ITB-24-2 PVRCC Renovation - Construction Plans.pdf
PDF 33 MB Posted
- Solicitation number
- ITB-24-2
- Issued by
- Chaves County, Rowe CDP, New Mexico
About this file
The document is a comprehensive set of architectural and engineering construction plans for the Pecos Valley Regional Communications Center Renovation project, involving Chaves County, New Mexico, located in Roswell. The project consists of a selective renovation of the existing administrative center, with the base bid scope including interior demolition, new partitions, exterior wall modifications, finishes, plumbing, pneumatic tube system, transaction drawer installation, sprinkler system modifications, site work, and comprehensive electrical, telecommunications, and special systems infrastructure. The project includes several additive alternates: a new diesel generator, redundant HVAC systems with structural bracing, exterior parking area improvements, and a chemical fire suppression system for the new I.T. room. The renovation will transform the existing south-western wing to house the Pecos Valley Regional Communications Center, currently located in the north-eastern wing of the facility.
The construction documents indicate a detailed approach to the renovation, with specific technical specifications across architectural, mechanical, electrical, plumbing, and special systems domains. The project's total existing building gross area is 72,908 square feet, with 3,217 square feet of new work proposed. The facility is classified as a Group B occupancy, Type IIIB construction, and will be sprinklered. The electrical design includes a new 175-kW diesel generator, multiple electrical panels, and comprehensive telecommunications infrastructure. Funding appears to be from county sources, with the project designed to modernize and improve the regional communications center's operational capabilities. The documents suggest a comprehensive, systematic approach to upgrading the facility's technological and physical infrastructure while maintaining existing building characteristics.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ITB-24-2 PVRCC Renovation.pdf | ||
| ITB-24-2 PVRCC Renovation - Project Manual.pdf | ||
| ITB-24-2 PVRCC Renovation - Sample Contract.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECTION (PLAN / ELEVATION)
MEMBRANE ROOFING
STUCCO
CUT (SECTION)
CONCRETE
EARTH
RIGID INSULATION
BATT INSULATION
WOOD BLOCKING
SPRAYED INSULATION
1HR FIRE RATED WALL ASSEMBLY
CMU
EXISTING WALL TO REMAIN
NEW WALL
BUILDING SECTION SYMBOL WALL SECTION SYMBOL
ELEVATION SYMBOLS REFERENCE KEYNOTE SYMBOL
A101
SIM
DETAIL SYMBOL
A101
SIM
SIMILAR, TYPICAL, OR MIRRORED
REFERENCE
SIMILAR, TYPICAL, OR MIRRORED
REFERENCE
SPOT DIMENSIONS
HEIGHT INDICATION (ABOVE RESPECTIVE
GROUND FLOOR LEVEL ELEVATION)
0'-0"
WINDOW/ DOOR TAG SYMBOLS
WALL TAG SYMBOL
PARTITION TYPE
1,234 SF
ROOM NUMBER
AREA
OCCUPANT LOAD
ROOM TAG SYMBOL
Room name
CH= 1'-0"
CEILING TAG SYMBOL
HEIGHT INDICATION (ABOVE RESPECTIVE
FLOOR LEVEL ELEVATION)
DETAIL
SHEET NUMBER
SHEET NUMBER
BUILDING SECTION
NUMBER
SHEET NUMBER
DETAIL
SHEET NUMBER
BUILDING SECTION NUMBER
SHEET NUMBER
ELEVATION NUMBER
A1 A101
E3/A504
DETAIL / SHEET #E
/A
A101
SIM
A101
SIM
A101
SIM
A101
1t
101 DOOR TAG
1t
WINDOW TAG
KEYED NOTE - REFERS
TO KEYNOTE LEGEND
ON EACH SHEET
PROJECT
LOCATION
S M
A
IN
S T
ST. MARY'S PL E. CHISUM ST. W. CHISUM ST.
U S
H W
Y
E. WILDY ST.
E. HOBBS ST.
S R
IC
H
A R
D S
O N
A V
E
S G
R A
N D
A V
E
ADDITIVE ALTERNATE #1:
• NEW BACK-UP DIESEL GENERATOR AND ASSOCIATED PAD, CONDUIT AND FEEDERS.
REFER TO ELECTRICAL.
ADDITIVE ALTERNATE #2:
• NEW REDUNDANT HVAC SYSTEM (AND ASSOCIATED STRUCTURAL BRACING) SERVING
DISPATCH AREA. REFER TO MECHANICAL AND STRUCTURAL.
ADDITIVE ALTERNATE #3:
• EXTERIOR IMPROVEMENTS TO SECURE PARKING AREA TO INCLUDE:
1. DEMOLITION OF EXISTING SITE CONDITIONS. REF. ARCHITECTURAL AND CIVIL.
2. NEW CONCRETE AND ASPHALT PAVING. REFER TO ARCHITECTURAL AND CIVIL.
3. PARKING LOT STRIPING. REFER TO ARCHITECTURAL AND CIVIL.
4. NEW LANDSCAPING. REFER TO LANDSCAPING AND IRRIGATION PLAN.
5. NEW CMU SITE WALL AT GENERATOR LOCATION.
6. NEW SITE FURNISHINGS.
ADDITIVE ALTERNATE #4:
• CHEMICAL FIRE SUPPRESSION SYSTEM FOR NEW I.T. ROOM. REFER TO PLUMBING.
R E
G
I S
T ERED A RCH
I T
E C
T
S T
A T
E
OF NEW
MEX
IC
ORICHARD HAAS
NO. 2530
This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.
DESERT PEAK ARCHITECTS P.C.
311 N MAIN STREET
LAS CRUCES
NEW MEXICO 88001
P. 575.528.0022
SHEET NO.
SHEET TITLE
IS
S
U E
D
C
B
A
1 3 4 52
PROJECT NO.
550-01
G001
COVER SHEET
/0
/2
P E
C O
S V
A L
L E
Y R
E G
IO
N
A L
C O
M M
U N
IC
A
T
IO
N S
C E
N T
E R
R E
N O
V A
T
IO
N S
T M
A R
Y 'S
P L
R
O S
W E
L L
N M
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
07/06/2023
DRAWING INDEXOWNER:
CHAVES COUNTY
CONTACT:
MAC ROGERS
PUBLIC SERVICES DIRECTOR
575-624-6611
CONSULTANTS:
STRUCTURAL ENGINEERING
LILLY ENGINEERING INC.
5160 CALLE BELLISIMA,
LAS CRUCES, NM 88011
P: (575) 521-0006
CONTACT: DAN LILLEY
ARCHITECT:
DESERT PEAK ARCHITECTS, INC
311 NORTH MAIN STREET
LAS CRUCES, NM 88005
P. (575) 528 - 0021
CONTACT: RUBEN CONTRERAS
MECHANICAL, ELECTRICAL, PLUMBING
VICINITY MAP
PECOS VALLEY REGIONAL
COMMUNICATIONS CENTER
RENOVATION
TESTUDO ENGINEERING
7007 WYOMING BLVD NE SUITE E,
ALBUQUERQUE, NM 87109
(505) 554 - 1282
CONTACT: WAYNE YEVOLI
1 ST. MARY'S PL.
ROSWELL, NM 88203
CIVIL ENGINEERING
SOUDER MILLER & ASSOCIATES
3500 SEDONA HILLS PKWY,
LAS CRUCES, NM 88001
P: (575) 647-0799
CONTACT: MICHAEL JOHNSON
MATERIAL LEGEND
SYMBOL LEGEND
2015 INTERNATIONAL BUILDING CODE
2015 INTERNATIONAL EXISTING BUILDING CODE
2015 NM COMMERCIAL CODES
2021 UNIFORM PLUMBING CODE
2021 NM PLUMBING CODE
2021 UNIFORM MECHANICAL CODE
2021 NM MECHANICAL CODE
2017 NM ELECTRICAL CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE
DESIGN CODES
COVER G-SHEETS
G001 COVER SHEET
G002 CODE REVIEW DATA
G005 ACCESSIBLE MOUNTING HEIGHTS
ARCHITECTURAL
A100 ARCHITECTURAL SITE PLAN
A101 OVERALL FLOOR PLAN
A102 ENLARGED FLOOR PLAN AND SITE PLAN
A111 FIRST FLOOR DIMENSIONED PLAN & WALL PARTITION TYPES
A121 FIRST FLOOR REFLECTED CEILING PLAN
A131 ROOF PLAN
A201 EXTERIOR ELEVATIONS
A301 BUILDING SECTIONS AND WALL SECTIONS
A401 ENLARGED FLOOR PLANS & INTERIOR ELEVATIONS
A510 DETAILS
A520 INTERIOR DETAILS
A602 DOOR AND WINDOW SCHEDULE
A651 INTERIOR FINISH PLANS
DEMOLITION
D100 DEMOLITION PLAN
ELECTRICAL
E001 ELECTRICAL GENERAL NOTES, LEGEND & FIXTURE SCHEDULE
E101 LIGHTINGNEW WORK PLAN
E201 POWER NEW WORK PLAN
E301 MECHANICAL EQUIPMENT CONNECTIONNEW WORK PLAN
E401 FIRE ALARMNEW WORK PLAN
E600 RISER DIAGRAM
E601 PANEL SCHEDULES
ED101 DEMOLITION LIGHTING AND POWER PLAN
ES101 ELECTRICAL SITE PLAN
MECHANICAL
M101 MECHANICALHVAC FLOOR PLAN
M101A MECHANICAL HVAC FLOOR PLAN (ALT)
MP501 MECHANICAL DETAILS
MP601 MECHANIAL AND PLUMBING GENERAL
NOTES, SCHEDULES AND LEGENDS
PLUMBING
P101 PLUMBING FLOOR PLAN, RISER DIAGRAM AND
CLEAN AGENT CONTROL SCHEMATIC
ALTERNATE SCHEDULE
LANDSCAPE
LA101 LANDSCAPING AND IRRIGATION PLAN
SPECIAL SYSTEMS
CURREY ADKINS
100 S ALTO MESA DR, EL PASO, TX 79912
(915) 833-6604
CONTACT: ROBERT FARAH
CIVIL
C100 GENERAL NOTES
C201 DEMOLITION PLAN
C300 GRADING PLAN
C400 UTILITY PLAN
C600 PROJECT DETAILS
C700 SIGNAGE AND STRIPING PLAN
C900 EROSION CONTROL PLAN - PRE CONSTRUCTION
C901 EROSION CONTROL PLAN - DURING CONSTRUCTION
DS-1 DRAINAGE SHEET
M a rk
D a te
D e s c ri p ti o n
STRUCTURAL
S001 GENERAL STRUCTURAL NOTES AND STRUCTURAL BRACING PLAN
SPECIAL SYSTEMS
TS01 COVER
TS100 SPECIAL SYSTEMS LEGEND AND KEY PLAN
TS101 SPECIAL SYSTEMS SITE PLAN
TS102 SPECIAL SYSTEMS PLAN AND REFLECTED CEILING PLAN
TS201 SPECIAL SYSTEMS DIAGRAMS AND DETAILS
TS301 SURVEILANCE DETAILS
TS401 SPECIAL SYSTEMS DETAILS
TS402 SPECIAL SYSTEMS DETAILS AND BACKBONE RISER DIAGRAM
TS403 SPECIAL SYSTEMS EQUIPMENT LAYOUTS
TS404 RACK ELEVATION LAYOUT
PROJECT TYPE:
LEVEL 2 ALTERATIONS TO EXISTING BUILDING.
Per IBC 2015 - 304.1
OCCUPANCY CLASSIFICATION - GROUP B
EXISTING CONSTRUCTION TYPE - IIIB
SPRINKLERED: YES
TOTAL EXISTING BUILDING GROSS BUILDING AREA: 72,908 SF (UNCHANGED)
TOTAL NEW WORK GFA: 3,217 SF
MEANS OF EGRESS - Per IBC 2015 CHAPTER 10
MINIMUM REQUIRED EGRESS
STAIRS 0.3"/ OCCUPANT
EXITS 0.2"/ OCCUPANT
EGRESS DOORS: 32" MINIMUM CLEAR
EXIT TRAVEL DISTANCE REQUIREMENTS - Per IBC 2015 1017.2
OCCUPANCY CLASSIFICATION B (SPRINKLERED) - 300'-0" MAX DISTANCE
SEPARATION REQUIREMENTS - (IBC 2015)
Per IBC 2015 TABLE 508.4 REQUIRED SEPARATION OF OCCUPANCIES
NO SEPARATION REQUIRED BETWEEN B AND B OCCUPANCIES
Per IBC 2015 1020.1 CORRIDOR < 30 OCC. 0 FIRE RESISTANT RATING
REQUIRED
Per IBC 2015 1020.1 CORRIDOR > 30 OCC. (SPRINKLERED) 0 FIRE RESISTANT
RATING REQUIRED
1 HR. RATED ASSEMBLY PROVIDED AT CORRIDOR.
OCCUPANT LOAD FACTOR - Per IBC 2015 1004.1.2
BUSINESS AREA (B) - 100 GSF/OCCUPANT
OCCUPANT LOAD (WORK AREA): 3,217 SF/100 = 32.17 = 33 OCCUPANTS
EXIT CORRDOR WIDTH REQUIREMENTS - Per IBC 2015 1020.2
OCCUPANCY: "WITH AN OCCUPANT LOAD OF LESS THAN 50"
REQUIRED: 36" CLEAR WIDTH PROVIDED: 60" CLEAR WIDTH
CODE REVIEW
PROJECT INFORMATION
• ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE PLANE:
- TYPE III B (SPRINKLERED): 75'
ACTUAL BUILDING HEIGHT IN FEET ABOVE GRADE PLANE: 53'-8" (UNCHANGED)
• ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE:
-TYPE III B (SPRINKLERED): 4
ACTUAL NUMBER OF STORIES ABOVE GRADE PLANE: 1 (UNCHANGED)
• ALLOWABLE AREA IN SQUARE FEET
- TYPE III B (SPRINKLERED): 76,000 SF
ACTUAL AREA IN SQUARE FEET: 72,908 SF (UNCHANGED)
MAX EXIT TRAVEL DISTANCE: 49'-0"
GENERAL BUILDING HEIGHTS AND AREAS - Per IBC 2015 - TABLES 504.3, 504.4, 506.2
NUMBER OF EXITS AND EXIT ACCESS DOORWAYS - Per IBC 2015 1006.2.1
TWO EXITS OR EXIT ACCESS DOORWAYS FRAM ANY SPACE SHALL BE
PROVIDED WHERE THE DESIGN OCCUPANT LOAD OR COMMON PATH OF
EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES LISTED IN TABLE 1006.2.1
PER TABLE 1006.2.1 - 2 EXITS SHALL BE REQUIRED FOR BUSINESS OCCUPANCY
EXCEEDING 49 OCCUPANTS
100' MAX COMMON PATH OF EGRESS TRAVEL FOR B OCCUPANCIES WITH
ONE EXIT OR EXIT ACCESS DOORWAY
PLUMBING REQUIREMENTS:
USE REQUIRED EXISTING TO REMAIN
47 WOMEN
46 MEN
TOTAL OCCUPANT LOAD (93) =
(IBC 2015 CHAPTER 29: TABLE 2902.1)
W.C. LAV. W.C. LAV.
MEN 2 2 3 3
WOMEN 2 2 2 2
DRINKING FOUNTAINS REQUIRED EXISTING TO REMAIN
OCCUPANTS (93) 1 1
SERVICE SINK REQUIRED EXISTING TO REMAIN
1 MULTIPLE SERVICE
SINKS AVAILABLE IN OTHER
PORTIONS OF THE BUILDING.
OCCUPANCY: B (BUSINESS)
WING D PLUMBING REQUIREMENTS:
5'-1" CLEAR
NO WORK THIS AREA
BUSINESS AREA: 5,947 SF
OCC: 59.47
305 SF
BUSINESS AREA
OCC-3.05
3035 SF
BUSINESS AREA
OCC-30.35
A8
B
D
C
MAX TRAVEL
DISTANCE TO
EXIT: 49'-0"
MAX TRAVEL
DISTANCE TO
EXIT: 72'-0"
36" CLEAR MIN.
M
IN
EGRESS LEGEND
A EXIT IDENTIFICATION MARKER
# TOTAL NUMBER OF OCCUPANTS
SERVED BY AN EXIT
MAX TRAVEL DISTANCE LINE
LOCATION OF EXIT SIGNAGE
MERCANTILE
1004 SF
OCC-16.73
FUNCTION OF SPACE
AREA OF SPACE
OCCUPANT LOAD OF
SPACE
EXIT CAPACITIES
MARK CLEAR WIDTH FACTOR CAPACITY ACTUAL USAGE
A 44" .2 220 8 B 64" .2 320 21 C 64" .2 320 21 D 64" .2 320 29
PROJECT
NORTH
R E
G
I S
T ERED A RCH
I T
E C
T
S T
A T
E
OF NEW
MEX
IC
ORICHARD HAAS
NO. 2530
This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.
DESERT PEAK ARCHITECTS P.C.
311 N MAIN STREET
LAS CRUCES
NEW MEXICO 88001
P. 575.528.0022
SHEET NO.
SHEET TITLE
IS
S
U E
D
C
B
A
1 3 4 52
PROJECT NO.
550-01
G002
CODE REVIEW DATA
/0
/2
P E
C O
S V
A L
L E
Y R
E G
IO
N
A L
C O
M M
U N
IC
A
T
IO
N S
C E
N T
E R
R E
N O
V A
T
IO
N S
T M
A R
Y 'S
P L
R
O S
W E
L L
N M
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
07/06/2023
1/8" = 1'-0"G002
B3 EXITING DIAGRAM - WING D
M a rk
D a te
D e s c ri p ti o n
5' -0
6' -6
1' -6
4"
2' -0
3"
10"
5' -0
7' -2
4"
2' -0
3"
10"
4" 4"
1' -6
1'-0" 1'-0"
2' -6
2' -6
1"R
(TYP.)
2"∅ STD WT GALV. STL PIPE POST
FINISH GRADE OR PAVING
REF. SITE PLAN
1'-0"∅ CONC. FTG
SLOPE TOP TO DRAIN
3 #10x3/4" SELF TAPPING VANDAL
PROOF SCREWS
INTERNATIONAL SYMBOL OF
ACCESSIBILITY AND GRAPHICS
PAINTED W. WHITE REFLECTORIZED
PAINT - GRAPHICS AS FOLLOWS:
"RESERVED FOR HANDICAPPED
"VAN ACCESSIBLE" WHERE REQUIRED
16 GA. GALV STL SIGN PAINTED
W/ BLUE REFLECTORIZED PAINT
INCLUDING FASTENERS
1"R
(TYP.)
4"∅ STD WT GALV. STL PIPE POST
VAN ACCESSIBLE
HANDICAPPED
FOR
RESERVED
HANDICAPPED
FOR
RESERVED
Max.
10"
M in
M a x
M a x
10" - 24"
M a x
CLEAR TURNING
CIRCLE
60" DIAMETER
CLEAR
FLOOR
AREA
CLEAR
FLOOR
AREA
30"
12" 36" 12"
T-SHAPED TURNING
SPACE
URINALS
LAVATORIES
WATER CLOSETS
ALIGN
CENTER ON
FIXTURE
WRAP HOT & WASTE
WATER PIPING WITH
INSULATION
ADULT
HC
ADULT
R E
F L E
C T
IV
S
U R
F A
C
EQ EQ
IN
K R
IM
L
E V
E L
EQ EQ
CLEAR
30"
T O
B O
T O
F
17"-20"
T O
S
IN
K R
IM
8"
11"
17"-25"
T O
S P
O U
T
CLR MIN TYP
30"
EQ EQ
T O
S P
O U
T
M A
X T
O A
IR
O
U T
L E
T
INSTALL AS LOW AS
POSSIBLE; PREFERED
MOUNTING TO HAVE
BOTTOM OF MIRROR AT
SINK RIM LEVEL
EHD SD
MI36
PD
DF
DF
19" MAX
M
IN
48" MIN.
1 22
T O
S P
O U
T
M A
X T
O T
O P
O F
L E
V E
R
FLUSH
CONTROL
AT OPEN
SIDE
T O
R
IM
M
IN
M A
X
7"-9" 13"
12" MAX
42"
40"
-1
/2
M
IN
M
IN
M A
X
36"
6" MAX
18"
M A
X
CLEAR
30"
T O
T O
P O
F C
O N
T R
O L
S
M A
X
EQ EQ
TD
SND
GB42
G B
GB36
TD
GB42
G B
GB36
M
IN
MIN.
5'-0"
1'-6" 3'-0" 6"
16" MIN. - 18" MAX.
M
IN
CLEAR FLOOR
SPACE
3 4
F R
O M
F L O
R
M
A X
BABY CHANGING STATION
T O
W O
R K
U R
F A
W
H E
N I N
P
N
P
S
IT
IO
N
ABBREVIATION LEGEND
RS: ROOM SIGNAGE
RH: ROBE HOOK
SR: SHOWER CURTAIN ROD
TB: TOWEL BAR
SK: SINK
MI: MIRROR
TP: TOILET PAPER DISPENSER
SND: SANITARY NAPKIN DISPOSAL
GB42: GRAB BAR- 42" LONG
GB36: GRAB BAR- 36" LONG
GB18: VERTICAL GRAB BAR - 18" LONG
EHD: ELECTRIC HAND DRYER
SD: SOAP DISPENSER
PD: PAPER TOWEL DISPENSER
DF: DRINKING FOUNTAIN
FE: FIRE EXTINGUISHER
WC: WATER CLOSET
UR: URINAL
T O
C E
N T
E R
L
IN
E O
F E
X T
IN
G
U
IS
H E
R B
R A
C K
E T
M
A X
FIRE EXTINGUISHER
CABINET BODY
FIRE EXTINGUISHER
CABINET WALL TRIM
5/8" GYPSUM WALL BOARD
AS CHEDULED.
PROVIDE FIRE RATING AS
SCHEDULED
METAL STUD
METAL STUD AS CHEDULED.
PROVIDE FIRE RATING AS
SCHEDULED
5/8" GYPSUM WALL BOARD
BUILDING SIGNAGE SHALL
COMPLY WITH SECTION 703 OF
THE ADAAG DESIGN GUIDELINES
LIBRARY
C H
A R
A C
T E
R H
E
IG
H T
/8
M
IN
M A
X
RAISED CHARACTERS SHALL BE 1/32" MIN. ABOVE THEIR
BACKGROUND,SHALL BE UPPERCASE, SHALL BE SANS
SERIF OF STANDARD FORMAT FONT. CHARACTER
SHALL BE SELECTED FROM FONTS WHERE THE WIDTH
OF THE UPPERCASE LETTER "O" IS 55% MIN. AND 110%
MAX. OF THE HEIGHT OF THE UPPERCASE LETTER "I".
F R
O M
R A
IS
E
D L
E T
T E
R S
/8
M
IN
S
P A
C
IN
G
F R
O M
R A
IS
E
D B
O R
D E
R S
/8
M
IN
S
P A
C
IN
G
T O
B A
S E
L
IN
E O
F T
H E
L O
W E
S T
T A
C T
IL
E
C H
A R
A C
T E
R
M
IN
FINISHED FLOOR
T O
B A
S E
L
IN
E O
F H
IG
H
E S
T T
A C
T
IL
E C
H A
R A
C T
E R
M
A X
BRAILLE SHALL BE CONTRACTED
(GRADE 2) AND SHALL COMPLY WITH
SECTIONS 703.3 AND SECTIONS 703.4 OF
THE ADAAG DESIGN GUIDELINES
REFUGE
AREA OF
AREA OF
REFUGE
M
IN
M A
X
ALL DOOR HARDWARE TO COMPLY WITH
SECTION 1010.1.9
REGARDING: HARDWARE, HARDWARE HEIGHT, LOCKS
AND LATCHES, BOLT LOCKS, UNLATCHING,
CONTROLLED EGRESS DOORS, DELAYED EGRESS,
SENSOR RELEASE OF ELECTRICALLY LOCKED EGRESS
DOORS, ELECTROMAGNETIC LOCKED EGRESS DOORS,
LOCKING ARRANGEMENTS IN CORRECTIONAL
FACILITIES AND STAIRWAY DOORS
1/2" = 1'-0"G005
B4 TYPICAL ADA MOUNTING HEIGHTS (ADULT)
3/8" = 1'-0"G005
A5 01 FLOOR AREA DIAGRAMS
1/2" = 1'-0"G005
B1 TYPICAL ADA MOUNTING HEIGHTS (ADULT)
1/2" = 1'-0"G005
A1 TYPICAL ADA MOUNTING HEIGHTS (ADULT)
3/4" = 1'-0"G005
D2 FEC MOUNTING DETAIL
1 1/2" = 1'-0"G005
C2 FIRE EXTINGUISHER CABINET DETAIL
R E
G
I S
T ERED A RCH
I T
E C
T
S T
A T
E
OF NEW
MEX
IC
ORICHARD HAAS
NO. 2530
This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.
DESERT PEAK ARCHITECTS P.C.
311 N MAIN STREET
LAS CRUCES
NEW MEXICO 88001
P. 575.528.0022
SHEET NO.
SHEET TITLE
IS
S
U E
D
C
B
A
1 3 4 52
PROJECT NO.
550-01
G005
ACCESSIBLE
MOUNTING HEIGHTS
/0
/2
P E
C O
S V
A L
L E
Y R
E G
IO
N
A L
C O
M M
U N
IC
A
T
IO
N S
C E
N T
E R
R E
N O
V A
T
IO
N S
T M
A R
Y 'S
P L
R
O S
W E
L L
N M
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
07/06/2023
1/2" = 1'-0"G005
C3 BUILDING SIGNAGE
1/2" = 1'-0"G005
C4 TACTILE SIGN
1/2" = 1'-0"G005
D3 HARDWARE
1/2" = 1'-0"G005
C1 ACCESSIBILITY SIGN
M a rk
D a te
D e s c ri p ti
AS SHOWN
C100Sheet:
Horiz:Scale:
Project No:
Vert:
Date:
C hk
'd By
D es cr ip tio n
D at e R ev
THIS DRAWING IS INCOMPLETE
AND NOT TO BE USED FOR
CONSTRUCTION UNLESS IT IS
STAMPED, SIGNED AND DATED
© Copyright 2020 Souder, Miller & Associates - All Rights Reserved
Designed CheckedDrawn
PE
C
O S
VA
LL
EY
R
EG
IO
N
AL
C O
M M
U N
IC
AT
IO
N
S C
EN
TE
R R
EN
O
VA
TI
O N
R O
SW
EL
L, N
EW
M
EX
IC
O
MJ MJ
March 2023
9B31722
D
ES
ER
T
PE
AK
A R
C H
IT
EC
TS
LA
S C
R U
C
ES
, N
EW
M
EX
IC
O
P:\9-DPA Pecos Valley RCC Renovation (9B31722)\CAD\Civil\Construction Drawings\9B31722 - GENERAL NOTES.dwg 3/2/2023 3:46 PM AXA
NOTE: THESE DRAWINGS ARE TO BE USED TO
ACQUIRE PERMITS FROM JURISDICTIONAL
GOVERNMENTAL AGENCIES AND ARE NOT TO BE
RELIED UPON FOR PROJECT BIDDING PURPOSES
OR FOR CONSTRUCTION UNTIL APPLICABLE
CONSTRUCTION PERMITS ARE ISSUED
SM
ASO
U D
ER
, M
IL
LE
R
A
SS
O C
IA
TE
S E ng in ee ri ng
E nv ir on m en ta l
G eo m at ic s
Se rv in g th e
So ut hw es t & R oc ky
M ou nt ai ns w w w .s ou de rm ille r.c om
Ph on e (5
) 6
-0
F ax
(5
) 6
-0
S ed on a
H ill s P kw y.
La s C ru ce s, N M
/2
2/
In iti al
S ub m itt al
AX
A M
J
3/2/2023
MICHAEL D. JOHNSON
NEW
MEXICO
REGISTERED PROFESSIONAL ENG
INE
ER
G
EN
ER
AL
N
O
TE
S
1. THE GENERAL CONTRACTOR TO BECOME FAMILIAR WITH AND APPLY THE ADA MINIMAL
REQUIREMENTS AND REPORT TO THE ARCHITECT/ENGINEER ANY DISCREPANCIES
BEFORE CONSTRUCTION.
2. ACCESSIBLE ROUTES ON AN ACCESSIBLE SITE AND FOR NEW SITE IMPROVEMENTS
SHALL BE PROVIDED TO SERVE ALL ACCESSIBLE SPACES OR ELEMENTS.
3. THE MINIMAL CLEAR WIDTH OF AN ACCESSIBLE ROUTE PER CODE IS 36".
4. EACH ACCESSIBLE PARKING SPACE IS TO BE A MINIMUM OF 14' WIDE, CONSISTING OF A
5' WIDE ACCESS AISLE AND A 9' WIDE PARKING SPACE, EACH VAN ACCESSIBLE PARKING
SPACE IS TO BE A MINIMUM OF 16' WIDE, CONSISTING OF A 8' WIDE ACCESS AISLE AND
A 8' WIDE PARKING SPACE. THE ACCESS AISLE SHALL BE ON THE PASSENGER'S SIDE OF
THE VAN ACCESSIBLE SPACE.
5. ACCESSIBLE PARKING SPACES ARE TO BE LOCATED AS CLOSE TO THE BUILDING
ENTRANCE AS POSSIBLE AND SHALL BE IDENTIFIES WITH A SIGN.
6. RAMPS MUST NOT EXTEND OUT FROM THE CURB INTO THE ACCESS AISLE ANY
ACCESSIBLE PARKING SPACE.
7. TWO PARKING SPACES MAY SHARE THE SAME ACCESS AISLE.
8. ALL ADA PARKING SPACES SHALL BE STRIPED USING 4" WIDE DOUBLE LAYER OF
FEDERAL BLUE PAINT, UNLESS OTHERWISE NOTED.
9. ACCESSIBLE PARKING SPACES AND ACCESS AISLES SHALL NOT EXCEED A SLOPE OF
1:50 (2.0%) IN ANY DIRECTION.
10. EACH ACCESSIBLE PARKING SPACE SHALL HAVE AN IDENTIFICATION SIGN (SEE TYPICAL
H.C. PARKING SYMBOL DETAIL ON SHEET C-600).
11. AN ACCESSIBLE ROUTE WITH A RUNNING SLOPE GREATER THAN 1:20 (5.0%) IS A RAMP
AND SHALL COMPLY WITH THE RAMP REQUIREMENTS.
12. AN ACCESSIBLE ROUTE MAY CROSS OPEN PAVEMENT OR CONDITIONS. THE RUNNING
SLOPE OF AN ACCESSIBLE ROUTE ACROSS OPEN PAVEMENT MUST NOT EXCEED 1:20
(5.0%), WITH A CROSS SLOPE NOT EXCEEDING 1:50 (2.0%). SLOPES EXCEEDING 1:20
(5.0%), BUT LESS THAN 1:12 (8.33%) , CONSTITUTE RAMPS AND MUST CONFORM TO THE
REQUIREMENTS OF RAMP DESIGN (HANDRAILS, CURBS, LANDINGS, RISE AND RUN
LIMITS, ETC.) AS DETAILED ON THE CIVIL PLANS. NO RAMP SHALL HAVE A RUNNING
SLOPE EXCEEDING 1:12 (8.33%), NOR HAVE A CROSS SLOPE EXCEEDING 1:50 (2.0%).
13. THE GENERAL CONTRACTOR/CONTRACTOR SHALL MEASURE THE SUBGRADE AND
ACROSS FORMS PRIOR TO INSTALLATION OF ASPHALT OR CONCRETE IMPROVEMENTS
TO ASSURE THE IMPROVEMENTS WILL MEET THESE MINIMAL ADA REQUIREMENTS. ANY
DISCREPANCIES SHALL BE REPORTED TO THE CIVIL ENGINEER PRIOR TO INSTALLATION
OF THE IMPROVEMENTS.
14. A CURB RAMP SHALL BE PROVIDED WHEREVER AN ACCESSIBLE ROUTE CROSSES A
CURB.
15. CURBS RAMPS HAVE A MAXIMUM SLOPE OF 1:12 (8.33%) AND DO NOT REQUIRE
HANDRAILS.
16. IF A CURB RAMP IS LOCATED WHERE PEDESTRIANS MUST WALK ACCROSS THE RAMP,
OR WHERE IS IS NOT PROTECTED BY HANDRAILS, IT SHALL HAVE FLARED SIDES; THE
MAXIMUM SLOPE OF THE FLARE SHALL BE 1:12 (8.33%).
AMERICANS WITH DISABILITIES ACT
(ADA) MINIMAL REQUIREMENTS:
1. THESE SPECIFICATIONS APPLY TO THE PROJECT SITE WORK AREA INDICATED WITHIN
THESE PLANS ONLY.
2. THE ENGINEER AND OWNER ARE NOT RESPONSIBLE FOR PROJECT SITE SAFETY OR
COMPLIANCE TO OSHA REGULATIONS.
3. THE CONTRACTOR AND/OR HIS SUBCONTRACTORS SHALL, AT THE TIME OF
CONSTRUCTION AND/OR INSTALLATION, HAVE ALL APPROPRIATE STATE LICENSES TO
PERFORM THESE WORK ACTIVITIES. CONSTRUCTION AND/OR INSTALLATION WORK
PERFORMED BY UNLICENSED CONTRACTORS AND/OR SUBCONTRACTORS SHALL NOT
BE PAID FOR BY THE OWNER.
4. SHOULD CONFLICTING INFORMATION OR INTERFERENCE PROBLEMS APPEAR WITHIN
THESE CONSTRUCTION DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL
BRING THAT INFORMATION TO THE ATTENTION OF THE ENGINEER IMMEDIATELY PRIOR
TO INSTALLATION OR CONSTRUCTION. FAILURE TO COMPLY SHALL NOT BE THE BASIS
FOR EXTRA PAYMENT TO THE CONTRACTOR.
5. WHERE TWO OF MORE SPECIFICATIONS, DETAILS OR PLANS ARE IN CONFLICT, THE
MORE RESTRICTIVE SHALL APPLY.
6. THESE PLANS AND SPECIFICATIONS DO NOT SHOW EVERY CONSTRUCTION DETAIL,
CONSTRUCTION ITEMS, FITTINGS, FIXTURES, MATERIAL TYPES, ETC. THAT ARE
REQUIRED TO COMPLETE THE SPECIFIED CONSTRUCTION ACTIVATES. IT IS ASSUMED
THAT THE CONTRACTOR HAS SUFFICIENT EXPERIENCE AND KNOWLEDGE OF ALL
APPLICABLE CONSTRUCTION AND BUILDING CODES TO CORRECTLY COMPLETE THE
INSTALLATION/CONSTRUCTION OF ALL WORK UNDERTAKEN
7. EXISTING UTILITIES SHOWN WITHIN THESE DRAWINGS ARE FOR REFERENCE ONLY.
THE CONTRACTOR SHALL CONTACT APPLICABLE UTILITY COMPANIES FOR EXACT
FIELD VERIFIED LOCATIONS PRIOR TO THE START OF CONSTRUCTION.
8. AT A MINIMUM, ALL EARTHWORK, CONCRETE CONSTRUCTION AND ASPHALT
PAVEMENT CONSTRUCTION SHALL MEET THE REQUIREMENTS OF THE NEW MEXICO
DEPARTMENT OF TRANSPORTATION “STANDARD SPECIFICATIONS FOR HIGHWAY AND
BRIDGE CONSTRUCTION”, LATEST EDITION AND/OR THE CITY OF ROSWELL “TECHNICAL
STANDARDS”, LATEST EDITION.
9. THE CONTRACTOR SHALL KEEP AN ACCURATE AND UPDATED SET OF AS-BUILT
CONSTRUCTION DRAWINGS AND SHALL MAKE THESE DRAWINGS AVAILABLE FOR
REVIEW BY THE OWNER OR ENGINEER UPON REQUEST. WITHIN 24 HOURS OF THE
CONTRACTOR NOTIFYING THE OWNER THAT CONSTRUCTION IS COMPLETE, THE
CONTRACTOR SHALL SUBMIT FINAL AS-BUILT DRAWINGS TO THE ENGINEER.
10. THE CONTRACTOR WILL BE RESPONSIBLE OF THE REPAIR AND/OR REPLACEMENT OF
ANY DAMAGE DETERMINED TO BE CAUSED BY THE CONSTRUCTION OF THIS PROJECT
TO EXISTING UTILITIES, INCLUDING CONDUIT,WIRING, EQUIPMENT AND FIBER-OPTICS.
1. ALL EARTHWORK SHALL MEET THE REQUIREMENTS ON THE CITY OF ROSWELL
“PUBLIC WORKS SPECIFICATIONS.”
2. PRIOR TO BEGINNING EARTHWORK OPERATIONS ALL NECESSARY CLEARING AND
GRUBBING IN THAT AREA SHALL HAVE BEEN PERFORMED. THE PROJECT AREA SHALL
BE CLEARED OF VEGETATION GROWTH, STUMPS, ROOTS, TRASH, DEBRIS, ROCKS
OVER 3" IN DIAMETER, AND OTHER OBJECTIONABLE MATERIALS. DISPOSAL OF THESE
MATERIALS SHALL ARE THE RESPONSIBILITY OF THE CONTRACTOR AND ALL
DISPOSAL ACTIVITIES SHALL BE IN CONFORMANCE TO ALL LOCAL, STATE AND
FEDERAL REGULATIONS.
3. ALL CUT AREAS SHALL BE REMOVED TO SUBGRADE ELEVATION FOR THE FULL WIDTH
OF THE PROPOSED CONSTRUCTION. THE 6" LAYER OF NATIVE SUBGRADE SHALL BE
SCARIFIED AND BROUGHT TO A MOISTURE CONTENT OF 2% ± OF OPTIMUM AND
COMPACTED TO NOT LESS THAN 95% OF MAXIMUM DENSITY AS DETERMINED BY
ASTM D1557.
4. FILL MATERIALS SHALL BE PLACED IN 12" LOOSE LIFTS NOT TO EXCEED 9” IN DEPTH
WHEN COMPACTED. FILL MATERIALS SHALL BE FREE OF ANY ORGANIC OR
DELETERIOUS SUBSTANCES. THE FILL MATERIAL UNIFIED SOILS CLASSIFICATION
SYSTEM CLASSIFIED MATERIAL TYPE GW, GP, SW, SP, GM, SM, OR GC AND SHALL
MEET THE FOLLOWING GRADATION:
SIEVE SIZE % PASSING
3" 100% 3/4" 70 - 100% #4 50 - 100% #200 0 - 20%
PLASTIC INDEX 15 MAXIMUM
WHERE FILL IS TO BE PLACED ON SLOPES STEEPER THAN ONE (1) VERTICAL TO FIVE (5)
HORIZONTAL, THE GROUND SURFACE SHALL BE BENCHED TO PROVIDE A FIRM BOND
WITH THE FILL. NO FILL MATERIAL SHALL BE PLACED, SPREAD OR ROLLED WHILE IT IS
FROZEN OR THAWING, OR DURING UNFAVORABLE WEATHER CONDITIONS.
5. CONTRACTOR RESPONSIBLE FOR ALL SITE MATERIAL TESTING. TEST REPORTS TO BE
SUBMITTED TO THE ENGINEER AND OWNER TO BE INCLUDED IN FINAL
DOCUMENTATION.
1. ALL CONCRETE SHALL BE PLACED IN A SINGLE CONTINUOUS OPERATION SO AS TO
PRODUCE A MONOLITHIC SLAB/FOUNDATION BETWEEN CONSTRUCTION JOINTS.
2. CONCRETE SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 3,000 PSI
UNLESS OTHERWISE NOTED. CEMENT SHALL CONFORM TO ASTM C150, TYPE I, II, OR
III. CONCRETE AGGREGATE SHALL CONFORM TO ASTM C33. CONCRETE SHALL BE
PROTECTED FROM LOSS OF MOISTURE FOR A MINIMUM OF 7 DAYS.
3. ALL REINFORCING SHALL CONFORM TO ASTM A617, GRADE 40, AND ACI 318-89 UNLESS
OTHERWISE NOTED.
1. CITY OF ROSWELL - PUBLIC WORKS DEPARTMENT ( RPW ) CONTACT NUMBER:
(575)-624-6730.
2. RPW SHALL BE NOTIFIED 72 HOURS PRIOR TO COMMENCING ANY WORK IN THE PUBLIC
RIGHT OF WAY. ALL INSTALLATIONS REQUIRE A VISUAL INSPECTION AS WELL AS
MATERIALS TESTING.
3. PAVEMENTS CUTS MUST BE A STRAIGHT LINE SAW CUT AND EXTEND FROM EXISTING
JOINT TO JOINT TO THE EXTENTS POSSIBLE.
4. ROADWAY SECTION SHALL MEET CURRENT CITY STANDARDS FOR DEPTH OR MATCH
EXIST. DEPTH, WHICHEVER IS THICKER.
5. TRAFFIC CONTROL PLAN MUST BE SUBMITTED TO RPW 72 HOURS PRIOR TO ANY ROAD
OR LANE CLOSURES.
6. IDENTIFY CONTRACTORS WHO WILL BE REFORMING WORK AND NOTE THEIR
CORRESPONDING LICENSE NUMBER.
7. IDENTIFY OWNERSHIP OF RIGHT-OF-WAY OR UTILITY LINES ON PLAN SET. SUCH AS
COUNTY, CITY OR PRIVATE R-O-W AND PRIVATE OR CITY UTILITY.
8. RECORD DRAWINGS OF WORK COMPLETED SHALL BE SUBMITTED TO RPW PRIOR TO
FINAL ACCEPTANCE OF THE INSTALLATIONS.
CITY OF ROSWELL PUBLIC WORKS
GENERAL CONSTRUCTION NOTES
COMMERCIAL UTILITY NOTES
1. THE DESIGN ENGINEER IS RESPONSIBLE FOR DETERMINING, RESEARCHING, CALLING
FOR DESIGN LOCATES NEW MEXICO ONE CALL (811), LOCATING EXISTING MAINS,
SERVICE LINE STUB-OUTS, AND OTHER FACILITIES AND SHOWING THEM
APPROPRIATELY ON THE UTILITY SHEET.
2. IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY FOR JOB SAFETY OR COMPLIANCE
WITH OSHA REGULATIONS.
3. SHOULD CONFLICTING INFORMATION OR INTERFERENCE PROBLEMS APPEAR IN THE
CONSTRUCTION DRAWINGS THE CONTRACTOR SHALL BRING THAT INFORMATION TO
THE ATTENTION OF THE ENGINEER IMMEDIATELY PRIOR TO INSTALLATION.
4. ALL CONSTRUCTION MATERIALS AND WORKMANSHIP DONE WITHIN THE PUBLIC
RIGHT-OF-WAY SHALL CONFORM TO THE CITY OF ROSWELL UTILITY STANDARDS
5. THE CONTRACTOR SHALL NOTIFY ALL UTILITY COMPANIES BEFORE COMMENCING
WORK AND SHALL BE RESPONSIBLE FOR COMPLYING WITH NEW MEXICO ONE-CALL
PROCEDURES. ANY DAMAGE TO EXISTING UTILITIES MUST BE IMMEDIATELY REPORTED
TO THE APPROPRIATE UTILITY COMPANY.
6. ROADWAY, RIGHT-OF-WAY AND SUB GRADE TO BE ESTABLISHED WITHIN 6 INCHES
(BOTH HORIZONTAL AND VERTICAL) OF FINAL LOCATION PRIOR TO INSTALLATION OF
ANY UTILITIES. GAS AND WATER UTILITIES TO BE PLACED WITHIN 6 INCHES OF FINAL
REQUIRED DEPTH AND LOCATION. THE CONTRACTORS WILL AT HIS EXPENSE
RELOCATE OR REPLACE UTILITIES, WHICH FAIL TO ADHERE TO THIS SPECIFICATION.
7. CURB CONTRACTOR TO STAMP, FRESH CONCRETE SIDEWALK WITH G. S. AND W.
DIRECTLY ABOVE GAS, SEWER, AND WATER STUB OUT LOCATIONS. A UTILITY
INSPECTOR SHALL BE PRESENT WHEN MARKING. FAILURE TO APPLY STAMPS SHALL BE
CAUSE FOR REJECTION OF THE IMPROVEMENT BY THE CITY.
8. IT WILL BE THE DEVELOPER’S RESPONSIBILITY TO SUBMIT THE “AS-BUILT” DRAWINGS,
AS COMPLETED BY THE CONTRACTOR AND TURNED IN TO THE CITY OF ROSWELL
PROJECT MANAGER, FOR APPROVAL AND ACCEPTANCE.
9. THE CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS OF THE IMPROVEMENTS TO
THE GAS SYSTEM BEFORE THOSE IMPROVEMENTS ARE TIED INTO THE EXISTING GAS
SYSTEM.
10. THE INSTALLATION OF MAINS/SERVICE LINES IN CITY OF ROSWELL AND NMDOT
RIGHT-OF-WAY REQUIRE A PERMIT FROM THAT GOVERNMENT ENTITY AND MUST BE
INITIATED BY THE PERSON REQUESTING THE SERVICE. THE OWNER IS RESPONSIBLE
FOR ANY FEES RELATED TO THE PERMIT PROCESS.
11. EXCESS FLOW VALVES (EFV) ARE REQUIRED PER MOST CURRENT CODE OF FEDERAL
REGULATION TITLE 49 PART 192.
12. TREES SHALL HAVE A 10’ MINIMUM CLEARANCE FROM ALL CITY OF ROSWELL UTILITIES
SERVICES.
13. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY WORK INCLUDING TRAFFIC
CONTROL, PAVEMENT CUTS, EXCAVATION, INSTALLATION AND RESTORATION.
14. ANY CHANGES FROM THE PREVIOUSLY APPROVED UTILITY PLAN REQUIRE A WRITTEN
REQUEST FROM THE ENGINEER OR AN AMENDMENT TO THE UTILITY PLAN.
FIRE DEPARTMENT GENERAL NOTES:
1. PRIVATE FIRE SERVICE UNDERGROUND MAINS AND APPURTENANCES SHALL BE
INSTALLED IN ACCORDANCE WITH THE MOST CURRENTLY ADOPTED INTERNATIONAL
FIRE CODE AND CITY OF ROSWELL UTILITY STANDARDS. ANY WORK SHALL REMAIN OPEN
AND UNCOVERED UNTIL INSPECTED BY CITY OF ROSWELL FIRE DEPARTMENT.
WHENEVER ANY INSTALLATION SUBJECT TO INSPECTION IS COVERED OR CONCEALED
WITHOUT HAVING FIRST BEEN INSPECTED, THE FIRE CODE OFFICIAL SHALL HAVE THE
AUTHORITY TO REQUIRE THAT SUCH WORK BE FULLY EXPOSED AND EASILY
ACCESSIBLE FOR INSPECTION.
2. A BLUE REFLECTIVE MAKER ( TYPE AND SIZE AS APPROVED BY CITY OF ROSWELL
FIRE OFFICIAL) SHALL BE INSTALLED ALONG THE AXIS OF A PERPENDICULAR LINE
DRAWN FROM THE CENTERLINE OF THE DRIVING AISLE TO THE FIRE HYDRANT.
REQUIRED AT EACH FIRE HYDRANT LOCATION.
1. SILT FENCE SHALL BE CONSTRUCTED BEFORE UPSLOPE LAND DISTURBANCE BEGINS.
2. WHERE POSSIBLE, SILT FENCE SHALL BE PLACED ON THE FLATTEST AREA AVAILABLE.
3. THE HEIGHT OF THE SILT FENCE SHALL BE A MINIMUM OF 16" ABOVE THE ORIGINAL
GROUND SURFACE.
4. THE SILT FENCE SHALL BE PLACED IN A TRENCH CUT A MINIMUM OF 6" DEEP. THE
TRENCH SHALL BE CUT WITH A TRENCHER, OR OTHER SUITABLE DEVICE WHICH WILL
INSURE ADEQUATE UNIFORM TRENCH DEPTH.
5. THE SILT FENCE SHALL BE PLACED WITH THE STAKES ON THE DOWNSLOPE SIDE OF
THE GEOTEXTILE AND SO THAT 8" OF THE CLOTH ARE BELOW THE GROUND SURFACE.
EXCESS MATERIAL SHALL LAY ON THE BOTTOM OF THE 6" DEEP TRENCH. THE TRENCH
SHALL BE BACKFILLED AND COMPACTED.
6. SEAMS BETWEEN SECTIONS OF THE SILT FENCE SHALL BE OVERLAPPED WITH THE END
STAKES OF EACH SECTION WRAPPED TOGETHER BEFORE DRIVING INTO THE GROUND.
7. SILT FENCE SHALL ALLOW RUNOFF TO PASS ONLY AS DIFFUSE FLOW THROUGH THE
GEOTEXTILE. IF RUNOFF OVERTOPS THE SILT FENCE, FLOWS UNDER OR AROUND THE
ENDS, OR IN ANY OTHER WAY BECOMES A CONCENTRATED FLOW, ONE OF THE
FOLLOWING SHALL BE PERFORMED, AS APPROPRIATE: 1) THE LAYOUT OF THE SILT
FENCE SHALL BE CHANGED, 2) ACCUMULATED SEDIMENT SHALL BE REMOVED, OR 3)
OTHER PRACTICES SHALL BE INSTALLED.
8. SEDIMENT SHALL BE REMOVED FROM SILT FENCE WHEN FABRIC IS AT 50% CAPACITY.
1. CONTRACTOR RESPONSIBLE FOR ALL SITE MATERIAL TESTING. TEST REPORTS TO BE
SUBMITTED TO THE ENGINEER AND OWNER TO BE INCLUDED IN FINAL
DOCUMENTATION.
2. ALL STATIONING IS CENTERLINE STATIONING. STATIONS ALONG CURVES ARE RADIAL.
3. ALL ROADWAY CONSTRUCTION SHALL MEET THE REQUIREMENTS AND STANDARD
SPECIFICATIONS OF THE CITY OF ROSWELL "PUBLIC WORKS SPECIFICATIONS" AND
"ZONING ORDINANCE", LATEST EDITIONS.
4. EXISTING AND FINISHED TOPOGRAPHIC INFORMATION SHOWN AT 1 FOOT INTERVALS.
FINISH TOPOGRAPHY IS APPROXIMATE AND DOES NOT CONSIDER CURBS AND OTHER
DETAIL CHANGES. DEFER TO SPOT ELEVATIONS WHERE PROVIDED.
5. ALL GRADING SHALL BE A MINIMUM OF 4:1 SLOPES OR FLATTER UNLESS OTHERWISE
NOTED. ALL CUT AND FILL TRANSITIONS SHALL BE ROUNDED. CONSTRUCTION
SLOPES WHICH EXCEED 4H:1V SHALL BE PROTECTED.
6. PROVIDE SMOOTH DRIVING TRANSITION AT ALL INTERSECTION.
7. ALL SPOT ELEVATIONS ARE FINISH DESIGN GRADES UNLESS OTHERWISE NOTED.
8. SUBGRADE AND BACKFILL MATERIALS FOR FOUNDATION SHALL BE COMPACTED TO A
MINIMUM OF 95% OF MODIFIED PROCTOR AS DETERMINED BY ASTM STANDARD
D1557.
9. BACKFILL MATERIALS TO BE PLACED UNDER CONCRETE SLABS SHALL BE A
GRANULAR SOIL. EXPANSIVE TYPE SOILS ARE PROHIBITED AS BACKFILL MATERIALS.
10. ALL CONCRETE SHALL BE PLACED IN A SINGLE CONTINUOUS OPERATION SO AS TO
PRODUCE A MONOLITHIC FOUNDATION WHERE APPLICABLE.
11. CEMENT SHALL CONFORM TO ASTM C150, TYPE I, II, OR III.
12. CONCRETE SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 3,000 PSI.
CONCRETE AGGREGATE SHALL CONFORM TO ASTM C33. CONCRETE SHALL BE
PROTECTED FROM LOSS OF MOISTURE FOR AN ADEQUATE AMOUNT OF TIME TO
PREVENT CURING TENSION CRACKS FROM FORMING IN THE FOUNDATION.
FOUNDATIONS OR SLABS SPECIFIED TO HAVE AIR ENTRAINMENT SHALL NOT BE
STEEL TROWEL FINISHED. CONCRETE SHALL NOT HAVE A SLUMP IN EXCESS OF 4
INCHES PRIOR TO PLACEMENT. CONCRETE SHALL BE PLACED WITHIN 90 MINUTES OF
BATCHING.
13. ALL SIGNAGE SHALL BE IN CONFORMANCE WITH CITY OF ROSWELL STANDARDS,
INCLUDING SIGN POST.
1. THE FLOW ARROWS SHOWN ON THE SITE GRADING DRAWING(S) INDICATE THE
GENERAL DIRECTION OF SURFACE RUNOFF. THE CONTRACTOR SHALL NOT
CONSTRUCT LOW POINTS IN PAVED SURFACES THAT ALLOW SURFACE RUNOFF TO
POND.
2. STORM WATER SHALL NOT BE ALLOWED TO POND WITHIN 10 FEET OF ANY BUILDING
FOUNDATION SYSTEM.
3. THE CONTRACTOR SHALL NOT ALLOW SURFACE RUNOFF TO CAUSE EROSION
DAMAGE TO EARTHWORK AREAS DURING CONSTRUCTION.
4. IF REQUIRED, THE CONTRACTOR IS RESPONSIBLE FOR PREPARING A STORM WATER
POLLUTION PREVENTION PLAN (SWPPP) FOR COMPLIANCE TO THE NATIONAL
POLLUTANT DISCHARGE ELIMINATION SYSTEM.
ALL INFORMATION SHOWN ON THIS SHEET THAT REFERENCES WATER, GAS AND SEWER
CALCULATIONS, METERS AND BACKFLOW PREVENTION DEVICES WERE PROVIDED BY
OTHERS AND ARE SHOWN FOR INFORMATIONAL PURPOSES ONLY.
EARTHWORK:
GRADING NOTES:
FIXTURE SUPPLY UNITS AND DEVICES NOTE:
GENERAL CONSTRUCTION NOTES:
EROSION CONTROL NOTES:
CONCRETE:
C.M.P. CORRUGATED METAL PIPE
D.I. DUCTILE IRON
EX OR EXIST. EXISTING
I.D. INNER DIAMETER
INV INVERT
LF LINEAR FEET
NAVD NORTH AMERICAN VERTICAL DATUM
NGS NATIONAL GEODETIC SURVEY
N.T.S. NOT TO SCALE
PI POINT OF INTERSECTION
psi POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
ROW RIGHT OF WAY
STA STATION
SWPPP STORMWATER POLLUTION PREVENTION PLAN
TYP TYPICAL
ABBREVIATIONS
SITE DRAINAGE:
1. CITY OF ROSWELL PUBLIC WORKS DEPARTMENT (RPW) CONTACT NUMBER:
(575)-624-6730.
2. RPW SHALL BE NOTIFIED 72 HOURS PRIOR TO COMMENCING ANY WORK IN THE
PUBLIC RIGHT OF WAY. ALL INSTALLATIONS REQUIRE VISUAL INSPECTION AS WELL
AS MATERIALS TESTING.
3. TRAFFIC CONTROL PLAN MUST BE SUBMITTED TO RPW 72 HOURS PRIOR TO ANY
SCHEDULED ROAD OR LANE CLOSURES. TRAFFIC CONTROL MUST MEET CURRENT
EDITION OF MUTCD.
4. CONTRACTOR SHALL CONTACT RPW BEFORE ANY TRAFFIC CONTROL IS IN PLACE OR
BEFORE ANY CONSTRUCTION (INCLUDING DEMOLITION) HAS BEGUN.
5. RPW ROADWAY INSPECTOR SHALL BE PRESENT AT THE TIME OF POTHOLING.
6. ROADWAY SECTION SHALL MEET CURRENT CITY STANDARDS FOR DEPTH OR MATCH
EXISTING DEPTH, WHICHEVER IS THICKER. ANY PAVEMENT OR CONCRETE
DISRUPTION CAUSED BY THE CONSTRUCTION/DEVELOPMENT SHALL BE REMOVED
AND REPLACED PER CITY STANDARDS.
7. BLUE STAKE LOCATES SHALL BE FIELD VERIFIED BY THE CONTRACTOR THROUGH
POTHOLING AND COORDINATION WITH UTILITY OWNER.
8. RECORD DRAWINGS OR WORK COMPLETED SHALL BE SUBMITTED TO RPW PRIOR TO
FINAL ACCEPTANCE OF THE INSTALLATIONS.
CONSTRUCTION MANAGEMENT NOTE:
PROJECT CONTACT INFORMATION
CITY OF ROSWELL
ENGINEERING DEPARTMENT - (575)-637-6281
WATER AND WASTEWATER - (575)-637-6255
DEPARTMENT - (575)-624-6711
SOLID WASTE DEPARTMENT - (575)-624-6746
XCEL ENERGY (ELECTRIC) - (800)-895-4999
NM GAS COMPANY - (888)-664-2726
PUBLIC WORKS - (575)-624-6730
AXA
AutoCAD SHX Text 10751
IR
IRRV
GM
IR
R
EX-G
IR
R
IRR
IRRV
WV
UGE
TEL TEL
AS SHOWN
C201
D
EM
O
LI
TI
O
N P
LA
N
NOTE TO CONTRACTOR:
WHILE THIS SHEET IS INTENDED TO DELINEATE THE
DEMOLITION ITEMS, THE CONTRACTOR SHALL BE
AWARE THAT ALL ITEMS CONFLICTING WITH THE
PROPOSED CONSTRUCTION SHALL BE REMOVED
AND/OR RELOCATED WHETHER OR NOT SPECIFICALLY
DESIGNATED. CONTRACTOR SHALL VERIFY THAT ALL
UTILITY ITEMS SHOWN AS PREVIOUSLY REMOVED
HAVE BEEN REMOVED AND TO WHAT EXTENT THEY
WERE REMOVED.
DEMOLITION NOTES:
1. THE CONTRACTOR IS RESPONSIBLE TO INSPECT AND BECOME
FAMILIARIZED WITH ALL EXISTING SITE CONDITIONS WITHIN THE
DEMOLITION LIMITS. NOT ALL ITEMS TO BE RAZED AND
REMOVED ARE SHOWN ON THIS DEMOLITION PLAN.
2. REMOVE ALL EXISTING PAVING, CONCRETE STRUCTURES,
CURBING, FENCING, FLATWORK, VEGETATION, TIRES AND ALL
DELETERIOUS ITEMS WITHIN THE DEMOLITION LIMITS OF THE
PROJECT, WHERE APPLICABLE.
3. ABANDON, REMOVE AND CUT/CAP EXISTING UTILITIES WITHIN
DEMOLITION LIMITS AS APPLICABLE, PER UTILITY OWNERS
DIRECTION. ACTUAL LOCATION AND NUMBER OF UTILITIES MAY
VARY IN THE FIELD. SEE UTILITY PLAN FOR UTILITY
RECONFIGURATION, WHERE APPLICABLE.
NOTE : AT A MINIMUM ALL DEMOLITION AND CONSTRUCTION SHALL MEET THE
REQUIREMENTS OF THE NEW MEXICO DEPARTMENT OF TRANSPORTATION
“STANDARD SPECIFICATIONS FOR HIGHWAY AND BRIDGE CONSTRUCTION”, LATEST
EDITION AND/OR THE CITY OF ROSWELL “PUBLIC WORKS SPECIFICATIONS”, LATEST
EDITION.
DEMOLITION LEGEND
= LIMITS OF DEMOLITION AREA
= EXISTING GRAVEL TO BE REMOVED
= CONCRETE / ASPHALT TO BE REMOVED
= INTERIOR BUILDING COMPONENTS TO BE REMOVED
= PORTION OF CURB AND GUTTER TO BE REMOVED
= EXISTING UNDER GROUND IRRIGATION LINE
= EXISTING UNDERGROUND GAS LINE
= PROPOSED COMMUNICATION LINE
= PROPOSED UNDERGROUND CONDUIT
= IRRIGATION VALVE
= IRRIGATION VALVE BOX
= WATER VALVE
= GAS METER
EXISTING UNDERGROUND.
IRRIGATION LINE TO REMAIN.
VERIFY EXACT LOCATION AND
EXTENTS INFIELD. PROTECT
DURING CONSTRUCTION .
EXISTING UNDERGROUND.
IRRIGATION LINE TO REMAIN.
VERIFY EXACT LOCATION AND
EXTENTS INFIELD. PROTECT
DURING CONSTRUCTION .
RELOCATE EXISTING WATER VALVE
OUTSIDE AREA OF NEW CONCRETE
PAVING. CONTRACTOR TO VERIFY
WORKING CONDITION OF WATER VALVE.
REMOVE EXISTING PARKING
STOPS. SALVAGE FOR RE-USE
IN NEW WORK.
DEMOLISH AND REMOVE
EXISTING ASPHALT RAMP.
PREP FOR NEW ASPHALT IN
NEW WORK.
DEMOLISH AND REMOVE
EXISTING ASPHALT RAMP.
PREP FOR NEW ASPHALT IN
NEW WORK.
REMOVE EXISTING PARKING
STOPS. SALVAGE FOR RE-USE
IN NEW WORK.
Sheet:
Horiz:Scale:
Project No:
Vert:
Date:
C hk
'd By
D es cr ip tio n
D at e R ev
THIS DRAWING IS INCOMPLETE
AND NOT TO BE USED FOR
CONSTRUCTION UNLESS IT IS
STAMPED, SIGNED AND DATED
© Copyright 2020 Souder, Miller & Associates - All Rights Reserved
Designed CheckedDrawn
PE
C
O S
VA
LL
EY
R
EG
IO
N
AL
C O
M M
U N
IC
AT
IO
N
S C
EN
TE
R R
EN
O
VA
TI
O N
R O
SW
EL
L, N
EW
M
EX
IC
O
MJ MJ
March 2023
9B31722
D
ES
ER
T
PE
AK
A R
C H
IT
EC
TS
LA
S C
R U
C
ES
, N
EW
M
EX
IC
O
P:\9-DPA Pecos Valley RCC Renovation (9B31722)\CAD\Civil\Construction Drawings\9B31722 - DEMOLITION PLAN.dwg 3/2/2023 3:46 PM AXA
NOTE: THESE DRAWINGS ARE TO BE USED TO
ACQUIRE PERMITS FROM JURISDICTIONAL
GOVERNMENTAL AGENCIES AND ARE NOT TO BE
RELIED UPON FOR PROJECT BIDDING PURPOSES
OR FOR CONSTRUCTION UNTIL APPLICABLE
CONSTRUCTION PERMITS ARE ISSUED
SM
ASO
U D
ER
, M
IL
LE
R
A
SS
O C
IA
TE
S E ng in ee ri ng
E nv ir on m en ta l
G eo m at ic s
Se rv in g th e
So ut hw es t & R oc ky
M ou nt ai ns w w w .s ou de rm ille r.c om
Ph on e (5
) 6
-0
F ax
(5
) 6
-0
S ed on a
H ill s P kw y.
La s C ru ce s, N M
/2
2/
In iti al
S ub m itt al
AX
A M
J
3/2/2023
MICHAEL D. JOHNSON
NEW
MEXICO
REGISTERED PROFESSIONAL ENG
INE
ER
AXA
UNDERGROUND CONDUIT
AND COMMUNICATION LINE
FROM EXISTING RADIO ROOM.
TRENCH AND BACKFILL AS
REQUIRED. REFER TO
ELECTRICAL AND SPECIAL
SYSTEMS. TO BE INCLUDED IN
BAES BID.
INTERIOR BUILDING
COMPONENTS TO BE
REMOVED - REFER TO
ARCHITECTURAL
DEMOLITION PLAN
SCALE: 1" = 10'
10'
SCALE: 1" = 10'
0 20'
SMA
LIMITS OF
DEMOLITION
AREA
LIMITS OF
DEMOLITION
AREA
DEMOLISH AND
REMOVE EXISTING
CURB AND GUTTER..
SAW CUT AND REMOVE 105 SQFT
OF EXISTING ASPHALT. SEE
WALKING TRAIL - GRADING PLAN
ENLARGEMENT FOR LIMITS.
DEMOLISH AND
REMOVE EXISTING
CONCRETE SIDEWALK
IR
GM
IRRV
WV
NOTE: ALL DEMOLITION WORK
SHOWN SHALL BE INCLUDED AS
PART OF ADDITIVE ALTERNATIVE
#3. REFER TO ARCHITECTURAL.
AutoCAD SHX Text 10751
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text N
NO
PARKING
10.39
FG
10.37
FG
10.38
FG
10.39
FG
10.25 BoW
10.09
EG
10.24
EG
9.77 ToC
9.27 FL
10.60 ToC
10.10 FL 10.20
EG
10.53 ToC
10.03 FL
10.50 ToC
10.00 FL
.4
To
C 9.
F
L
.3
To C
9.
F L
10.35 ToC
9.85 FL
10.31 ToC
9.81 FL
.1
To
C 9.
F
L
10.14 ToC
9.64 FL
.1
To
C 9.
F
L
9.31 ToA
9.44 ToA
9.49 ToA
10.51 ToC
10.01 FL
.1
To
C 9.
F
L
9.34 EoP
9.73 ToC
9.23 FL
MATCH TO
EXISTING
ASPHALT
MATCH TO
EXISTING
ASPHALT
10.26 BoW
10.27 BoW
10.18 BoW
10.15 BoW
10.20 BoW
10.09 BoW
10.04 BoW
.4
To
C 9.
F
L
.3
To C
9.
F L
.2
To
C 9.
F
L
9.54 ToA
.4
To
C 9.
F
L
10.25 ToC
9.75 FL
.0
To
C 9.
F
L
10.20
EG
10.57 ToC
10.07 FL
9.48 EoP
9.72 ToA
9.66 ToA
9.45 ToA
9.36 ToA
10.25 ToC
9.75 FL
9.65 ToC
9.15 FL
9.71 ToC
9.21 FL
9.58 ToC
9.20 EoP
9.22 EoP
7.89
FG
9.00
FG
7.73
FG
9.00
FG
9.49 EoP
9.00
FG
1.52%
0.
0.
1.59% 0.
2.16%
0.
0.
WV
0.53%
0.51% 1.83%
NO
PARKING
10.27 ToC
9.95 FL10.28BoW
10.28BoW
10.27 ToC
9.77 FL
10.25 ToC
9.75 FL
10.27BoW
0.87%
9.74 EoP
9.75 EoP
9.66 EoP
9.66 EoP
9.74 EoP
9.86 EoP
9.75 EoP
9.
Eo P
9.78 EoP
WV
4.75% 1.77%
2.
0.28%
0.
0.
0.
9.80
FG
9.61 ToC
9.11 FL
9.56 EoP
7.89
FG 7.73
FG
9.00
FG
9.90 EoP
9.75 EoP
9.69 EoP
9.48 EoP
9.00
FG
9.09
FG
10.01 ToC
9.51 FL
9.61 ToC
9.11 FL
9.04
FG
9.02
FG
8.91
FG
N:864032.23 E:483704.61 3609.83
N:864027.69 E:483706.53 3609.78
N:864025.78 E:483699.12 3609.53
N:864030.03 E:483696.74 3609.56
N:864027.78 E:483692.66
3609.52
N:864023.53 E:483695.05
3609.51
N:864019.17 E:483689.52 3609.61
N:864022.96 E:483686.56
3609.62
5.50'
4.00'
9.06
FG
8.97
FG
4.60'
9.56
FG
9.56
FG
9.59
FG
9.59
FG
9.47
FG
9.47
FG
4.00'
4.00'
AS SHOWN
C300Sheet:
Horiz:Scale:
Project No:
Vert:
Date:
C hk
'd By
D es cr ip tio n
D at e R ev
THIS DRAWING IS INCOMPLETE
AND NOT TO BE USED FOR
CONSTRUCTION UNLESS IT IS
STAMPED, SIGNED AND DATED
© Copyright 2020 Souder, Miller & Associates - All Rights Reserved
Designed CheckedDrawn
PE
C
O S
VA
LL
EY
R
EG
IO
N
AL
C O
M M
U N
IC
AT
IO
N
S C
EN
TE
R R
EN
O
VA
TI
O N
R O
SW
EL
L, N
EW
M
EX
IC
O
MJ MJ
March 2023
9B31722
D
ES
ER
T
PE
AK
A R
C H
IT
EC
TS
LA
S C
R U
C
ES
, N
EW
M
EX
IC
O
P:\9-DPA Pecos Valley RCC Renovation (9B31722)\CAD\Civil\Construction Drawings\9B31722 - GRADING PLAN.dwg 3/2/2023 3:46 PM AXA
NOTE: THESE DRAWINGS ARE TO BE USED TO
ACQUIRE PERMITS FROM JURISDICTIONAL
GOVERNMENTAL AGENCIES AND ARE NOT TO BE
RELIED UPON FOR PROJECT BIDDING PURPOSES
OR FOR CONSTRUCTION UNTIL APPLICABLE
CONSTRUCTION PERMITS ARE ISSUED
SM
ASO
U D
ER
, M
IL
LE
R
A
SS
O C
IA
TE
S E ng in ee ri ng
E nv ir on m en ta l
G eo m at ic s
Se rv in g th e
So ut hw es t & R oc ky
M ou nt ai ns w w w .s ou de rm ille r.c om
Ph on e (5
) 6
-0
F ax
(5
) 6
-0
S ed on a
H ill s P kw y.
La s C ru ce s, N M
/2
2/
In iti al
S ub m itt al
AX
A M
J
3/2/2023
MICHAEL D. JOHNSON
NEW
MEXICO
REGISTERED PROFESSIONAL ENG
INE
ER
G
R
AD
IN
G
P
LA
N
AXA
GRADING PLAN
NOTE : AT A MINIMUM ALL DEMOLITION AND CONSTRUCTION SHALL MEET THE
REQUIREMENTS OF THE NEW MEXICO DEPARTMENT OF TRANSPORTATION
“STANDARD SPECIFICATIONS FOR HIGHWAY AND BRIDGE CONSTRUCTION”, LATEST
EDITION AND/OR THE CITY OF ROSWELL “PUBLIC WORKS SPECIFICATIONS”, LATEST
EDITION.
GRADING LEGEND
TOP OF CURB ELEVATION
FLOW LINE ELEVATION
EDGE OF PAVING ELEVATION
BACK OF SIDEWALK ELEVATION
FINISH GRADE ELEVATION
EXISTING GRADE
TOP OF ASPHALT
STORM WATER FLOW DIRECTION
DIRECTION OF PROPOSED SURFACE GRADE
EXISTING MAJOR CONTOURS
EXISTING MINOR CONTOURS
1. THE FLOW ARROWS SHOWN ON THE SITE GRADING
DRAWING(S) INDICATE THE GENERAL DIRECTION OF SURFACE
RUNOFF. THE CONTRACTOR SHALL NOT CONSTRUCT LOW
POINTS IN PAVED SURFACES THAT ALLOW SURFACE RUNOFF
TO POND.
2. STORM WATER SHALL NOT BE ALLOWED TO POND WITHIN 10
FEET OF ANY BUILDING FOUNDATION SYSTEM.
3. THE CONTRACTOR SHALL NOT ALLOW SURFACE RUNOFF TO
CAUSE EROSION DAMAGE TO EARTHWORK AREAS DURING
CONSTRUCTION.
4. THE CONTRACTOR IS RESPONSIBLE FOR PREPARING A STORM
WATER POLLUTION PREVENTION PLAN (SWPPP) FOR
COMPLIANCE TO THE NATIONAL POLLUTANT DISCHARGE
ELIMINATION SYSTEM.
SITE DRAINAGE
ToC
FL
EoP
BoW
FG
EG
ToA
SW
0.0%
SMA
ADA - GRADING PLAN
5'
SCALE: 1" = 5'
0 10'
SEE RIGHT FOR ENLARGED
ADA RAMP - GRADING PLAN
CAST-IN-PLACE
CONCRETE
SIDEWALK
CURB
TRANSITION
AREA
PRE-CAST
CONCRETE
WHEEL
STOPS
RELOCATED
EXISTING
WHEEL
STOPS
EXISTING
ASPHALT
LANDSCAPING
AREA. REFER TO
LANDSCAPE AND
IRRIGATION PLAN.
EXISTING KEY
PEDESTAL TO REMAIN.
CONTRACTOR TO
PROTECT DURING
CONSTRUCTION.
N: 864041.41 E: 483691.22
2.5' WIDE CURB CUT. SEE DETAIL
5 ON SHEET C301 FOR DETAILS.
CONTRACTOR
TO REWORK
CHAINLINK FENCE
C301
C301
C301
C301
C301
C301
C301
C301
C301
C301
C301
C301
C301
C301
3/8" THICK DIAMMOND
STEEL PLATE. SEE
DETAIL 8 ON SHEET C301.
AREA OF WALK PATH TO BE
REMOVED.
AREA OF WALK PATH
TO BE REMOVED.
WALKING TRAIL- GRADING PLAN
5'
SCALE: 1" = 5'
0 10'
SEE RIGHT FOR
ENLARGED WALKING
TRAIL - GRADING PLAN BOTTOM OF EARTHEN
DRAINAGE SWALE.
C301
C301
9C301
6C301
6C301
GRADE TO
EXISTING 4:1
GRADE TO
EXISTING 4:1
5.5' X 4.5' X 2' DEEP
RIVER ROCK RIP RAP
EXISTING
RETENTION POND
LOADING
ZONE
DAYLIGHT SWALE
INTO EXISTING
RETENTION POND 4:1
CMU SITE WALL. SEE
DETAIL 10 ON SHEET C301
FOR DETAIL.
NOTE : ALL NEW SITE WORK
SHOWN SHALL BE INCLUDED AS
PART OF ADDITIVE ALTERNATE #3.
REFER TO ARCHITECTURAL.
AutoCAD SHX Text 10751
AutoCAD SHX Text
SCALE: 1" = 10'
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text
SCALE: 1" = 5'
SCALE: 1" = 5'
3000 PSI
CONCRETE
(MIN.)
AS SHOWN ON PLAN
(5' MIN.)
8" SUBGRADE PREPARATION
COMPACTED TO 95% PROCTOR
4"
2% MAX
SIDEWALK DETAIL (TYPICAL)
NOT TO SCALE
EXPANSION
JOINT
@ EVERY12'
CONTROL
JOINT
@ EVERY 4'
AS
S
H O
W N
O N
P
LA
N
4' 4' 4'
CONTROL
JOINT
@ EVERY 4'
EXPANSION JOINT
@ EVERY12'
SIDEWALK - PLAN VIEW
NOT TO SCALE
SAW CUT
CONCRETE
SIDEWALK
1/2" DEEP
4" THICK
3000 PSI
CONCRETE
SIDEWALK
CONTROL JOINT
NOT TO SCALE
1/2"
1/ 4"
1"
SEALANT (DOW
CORNING 888
SILICONE JOINT
SEALANT)
BACKER
ROD
PREFORMED
BITUMINOUS FIBER
JOINT FILLER
MATERIAL
4" THICK
3000 PSI
CONCRETE
SIDEWALK
EXPANSION JOINT
NOT TO SCALE
2" H.M.A.C.
6" BASE COURSE
COMPACTED TO
95% MOD. PROCTER
12" SUBGRADE COMPACTED TO
95% MOD. PROCTER
NOT TO SCALE
ASPHALT PAVING
SECTION
VARIESVARIES
4:1 SLOPE
4:1 SLOPE
PL
DRAINAGE SWALE
NOT TO SCALE
GRADE TOEXISTING
GRADE TO
EXISTING
2"- 4" RIVER ROCK
8" SUBGRADE
COMPACTED
TO 95% MOD.
PROCTER
6"
1'
CURB CUT ELEVATION
NOT TO SCALE
HEADER CURB
6"
3/4" R
FILLET
TYP.
2.5 'CURB
CUT
TOP OF
ASPHALT
SURFACING
BOTTOM
OF CURB
2'
TOP OF CURB
FLOWLINE
STANDARD CURB
TOP OF CURB
FLOWLINE
VARIESVARIES
4:1 SLOPE
4:1 SLOPE
PL
EARTHEN DRAINAGE
SWALE
NOT TO SCALE
GRADE TOEXISTING
GRADE TO
EXISTING
8" SUBGRADE
COMPACTED
TO 95% MOD.
PROCTER
8"
NATIVE SOIL
CMU WALL SECTION
EXISTING GRADEFINISH GRADE
NOT TO SCALE
CAP
#5 BARS
@ 24" O.C.
LEAVE EVERY OTHER CELL
VOID OF GROUT UNTIL
UPPER WALL IS DEVELOPED
2 - "L SHAPE" #5 BARS
-10" X 36" @ 24" O.C.
#5 BARS @ 24" O.C.
SUPPORTS @ 48" O.C.
SUPPORTS @ 48" O.C.
3 - #5 BARS
CONTINUOUS
2.33'
1.
8" 8"
C
O U
R
SE
S
6.
BOND BEAM W/ 2 - #5 BARS
CONTINUOUS NOT TO EXCEED
4' VERTICAL SPACING
8x8x16 CMU BLOCK
WITH GROUT FILLED
AS SHOWN
C301Sheet:
Horiz:Scale:
Project No:
Vert:
Date:
C hk
'd By
D es cr ip tio n
D at e R ev
THIS DRAWING IS INCOMPLETE
AND NOT TO BE USED FOR
CONSTRUCTION UNLESS IT IS
STAMPED, SIGNED AND DATED
© Copyright 2020 Souder, Miller & Associates - All Rights Reserved
Designed CheckedDrawn
PE
C
O S
VA
LL
EY
R
EG
IO
N
AL
C O
M M
U N
IC
AT
IO
N
S C
EN
TE
R R
EN
O
VA
TI
O N
R O
SW
EL
L, N
EW
M
EX
IC
O
MJ MJ
March 2023
9B31722
D
ES
ER
T
PE
AK
A R
C H
IT
EC
TS
LA
S C
R U
C
ES
, N
EW
M
EX
IC
O
P:\9-DPA Pecos Valley RCC Renovation (9B31722)\CAD\Civil\Construction Drawings\9B31722 - GRADING PLAN.dwg 3/2/2023 3:46 PM AXA
NOTE: THESE DRAWINGS ARE TO BE USED TO
ACQUIRE PERMITS FROM JURISDICTIONAL
GOVERNMENTAL AGENCIES AND ARE NOT TO BE
RELIED UPON FOR PROJECT BIDDING PURPOSES
OR FOR CONSTRUCTION UNTIL APPLICABLE
CONSTRUCTION PERMITS ARE ISSUED
SM
ASO
U D
ER
, M
IL
LE
R
A
SS
O C
IA
TE
S E ng in ee ri ng
E nv ir on m en ta l
G eo m at ic s
Se rv in g th e
So ut hw es t & R oc ky
M ou nt ai ns w w w .s ou de rm ille r.c om
Ph on e (5
) 6
-0
F ax
(5
) 6
-0
S ed on a
H ill s P kw y.
La s C ru ce s, N M
/2
2/
In iti al
S ub m itt al
AX
A M
J
3/2/2023
MICHAEL D. JOHNSON
NEW
MEXICO
REGISTERED PROFESSIONAL ENG
INE
ER
PR
O
JE
T D
ET
AI
LS
AXA
NOTE : AT A MINIMUM ALL DEMOLITION AND CONSTRUCTION SHALL MEET THE
REQUIREMENTS OF THE NEW MEXICO DEPARTMENT OF TRANSPORTATION
“STANDARD SPECIFICATIONS FOR HIGHWAY AND BRIDGE CONSTRUCTION”, LATEST
EDITION AND/OR THE CITY OF ROSWELL “PUBLIC WORKS SPECIFICATIONS”, LATEST
EDITION.
3'
3'
5' S
ID
EW
AL
K
3/8" THICK DIAMOND
STEEL PLATE
48" WIDE x
EXISTING SIDEWALK
WIDTH (5' V.I.F.)
REMOVE 4.67' OF EXISTING SIDEWALK
4' 4"4"
MATCH WIDTH AND
THICKNESS OF THE
EXISTING SIDEWALK
2" EXPANSION
JOINT
6" 4"
1 1/2"X1 1/2"X1/4"
ANGLE (BOTH SIDES)
3" NELSON STUD
3 REQ. BOTH SIDES
WELD TO ANGLE IRON
CONCRETE
DRAIN CHANNEL
3000 PSI CONCRETE
4" THICK, WIDTH TO
MATCH EXISTING
SIDEWALK WIDTH
2" EXPANSION
JOINT
EXISTING
SIDEWALK
EXISTING
SIDEWALK
SECTION 'A'
3/8" THICK DIAMOND
STEEL PLATE
48" WIDE x
EXISTING SIDEWALK
WIDTH (5' V.I.F.)
4" 48" 4"
FL
O
W
NEW
CONCRETE
NEW
CONCRETE
PLAN VIEW - WALKING TRAIL
NOT TO SCALE
NOT TO SCALE
AA
SAW CUT EXISTING
PAVEMENT
SAW CUT EXISTING
PAVEMENT
C301
C301
C301
C301
C301
C301
C301
C301
C301
C301
WV
WM
IR
IR
IR
IR
IR
IR
IR
IR
IRRV
IRRV
IRRV
IRRV
IRRV IRRV
IRRV
IRRV
GM
IR
R
EX-G
EX-G
EX-GEX-G
EX
-G
EX
-G
EX
-G
EX-G
UGEUGE
U G
E U
G E
U G
E
U G
E
NO
PARKING
LOADING
ZONE
IR
R
IRR
IRR
IRR
IRR
IRR
IRR
IR
R
IRR IRR
IRR IRR
IR
R
IRRV
WV
WV
UGE UGE UGE UGE
TEL TEL TELTELTEL
AS SHOWN
C400Sheet:
Horiz:Scale:
Project No:
Vert:
Date:
C hk
'd By
D es cr ip tio n
D at e R ev
THIS DRAWING IS INCOMPLETE
AND NOT TO BE USED FOR
CONSTRUCTION UNLESS IT IS
STAMPED, SIGNED AND DATED
© Copyright 2020 Souder, Miller & Associates - All Rights Reserved
Designed CheckedDrawn
PE
C
O S
VA
LL
EY
R
EG
IO
N
AL
C O
M M
U N
IC
AT
IO
N
S C
EN
TE
R R
EN
O
VA
TI
O N
R O
SW
EL
L, N
EW
M
EX
IC
O
MJ MJ
March 2023
9B31722
D
ES
ER
T
PE
AK
A R
C H
IT
EC
TS
LA
S C
R U
C
ES
, N
EW
M
EX
IC
O
P:\9-DPA Pecos Valley RCC Renovation (9B31722)\CAD\Civil\Construction Drawings\9B31722 - UTILITY PLAN.dwg 3/2/2023 3:47 PM AXA
NOTE: THESE DRAWINGS ARE TO BE USED TO
ACQUIRE PERMITS FROM JURISDICTIONAL
GOVERNMENTAL AGENCIES AND ARE NOT TO BE
RELIED UPON FOR PROJECT BIDDING PURPOSES
OR FOR CONSTRUCTION UNTIL APPLICABLE
CONSTRUCTION PERMITS ARE ISSUED
SM
ASO
U D
ER
, M
IL
LE
R
A
SS
O C
IA
TE
S E ng in ee ri ng
E nv ir on m en ta l
G eo m at ic s
Se rv in g th e
So ut hw es t & R oc ky
M ou nt ai ns w w w .s ou de rm ille r.c om
Ph on e (5
) 6
-0
F ax
(5
) 6
-0
S ed on a
H ill s P kw y.
La s C ru ce s, N M
/2
2/
In iti al
S ub m itt al
AX
A M
J
3/2/2023
MICHAEL D. JOHNSON
NEW
MEXICO
REGISTERED PROFESSIONAL ENG
INE
ER
U
TI
LI
TY
P
LA
N
UTILITY PLAN
SCALE: 1" = 30'
SCALE: 1" = 30'
60'30'0 NOTE : AT A MINIMUM ALL DEMOLITION AND CONSTRUCTION SHALL MEET THE
REQUIREMENTS OF THE NEW MEXICO DEPARTMENT OF TRANSPORTATION
“STANDARD SPECIFICATIONS FOR HIGHWAY AND BRIDGE CONSTRUCTION”, LATEST
EDITION AND/OR THE CITY OF ROSWELL “PUBLIC WORKS SPECIFICATIONS”, LATEST
EDITION.
LEGEND
EX W
G
WILKINS REGULATOR COMPANY
AMES FIRE & WATERWORKS
A.R.I.FLOW CONTROL ACCESSORIES
BACKFLOW DIRECT
FEBCO
WATTS
APOLLO/CONBRACO INDUSTRIES, INC.
BEECO
CLA - VAL
WATER FIXTURE SUPPLY UNITS
ALL INFORMATION SHOWN ON THIS SHEET THAT REFERENCES WATER,
GAS AND SEWER CALCULATIONS AND BACKFLOW PREVENTION DEVICE
WERE PROVIDED BY OTHERS AND ARE SHOWN FOR FOR INFORMATION
ONLY. 1" DOMESTIC WATER METER DEMAND IS 0.25 PSI.
APPROVED BACKFLOW PREVENTER
MANUFACTURERSEXISTING WATER LINE
EXISTING WATER METER BOX
EXISTING WATER VALVE
EXISTING IRRIGATION VALVE
EXISTING IRRIGATION LINE
EXISTING UNDER GROUND ELETRIC
EXISTING STREET LIGHT
EXISTING ELECTRIC UTILITY COMPONENTS
EXISTING TELEPHONE UTILITY COMPONENTS
EXISTING FIBER OPTIC UTILITY COMPONENTS
EXISTING GAS LINE
EXISTING GAS METER
PROPOSED TELECOMMUNICATION LINE
PROPOSED UNDER GROUND ELECTRICAL
FOPB
ET
F
PROPOSED NEW LOCATION OF IRRIGATION
VALVE. CONNECT TO EXISTING SYSTEM.
CONTRACTOR TO VERIFY IRR VALVE IS IN
SAME WORKING CONDITION.
UNDERGROUND COMMUNICATION
LINE FROM EXISTING RADIO
ROOM TO NEW DISPATCH AREA.
TRENCH AND BACKFILL AS
REQUIRED. REFER TO
ELECTRICAL AND SPECIAL
SYSTEMS. TO BE INCLUDED IN
BASE BID.
WM
IRRV
IRR
TEL
GM
SMA
AXA
UGE
EXISTING OLD LOCATION OF
IRRIGATION VALVE. CONTRACTOR TO
VERIFY CONDITION OF IRRIGATION
VALVE BEFORE RELOCATION.
TEL
UGE
UNDERGROUND CONDUIT
FROM EXISTING RADIO
ROOM TO NEW DISPATCH
AREA. TRENCH AND
BACKFILL AS REQUIRED.
REFER TO ELECTRICAL AND
SPECIAL SYSTEMS. TO BE
INCLUDED IN BASE BID.
NOTE : TRENCHING AND BACKFILL
AS SHOWN TO BE INCLUDED IN
BASE BID.
LOCATION OF NEW
I.T. ROOM FOR
TELECOMMUNICATION
TERMINATION
PROPOSED UNDERGROUND
COMMUNICATION LINE.
COORDINATE WITH COMCAST
FOR FINAL
CONNECTION.TRENCH AND
BACKFILL AS REQUIRED. TO
BE INCLUDED IN BASE BID.
EXISTING UNDERGROUND.
IRRIGATION LINE TO
REMAIN. VERIFY EXACT
LOCATION AND EXTENTS
IN FIELD. PROTECT
DURING CONSTRUCTION.
AutoCAD SHX Text 10751
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text N
NO
PARKING
LOADING
ZONE
WV
NO
PARKING
SIGN TYPE R7-8 (12"X18")
- SIGN FILED IS WHITE
- SIGN LETERING AND BORDER ARE GREEN
- INTERNATIONAL SYMBOL OF ACCESSIBILITY
IS WHITE ON A BLUE BACKGROUND
REQUIRED LANGUAGE PER
NMSA 197866-7-352.4C
SIGNTYPE R7-8A (6"X12")
- SIGN FIELD IS WHITE
- SIGN LETTERING AND BORDER ARE GREEN
2" DIA STD WT STL
PIPE POST - GALV
FIN GRADE OR PAVING
1'-0" DIA CONC
FTG - SLOPE
TOP TO DRAIN
VIOLATOR'S ARE
SUBJECT TO A FINE
AND/OR TOWING
1' -6
4"
8" 4'
-4
1/
2" 1'
-5
3"
2' 6'
=6
ADA PARKING SIGN
6" DIA. CONCRETE FILLED
STEEL PIPE BOLLARD.
PAINTED YELLOW.
VAN
ACCESSIBLE
REQUIRED LANGUAGE (VAN ACCESSIBBLE
SPACES) ANSI 502.7
NON-VAN ACCESSIBLE
SPACES BOTTOM OF
THIS SIGN 60" MIN.
ABOVE GROUND
ANSI502.7
VAN ACCESSIBLE
SPACES BOTTOM OF
THIS SIGN 60" MIN.
ABOVE GROUND
ANSI502.7
AS SHOWN
C700Sheet:
Horiz:Scale:
Project No:
Vert:
Date:
C hk
'd By
D es cr ip tio n
D at e R ev
THIS DRAWING IS INCOMPLETE
AND NOT TO BE USED FOR
CONSTRUCTION UNLESS IT IS
STAMPED, SIGNED AND DATED
© Copyright 2020 Souder, Miller & Associates - All Rights Reserved
Designed CheckedDrawn
PE
C
O S
VA
LL
EY
R
EG
IO
N
AL
C O
M M
U N
IC
AT
IO
N
S C
EN
TE
R R
EN
O
VA
TI
O N
R O
SW
EL
L, N
EW
M
EX
IC
O
MJ MJ
March 2023
9B31722
D
ES
ER
T
PE
AK
A R
C H
IT
EC
TS
LA
S C
R U
C
ES
, N
EW
M
EX
IC
O
P:\9-DPA Pecos Valley RCC Renovation (9B31722)\CAD\Civil\Construction Drawings\9B31722 - SIGNAGE AND STRIPPING PLAN.dwg 3/2/2023 3:47 PM AXA
NOTE: THESE DRAWINGS ARE TO BE USED TO
ACQUIRE PERMITS FROM JURISDICTIONAL
GOVERNMENTAL AGENCIES AND ARE NOT TO BE
RELIED UPON FOR PROJECT BIDDING PURPOSES
OR FOR…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .