J-1a Drawings.pdf
PDF 10 MB Posted
- Attached to
- SLN Re-Roof of the ATCT Cab and Walkway
- Solicitation number
- 697DCK-23-R-00327
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions and Answers.pdf | ||
| 697DCK-23-R-00327 0002.pdf | ||
| 697DCK-23-R-00327 0001.pdf | ||
| J-5 Solicitation Questions Form.doc | DOC document | |
| J-1 Specifications.pdf | ||
| J-4 Site Visit Registration Form.doc | DOC document | |
| J-3 Past Performance Questionnaire.pdf | ||
| J-2 Wage Determination.pdf | ||
| 697DCK-23-R-00327.pdf | ||
| J-1b Supplemental Drawings.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
WEATHERTIGHT INSTALLATION.
MANUFACTURER DETAILS AND RECOMMENDATIONS FOR A COMPLETE,
ANYWHERE ON THE CAB ROOF OR CATWALK. FOLLOW ALL ROOFING
DRAINAGE TOWARDS ROOF/FLOOR DRAINS, AND PREVENT PONDING
INSULATION BOARD SHALL BE TAPERED TO ACHIEVE POSITIVE
FLASHING AROUND PARAPET AND WALKWAY WALLS. ALL NEW
AND TERMINATION BARS AROUND CATWALK. RE-INSTALL CAP
INSULATION AT CAB ROOF AND CATWALK. INSTALL NEW SEALANTS
INSTALL NEW EPDM ROOFING MEMBRANE, WALKPADS, AND RIGID
(TYPICAL 4 PLACES)
FLOOR DRAIN ON CATWALK
WEATHERTIGHT INSTALLATION. TYPICAL
MANUFACTURER TO ENSURE
AS RECOMMENDED BY ROOFING
ROOF DRAINS. INSTALL CUT-OFF MASTIC
UNDER CLAMPING RING AT ALL FLOOR/
ENSURE NEW EPDM MEMBRANE EXTENDS
A
/A
A01/A11
/2
ACCESS
PANELS AT CONSOLE
PRECAST CONCRETE
BELOW
EXTERIOR WALKWAY
TO DET. 3, DWG A14. (TYP 4 PLACES)
BOTTOM 2 INCHES ABOVE ROOF DRAIN. SIM.
OVERFLOW SCUPPER THRU PARAPET WALL.
SEE ELECTRICAL
SUPPORT. (TYP 4 PLCS)
OBSTRUCTION LIGHT
SEAL WATERTIGHT.
MANUFACTURER'S INSTRUCTIONS.
INTO SCUPPER OPENING PER
PROTECTED. INSTALL EPDM MEMBRANE
RE-USED IF IN GOOD CONDITION AND
OVERFLOW SCUPPER FLASHING CAN BE
WEATHERTIGHT INSTALLATION. TYPICAL
MANUFACTURER TO ENSURE
AS RECOMMENDED BY ROOFING
ROOF DRAINS. INSTALL CUT-OFF MASTIC
UNDER CLAMPING RING AT ALL FLOOR/
ENSURE NEW EPDM MEMBRANE EXTENDS
INSTALLATION. TYPICAL
SUPPORTS FOR WEATHERTIGHT
TERMINAL SUPPORTS AND ANTENNA
INSTALL NEW SEALANTS AROUND AIR
SECURE ALL CONDUITS/BOXES.
FOR SUPPLEMENTAL AC UNIT.
RE-INSTALL DISCONNECT SWITCH
MOUNTED ON BLOCKS
SUPPLEMENTAL AC UNIT
BY THE ROOFING MANUFACTURER.
ANY NECESSARY REPAIRS AS RECOMMENDED
ROOFING. INSPECT PITCHPOCKET AND MAKE
VIA A PENETRATION/PITCH POCKET THROUGH
REFRIGERANT LINES ENTER CONTROL CAB
IS FULLY OPERATIONAL.
CONDUCTORS. TEST TO ENSURE SYSTEM
CONNECT REFRIGERANT LINES AND POWER
ALL ROOFING WORK IS COMPLETE RE-
RE-INSTALL SUPPLEMENTAL AC UNIT AFTER
STANDARD DETAILS. (TYP)
PER MANUFACTURER'S INSTRUCTIONS AND
ETC FOR ALL PIPES AND ROOF PENETRATIONS
INSTALL NEW BOOTS, CLAMPS, SEALANT,
HATCH SHALL BE FLASHED ACCORDING TO MANUFACTURER'S INSTRUCTIONS TO ENSURE
INSTALL NEW ROOF HATCH LID AND HARDWARE AND RESTORE TO LIKE-NEW CONDITION.
A04/A16
IS FULLY OPERATIONAL.
CONDUCTORS. TEST TO ENSURE SYSTEM
CONNECT REFRIGERANT LINES AND POWER
ALL ROOFING WORK IS COMPLETE RE-
RE-INSTALL SUPPLEMENTAL AC UNIT AFTER
2'-6" X 2'-6" HATCH
SEE DET. 11C ON SHEET A07.
SEE DWG A18. (TYP)
CONTROL CAB CONSOLES
6.0 CU. FT. REFRIGERATOR
SINK W/GARBAGE
DISPOSER.
SCALE: 3/8" = 1'-0"
CAB LEVEL FLOOR PLAN (LEVEL - 8)
A04/A04
RM 801
CAB LEVEL
RM 820
CAB STAIR
EL = 197'-0"
DC
FE
D
H
G
F
E
C
B
8 1234567
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY DATE
DRAWING NO
DESIGNED
REVIEWED BY
IL
P M lo t t e d b y
S R
V
O
APPROVED
8 23467 5
SLOPE
DN 3"
L
N
42" HIGH STEEL
PIPE GUARDRAIL
ROOF
DRAIN
ROOF HATCH
AT CAB LADDER
BULKHEAD PLATE
ENCLOSURE. SEE
ELEC DWGS.
(TYP 3 PLACES)
DN 2"
TAPERED INSULATION
TYPICAL AT CAB
ROOF. SLOPE TO DRAINS
AIR TERMINAL SUPPORT
PIPE (TYP 10 PLACES)
SEE ELEC DWGS.
SINGLE PLY
ROOFING MEMBRANE EXHAUST FAN
SEE MECH
RUBBER
WALKPADS (TYP)
(TYP 10 PLACES)
ANTENNA SUPPORT.
(TYP 4 PLACES)
CAB ROOF ANTENNA MOUNTS
CAB LEVEL ROOF PLAN
A04/A04
INSTALL NEW SEALANTS AROUND
OBSTRUCTION LIGHT SUPPORTS.
RE-CONNECTED.
COR TO HAVE ALL ANTENNAS
COMPLETE. COORDINATE WITH FAA
MEMBRANE AND SEALANTS ARE
ENCLOSURES AFTER NEW ROOFING
RE-INSTALL BULKHEAD PLATE
MANUFACTURER DETAILS AND RECOMMENDATIONS FOR A COMPLETE,
ANYWHERE ON THE CAB ROOF OR CATWALK. FOLLOW ALL ROOFING
DRAINAGE TOWARDS ROOF/FLOOR DRAINS, AND PREVENT PONDING
INSULATION BOARD SHALL BE TAPERED TO ACHIEVE POSITIVE
FLASHING AROUND PARAPET AND WALKWAY WALLS. ALL NEW
AND TERMINATION BARS AROUND CATWALK. RE-INSTALL CAP
INSULATION AT CAB ROOF AND CATWALK. INSTALL NEW SEALANTS
INSTALL NEW EPDM ROOFING MEMBRANE, WALKPADS, AND RIGID
EL = 221'-0" (TOS)
IS
U
08/09/2022
MGR: ENGINEERING - KANSAS CITY
SALINA
SLN-1401822-A001
ATCT
AIRPORT TRAFFIC CONTROL TOWER/BASE BLDG.
AND CAB LEVEL ROOF PLAN
s ln -1
-a
.d w g
TERMINAL
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
T
IO
SALINA MUNICIPAL AIRPORT
DRAWING PRODUCED ON ACE RO MICROSTATION SYSTEM
PROJECT ENGINEER
1301965
KS
2' 0 2' 6'
4'
CAB COLUMN RACEWAY SCHEDULE
COL. NO. USE REMARKS
COLUMN USE DESIGNATION IS
CRITICAL TO THE OPERATION OF
THE ATCT. ANY DEVIATION FROM
THIS DESIGN MUST BE
AUTHORIZED BY THE COR.
1 ANTENNA CABLE
2 ROOF DRAIN
3 POWER
POWER4
5 SPARE
ANTENNA CABLE
ROOF DRAIN
FIRE PROTECTION
SPARE
POWER
REVISION , DATED
THIS PROJECT COPY IS BASED ON
DRAWING
REV. 1, 6/27/2002, AS-BUILT
CE-E-4039-A04
CONTRACTOR SHALL PERFORM ALL WORK SHOWN IN CLOUDS
sln-1401822-a001
2023-03-03T13:07:12-0600
DOUGLAS E WEAVER
2023-03-03T12:19:26-0600
DARREN R BRINKER
PANELS (IMP-1)
INSULATED METAL
PANELS
SEE STRUC. COLOR=PCS-1)
PANELS ON ATCT (TYP.)
SEE DET. 7 ON A15
OVERFLOW SCUPPER (TYP)
SEE DET. 2, SHT. S9C.I.Q.
REVEAL (TYP.)C.I.P.
WALL HYDRANT(TYP)
(SEE MECH.)
FIRE DEPT. CONNECTION
SEE DETAILS ON THIS SHT.
11'-4" WIDE DOUBLE-SWING METAL GATE. FIRE DEPT. CONN.(SEE MECH.)
EQUIP. YARD WALLS. (COLOR = CIP-1)
BLDG. WALLS AND EXT. SURFACE OF
APPLIED TO SURFACE. TYP. ALL BASE
ON BASE BLDG. W/ ACRYLIC STUCCO
CAST-IN-PLACE CONCRETE WALLS
PRECAST CONCRETE PANELS
OVERFLOW SCUPPER (TYP)
METAL FASCIA (MF-1)(COLOR MCF-1)
FLASHING
METAL CAP
WALL (COLOR CIP-1)
8' TALL C.I.P. SCREEN
(TYPICAL 10 PLACES)
TERMINAL SUPPORTS
AIR TERMINAL AND AIR
INTAKE LOUVER
STAIR PRESS.
(COLOR=CIP-1)
C.I.P. SCREEN WALL
(COLOR MCF-1)
METAL CAP FLASHING
BASE BLDG. (TYP.) (COLOR=CIP-1)
CAST-IN-PLACE CONCRETE WALLS ON
METAL FASCIA (MF-1)
SEE STRUC. (COLOR=PCS-1)
(TYP) SEE DET. 7 ON A15
OVERFLOW SCUPPER
SCUPPER (TYP)
OVERFLOW
WALL
CONC SCREEN
4"11'-4" CLR4"
12'-0"
.F
1'-0"
1"3"1"1"
4"
SQUARE PICKETS AT 5" O.C.
FRAME AND 1/2"
ALUM. GATE W /2"X4" ASTRAGAL
PICKETS AT 5" O.C.
FRAME AND 1/2" SQUARE
ALUM. GATE W /2"X4"
BRACING (TYP)
1"x1" ALUM. TUBE
1/2" SOLID PICKET (TYP)
2"X1/4" ASTRAGAL
BARREL BOLT/LOCK
PIPE WELDED TO GATE
3/4" DIA x 2" LONG STL
BOLT W/ 2" LONG HANDLE (TYP)
5/8" DIAM. x 10" LONG STL CANE
CONC SLAB
PIPE SLEEVE SET IN CONC.
2 1/2" LONG x 3/4" DIAM. PVC
WELDED TO GATE AND ANGLE.
(3) ALUM HINGES
FULL LENGTH. BOLT AT 12" O.C.
PROVIDE GALVONIC SEPARATOR
TO STL ANGLE WITH S.S. BOLTS.
4x3x3/8" CONT. ALUM ANGLE. BOLT
SEE STRUC.
STL PLATE
STL ANGLE.
4x3.5x3/8"
SCREEN
CONC
4x3 ALUM ANGLE
PIPE & GATE FRAME
PLATE WELDED TO
1" DIA PIPE W/ 1/4"x4"x4"
BOTTOM SLEEVE
SLEEVE AND SET IN
WELDED TO TOP PIPE
8" LONG ROD
AND JAMB
WELDED TO PIPE
1/4"x4"x4" PLATE
1" DIA PIPE WITH
ALUM. PICKET
ALUM. FRAME
CONC. WALL
/4
Y
IN
CONC. SCREEN WALL
BOLT AT 12" O.C.
PROVIDE GALVONIC
ANGLE WITH S.S. BOLTS.
ANGLE. BOLT TO STL
4x3x3/8" CONT. ALUM
STRIKE PLATE.INCL.
CUT STRIKE AND
LOCKSET
STAINLESS STL
SCREEN WALL
CONC.
(TYP 2 PLACES) FIELD LOCATE
GATE STOP/LATCH
TUBE FRAME
2" X 4" ALUM
AT LOCKSET
ASTRAGAL
SCALE: 3/16" = 1'-0"
NORTH ELEVATION
A01-A08
EAST ELEVATION
EL. 211'-0"
T/STEEL
MAX. EL. 229'-4"
SUPPORTS
TOP OF AIR TERMINAL
EL. 197'-0"
EL. 189'-8 3/4"
CONSOLE ACCESS
LEVEL-7
EL. 180'-0"
JUNCTION LEVEL
LEVEL-6
EL. 164'-0"
LEVEL-5
EL. 148'-0"
LEVEL-4
EL. 132'-0"
LEVEL-3
EL. 116'-0"
LEVEL-2
EL. 100'-0"
FIRST FLOOR
107A
L-9 L-9 L-9 G-2 G-2 G-2 G-2 G-2
G-2
L-7
G-1 CAB GLASS
WEATHERTIGHT FINAL INSTALLATION.
AND SEALANT AS REQUIRED OF ACHIEVE A
COMPLETE. INSTALL FLASHING, TERMINATION BARS,
TEMPORARILY REMOVED AFTER ROOFING WORK IS
CATWALK. RE-INSTALL ITEMS THAT WERE
MEBRANE, AND WALKPADS AT CAB ROOF AND
INSTALL NEW INSULATION, EPDM ROOFING
G-2G-2G-2G-2G-2G-2G-2G-2
L-8
210A
L-6 t t e d b
SCALE: 1/2" = 1'-0"
GATE LATCH & CANE BOLT DETAIL
A8-A8
LATCH DETAIL
GATE JAMB AT HINGE
SCREEN WALL GATE
WALK-THROUGH GATE
HINGE DETAIL
PLAN
ELEVATION
SIM
1/4 2-12
SLN-1401822-A002
GM
EXTERIOR ELEVATIONS
EAST AND NORTH TOWER VIEWS
BUILDING GLASS SCHEDULE
OF ANNEALED GLASS WITH A 1/2" AIRSPACE.
1-1/2" THICK INSULATING GLASS UNITS CONSISTING OF 2 LITES
GRAY.
BUTYRAL (PVB) INNER LAYER. COLOR OF PVB SHALL BE LIGHT
OF 1/8" THICK ANNEALED GLASS WITH A 0.060 POLYVINYL
OUTER LITES ARE LAMINATED GLASS CONSISTING OF 2 PANES
LAMINATED GLASS WITH A 1/2" AIRSPACE. THE INNER AND
1" THICK INSULATING GLASS UNITS CONSISTING OF 2 LITES OF
OUTER LITES ARE TEMPERED.
MONOLITHIC GLASS WITH A 1/2" AIRSPACE. THE INNER AND
EXTERIOR COLOR SCHEDULE
AL-2 ALUM. LOUVER - SW 2128 MARCH WIND
AL-1 ALUM. LOUVER - DARK SLATE
MG-1 METAL GATE - DARK SLATE
IMP-1 INSULATED METAL PANEL - DARK SLATE
COLOR = SW 2128 MARCH WIND
CIP-1 CAST IN PLACE CONCRETE
MCF-1 METAL CAP FLASHING COLOR - DARK SLATE
MF-1 METAL FASCIA SYSTEM - DARK SLATE
PCS-1 PRECAST CONCRETE PANELS
DESCRIPTIONKEY
LOUVER SCHEDULE
KEY DESCRIPTION COLOR
24" X 24" FIXED BLADE, ALUM. AL-2
AL-2
AL-1
20" X 20" FIXED BLADE, ALUM.
36" X 36" FIXED BLADE, ALUM.
72" X 72" FIXED BLADE, ALUM.
16" X 16" FIXED BLADE, ALUM.
48" X 48" FIXED BLADE, ALUM.
32" X 52" FIXED BLADE, ALUM.
36" X 24" FIXED BLADE, ALUM.
ALUM GRILLES @ LEVEL 5A
L-9
G-1
G-3
L-1
L-2
L-3
L-4
L-5
L-10
L-11
4' 0 4' 12'
8'
1' 0 3' 5'
1' 2' 4'
SHOWN IN CLOUDS.
CONTRACTOR SHALL PERFORM ALL WORK
sln-1401822-a002
2023-03-03T13:07:28-0600
DOUGLAS E WEAVER
2023-03-03T12:19:43-0600
DARREN R BRINKER
WEATHERTIGHT.
PER MANUFACTURER'S INSTRUCTIONS AND ENSURE FINAL INSTALLATION IS COMPLETELY
MAY BE REQUIRED TO PERFORM WORK DURUNG LOW AIR TRAFFIC TIMES. INSTALL COMPONENTS
ALL WORK WITH THE FAA COR AND AIR TRAFFIC PERSONNEL PRIOR TO STARTING. CONTRACTOR
TEMPERATURE, ETC.) DURING DEMOLITION AND INSTALLATION WORK. FULLY COORDINATE
OPERATIONAL RISK MANAGEMENT (ORM) CONSIDERATIONS WILL BE REQUIRED (NOISE, CAB
COORDINATE ALL WORK SO THE LID/HARDWARE CAN BE REMOVED/REPLACED IN ONE DAY.
INSTALL NEW CAB ROOF HATCH LID AND HARDWARE. FOR SECURITY AND WEATHER PROTECTION, TIME THAT IS REQUIRED BY THE AIR TRAFFIC CONTROLLERS.
HOWEVER IT WILL NEED TO BE FULLY RETRACTED AT THE END OF EACH WORK SHIFT AND AT ANY
SEPARATE COMPONENTS. NO WORK ON THE FOLDING STAIR IS REQUIRED UNDER THIS CONTRACT;
MANAGEMENT, AND THE CAB OCCUPANTS. THE FOLDING STAIR AND THE ROOF HATCH ARE TWO
CAB. ALL WORK SHALL BE FULLY COORDINATED IN ADVANCE WITH THE FAA COR, AIR TRAFFIC
ALL WORK ON THE CAB ROOF WILL LIKELY BE DISRUPTION TO AIR TRAFFIC CONTROL OPERATIONS IN THE
THE ONLY ACCESS TO THE CAB ROOF IS VIA THE FOLDING STAIR IN THE CONTROL CAB CEILING. ANY AND
PLUMBING CHASE
TO 178'-10'
EXTEND FROM ELEV. 96'-0"
W/ROSE SAFETY CLIMBING RAIL.
CLIMBING LADDER (SEE STRUC)
(SEE STRUC)
PILE CAP
COUNTERWEIGHT
2HR RATING
SPRAY FIRE PROOFING
A02/A02
4 HR RATING
WET BUILDING COMPONENTS OR CONTENTS SHALL BE THOROUGHLY DRIED IMMEDIATELY
BREACHES THAT ALLOW WATER ENTRY COULD DAMAGE AIR TRAFFIC EQUIPMENT OR BUILDING CONTENTS.
BUILDING AT ANY TIME. SEE DEMOLITION DRAWING D004 FOR MORE DETAILS. ANY BUILDING ENVELOPE
REMAIN DRY AT ALL TIMES. NO WIND AND/OR RAIN SHALL BE ALLOWED TO ENTER THE CONTROL TOWER
IS FULLY RESPONSIBLE FOR PROVIDING ANY AND ALL WEATHER PROTECTION TO ENSURE INTERIOR SPACES
FROM CRANE, DISCONNECT OF RADIO ANTENNA, DISCONNECTION OF GROUNDING WIRES, ETC.) CONTRACTOR
AIR TRAFFIC CONTROL AND/OR AIR TRAFFIC OPERATIONS (NOISE, FUMES FROM VOC'S LINE-OF-SITE IMPACTS
NECESSARY BEFORE PENETRATIONS. COMPLY WITH FAA ORM REQUIREMENTS FOR WORK THAT MAY IMPACT
ITEMS AS NECESSARY TO ENSURE COMPLETE REMOVALS AND RE-INSTALLATIONS. INSTALL NEW SEALANTS AS
SEALANTS, ETC AT THE ATCT CAB ROOF AND CATWALK LEVELS. TEMPORARILY REMOVE SURFACE-MOUNTED
REMOVE EPDM ROOFING MEMBRANE WALKPADS. INSULATION, FLASHING, TERMINATION BARS, PIPE BOOTS, QUIET AREA
EL=229'-4"
TOP OF AIR TERMINAL SUPPORT
EL=211'-0"
EL=197'-0"
EL=189'-8 3/4"
LEVEL 7
EL=180'-0"
LEVEL 6
EL=172'-0"
LEVEL 5A
EL=164'-0"
LEVEL 5
EL=156'-0"
LEVEL 4A
EL=148'-0"
LEVEL 4
EL=140'-0"
LEVEL 3A
EL=132'-0"
LEVEL 3
EL=124'-0"
LEVEL 2A
EL=116'-0"
LEVEL 2
EL=108'-0"
LEVEL 1A
EL=100'-0"
FIIRST FLOOR
ELEVATOR SHAFT
ELEVATOR CAR
PLUMBING
MECHANICAL
EQUIPMENT
618A
ELEVATOR
EQUIPMENT107
SCALE: 1/4" = 1'-0"
BUILDING SECTION
A01/A10
A10/A12 t t e d b
SLN-1401822-A003
TOWER SECTION
CONTRACTOR TO PERFORM ALL WORK SHOWN IN CLOUDS
4' 0 4' 8'
1 06-27-2002
CE-E-4039-A10
sln-1401822-a003
2023-03-03T13:07:46-0600
DOUGLAS E WEAVER
2023-03-03T12:20:03-0600
DARREN R BRINKER
TRAY
CABLE
GYPSUM BOARD CEILING
BEYOND (TYP)
CABLE TRAY
FROM ELEV. 96'-0" TO 186'-0".
WITH ROSE SAFETY CLIMBING RAIL. EXTEND
STEEL CLIMBING LADDER (SEE STRUCTURAL)
CABLE TRAY (BEYOND)
(TYP)
METAL GRATING
CEILING
GYPSUM BOARD
IF
IG
W
IT
/1
VARIES
AND RIGID INSULATION
1/2" GYPSUM BOARD ON 3" Z FURRING
6"
CAP
ON A08
LOUVER L-10, SEE SCHEDULE
ELEVATOR RELIEF DAMPER.
WALKWAY PADS OVER ERDM
INSULATION BOARD
90 mil EPDM MEMBRANE OVER
SURFACE MOUNTED COUNTER FLASHING
90 mil EPDM MEMBRANE
SCUPPER
PANEL
CONCRETE
PRECAST
(SLOPE TO DRAINS)
4" (MAX) RIGID INSULATION
DUCT WORK, SEE MECHANICAL DWGS.
REMOVABLE STEEL GRATING
STEEL TUBE COLUMNS AT CAB
PARTITION TYPE - "C"
2 HOUR FIRE RATED GYPSUM
DRAWINGS
ELECTRICAL
CABLE TRAY SEE
SEE MECHNICAL DWGS.
TO CAB GRILLES
MECHNICAL SUPPLY DUCTS
CAB CONSOLES
SLAB AT CAB
METAL DECK AND CONCRETE
SPRAYED FIRE PROOFING 2 HOUR RATING
TYPE - "C"
GYPSUM PARTITION
2 HOUR FIRE RATED
PRECAST CONCRETE PANEL.
WALKWAY, AND UP THE FACE OF THE INTERIOR
CONCRETE PANEL ON OUTSIDE PERIMETER OF
EXTEND EPDM MEMBRANE UP AND OVER PRECAST
THE TOP OF WALL TYPICAL.
PARAPET AFTER EPDM MEMBRANE IS EXTENDED OVER
RE-INSTALL ALUMINUM CAP FLASHING AROUND WALKWAY
LEVEL-1
ROOM
ELECTRONICS EQUIPMENT
LOBBY
2A11
4A11
PARTIAL TOWER SECTION
A01/A12 t t e d b
TOP OF STEEL
EL = 211'-0"
A12 A15
DETAILS
DETAIL 3 ON DRAWING A15 FOR MORE
BOXES, ACCESS PLATES, ETC. SEE
CONDUITS FOR SURFACE MOUNTED
MOUNTS, AIR TERMINAL SUPPORTS,
PENETRATIONS INCLUDING ANTENNA
INSTALL NEW SEALANT AT ALL FLASHING
THE LIVES OF THE FLYING PUBLIC.
IN DAMAGE TO ELECTRONICS EQUIPMENT AND ENDANGER
CONTROL CAB OR EQUIPMENT ROOMS COULD RESULT
ALL AREAS ARE WEATHERTIGHT. RAIN ENTRY INTO THE
REMAIN DRY UNTILL FINAL ROOFING IS INSTALLED AND
ENSURE THE CONTROL CAB AND ALL INTERIOR SPACES
TEMORARY WEATHER PROTECTION AS NECESSARY TO
CONTRACTOR IS REPONSIBLE FOR PROVIDING ANY AND ALL
SCALE: 3/4" = 1'-0"
UNDER SILL
EXTEND EPDM
METAL FLASHING
1/2" GYPSUM BOARD
CAULK
H. MET. DOOR AND FRAME
ALUMINUM THRESHOLD
3" RIGID INSULATION BOARD
1/2" GYPSUM BOARD ON Z-FURRING
CONCRETE CURB
SEALANT
DRIP FLASHING
PRECAST CONCRETE PANEL
3 5/8"
TITLE
A03/A12
REMOVED/REPLACED
MEMBRANE CAN BE
DOOR TO ENSURE EPDM
FLASHING AT CATWALK
LOOSEN SILL AND METAL
SLN-1401822-A004
TOWER SECTIONS
2 07/13/2002
CE-E-4039-A12
1' 0 1' 3'
2'
DRAINS AND INSTALL CUT-OFF MASTIC PER MANUFACTURER'S RECOMMENDATIONS.
REMOVED IN GOOD CONDITION AND PROTECTED. TERMINATE EPDM MEMBRANE UNDER ALL CLAMP/SPRINGS AT ROOF
ALUMINUM CAP FLASHING, ALUMINUM SCUPPER FLASHING, AND COUNTER FLASHING CAN BE RE-USED IF IT IS
CATWALK LEVEL. EPDM MEMBRANE AT SCUPPERS (TOTAL OF 4) SHALL BE COMPLETELY REMOVED AND REPLACED.
ALL NEW INSULATION TO ROOF DRAINS TO ENSURE POSITIVE DRAINAGE AND NO PONDING ANYWHERE ON THE
INSULATION AND EPDM MEMBRANE ARE INSTALLED. ROOF DRAINS SHALL BE PROTECTED AND CAN BE RE-USED. SLOPE
FLASHING FOR WEATHERTIGHT INSTALLATION. RE-INSTALL CAP FLASHING AND OTHER PROTECTED ITEMS AFTER NEW
CATWALK LEVEL EXTENDS AROUND ENTIRE PERIMETER OF CONTROL CAB. INSTALL NEW TERMINATION BAR/COUNTER sln-1401822-a004
2023-03-03T13:08:01-0600
DOUGLAS E WEAVER
2023-03-03T12:20:34-0600
DARREN R BRINKER
SEALANT (TYP)
THRU WALL.
ALUM. FLASHING
ANCHOR
SCHEDULED
ALUM. LOUVER AS
PRECAST CONC.
1/2" GYP. BD.
3" RIGID INSUL.
LAMINATE.
COVERED W/ PLASTIC
3/4 INCH SILL
ANCHOR (TYP.)
LOUVER CLIP W/ EXP.
PRECAST CONC. PANELS
(DARK SLATE)
W/KYNAR FINISH
ALUM. LOUVER
INSUL. (TYP.)
STUFF W/R-13 BATT
EPDM
RUBBER SEAM SEAL (2 LAYERS)
AND CATWALK TYPICAL
ALL SCUPPERS AT CAB ROOF
MEMBRANE FLASHING AROUND
REPLACE SERALANTS AND
TYPICAL ALL LOCATIONS
PROTECTED FROM DAMAGE.
CORROSION, AND
CONDITION WITH NO
RE-USED IF IT IS IN GOOD
METAL INSERT CAN BE
RUBBER SEAM SEAL (2 LAYERS)
METAL INSERT
t t e d b
A15-A15
INSUL MET.
ROD AND SEALANT
MET. FLASHING BACKER
FRAME SYSTEM
ALUM. WINDOW
CAB GLASS
AND GYP. BD
MET. STUDS
WINDOW SHADE
PAINT BLACK
2x10 NAILER
2X4 NAILER
FIXTURE (SEE ELEC)
TRACK AND LIGHT
1/2" GYP BD.
GYP, (TYP)
MET. STUDS AND
TILE (FULL PANEL)
ACOUSTICAL CEILING
SHADE PER
ADDITIONAL WINDOW
05-05
EXTERIOR INTERIOR
TS6 x 3
COATED COLOR: FLAT BLACK
COVERS OVER STEEL COLUMN.
0.032 ALUM. COL.
COLUMN. COLOR: FLAT BLACK
0.032 ALUM. COVERS OVER STEEL
LINEAR DIFFUSER
CONTINUOUS P.T. NAILER
SEE MECH FOR DUCT
BACK OF CAB CONSOLES
CAB COLUMN (BEYOND)
ALUMINUM WINDOW
AND SEALANT
BACKER ROD
CONSOLE TURRET
BENT PLATE
3-1/2"X3-1/2" X 1/4"
METAL PANELS
2" INSULATED
SEE STRUCT.
STEEL TUBE.
UN-USEABLE. TYPICAL 10 LOCATIONS.
TOO THICK SO THAT THREADS ARE
APPROVED EQUAL. DO NOT APPLY PAINT
PRIME/PAINT WITH RUSTOLEUM, OR
SUPPORTS AND NUTS TO REMOVE RUST.
WIRE-BRUSH THREADED ANTENNA
PROVIDE 2 3/4" DIAM. OPENING IN TUBE.
WELED ALL AROUND AT BASE TO
2 1/2" I.D. THREADED SCH. 40 PIPE
SEPARTION (TYP).
(FINISH IMP-1). W/ GALVONIC
.090" ALUM. CAP FLASHING.
(FINISH IMP-1)
.090" ALUM. FLASHING
ANTENNA MOUNT OPENING.
COVER PLATE AT EACH
8"x8"x1/8" STAINLESS STEEL
MEMBRANE ROOF.
FULLY-ADHERE EPDM
BACKER ROD & SEALANT
DRAINS.
TAPERED TO ROOF
2-INCH RIGID INSUL. BD.
REPLACEMENT. TYPICAL.
A CONTRACT CHANGE CAN BE NEGOTIATED FOR
FAA COR IMMEDIATELY IF DAMAGE IS FOUND SO
CAB PARAPET IF IN GOOD CONDITION. NOTIFY
RE-USE EXTERIOR GRADE PLYWOOD AROUND
AND CATWALK. TYPICAL
TYPICAL AROUND ENTIRE CAB
REPLACE IF COMPROMISED.
IF STILL IN GOOD CONDITION.
ALWAYS SHOWN) AT CORNERS
RE-USE WOOD CANTS (NOT
STRUCTURE
CAB MULLION SEE
INSUL. METAL PANEL
W/ BACKER ROD &
GALVONIC SEPARATOR
TO MATCH IMP-1
FLASHING FINISH
.090" ALUMINUM
GROMMET PER NFPA-70
COLUMN THRU TS WITH
3" X 10" OPNG AT EACH
.090" ALUM. CAP
TS, SEE STRUC.
WASHERS AT 2'-0" O.C. (TYP)
SCREWS W/ NEOPRENE
1/4" SELF-TAPPING S.S.
MOUNT (TYP)
CAP ON ANTENNA
BOTH SIDES.
ND WASHER,
THREADED NUT
BUSHING
OBSTR. LIGHT MOUNTS SIMILAR.
SPECIFIED. (SEE ELEC FOR REQ)
AIR TERMINAL SUPPORT WHERE
CONT. ANGLE (SEE STRUC)
MIL POLY VAPOR BARRIER (TYP)
MET. DECK AND CONC.W/ 6
INSTALL NEW. TYPICAL
GRADE PLYWOOD
2 LAYERS 3/4" EXTERIOR
42-INCH PARAPET HEIGHT AROUND ENTIRE CAB ROOF.
APPROVED EQUAL. MAINTAIN A MINIMUM
INSULATION BOARD WITH DENSDEC, OR
COMPLETE DRAINAGE. COVER RIGID
INSULATION TO ROOF DRAINS TO ENSURE
MANUFACTURER'S INSTRUCTIONS. TAPER
REPLACE ALL RIGID INSULATION. SECURE PER
INSUL. BD.
3-INCH RIGID
IN ITS ENTIRETY
REPLACE EPDM ROOF
RE-TIGHTENING. TYPICAL.
FASTENER HEADS BEFORE
BEHIND IT. APPLY SEALANT UNDER
MEMBRANE IS TUCKED/INSTALLED
PIECE OF FLASHING AFTER EPDM
SECURE FASTENERS FOR BOTTOM
COVER PLATES. TYP OF 10
AROUND ANTENNA MOUNT
INSTALL NEW SEALANT
TYPICAL ENTIRE CAB.
INSTALL NEW SEALANT FOR
IN TOP OF PARAPET.
VERTICAL PENETRATION EXISTS
OTHER LOCATION WHERE A
ANTENNA MOUNT (10) AND ANY
INSTALL NEW SEALANT AT EACH
FOR ROUTING DRAIN LINE
W/ 3-INCH OULET. SEE MECH
FLOOR DRAIN (ZURN Z100)
VARIES)
BOARD (THICKNESS
RIGID INSULATION
FLOOR
INSTRUCTIONS TO ENSURE A LONG-TERM
MEMBRANE AND DRAIN MANUFACTURER'S
SEALANT / CUTOFF MASTIC AS REQUIRED PER
FLOOR DRAIN COLLAR AND PROVIDE / INSTALL
MEMBRANE OF A SUFFICIENT LENGTH UNDER THE
PROTECT FROM DAMAGE. EXTEND EPDM
FLOOR DRAINS AT CATWALK CAN BE RE-USED.
MEMBRANE
AND EPDM
REPLACE RIGID
UNDER COLLAR
DRAIN AND BOLTED
EXTENDED INTO FLOOR
EPDM MEMBRANE
SEALANT CONT.
BACKER ROD & SEALANT
3" RIGID INSUL. ON "Z" FURRING
1/2" GYP. BOARD
AS ONE PIECE
SHOP FABRICATE
1/4" BENT PLATE
CTSK BOLTS
PLATE FOR 1/4"
DRILL & TAP
(SEE MECH)
SEE STRUCT. DWGSSTS.
STEEL TUBE. STR.
FACED WITH ALUMINUM
ON STEEL, TYP WHERE
BITUMINOUS COATING
PLATE
COATED STEEL
1/4" EPOXY
SLN-1401822-A005
EXTERIOR DETAILS
SALINA MUNICIPAL AIRPORT - SALINA, KANSAS
SCALE: 3" = 1'-0"
HEAD @ CAB WINDOW
A12-A18
SCALE: 1-1/2" = 1'-0"
SPANDREL GLASS @ 6TH LEVEL
A03-A15
WINDOW @ 6TH LEVEL
TYPICAL LOUVER INSTALLATION
LOUVER @ LEVEL 5A
FLOOR DRAIN @ WALKWAY
CAB ROOF PARAPET
SILL @ CAB WINDOW
PANEL @ CAB COLUMN
CAB COLUMN WINDOW
PRECAST JOINT DETAIL
A15
SHOWN IN CLOUDS.
CONTRACTOR SHALL PERFORM ALL WORK
SUPPER @ WALKWAY
A10-A15
1' 0 1'
SCALE: 1 1/2" = 1'-0"
3"6"9"
3" 0 6" 9"
3" sln-1401822-a005
2023-03-03T13:08:21-0600
DOUGLAS E WEAVER
2023-03-03T12:20:53-0600
DARREN R BRINKER
348.67'
92.00' 31.50' 104.00' 80.00' 41.17'
SCHILLING SUBDIVISION NO. 5
NW CORNER OF LOT 1, BLOCK 5
.7
POINT OF BEGINNING
EXISTING LIGHT POLE
.0
5' WIDE SIDEWALK
DROP INLET
STORM SEWER
12' GATE (SEE SHT C02)
FENCE
CONCRETE FILL
(SEE SHT C02)
5' GATE
FLAGPOLE (SEE SHT C02)
6' WIDE SIDEWALK
(EL. 96.46')
(SEE SHT. C5)
LOADING DOCK LIFT
(SEE SHT. C4)
(EL. 97.55)
EQUIPMENT YARD
(SEE SHT. A8)
3'-10" GATE
LEASE BOUNDARY
FENCE
(SEE SHT. C02)
HANDICAP SIGN
(EL. 97.85')
(EL.97.40')
12' GATE (SEE SHT. A8)
50' RAD.
(EL.97.27')
BASE BUILDING
(SEE SHT. C02)
5' GATE
12"
50' RAD.
YARD SIGN (SEE SHT. C02)
24'245.00'
CONCRETE ENTRANCE ROAD
40' RAD.
15' RAD.
79.67'
.8
.0
.9
THE GRASSY AREA ON THE EAST SIDE OF THE FACILITY SHALL NOT BE USED FOR CRANE LOCATION.
CONTROLLERS AND COMPLY WITH OPERATIONAL RISK MANAGEMENT (ORM) PROCEDURES/REQUIREMENTS.
LOCATION FOR A TEMPORY CRANE. CRANE/BOOM POSITION SHALL BE COORDINATED WITH THE AIR TRAFFIC
CONTRACTOR SHALL COORDINATE WITH FAA AND SALINA AIRPORT AUTHORITY TO DETERMINE A SUITABLE
BUILDING
CONCRETE PARKING LOT
(SEE SHT. C5)
DELIVERY LANE
PARKING LOT
KNEUBUHL COURT
SCALE: 1" = 10'-0"
SALINA ATCT - SITE PLAN
NOTE: ELEVATION 100.00' = 1258.99' ACTUAL
FINISH FLOOR = 97.85' = 1256.84' ACTUAL
CLCL
ROAD/PIT
/C
2.5"
GRASS
ASPHALT APRON
t t e d b
END POST
AIRPORT
Administration
Federal Aviation
CONTROL
of Transportation
U.S. Department
FINISH GRADE
TRAFFIC
TOWER
GRADE
TENSILE RAIL STEEL, NON-PERFORATED.
2. POSTS SHALL BE 8' LONG (MINIMUM) HOT-ROLLED HIGH
FINISH WITH SLATE GRAY ENAMEL.
1. SIGNS SHALL BE 12 X 18 INCH
SHEETING ON .080 ALUMINUM.
NOTE:
NOTE: MOUNT SIGNS SECURELY TO POST
(NOTE 2)
END POST
(NOTE 7)
CHAIN LINK FABRIC
BARBED WIRE (NOTE 9)
3 STRANDS OF POINT
(SEE NOTE 12)
WELDED TO POST GROUND ROD
FABRIC AND EXOTHERMICALLY
NO. 6 BC WOVEN THRU FENCE
(NOTE 6)
TENSION WIRE
GROUND ROD
3/4" x10'
NOT TO SCALE
TYPICAL FENCE SECTION
OR GATE POST
END, CORNER,
TENSION BAND
TENSION BAR
DETAIL
TENSION BAND AND TENSION BAR
GATE POSTPIVOT
GATE FRAME
OF HALF THE POST DIA.
GATE POST BY A MINIMUM
FORK LATCH FITS AROUND
WITH A PADLOCK
FRAME AND LOCKABLE
SECURELY TO THE GATE
FORK LATCH FASTENED
SWING GATE FORK LOCK
(NOTE 10)
BRACE AND LINE POST CAP
AND TOP RAIL SUPPORT
FENCE DETAILS
TOP RAIL END OR HORIZONTAL BRACE SUPPORT
HINGE FOR 4" O.D. AND LARGER TUBULAR POSTS
TOP RAIL COUPLING
END, BRACE, CORNER, OR GATE POST
TOP
RAIL
END
SUPPORT
OR
HORIZONTAL
BRACE
INSIDE
DIA,
OF
MATCHES
OUTSIDE
DIA.
RAIL
DESIGNATED
OF A TRUSS ROD WHERE
ACCOMODATING ATTACHMENT
TENSION BAND IS OF THE TYPE
GATE FRAME
GATE POST
HINGE SIDE
GROUND CLAMP
HEAVY DUTY BRONZE
FREELY EACH DIRECTION
SUFFICENT LENGTH TO SWING
1/2" WIDE COPPER BRAID OF
GATE GROUND STRAP CONNECTION
PROVIDE EXPANSION COUPLING AT EVERY
FIFTH LOCATION
PEDESTRAIN GATE
NOTE: OTHER PEDESTRIAN GATE OPPOSITE HAND
4/0
NO.
POSTS
GATE
CONNECTING
TO EES
NO. 4/0 CONNECTING
PIPE CAP (TYP)
3 STRANDS BARBED WIRE
HINGE
4" O.D.
TUBULAR POST
BARS WITH BANDS
1/4 x 3/4 STRETCHER
COPPER GROUND STRAP
1" x 1/8" FLEXIBLE TINNED
HINGE
TYP. OF 2
EXOTHERMIC WELD
TIE WIRES
@ 12" CTRS
2" O.D.
FRAME (TYP)
YARD SIGN DETAILS
SECTION A-A
C2/C2
3 1/2"3 1/2"
CHAIN LINK FABRIC
9 GA., 2" MESH
VINYL GRAPHIC
COLOR METAL-2 W/ WHITE
1/4" METAL FASCIA PANEL
METAL-2
COLOR TO MATCH
ALUMINUM LETTERS-
1/4" THICK 4" HIGH CUT
FOOTINGC.I.P.
1-1/2" CVR
NO. 5 @ 12" O.C. EA. WAY EA. FACE
PANEL (SEE 24/A18) CENTERED ON PL 1/2"P.C.
NO. 5 24" @ 12" O.C.
3" C.I.P. CONCRETE WATERPROOFING
L 4x3x1/4 LLV CONT. @ P.C.
PL 1/2"x1'-2" x CONT. CENTERED ON FTG.
NO. 4 @ 6" O.C. (A-706 BARS)
18" DIA. CONCRETE RING
FINISHED GRADE
STEEL POST
ON SLATE GRAY BACKGROUND
BLUE 6" SQUARE AND WHITE LETTERS
WHITE ACCESSIBLE INSIGNIA ON
12" x 18" SIGN
BLUE BACKGROUND
WHITE LETTERS ON
12" x 4" SIGN
VAN
ACCESSIBLE
HANDICAP SIGNAGE DETAIL
(PROVIDE 2'-9" CAST ALUMINUM CLEATS).
REVOLVING NON-FOULING TYPE .
DOUBLE SHEAVE TRUCK, CAST ALUMINUM,
ALUMINUM BALL, FLUSH SEAM
6" DIA. GOLD ANODIZED SPUN
80-120 GRIT SATIN BRUSH FINISH
TAPERED ALUMINUM FLAGPOLE
WATERPROOF COMPOUND 2" DEEP
1/2" CHAMFER
CAST-IN PLACE CONCRETE
FLAGPOLE DETAIL
4 HARDWOOD WEDGES
FILL SPACE W/DRY PACKED SAND
CORRUGATED STEEL TUBE
8" DIA. 16 GUAGE GALVANIZED
4 WELDED STEEL WEDGES
1/2"
1/4" 1/4"
YARD SIGN REINFORCEMENT
(4)-NO. 5 CONT. @ FOOTING
FOOTING 3-0"x8'-2"
OVER POST
CAP FITS SNUGLY
RESERVED
PARKING
10"X10"X12" WELDED STEEL PLATE
6"X6"X1/2" PLATE SUPPORT WELDED
GROUND SPIKE WELDED PLATES
3/4" DIA. STEEL LIGHTNING
SLN-1401822-C001
SITE PLAN
-c
LEGAL DESCRIPTION:
COUNTY, KANSAS, AND BEING MORE PARTICULARY DESCRIBED AS FOLLOWS:
MERIDIAN, BEING A PART OF LOTS 1, 2, AND 3 OF BLOCK 5, OF SCHILLING SUBDIVISION NUMBER 5 OF THE CITY OF SALINA, SALINE A TRACT OF LAND LYING IN THE SOUTH HALF (S 1/2) OF SECTION 34, TOWNSHIP 14 SOUTH, RANGE 3 WEST OF THE 6th PRINCIPAL
THE ABOVE DESCRIBED TRACT CONTAINING 62337.49 SQUARE FEET, OR 1.43 ACRES, MORE OR LESS.
OF BEGINNING.
1. SEE SHEET C4 FOR SITE UTILITY PLAN.
SEE SHEETS M2 AND CE1, SHEETS 1 AND 2, FOR LOCATIONS OF MECHANICAL
AND ELECTRICAL EQUIPMENT.
SEE SHEET S2 FOR EQUIPMENT PADS AND ATCT/BASE BUILDING DIMENSIONS.
SEE SHEET C5 FOR PARKING LOT/PAVEMENT DETAILS. SEE DETAILS 7
AND 9 ON C5 FOR PAVEMENT MARKINGS, DETAIL 8 FOR HANDICAP SIGN.
10' 0 10' 20'
SCALE: 1" = 10'
2 06-20-2005
CE-E-4039-C02
GENERAL NOTES:
2. NOT USED.
3. THE CURB AT THE END OF THE ENTRANCE ROAD WAS REPLACED WITH A DRIVEWAY SECTION.
4. AREAS LABELED WERE SEEDED PER SPCIFICATIONS.GRASS
5. NOT USED.
6. THE FENCE INSTALLED PER THE DETAILS ON THIS SHEET.
7. THE BASE BUILDING ALIGNS N-S PARALLEL TO THE LEASE BOUNDARY.
BY THE HOT DIP PROCESS PRIOR TO ASSEMBLY.
FENCE AND GATE LAYOUT ARE AS SHOWN. ALL STEEL FENCING MATERIAL IS GALVANIZED
1. GALVANIZED FENCE WITH GATES, INCLUDING ALL FITTINGS, FASTENERS, AND ACCESSORIES, FENCE NOTES:
18" DIA. X 4" MIN. DEPTH CONCRETE FOUNDATION.
2. GATE POSTS, CORNER POSTS, AND END POSTS ARE 4" ALLIED SS-40 STEEL POSTS AND SET IN
CONCRETE FOUNDATION. ALL INTERMEDIATE POSTS ARE 6" O.C. MAXIMUM.
3. BRACE AND LINE POSTS ARE 2.5" ALLIED SS-40 STEEL POST AND SET IN 12" DIA. X 3'-4" MIN. DEPTH
4. HORIZONTAL BRACES AND TOP RAILS ARE 1-5/8" ALLIED SS-40 STEEL.
TENSION BANDS FOR SECURING TENSION BARS TO POSTS HAVE A MAXIMUM SPACING OF 12" O.C.
1/4" x 3/4". TENSION BARS ARE USED ON ALL CORNER POSTS, GATE POSTS, AND GATE FRAMES.
5. TENSION BARS EXTEND THE FULL HEIGHT OF THE FABRIC WITH A MINIMUM CROSS SECTION OF
TENSION BANDS FOR SECURING TENSION BARS TO POSTS HAVE A MAXIMUM SPACING OF 12" O.C.
1/4" x 3/4". TENSION BARS ARE USED ON ALL CORNER POSTS, GATE POSTS, AND GATE FRAMES.
5. TENSION BARS EXTEND THE FULL HEIGHT OF THE FABRIC WITH A MINIMUM CROSS SECTION OF
6. TENSION WIRE IS 9 GA. GALVANIZED WIRE WITH 12 GA. TIE WIRES SPACED 12" O.C.
POSTS, D] LINE POSTS, AND E] HORIZONTAL BRACES.
FABRIC TO: A] TOP AND BOTTOM RAILS OF ALL GATES, B] TOP RAIL ON ALL FENCE, C] BRACE TIE WIRES ARE 9 GA. GALV. WIRE AND SPACED 14" O.C. AND USED TO SECURE THE CHAIN LINK
7. CHAIN LINK IS 84" HIGH, 2" WIRE MESH, 9 GA. GALV. BARBED AND TWISTED TOP AND BOTTOM.
GATE POST.
AND ARE EQUIPPED WITH A TURNBUCKLE. TRUSS RODS ARE INSTALLED AT EACH POST AND
8. DIAGONAL TRUSS RODS ARE 3/8" DIA. GALV. STEEL RODS. TRUSS RODS HAVE THREADED ENDS
OF THE TOP RAIL AND ARE 12 GA. GALV. STEEL.
PULL AT THE OUTERMOST END OF THE ARM. BARBED WIRE ARMS HAVE A HOLE FOR PASSAGE
9. BARBED WIRE EXTENSION ARMS ARE CAPABLE OF WITHSTANDING 250 LBS. OF DOWNWARD
SPACED AT 4" O.C..
10. BARBED WIRE IS 2 STRAND 12 GA. GALV. WIRE WITH 12 GA. GALV. 4-POINT ROUND BARBS
EXOTHERMAL WELD, 6" ABOVE GRADE.
11. A NO. 2/0 BARE COPPER CONDUCTOR IS ATTACHED TO THE POST EACH SIDE OF GATE USING AN
CLAMP TO EACH POST THAT IS CONNECTED TO A GROUND ROD.
HORIZONTALLY THRU THE FENCE FABRIC AT 62" ABOVE GRADE AND CONNECTED BY PIPE GROUND AND EXOTHERMICALLY WELDED TO THE ROD AT 12" MIN. BELOW GRADE. A NO. 6 B.C. SHALL BE WOVEN A NO. 6 B.C. SHALL BE WOVEN VERTICALLY THRU THE FENCE FABRIC AT EACH FENCE GROUND ROD SHALL BE BONDED BY EXOTHERMIC WELD TO THE FENCE POST WITH NO. 4/0 BARE COPPER WIRE.
12. 3/4" x10' COPPERCLAD GROUND RODS SHALL BE INSTALLED AT EVERY FOURTH FENCE POST AND
THE PEDESTRIAN GATE DETAIL.
13. THE 12" SWING GATE IS CONSTRUCTED OF LIKE MATERIALS AND GROUNDED PER NOTE 12 AND sln-1401822-c001
2023-03-03T13:09:42-0600
DOUGLAS E WEAVER
2023-03-03T12:21:19-0600
DARREN R BRINKER
(TYPICAL 4 PLACES)
FLOOR DRAIN ON CATWALK
PONDING ANYWHERE ON THE CAB ROOF OR CATWALK.
POSITIVE DRAINAGE TOWARDS ROOF/FLOOR DRAINS, AND PREVENT
DRAINS. ALL NEW INSULATION BOARD SHALL BE TAPERED TO ACHIEVE
DEMOLITION DRAWINGS. RETAIN/PROTECT/RE-USE EXISTING ROOF/FLOOR
TEMPORARY AND PERMANENT REMOVALS ARE DEPICTED ON OTHER
CAN BE ACHIEVED AND THE NEW INSTALLATION IS WEATHERTIGHT.
AND WALKWAY WALLS AS REQUIRED TO ENSURE THOROUGH DEMOLITION
SURFACE MOUNTED ITEMS FROM ENTIRE CAB ROOF/PARAPET AND
CATWALK, GROUNDING LUGS/CABLES, CONDUITS, BOXES, AND OTHER
TEMPORARILY REMOVE CAP FLASHING AROUND PARAPET WALL OF
AND TERMINATION BARS FROM AROUND CATWALK AND DISCARD.
INSULATION FROM CAB ROOF AND CATWALK. REMOVE OLD SEALANTS
REMOVE EPDM ROOFING MEMBRANE, WALKPADS, AND RIGID
TO DET. 3, DWG A14. (TYP 4 PLACES)
BOTTOM 2 INCHES ABOVE ROOF DRAIN. SIM.
OVERFLOW SCUPPER THRU PARAPET WALL.
SUPPORT. (TYP 4 PLCS)
OBSTRUCTION LIGHT
SCUPPERS. (TYP).
MEMBRANE COMPLETELY FROM
REMOVE OLD SEALANTS AND EPDM
FLASHING AND PROTECT FOR RE-USE.
REMOVE OVERFLOW SCUPPER METAL
FOR NEW SEALANT.
AND ANTENNA SUPPORTS AND PREPARE
FROM AROUND AIR TERMINAL SUPPORTS
REMOVE ALL OLD/EXISTING SEALANTS
AC UNIT.
FOR SUPPLEMENTAL\
DISCONNECT SWITCH
MOUNTED ON BLOCKS
SUPPLEMENTAL AC UNIT
ROOFING.
VIA A PENETRATION/PITCH POCKET THROUGH
REFRIGERANT LINES ENTER CONTROL CAB
DISCONNECT SWITCH, AND CONDUIT.
AC UNIT, REFRIGERANT LINES,
TEMPORARILY REMOVE SUPPLEMENTAL
ETC FOR ALL PIPES AND ROOF PENETRATIONS.
REMOVE BOOTS, CLAMPS, EXCESS SEALANT,
MANUFACTURER'S INSTRUCTIONS TO ENSURE WEATHERTIGHT INSTALLATION.
AND RESTORE TO LIKE-NEW CONDITION. HATCH SHALL BE FLASHED ACCORDING TO
REMOVE EXISTING ROOF HATCH LID AND HARDWARE. REPLACE WITH NEW COMPONENTS
PONDING ANYWHERE ON THE CAB ROOF OR CATWALK.
POSITIVE DRAINAGE TOWARDS ROOF/FLOOR DRAINS, AND PREVENT
DRAINS. ALL NEW INSULATION BOARD SHALL BE TAPERED TO ACHIEVE
DEMOLITION DRAWINGS. RETAIN/PROTECT/RE-USE EXISTING ROOF/FLOOR
TEMPORARY AND PERMANENT REMOVALS ARE DEPICTED ON OTHER
CAN BE ACHIEVED AND THE NEW INSTALLATION IS WEATHERTIGHT.
AND WALKWAY WALLS AS REQUIRED TO ENSURE THOROUGH DEMOLITION
SURFACE MOUNTED ITEMS FROM ENTIRE CAB ROOF/PARAPET AND
CATWALK, GROUNDING LUGS/CABLES, CONDUITS, BOXES, AND OTHER
TEMPORARILY REMOVE CAP FLASHING AROUND PARAPET WALL OF
AND TERMINATION BARS FROM AROUND CATWALK AND DISCARD.
INSULATION FROM CAB ROOF AND CATWALK. REMOVE OLD SEALANTS
REMOVE EPDM ROOFING MEMBRANE, WALKPADS, AND RIGID
A04/A16
DISCONNECT SWITCH, AND CONDUIT.
AC UNIT, REFRIGERANT LINES,
TEMPORARILY REMOVE SUPPLEMENTAL
SEALANT.
SUPPORTS AND PREPARE FOR NEW
FROM AROUND OBSTRUCTION LIGHT
REMOVE ALL OLD/EXISTING SEALANTS
2'-6" X 2'-6" HATCH
PANELS AT CONSOLE
SEE DET. 11C ON SHEET A07.
SEE DWG A18. (TYP)
CONTROL CAB CONSOLES
EXTERIOR WALKWAY
BELOW
6.0 CU. FT. REFRIGERATOR
SINK W/GARBAGE
DISPOSER.
A001
RM 801
RM 820
CAB STAIR
EL = 197'-0"
DC
FE
42" HIGH STEEL
PIPE GUARDRAIL
ROOF HATCH
AT CAB LADDER
ENCLOSURE. SEE
ELEC DWGS.
(TYP 3 PLACES)
TAPERED INSULATION
TYPICAL AT CAB
ROOF. SLOPE TO DRAINS
AIR TERMINAL SUPPORT
PIPE (TYP 10 PLACES)
SEE ELEC DWGS.
SINGLE PLY
ROOFING MEMBRANE EXHAUST FAN
SEE MECH
RUBBER
WALKPADS (TYP)
(TYP 10 PLACES)
ANTENNA SUPPORT.
(TYP 4 PLACES)
CAB ROOF ANTENNA MOUNTS
CAB LEVEL ROOF PLAN
A04/A14
EL = 221'-0" (TOS)
COORDINATE TEMPORARY REMOVAL
BULKHEAD PLATE ENCLOSURES OF
WITH FAA COR. FOLLOW OPERATIONAL
RISK MANAGEMENT PROCEDURES AND
DO NOT DISCONNECT ANY ANTENNAS
WITHOUT FAA APPROVAL.
SLN-1401822-D001
CAB LEVEL FLOOR PLAN (LEVEL - 8) AND
CAB LEVEL ROOF PLAN - DEMOLITION
-d
IM
CAB COLUMN RACEWAY SCHEDULE
COL. NO. USE REMARKS
COLUMN USE DESIGNATION IS
CRITICAL TO THE OPERATION OF
THE ATCT. ANY DEVIATION FROM
THIS DESIGN MUST BE
AUTHORIZED BY THE COR.
1 ANTENNA CABLE
2 ROOF DRAIN
3 POWER
POWER4
5 SPARE
ANTENNA CABLE
ROOF DRAIN
FIRE PROTECTION
SPARE
POWER
2' 0 2' 6'
4' sln-1401822-d001
2023-03-03T13:16:53-0600
DOUGLAS E WEAVER
2023-03-03T13:27:08-0600
DARREN R BRINKER
ATCT (TYP.) SEE STRUC. COLOR=PCS-1)
PRECAST CONCRETE PANELS ON
FIRE DEPT. CONNECTION
GATE. SEE DETAILS ON THIS SHT.
11'-4" WIDE DOUBLE-SWING METAL
EQUIP. YARD WALLS. (COLOR = CIP-1)
BLDG. WALLS AND EXT. SURFACE OF
APPLIED TO SURFACE. TYP. ALL BASE
ON BASE BLDG. W/ ACRYLIC STUCCO
CAST-IN-PLACE CONCRETE WALLS
METAL FASCIA (MF-1)(COLOR MCF-1)
WALL (COLOR CIP-1)
8' TALL C.I.P. SCREEN
(TYPICAL 10 PLACES)
TERMINAL SUPPORTS
AIR TERMINAL AND AIR
INTAKE LOUVER
STAIR PRESS
(COLOR=CIP-1)
C.I.P. SCREEN WALL
(COLOR MCF-1)
BASE BLDG. (TYP.) (COLOR=CIP-1)
CAST-IN-PLACE CONCRETE WALLS ON
METAL FASCIA (MF-1)
SEE STRUC. (COLOR=PCS-1)
FIRE DEPT. CONN.
CONC SCREEN
4"11'-4" CLR4"
12'-0"
1'-0"
1"3"1"1"
4"
1/2" SQUARE PICKETS AT 5" O.C.
ALUM. GATE W /2"X4" FRAME AND
PICKETS AT 5" O.C.
FRAME AND 1/2" SQUARE
ALUM. GATE W /2"X4"
BRACING (TYP)
1"x1" ALUM. TUBE
1/2" SOLID PICKET (TYP)
2"X1/4" ASTRAGAL
BARREL BOLT/LOCK
PIPE WELDED TO GATE
3/4" DIA x 2" LONG STL
BOLT W/ 2" LONG HANDLE (TYP)
5/8" DIAM. x 10" LONG STL CANE
CONC SLAB
PIPE SLEEVE SET IN CONC.
2 1/2" LONG x 3/4" DIAM. PVC
GATE AND ANGLE.
(3) ALUM HINGES WELDED TO
FRAME.
2"X4" ALUM TUBE
FULL LENGTH. BOLT AT 12" O.C.
PROVIDE GALVONIC SEPARATOR
TO STL ANGLE WITH S.S. BOLTS.
4x3x3/8" CONT. ALUM ANGLE. BOLT
SEE STRUC.
STL PLATE
STL ANGLE.
4x3.5x3/8"
CONC
4x3 ALUM ANGLE
& GATE FRAME
PLATE WELDED TO PIPE
1" DIA PIPE W/ 1/4"x4"x4"
BOTTOM SLEEVE
SLEEVE & SET IN
WELDED TO TOP PIPE
8" LONG ROD
& JAMB
WELDED TO PIPE
1/4"x4"x4" PLATE
1" DIA PIPE WITH
ALUM. PICKET
ALUM. FRAME
CONC. WALL
CONC. SCREEN WALL
BOLT AT 12" O.C.
PROVIDE GALVONIC
ANGLE WITH S.S. BOLTS.
ANGLE. BOLT TO STL
4x3x3/8" CONT. ALUM
STRIKE PLATE.INCL.
CUT STRIKE AND
LOCKSET
STAINLESS STL
CONC.
FIELD LOCATE.
(TYP 2 PLACES)
GATE STOP/LATCH
AT LOCKSET
NORTH ELEVATION
EAST ELEVATION
EL. 211'-0"
MAX. EL. 229'-4"
SUPPORTS
TOP OF AIR TERMINAL
FIRST FLOOR
107A
L-9 L-9 L-9 G-2 G-2 G-2 G-2 G-2
THROUGH THE CABS AND CATWALK AREAS.
DEMO DRAWINGS D03 AND D04 FOR SECTIONS
AND WEATHERTIGHT FINAL INSTALLATION. SEE
DRAWINGS TO ENSURE A COMPLETE REMOVAL
REMOVALS DEPICTED ON OTHER DEMOLITION
PERFORM OTHER TEMPORARY AND PERMANENT
AND INSULATION FROM CAB ROOF AND CATWALK.
REMOVE EPDM ROOFING MEMBRANE, WALKPADS,
G-2G-2G-2G-2G-2G-2G-2G-2
210A
GATE LATCH & CANE BOLT DETAIL
LATCH DETAIL
GATE JAMB AT HINGE
SCREEN WALL GATE
WALK-THROUGH GATE
HINGE DETAIL
CONTRACTOR SHALL PERFORM ALL WORK SHOWN IN CLOUDS.
t t e d b
SLN-1401822-D002
AIRPORT TRAFFIC CONTROL/BASE BLDG.
EXTERIOR VIEWS - EAST AND NORTH TOWER VIEWS
DEMOLITION
BUILDING GLASS SCHEDULE
OF ANNEALED GLASS WITH A 1/2" AIRSPACE.
1-1/2" THICK INSULATING GLASS UNITS CONSISTING OF 2 LITES
GRAY.
BUTYRAL (PVB) INNER LAYER. COLOR OF PVB SHALL BE LIGHT
OF 1/8" THICK ANNEALED GLASS WITH A 0.060 POLYVINYL
OUTER LITES ARE LAMINATED GLASS CONSISTING OF 2 PANES
LAMINATED GLASS WITH A 1/2" AIRSPACE. THE INNER AND
OUTER LITES ARE TEMPERED.
MONOLITHIC GLASS WITH A 1/2" AIRSPACE. THE INNER AND
EXTERIOR COLOR SCHEDULE
AL-2 ALUM. LOUVER - SW 2128 MARCH WIND
AL-1 ALUM. LOUVER - DARK SLATE
MG-1 METAL GATE - DARK SLATE
IMP-1 INSULATED METAL PANEL - DARK SLATE
CIP-1 CAST IN PLACE CONCRETE
MCF-1 METAL CAP FLASHING COLOR - DARK SLATE
MF-1 METAL FASCIA SYSTEM - DARK SLATE
PCS-1 PRECAST CONCRETE PANELS
DESCRIPTIONKEY
LOUVER SCHEDULE
KEY DESCRIPTION COLOR
24" X 24" FIXED BLADE, ALUM. AL-2
20" X 20" FIXED BLADE, ALUM.
72" X 72" FIXED BLADE, ALUM.
48" X 48" FIXED BLADE, ALUM.
32" X 52" FIXED BLADE, ALUM.
36" X 24" FIXED BLADE, ALUM.
ALUM GRILLES @ LEVEL 5A
L-1
L-2
L-3
L-4
L-5
L-10
L-11
G-3
G-1
4' 0 4' 12'
8'
1' 0 3' 5'
1' 2' 4' sln-1401822-d002
2023-03-03T13:10:11-0600
DOUGLAS E WEAVER
2023-03-03T12:22:00-0600
DARREN R BRINKER
LOW AIR TRAFFIC TIMES. INSTALL PARTS PER MANUFACTURER'S INSTRUCTIONS AND ENSURE
PERSONNEL PRIOR TO STARTING. CONTRACTOR MAY BE REQUIRED TO PERFORM WORK DURING
AND INSTALLATION WORK. FULLY COORDINATE ALL WORK WITH THE FAA COR AND AIR TRAFFIC
MANAGEMENT (ORM) CONSIDERATIONS WILL BE REQUIRED (NOISE, FUMES) DURING DEMOLITION
OLD HATCH LID/HARDWARE CAN BE REMOVED/REPLACED IN ONE DAY. OPERATIONAL RISK
CONDITION. FOR SECURITY AND WEATHER PROTECTION, COORDINATE ALL WORK SO THE
REMOVE/REPLACE THE CAB ROOF HATCH LID AND HARDWARE TO RESTORE TO A LIKE-NEW
TIME THAT IS REQUIRED BY THE AIR TRAFFIC CONTROLLERS.
HOWEVER IT WILL NEED TO BE FULLY RETRACTED AT THE END OF EACH WORK SHIFT AND AT ANY
SEPARATE COMPONENTS. NO WORK ON THE FOLDING STAIR IS REQUIRED UNDER THIS CONTRACT;
MANAGEMENT, AND THE CAB OCCUPANTS. THE FOLDING STAIR AND THE ROOF HATCH ARE TWO
THE CAB. ALL WORK SHALL BE FULLY COORDINATED IN ADVANCE WITH THE FAA COR, AIR TRAFFIC
ALL WORK ON THE CAB ROOF WILL LIKELY BE A DISRUPTION TO AIR TRAFFIC CONTROL OPERATIONS IN
THE ONLY ACCESS TO THE CAB ROOF IS VIA THE FOLDING STAIR IN THE CONTROL CAB CEILING. ANY AND
PLUMBING CHASE
TO 178'-10'
EXTEND FROM ELEV. 96'-0"
W/ROSE SAFETY CLIMBING RAIL.
CLIMBING LADDER (SEE STRUC)
(SEE STRUC)
PILE CAP
COUNTERWEIGHT
2HR RATING
A02/A02
SPRAY FIRE PROOFING 4 HR RATING
RM 615
DETAILS.
SHALL BE ALLOWED TO ENTER THE CONTROL TOWER BUILDING AT ANY TIME. SEE DEMOLITION DRAWING D04 FOR MORE
AND ALL WEATHER PROTECTION TO ENSURE INTERIOR SPACES REMAIN DRY AT ALL TIMES. NO WIND AND/OR RAIN
ANTENNAS, DISCONNECTION OF GROUNDING WIRES, ETC.) CONTRACTOR IS FULLY RESPONSIBLE FOR PROVIDING ANY
AIR TRAFFIC OPERATIONS (NOISE, FUMES FROM VOC'S, LINE-OF-SITE IMPACTS FROM CRANE, DISCONNECTION OF RADIO
PENETRATIONS. COMPLY WITH FAA ORM REQUIREMENTS FOR WORK THAT MAY IMPACT AIR TRAFFIC CONTROL AND/OR
RE-INSTALLING SURFACE-MOUNTED ITEMS TO ENSURE WEATHERTIGHT SEAL AT ALL FASTENERS AND MEMBRANE
TO ENSURE COMPLETE REMOVALS AND RE-INSTALLATIONS. INSTALL NEW SEALANTS AS NECESSARY BEFORE
ETC AT THE ATCT CAB ROOF AND CATWALK LEVELS. TEMPORARILY REMOVE SURFACE-MOUNTED ITEMS AS NECESSARY
REMOVE EPDM ROOFING MEMBRANE, WALKPADS, INSULATION, FLASHING, TERMINATION BARS, PIPE BOOTS, SEALANTS, EL=229'-4"
TOP OF AIR TERMINAL SUPPORT
EL=211'-0"
EL=197'-0"
EL=189'-8 3/4"
LEVEL 7
EL=180'-0"
LEVEL 6
EL=172'-0"
LEVEL 5A
EL=164'-0"
LEVEL 5
EL=156'-0"
LEVEL 4A
EL=148'-0"
LEVEL 4
EL=140'-0"
LEVEL 3A
EL=132'-0"
LEVEL 3
EL=124'-0"
LEVEL 2A
EL=116'-0"
LEVEL 2
EL=108'-0"
LEVEL 1A
EL=100'-0"
FIIRST FLOOR
ELEVATOR SHAFT
RM 614
RM 618
MECHANICAL
618A
RM 106
EQUIPMENT107
BUILDING SECTION
A01/A10 t t e d b
SLN-1401822-D003
TOWER SECTION
1 06-27-2002
CE-E-4039-A10
sln-1401822-d003
2023-03-03T13:10:51-0600
DOUGLAS E WEAVER
2023-03-03T12:22:19-0600
DARREN R BRINKER
IF
W
VARIES
AND RIGID INSULATION
1/2" GYPSUM BOARD ON 3" Z FURRING
CAP
ON A08
LOUVER L-10, SEE SCHEDULE
ELEVATOR RELIEF DAMPER.
WALKWAY PADS OVER ERDM
90 mil EPDM MEMBRANE OVER
SURFACE MOUNTED COUNTER FLASHING
90 mil EPDM MEMBRANE
SCUPPER
PANEL
(SLOPE TO DRAINS)
4" (MAX) RIGID INSULATION
DUCT WORK, SEE MECHANICAL DWGS.
REMOVABLE STEEL GRATING
STEEL TUBE COLUMNS AT CAB
PARTITION TYPE - "C"
2 HOUR FIRE RATED GYPSUM
DRAWINGS
ELECTRICAL
CABLE TRAY SEE
SEE MECHNICAL DWGS.
TO CAB GRILLES
MECHNICAL SUPPLY DUCTS
CAB CONSOLES
SLAB AT CAB
METAL DECK AND CONCRETE
SPRAYED FIRE PROOFING 2 HOUR RATING
TYPE - "C"
GYPSUM PARTITION
2 HOUR FIRE RATED
PRECAST CONCRETE PANEL.
WALKWAY, AND UP THE FACE OF THE INTERIOR
CONCRETE PANEL ON OUTSIDE PERIMETER OF
EXTEND EPDM MEMBRANE UP AND OVER PRECAST
THE TOP OF WALL TYPICAL.
PARAPET AFTER EPDM MEMBRANE IS EXTENDED OVER
RE-INSTALL ALUMINUM CAP FLASHING AROUND WALKWAY
PRIME AND PAINT. (TYPICAL)
COMPONENTS ON THE CAB ROOF.
REMOVE RUST FROM ALL METAL
UNDER SILL
EXTEND EPDM
METAL FLASHING
1/2" GYPSUM BOARD
H. MET. DOOR AND FRAME
ALUMINUM THRESHOLD
3" RIGID INSULATION BOARD
1/2" GYPSUM BOARD ON Z-FURRING
CONCRETE CURB
8"
/8
DRIP FLASHING
PRECAST CONCRETE PANEL
REMOVED/REPLACED
MEMBRANE CAN BE
DOOR TO ENSURE EPDM
FLASHING AT CATWALK
LOOSEN SILL AND METAL
LEVEL-1
ELECTRONICS EQUIPMENT
GYPSUM BOARD CEILING
FROM ELEV. 96'-0" TO 186'-0".
WITH ROSE SAFETY CLIMBING RAIL. EXTEND
STEEL CLIMBING LADDER (SEE STRUCTURAL)
CABLE TRAY (BEYOND)
METAL GRATING
2A11
4A11
GYPSUM BOARD
EL = 211'-0"
DETAIL 3 ON DRAWING A15 FOR MORE
BOXES, ACCESS PLATES, ETC. SEE
CONDUITS FOR SURFACE MOUNTED
MOUNTS, AIR TERMINAL SUPPORTS,
PENETRATIONS INCLUDING ANTENNA
REMOVE OLD SEALANT AT ALL FLASHING
THE LIVES OF THE FLYING PUBLIC.
IN DAMAGE TO ELECTRONICS EQUIPMENT AND ENDANGER
CONTROL CAB OR EQUIPMENT ROOMS COULD RESULT
ALL AREAS ARE WEATHERTIGHT. RAIN ENTRY INTO THE
REMAIN DRY UNTILL FINAL ROOFING IS INSTALLED AND
ENSURE THE CONTROL CAB AND ALL INTERIOR SPACES
TEMORARY WEATHER PROTECTION AS NECESSARY TO
CONTRACTOR IS REPONSIBLE FOR PROVIDING ANY AND ALL
TITLE
A03/A12 t t e d b
SLN-1401822-D004
TOWER SECTIONS
2 07/13/2002
CE-E-4039-A12
A10-A12
A10-A12
CLAMPS/RINGS AT ROOF DRAINS AND SEAL PER MANUFACTURER'S RECOMMENDATIONS.
AND OLD SEALANTS SHALL BE REMOVED AND DISCARDED. ADEQUATELY TERMINATE EPDM MEMBRANE UNDER ALL
AND COUNTER FLASHING CAN BE REUSED IF IT IS REMOVED IN GOOD CONDITION AND PROTECTED. TERMINATION BARS
FLASHING AT SCUPPERS (TOTAL OF 4) SHALL BE COMPLETELY REMOVED AND REPLACED. ALUMINUM CAP FLASHING, TO ENSURE POSITIVE DRAINAGE AND NO PONDING ANYWHERE ON THE CATWALK LEVEL EPDM MEMBRANE/METAL
MEMBRANE. ROOF DRAINS SHALL BE PROTECTED AND CAN BE RE-USED. SLOPE ALL NEW INSULATION TO ROOF DRAINS
FLASHING AND ALUMINUM CAP FLASHING FROM ENTIRE WALKWAY ALONG WITH RIGID INSULATION BOARD AND EPDM
CATWALK LEVEL EXTENDS AROUND ENTIRE PERIMETER OF CONTROL CAB. REMOVE TERMINATION BAR/COUNTER sln-1401822-d004
2023-03-03T13:11:13-0600
DOUGLAS E WEAVER
2023-03-03T12:22:47-0600
DARREN R BRINKER
W/ PLASTIC LAMINATE.
3/4 INCH SILL COVERED
(THICKNESS VARIES)
RIGID INSULATION BOARD
INSTRUCTIONS TO ENSURE A LONG-TERM
MEMBRANE AND DRAIN MANUFACTURER'S
SEALANT/CUTOFF MASTIC AS REQUIRED PER
FLOOR DRAIN COLLAR AND PROVIDE/INSTALL
MEMBRANE OF A SUFFICIENT LENGTH UNDER THE
PROTECT FROM DAMAGE. EXTEND EPDM
FLOOR DRAINS AT CATWALK CAN BE RE-USED.FOR ROUTING DRAIN LINE.
W/3-INCH OUTLET. SEE MECH
FLOOR DRAIN, (ZURN Z100)
UNDER COLLER.
DRAIN AND BOLTED
EXTENDED INTO
EPDM MEMBRANE.
AND EPDM MEMBRANE
REMOVE RIGID INSULATION
AND EPDM MEMBRANE
REMOVE RIGID INSULATION
W/ EXP. ANCHOR (TYP.)
LOUVER CLIP
(DARK SLATE)
W/KYNAR FINISH
ALUM. LOUVER
BATT INSUL. (TYP)
STUFF W/ R-13
FOR ROUTING DRAIN LINE.
W/3-INCH OUTLET. SEE MECH
FLOOR DRAIN, (ZURN Z100)
INSUL MET. PANELS
ROD AND SEALANT
MET. FLASHING BACKER
ALUM. WINDOW
AND GYP. BD
MET. STUDS
WINDOW SHADE
2x10 NAILER
2X4 NAILER
FIXTURE (SEE ELEC)
TRACK AND LIGHT
GYP, (TYP)
MET. STUDS AND
TILE (FULL PANEL)
ACOUSTICAL CEILING
SHADE PER
ADDITIONAL WINDOW
05-05
TS6 x 3
COLOR: FLAT BLACK
COLUMN. COATED
COVERS OVER STEEL
0.032 ALUM. COL.
COLUMN. COLOR: FLAT BLACK
0.032 ALUM. COVERS OVER STEEL
CONTINUOUS P.T. NAILER
SEE MECH FOR DUCT
BACK OF CAB CONSOLES
CAB COLUMN (BEYOND)
ALUMINUM WINDOW
AND SEALANT
BACKER ROD
CONSOLE TURRET
BENT PLATE
3-1/2"X3-1/2" X 1/4"
SEE STRUCT.
STEEL TUBE.
SEALANT ARE UN-USEABLE. TYPICAL 10 LOCATIONS.
PAINT TOO THICK SO THAT THREADS
OR APPROVED EQUAL. DO NOT APPLY
RUST. PRIME/PAINT WITH RUSTOLEUM,
SUPPORTS AND NUTS TO REMOVE
WIRE-BRUSH THREADED ANTENNA
OPENING IN TUBE.
TO PROVIDE 2 3/4" DIA.
ALL AROUND AT BASE
SCH. 40 PIPE WELDED
2 1/2" I.D. THREADED
SEPARTION (TYP).
(FINISH IMP-1). W/ GALVONIC
.090" ALUM. CAP FLASHING.
BACKER ROD AND SEALANT
GRADE PLYWOOD.
2 LAYERS 3/4" EXTERIOR
TYPICAL AROUND ENTIRE CAB
IF STILL IN GOOD CONDITION.
ALWAYS SHOWN) AT CORNERS
RE-USE WOOD CANTS (NOT
SEE STRUCTURE
CAB MULLION
INSUL. METAL PANEL
W/ BACKER ROD &
GALVONIC SEPARATOR
.090" ALUMINUM
GROMMET PER NFPA-70
COLUMN THRU TS WITH
3" X 10" OPNG AT EACH
.090" ALUM. CAP
TS, SEE STRUC.
WASHERS AT 2'-0" O.C. (TYP)
SCREWS W/ NEOPRENE
1/4" SELF-TAPPING S.S.
MOUNT (TYP)
CAP ON ANTENNA
THREADED NUT AND WASHER, BOTH SIDES.
BUSHING
OBSTR. LIGHT MOUNTS SIMILAR.
SPECIFIED. (SEE ELEC FOR REQ)
AIR TERMINAL SUPPORT WHERE
CONT. ANGLE (SEE STRUC)
PENETRATION EXISTS IN TOP OF PARAPET.
OTHER LOCATION WHERE A VERTICAL
EACH ANTENNA MOUNT (10) AND ANY
REMOVE OLD SEALANT AND APPLY NEW AT
NEW. TYPICAL ENTIRE CAB.
REMOVE OLD SEALANT AND INSTALL
TIGHTENING.
FASTENER HEADS BEFORE RE-
NEATH IT. APPLY SEALANT UNDER
EPDM CAN BE EXTENDED UNDER-
ONLY. LOOSEN ADEQUATELY SO
FOR BOTTOM PIECE OF FLASHING
TEMPORARILY LOOSEN FASTENERS
MOUNT OPENING.
AT EACH ANTENNA
STEEL COVER PLATE
8"x8"x1/8" STAINLESS
TYP. OF 10.
ANTENNA MOUNT COVER PLATES.
AND INSTALL NEW SEALANT AROUND
REMOVE OLD SEALANT COMPLETELY
REMOVE AND REPLACE TYPICAL.
FOR REPLACEMENT. TYPICAL.
SO A CONTACT CHANGE CAN BE NEGOTIATED
FAA COR IMMEDIATELY IF DAMAGE IS FOUND
CAB PARAPET IF IN GOOD CONDITION. NOTIFY
RE-USE EXTERIOR GRADE PLYWOOD AROUND
ROOF.
FULLY-ADHERED EPDM MEMBRANE
TAPERED TO ROOF DRAINS.
2-INCH RIGID INSUL. BD.
3-INCH RIGID INSUL. BD.
POLY VAPOR BARRIER (TYP.)
MET. DECK AND CONC. W/6 MIL
IN ITS ENTIRETY. TYPICAL.
REMOVE EPDM MEMBRANE
TO METAL DECK.
INSULATION DOWN
REMOVE ALL RIGID
GALVANIZED STEEL COMPONENTS SHALL BE
PAINTED WITH A ZINC-RICH PRODUCT LIKE
COLD-GALV, OR APPROVED EQUAL
SEALANT CONT.
BACKER ROD &
"Z" FURRING
3" RIGID INSUL. ON
1/2" GYP. BOARD
AS ONE PIECE
SHOP FABRICATE
1/4" BENT PLATE
FOR 1/4" CTSK BOLTS
DRILL & TAP PLATE
(SEE MECH)
SEE STRUCT. DWGSSTS.
STEEL TUBE.STR.
FACED WITH ALUMINUM
ON STEEL, TYP WHERE
BITUMINOUS COATING
STEEL PLATE
COATED
1/4" EPOXY
(2 LAYERS)
RUBBER SEAM SEAL
(2 LAYERS)
RUBBER SEAM SEAL
METAL INSERT
ALL SCUPPERS AT CAB ROOF
MEMBRANE/FLASHING AROUND
REMOVE SEALANTS AND EPDM
TYPICAL ALL LOCATIONS
WITH NO CORROSION.
IF IT IS IN GOOD CONDITION
METAL INSERT CAN BE RE-USED
t t e d b
SLN-1401822-D005
DEMOLITION - EXTERIOR DETAILS
SALINA MUNICIPAL AIRPORT - SALINA, KANSAS
CAB ROOF PARAPET
4 SCALE: 3" = 1'-0"
5INSULATED METAL
SCUPPER @ WALKWAY
A10-A15
HEAD @ CAB WINDOW
SPANDREL GLASS @ 6TH LEVEL
WINDOW @ 6TH LEVEL
4 SCALE: 3" = 1'-0"
PRECAST JOINT DETAIL
A15
CONTRACTOR SHALL PERFORM ALL WORK SHOWN IN CLOUDS.
2 07/13/2006
CE-E-4039-A15
sln-1401822-d005
2023-03-03T13:11:32-0600
DOUGLAS E WEAVER
2023-03-03T12:23:53-0600
DARREN R BRINKER
6'-6 1/2"
X
MOUNTING BRACKETS
1/8" STEEL FRAME 48" DEEP
ALUMINIMUM STEPS
HANDRAIL
EXTRA HEAVY OPERATING ARM
PROVIDE INSULATED HATCH LID IF AVAILABLE.
THE MANUFACTURER TO ENSURE REPLACEMENT PARTS ARE A PERFECT MATCH.
RESTORE THE ROOF HATCH TO A LIKE-NEW CONDITION. COORDINATE WITH
MANUFACTURER IS PRECISION LADDERS, LLC AT "PRECISION LADDERS,COM"
REMOVE AND REPLACE THE CAB ROOF HATCH LID AND ALL HARDWARE. THE
BATTEN 1/8" ALUMINUM
EXTRA HEAVY OPERATING ARM
DOOR PANEL 1/8" ALUMINUM
DOUBLE SPRING ACTION
2'-6"
HANDRAIL BOTH SIDES
SIDE RUNNER 5" ALUMINIMUM
MIDDLE SECTION
TREAD (STEPPED ALUMINIUM)
1'-9 1/2 "
1'-7 1/2 "
SPRAYED INSULATION
MAINTAIN STEP SPACING
STEEL PIANO DOOR HINGE
BELOW BOTTOM OF FRAME.
TOP STEP LOCATED AT ONE INCH
BATTEN 1/8" ALUMINIUM
SIDE RUNNER 5" ALUMINIUM
OPENING AND CLOSING EYE POLE OPERATED
MIDDLE SECTION
TREAD (SERRATED ALUMINIUM)
BOTTOM SECTION
ADJUSTABLE FOOT
9 1/2"
HANDRAIL BOTH SIDES
DOUBLE SPRING ACTION
SECTION
BOTTOM
FOOT
ADJUSTABLE
A16-A16
3B
5 1/2 "
1 1/2"
5 1/2 "
WALL CAP
5 1/2" x 1 1/8" HARDWOOD
STUD RUNNER WITH SHIMS
5/8" GWB
AT 1'-4" O.C. BRACED TO COLUMNS
3 5/8"-18 GUAGE METAL STUDS
FOR HANDRAIL SUPPORT
6" x 23" 16 GUAGE STEEL PLATE
PIPE HANDRAIL
1-1/2" STEEL
AT 8'-0" MAX.
BRACKETS
WALL PANEL
PIPE HANDRAIL
1-1/2" STEEL
AT 8'-0" MAX.
BRACKETS
EL. 97'-0"
EL. 95'-0"
CAB ROOF
1. LADDER "PRECISION STAIR CORPORATION"
NOTES:
1"1"
MODEL NO. SS/AL/-140 W/500 POUND LOADING.
2. LADDER AND HANDRAIL COMPLY WITH O.S.H.A.
REQUIREMENTS.
SYSTEM TO ENSURE QUIET OPERATION.
OF THE DISAPPEARING LADDER
GREASE/OIL ALL HINGE/PIVOTS/ETC.
SECTION AT CAB ROOF LADDER
A04-A16
SECTION AT CAB ROOF LADDER
A04-A16 t t e d b
HANDRAIL ELEVATION
HANDRAIL PLAN
EDGE OF STAIR TREAD
AND RETURN TO WALL
PAST EDGE OF STAIR TREAD
EXTEND HANDRAIL 1'-11"
SCALE: 3"" = 1'-0"
HANDRAIL SECTION
CAB HANDRAIL SECTION
HANDRAIL DETAILS
A11-A16
1 1/2"
SLN-1401822-D006
1 06/27/2002
CE-D-4039-A16
-A
POTENTIAL IMPACTS TO AIRCRAFT ON THE AIRPORT.
SHALL BE SECURELY FASTENED TO PREVENT LOOSENING IN THE WIND WHICH COULD RESULT IN
LEAK SHALL BE FULLY REMEDIED WITHIN 2 HOURS AFTER NOTIFICATION BY FAA. WEATHER PROTECTION
CONTRACTOR DEPARTS THE JOB SITE FOR THE DAY/WEEKEND, THE WEATHER PROTECTION AND/OR
A POSSIBILITY. IF WEATHER PROTECTION IS NOT SUFFICIENT AND/OR A LEAK DEVELOPS AFTER THE
AT THE END OF EACH WORK SHIFT. DO NOT SCHEDULE REMOVAL WORK IF INCLIMATE WEATHER IS
AND ENSURING THAT THE CONTROL CAB AND ATCT BUILDING ENVELOPE ARE FULLY PROTECTED
THE CONTRACTOR IS RESPONSIBLE FOR ALL WEATHER PROTECTION DURING THE ENTIRE CONTRACT, DEMOLITION WORK AT THE CAB ROOF LEVEL.
MATERIALS FOR THIS PROJECT MUST BE ORDERED AND ON-HAND PRIOR TO BEGINNING ANY
ADVANCE OF ANY WORK TAKING PLACE.
ISSUES THAT COULD IMPACT THE AIR TRAFFIC OPERATION MUST BE DISCUSSED AND RESOLVED IN
NOISE, FUMES, LOSS OF HEAT/COOLING, WEATHER PROTECTION DURING CONSTRUCTION, AND OTHER
RETRACTED MULTIPLE TIMES PER DAY IF IT IS INTERFERING WITH AIR TRAFFIC CONTROL. ROOF ACCESS, OF THE AIRPORT TRAFFIC CONTROL TOWER. THE DISAPPEARING LADDER SYSTEM MAY NEED TO BE
THE ONLY PERSONNEL/WORKER ACCESS TO THE CAB ROOF IS THROUGH THE EXISTING CONTROL CAB sln-1401822-d006
2023-03-03T13:11:54-0600
DOUGLAS E WEAVER
2023-03-03T12:24:10-0600
DARREN R BRINKER
DOWN CONNECTOR
LIGHTNING PROTECTION
NOTE 3
DRAWING E22
SEE DETAIL 8,
DOWN CONDUCTOR
(4 TOTAL)
3'X28 GA COPPER STRAP
#2 AWG GREEN/W ORANGETRACER (TYP.)
CAB MULLION BONDED TO GROUND BUS WITH
DETAIL 13, DRAWING E21 SHEET 2
PERIMETER GROUND BUS SEE
GROUND CONDUCTOR
TRANSIENT PROTECTION
NOTE 4
PLANE
EQUPOTENTIAL
NOTE 3
EQUIPOLENTIAL PLAN
SYSTEM HAS BEEN INSTALLED. TYPICAL
COMPONENTS AFTER NEW ROOF
AND REPLACEMENT. RE-INSTALL ALL
COMPLETE ROOF SYSTEM REMOVAL
CATWALK LEVEL TO PERFORM
TRANSIENT PROTECTION AT THE
LIGHTNING PROTECTION AND
TEMPORARILY LOOSEN REMOVE ALL
t t e d b
MAIN GROUND
PLATE, NOTE 9
MULTIPOINT GROUND
ENTIRE ROOM, SEE DWG. E21
EQUIPOTENTIAL PLANE THROUGHOUT
24" CABLE TRAY
TP
COAXIAL
BULKHEAD
BOX
PG
MECHANICAL EQUIPMENT
DN
14R
UP
DN
MPG5
SNAKE CABLE
PLUMBING ACCESS ROOM
NORTH STAIR
SOUTH STAIR
CAB STAIRS
REST ROOM
ELEVATOR LOBBY
610 ELECTRIC EQUIPMENT
CABLE CHASE
JANITOR
JUNCTION GROUNDING PLAN (LEVEL-6)
E10-E10
SPG
3 4
EXTERIOR
WALKWAY
PLATE, NOTE 8
SINGLEPOINT GROUND
2-12" C.T.
PLATE, NOTE 8
MULTIPOINT GROUND
WELD (TYP.)
EXOTHERMIC
(TYP.)
SEE NOTES
NOTE 6
24" CABLE TRAY
18" CABLE TRAY
12" VERTICAL
NOTE 5
NOTE 5
WELD (TYP.)
1-24" CABLE TRAY
BETWEEN COLUMNS NO. 3 AND NO. 4
24" CABLE TRAY SET ON SIDE
CONSOLE
CONSOLE
CAB
STAIRS
HATCH ACCESS
EXTERIOR
WALKWAY
CONSOLE ACCESS GROUNDING PLAN (LEVEL-7)
9 8
CAB LEVEL GROUNDING PLAN
NOTE 11
(2 TOTAL)
BONDING LUG
SECONDARY
WELD TYP
CAB LADDER
ROOF HATCH AT
BONDING LUG
SECONDARY
THRU ROOF
3" VENT
TERMINAL (10 TOTAL), NOTE 10
LIGHTNING PROTECTION AIR
EXOTHERMIC WELD TYP.
ENCLOSURE (3 TOTAL)
TRANSIENT PROTECTION GROUND
CONDUCTOR NO. 4/0 AWG GREEN
W/RED TRACER IN 1" PVC,
SUPPORT 3'-0" O.C.
CONDUCTOR (2 TOTAL), NOTE 11
LIGHTNING PROTECTION DOWN
28 STRANDS NO.14 COPPER (CLASS II)
LIGHTNING PROTECTION CONDUCTOR
IN 1" PVC, SUPPORT 3'-0" 0.C.
HATCH
BONDING
EXHAUST FAN
(2 TOTAL)
BONDING PLATE
EXOTHERMIC WELD TYP.
T T
3 4
BULKHEAD
ENCLOSURE
CAB LEVEL ROOF GROUNDING PLAN
RE-INSTALLATION (TYPICAL)
COMPLETE ROOF REMOVAL AND
REQUIRED TO PERFORM THE
AND BONDING WIRES/LUGS AS
TEMPORARILY REMOVE GROUNDING
SLN-1401822-D007
GROUNDING PLAN, JUNCTION, CONSOLE ACCESS
AND ROOF LEVELS - DEMOLITION
FOR LEGEND, SEE DRAWING E01.1.
3.ROUTE LIGHTNING PROTECTION DOWN CONDUCTOR IN 1" PVC NEXT TO CAB
MULLION. SEE DETAIL 1 AND 2, DRAWING E22.
FOR GROUNDING RISER, SEE DRAWING E172.
4.ROUTE TRANSIENT PROTECTION GROUND CONDUCTOR IN 1" PVC NEXT TO CAB
MULLION. SEE DETAIL 2 AND 3, DRAWING E22.
This is the start of the file's text. The full file is on GovTribe.