Irrigation_Plan_Set_2.pdf
PDF 2 MB Posted
- Attached to
- 90 North Park Irrigation
- Solicitation number
- 2023-IFB-066
- Issued by
- Cook County, Illinois
About this file
The document is a final engineering plan set for the Schaumburg 90 NDW Urban Park Irrigation project, prepared by Site Design Group (Landscape Architect) and V3 Companies (Engineer) for the Village of Schaumburg, Illinois. The plan set consists of three sheets: a title sheet (C0.0), general notes and specifications sheet (C1.0), and an overall utility sheet (C2.0), which detail the irrigation infrastructure for the park. The project involves installing a new water service connection, including a 2-inch water service, a 12-inch water stub for future connection, valve boxes, and related appurtenances.
The engineering plans provide technical specifications for water main distribution, including detailed requirements for pipe materials (ductile iron pipe, Class 52), minimum cover depths, valve vault configurations, and Illinois Environmental Protection Agency (IEPA) crossing requirements. The utility sheet shows the proposed water infrastructure layout, with specific notes indicating that above-ground work, including the meter box and booster pump, will be completed by the irrigation contractor. The plan set is dated August 9, 2023, and is marked as "Issued for Review," suggesting the project is in the final design stages before potential construction bidding.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C0.0 N:\2020\20096\20096.PH2\Drawings\ACAD\LD\S04\Sheet Drawings\C0.0 Tsht 20096.PH2.dwg
TITLE SHEET
BENCHMARKS
Date Issued
Sheet Title:
Drawing Number:
Progress Parkway, Schaumburg, IL 60173
Schaumburg 90 NDW Urban Park
Landscape Architect 888 South Michigan Avenue #1000, Chicago, IL 60605
p. 312.427.7240 w. www.site-design.com
V3 Companies Engineer 7325 Janes Avenue, Woodridge, IL 60517
p. 630.724.9200 w. www.v3co.com
Rev. #
File :
20096.PH2
Approved :
Drawn :
Project No :
Scale : AS NOTEDChecked :
C0.0 Tsht 20096.PH2.dwg
08/09/202301 ISSUED FOR REVIEW
NRS
LAC
Description
ILLINOIS LICENSED DESIGN FIRM NO. 184-000902
Joint
Utility
Locating
Information for
Excavators
Call
48 hours before you dig
PROFESSIONAL ENGINEER'S CERTIFICATION
SOURCE:
BENCHMARK ESTABLISHED VIA TRIMBLE'S VRS NETWORK.
DATUM IS NAVD88
LATITUDE: 42°03'55.92860 N
LONGITUDE: 88°03'07.23065 W
ELLIPSOIDAL HEIGHT: 611.508 SFT
GROUND SCALE FACTOR: 1.0000475119 GEOID 12A U.S.
SITE:
STATION DESIGNATION: SBM#1
ESTABLISHED BY: V3 COMPANIES
DATE: 04-02-20
ELEVATION: 735.31 (MEASURED)
DATUM: NAVD88
DESCRIPTION: NORTHWEST ARROW BOLT ON FIRE
HYDRANT LOCATED ALONG THE NORTH SIDE OF
PROGRESS PARKWAY.
STATION DESIGNATION: SBM#2
ESTABLISHED BY: V3 COMPANIES
DATE: 04-02-20
ELEVATION: 735.31 (MEASURED)
DATUM: NAVD88
DESCRIPTION: NORTHEAST ARROW BOLT ON FIRE
HYDRANT LOCATED ALONG THE NORTH SIDE OF
PROGRESS PARKWAY.
THE ELEVATIONS ABOVE WERE KNOWN TO BE ACCURATE
AT THE TIME THEY WERE ESTABLISHED. V3 DOES NOT
CERTIFY TO THE ACCURACY THEREAFTER, NOR ASSUMES
RESPONSIBILITY FOR THE MIS-USE OR
MIS-INTERPRETATION OF THE INFORMATION SHOWN
HEREON.
IT IS ADVISED THAT ALL OF THE ABOVE ELEVATIONS BE
CHECKED BETWEEN EACH OTHER AND VERIFY A MINIMUM
OF 3 SURROUNDING UTILITY RIM ELEVATIONS AND ANY
ADJACENT BUILDING FINISHED FLOOR OR TOP OF
FOUNDATION ELEVATIONS SHOWN HEREON PRIOR TO USE
OR COMMENCEMENT OF ANY CONSTRUCTION OR OTHER
WORK.
PERSONS USING THIS INFORMATION ARE TO CONTACT V3
IMMEDIATELY WITH ANY DISCREPANCIES FOUND PRIOR TO
THE START OF ANY WORK.
DRAINAGE CERTIFICATE:
TO THE BEST OF MY KNOWLEDGE AND BELIEF, THE DRAINAGE OF SURFACE WATERS WILL
NOT BE CHANGED BY THE PROPOSED DEVELOPMENT. IF ANY DRAINAGE PATTERNS WILL
BE CHANGED, REASONABLE PROVISIONS HAVE BEEN MADE FOR THE COLLECTION AND
DIVERSION OF SUCH WATERS INTO THE PUBLIC AREA, OR DRAINS APPROVED FOR THE
USE BY THE MUNICIPAL ENGINEER, AND THAT SUCH SURFACE WATERS ARE PLANNED
FOR IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING PRACTICES SO AS TO
REDUCE THE LIKELIHOOD OF DAMAGES TO ADJOINING PROPERTIES.
DESIGN ENGINEER DATE
FOR
SCHAUMBURG, ILLINOIS
FINAL ENGINEERING PLANS
SCHAUMBURG 90ND PARK IRRIGATION
NO SCALE
PROJECT TEAM
ENGINEER
OWNER/DEVELOPER
TITLE SHEET
GENERAL NOTES , SPECIFICATIONS, LEGEND,
AND ABBREVIATIONS
UTILITY PLAN
C0.0
C1.0
C2.0
Site Design Group, Ltd.
888 South Michigan Avenue
Suite 1000
Chicago, Illinois 60605
312 427 7240
Contact: Bradely McCauley
CIVIL ENGINEERING PLANS
NO SCALE
INDEX
LOCATION MAP
VICINITY MAP
V3 Companies, Ltd.
7325 Janes Avenue
Woodridge, Illinois 60517
630 724 9200
Project Manager: Daniel E. Free, P.E.
dfree@v3co.com
Project Engineer: Lisa Cassaidy, P.E.
lcassaidy@v3co.com
I, LISA A. CASSAIDY, A LICENSED PROFESSIONAL ENGINEER OF ILLINOIS, HEREBY CERTIFY THAT
THE CIVIL ENGINEERING PLANS WERE PREPARED ON BEHALF OF SITE DESIGN GROUP, LTD.
BY V3 COMPANIES, LTD. UNDER MY PERSONAL DIRECTION. THIS TECHNICAL SUBMISSION IS
INTENDED TO BE USED AS AN INTEGRAL PART OF AND IN CONJUNCTION WITH THE PROJECT
SPECIFICATIONS AND CONTRACT DOCUMENTS.
DATED THIS DAY OF , A.D., 2023.
ILLINOIS LICENSED PROFESSIONAL ENGINEER 062-054453
MY LICENSE EXPIRES ON NOVEMBER 30, 2023
PROJECT
LOCATION
PROJECT
LOCATION
AutoCAD SHX Text N
AutoCAD SHX Text N
C1.0 N:\2020\20096\20096.PH2\Drawings\ACAD\LD\S04\Sheet Drawings\C1.0 Gal 20096.PH2.dwg
GENERAL NOTES, SPECIFICATIONS,
LEGEND AND ABBREVIATIONS
Date Issued
Sheet Title:
Drawing Number:
Progress Parkway, Schaumburg, IL 60173
Schaumburg 90 NDW Urban Park
Landscape Architect 888 South Michigan Avenue #1000, Chicago, IL 60605
p. 312.427.7240 w. www.site-design.com
V3 Companies Engineer 7325 Janes Avenue, Woodridge, IL 60517
p. 630.724.9200 w. www.v3co.com
Rev. #
File :
20096.PH2
Approved :
Drawn :
Project No :
Scale : AS NOTEDChecked :
C1.0 Gal 20096.PH2.dwg
08/09/202301 ISSUED FOR REVIEW
NRS
LAC
Description
X X
W
G
T/E
E
T
BENCHMARK
EASEMENT LINE
FENCE LINE
CENTERLINE
PROPERTY CORNER
UNDERGROUND TELEPHONE
& ELECTRIC DUCT BANK
BURIED CABLE-TELEPHONE
SOIL BORING
TELEPHONE MANHOLE
CONTOUR
SPOT ELEVATION
WATER MAIN
GAS MAIN
CURB INLET
UTILITY STUB
POST INDICATOR VALVE
THRUST BLOCK
CONCRETE HEADWALL
FLARED END SECTION (F.E.S.)
SUBMERGED HEADWALL
GUY WIRES
FLOOD LIGHT
FIRE HYDRANT
LIGHT STANDARD
IRRIGATION HEADS
SIGN
UTILITY POLE
UTILITY TO BE ABANDONED
FEATURE TO BE REMOVED
DESCRIPTION
STORMWATER FLOW DIRECTION
SANITARY SEWER
STORM SEWER
SILT FENCE
WATER MAIN PROTECTION
RAILROAD TRACKS
GUARDRAIL
HAND HOLE
GATE VALVE IN VALVE VAULT
REVISION DELINEATION
STORMWATER OVERFLOW ROUTE
VALVE IN VALVE BOX
DRAINAGE STRUCTURE WITH OPEN LID
SANITARY FORCE MAIN
PROPERTY LINE (EXTERIOR)
LOT LINE (INTERIOR)
TREE
TREE LINE
TRAFFIC SIGNAL POLE
TELEPHONE PEDESTAL
TRANSFORMER PAD
UTILITY STRUCTURE WITH CLOSED LID
RIGHT-OF-WAY LINE
MONITORING WELL
CONSTRUCTION LIMIT LINE
REVERSE PITCHED CURB
RETAINING WALL
TREE PROTECTION FENCE
CURB & GUTTER
DEPRESSED CURB & GUTTER
DITCH CHECK
BURIED CABLE-ELECTRIC
TOP OF CURB ELEVATION
EDGE OF PAVEMENT ELEVATION
UTILITY CROSSING LABEL
INLET FILTER BASKET
RIP RAP
BOLLARD
BACK OF CURB
CATCH BASIN
FIRE HYDRANT
BACK TO BACK OF CURB
B/C
B-B
BM
CURB AND GUTTERC & G
CB
DRAWING
DIWM DUCTILE IRON WATER MAIN
DIAMETER
F/G FINISHED GRADE
F-F FACE TO FACE OF CURB
F/L
FH
FES
FLOW LINE
FLARED END SECTION
G
GV/VB
GV/VV
HDPE
HORIZONTAL
HP
HWL
IE
HIGH POINT
HIGH WATER LEVEL
INVERT ELEVATION
INLET
LP
L LEFT
MH MANHOLE
NWL NORMAL WATER LEVEL
PCC
PI
PRC
POINT OF INTERSECTION
POINT OF REVERSE CURVATURE
POINT OF TANGENCY
PROPERTY LINE
POINT OF CURVATURE
POINT OF VERTICAL INTERSECTION
PVC
PT
PL
PC
PVI
R
RIGHT OF WAY
SFM
SHT
SANITARY FORCE MAIN
SHEET
STATION
STORM MANHOLE
SUBMERGED HEADWALLSHW
STMH
S
SAN
SMH
SANITARY
SANITARY MANHOLE
T
T/C
T/P TOP OF PIPE
TYP TYPICAL
VERTICAL
WATER MAINWM
ELEVATION
EJ EXPANSION JOINT
PP POWER POLE
PORTLAND CEMENT CONCRETE
VC VERTICAL CURVE
E
N NORTH
POINT OF VERTICAL CURVATURE
OR POLYVINYL CHLORIDE PIPE
SLOPE OR SOUTH
W WEST
OL OPEN LID
F & G FRAME & GRATE
TY TYPE
CL CLOSED LID
PUBLIC UTILITY EASEMENT
EAST OR ELECTRIC OR EDGE
E/P EDGE OF PAVEMENT
EXISTING
FINISHED FLOOR
GAS LINE
HDW HEADWALL
GATE VALVE IN VALVE BOX
GATE VALVE IN VALVE VAULT
HIGH DENSITY POLYETHYLENE PIPE
RCP REINFORCED CONCRETE PIPE
ST
TANGENT LENGTH OR TELEPHONE
LF LINEAL FEET
SF SILTATION FENCE
LOW POINT OR LIGHT POLE
BV/VV BUTTERFLY VALVE IN VALVE VAULT
BLDG BUILDING
IN
C
L
DIP DUCTILE IRON PIPE
EX.
PGL PROFILE GRADE LINE
PVT POINT OF VERTICAL TANGENCY
RADIUS OR RIGHT
CENTERLINE
NOT IN CONTRACT / NOT INCLUDED
TOP OF CURB
STORM STRUCTURE OR STORM SEWER
HDCP HANDICAP
ON CENTER
UP UTILITY POLE
MW MONITORING WELL
T/W TOP OF WALL
MATCH EXISTING
F & OL
F & CL FRAME & CLOSED LID
FRAME & OPEN LID
CO CLEAN OUT
B/P BOTTOM OF PIPE
A ARC LENGTH
OR POINT OF COMPOUND CURVE
VERT
STA
DIA
DWG
ELEV
FF
HOR
ME
NIC
OC
PUE
ROW
706.0
782.62
782.12
SF
CLL
VCP VITRIFIED CLAY PIPE
C01
PROPOSEDEXISTING
ATLAS LOCATED UTILITY
LEGEND ABBREVIATIONS
TRENCH BACKFILL
GENERAL NOTES
1. EXISTING SITE TOPOGRAPHY, UTILITIES, RIGHT-OF-WAY AND
HORIZONTAL CONTROL SHOWN ON THE DRAWINGS WERE
OBTAINED FROM A SURVEY PREPARED BY:
V3 COMPANIES, LTD.
7325 JANES AVENUE
WOODRIDGE, IL 60517
COPIES OF THE SURVEY ARE AVAILABLE FROM THE
SURVEYOR. SITE CONDITIONS MAY HAVE CHANGED SINCE THE
SURVEY WAS PREPARED. CONTRACTORS TO VISIT SITE TO
FAMILIARIZE THEMSELVES WITH THE CURRENT CONDITIONS.
2. ALL EXISTING TOPOGRAPHY, UNDERGROUND UTILITIES,
STRUCTURES AND ASSOCIATED FACILITIES SHOWN ON THESE
DRAWINGS HAVE BEEN PLOTTED FROM AVAILABLE SURVEYS
AND RECORDS. THEREFORE, THEIR LOCATIONS AND
ELEVATIONS MUST BE CONSIDERED APPROXIMATE ONLY.
THERE MAY BE OTHER FACILITIES, THE EXISTENCE OF WHICH
ARE NOT PRESENTLY KNOWN.
3. CONTRACTOR IS TO VERIFY ALL EXISTING STRUCTURES AND
FACILITIES AND NOTIFY ENGINEER OF ANY DISCREPANCIES
PRIOR TO ORDERING MATERIAL AND STARTING WORK.
4. ALL APPLICABLE PROVISIONS OF THE CURRENT
OCCUPATIONAL SAFETY AND HEALTH ACT ARE HEREIN
INCORPORATED BY REFERENCE.
5. THE CONTRACTOR SHALL SUBSCRIBE TO ALL GOVERNING
REGULATIONS AND SHALL OBTAIN ALL NECESSARY PUBLIC
AGENCY PERMITS PRIOR TO STARTING WORK. THE
CONTRACTOR, BY USING THESE PLANS FOR THEIR WORK,
AGREE TO HOLD HARMLESS V3 COMPANIES LTD., THE
MUNICIPALITY, THEIR EMPLOYEES AND AGENTS AND THE
OWNER WHILE ACTING WITHIN THE SCOPE OF THEIR DUTIES
FROM AND AGAINST ANY AND ALL LIABILITY, CLAIMS,
DAMAGES, AND THE COST OF DEFENSE ARISING OUT OF
CONTRACTOR(S) PERFORMANCE OF THE WORK DESCRIBED
HEREIN, BUT NOT INCLUDING THE SOLE NEGLIGENCE OF THE
OWNER, HIS AGENTS, THE ENGINEER, HIS EMPLOYEES AND
AGENTS.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING
ALL REQUIRED PERMITS FOR CONSTRUCTION ALONG OR
ACROSS EXISTING STREETS OR HIGHWAYS. CONTRACTOR
SHALL MAKE ARRANGEMENTS FOR THE PROPER BRACING,
SHORING AND OTHER REQUIRED PROTECTION OF ALL
ROADWAYS BEFORE CONSTRUCTION BEGINS. CONTRACTOR
SHALL BE RESPONSIBLE FOR ANY DAMAGE TO THE STREETS
OR ROADWAYS AND ASSOCIATED STRUCTURES AND SHALL
MAKE REPAIRS AS NECESSARY TO THE SATISFACTION OF THE
OWNER OF THE ROADWAY.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
INSTALLATION AND MAINTENANCE OF ADEQUATE SIGNS,
TRAFFIC CONTROL DEVICES AND WARNING DEVICES TO
INFORM AND PROTECT THE PUBLIC DURING ALL PHASES OF
CONSTRUCTION. BARRICADES AND WARNING SIGNS SHALL BE
PROVIDED IN ACCORDANCE WITH THE IDOT STANDARD
SPECIFICATIONS. ALL TRAFFIC CONTROL WORK SHALL BE
DONE IN ACCORDANCE WITH THE "MANUAL ON UNIFORM
TRAFFIC CONTROL DEVICES."
8. EXCEPT WHERE MODIFIED BY THE CONTRACT DOCUMENTS,
ALL WORK PROPOSED HEREON SHALL BE IN ACCORDANCE
WITH THE FOLLOWING SPECIFICATIONS WHICH ARE HEREBY
MADE A PART HEREOF:
a. "STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE
CONSTRUCTION" AS PREPARED BY IDOT, LATEST EDITION.
b. ”STANDARD SPECIFICATIONS FOR WATER AND SEWER MAIN
CONSTRUCTION IN ILLINOIS," LATEST EDITION.
c. ILLINOIS RECOMMENDED STANDARDS FOR SEWAGE
WORKS," AS PUBLISHED BY THE IEPA. LATEST EDITION.
d. THE LATEST EDITIONS OF THE MUNICIPAL CODE AND
STANDARDS OF THE VILLAGE OF SCHAUMBURG.
e. THE NATIONAL ELECTRIC CODE.
f. THE ILLINOIS ACCESSIBILITY CODE.
g. CLEAN CONSTRUCTION OR DEMOLITION DEBRIS (CCDD)
REQUIREMENTS AS PUBLISHED BY THE IEPA. TESTING OF
SOILS BEING EXPORTED FROM THE SITE AND APPROPRIATE
DISPOSAL SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
IN THE EVENT OF CONFLICTING SPECIFICATIONS WITH REGARD
TO SITE WORK ISSUES DESIGNED BY THE ENGINEER, THE
MORE STRINGENT REQUIREMENT SHALL GOVERN.
9. THE CONTRACTOR SHALL NOTIFY THE AUTHORITY HAVING
JURISDICTION AT LEAST 48 HOURS PRIOR TO COMMENCING
ANY WORK AND FOR ANY NEW CONSTRUCTION REQUIRING
INSPECTION.
10. ALL TREES TO BE SAVED SHALL BE IDENTIFIED PRIOR TO
CONSTRUCTION AND SHALL BE PROTECTED PER IDOT
STANDARDS. THE RIGHT-OF-WAY LINE AND LIMITS OF THE
CONTRACTOR'S OPERATIONS SHALL BE CLEARLY DEFINED
THROUGHOUT THE CONSTRUCTION PERIOD. ALL TREES
IDENTIFIED TO REMAIN SHALL BE PROTECTED FROM DAMAGE
INCLUDING TRUNKS, BRANCHES AND ROOTS. NO EXCAVATING,
FILLING OR GRADING IS TO BE DONE INSIDE THE DRIP LINE OF
TREES UNLESS OTHERWISE INDICATED.
11. CONSTRUCTION ACCESS POINTS TO THE SITE SHALL BE
PROTECTED IN SUCH A WAY AS TO PREVENT ACCUMULATION
OF MUD OR SOIL ON PUBLIC THOROUGHFARES. AT THE END OF
EACH DAY AND AS OFTEN AS OTHERWISE NECESSARY THE
CONTRACTOR SHALL CLEAN UP ALL MUD OR SOIL WHICH HAS
BEEN TRACKED ONTO PUBLIC STREETS AS REQUIRED BY THE
AUTHORITIES HAVING JURISDICTION AND AS DETAILED IN THE
STORM WATER POLLUTION PREVENTION PLAN.
12. THE CONTRACTOR SHALL PROVIDE FOR THE SAFE AND
ORDERLY PASSAGE OF TRAFFIC AND PEDESTRIANS WHERE
HIS/HER OPERATIONS ABUT PUBLIC THOROUGHFARES AND
ADJACENT PROPERTY IN ACCORDANCE WITH THE VILLAGE OF
SCHAUMBURG MUNICIPAL CODE AND IDOT REQUIREMENTS.
13. NO HOLES ARE TO BE LEFT OPEN IN THE PAVEMENT OR
PARKWAY OVER A HOLIDAY, WEEKEND OR AFTER 3:00 P.M. ON
THE DAY PRECEDING A HOLIDAY OR A WEEKEND.
14. ALL EXISTING PAVEMENT OR CONCRETE TO BE REMOVED
SHALL BE SAWCUT ALONG LIMITS OF PROPOSED REMOVAL
BEFORE COMMENCEMENT OF PAVEMENT REMOVAL.
15. REMOVED PAVEMENT, SIDEWALK, CURB AND GUTTER, ETC.
SHALL BE LEGALLY DISPOSED OF BY THE CONTRACTOR AS
PART OF THE BASE CONTRACT.
16. NO BURNING OR INCINERATION OF RUBBISH WILL BE
PERMITTED ON SITE.
17. FOR REGULATED UTILITY LOCATIONS, THE CONTRACTOR
SHALL CONTACT THE JOINT UTILITY LOCATION INFORMATION
FOR EXCAVATORS, "J.U.L.I.E." AT 1-800-892-0123. LOCAL
GOVERNMENT AGENCIES SHOULD BE CONTACTED BY THE
CONTRACTOR FOR LOCATION OF ALL NONREGULATED UTILITY
LOCATIONS. CALL FOR LOCATES AT LEAST 48 HOURS IN
ADVANCE OF CONSTRUCTION.
18. BEFORE EXCAVATING OVER OR ADJACENT TO ANY EXISTING
UTILITIES, CONTRACTOR SHALL NOTIFY THE OWNER OF SUCH
UTILITIES TO ENSURE THAT PROTECTIVE WORK WILL BE
COORDINATED AND PERFORMED BY THE CONTRACTOR IN
ACCORDANCE WITH THE REQUIREMENTS OF THE OWNER OF
THE UTILITY INVOLVED. IF ANY EXISTING SERVICE LINES,
UTILITIES AND UTILITY STRUCTURES WHICH ARE TO REMAIN IN
SERVICE ARE UNCOVERED OR ENCOUNTERED DURING THIS
OPERATION, THEY SHALL BE SAFEGUARDED, PROTECTED
FROM DAMAGE AND SUPPORTED IF NECESSARY.
19. THE CONTRACTOR IS RESPONSIBLE FOR HAVING A SET OF
"APPROVED" ENGINEERING PLANS WITH THE LATEST REVISION
DATE ON THE JOB SITE PRIOR TO THE START OF
CONSTRUCTION.
20. THE CONTRACTOR SHALL BE RESPONSIBLE FOR EROSION AND
SEDIMENTATION CONTROL AS DETAILED IN THE STORM WATER
POLLUTION PREVENTION PLAN.
21. ALL CURB RADII REFER TO BACK OF CURB.
22. ANY AREAS THAT ARE DISTURBED DURING CONSTRUCTION
SHALL BE RESTORED IN CONFORMANCE WITH THE
REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION
AND SHALL BE INCIDENTAL TO THE CONTRACT.
23. STREET PAVING AND CURBS TO REMAIN SHALL BE PROTECTED
FROM DAMAGE AND IF DAMAGED, SHALL BE REPLACED
PROMPTLY IN CONFORMANCE WITH THE MUNICIPALITY OR
IDOT STANDARD SPECIFICATIONS IN MATERIALS AND
WORKMANSHIP.
24. PROPOSED ELEVATIONS INDICATE FINISHED CONDITIONS. FOR
ROUGH GRADING ELEVATIONS ALLOW FOR THICKNESS OF
PROPOSED PAVING (ROADS, WALKS, DRIVES, ETC.) OR
TOPSOIL AS INDICATED ON DRAWINGS.
25. CAD FILES ARE AVAILABLE FOR CONSTRUCTION LAYOUT UPON
REQUEST.
26. BACKFILL SHALL BE PLACED NEXT TO THE CURB AS SOON AS
PERMISSIBLE AFTER CONSTRUCTION TO PREVENT SCOURING
AND UNDERCUTTING BY STORM WATER RUNOFF.
27. BUTT JOINTS SHALL BE PROVIDED WHEREVER NEW PAVEMENT
ABUTS EXISTING PAVEMENT. ALL BUTT JOINTS SHALL BE
CONSTRUCTED BY MILLING AND SHALL BE CONSIDERED
INCIDENTAL TO THE COST OF THE BITUMINOUS SURFACE
COURSE.
28. WHEN AN EXISTING DRAINAGE ROUTE, EITHER A STORM
SEWER OR WATERWAY, IS INTERRUPTED DUE TO
CONSTRUCTION, THE DRAINAGE ROUTE SHALL BE
REESTABLISHED TO ORIGINAL CONDITIONS BY THE END OF
THE SAME WORK DAY. POSITIVE DRAINAGE MUST BE
MAINTAINED AT ALL TIMES DURING CONSTRUCTION.
29. PROVIDE SMOOTH VERTICAL CURVES THROUGH HIGH AND
LOW POINTS INDICATED BY SPOT ELEVATIONS. PROVIDE
UNIFORM SLOPES BETWEEN NEW AND EXISTING GRADES.
AVOID RIDGES AND DEPRESSIONS.
30. FINAL ADJUSTMENT OF FIRE HYDRANTS, VALVE VAULTS AND
MANHOLES TO FINISHED GRADE ARE INCIDENTAL TO THEIR
COST.
31. ANY EXISTING UTILITY STRUCTURES REQUIRING ADJUSTMENT
ARE TO BE ADJUSTED OR RECONSTRUCTED BY THE
CONTRACTOR TO THE UTILITY OWNER'S SATISFACTION.
ADJUSTMENTS OR RECONSTRUCTIONS NOT CALLED FOR ON
THE PLANS SHALL BE CONSIDERED INCIDENTAL TO THE
CONTRACT.
32. ALL UTILITY CONNECTIONS TO EXISTING LINES SHALL BE
CONSTRUCTED IN ACCORDANCE WITH THE REGULATIONS AND
TO THE SATISFACTION OF THE UTILITY OWNER.
33. PROVIDE TRENCH BACKFILL IN ACCORDANCE WITH THE
DETAILS OF THE PLANS FOR ALL UTILITY LINES (OR AS
OTHERWISE NOTED ON PLANS). BACKFILL SHALL BE PLACED
AND COMPACTED PER THE SCHAUMBURG MUNICIPALITY AND
IDOT SPECIFICATIONS. COST OF BACKFILL IS TO BE
CONSIDERED INCIDENTAL TO THE UTILITY WORK.
34. ANY DAMAGE TO EXISTING UTILITIES SHALL BE REPAIRED AT
THE CONTRACTOR'S EXPENSE.
35. PRIOR TO DEMOBILIZATION, ALL WORK SHALL BE CLEANED
AND INSPECTED TO THE SATISFACTION OF THE AUTHORITY
HAVING JURISDICTION. THE COST OF THIS WORK SHALL BE
CONSIDERED INCIDENTAL TO THE CONTRACT.
36. THE GENERAL CONTRACTOR SHALL COORDINATE WITH
UTILITY COMPANIES TO PROVIDE CABLE TV, PHONE, ELECTRIC,
GAS AND IRRIGATION SERVICES. GENERAL CONTRACTOR
SHALL BE RESPONSIBLE FOR SECURING SITE LAYOUTS FOR
THESE UTILITIES AND SHALL COORDINATE AND PROVIDE
CONDUIT CROSSINGS AS REQUIRED. THIS COORDINATION
SHALL BE CONSIDERED INCIDENTAL TO THE CONTRACT. ANY
CONFLICTS IN UTILITIES SHALL BE CORRECTED BY THE
GENERAL CONTRACTOR AT NO ADDITIONAL COST TO THE
OWNER.
37. BAND-SEAL CONNECTORS OR EQUIVALENT SHALL BE USED TO
JOIN PIPES OF DISSIMILAR MATERIAL.
38. CONTRACTOR SHALL MAINTAIN ACCURATE RECORDS OF ALL
CONSTRUCTION IN CONFORMANCE WITH ALL MUNICIPAL AND
CLIENT REQUIREMENTS FOR USE IN PREPARING RECORD
DRAWINGS.
39. THE SUBCONTRACTOR SHALL INSTALL A 2”x4”x6' POST
ADJACENT TO THE TERMINUS OF UTILITY MAINS AND SERVICE
LINES. POSTS SHALL BE MARKED IN ACCORDANCE WITH THE
VILLAGE STANDARDS.
40. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DEWATERING
ANY EXCAVATION. ANY DEWATERING REQUIRED SHALL BE
INCIDENTAL TO THE CONTRACT.
41. COPIES OF SOILS INVESTIGATION REPORTS MAY BE OBTAINED
FROM THE OWNER. ANY BRACING, SHEETING OR SPECIAL
CONSTRUCTION METHODS REQUIRED IN ORDER TO INSTALL
THE PROPOSED IMPROVEMENTS SHALL BE CONSIDERED
INCIDENTAL TO THE COST OF THE PROJECT. ANY ADDITIONAL
SOILS DATA NEEDED TO CONFIRM THE CONTRACTOR'S
OPINIONS OF THE SUBSOIL CONDITIONS SHALL BE DONE AT
THE CONTRACTOR'S EXPENSE. THE CONTRACTOR SHALL
OBTAIN THE OWNER'S WRITTEN AUTHORIZATION TO ACCESS
THE SITE TO CONDUCT A SUPPLEMENTAL SOILS
INVESTIGATION.
42. ALL FIELD TILE ENCOUNTERED DURING CONSTRUCTION
OPERATIONS SHALL BE CONNECTED TO THE PROPOSED
STORM SEWER OR EXTENDED TO OUTLET INTO A PROPOSED
DRAINAGE WAY AS DETERMINED BY THE ENGINEER. IF THIS
CANNOT BE ACCOMPLISHED, THEN IT SHALL BE REPAIRED
WITH NEW PIPE OF SIMILAR SIZE AND MATERIAL TO THE
ORIGINAL LINE AND PUT IN ACCEPTABLE OPERATIONAL
CONDITION. A RECORD OF THE LOCATION OF ALL FIELD TILE
FOR ON-SITE DRAIN PIPE ENCOUNTERED SHALL BE KEPT BY
THE SUBCONTRACTOR AND SUBMITTED TO THE ENGINEER
UPON COMPLETION OF THE PROJECT. ALL FIELD TILE REPAIRS
SHALL BE CONSIDERED AS INCIDENTAL TO THE CONTRACT
AND NO ADDITIONAL COMPENSATION WILL BE PROVIDED.
43. THE ENGINEER AND OWNER ARE NOT RESPONSIBLE FOR THE
CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES
OR PROCEDURES, TIME OF PERFORMANCE, PROGRAMS OR
FOR ANY SAFETY PRECAUTIONS USED BY THE CONTRACTOR.
THE CONTRACTOR IS SOLELY RESPONSIBLE FOR EXECUTION
OF HIS/HER WORK IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS AND SPECIFICATIONS.
SPECIFICATIONS
WATERMAIN DISTRIBUTION SYSTEM
1. WATER MAIN SHALL BE CONSTRUCTED OF THE
FOLLOWING MATERIAL AS SPECIFIED ON THE PLANS:
A. DUCTILE IRON PIPE, CLASS 52 CONFORMING TO ANSI
A21.51, AWWA C-151 WITH CEMENT LINING
CONFORMING TO ANSI A21.4, AWWA C-104 AND
PUSH-ON JOINTS CONFORMING TO ANSI A21.11,
AWWA C-111. FITTINGS SHALL COMPLY WITH ANSI
A21.10, AWWA C110. ALL DUCTILE IRON PIPE SHALL
BE WRAPPED IN POLYETHYLENE IN ACCORDANCE
WITH AWWA C105.
B. WATER SERVICE LINES SHALL BE CONSTRUCTED OF
CLASS K COPPER.
2. MINIMUM COVER OVER WATER MAIN SHALL BE 5' - 6”
FROM FINISHED GRADE TO TOP OF PIPE.
3. VALVE VAULTS SHALL BE USED AT ALL VALVE LOCATIONS
WHERE WATER MAIN IS 8” DIAMETER OR LARGER.
VAULTS SHALL BE PRECAST CONCRETE STRUCTURES,
WITH APPROPRIATE FRAME AND LIDS (SEE
CONSTRUCTION DETAIL SHEETS). LIDS SHALL BE
IMPRINTED “WATER”.
4. THRUST BLOCKING OR RESTRAINED JOINTS SHALL BE
INSTALLED ON WATER MAINS AT ALL BENDS, TEES,
ELBOWS, ETC. AS REQUIRED BY THE AUTHORITY HAVING
JURISDICTION. COST OF SAME SHALL BE INCIDENTAL TO
THE UNIT PRICE FOR PIPE INSTALLED.
5. WATER MAIN FITTINGS (BENDS, ELBOWS, TEES,
INCREASES, REDUCERS, ETC.) MAY OR MAY NOT BE
SPECIFICALLY REFERENCED ON THE CONSTRUCTION
PLANS. THEY ARE TO BE CONSIDERED AS INCIDENTAL
AND INCLUDED IN THE LINEAL FOOTAGE COST OF THE
WATER MAIN.
6. ALL WATER LINES ARE TO BE PRESSURE TESTED AND
CHLORINATED PER THE REQUIREMENTS OF THE
MUNICIPALITY AND THE ILLINOIS ENVIRONMENTAL
PROTECTION AGENCY.
IEPA CROSSING REQUIREMENTS
1. HORIZONTAL SEPARATION:
A. WATERMAINS SHALL BE LAID AT LEAST TEN FEET
HORIZONTALLY FROM ANY EXISTING OR PROPOSED
DRAIN, STORM SEWER, SANITARY SEWER OR SEWER
SERVICE CONNECTION.
B. WATERMAINS MAY BE LAID CLOSER THAN TEN FEET
TO A SEWER LINE WHEN:
I. LOCAL CONDITIONS PREVENT A LATERAL
SEPARATION OF TEN FEET;
II. THE WATERMAIN IS AT LEAST 18 INCHES ABOVE
THE CROWN OF THE SEWER; AND
III. THE WATERMAIN IS EITHER IN A SEPARATE
TRENCH OR IN THE SAME TRENCH ON AN
UNDISTURBED EARTH SHELF LOCATED TO ONE
SIDE OF THE SEWER.
C. BOTH THE WATERMAIN AND DRAIN OR SEWER SHALL
BE CONSTRUCTED OF SLIP-ON OR MECHANICAL
JOINT CAST OR DUCTILE IRON PIPE, PRESTRESSED
CONCRETE PIPE, OR PVC PIPE MEETING THE
REQUIREMENTS OF SECTION 653.111 WHEN IT IS
IMPOSSIBLE TO MEET (A) OR (B) ABOVE. THE DRAIN
OR SEWER SHALL BE PRESSURE TESTED TO THE
MAXIMUM EXPECTED SURCHARGE HEAD BEFORE
BACKFILLING.
2. VERTICAL SEPARATION:
A. WATERMAIN SHALL BE LAID SO THAT ITS INVERT IS 18
INCHES ABOVE THE CROWN OF THE DRAIN OR
SEWER WHENEVER WATERMAINS CROSS STORM
SEWERS, SANITARY SEWERS OR SEWER SERVICE
CONNECTIONS. THE VERTICAL SEPARATION SHALL
BE MAINTAINED FOR THAT PORTION OF THE
WATERMAIN LOCATED WITHIN TEN FEET
HORIZONTALLY OR ANY SEWER OR DRAIN CROSSED.
A LENGTH OF WATERMAIN PIPE SHALL BE CENTERED
OVER THE SEWER TO BE CROSSED WITH JOINTS
EQUIDISTANT FROM THE SEWER OR DRAIN.
B. BOTH THE WATERMAIN AND SEWER SHALL BE
CONSTRUCTED OF SLIP-ON OR MECHANICAL JOINT
CAST OR DUCTILE IRON PIPE, PRESTRESSED
CONCRETE PIPE, OR PVC PIPE MEETING
REQUIREMENTS OF SECTION 653.111 WHEN:
I. IT IS IMPOSSIBLE TO OBTAIN THE PROPER
VERTICAL SEPARATION AS DESCRIBED IN (A)
ABOVE; OR
II. THE WATERMAIN PASSES UNDER A SEWER
DRAIN.
C. A VERTICAL SEPARATION OF 18 INCHES BETWEEN THE
INVERT OF THE SEWER OR DRAIN AND THE CROWN OF THE
WATERMAIN SHALL BE MAINTAINED WHERE A WATERMAIN
CROSSES UNDER A SEWER. SUPPORT THE SEWER OR DRAIN
LINES TO PREVENT SETTLING AND BREAKING THE
WATERMAIN.
D. CONSTRUCTION SHALL EXTEND ON EACH SIDE OF THE
CROSSING UNTIL THE NORMAL DISTANCE FROM THE
WATERMAIN TO THE SEWER OR DRAIN LINE IS AT
LEAST TEN FEET.
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text 706.00
AutoCAD SHX Text W
AutoCAD SHX Text G
AutoCAD SHX Text T/E
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text x
AutoCAD SHX Text
SF
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text x
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text V V V V V
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text 12"
AutoCAD SHX Text 12"
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
TP
AutoCAD SHX Text
TP
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text 782.62
AutoCAD SHX Text 782.12
AutoCAD SHX Text
W A
T E
R S
T U
B
E L E
C T
R I C
V A
U L T
W V
V
R
IM
.6
U N
A B
L E
T O
O P
E N
A S
P H
A L T
S E
A L E
D
W V
V
R
IM
.0
U N
A B
L E
T O
O P
E N
A S
P H
A L T
S E
A L E
D
W V
V
R
IM
.7
T /P
IP
E
E -W
N
.3
W V
V
R
IM
.7
T /P
IP
E
E -W
.8
#11190
W V
V
R
IM
.3
T /P
IP
E
E -W
.4
S C
C
S C
C
W V
V
R
IM
.5
(T /P
IP
E
.5
W V
V
R
IM
.9
(T /P
IP
E
.4
W V
V
R
IM
.5
(T /P
IP
E
.4
W V
V
R
IM
.2
(T /P
IP
E
.5
F M
N
F M
N
F M
N
F I R
F I
S B
M
E L E
V
S B
M
E L E
V
B E
N C
H M
A R
K
B
Y
O
T H
E R
S
L I S
T E
D
M E
A S
U R
E D
P
A
R
K
S
I D
E
I V
E
P R
O G
R E
S
P
A R
K W
A Y
N O
B
U I L D
I N
G
X I S
T I N
G
O
N
S U
R V
E Y
P
O
P E
R T
Y
F M
N
F M
N
F C
C
S C
C
F C
C
S C
C
O
N
L
Y
O
N
L
Y
O N
L Y
A
S
P
H
A
L
T
A S
P H
A L T
A S
P H
A L T
PROPOSED 3" WATER SERVICE
SEE IRRIGATION PLANS
FOR CONTINUATION
PROPOSED 2" WATER SERVICE
SEE IRRIGATION PLANS
FOR CONTINUATION
LOCATION OF BOOSTER PUMP
SEE IRRIGATION PLANS
FOR DETAILS
LOCATION OF BOOSTER PUMP
SEE IRRIGATION PLANS
FOR DETAILS
PROPOSED 12" WATER STUB
FOR FUTURE CONNECTION
CONNECT TO EXISTING
12" WATER STUB
CONNECT TO EXISTING
8" WATER STUB
INSTALL 8"X3" REDUCER
**CAUTION:
PROPOSED WATERMAIN
TO CROSS EXISTING
STORM SEWER
B/P STM = 725.50
T/P WAT = 724.00
2' VALVE IN B-BOX
2" BLOW OFF WITH
THREADED PLUG ON
EXTENSION IN B-BOX
2' VALVE IN B-BOX
2" BLOW OFF WITH
THREADED PLUG ON
EXTENSION IN B-BOX
DIRECTIONAL BORE UNDER
EXISTING SIDEWALK
DIRECTIONAL BORE UNDER
EXISTING SIDEWALK
C2.0 N:\2020\20096\20096.PH2\Drawings\ACAD\LD\S04\Sheet Drawings\C2..0 Util20096.PH2.dwg
OVERALL UTILITY SHEET
Date Issued
Sheet Title:
Drawing Number:
Progress Parkway, Schaumburg, IL 60173
Schaumburg 90 NDW Urban Park site design group, ltd. Landscape Architect 888 South Michigan Avenue #1000, Chicago, IL 60605
p. 312.427.7240 w. www.site-design.com
V3 Companies Engineer 7325 Janes Avenue, Woodridge, IL 60517
p. 630.724.9200 w. www.v3co.com
ISSUANCES
Rev. #
File :
20096.PH2
Approved :
Drawn :
Project No :
Scale : AS NOTEDChecked :
C2..0 Util20096.PH2.dwg
08/09/202301 ISSUED FOR REVIEW
NRS
LAC
Description
GRAPHIC SCALE
METER BOX BY
IRRIGATION
CONTRACTOR
BOOSTER PUMP BY
IRRIGATION
CONTRACTOR
CONTINUED BY IRRIGATION
CONTRACTOR-SEE PLANS BY OTHERS
VALVE BOX
CONCRETE BLOCK
WATER MAIN
SCREW TYPE ADJUSTMENTS
FOR DEPTH. IN PAVEMENT
USE SLIDE TYPE ADJUSTMENTS
C.I. VALVE BOX
"WATER" ON LID
M I N
I M
U M
D
E P
T H
M
I N
C
O V
E R
2' VALVE IN B-BOX
SEE DETAIL THIS SHEET.
2" BLOW OFF WITH THREADED
PLUG ON AN EXTENSION TO SURFACE,
IN 12"X18" IRRIGATION VALVE BOX.
SEE PLANS ABOVE FOR
CONNECTION
NOTES:
1. CONNECTION TO MAIN, 2' VALVE BOX
AND 2" BLOW OFF BY SITE UTILITY
CONTRACTOR.
2. ABOVE GROUND WORK, INCLUDING
METER BOX AND BOOSTER PUMP BY
IRRIGATION CONTRACTOR. SEE
IRRIGATION PLANS BY OTHERS.
AutoCAD SHX Text 1" =
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
50'
| C0.0 Title Sheet |
| C1.0 Notes and Specs |
| C2.0 Overall Utility Sheet |