J2a P50_BB_TRACON_Drawings.pdf
PDF 27 MB Posted
- Solicitation number
- 697DCK-24-R-00382
About this file
This document is a Solicitation for the FAA's requirement for fire suppression, fire life safety system, and leak repairs at the PHX Base Building and PH50 TRACON in Phoenix, AZ. The Solicitation Number is 697DCK-24-R-00382 and the Opportunity Type is a Solicitation. Key details include:
The FAA has a requirement for fire life safety system upgrades and leak repairs at the PHX Base Building and PH50 TRACON in Phoenix, AZ. Proposals are due by 1500 EDT on July 9, 2024. A site visit is scheduled for June 11, 2024 at 0900 MST and interested participants must submit interest by June 6, 2024. All questions must be submitted by 1500 EDT on June 19, 2024. The offeror must have a current SAM registration to be eligible for award. This is not a guaranteed procurement, and the government will not reimburse vendors for proposal costs.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| J1 P50 - Request for Offer (RFO).doc | DOC document | |
| 697DCK-24-R-00382-0003 EXECUTED.pdf | ||
| Attachment J5 Questions and Answers.pdf | ||
| L3 - Standardized Proposal Breakdown v1.xls | XLS spreadsheet | |
| Attachment J4 Wage Determination Rates.pdf | ||
| 697DCK-24-R-00382 Amend 0002.pdf | ||
| 697DCK-24-R-00382 Amend 01.pdf | ||
| 697DCK-24-R-00382.pdf | ||
| L3 Standardized Proposal Breakdown.xlsx | XLSX spreadsheet | |
| J2e DDH - P50.pdf | ||
| J3 BIL Uniform Report.xlsx | XLSX spreadsheet | |
| J2c EOSH Checklist P50 TRACO FLS - 1_Redacted.pdf | ||
| J2d FAA Form 3900-17 P50 TRACO FLS - 1_Redacted.pdf | ||
| J2 P50 Fire Sprinkler Upgrade Specs.pdf | ||
| J2b P50 Phasing.pdf | ||
| L1 Bid Bond.pdf | ||
| L2 Past Performance Questionairre.pdf | ||
| J1 P50 - Request for Offer (RFO).pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
GENERAL NOTES
SCOPE OF WORK
APPLICABLE CODES
PROVIDE A NEW AUTOMATIC FIRE SPRINKLER SYSTEM FOR PHOENIX SKY
HARBOR ATCT BASE BUILDING, INCLUDING P50 TRACON, ESU BUILDING,
CONNECTION TO THE EXISTING TOWER SYSTEM, NEW FIRE PUMPS IN
BASEMENT AND ON ATCT LEVEL 10 AND ASSOCIATED PIPING IN PHOENIX,
AZ.
THE NEW SYSTEM SHALL BE IN ACCORDANCE WITH APPLICABLE CODES
AND STANDARDS.
1. THESE DRAWINGS ARE DIAGRAMMATIC IN ACCORDANCE WITH FAA REGULATIONS AND NOT INTENDED AS SHOP DRAWINGS.
2. FIRE PROTECTION SYSTEM SHALL COMPLY WITH PROJECT SPECIFICATIONS AND ALL APPLICABLE STATE AND LOCAL CODES.
3. INSTALLING CONTRACTOR AND PERSONNEL SHALL OBTAIN ALL REQUIRED PERMITS AND LICENSES.
4. DESIGN & INSTALLATION SUBJECT TO FINAL INSPECTION AND APPROVAL BY FAA AND CONTRACTING OFFICER'S
REPRESENTATIVE/ENGINEER.
5. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS SHALL BE DONE ONLY WITH THE WRITTEN APPROVAL OF THE
CONTRACTING OFFICER'S REPRESENTATIVE.
6. FIRE STOP ALL PENETRATIONS OF FIRE/SMOKE BARRIERS, RATED WALLS, CEILINGS, FLOORS, ROOFS, ETC. FLASH AND
COUNTERFLASH ROOF PENETRATIONS.
7. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES.
8. SPRINKLERS SHALL BE ALIGNED/COORDINATED WITH ALL DIFFUSERS, SPEAKERS, LIGHTING FIXTURES AND CEILING SYSTEMS.
9. METHODS OF SEISMIC PROTECTION AND HANGING PIPES, HEADERS AND BRANCHES SHALL BE IN ACCORDANCE WITH NFPA 13.
10. AUTOMATIC SPRINKLER TEMPERATURE RATINGS OF FUSIBLE ELEMENTS SHALL BE IN ACCORDANCE WITH NFPA 13.
11. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES, INC. AND/OR THE FACTORY MUTUAL LABORATORIES. VALVES SHALL BE FACTORY MARKED "UL" AND/OR "FM", 175 PSI WORKING PRESSURE.
12. STEEL SPRINKLER PIPE SHALL BE SCHEDULE 40, GROOVED ENDS SHALL BE CUT-GROOVED.
13. ONLY NEW MATERIALS SHALL BE USED IN THE INSTALLATION OF THIS SYSTEM.
14. ALL FIRE SPRINKLERS MOUNTED IN CEILING SHALL BE LOCATED A MINIMUM OF 4" AWAY FROM ANY WALLS, CEILING HEIGHT CHANGES OR ANY OTHER VERTICAL INTERSECTING SURFACE MEASURED FROM CENTER OF SPRINKLER. SPRINKLERS SHALL BE
LOCATED AT CENTER OF TILE OR QUARTER POINT IN ACOUSTIC CEILING TILE CEILING.
15. PIPE DRAINS TO OUTSIDE LOCATION TO BE APPROVED BY CONTRACTING OFFICERS TECHNICAL REPRESENTATIVE(COTR).
16. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
17. INSTALL PRESSURE GAUGE ON EACH FLOOR CONTROL ASSEMBLY AND/OR AT EACH TEST CONNECTION. PROVIDE GAUGE WITH A CONNECTION NOT LESS THAN 1/4" AND HAVING A SOFT METAL SEATED GLOBE VALVE. TEST CONNECTIONS MAY ALSO SERVE AS
DRAIN PIPES.
18. ALL BRANCHLINE PIPING SHALL BE RESTRAINED TO RESIST UPWARD MOVEMENT PER NFPA 13.
19. INSTALL GROOVED COUPLINGS IN PIPES 2" AND SMALLER, ADJACENT EACH VALVE ON BOTH SIDES.
20. THE AUTOMATIC FIRE SPRINKLER SUBMITTAL SHALL MATCH AND COORDINATE WITH THE UNDERGROUND PIPING PLANS AND OTHER
WATER SUPPLY COMPONENTS FOR THE PROJECT.
21. FOR NAS CONTROL SPACES, PNEUMATICALLY TEST PIPING. PRESSURE TEST SHALL BE PERFORMED PRIOR TO HYDROSTATIC TESTING, PRIOR TO PUTTING SYSTEMS INTO SERVICE. PNEUMATIC TEST SHALL BE PERFORMED AT 40 PSI FOR 24 HOURS WITH A PRESSURE LOSS NO GREATER THAN 1½ PSI. ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED AT 200 PSI, OR 50 PSI IN EXCESS OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER, AND SHALL MAINTAIN THAT PRESSURE WITH OUT LOSS FOR 2 HOURS. (PROJECT INSPECTOR SHALL
WITNESS AND CONFIRM COMPLIANCE).
22. FOR INDIVIDUAL SYSTEMS AND PHASED FLOOR SYSTEM SECTORS DEFINED BY FLOOR CONTROL VALVE ASSEMBLIES, COMPLETE SYSTEM FORMAL HYDROSTATIC TESTS WILL BE REQUIRED FOR THE FLOOR SYSTEM, IN ADDITION TO PRELIMINARY INDIVIDUAL PNEUMATIC AND HYDROSTATIC TESTING FOR SYSTEM AREAS DEFINED BY NON-FLOOR CONTROL ASSEMBLY DIVISIONAL VALVES.
23. PROVIDE SPARE SPRINKLER HEAD CABINET, SPRINKLER WRENCH, AND NO FEWER THAN TWELVE (12) SPARE SPRINKLER HEADS
MATCHING THE TYPES AND TEMPERATURE RATING IN EACH PROTECTED AREA.
24. THE INSPECTOR'S TEST VALVE SHALL BE INSTALLED DOWNSTREAM OF THE WATERFLOW ALARM DEVICE, USING A PIPE SIZE OF NOT LESS THAN 1 INCH, WITH A SMOOTH BORE, CORROSION RESISTANT ORIFICE, GIVING THE FLOW EQUIVALENT TO ONE SPRINKLER OF A TYPE HAVING THE SMALLEST ORIFICE INSTALLED WITHIN THE SYSTEM. THE DISCHARGE SHALL BE TO THE EXTERIOR OF THE
BUILDING, UNLESS A COMBINATION TEST AND DRAIN VALVES DISCHARGE TO A DRAIN RISER.
25. CONNECTIONS TO PROTECTED PREMISES AND SUPERVISING STATION FIRE ALARM SYSTEMS SHALL BE TESTED TO VERIFY PROPER IDENTIFICATION AND TRANSMISSION OF ALARMS FROM AUTOMATIC FIRE EXTINGUISHING SYSTEMS.
26. SIGNAGE SHALL BE PROVIDED AS REQUIRED PER NFPA 13.
27. ALL VALVES CONTROLLING THE WATER SUPPLY FOR AUTOMATIC SPRINKLER SYSTEMS, PUMPS, TANKS, WATER LEVELS AND TEMPERATURES, CRITICAL AIR PRESSURES, AUTOMATIC AIR VENTS AND WATER FLOW SWITCHES ON ALL SPRINKLER SYSTEMS SHALL BE SUPERVISED AND SHALL BE THE RESPONSIBILITY OF THE FIRE SPRINKLER CONTRACTOR.
28. A PERMANENTLY ATTACHED HYDRAULIC PLACARD PLATE STATING THE REQUIRED DESIGN CRITERIA FOR EACH HYDRAULICALLY
DESIGNED SYSTEM SHALL BE ATTACHED TO EACH RISER PER NFPA 13.
29. SPRINKLER CONTRACTOR SHALL COMPLETE AND SIGN CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR THE ABOVE GROUND PIPING. THIS FORM SHALL BE GIVEN TO THE COTR WHO WILL FORWARD TO FAA FOR FILING IN PROJECT RECORDS.
30. REQUEST FOR FINAL APPROVAL OF INSTALLATION SHALL INCLUDE WRITTEN STATEMENT OF COMPLIANCE, FROM INSTALLING
CONTRACTOR.
31. RECORD (AS-BUILT) DRAWINGS SHALL BE MAINTAINED ON THE PREMISES FOR A MINIMUM OF THREE YEARS WITH COPIES PROVIDED
TO THE FAA, IN PAPER AND ELECTRONIC FORMATS.
32. CONNECTIONS TO PROTECTED PREMISES AND SUPERVISING STATION FIRE ALARM SYSTEMS SHALL BE TESTED TO VERIFY RECEIPT OF TRANSMISSION OF ALARMS FROM AUTOMATIC FIRE EXTINGUISHER SYSTEMS WITHIN 90 SECONDS OF INITIATION (WITNESSED BY
PROJECT INSPECTOR).
33. A WATERFLOW ALARM TEST SHALL BE CONDUCTED BY OPENING THE INSPECTOR'S TEST VALVE OR ALARM BYPASS VALVE. AN AUDIBLE DEVICE MUST ACTIVATE WITHIN 90 SECONDS OF VALVE OPENING.(WITNESSED BY PROJECT INSPECTOR).
34. PROVIDE IDENTIFICATION SIGNAGE AT FIRE PROTECTION EQUIPMENT.
35. SPRINKLER DROPS TO BE EASYFLEX FLEXIBLE SPRINKLER HOSE ULTRA HIGH PERFORMANCE 72" OR EQUIVALENT.
36. WHERE POSSIBLE, ALL NEW AND REPLACEMENT PIPING SHALL BE INSTALLED WITH BRANCHLINES HAVING A PITCH TOWARDS DRAIN OF ½" PER 10-FEET, AND MAINS SHALL BE INSTALLED HAVING A PITCH OF ¼" PER 10-FEET SIMILAR TO THE REQUIREMENTS OF
PRE-ACTION SYSTEMS IN ACCORDANCE WITH 2022 NFPA 13, SECTION 16.10.3.2.
37. CONTRACTOR TO FIRESTOP PENETRATIONS MADE OR RE-USED THROUGH RATED PARTITIONS. CONTRACTOR TO PATCH AND PAINT
AFTER PIPING AND CONDUIT INSTALLATION.
PRELIMINARY HYDRAULIC CALCULATIONS
LIGHT HAZARD (OFFICES, 3RD FLOOR BREAKROOM)
0.10 GPM/SQ.FT. OVER 1,500 SQ.FT.
SPRINKLER K-FACTOR = 5.6
ANTICIPATED SPRINKLER FLOW DEMAND
1500 SQ.FT. x 0.10 GPM/SQ.FT. = 150 GPM
150 GPM + 30% (SYSTEM OVERAGE) = 195 GPM
195 GPM + 100 GPM (HOSE DEMAND) = 295 GPM
ANTICIPATED SPRINKLER PRESSURE DEMAND
225 SQ.FT (MAXIMUM COVERAGE OF SPRINKLERS) * 0.10 GPM/SQ.FT. = 22.5 GPM
P = (Q / K-FACTOR)² (22.5 GPM / 5.6)² = 16.14 PSI - MINIMUM SPRINKLER OPERATING PRESSURE.
16.14 PSI + 13.85 PSI (ELEVATION LOSS)* = 29.99 PSI
29.99 PSI + 10 PSI (BACKFLOW LOSS) = 39.99 PSI
33.99 PSI + 10% (FRICTION LOSS) = 43.99 PSI
37.39 PSI + 5% (UNDERGROUND LOSS) = 46.19 PSI
ORDINARY HAZARD GROUP II (THIRD FLOOR EQUIPMENT ROOM, ELECTRICAL ROOMS)
0.20 GPM/SQ.FT. OVER 1,500 SQ.FT.
SPRINKLER K-FACTOR = 8.0
ANTICIPATED SPRINKLER FLOW DEMAND - THIRD FLOOR
1500 SQ.FT. x 0.20 GPM/SQ.FT. = 300 GPM
300 GPM + 30% (SYSTEM OVERAGE) = 390 GPM
390 GPM + 250 GPM (HOSE DEMAND) = 640 GPM
ANTICIPATED SPRINKLER PRESSURE DEMAND - THIRD FLOOR
130 SQ.FT (MAXIMUM COVERAGE OF SPRINKLERS) / 0.20 GPM/SQ.FT. = 26 GPM
P = (Q / K-FACTOR)² (26 GPM / 8.0)² = 10.6 PSI - MINIMUM SPRINKLER OPERATING PRESSURE.
10.6 PSI + 13.85 PSI (ELEVATION LOSS)* = 23.85 PSI
23.85 PSI + 10 PSI (BACKFLOW LOSS) = 33.85 PSI
27.85 PSI + 30% (FRICTION LOSS) = 44 PSI
29.15 + 10% (UNDERGROUND LOSS) = 48.4 PSI
TYPICAL WET FLOOR RISER DIAGRAM
FIRST FLOOR
BASEMENT FLOOR
3" CHECK VALVE, TYP.
FLOW SWITCH, TYP.
3" MAIN CONTROL VALVE
W/ TAMPER SWITCH, TYP.
6"
6" 6"
NOTE:
· PIPING DIAMETERS SHOWN ARE EXISTING AND SHALL BE CONFIRMED BY HYDRAULIC CALCULATIONS.
· UNDERGROUND FIRE LINE EXISTING
· RISERS IN TOWER CORE MAY VARY SLIGHTLY
· DRAINS AND CONNECTIONS NOT SHOWN FOR CLARITY.
6"
* A DATUM HEIGHT OF 32'-0" WAS CONSERVATIVELY USED FOR ELEVATION LOSS FOR
PRELIMINARY CALCULATIONS ABOVE.
KEY PLAN
PLAN
NORTH
INTERNATIONAL BUILDING CODE (IBC) 2021 EDITION
INTERNATIONAL FIRE CODE (IFC) 2021 EDITION
2022 NFPA 13 - STANDARD FOR INSTALLATION OF SPRINKLER SYSTEMS
2022 NFPA 20 - STANDARD FOR THE INSTALLATION OF STATIONARY PUMP
FOR FIRE PROTECTION
N.T.S
SCOPE OF WORK
EXISTING PRE-ACTION FLOOR RISER DEMO DIAGRAM
UPPER FLOOR(S)
BASEMENT FLOOR
4" CHECK VALVE, TYP.
FLOW SWITCH, TYP.
4" MAIN CONTROL VALVE
W/ TAMPER SWITCH, TYP.
4"
NOTE:
· DEMOLISH ALL PRE-ACTION PIPING, HANGER ATTACHMENTS, AND ALL THREAD ROD.
· PRE-ACTION SYSTEMS HAVE RISER MOUNTED AIR COMPRESSORS TO BE DEMOLISHED,
PULL BACK POWER TO CLOSEST JUNCTION BOX.
· PIPING SUPPORTS, PIPE STANDS SHALL BE REMOVED, STRUCTURAL PIPE SUPPORT
ATTACHMENTS ARE ALLOWED TO REMAIN.
· PUMP ROOM FLOOR FINISH TO BE REPAIRED WHERE NEEDED, 2-PART EPOXY TO MATCH
EXISTING.
4"
4"
4"
4"
4"
4" DRY VALVE, TYP.
6-INCH FEED FROM
FIRE PUMP6"
6"
6" MANIFOLD
SECOND FLOOR
6-INCH FEED FROM
FIRE PUMP
THIRD FLOOR
2½" RISER ASSEMBLY
4" RISER ASSEMBLY
4" RISER ASSEMBLY
6" 6"
6-INCH ISOLATION
BUTTERFLY VALVE
STAIR 3
DRAWING INDEX
ITEM SHEET NUMBER SHEET DESCRIPTION
1 PHX-D-TRACO-F000 COVER SHEET
2 PHX-D-TRACO-F001 SITE PLAN
3 PHX-D-TRACO-F100 BASEMENT FIRE PUMP PLAN
4 PHX-D-TRACO-F101 LEVEL 10 FIRE PUMP PLAN
5 PHX-D-TRACO-F102 EXISTING BASEMENT FLOOR PIPING PLAN
6 PHX-D-TRACO-F103 EXISTING FIRST FLOOR PIPING PLAN
7 PHX-D-TRACO-F104 EXISTING SECOND FLOOR PIPING PLAN
8 PHX-D-TRACO-F105 EXISTING THIRD FLOOR PIPING PLAN
9 PHX-D-TRACO-F106 BASEMENT FLOOR PIPING PLAN
10 PHX-D-TRACO-F107 FIRST FLOOR PIPING PLAN
11 PHX-D-TRACO-F108 SECOND FLOOR PIPING PLAN
12 PHX-D-TRACO-F109 THIRD FLOOR PIPING PLAN
13 PHX-D-TRACO-F110 STAIR 3 AND STAIR 4
14 PHX-D-TRACO-F111 SIXTEENTH FLOOR PLAN - NITROGEN
GENERATOR
15 PHX-D-TRACO-F500 FIRE ALARM GENERAL NOTES
16 PHX-D-TRACO-F501 FIRE ALARM PLAN - BASEMENT FLOOR
17 PHX-D-TRACO-F502 FIRE ALARM PLAN - FIRST FLOOR
18 PHX-D-TRACO-F503 FIRE ALARM PLAN - SECOND FLOOR
19 PHX-D-TRACO-F504 FIRE ALARM PLAN - THIRD FLOOR
20 PHX-D-TRACO-F600 THIRD FLOOR TEMPORARY OFFICE
21 PHX-D-TRACO-F700 COMPLEX AREA PHOTOGRAPHS
22 PHX-D-TRACO-F701 COMPLEX AREA PHOTOGRAPHS
23 PHX-D-TRACO-F800 FIRST FLOOR LOBBY
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
ENGINEERING SERVICES
LCC
LCC
TJF
10/11/2023
PHX-D-TRACO-F000 X
2½" ANGLED HOSE
VALVE, PHX THREADS
2½" ANGLED HOSE VALVE, PHX THREADS
2½" ANGLED HOSE VALVE, PHX THREADS
2½" ANGLED HOSE VALVE, PHX THREADS
UG1
UG4
SRC
UG2
UG3
UG5
UG6
EXISTING REDUCED
PRESSURE PRINCIPAL
DEVICE
EXISTING REDUCED
PRESSURE PRINCIPAL
DEVICE
BF3
BF4
BF1
BF2
SITE LEGEND
FIRE HYDRANT
XXX HYDRAULIC REFERENCE
POINTS / NODES
UNDERGROUND SECTION VALVE
UNDERGROUND DOMESTIC
WATER LINE
UNDERGROUND FIRE
WATER LINE
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
FLOW TEST SUMMARY
SITE PLAN
PLAN
NORTH
1" = 20'-0"
FLOW TEST REDUCTION
ACTUAL REDUCED (10 PSI)
STATIC 79 69
RESIDUAL 72 62
GPM 2,287
SITE PLAN GENERAL NOTES:
A SIMILAR FLOW TEST WAS
PERFORMED, SAME DATE, ON THE
SOUTH SIDE OF THE PROJECT AREA.
THE MORE CONSERVATIVE RESULTS
WERE USED IN THE DESIGN PROCESS,
AND ARE SHOWN ON THIS SHEET.
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
BACKFLOW PREVENTER FRICTION LOSS
ENGINEERING SERVICES
LCC
LCC
TJF
10/11/2023
PHX-D-TRACO-F001 X
5 5.2
'-0
6" FEED FOR BASE
BUILDING AND
TRACON TO STAIR #3
6" FEED FOR
TOWER STANDPIPE
TO STAIR #1
6" FEED FROM FIRE
PUMP DISCHARGE
6" FEED FROM FIRE
PUMP BYPASS
6" FROM FLOW
METER LOOP
3 FIRE PUMP PLAN VIEW
1/2" = 1'-0"SCALE:
NORMALLY
OPEN
NORMALLY
OPEN
H4
H3
2 FIRE PUMP SECTION
3/4" = 1'-0"SCALE:
'-0
NORMALLY
CLOSED
NORMALLY
OPEN
NORMALLY
OPEN
NORMALLY
CLOSED
NORMALLY
CLOSED
PO PI
H4 S1
S2H3
JOCKEY PUMP
CONTROLLER
FIRE PUMP
CONTROLLER
6" WATER
SUPPLY FROM
MUNICIPALITY
6" TO
EXTERIOR
FDC
6" TO EXTERIOR
TEST HEADER
6" FEED FOR
TOWER STANDPIPE
TO STAIR #1
6" FEED FOR BASE
BUILDING AND
TRACON TO STAIR #3
CLEAR ZONE
CLEAR ZONE
1 FIRE PUMP PLAN VIEW
1/2" = 1'-0"SCALE:
NORMALLY
OPEN
NORMALLY
OPEN
NORMALLY
OPEN
NORMALLY
OPEN
S2
UG1
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
X-### A
F-100
OS
&Y
VA
LV
E w
/TA
MP
ER
CH
EC
K V
AL
VE
OS&Y VALVE w/TAMPER
RELIEF VALVE
3/32" ORIFICE IN CLAPPER
(TYP.2)
BRONZE CHECK VALVE W/
FIRE PUMP
1/2" GLOBE VALVE
PUMP CONTROLLER
PRESSURE SWITCH
(AT CONTROL PANEL)
BRONZE CHECK VALVE W/
3/32" ORIFICE IN CLAPPER
(TYP.2)
JOCKEY PUMP
1/2" GLOBE VALVE
CONTROLLER
PRESSURE SWITCH
(AT CONTROL PANEL)
RE
LIE
F V
AL
VE
1/4" PLUG
TEST CONNECTION AT OR
NOT LESS THAN 5 ft 0 in
1/2" BRASS/COPPER PIPE
AND FITTINGS
1/4" PLUG
1/4" PLUG
TEST CONNECTION AT OR
1/4" PLUG
NOT LESS THAN 5 ft 0 in
BRONZE CHECK VALVE W/3 /32" ORIFICE IN CLAPPER
SPRINKLER
PIPING
AFCON #410
PIPE CLAMP
2" x 2 1/2" BELL.
WELDED
2" COMPANION FLANGE W/
(4) 12" x 51
2" HILTI KWIK BOLT TZ
WELDED
CONCRETE
2" SCH 40 PIPE
BETWEEN CONTROL VALVE
CONNECT TO DISCHARGE
AND CHECK VALVE
BETWEEN CONTROL VALVE
CONNECT TO DISCHARGE
AND CHECK VALVE
1/2" BRASS/COPPER PIPE
AND FITTINGS
SUCTION DISCHARGE DISCHARGE
SENSING LINE
JOCKEY PUMP
JOCKEY PUMP
FIRE PUMP NOTES
1. FIRE PUMP INSTALLATION SHALL CONFORM TO NFPA 20 2022 EDITION.
2. FIRE PUMP SEQUENCING:
PRIMARY PUMP CHURN: 97 PSI
PRIMARY PUMP RATING: 90 PSI
STOP POINT FOR JOCKEY PUMP: 166 PSI
JOCKEY PUMP START POINT: 156 PSI
PRIMARY PUMP START POINT: 151 PSI
STOP POINT FOR PRIMARY PUMP: 166 PSI
THE PUMP WILL CONTINUE RUN UNTIL
1.MANUAL STOP OR
2.OPERATION BY AUTOMATIC PERIODIC EXERCISE TIMERS USED FOR THE
REQUIRED PREVENTIVE MAINTENANCE RUN TIMES OR
3. AUTOMATIC SHUT DOWN UPON TOTAL EXHAUSTION OF SUCTION WATER.
ALL PIPING TO BE REQUIRED TO BE HYDROSTATICALLY TESTED I.E.
SUCTION SIDE , DISCHARGE SIDE & TEST HEADER.
BASEMENT FIRE PUMP GENERAL NOTES:
1. FLOOR FINISH TO BE REPAIRED WHERE NEEDED, 2-PART EPOXY TO MATCH
EXISTING.
2. POWER TO PUMP CONTROLLERS SHALL BE ROUTED INTO THE BOTTOM OF THE
CONTROLLER.
3. FIRE PUMP AND ALL ASSOCIATED PIPING/VALVES TO BE REPLACED.
X-
A
F-100
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
ENGINEERING SERVICES
LCC
LCC
TJF
10/11/2023
PHX-D-TRACO-F100 X
XXX
JOCKEY PUMP
CONTROLLER
FIRE PUMP
CONTROLLER
CLEAR ZONE
CLEAR ZONE
1 FIRE PUMP PLAN VIEW
1/2" = 1'-0"SCALE:
NORMALLY
OPEN
4" TO
EXTERIOR FDC
ON LEVEL 1
6" TO EXTERIOR
TEST HEADER ON
LEVEL 1
STAIR 2 STANDPIPE
CONNECTION
STAIR 1 STANDPIPE
CONNECTION
NORMALLY
OPEN
6" X 4"
CONC.
RED.
EXISTING FLOOR
PENETRATION FOR
FIRE PUMP FEED
NORMALLY
OPEN
NORMALLY
OPEN
3 FIRE PUMP SECTION
1/2" = 1'-0"SCALE:
6" TO
EXTERIOR FDC
6" TO EXTERIOR
TEST HEADER
6" FROM FLOW
METER LOOP
6" FEED TO
STAIR 1
6" FEED TO
STAIR 2
6" FEED FROM FIRE
PUMP DISCHARGE
6" FEED FROM FIRE
PUMP BYPASS
NORMALLY
CLOSED
NORMALLY
OPEN16
'-0
2 FIRE PUMP SECTION
1/2" = 1'-0"SCALE:
NORMALLY
CLOSED
NORMALLY
CLOSED
NORMALLY
OPEN
NORMALLY
OPEN
NORMALLY
OPEN
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
FIRE PUMP NOTES
1. FIRE PUMP INSTALLATION SHALL CONFORM TO NFPA 20 2022 EDITION.
2. FIRE PUMP SEQUENCING:
PRIMARY PUMP CHURN: 76 PSI
PRIMARY PUMP RATING: 65 PSI
STATIC PRESSURE FROM BASEMENT FIRE PUMP: 82 PSI
STOP POINT FOR JOCKEY PUMP: 158 PSI
JOCKEY PUMP START POINT: 148 PSI
PRIMARY PUMP START POINT: 143 PSI
STOP POINT FOR PRIMARY PUMP: 158 PSI
THE PUMP WILL CONTINUE RUN UNTIL
1.MANUAL STOP OR
2.OPERATION BY AUTOMATIC PERIODIC EXERCISE TIMERS USED FOR THE
REQUIRED PREVENTIVE MAINTENANCE RUN TIMES OR
3. AUTOMATIC SHUT DOWN UPON TOTAL EXHAUSTION OF SUCTION WATER.
ALL PIPING TO BE REQUIRED TO BE HYDROSTATICALLY TESTED I.E.
SUCTION SIDE , DISCHARGE SIDE & TEST HEADER.
LEVEL 10 FIRE PUMP GENERAL NOTES:
1. POWER TO PUMP CONTROLLERS SHALL BE ROUTED INTO THE BOTTOM OF THE
CONTROLLER.
2. FIRE PUMP AND ALL ASSOCIATED PIPING/VALVES TO BE REPLACED BACK TO
VERTICAL RISERS.
X-### A
F-100
X-
A
F-100
OS
&Y
VA
LV
E w
/TA
MP
ER
CH
EC
K V
AL
VE
OS&Y VALVE w/TAMPER
RELIEF VALVE
3/32" ORIFICE IN CLAPPER
(TYP.2)
BRONZE CHECK VALVE W/
FIRE PUMP
1/2" GLOBE VALVE
PUMP CONTROLLER
PRESSURE SWITCH
(AT CONTROL PANEL)
BRONZE CHECK VALVE W/
3/32" ORIFICE IN CLAPPER
(TYP.2)
JOCKEY PUMP
1/2" GLOBE VALVE
CONTROLLER
PRESSURE SWITCH
(AT CONTROL PANEL)
RE
LIE
F V
AL
VE
1/4" PLUG
TEST CONNECTION AT OR
NOT LESS THAN 5 ft 0 in
1/2" BRASS/COPPER PIPE
AND FITTINGS
1/4" PLUG
1/4" PLUG
TEST CONNECTION AT OR
1/4" PLUG
NOT LESS THAN 5 ft 0 in
BRONZE CHECK VALVE W/3 /32" ORIFICE IN CLAPPER
SPRINKLER
PIPING
AFCON #410
PIPE CLAMP
2" x 2 1/2" BELL.
WELDED
2" COMPANION FLANGE W/
(4) 12" x 51
2" HILTI KWIK BOLT TZ
WELDED
CONCRETE
2" SCH 40 PIPE
BETWEEN CONTROL VALVE
CONNECT TO DISCHARGE
AND CHECK VALVE
BETWEEN CONTROL VALVE
CONNECT TO DISCHARGE
AND CHECK VALVE
1/2" BRASS/COPPER PIPE
AND FITTINGS
SUCTION DISCHARGE DISCHARGE
SENSING LINE
JOCKEY PUMP
JOCKEY PUMP
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
ENGINEERING SERVICES
LCC
LCC
TJF
10/11/2023
PHX-D-TRACO-F101 X
XXX
SOV
FROM FIRE PUMP
STANDPIPE FEED
2" DRAIN
1¼" RISER ASSEMBLY
6" COMBINATION
STANDPIPE W/
STANDPIPE ISOLATION
VALVE
1¼" RISER ASSEMBLY
DRAIN TO
AREAWAY
OPEN TO ABOVE
STANDPIPE AND
DRAIN SEISMIC
ASSEMBLY
4" BUTTERFLY
VALVE
PRE-ACTION
SYSTEM LEVEL 3
STAIR #4 HORIZONTAL
STANDPIPE
PRE-ACTION
SYSTEM LEVEL 2
6" STANDPIPE
2" DRAIN
2" DRAIN UP
1 EXISTING BASEMENT PIPING PLAN
1/8" = 1'-0"SCALE:
STAIR 3
7-11
3-
8½
0-7½
1-8
1¼ 2-
1¼ 6- 3½
1¼ 8-
½
1¼ 9-
½
1¼ 5-
1¼ 8-
½
1¼ 5-
1¼ 8-
½
1¼ 5-
1¼ 8-
½
1¼ 5-
1¼ 8-
½
1¼ 5-
1¼ 8-
½
1¼ 8-
½
1¼ 8-
½
1¼ 8-
½
1¼ 8-
½
1¼ 8-
½
1¼ 4-
1¼ 8-
½
1¼ 3-
1-3½
1¼ 8-
½
1¼ 7- 7½
1¼ 4-
1¼ 1- 8½
1¼ 2-3½
1¼ 1-
1¼ 6-
½
1¼ 6-
½
1¼ 9-
½
1¼ 9-
½
1¼ 9-
½
1¼ 9-
½
1¼ 9-
½
1¼ 9-
½
1¼ 7- 4½
1¼ 7-
½
1¼ 1-
2½ 0-6
1¼ 7- 4½
1¼ 7-
½
1¼ 1-
1¼ 7- 4½
1¼ 7-
½
1¼ 1-
1¼ 7- 4½
1¼ 7-
½
1¼ 1-
1¼ 7- 4½
1¼ 7-
½
1¼ 1- 32½
3-4 2½ 2-0
2½ 4-
2½ 8-
2½ 0-
2½ 6-
2½ 4-0
2½ 12-10
2½ 18-4
2½ 2- 4½
2½ 0-
2½ 3-
2½ 3-
2½ 2- 2½
2½ 3-
2½ 3-
2½ 3-
2½ 1-
2½ 4-
2½ 3-
2½ 0-
1½ 2-
1½ 1-7½
1¼ 10-6½
1¼ 0-4
1¼ 0-6
1¼
-5 ½
1¼ 9-
½
1¼
-5 ½
1¼ 9-
½
1¼ 8-2
1¼ 7-10½
1¼ 5-4
1¼ 1-10
1¼ 3- 7½
1¼ 5-4
1¼ 1-10
1¼ 7-10½
1½ 2-3
1¼ 7-4½
1¼ 7-10½
1¼ 2-3
1¼ 5-3
1¼ 7-10½
1¼ 7-4½
1¼ 7-10½
1¼ 2-3
1¼ 5-3
1¼ 7-10½
1¼ 3-1½
1¼ 7-10½
1¼ 2-3
1¼ 5-3
1¼ 7-10½
1¼ 2-3
1¼ 5-3
1¼ 7-10½
1¼ 1-10
1¼ 7-10½
1¼ 7-4½
1¼ 0- 9½
1¼ 7-4½
1¼ 7-10½
1¼ 2-3
1¼ 5-3
1¼ 7-10½
1¼ 7-4½
1¼ 7-10½
1¼ 3-0
1¼ 2-3
1¼ 5-3
1¼ 7-10½
2½ 16-1
2½ 3-4
2½ 10-6
2½ 0-6
1½ 0-
1½ 0-
1½ 6-
½
1½ 6-
½
1½ 6-
½
1½ 6-
½
2-0
1-0
4 7-
4 7-
7-
5-5
2-10
-7
-1
6 8-
8-0
6 9-
2-6½
5-10½1
5-2½
1¼ 1-
3½
2-1½
6 9- 2½
6-5
-1
1½ 4- 5½
1½ 6- 9½
1¼ 3-
4-4½
11-7½ 1 2-
11-0
1-4
1½ 1-3
½
24-0
1-5½
4 4
0-5
½
2½ 1-1½
1¼ 1-11½1¼
1-11
1¼ 3-0
1¼ 1-11½1¼
1-11
1¼ 2-11
1¼ 1-11½
1¼ 3-0
1¼ 1-11½1¼
1-11
1¼ 3-0
1¼ 1-11½1¼
1-11
1¼ 3-0
1¼ 1-11½1¼
1-11
1¼ 3-0
1¼ 1-11½1¼
1-11
2½ 3-
2½ 2- 8½
2½ 2- 8½
2½ 3- 2½
2½ 3-
2½ 3-
2½ 3-
2½ 3-
2½ 2-
2½ 4-7
2½ 0-6
2½ 3-2
1¼ 3- 2½
1¼ 2-
2½ 5-8
2½ 2-10
2½ 0-10 2½
2-0 2½ 3-4
2½ 3-4
2½ 3-4
2½ 3-4
2½ 4-4
2½ 4-4
2½ 4-4
2½ 4-4
2½ 4-4
2½ 4-6
2½ 3-2
2½ 3-2
2½ 4-6
2½ 3-
2½ 4-
2½ 2-
1¼ 3-
1¼ 2-
1¼ 3-
1¼ 2- 7½
1¼ 3-
1¼ 3-
1¼ 2- 7½
1¼ 3-
1¼ 3-
1¼ 2- 7½
1¼ 3-
1¼ 3-
1¼ 1- 7½
1¼ 3-
1¼ 3-
1¼ 2- 7½
1¼ 4-
1¼ 2-
½ 1¼ 1-
1¼ 4-
1¼ 2-
½ 1¼ 1-
1¼ 4-
1¼ 2-
½ 1¼ 1-
1¼ 4-
1¼ 2-
½ 1¼ 1-
1¼ 4-
1¼ 2-
½ 1¼ 1-
1¼ 4-
1¼ 2-
½ 1¼ 1-
3-44
2-0 44-842-643-5
2-104
2-0 44-842-640-11
2-10
2-0
1-5
3-4
3-4
3-4
8-10½
3-4
8-10½
3-4
8-10½
3-4
3-4
3-5
8-10
8-8
3-4
3-4
8-10
8-8
3-4
3-4
8-10
8-8
4-5
1¼ 4-2½
3-6
4-4½
4-6
4-6
6-7
1 0-
1 1-
1 0-
1 1-
1 4-
1 0-
1-3
1 4-
1 0-
1-3
1-3
0-
0-9
3-8
0-
0- 8 1
1-7
0-8
0-8
0-
3-7
0-8
0-8
0-8
FIRE
PUMP
ROOM
6" STANDPIPE,
LEVEL 10 FIRE
PUMP FEED
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
ENGINEERING SERVICES
LCC
LCC
TJF
PHX-D-TRACO-F102 X
EQ. EQ.
EQ.
71.9878
EQ.
EQ.
EQ. EQ.
71.9878
EQ. EQ.
75.0237 75.0237 75.0237 75.0237
EQ.
EQ.
74.0000
EQ.
20.0000
20.0000
MISSING WALL
MECHANICAL
TEE
6" COMBINATION
STANDPIPE W/
ISOLATION VALVE
6" STANDPIPE
FROM BASEMENT
WITH GATE VALVE
2" DRAIN
6" STANDPIPE
2" DRAIN
8" TEST HEADER
CONNECTION TO
FP-2
4" UP TO 10TH
FLOOR FIRE PUMP
(FP-2)
TEST HEADER CONNECTION
FOR FP-2 FROM 10TH FLOOR
3 X 2½" WITH CONTROL VALVES
SOV
METRAFLEX
SPRINKLER FCA
4" STANDPIPE
RISER
1 EXISTING FIRST FLOOR PIPING PLAN
1/8" = 1'-0"SCALE:
STAIR 3 STAIR 4
9-
½
5-11½
6-5½
1 0-
0-
½
0-
½
0-10½
10-11½
4-
9½ 1¼ 5- 6½
8-
1 5-
4-10
2-11
1¼ 0-9
½
3 6-
3-1
9-10 1
1-
3 0-
5-
0-8 ½
1¼ 0-8
½
4-3
7-4½
4-
½
7-
0½
1¼ 5-2
9-10½
10-0½
8-10½
4-
½
3 5-
1-
2½
1¼ 0-8
½
1¼ 5-8
8-10½
10-6½
7-10½
1¼ 5-8
8-
½
1¼ 6-11
1¼ 8-10½
1¼ 10-6½
1¼ 7-10½
7-
9½
0-6½
5-
8½ 3 8-
0-
1-0
1¼ 0-8
½
0-8 ½
1¼
0-8 ½
-0
0-6
1¼ 8-10½
1¼ 8-10½
8-10½
0-8
-0
0-81½ 8-2
1½ 8-10½
1¼ 7-7
1-1½
4-1½
1¼ 1-1
4-7½
1 3-
1¼ 2- 4½1 2-
0-2
2½ 2-9
2½ 6-0
1 6-
1 5-
7-
3-11
2½ 4-8½
2½ 1-3½
2½ 10-0
7-10
1 5-
4-
6-
2½ 1-0
2½ 7-
2½ 1- 6½
1¼ 11-0
11-3
3-9
7-10
2½ 0-
2½ 2- 6½
1¼ 1-6
3-0
1-
4½
3-
½
6-6
9-10
1¼ 2-10
1¼ 4-4½ 1
4-10
11-4
7-10
2½ 6-
2½ 1-
10-10
6-4
13-10
1 0-
1 1-
1¼ 1-6
8-5
5-3½
1 1-
1 1-
2½
-2 ½
1¼ 2-0
1-
3½
0-
7-11
5-3½
11-10
2½ 0- 5½
0-8
2½ 1- 6½
2½ 1- 2½
10-10
6-4
13-10 1 1-
2½ 5-
8-10
6-6½
0-
9½
2½ 1-
1 1-
1¼ 0-8 1¼
6-7
4-10
11-4
7-10
2½ 3- 6½
2½ 0-
½
8-10
6-7
7-101
2- 0½
1 1- 2 1
0- 8½
1¼ 0-8
10-10
11-1
10-2
1-
0½
2½ 8- 5½
2½ 2-
2½ 0-
4-3½
11-10
5-7
9-10
11-10
2½ 3-0
2½ 8-8½
2½ 5-3½
1¼ 10 -0
9-
½
1-
4½
1-
½
11-4
7-10½
2½ 10-3
2½ 6-2½
1-
8½
2½ 0-6
2½ 23-1
2½ 24-0
2½ 2- 8½
12-9
9-10
2½ 3- 8½
6-0
11-10
12-1½
9-5 1 1-
1-
3½
1-
6½
2½ 2- 11 1 1-
4 1 1- 4 1 1-
0-
9½
1¼ 5-6
1¼ 13-10
13-10
2-4½
3-7
2½ 8-
2½ 0-
5-0½
12-7
11-10
9-0
14-10½
9-10
2½ 2-
3-5
1¼ 3-6
11-61¼
9-6
7-3
7-91
1- 5½1
0- 2½
2½ 3-
2½ 1- 6½
1¼ 12-9
1¼ 9-10
8-4
1 3-
1-
1½
1-
½
8-3
2-7
2½ 7-
1¼ 3-6
1¼ 11-6
1¼ 9-6
1 2-
7-3
7-9
3-
1½ 1 2- 7 1
1-
1 4-
0-4
2½ 4- 1½
1¼ 3-5
1¼ 9-2
1¼ 9-10
1¼ 7-4
1-
3½
3-
8½
2-
2½
8-2½
1 3-
1-10
1 2-
1-
6½
2½ 7-
½
1¼ 3-6
8-81
1-
7-9
1 3-
2½ 1-
½
2½ 0-
3-5
2½ 3-
1¼ 12-9
1¼ 9-10
1¼ 8-4
10-2½
1-
8½
3-
3½ 2½ 4-
1¼ 4-6
1¼ 9-9½
10-3
0-
7½
7-3
7-9
0-
½ 1
1- 4½
2½ 2-
1¼ 3-5
1¼ 9-2
8-41
2-0
6-8½
1 3- 21 0-
0-
6½
1 1-
1 0-
2½ 4-
1¼ 8-1
1¼ 10-2
10-2
10-4
3-11½
1 3-
2½ 1-
1¼ 8-1½
1¼ 0-5½
11-10
7-4
8-6 1
0- 5½
2½ 6-
2½ 3-
2½ 2- 5½
2½ 0-
1¼ 6-6
1¼ 4-7
8-11½
1¼ 12-1½
2-
3½
1 1-
1 6-
1 1-
3-2½
7-6
1 2-
1¼ 5-0
1¼ 12-0
11-7
7-10
11-7
1-
5- 3½
2-
4½
0- 4½
4 9-
17-10
1½ 2-
1½ 1-
6-6
1-10
1¼ 9-
9-10
1¼ 6-
1 1-
1-
1 0- 4 1 0- 4 1 0-
0-
4½
0-
5-9½
1¼ 0-10
5-9½
0-8½
1 4-
1-10½
9-9½1 0-
1 0-
1-
3-6½
1-
4½
1-
8½1 1-
8½
2½ 1-9½
1-
8½
3-9½
5-10½
1-
8½1 1-
8½
5-4½
9-10½
6-5½
3 6-
-0
4-
½
1- 8½
3-9½
13-10
14-5½
12-10½
1-9½
8-7½
0-4
11-0½
0-4
11-0½
1¼ 0-9
½
0-6
3-10
1¼ 7-8
1¼ 3- 8½
1-
0½
3 3-
-4 ½
1 0-
-4 ½
1 0-
24-0
5-8
0-6
1½ 8-2
0-6½
0-6½
0-6½
2-1
24-0
24-04
5-9
4 6-
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
ENGINEERING SERVICES
LCC
LCC
TJF
PHX-D-TRACO-F103 X
6" STANDPIPE
4" UP TO 10TH
FLOOR FIRE PUMP
(FP-2)
TEST HEADER
CONNECTION FOR FP-2
FROM 10TH FLOOR
6" COMBINATION
SPRINKLER/STANDPIPE
RISER
EXPRESS DRAIN
4" STANDPIPE
RISERSPRINKLER FCA
1 EXISTING SECOND FLOOR PIPING PLAN
1/8" = 1'-0"SCALE:
STAIR 3 STAIR 4
11'-10"
7'-9"19'-10"
2½ 2-2 6
1-
½
2½ 4-
2½ 1-11½
11-9
10-10
1 2-
1-4
2½ 2-0 1 1-
2½ 6-1
2½ 7-5
1 7-
7-
10 1 7-
1 7-
2½ 6-7
2½ 0-9½
2½ 6-4½
2½ 2- 5½
1¼ 9-8
1¼ 7-0
2-8
9-10
1-10½
1 6-
6-1½
1¼ 8-
9-
½
1 2-
1 1-
8-0
6-0
2½ 9-
2½ 0-
2½ 13 -7
2½ 6-
2½ 3-
2½ 0-
2½ 6- 5½
2½ 7-
½
2½ 7- 5½
2½ 1- 3½
2½ 0-
4-5
15-0
7-8
5-7
13-10
7-9
1 2-
1 1-
13-10½
9-10
7-10
3-5
11-10
1-3
2-10
12-3½
9-6
1 1-
8-8
9-10
9-6 1 1-
61 1-
0-
½
1¼ 2-7
11-10
7-10
5-7
1-
5-9
9-4½
10-5
1-
3½ 1 0-
6½
1¼ 4-10
6-6
5-6
8-11 1-
0-
9½ 1 0-
9½ 1 0-
9½
1 1- 21 1-
4-8
13-10
1¼ 4-0½
9-6
10-11½
7-10
1¼ 1-9
½
1¼ 7-5½
1¼ 5-7½
1¼ 5-9½
7-5
1 1-
6-4
2-8
5-6
2-
3 8-
23-11½
24-0
1½ 2-
1½ 1- 1 1
6-6
4-0
1¼ 9-
1-5½
9-10
1¼ 6-
1 3-
1 1-
1 2-
2-11½
5-5½
4-11½
1-
6½
1 1-
1-10
1 0- 3 1 0-
1-
1½
9-5
3 2-
1¼ 4-8
6-11½
6-3
9-10
1¼ 4-9
7-10
11-3½
13-10
3 9-
1¼ 1-8
12-10
3-
1¼ 0-10
5-11
6-3½ 1 1-
1 3-
1-3
½
0-
7½ 3 0-
1¼ 10-91
1-
3-
0-10
11-10
2-10
2-
6-1½
3-
5½
3 6-
1¼ 7-8
3 0-
1¼ 6-10
1¼ 0-10
1¼ 7-10
3-10
3-10
7-10½
1 6-
1 0-
5-
0½
1 1-
1 3-
2-
7½
3 0-
1¼ 1-9
11-10
17-10 1
1-
0-
3 8-
1¼ 10-9
12-10
11-10
3-101
1- 10 1
0-
3 4-
1-
5-9
1¼ 3-8
1¼ 0-10
1¼ 18-10
8-10
4-10
3-10½
3-
1-
3-
1 2-
3 8-
1¼ 3-9
1¼ 11-10
1¼ 5-10
1¼ 7-10
1¼ 9-10
3-10
3-11½
1-1
1 2-
1 4-
0-
10 1 1-
0-
1-
1¼ 9-8
1¼ 5-10
1¼ 3-10
1¼ 1-10
5-10
5-10
5-10
1-
2-
5-
5-
2-
3-
3 2-
3 0-
-6
1¼ 3-9
1¼ 11-10
1¼ 5-10
1¼ 9-10
1¼ 7-10
3-10
4-1½
1-0
1 2-
4-
0½
0-
0-
3-
1-
1¼ 9-8
1¼ 5-10
11-10
5-10
5-10
3-
0-
1-
0-
19-10
7-9
3 8-
3 4-
1¼ 1-8
1¼ 2-10
1¼ 10-10
1¼ 1-10
3-10
6-10
4-10
3-
5-
3-
3-
3 0-
3 1-
1¼ 10-9
1¼ 8-10
11-10
2-101
4-10
3-
4-
0-
1-
3-8½
16-10
4-10
1-
3 8-
3 3-
7-9
13-10
3-10
2-
2-
7-8½
5-10
2-
3 4-
6-9 3 1-
3 4-
13-9
3 2-
3 0-
P P
P P
P
P
P
P
P
P
P
P P
P
P
P
P
P
P - SPRINKLERS IN EQUIPMENT RING SOFFIT REMOVED AND PLUGGED (TYPICAL)
3-0½
4-9
1-
6½
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
ENGINEERING SERVICES
LCC
LCC
TJF
PHX-D-TRACO-F104 X
FLOOR FIRE PUMP
(FP-2)
TEST HEADER
CONNECTION FOR FP-2
FROM 10TH FLOOR
6" COMBINATION
SPRINKLER/STANDPIPE
RISER
EXPRESS DRAIN
4" STANDPIPE
RISER
1 EXISTING THIRD FLOOR PIPING PLAN
1/8" = 1'-0"SCALE:
2½ 2-2
2½ 0-
1 8-
2½ 0-
1-
½
0-7½
2½ 0-
2½ 0-6
2½ 6-
1¼ 0-8
½
2½ 3-3½
2½ 6-5
3-
1 9-
8-
-4
8-
2½ 4-0
1 3-
2½ 0-8½
2½ 2-5½
9-
8½
9-
½
2½ 3-3
2½ 5-4½
1¼ 6-
1 7-
3-
3½
2- 1½
8-2½
2½ 1-8
2½
-8 ½
2½ 10 -0
2½ 0-
1¼ 6-2½
7-6
9-10
5-10
1¼ 7-3
9-10
6-0½
13-10
1¼ 6-2½
7-6
9-10
7-10
1¼ 7-3
9-10
6-0½
13-10
1¼ 7-
7-0½
4-7½
8-3½
3-
3-
2½ 9-1½
1¼ 3-4½
9-6½
11-10
2½ 4-
2½ 1- 7½ 1¼
1-81 0-
½
1 0-
1¼ 9-10
1 1-
1¼ 10-2 1¼
9-0½
1 0-
6-11½
5-10
5-10
2½ 3- 6½
2½ 5- 9½
1¼ 3-4½
5-4½
7-10½
8-0
1 0-
0-
½1
0-
½
2½ 0-
1¼ 1-8
1¼ 9-10
1¼ 10-2
1¼ 5-7
6-5½
7-10
7-10
1 0-
1 0-
3-
3½
1 0-
2½ 12 -7
1¼ 3-4½
5-4½
7-10½
8-0
1 1-
1 1-
0-
2½
1¼ 1-8
1¼ 9-10
1¼ 9-2
1¼ 6-1½
6-11
7-10
7-10
1 1- 2 1 1- 2 1 1-
1 0- 7 1 0- 71 0-
2½ 4-
1¼ 2-3
8-10½
8-10
8-10
0-
0-
1¼ 9-3
1¼ 11-10
11-10
11-10
4-10 1
1-
2½ 8-
1¼ 2-3
8-10½
8-10
8-10
1 1-
1¼ 2-3
8-10½
8-10
8-10
1 1- 21 1- 21 1-
0-
10 1 0-
2½ 2-
2½ 7-
2½ 0-
1¼ 9-3
1¼ 11-10
11-10
11-10
1¼ 9-3
1¼ 11-10
11-10
7-10
8-10
1 1- 2 1 1- 2 1 1- 2 1 1-
0-
10 1 0-
10 1 0-
10 1 0-
2-
1¼ 11-10
11-10
-4
2-
½
-9
23-11
24-0
15-2
-1
-3 ½
4-1½
6-6
3-6
10-0
8-0
2-0
7-
2½
-1
-1
7-
2½
-1
-1
7-
2½
-1
-1
7-
2½
-1
-1
0-6
1-10
2-
2½
9-
2-
2½
9-
9-
2-
2½
9-
9-
1¼ 2- 2½
9-
9-
7-
1¼ 2- 2½
9-
9-
7-
1¼ 2- 2½
9-
9-
7-
1¼ 2- 2½
9-
9-
7-
7-
2½1 7-
2½
3-2
4-3
3-9
1 6-
15-5½14-2½
7-
2½
8-0
5-9
1-
7½
-1
1-
0½
-1
1-63
3-10
0-6
1¼ 9-
½
9-
½
1 6-
3-
2½
6-11½
2-
5½
1-
5-10½
4-5½
1¼ 7-
1½ 4-
-4
-4
9-6
2-2½
9-6
2-2½
3-6
5-10½
1¼ 1-
4-
4½
1-
0-
2½ 2-0
1 2-
13-11
7-10
7-10
2½ 1-4
2½ 6-4
1 2-
2½ 0-6½
2-
2½ 4-
2½ 2-10½ 1 2-
9-
8½
9-
½
1¼ 2- 3½
0-2
2½ 11-6
1 2-
1 7-
2½ 4-4½
2½ 2-9
2½ 7-9
1 2-
2½ 12-0
1 2-
2½ 4-3
2½ 5-5½
1¼ 2- 3½
11-10½
8-9½
0-6
2½ 0-
3-
1 1- 0 1 1- 0 1 1-
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
ENGINEERING SERVICES
LCC
LCC
TJF
PHX-D-TRACO-F105 X
6" STANDPIPE,
LEVEL 10 FIRE
PUMP FEED
FROM FIRE PUMP
STANDPIPE FEED,
SEE F100 FOR
CONTINUATION
2" DRAIN
1¼" RISER ASSEMBLY
6" COMBINATION
STANDPIPE W/
STANDPIPE ISOLATION
VALVE
1¼" RISER ASSEMBLY
WITH WATERFLOW
MAIN DRAIN LOCATION:
DRAIN TO AREAWAY W/
SUPERVISED BALL VALVE
FOR NITROGEN INERTING
OPEN TO ABOVE
STANDPIPE AND DRAIN
SEISMIC SEPARATION
ASSEMBLY, PROVIDE
AUXILIARY DRAINS FOR
LOW POINT DRAINING
AND NITROGEN
PURGING. DRAIN FIRST
BEFORE NITROGEN
PURGING.
STAIR #4 HORIZONTAL
STANDPIPE
6" STANDPIPE
2" DRAIN
2" DRAIN UP
1 NEW BASEMENT PIPING PLAN
1/8" = 1'-0"SCALE:
STAIR 3
SPB1
H1
H2
INLINE
CORROSION
DETECTOR AT
TOP OF RISER
2½" BUTTERFLY
VALVE W/ CHAIN
OPERATION
2½" BUTTERFLY
VALVE W/ CHAIN
OPERATION
AUTOMATIC
AIR VENT
AUTOMATIC
AIR VENT
AUXILIARY DRAIN
CONNECT TO ADJACENT
FLOOR DRAIN
1-4
1¼ 1-
1¼ 9-
1¼ 8-
½
1¼ 9-
½
1¼ 5-
1¼ 8-
½
1¼ 5-
1¼ 8-
½
1¼ 5-
1¼ 8-
½
1¼ 5-
1¼ 8-
½
1¼ 5-
1¼ 8-
½
1¼ 8-
½
1¼ 8-
½
1¼ 8-
½
1¼ 2-
1¼ 8-
½
1¼ 3-
1¼ 1-3½
1¼ 8-
½
1¼ 7- 7½
1¼ 4-
1¼ 1- 8½
1¼ 2-3½
1¼ 1-
1¼ 6-
½
1¼ 6-
½ 1¼
9-
½
1¼ 9-
½
1¼ 9-
½
1¼ 9-
½
1¼ 9-
½
1¼ 9-
½
1¼ 7- 4½
1¼ 7-
½
1¼ 1-
2½ 0-6
1¼ 7- 4½
1¼ 7-
½
1¼ 1-
1¼ 7- 4½
1¼ 7-
½
1¼ 1-
1¼ 7- 4½
1¼ 7-
½
1¼ 1-
1¼ 7- 4½
1¼ 7-
½
1¼ 1-
2½ 3-4
2½ 2-2
2½ 4-
2½ 8-
2½ 0-
2½ 6-
2½ 4-0
2½ 12-10
2½ 18-4
2½ 2- 4½
2½ 0-
2½ 3-
2½ 3-
2½ 2- 2½
2½ 3-
2½ 3-
2½ 3-
2½ 1-
2½ 4-
2½ 3-
2½ 0-
1½ 2-
1½ 1-7½
1¼ 10-6½
1¼ 0-4
1¼ 0-6
1¼
-5 ½
1¼ 9-
½
1¼
-5 ½
1¼ 9-
½
1¼ 8-2
1¼ 7-10½
1¼ 5-4
1¼ 1-10
1¼ 3- 7½
1¼ 5-4
1¼ 1-10
1¼ 7-10½
1½ 2-3
1¼ 7-4½
1¼ 7-10½
1¼ 2-3
1¼ 5-3
1¼ 7-10½
1¼ 7-4½
1¼ 7-10½
1¼ 2-3
1¼ 5-3
1¼ 7-10½
1¼ 3-1½
1¼ 7-10½
1¼ 2-3
1¼ 5-3
1¼ 7-10½
1¼ 2-3
1¼ 5-3
1¼ 7-10½
1¼ 1-10
1¼ 7-10½
1¼ 7-4½
1¼ 0- 9½
1¼ 7-4½
1¼ 7-10½
1¼ 2-3
1¼ 5-3
1¼ 7-10½
1¼ 7-4½
1¼ 7-10½
1¼ 3-0
1¼ 2-3
1¼ 5-3
1¼ 7-10½
2½ 16-1
2½ 3-4
2½ 10-6
2½ 0-6
1½ 0-
1½ 0-
1½ 6-
½
1½ 6-
½
1½ 6-
½
1½ 6-
½
7-
5-5
6 8-
8-0
6 9-
2-6½
5-10½1
5-2½
1¼ 1-
3½
2-1½
6 9- 2½
6-5
-1
1½ 4- 5½
1½ 6- 9½
1¼ 3-
4-4½
11-7½ 1 2-
11-0
1-4
1½ 1-3
½
24-0
1-5½
0-5
½
2½ 1-1½
1¼ 1-11½
1¼ 1-11
1¼ 3-0
1¼ 1-11½
1¼ 1-11
1¼ 2-11
1¼ 1-11½
1¼ 3-0
1¼ 1-11½1¼
1-11
1¼ 3-0
1¼ 1-11½1¼
1-11
1¼ 3-0
1¼ 1-11½1¼
1-11
1¼ 3-0
1¼ 1-11½1¼
1-11
2½ 3-
2½ 2- 8½
2½ 2- 8½
2½ 3- 2½
2½ 3-
2½ 3-
2½ 3-
2½ 3-
2½ 2-
2½ 4-7
2½ 0-6
2½ 3-2
1¼ 3- 2½
1¼ 2-
2½ 5-8
2½ 2-10
2½ 0-10 2½
2-0 2½ 3-4
2½ 3-4
2½ 3-4
2½ 3-4
2½ 4-4
2½ 4-4
2½ 4-4
2½ 4-4
2½ 4-4
2½ 4-6
2½ 3-2
2½ 3-2
2½ 4-6
2½ 3-
2½ 4-
2½ 2-
1¼ 3-
1¼ 2-
1¼ 3-
1¼ 2- 7½
1¼ 3-
1¼ 3-
1¼ 2- 7½
1¼ 3-
1¼ 3-
1¼ 2- 7½
1¼ 3-
1¼ 3-
1¼ 1- 7½
1¼ 3-
1¼ 3-
1¼ 2- 7½
1¼ 4-
1¼ 2-
½ 1¼ 1-
1¼ 4-
1¼ 2-
½ 1¼ 1-
1¼ 4-
1¼ 2-
½ 1¼ 1-
1¼ 4-
1¼ 2-
½ 1¼ 1-
1¼ 4-
1¼ 2-
½ 1¼ 1-
1¼ 4-
1¼ 2-
½ 1¼ 1-
2-10
2-04
1-5
3-4
3-4
8-10½
3-4
3-4
8-10
8-8
1¼ 4-2½
3-6
4-4½
4-6
4-6
6-7
0-
7½
1 1-
1 0-
1-3
1-3
0-
0-9
3-81
0-
0-
8 1 1-7
0-8
0-8
10-8
3-7
0-8
10-8
0-8
FIRE
PUMP
ROOM
EXISTING
PRE-ACTION
SYSTEM TO BE
DEMOLISHED
DEMO
DEMO
DEMO
DEMO
DEMO
DEMO
DEMO
DEMO
DEMO
DEMO
D
EM
O
D
EM
O
D
EM
O D
EM
O
SEE F100 FOR
CONTINUATION
ECS RIS-1
INERTING STATION
AUXILIARY DRAIN,
GANG BRANCHLINES
TOGETHER
ECS RIS-1
INERTING STATION
1¼ 8-
½
0-
7½
1¼ 8-
½
0-
7½
1¼ 2-
0-8
0-8
2-0
1-2
1 3-
0-8
3-7
AUXILIARY DRAIN
AND PIPE TO
FLOOR DRAIN
1¼ 2-5
1¼ 5-1½
5-1½
1 4-
1 2-
4" BUTTERFLY
VALVE W/ CHAIN
OPERATION
CORE AND DRILL
CONCRETE WALL
SHEET LEGEND
NEW BUTTERFLY ISOLATION
VALVE
XXX HYDRAULIC REFERENCE
POINTS / NODES
PIPE HANGER
LATERAL SEISMIC BRACING
FOUR-WAY SEISMIC
BRACING
LONGITUDINAL SEISMIC
BRACING
PIPING OFFSET
FLEXIBLE HOSE SPRINKLER
DROP
RIGID ONE-SIDED
BRANCHLINE RESTRATINT
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
SEISMIC BRACING AND RESTRAINT NOTES:
1. LATERAL BRACING AND LINE RESTRAINTS SHALL NOT BE REQUIRED FOR PIPES SUPPORTED BY RODS
LESS THAN 6" IN ACCORDANCE WITH NFPA 13 SECTION 18.6.5
2. FOUR-WAY BRACE SHALL CONSIST OF 1 LATERAL AND 1 LONGITUDINAL BRACE PER DETAILS IN
COMPLIANCE WITH SECTIONS 18.5.5.8 AND 18.5.6.2.
3. A FOUR-WAY BRACE SHALL BE PROVIDED AT THE TOP OF EACH SPRINKLER RISER AND STANDPIPE PER NFPA 13 SECTION 17.4.5.4, AND AT MAXIMUM 25 FEET SPACING ON INDIVIDUAL RISERS.
4. LATERAL BRACING TO ACT AS LONGITUDINAL BRACING WHEN INSTALLED WITHIN 24" OF THE
CENTERLINE OF PIPING TO BE BRACED LONGITUDINALLY PER NFPA 13 SECTION 18.5.5.8
5. LONGITUDINAL BRACING TO ACT AS LATERAL BRACING WHEN INSTALLED WITHIN 24" OF THE
CENTERLINE OF PIPING TO BE BRACED LATERALLY PER NFPA 13 SECTION 18.5.6.2
BRACE PIPE
LONGITUDINAL SEISMIC BRACE
THREADED BRACE PIPE -
FIG. 910
SWIVEL SWAY
BRACE FITTING
FOR SWAY BRACE
PIPE CLAMP
FIG. 4A
BRACE PIPE
SWAY BRACE ATTACHMENT
``FAST CLAMP''
LATERAL SEISMIC BRACE
BRACE PIPE THREADED ONE END
FIG. 1000
FIG. 910
SWIVEL SWAY
BRACE FITTING
R
SELF DRILLING ANCHOR, ROD AND RING
POST-INSTALLED
ADJUSTABLE RING HANGER
TOLCO
ALL THREAD ROD
CONCRETE ANCHOR
SURGE RESTRAINERS
BRANCH LINE SWAY RESTRAINT
BRANCH LINE
EQ.
CONCRETE DECK
SWIVEL ATTACHMENT
45 DEG.
EXPANSION ANCHOR MIN.3/8"
BRACING AND RESTRAINTS NOT SHOWN
BRACING AND RESTRAINTS NOT SHOWN
TOLCO
TOLCO
E Q
AUTOMATIC AIR VENT DETAIL
ECS PAV-WNS NITROGEN
INERTING VENT
PGSP-1 GAS
SAMPLE PORT
1" GATE VALVE
AUXILIARY DRAIN W/ PLUG
OR DRAIN TO EXTERIOR
BRANCHLINE
PROVIDE VALVES WITH LOCKABLE
OR REMOVABLE HANDLES TO
AAV PRESSURE SENSOR WIRING INSTALLATION DETAIL
PREVENT TAMPERING
JUNCTION BOX
OVER PRESSURE
SENSOR
FLEXIBLE STEEL
CONDUIT
MONITORING
MODULE
ECS PAV-WNS
NITROGEN
INERTING VENT
CEILING WHERE APPLICABLE
INSTALL COMPRESSION
FITTING OVER METAL
PORTION OF PRESSURE
SENSOR
NOTE: NO HANGING FROM SHARED
SUPPORT STRUCTURES I.E DUCTS.
F-100
GENERAL NOTES:
1. WHERE POSSIBLE, ALL NEW AND REPLACEMENT PIPING SHALL BE INSTALLED WITH
BRANCHLINES HAVING A PITCH TOWARDS DRAIN OF ½" PER 10-FEET, AND MAINS SHALL BE
INSTALLED HAVING A PITCH OF ¼" PER 10-FEET SIMILAR TO THE REQUIREMENTS OF
PRE-ACTION SYSTEMS IN ACCORDANCE WITH 2022 NFPA 13, SECTION 16.10.3.2.
2. * - RIGID ONE-SIDED BRANCHLINE RESTRAINT, SEE DETAIL ON THIS SHEET.
3. SPRINKLER DROPS SHALL BE EASYFLEX FLEX 72" SPRINKLER HOSE - ULTRA HIGH
PERFORMANCE OR EQUIVALENT.
4. SEE F700 AND F701 FOR INFORMATION PHOTOGRAPHS WHICH IDENTIFY KEY CEILING AND
OVERHEAD CONDITIONS WHERE INSTALLATION MAY BE MORE CHALLENGING.
TY
PE
FL
OO
R
TO
TA
L
OR
IF
IC
E
RE
SP
ON
SE
TY
PE
TH
RE
AD
TE
M P.
K-
FA
CT
OR
FI
NI
SH
QT
Y.
SY
M
BO
L
S P
R
IN
K L E
R L
E G
E N
D
R
EL
IA
BL
E F1
FR
R A3
SS
U
QR
BR
AS
S
8.
¾
0°
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
1 FIRST FLOOR LOBBY
1/8" = 1'-0"SCALE:
F-106
ENGINEERING SERVICES
LCC
LCC
TJF
PHX-D-TRACO-F106 X
1 FIRST FLOOR LOBBY STAIR SECTION
1/4" = 1'-0"SCALE:
FEED FROM FIRST
FLOOR LOBBY
SPRINKLER PIPING
PROVIDE
SPRINKLER
PROTECTION
UNDER STAIR
EQ. EQ.
EQ.
71.9878
EQ.
EQ.
EQ. EQ.
71.9878
EQ. EQ.
75.0237 75.0237 75.0237 75.0237
EQ.
EQ.
74.0000
EQ.
20.0000
20.0000
6" COMBINATION
STANDPIPE W/
ISOLATION VALVE
6" STANDPIPE
FROM BASEMENT
WITH GATE VALVE
2" DRAIN
6" STANDPIPE
2" DRAIN
FDC PIPING UP TO
10TH FLOOR FIRE
PUMP (F101)
TEST HEADER CONNECTION
FOR F101 FROM 10TH FLOOR
3 X 2½" WITH CONTROL VALVES
METRAFLEX
SPRINKLER FCA
4" STANDPIPE
RISER
1 NEW FIRST FLOOR PIPING PLAN
1/8" = 1'-0"SCALE:
STAIR 3
SP1
3" BUTTERFLY
VALVE
2½" BUTTERFLY
VALVE
2½" BUTTERFLY
VALVE
REMOVE AND REPLACE
ALL PIPING, RESTORE
CEILINGS TO ORIGINAL
CONDITION
AUTOMATIC
AIR VENT
AUXILIARY DRAIN
WITH ACCESS PANEL
AUXILIARY DRAIN
W/ ACCESS PANEL
AUXILIARY DRAIN
W/ ACCESS PANEL
SPRINKLER
BELOW
SOFFIT ON
INTERMEDIATE
LANDING
9-
½
5-11½
5-8½
2-1½
9-8½
4-
9½ 1¼ 5- 6½
8-
1 5-
4-10
2-11
1¼
0-9
½
3 6-
5-8
7-8
3 0-
3 5-
0-8
½
1¼ 0-8
½
4-3
7-4½
4-
½
7-
0½
1¼ 5-2
9-10½
10-0½
8-10½
4-
½
3 5-
1-
2½
1¼ 0-8
½
1¼ 5-8
8-10½
10-6½
7-10½
7-4
8-
½
1¼ 6-11
1¼ 8-10½
1¼ 10-6½
1¼ 7-10½
8-
9½
4- 8½
3 8-
0-
1-0
0-8
½
0-8 ½
1¼
0-8 ½
-0
0-6
1¼ 8-10½
1¼ 8-10½
8-10½
0-8
-0
0-81½ 8-2
1½ 8-10½
1¼ 7-7
1-1½
4-1½
1¼ 1-1
4-7½
1 3-
1¼ 2- 4½1 2-
0-2
2½ 2-9
2½ 6-0
1 6-
1 5-
7-
3-11
2½ 4-8½
2½ 1-3½
2½ 10-0
9-6
1 5-
4-
6-
2½ 1-0
2½ 7-
2½ 1- 6½
1¼ 11-0
1¼ 11-3
3-9
8-0
2½ 0-
2½ 2- 6½
1¼ 1-6
3-0
3-
½
6-6
9-10
1¼ 2-10
1¼ 4-4½ 1
4-10
11-4
7-10
2½ 6-
2½ 1-
9-10
6-4
13-10
1 0-
1 1-
1¼ 1-6
8-5
5-3½
2½
-2 ½
1¼ 2-0
1 1-
0-
7-11
5-3½
11-10
2½ 0- 5½
0-8
2½ 1- 6½
2½ 1- 2½
9-10
6-4
13-10 1 1-
2½ 5-
8-10
6-6½
2½ 1-
1 1-
1¼ 0-8 1¼
6-7
4-10
11-4
7-10
2½ 3- 6½
2½ 4- 0½
1¼ 8-10
6-7
7-10
0-
8½
1¼ 0-8
10-10
11-1
10-2
1-
0½
2½ 4- 9½
2½ 2-
2½ 0-
4-3½
11-10
5-7
9-10
11-10
2½ 3-0
2½ 8-8½
2½ 5-3½
1¼ 10 -0
1¼ 9-
½
1¼ 1- 4½
1-
½
1¼ 11-4
7-10½
2½ 10-3
2½ 6-2½
1-
8½
2½ 0-6
2½ 23-1
2½ 24-0
2½ 2- 8½
11-9
10-0
2½ 3- 8½
6-0
11-10
12-1½
9-5
1-
6½
2½ 2- 11 1 1-
0-
9½
1¼ 5-6
1¼ 13-10
13-10
2-4½
3-7
2½ 8-
2½ 0-
1¼ 5-0½
1¼ 12-7
11-10
1¼ 9-0
1¼ 14-10½
11-0
2½ 2-
2-0
1¼ 3-6
11-61¼
9-6
7-3
8-6
2½ 3-
2½ 1- 6½
1¼ 12-9
1¼ 9-10
8-4
1 3-
1-
½
8-3
2-7
2½ 7-
1¼ 3-6
1¼ 11-6
1¼ 9-6
1 2-
8-9
8-2
3-
1½ 1 2-
1 4-
0-4
2½ 4- 1½
1¼ 3-5
1¼ 9-2
1¼ 9-10
1¼ 7-4
1 3-
1 1-
8-2½
1 3-
1-10
1 2-
1-
6½
2½ 7-
½
1¼ 3-6
10-0
1 1-
7-91 1-
2½ 1-
½
2½ 0-
2-0
2½ 3-
1¼ 12-9
1¼ 9-10
1¼ 8-4
10-2½
1-
8½
3-
3½ 2½ 4-
1¼ 4-6
1¼ 9-9½
10-3
7-3
8-0
2½ 2-
1¼ 3-5
1¼ 9-2
8-41
2-0
6-0
1 2- 01 0-
0- 6½
1 1-
2½ 4-
1¼ 8-1
1¼ 10-2
10-2
10-4
3-11½
1 3-
2½ 1-
1¼ 8-1½
1¼ 0-5½
11-10
7-4
8-6
2½ 6-
2½ 3-
2½ 2- 5½
2½ 0-
1¼ 6-6
1¼ 4-7
8-11½
1¼ 12-1½
2-
3½
1 1-
1 5-
1 1-
3-2½
7-6
1 2-
1¼ 5-0
1¼ 12-0
11-7
7-10
11-7
1-
5- 3½
2-
4½
0- 4½
-9
24-0
17-10
1½ 2-
1½ 1-
6-6
1¼ 1-10
1¼ 9-
9-10
1¼ 6-
1 1-
1 0- 4 1 0- 4 1 0-
0-
4½
0-
5-9½
1¼ 0-10
5-9½
0-8½
1 4-
0-8½
9-9½
1 1-
1-
3-6½
1-
4½
2½ 1-9½
1 1-
3-9½
5-10½
1 1-
5-4½
9-10½
9-6½
3 6-
-0
4-
½
3-7½
13-10
14-5½
9-4½
3-9½
9-1½
0-4
11-0½
0-4
11-0½
1¼ 0-9
½
0-6 3
3-10
1¼ 7-8
1¼ 3- 8½
1-
0½
3 3-
-4 ½
1 0-
-4 ½
1 0-
24-0
0-6
1½ 8-2
2-1
24-0
24-04
5-9
4 9-
0-
7½
0-11½
3-3
3-11
1 1-
1 1-
0-
8½ 1 1-
1 1-
1 1-
1 2-
1 1-
1 1-
1-0
1 1-
1-0
1 1-
AUTOMATIC AIR VENT
AUTOMATIC AIR VENT
PIPING TO UNDER
FIRST FLOOR LOBBY
STAIRS, SEE DETAIL 2
ON SHEET F107
ECS RIS-1
INERTING STATION
EXISTING
UNIT HEATER
COORDINATE WITH
EXISTING CONDUIT BANK
1 0-
ECS RIS-1
INERTING STATION
1¼ 1-5
1¼ 0-
½
SHEET LEGEND
NEW BUTTERFLY ISOLATION
VALVE
XXX HYDRAULIC REFERENCE
POINTS / NODES
PIPE HANGER
LATERAL SEISMIC BRACING
FOUR-WAY SEISMIC
BRACING
LONGITUDINAL SEISMIC
BRACING
PIPING OFFSET
FLEXIBLE HOSE SPRINKLER
DROP
RIGID ONE-SIDED
BRANCHLINE RESTRATINT
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
SEISMIC BRACING AND RESTRAINT NOTES:
1. LATERAL BRACING AND LINE RESTRAINTS SHALL NOT BE REQUIRED FOR PIPES SUPPORTED BY RODS
LESS THAN 6" IN ACCORDANCE WITH NFPA 13 SECTION 18.6.5
2. FOUR-WAY BRACE SHALL CONSIST OF 1 LATERAL AND 1 LONGITUDINAL BRACE PER DETAILS IN
COMPLIANCE WITH SECTIONS 18.5.5.8 AND 18.5.6.2.
3. A FOUR-WAY BRACE SHALL BE PROVIDED AT THE TOP OF EACH SPRINKLER RISER AND STANDPIPE PER NFPA 13 SECTION 17.4.5.4, AND AT MAXIMUM 25 FEET SPACING ON INDIVIDUAL RISERS.
4. LATERAL BRACING TO ACT AS LONGITUDINAL BRACING WHEN INSTALLED WITHIN 24" OF THE
CENTERLINE OF PIPING TO BE BRACED LONGITUDINALLY PER NFPA 13 SECTION 18.5.5.8
5. LONGITUDINAL BRACING TO ACT AS LATERAL BRACING WHEN INSTALLED WITHIN 24" OF THE
CENTERLINE OF PIPING TO BE BRACED LATERALLY PER NFPA 13 SECTION 18.5.6.2
BRACE PIPE
LONGITUDINAL SEISMIC BRACE
THREADED BRACE PIPE -
FIG. 910
SWIVEL SWAY
BRACE FITTING
FOR SWAY BRACE
PIPE CLAMP
FIG. 4A
BRACE PIPE
SWAY BRACE ATTACHMENT
``FAST CLAMP''
LATERAL SEISMIC BRACE
BRACE PIPE THREADED ONE END
FIG. 1000
FIG. 910
SWIVEL SWAY
BRACE FITTING
R
SELF DRILLING ANCHOR, ROD AND RING
POST-INSTALLED
ADJUSTABLE RING HANGER
TOLCO
ALL THREAD ROD
CONCRETE ANCHOR
SURGE RESTRAINERS
BRANCH LINE SWAY RESTRAINT
BRANCH LINE
EQ.
CONCRETE DECK
SWIVEL ATTACHMENT
45 DEG.
EXPANSION ANCHOR MIN.3/8"
BRACING AND RESTRAINTS NOT SHOWN
BRACING AND RESTRAINTS NOT SHOWN
TOLCO
TOLCO
E Q
AUTOMATIC AIR VENT DETAIL
ECS PAV-WNS NITROGEN
INERTING VENT
PGSP-1 GAS
SAMPLE PORT
1" GATE VALVE
AUXILIARY DRAIN W/ PLUG
OR DRAIN TO EXTERIOR
BRANCHLINE
PROVIDE VALVES WITH LOCKABLE
OR REMOVABLE HANDLES TO
AAV PRESSURE SENSOR WIRING INSTALLATION DETAIL
PREVENT TAMPERING
JUNCTION BOX
OVER PRESSURE
SENSOR
FLEXIBLE STEEL
CONDUIT
MONITORING
MODULE
ECS PAV-WNS
NITROGEN
INERTING VENT
CEILING WHERE APPLICABLE
INSTALL COMPRESSION
FITTING OVER METAL
PORTION OF PRESSURE
SENSOR
NOTE: NO HANGING FROM SHARED
SUPPORT STRUCTURES I.E DUCTS.
GENERAL NOTES:
1. WHERE POSSIBLE, ALL NEW AND REPLACEMENT PIPING SHALL BE INSTALLED WITH BRANCHLINES HAVING A PITCH TOWARDS DRAIN OF ½" PER 10-FEET, AND MAINS SHALL BE INSTALLED HAVING A PITCH OF ¼" PER 10-FEET SIMILAR TO THE REQUIREMENTS OF PRE-ACTION SYSTEMS IN ACCORDANCE WITH
2022 NFPA 13, SECTION 16.10.3.2.
2. * - RIGID ONE-SIDED BRANCHLINE RESTRAINT, SEE DETAIL ON THIS SHEET.
3. SPRINKLER DROPS SHALL BE EASYFLEX FLEX 72" SPRINKLER HOSE - ULTRA HIGH PERFORMANCE OR
EQUIVALENT.
4. SEE F700 AND F701 FOR INFORMATION PHOTOGRAPHS WHICH IDENTIFY KEY CEILING AND OVERHEAD
CONDITIONS WHERE INSTALLATION MAY BE MORE CHALLENGING.
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
TY
PE
FL
OO
R
TO
TA
L
OR
IF
IC
E
RE
SP
ON
SE
TY
PE
TH
RE
AD
TE
M P.
K-
FA
CT
OR
FI
NI
SH
QT
Y.
SY
M
BO
L
S P
R
IN
K L E
R L
E G
E N
D
R
EL
IA
BL
E R
A
S
SP
QR
W
HI
TE
5.
½
½
5°
R
EL
IA
BL
E R
A
S
SU
QR
BR
AS
S 5.
½
½
0°
R
EL
IA
BL
E G
5-
R A3
C O
N C
EA
LE
D
QR
CU
ST
OM
5.
½
½
5°
X-### A
F603
X-### A
F107
X-### A
F603
X-### A
F603
F-603
ENGINEERING SERVICES
LCC
LCC
TJF
PHX-D-TRACO-F107 X
FLOOR FIRE PUMP
(F101)
TEST HEADER
CONNECTION FROM 10TH
FLOOR SEE F101
6" COMBINATION
SPRINKLER/STANDPIPE
RISER
EXPRESS DRAIN
4" STANDPIPE
RISER
SPRINKLER FCA
1 NEW SECOND FLOOR PIPING PLAN
1/8" = 1'-0"SCALE:
STAIR 3 STAIR 4
SP2
1T
2T
3T
4T
L1
L2
L3
L4
5T
6T
7T
8T
9T
10T
11T
12T
13T
13 14T
15T
16T
17T
18T
L5
L6 L7
3" BUTTERFLY
VALVE
4" BUTTERFLY
VALVE
REMOTE AREA # 2
LIGHT HAZARD
DENSITY: 0.1GPM/SQFT
AREA: 1500 SQFT.
AUTOMATIC AIR VENT
AUTOMATIC AIR VENT
AUXILIARY DRAIN
W/ ACCESS PANEL
1-
½
4 5-
1-11½
1¼ 11-9
1¼ 10-10
1 1-
2-0
6-1
7-5
1 7-
7-
10 1 7-
1 7-
6-7
0-9½ 4
6-4½
2-
5½
9-8
7-0
2-8
7-2
1¼ 8-
9-
½
1 2-
1 1-
8-0
6-0
3 9-
-6 3 6-
3 3-
3 0-
6-
5½
7-
½
7- 5½
1-
3½ 3 0-
1¼ 4-5
1¼ 15-0
9-5
1¼ 5-7
1¼ 13-10
7-9
1 2-
13-10½
1¼ 9-10
1¼ 7-10
8-0
1¼ 1-3
1¼ 15-1½
1¼ 9-8
1¼ 8-8
1¼ 9-10
9-6
1¼ 2-7
1¼ 11-10
1¼ 7-10
5-7
1-
1¼ 5-9
1¼ 9-4½
10-5
1-
3½ 1 0-
6½
1¼ 4-10
1¼ 6-6
1¼ 5-6
8-1
0-
9½
0-
9½
0-
9½
1¼ 4-8
13-10
1¼ 4-0½
1¼ 9-6
1¼ 10-11½
7-10
1¼ 1-9
½
1¼ 7-5½
1¼ 5-7½
1¼ 5-9½
1¼ 10-10
1¼ 5-7
2-8
2-
11-1
1½ 2-
1½ 1- 1 1
6-6
4-0
1¼ 9-
1-5½
9-10
1¼ 6-
1 3-
1 4-
1 2-
2-11½
4-4½
6-0
1¼ 1- 6½
1 0-
1 0-
9-5 4 0-
1¼ 4-8
1¼ 6-11½
8-3
4 9-
1¼ 16-8
4-7
4-
7½
3-
2½
1¼ 10-9
1 4-
1¼ 14-8
6-1½
4 6-
1¼ 8-0
4 0-
1¼ 8-0
1¼ 10-0½
1¼ 3-10
1 6-
1 1- 0 1¼ 2- 7½
4 0-
1¼ 2-9
1¼ 11-10
17-10
-0
1¼ 11-9
1¼ 12-10
15-81 1-
4 2-
1¼ 2-8
1¼ 0-10
1¼ 18-10
13-8
8-0½
1 2-
1 2-
5-
1¼ 4-9
1¼ 11-10
1¼ 5-10
1¼ 7-10
1¼ 13-8
1¼ 3-11½1¼
1-1
1 1-
1 3-
1 1-
1¼ 8-8
1¼ 5-10
1¼ 5-4
1¼ 6-2
11-8
1 2-
1 4-
1 2-
3 2-
3 0-
-6
1¼ 4-9
1¼ 11-10
1¼ 5-10
1¼ 9-10
1¼ 11-8
1¼ 4-1½
1¼ 1-0
3-
0½
1¼ 9-8
1¼ 5-10
1¼ 8-1
11-8 1 1-
1 1-
19-10
1¼ 8-9
3 8-
3 4-
1¼ 4-6
1¼ 10-10
1¼ 1-10
1¼ 3-10
11-8
1 2-
1 4-
3 0-
3 1-
1¼ 11-9
1¼ 8-10
1¼ 11-10
7-6
3-
4-
1¼ 2-8½
21-8
3 8-
3 2-
1¼ 8-9
17-8
1 3-
12-6
2-
4-
3 5-
14-9
3 0-
P
1-6
4-9
1-
6½
1 1-
1 1-
1 1-
1 2-
3 3-
4-0
1 4-
1¼ 4-4
1¼ 5-5
1¼ 0-
1¼ 7-4
0-9
-0
2-3
3-4
6-0
1¼ 2-1
1¼ 4-6
0-10
49-10
41-8
40-6
412-0
42-11 41-6
9-3½
0-9½
DEMO DEMO DEMO DEMO
D
EM
O
D
EM
O D
EM
O
D
EM
O D
EM
O
D
EM
O D
EM
O
D
EM
O
EXISTING
PRE-ACTION
SYSTEM TO BE
DEMOLISHED
ECS RIS-1
INERTING STATION
ECS RIS-1
INERTING STATION
IN NEW WALL
ACCESS PANEL
AUXILIARY DRAIN
WITH ACCESS
PANEL AND SIGN
1-0
1 3-
THIS PIPING TO BE
REMOVED AND REPLACED,
COORDINATE WITH
EXISTING EQUIPMENT IN
CEILING SPACE
1-3
1-7
SHEET LEGEND
NEW BUTTERFLY ISOLATION
VALVE
XXX HYDRAULIC REFERENCE
POINTS / NODES
PIPE HANGER
LATERAL SEISMIC BRACING
FOUR-WAY SEISMIC
BRACING
LONGITUDINAL SEISMIC
BRACING
PIPING OFFSET
FLEXIBLE HOSE SPRINKLER
DROP
RIGID ONE-SIDED
BRANCHLINE RESTRATINT
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
Area
Hazard max. Spacing per Sprinkler (sq. ft.)
Hydraulic Data
Calculation No.
Density (gpm per sq. ft.)
Remote Area (sq. ft.)
Hose Allowance (gpm)
Sprinkler Demand (gpm) Required Flow at Source (gpm)
Required Pressure at Source (psi) Pressure Available at Source (psi)
TRACON
LIGHT
0.10
440.1 540.1
68.54
SEISMIC BRACING AND RESTRAINT NOTES:
1. LATERAL BRACING AND LINE RESTRAINTS SHALL NOT BE REQUIRED FOR PIPES SUPPORTED BY RODS
LESS THAN 6" IN ACCORDANCE WITH NFPA 13 SECTION 18.6.5
2. FOUR-WAY BRACE SHALL CONSIST OF 1 LATERAL AND 1 LONGITUDINAL BRACE PER DETAILS IN
COMPLIANCE WITH SECTIONS 18.5.5.8 AND 18.5.6.2.
3. A FOUR-WAY BRACE SHALL BE PROVIDED AT THE TOP OF EACH SPRINKLER RISER AND STANDPIPE PER NFPA 13 SECTION 17.4.5.4, AND AT MAXIMUM 25 FEET SPACING ON INDIVIDUAL RISERS.
4. LATERAL BRACING TO ACT AS LONGITUDINAL BRACING WHEN INSTALLED WITHIN 24" OF THE
CENTERLINE OF PIPING TO BE BRACED LONGITUDINALLY PER NFPA 13 SECTION 18.5.5.8
5. LONGITUDINAL BRACING TO ACT AS LATERAL BRACING WHEN INSTALLED WITHIN 24" OF THE
CENTERLINE OF PIPING TO BE BRACED LATERALLY PER NFPA 13 SECTION 18.5.6.2
BRACE PIPE
LONGITUDINAL SEISMIC BRACE
THREADED BRACE PIPE -
FIG. 910
SWIVEL SWAY
BRACE FITTING
FOR SWAY BRACE
PIPE CLAMP
FIG. 4A
BRACE PIPE
SWAY BRACE ATTACHMENT
``FAST CLAMP''
LATERAL SEISMIC BRACE
BRACE PIPE THREADED ONE END
FIG. 1000
FIG. 910
SWIVEL SWAY
BRACE FITTING
R
SELF DRILLING ANCHOR, ROD AND RING
POST-INSTALLED
ADJUSTABLE RING HANGER
TOLCO
ALL THREAD ROD
CONCRETE ANCHOR
SURGE RESTRAINERS
BRANCH LINE SWAY RESTRAINT
BRANCH LINE
EQ.
CONCRETE DECK
SWIVEL ATTACHMENT
45 DEG.
EXPANSION ANCHOR MIN.3/8"
BRACING AND RESTRAINTS NOT SHOWN
BRACING AND RESTRAINTS NOT SHOWN
TOLCO
TOLCO
E Q
AUTOMATIC AIR VENT DETAIL
ECS PAV-WNS NITROGEN
INERTING VENT
PGSP-1 GAS
SAMPLE PORT
1" GATE VALVE
AUXILIARY DRAIN W/ PLUG
OR DRAIN TO EXTERIOR
BRANCHLINE
PROVIDE VALVES WITH LOCKABLE
OR REMOVABLE HANDLES TO
AAV PRESSURE SENSOR WIRING INSTALLATION DETAIL
PREVENT TAMPERING
JUNCTION BOX
OVER PRESSURE
SENSOR
FLEXIBLE STEEL
CONDUIT
MONITORING
MODULE
ECS PAV-WNS
NITROGEN
INERTING VENT
CEILING WHERE APPLICABLE
INSTALL COMPRESSION
FITTING OVER METAL
PORTION OF PRESSURE
SENSOR
NOTE: NO HANGING FROM SHARED
SUPPORT STRUCTURES I.E DUCTS.
GENERAL NOTES:
1. WHERE POSSIBLE, ALL NEW AND REPLACEMENT PIPING SHALL BE INSTALLED WITH BRANCHLINES HAVING A PITCH TOWARDS DRAIN OF ½" PER 10-FEET, AND MAINS SHALL BE INSTALLED HAVING A PITCH OF ¼" PER 10-FEET SIMILAR TO THE REQUIREMENTS OF PRE-ACTION SYSTEMS IN ACCORDANCE WITH
2022 NFPA 13, SECTION 16.10.3.2.
2. * - RIGID ONE-SIDED BRANCHLINE RESTRAINT, SEE DETAIL ON THIS SHEET.
3. SPRINKLER DROPS SHALL BE EASYFLEX FLEX 72" SPRINKLER HOSE - ULTRA HIGH PERFORMANCE OR
EQUIVALENT.
4.SEE F700 AND F701 FOR INFORMATION PHOTOGRAPHS WHICH IDENTIFY KEY CEILING AND OVERHEAD
CONDITIONS WHERE INSTALLATION MAY BE MORE CHALLENGING.
3610 Commerce Drive Suite 817
Baltimore, MD 21227-1640 O: 410-737-8677 | F: 410-737-8688 www.jensenhughes.com
TY
PE
FL
OO
R
TO
TA
L
OR
IF
IC
E
RE
SP
ON
SE
TY
PE
TH
RE
AD
TE
M P.
K-
FA
CT
OR
FI
NI
SH
QT
Y.
SY
M
BO
L
S P
R
IN
K L E
R H
E A
D L
E G
E N
D
R
EL
IA
BL
E R
A
S
SP
QR
W
HI
TE
5.
½
½
5°
R
EL
IA
BL
E R
A
S
SU
QR
BR
AS
S 5.
½
½
5°
R
EL
IA
BL
E G
5-
R A3
C O
N C
EA
LE
D
QR
CU
ST
OM
5.
½
½
5°
ENGINEERING SERVICES
LCC
LCC
TJF
PHX-D-TRACO-F108 X
FLOOR FIRE PUMP
(F101)
TEST HEADER
CONNECTION FROM
10TH FLOOR SEE F101
6" COMBINATION
SPRINKLER/STANDPIPE
RISER
EXPRESS DRAIN
4" STANDPIPE
AND GANG DRAIN
WITH INSPECTORS
TEST
1 NEW THIRD FLOOR PIPING PLAN
1/8" = 1'-0"SCALE:
1T
2T
3T
4T
L1
L2
L3
L4
5T
6T
7T
8T
9T
10T
11T
12T
13T
14T
15T
16T
17T
18T
L5
L6
L7
SP3
2½" BUTTERFLY
VALVE 3" BUTTERFLY
VALVE
(2) AUTOMATIC AIR
VENT WITH ECS
RIS-1 INERTING
STATION, MUST BE
ACCESSIBLE BY
LADDER
INLINE
CORROSION
DETECTOR AT
TOP OF RISER
REMOTE AREA # 1
ORDINARY HAZARD II
DENSITY: 0.2 GPM/SQFT
AREA: 1500 SQFT.
AUXILIARY DRAIN
PIPING
AUXILIARY DRAIN
PIPING
3-0
4 1-
1 8-
1-
½
0-7½
4 3-
6-
1½ 0-8
½
3-6½
6-5
1 4-
1¼ 9-
8-
1¼ 12 -4
8-
4-0
1 6-
0-8½
3-3½
1¼ 9- 8½
9-
½
3-3
1¼ 6-
1¼ 7-
3-
3½
2- 1½
8-2½
1-8
2½
-8 ½
2½ 10 -0
2½ 0-
1¼ 3-6
1¼ 12-0
1¼ 6-6
1¼ 8-11
1¼ 6-6
1¼ 7-
7-0½
1¼ 4-7½
8-3½
1 3-
7-4
1¼ 4-2½
1¼ 9-6½
11-10
2½ 2-
1¼ 1-8
1¼ 5-0
1¼ 6-0 1¼
9-0½
1 0-
1¼ 7-6
1¼ 5-10
5-10
2½ 3- 6½
2½ 5- 9½
1¼ 4-2½
1¼ 5-4½
1¼ 7-10½
8-0
1 0-
0-
½ 2½ 0-
1¼ 2-9
1¼ 8-8
1¼ 10-2
1¼ 5-7
1¼ 10-5½
1¼ 8-0
6-0
3-
3½
2½ 12 -7
1¼ 4-2½
1¼ 5-4½
1¼ 7-10½
8-0
1 1-
1¼ 0-10
1¼ 9-10
1¼ 9-2
1¼ 6-1½
1¼ 6-11
1¼ 7-10
7-10
2½ 4-
1¼ 3-1
1¼ 8-10½
1¼ 8-10
8-10
0-
0-
1¼ 8-11
1¼ 12-0
1¼ 12-0
3-0
2½ 8-
1¼ 3-1
1¼ 8-10½
1¼ 8-10
8-10
1 1-
1¼ 3-1
1¼ 8-10½
1¼ 8-10
8-10
1 1- 21 1-
2½ 4-
2½ 8- 0½
2½ 0-
1¼ 8-3
1¼ 8-3
2-
1¼ 11-10
1¼ 11-10
-4 1¼ 2-
½
13-11½
3 8-
3 5-
8-0½
7-5
1-10½
1-1½
4-10½
8-2
5-9
1½ 1-
1 9-
1½ 6-1
1¼ 7-
1¼ 9-
½
1¼ 7-
2-
9½
6-11½
2-
5½
1-
5-10½
4-5½
1¼ 7-
1½ 4-
-4
-4
9-6
2-2½
9-6
2-2½
3-6
5-10½
1¼ 1-
4-
4½
1 3-
0-
2-0
1¼ 10-1
1¼ 8-0
8-0 4
7-6
0-5
2-
102½ 4-
3-7½
1¼ 6-
1¼ 2-
11-6
1 2-
1 7-
4-4½
2-9
7-9
12-0
4-3
5-5½
1¼ 2- 3½
1¼ 11-10½
1¼ 8-9½
1 2-
1-0 3
2-1½
12-0
1¼ 3-6
1¼ 12-0
12-0
12-0
12-0
1¼ 8-11
1¼ 10-0
1¼ 10-0
1¼ 12-0
1¼ 12-0
1¼ 12-0
12-0
1¼ 12-0
1¼ 12-0
1¼ 12-0
4-6
3 0-
1¼ 5-9½
1¼ 10-0
1¼ 8-0
1¼ 0-3
2-2½
TXT1¼
24-0
GXT
1¼ 5-9½
1¼ 10-0
1¼ 8-0
1¼ 0-3
2-2½
TXT1¼
24-0
GXT
1¼ 5-9½
1¼ 10-0
1¼ 8-0
1¼ 0-3
2-2½
TXT1¼
24-0
GXT
1¼ 5-9½
1¼ 10-0
1¼ 8-0
1¼ 0-3
2-2½
TXT1¼
24-0
GXT
1¼ 10-0
1¼ 8-0
1¼ 0-3
8-0
1¼ 0-6
1¼ 0-9
1¼ 9-3½
1¼ 10-0
1¼ 4-8½
1¼ 9-3½
1¼ 10-0
1¼ 4-8½
1¼ 9-3½
1¼ 10-0
1¼ 4-8½
4-3½
TXT
4-3½
TXT
4-3½
TXT 1¼
24-0
GXT
1¼ 24-0
GXT
1¼ 24-0
GXT
1¼ 5-3½
1¼ 6-0
1¼ 12-0
5-3½
TXT
1¼ 24-0
GXT
1¼ 0-8½
1-8
1¼ 12 -1
3 7-
3 1-
-0
3 3-
-0
-0
3 7-
3 4-
3 8-
-0
3 0-
9-
1½ 4-
1¼ 1-4
1 2- 0 1 2-
1¼ 5-8
1¼ 1- ½
1¼ 1- ½
3-9
TXT
EXISTING
PRE-ACTION
SYSTEM TO BE
DEMOLISHED
DEMO DEMO DEMO DEMO
DEMO DEMO DEMO DEMO
D
EM
O
D
EM
O D
EM
O
D
EM
O
1½
0-8 ½
1½ 0-6
1½ 1-6
2-
0½
3 0-
3 0-
2-2
4-9
4 0-
AUXILIARY DRAIN,
CONNECT INTO
GANG DRAIN
AUXILIARY DRAIN
PIPE TO FLOOR
DRAIN
AUXILIARY
DRAIN PIPING
2½ 2-
PIPING AT THE
TOP OF THE
SHAFT TO BE
ABANDONED IN
PLACE
1¼ 3-
1¼ 5-
1¼ 4- 4½
1¼ 9- 8½
7-6
7-6
7-6
SIDEWALL
SPRINKLERS TO
BE 12'-0" AFF
PROVIDE NEW 24" x 24"
ACCESS PANEL
PROVIDE NEW 24" x 24"
ACCESS PANEL
CUT, CAP, AND
LABEL "ABANDONED"
EXPOSED
EXPOSED
SHEET LEGEND
NEW BUTTERFLY ISOLATION
VALVE
XXX HYDRAULIC REFERENCE
POINTS / NODES
PIPE HANGER
LATERAL SEISMIC BRACING
FOUR-WAY SEISMIC
BRACING
LONGITUDINAL SEISMIC
BRACING
PIPING OFFSET
FLEXIBLE HOSE SPRINKLER
DROP
RIGID ONE-SIDED
BRANCHLINE RESTRATINT
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$ A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
12345678
REV
JCNDATE
APPROVED BY
DRAWING NO
ISSUED BY
SUBMITTED BY
REVIEWED BY
DESIGNED
DRAWN
CHECKED
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
Area
Hazard max. Spacing per Sprinkler (sq. ft.)
Hydraulic Data
Calculation No.
Density (gpm per sq. ft.)
Remote Area (sq. ft.)
Hose Allowance (gpm)
Sprinkler Demand (gpm) Required Flow at Source (gpm)
Required Pressure at Source (psi) Pressure Available at Source (psi)
TRACON EQUIPMENT
ORDINARY GRP II
0.20
541.8 791.8 35.5
68.02
SEISMIC BRACING AND RESTRAINT NOTES:
1. LATERAL BRACING AND LINE RESTRAINTS SHALL NOT BE REQUIRED FOR PIPES SUPPORTED BY RODS
LESS THAN 6" IN ACCORDANCE WITH NFPA 13 SECTION 18.6.5
2. FOUR-WAY BRACE SHALL CONSIST OF 1 LATERAL AND 1 LONGITUDINAL BRACE PER DETAILS IN
COMPLIANCE WITH SECTIONS 18.5.5.8 AND 18.5.6.2.
3. A FOUR-WAY BRACE SHALL BE PROVIDED AT THE TOP OF EACH SPRINKLER RISER AND STANDPIPE PER NFPA 13 SECTION 17.4.5.4, AND AT MAXIMUM 25 FEET SPACING ON INDIVIDUAL RISERS.
4. LATERAL BRACING TO ACT AS LONGITUDINAL BRACING WHEN INSTALLED WITHIN 24" OF THE
CENTERLINE OF PIPING TO BE BRACED LONGITUDINALLY PER NFPA 13 SECTION 18.5.5.8
5. LONGITUDINAL BRACING TO ACT AS LATERAL BRACING WHEN INSTALLED WITHIN 24" OF THE
CENTERLINE OF PIPING TO BE BRACED LATERALLY PER NFPA 13 SECTION 18.5.6.2
BRACE PIPE
LONGITUDINAL SEISMIC BRACE
THREADED BRACE PIPE -
FIG. 910
SWIVEL SWAY
BRACE FITTING
FOR SWAY BRACE
PIPE CLAMP
FIG. 4A
BRACE PIPE
SWAY BRACE ATTACHMENT
``FAST CLAMP''
LATERAL SEISMIC BRACE
BRACE PIPE THREADED ONE END
FIG. 1000
FIG. 910
SWIVEL SWAY
BRACE FITTING
R
SELF DRILLING ANCHOR, ROD AND RING
POST-INSTALLED
ADJUSTABLE RING HANGER
TOLCO
ALL THREAD ROD
CONCRETE ANCHOR
SURGE RESTRAINERS
BRANCH LINE SWAY RESTRAINT
BRANCH LINE
EQ.
CONCRETE DECK
SWIVEL ATTACHMENT
45 DEG.
EXPANSION ANCHOR MIN.3/8"
BRACING AND RESTRAINTS NOT SHOWN
BRACING AND RESTRAINTS NOT SHOWN
TOLCO
TOLCO
E Q
AUTOMATIC AIR VENT DETAIL
ECS PAV-WNS NITROGEN
INERTING VENT
PGSP-1 GAS
SAMPLE PORT
1" GATE VALVE
AUXILIARY DRAIN W/ PLUG
OR DRAIN TO EXTERIOR
BRANCHLINE
PROVIDE VALVES WITH LOCKABLE
OR REMOVABLE HANDLES TO
AAV PRESSURE SENSOR WIRING INSTALLATION DETAIL
PREVENT TAMPERING
JUNCTION BOX
OVER PRESSURE
SENSOR
FLEXIBLE STEEL
CONDUIT
MONITORING
MODULE
ECS PAV-WNS
NITROGEN
INERTING VENT
CEILING WHERE…