PANEL
NORMAL NEUTRAL
NORMAL HOT
(120/277v) White (Neutral In)
Black (120/277v In) Red (Load-A Switched Out)
NORMAL NEUTRAL
Violet (Load-A Dim) Gray (Load-A Dim)
CAP
WHITE (NEUTRAL IN)
BLACK (120/277V IN)
RED (LOAD-A SWITCHED OUT)
YELLOW (LOAD-B SWITCHED OUT)
YELLOW/VIOLET (LOAD-B DIM)
YELLOW/GRAY (LOAD-B DIM)
VIOLET (LOAD-A DIM)
GRAY (LOAD-A DIM)
LOW VOLTAGE WALL
SWITCH EQUAL TO
WATTSTOPPER
LMSW-102-W
Wattstopper
NOT TO SCALE
TYPICAL FAN/ LIGHTING (SWITCHING) CONTROL
WITH VACANCY SENSOR, AND SWITCH INPUT
CEILING MOUNT
VACANCY SENSOR
EQUAL TO
WATTSTOPPER
LMDC-100
NORMAL SWITCH LEG
TYPICAL
NORMAL
FIXTURE
NORMAL
LIGHTING
PANEL
NORMAL NEUTRAL
NORMAL HOT
(120/277v)
NORMAL NEUTRAL
NORMAL NEUTRAL
NORMAL SWITCH LEGTYPICAL FAN
FIXTURE
ON - LIGHTS
OFF - LIGHTS
ON-FANS
OFF-FANS
ON
OFF
EX
TE
RI
OR
LI
GH
TS
P-
SP
AR
E
SP
AR
E
NOT TO SCALE
ELECTRICAL PULLBOX DETAIL
24 1/2"
22 1/4"
BOX
33 7/8"
35 5/8"
37 5/8"
COVER
26"
ELECTRIC
24"
SECTION
2"
21"
3"
CONCRETE RING
AROUND BOX
CHAMFER EDGES
3/8-16 UNC STAINLESS
STEEL HEX HEAD BOLT
W/WASHER (2)
SKID RESISTANT
SURFACE
1/2" x 4"
PULL SLOT
4" x 4" MOUSEHOLES
(2) PG2436BB
COVER RATED AT 5,000 PSI
OVER 10"x10" AREA. LABEL
"ELECTRIC".
6 TO 8 INCHES
GRAVEL
COMPACTED EARTH
PLASTIC BUSHING ON
EACH CONDUIT END
CGCG
Job No.Christopher A. Garick; FL. PE No.53924 Thomas A. Alexander; FL. PE No.73172 Daniel J. White; FL. PE No.73790 Caleb W. Leonard; FL. PE No.91782
HG Engineers 142 Eglin Parkway SE Fort Walton Beach, Florida, 32548 E-mail: office@hgengineers.com Ph: 850.243.6723 Fl. Authorization No.00006680
23046
8/30/2024
DRAWING NUMBER:
DATE: FILE:
SHEET TITLE:
APPROVED BY:
REVISIONS:
21011
St ok es A rc hi te ct ur al
, I nc
St ok es A rc hi te ct ur al
, i nc
. h er eb y ex pr es sl y re se rv es it s co m m on -la w c op yr ig ht a nd o th er p ro pe rty ri gh ts to th es e pl an s.
D ra w in gs a re n ot to b e re pr od uc ed
, c ha ng ed
, o r c op ie d in a ny fo rm w ha ts oe ve r, no r a re th ey to b e as si gn ed to a ny th ird p ar ty w ith ou t f irs t o bt ai ni ng th e ex pr es s w rit te n pe rm is si on a nd c on se nt o f S to ke s
Ar ch ite ct ur al
, i nc
DRAWN BY:
CG
CHECKED BY:
CG
Ar ch ite ct te r P la nn rio r D es ig n
C lo ve rd al e
Bo ul ev ar d Fo rt W al to n Be ac h, F lo rid a
Ph on e:
(8
) 6
-2
0)
-6
FL
L ic en se
: A
R
C or p
Li ce ns e
A
AC
Architectural Inc.
Stokes
S a n ta
R o sa
B ea ch
Fl o ri d a
Nat ure
Cen ter at K ello gg P ark
- W alto n Co unt y E a st
N u rs er y R o a d
PROFESSIONAL SEAL:
AR0096630
100 % PERMIT DRAWINGS
E3.1
ELECTRICAL DETAILS
PANEL
NEW
P 120/208V
3PH, 4W
150A M.C.B.
NTS
POWER RISER
KEYNOTES
4 #1/0, IN 1 1/2" CONDUIT
INSTALL SURGE
SUPPRESSOR WITH 3 #6,
#10 GND IN 1" C. LEAD
LENGTH NOT TO EXCEED
14 INCHES PER ANSI/UL
1449-2016 4TH EDITION.
SEE GROUNDING DETAILS
240/120V GROUNDING SYSTEM DIAGRAM
NEUTRALGROUND
NOT TO SCALE
FINISHED FLOOR
NOT TO SCALE
T E
L E
B A
C K
B O
A R
D
4"
INSULATED GROUNDING BAR DETAIL
.25" 2"
NOT TO SCALE
4"
MAIN GROUNDING
ELECTRODE
GROUND BAR
METAL WATER PIPE WITHIN
5 FT OF ENTRANCE
208/120 VOLT
SERVICE ENTRANCE
EQUIPMENT
KEYNOTES
MAIN GROUNDING
ELECTRODE
GROUND BAR
TYPICAL - EACH CABLE:
LABEL WITH TYPE GROUND
I.E. "TELE BACKBOARD",
"COLD WATER GROUND",
4" HIGH CONCRETE CURB
AROUND CONDUITS
10"L (COPPER)
7/16" DIA.
3/8" DIA.
GROUND BAR NOTES:
1 INSTALL ONE BAR AT EACH COMMUNICATIONS ROOM.
3 CONNECT BARS WITH 1#6 BARE CU IN 1" CONDUIT.
GENERAL NOTES
1 BOND HOT AND COLD WATER PIPING SYSTEMS.
2 CONDUCTOR SIZES SHOWN ARE MINIMUM AND MAY BE LARGER
THAN THE MINIMUM SIZES REQUIRED BY NEC.
3 INSTALL GROUNDING CONNECTIONS TO BUILDING STRUCTURE
AND WATER PIPES AT LOCATIONS THAT ARE VISIBLE AND
ACCESSIBLE FOR INSPECTION, MAINTENANCE, AND TESTING.
4 INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH
METALLIC SERVICE ENTRANCE CONDUIT. BOND TO GROUND BUS
USING CONDUCTOR THAT IS SIZED BASED ON NEC TABLE 250-66
USING THE SERVICE PHASE CONDUCTOR SIZE.
5 INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH
METALLIC FEEDER CONDUIT. BOND TO GROUND BUS USING
CONDUCTOR THAT IS SIZED BASED ON NEC TABLE 250-122
USING THE FEEDER CIRCUIT OVERCURRENT DEVICE SIZE OR THE
SEPARATELY DERIVED SYSTEM OVERCURRENT DEVICE SIZE.
GROUNDING SYSTEM
TYPICAL ENCLOSURE
TYPICAL ENCLOSURE: EQUAL TO CARLON 'CIRCUIT-SAFE' JIC
ENCLOSURE: NON-METALLIC; SIDE OPENING, HINGED DOOR WITH
LOCK OR CATCH; POLYCARBONATE CONSTRUCTION. PROVIDE
A MICARTA PLATE, MECHANICALLY ATTACHED TO OUTSIDE
OF DOOR, ENGRAVED IN LETTERS 1" HIGH TO READ
"MAIN GROUND BUS BAR". SIZE ENCLOSURE TO ENSURE
A MINIMUM OF 2" CLEARANCE AT EACH END OF THE
GROUND BAR
7'-6"
MIN.
7'-6"
MIN.
NO DESCRIPTION
GROUND BAR
WALL MTG. BRACKET
INSULATORS
5/8"X1" H.H.C.S. BOLT
5/8" LOCKWASHER
ROUTE 1 #4 BARE CU IN 1" CONDUIT FROM GROUND BAR TO
BUILDING ELECTRICAL SERVICE ENTRANCE GROUND.
INSTALL GROUNDING ELECTRODE CONDUCTOR, TABLE 250-66 USING THE SERVICE PHASE
CONDUCTOR SIZE, BUT NOT SMALLER THAN NO 4.
10 FOOT MINIMUM X 3/4" DIAMETER COPPER CLAD STEEL SECTIONAL DRIVEN GROUND ROD.
INSTALL BONDING JUMPER WIRE THAT IS SIZED BASED ON NEC TABLE 250-66 OR 250.28(D)(1)
USING THE SERVICE OR SEPARATELY-DERIVED SYSTEM PHASE.
INSTALL A "MAIN GROUND ELECTRODE GROUND BAR" FOR SINGLE POINT GROUNDING.
LOCATE AT AN ACCESSIBLE POINT NEAR THE SERVICE ENTRANCE EQUIPMENT. MAKE
CONNECTIONS TO THE GROUND ELECTRODE CONDUCTOR USING IRREVERSIBLE
CONNECTORS OR EXOTHERMIC WELDS. MAKE OTHER CONNECTIONS TO THE GROUND BAR
USING TWO-HOLE COMPRESSION SPADE LUGS THAT MEET IEEE 837 REQUIREMENTS. LABEL
EACH CONNECTION TO THE GROUND BAR.
(3) 2" C. WITH PULL RIBBON. STUB-OUT, CAP
AND MARK LOCATION. REFER TO SITE PLAN
FOR APPROXIMATE LOCATION.
NEW PAD MOUNTED TRANSFORMER BY UTILITY COMPANY.
CONCRETE PAD BY CONTRACTOR PER UTILITY COMPANY
REQUIREMENTS.
CGCG
Job No.Christopher A. Garick; FL. PE No.53924 Thomas A. Alexander; FL. PE No.73172 Daniel J. White; FL. PE No.73790 Caleb W. Leonard; FL. PE No.91782
HG Engineers 142 Eglin Parkway SE Fort Walton Beach, Florida, 32548 E-mail: office@hgengineers.com Ph: 850.243.6723 Fl. Authorization No.00006680
23046
8/30/2024
DRAWING NUMBER:
DATE: FILE:
SHEET TITLE:
APPROVED BY:
REVISIONS:
21011
St ok es A rc hi te ct ur al
, I nc
St ok es A rc hi te ct ur al
, i nc
. h er eb y ex pr es sl y re se rv es it s co m m on -la w c op yr ig ht a nd o th er p ro pe rty ri gh ts to th es e pl an s.
D ra w in gs a re n ot to b e re pr od uc ed
, c ha ng ed
, o r c op ie d in a ny fo rm w ha ts oe ve r, no r a re th ey to b e as si gn ed to a ny th ird p ar ty w ith ou t f irs t o bt ai ni ng th e ex pr es s w rit te n pe rm is si on a nd c on se nt o f S to ke s
Ar ch ite ct ur al
, i nc
DRAWN BY:
CG
CHECKED BY:
CG
Ar ch ite ct te r P la nn rio r D es ig n
C lo ve rd al e
Bo ul ev ar d Fo rt W al to n Be ac h, F lo rid a
Ph on e:
(8
) 6
-2
0)
-6
FL
L ic en se
: A
R
C or p
Li ce ns e
A
AC
Architectural Inc.
Stokes
S a n ta
R o sa
B ea ch
Fl o ri d a
Nat ure
Cen ter at K ello gg P ark
- W alto n Co unt y E a st
N u rs er y R o a d
PROFESSIONAL SEAL:
AR0096630
100 % PERMIT DRAWINGS
E4.1
RISER AND GROUNDING
DETAILS
http://www.Humber-Garick.com http://www.Humber-Garick.com
| Sheets and Views |
| E0.1 LEGEND AND NOTES |
| E1.1 SITE PLAN - ELECTRICAL |
| E2.1 FLOOR PLAN - POWER |
| E2.2 FLOOR PLAN - LIGHTING |
| E2.3 FLOOR PLAN - MECH POWER |
| E3.1 ELECTRICAL DETAILS |
| E4.1 RISER AND GROUNDING DETAILS |
| 2024-08-28T14:44:58-0500 | |
| Christopher A Garick |
File details come from the government source that posted it. Updated .