BUS 402
BUS 394
SEE
ONE-LINE
BLDG 42
ARC FLASH UTILITY ONLY
DANGEROUS !!
CATEGORY 4
CATEGORY 3
CATEGORY 2
CATEGORY 1
CONNECTS TO
BUS 402. ON
ONE-LINE 13800
CORALVILLE
IOWA CITY
13800
CATEGORY 0
SEE
ONE-LINE
BLDG 41
SEE
ONE-LINE
BLDG 40
SEE ONE-LINE
7MPD, CHILLER 3,4&5
AND CHILLER GEN
SEE
ONE-LINE
7MPD, CHILLER 3,4&5
AND CHILLER GEN
SEE
ONE-LINE
SECTION B
(LV SWGR NORTH)
SEE ONE-LINE
SECTION A
(LV SWGR SOUTH)
SEE ONE-LINE
PANEL MPD AND
EMERGENCY GEN
SEE ONE-LINE
USB AND
EMERGENCY GEN
CONNECTS TO
BUS 402. ON
ONE-LINE 13800
Mid Am IOWA CITY Rated Voltage 13800 V SC Contribution 3P 5600.0 Amps SC Contribution SLG 4095.0 Amps
001 UTIL REL
Manufacturer ABB Frame/Model CO-11 CT Ratio 600 / 5 A Settings Tap (4-12A) 4 (480A) Time Dial (0.5-11) 0.5
INST (10-40A) 10 (1200A)
CBL-0001
CableSize 500 AWG/kcmil QtyPerPhase 1 Length 950.0 ft Ampacity 465.0 A
OO1 UTIL BUS
IncidentEnergy 0.44 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.489 kA BoltedFault 5.600 kA SystemNominalVoltage 13800.0 V
Iowa City Main B3 Manufacturer Phase: SEL Ground: SEL Frame/Model Phase: SEL-351-6 Ground: SEL-351 CT Ratio Phase CT: 300 / 5 Ground CT: 300 / 5 A Settings Phase 51PP(0.25-16.0 x CTR) 7 (420A) U4, Extremely Inverse 3 Ground 51GP(0.1-16.0 x CTR) 2.8 (168A) U4, Extremely Inverse 3 IOWA CITY BUS
IncidentEnergy 0.43 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.330 kA BoltedFault 5.435 kA SystemNominalVoltage 13800.0 V
Building 16 Boiler Plant Manufacturer Phase: SEL Neutral: SEL Frame/Model Phase: SEL-351A Neutral: SEL-351A CT Ratio Phase CT: 300 / 5 Neutral CT: 50 / 5 A Settings Phase 51PP(0.25-16.0 x CTR) 3.2 (192A) U4, Extremely Inverse 2 Neutral 51NP(0.5-16.0 x CTR) 14 (140A) U4, Extremely Inverse 1
CBL-0002
CableSize 2 AWG/kcmil QtyPerPhase 1 Length 600.0 ft Ampacity 155.0 A
004 CLF 30E
Manufacturer CUTLER-HAMMER Frame/Model CLE, 30E Frame/Rating 30.0 A InterruptingRating 50.0 kA Sensor/Trip 30.0 A Settings
30.0 Amps
S
P BLDG 16 XFMR
Nominal kVA 300.0 kVA Pri RatedVoltage 13800 V Sec RatedVoltage 480 V Z% 5.0000 %
HV BLDG 16 XFMR
IncidentEnergy 0.06 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.144 kA BoltedFault 5.243 kA SystemNominalVoltage 13800.0 V
South Transformer T3 Manufacturer Phase: SEL Neutral: SEL Frame/Model Phase: SEL-351A Neutral: SEL-351A CT Ratio Phase CT: 300 / 5 Neutral CT: 50 / 5 A Settings Phase 51PP(0.25-16.0 x CTR) 3.2 (192A) U4, Extremely Inverse 2 Neutral 51NP(0.5-16.0 x CTR) 14 (140A) U4, Extremely Inverse 1
CBL-0004
CableSize 2 AWG/kcmil QtyPerPhase 1 Length 573.0 ft Ampacity 155.0 A
008 SM-4 200E
Manufacturer S&C Frame/Model SM-4, 200E Frame/Rating 200.0 A InterruptingRating 12.5 kA Sensor/Trip 200.0 A Settings 200 Amps
S
P BLDG 1 XFMR (SOUTH)
Nominal kVA 1500.0 kVA Pri RatedVoltage 13800 V Sec RatedVoltage 480 V Z% 5.8600 %
HV T-3 (SOUTH)
IncidentEnergy 0.36 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.153 kA BoltedFault 5.252 kA SystemNominalVoltage 13800.0 V
LV T-3 (SOUTH)
IncidentEnergy 100.15 Cal/cm^2 PPE Category Dangerous!
AF_ArcingFault 14.628 kA BoltedFault 25.580 kA SystemNominalVoltage 480.0 V
CHILLER #3 BUILDING 7
Manufacturer Phase: SEL Neutral: SEL Frame/Model Phase: SEL-351A Neutral: SEL-351A CT Ratio Phase CT: 300 / 5 Neutral CT: 50 / 5 A Settings Phase 51PP(0.25-16.0 x CTR) 4 (240A) U4, Extremely Inverse 3 Neutral 51NP(0.5-16.0 x CTR) 14 (140A) U4, Extremely Inverse 1
CBL-0005
CableSize 2 AWG/kcmil QtyPerPhase 1 Length 83.0 ft Ampacity 155.0 A
010 CS-3 100E
Manufacturer GOULD SHAWMUT Frame/Model CS-3, 100E Frame/Rating 100.0 A InterruptingRating 50.0 kA Sensor/Trip 100.0 A Settings 100 Amps
S
P CHILLER 3 XFMR
Nominal kVA 1500.0 kVA Pri RatedVoltage 13800 V Sec RatedVoltage 480 V Z% 5.9000 %
HV CHILLER 3 XFMR
IncidentEnergy 0.11 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.484 kA BoltedFault 5.595 kA SystemNominalVoltage 13800.0 V
LV CHILLER 3 XFMR
IncidentEnergy 100.56 Cal/cm^2 PPE Category Dangerous!
AF_ArcingFault 14.684 kA BoltedFault 25.695 kA SystemNominalVoltage 480.0 V
1-7L TIE2 BKR
Manufacturer SQUARE D Frame/Model VAD-2-15100-12 Frame/Rating 1200.0 A InterruptingRating 37.0 kA Sensor/Trip 0.0 A Plug 0.0 A Settings
001 GEN BUS
IncidentEnergy 0.43 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.329 kA BoltedFault 5.434 kA SystemNominalVoltage 13800.0 V
CBL-0007
CableSize 1200 AWG/kcmil QtyPerPhase 1 Length 5.0 ft Ampacity 1200.0 A
Main Generator Manufacturer Voltage Restraint: SEL Ground: SEL Frame/Model Voltage Restraint: SEL-300G Ground: SEL-300G CT Ratio Voltage Restraint CT: 300 / 5 A Ground CT: 300 / 5 A Settings Voltage Restraint 51VP(0.25-16.0 x CTR) 3.5 (210A) U4, Extremely Inverse 5 Ground 51GP(0.1-16.0 x CTR) 3 (180A) U4, Extremely Inverse 2
CBL-0008
CableSize 2 AWG/kcmil QtyPerPhase 1 Length 54.0 ft Ampacity 150.0 A
003 GEN BUS
IncidentEnergy 0 Cal/cm^2 PPE Category AF_ArcingFault 0.000 kA BoltedFault 0.000 kA SystemNominalVoltage 13800.0 V
BERTHA
BaseVoltage 13800 V Rated kW 2500.0 kW
Op en
1-9L TIE2 BKR
Manufacturer SQUARE D Frame/Model VAD-2-15100-12 Frame/Rating 1200.0 A InterruptingRating 37.0 kA Sensor/Trip 0.0 A Plug 0.0 A Settings
CBL-0009
CableSize 1200 AWG/kcmil QtyPerPhase 1 Length 5.0 ft Ampacity 1200.0 A
CORALVILLE BUS
IncidentEnergy 0.45 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.511 kA BoltedFault 5.623 kA SystemNominalVoltage 13800.0 V
Mid Am CORALVILLE Rated Voltage 13800 V SC Contribution 3P 5800.0 Amps SC Contribution SLG 4300.0 Amps
001 UTIL REL1
Manufacturer ABB Frame/Model CO-11 CT Ratio 600 / 5 A Settings Tap (4-12A) 4 (480A) Time Dial (0.5-11) 0.5
INST (10-40A) 10 (1200A)
CBL-0010
CableSize 500 AWG/kcmil QtyPerPhase 1 Length 950.0 ft Ampacity 465.0 A
000 UTIL2 BUS
IncidentEnergy 0.46 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.682 kA BoltedFault 5.800 kA SystemNominalVoltage 13800.0 V
2-12L MAIN2 R
Manufacturer Phase: SEL Ground: SEL Frame/Model Phase: SEL-351-6 Ground: SEL-351 CT Ratio Phase CT: 300 / 5 Ground CT: 300 / 5 A Settings Phase 51PP(0.25-16.0 x CTR) 7 (420A) U4, Extremely Inverse 3 Ground 51GP(0.1-16.0 x CTR) 2.8 (168A) U4, Extremely Inverse 3
BLDG 20/40/41/42
Manufacturer Phase: SEL Neutral: SEL Frame/Model Phase: SEL-351A Neutral: SEL-351A CT Ratio Phase CT: 300 / 5 Neutral CT: 50 / 5 A Settings Phase 51PP(0.25-16.0 x CTR) 3.2 (192A) U4, Extremely Inverse 2 Neutral 51NP(0.5-16.0 x CTR) 14 (140A) U4, Extremely Inverse 1
CBL-0011
CableSize 2 AWG/kcmil QtyPerPhase 1 Length 600.0 ft Ampacity 155.0 A
013 CLF 30E
Manufacturer CUTLER-HAMMER Frame/Model CLE, 30E Frame/Rating 30.0 A InterruptingRating 50.0 kA Sensor/Trip 30.0 A Settings
30.0 Amps
BLDG 2 (T2 ARF)
Manufacturer Phase: SEL Neutral: SEL Frame/Model Phase: SEL-351A Neutral: SEL-351A CT Ratio Phase CT: 300 / 5 Neutral CT: 50 / 5 A Settings Phase 51PP(0.25-16.0 x CTR) 3.2 (192A) U4, Extremely Inverse 2 Neutral 51NP(0.5-16.0 x CTR) 14 (140A) U4, Extremely Inverse 1
CBL-0012
CableSize 2 AWG/kcmil QtyPerPhase 1 Length 500.0 ft Ampacity 155.0 A
015 EJ0-1 20E
Manufacturer GE Frame/Model EJO-1, 20E Frame/Rating 20.0 A InterruptingRating 50.0 kA Sensor/Trip 20.0 A Settings 20 Amps
HV T-2
IncidentEnergy 0.07 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.347 kA BoltedFault 5.452 kA SystemNominalVoltage 13800.0 V
S
P T-2 Nominal kVA 300.0 kVA Pri RatedVoltage 13800 V Sec RatedVoltage 208 V Z% 5.1200 %
LV T-2
IncidentEnergy 48.99 Cal/cm^2 PPE Category Dangerous!
AF_ArcingFault 5.935 kA BoltedFault 15.565 kA SystemNominalVoltage 208.0 V
NORTH TRANSFORMER T4
Manufacturer Phase: SEL Neutral: SEL Frame/Model Phase: SEL-351A Neutral: SEL-351A CT Ratio Phase CT: 300 / 5 Neutral CT: 50 / 5 A Settings Phase 51PP(0.25-16.0 x CTR) 3.2 (192A) U4, Extremely Inverse 2 Neutral 51NP(0.5-16.0 x CTR) 14 (140A) U4, Extremely Inverse 1
CBL-0013
CableSize 2 AWG/kcmil QtyPerPhase 1 Length 573.0 ft Ampacity 155.0 A
017 SM-4 200E
Manufacturer S&C Frame/Model SM-4, 200E Frame/Rating 200.0 A InterruptingRating 12.5 kA Sensor/Trip 200.0 A Settings 200 Amps
017 T-4 PRI
IncidentEnergy 0.36 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.322 kA BoltedFault 5.426 kA SystemNominalVoltage 13800.0 V
S
P NORTH XFMR T-4
Nominal kVA 1500.0 kVA Pri RatedVoltage 13800 V Sec RatedVoltage 480 V Z% 5.9000 %
018 T-4 SEC
IncidentEnergy 91.72 Cal/cm^2 PPE Category Dangerous!
AF_ArcingFault 13.486 kA BoltedFault 23.258 kA SystemNominalVoltage 480.0 V
T-1 CHILLER 4 & 5
Manufacturer Phase: SEL Neutral: SEL Frame/Model Phase: SEL-351A Neutral: SEL-351A CT Ratio Phase CT: 300 / 5 Neutral CT: 50 / 5 A Settings Phase 51PP(0.25-16.0 x CTR) 4 (240A) U4, Extremely Inverse 3 Neutral 51NP(0.5-16.0 x CTR) 14 (140A) U4, Extremely Inverse 1
CBL-0014
CableSize 2 AWG/kcmil QtyPerPhase 1 Length 200.0 ft Ampacity 155.0 A
019 CS-3 100E
Manufacturer GOULD SHAWMUT Frame/Model CS-3, 100E Frame/Rating 100.0 A InterruptingRating 50.0 kA Sensor/Trip 100.0 A Settings 100 Amps
HV CHILLER XFMR
IncidentEnergy 0.11 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.447 kA BoltedFault 5.556 kA SystemNominalVoltage 13800.0 V
S
P XFMR CHILLER 4&5 / ADMIN BLDG
Nominal kVA 2500.0 kVA Pri RatedVoltage 13800 V Sec RatedVoltage 480 V Z% 6.1300 %
LV CHILLER XFMR
IncidentEnergy 155.33 Cal/cm^2 PPE Category Dangerous!
AF_ArcingFault 17.258 kA BoltedFault 37.547 kA SystemNominalVoltage 480.0 V
CLINICAL ADDITION USB
Manufacturer Phase: SEL Neutral: SEL Frame/Model Phase: SEL-351A Neutral: SEL-351A CT Ratio Phase CT: 300 / 5 Neutral CT: 50 / 5 A Settings Phase 51PP(0.25-16.0 x CTR) 4 (240A) U4, Extremely Inverse 3 Neutral 51NP(0.5-16.0 x CTR) 14 (140A) U4, Extremely Inverse 1
CBL-0015
CableSize 2 AWG/kcmil QtyPerPhase 1 Length 151.0 ft Ampacity 155.0 A
021 CS-3 100E
Manufacturer GOULD SHAWMUT Frame/Model CS-3, 100E Frame/Rating 100.0 A InterruptingRating 50.0 kA Sensor/Trip 100.0 A Settings 100 Amps
HV USS XFMR
IncidentEnergy 0.11 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.284 kA BoltedFault 5.388 kA SystemNominalVoltage 13800.0 V
S
P USS XFMR
Nominal kVA 1500.0 kVA Pri RatedVoltage 13800 V Sec RatedVoltage 480 V Z% 5.9000 %
LV USS XFMR
IncidentEnergy 100 Cal/cm^2 PPE Category Dangerous!
AF_ArcingFault 14.608 kA BoltedFault 25.538 kA SystemNominalVoltage 480.0 V
HVSW T3
IncidentEnergy 0.41 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.153 kA BoltedFault 5.252 kA SystemNominalVoltage 13800.0 V
CBL-0147
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
HVSW T11IncidentEnergy 0.44 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.485 kA BoltedFault 5.596 kA SystemNominalVoltage 13800.0 V
CBL-0148
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
HVSW T4
IncidentEnergy 0.43 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.322 kA BoltedFault 5.427 kA SystemNominalVoltage 13800.0 V
CBL-0149
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
HVSW T020
IncidentEnergy 0.44 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.447 kA BoltedFault 5.557 kA SystemNominalVoltage 13800.0 V
CBL-0150
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
HVSW T022
IncidentEnergy 0.43 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.285 kA BoltedFault 5.388 kA SystemNominalVoltage 13800.0 V
HVSW T2
IncidentEnergy 0.43 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.347 kA BoltedFault 5.453 kA SystemNominalVoltage 13800.0 V
CBL-0152
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
HVSW T014
IncidentEnergy 0.43 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.313 kA BoltedFault 5.417 kA SystemNominalVoltage 13800.0 V
CBL-0153
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
HVSW T005
IncidentEnergy 0.41 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.145 kA BoltedFault 5.243 kA SystemNominalVoltage 13800.0 V
CBL-0155
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
HV XFMR 20/40/41/42
IncidentEnergy 0.06 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.312 kA BoltedFault 5.417 kA SystemNominalVoltage 13800.0 V
S
P XFMR 20/40/41/42
Nominal kVA 300.0 kVA Pri RatedVoltage 13800 V Sec RatedVoltage 480 V Z% 5.0000 %
LV XFMR 20/40/41/42
IncidentEnergy 38.73 Cal/cm^2 PPE Category 4 AF_ArcingFault 4.775 kA BoltedFault 6.897 kA SystemNominalVoltage 480.0 V
CBL-0080
CableSize 750 AWG/kcmil QtyPerPhase 1 Length 290.0 ft Ampacity 535.0 A
SOUTH MAIN BKR
Manufacturer SQUARE D Frame/Model NW20H Frame/Rating 2000.0 A InterruptingRating 100.0 kA Sensor/Trip 2000.0 A Plug 0.0 A Settings
LTPU (A);LTD 1 (2000A); 12
STPU 4 (8000A)
STD 0.3 (I^2t Out)
INST (NW**N) 8 (16000A)
CBL-0017
CableSize 2000 AWG/kcmil QtyPerPhase 1 Length 8.0 ft Ampacity 2000.0 A
SECTION A LV SWGR SOUTH
IncidentEnergy 15.97 Cal/cm^2 PPE Category 3 AF_ArcingFault 14.586 kA BoltedFault 25.495 kA SystemNominalVoltage 480.0 V
CBL-0006
CableSize 3000 AWG/kcmil QtyPerPhase 1 Length 100.0 ft Ampacity 3000.0 A
CHILLER 3 MAIN
Manufacturer WESTINGHOUSE Frame/Model DS-632 Frame/Rating 3200.0 A InterruptingRating 65.0 kA Sensor/Trip 2400.0 A Plug 0.0 A Settings
LTPU 1.0 (2400A)
LTD 4.0
STPU 4.0 (9600A)
STD-I2T 0.3 (I^2t Out)
CHILLER 3 PANEL
IncidentEnergy 16.13 Cal/cm^2 PPE Category 3 AF_ArcingFault 14.306 kA BoltedFault 24.923 kA SystemNominalVoltage 480.0 V
CBL-0077
CableSize 3/0 AWG/kcmil QtyPerPhase 2 Length 200.0 ft Ampacity 450.0 A
CBL-0143
CableSize 350 AWG/kcmil QtyPerPhase 2 Length 200.0 ft Ampacity 700.0 A
16-1 TKMA 800A
Manufacturer GE Frame/Model TKMA Frame/Rating 800.0 A InterruptingRating 42.0 kA Sensor/Trip 800.0 A Plug 0.0 A Settings Thermal Curve (Fixed) INST (3-8 x Trip) 5 (4000A)
CBL-0159
CableSize 800 AWG/kcmil QtyPerPhase 1 Length 5.0 ft Ampacity 800.0 A
PNL BLDG2
IncidentEnergy 0.79 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.007 kA BoltedFault 15.402 kA SystemNominalVoltage 208.0 V
SECTION B NORTH MAIN BKR
Manufacturer ITE Frame/Model K-2000 Frame/Rating 2000.0 A InterruptingRating 65.0 kA Sensor/Trip 2000.0 A Plug 2000.0 A Settings LTPU (0.5-1.0 x P) 1 (2000A) LTD (2-24 Sec.) 15 STPU (2-10 x LTPU) 3 (6000A) STD (0.1-0.5 Sec.) 0.1 (I^2t In) INST (2-12 x P) M1 (16000A)
CBL-0019
CableSize 2000 AWG/kcmil QtyPerPhase 1 Length 3.0 ft Ampacity 2000.0 A
SECTION B LV SWGR NORTH
IncidentEnergy 11.49 Cal/cm^2 PPE Category 3 AF_ArcingFault 11.452 kA BoltedFault 23.231 kA SystemNominalVoltage 480.0 V
CBL-0133
CableSize 750 AWG/kcmil QtyPerPhase 8 Length 50.0 ft Ampacity 4280.0 A
20-1 SE 4000A
Manufacturer SQUARE D Frame/Model SE Frame/Rating 4000.0 A InterruptingRating 100.0 kA Sensor/Trip 4000.0 A Plug 4000.0 A Settings LTPU (0.5-1.0 x P) 1.0 (4000A) LTD (2-36 Sec.) 2 STPU (2-10 xP) 2 (8000A) STD (0.1-0.5 Sec.) 0.1 (I^2t Out) INST (2-12 x P) 12.0 (48000A)
CHILLER PANEL 4&5
IncidentEnergy 8.91 Cal/cm^2 PPE Category 3 AF_ArcingFault 19.601 kA BoltedFault 36.033 kA SystemNominalVoltage 480.0 V
CBL-0085
CableSize 2000 AWG/kcmil QtyPerPhase 1 Length 5.0 ft Ampacity 2000.0 A
USB MAIN (CLINCAL ADDITION)
Manufacturer SQUARE D Frame/Model SE Frame/Rating 3000.0 A InterruptingRating 100.0 kA Sensor/Trip 3000.0 A Plug 2500.0 A Settings LTPU (0.5-1.0 x P) 1.0 (2875A)
LTD (1-4) 4
STPU (2-10 x P) 3 (7500A) STD (1-4) 3 (I^2t In) 800-3000A Override 42000A (42000A)
USB BUS (BASEMENT)
IncidentEnergy 68.09 Cal/cm^2 PPE Category Dangerous!
AF_ArcingFault 12.395 kA BoltedFault 25.486 kA SystemNominalVoltage 480.0 V
BLDG 41 MAIN BKR
Manufacturer SQUARE D Frame/Model MG Frame/Rating 800.0 A InterruptingRating 35.0 kA Sensor/Trip 600.0 A Plug 0.0 A Settings LTPU/LTD Fixed (600A); Fixed INST (2-8 x S) 2 (1200A)
BLDG 41 MAIN BUS (HDP)
IncidentEnergy 1.03 Cal/cm^2 PPE Category 0 AF_ArcingFault 4.272 kA BoltedFault 6.056 kA SystemNominalVoltage 480.0 V
BLDG 40 MAIN BKR
Manufacturer SQUARE D Frame/Model LA Frame/Rating 400.0 A InterruptingRating 30.0 kA Sensor/Trip 400.0 A Plug 0.0 A Settings Thermal Curve
INST LO (2000A)
BLDG 40 MIAN BUS (HDP)
IncidentEnergy 0.29 Cal/cm^2 PPE Category 0 AF_ArcingFault 4.160 kA BoltedFault 5.869 kA SystemNominalVoltage 480.0 V
4000A ATS BUS
IncidentEnergy 149.86 Cal/cm^2 PPE Category Dangerous!
AF_ArcingFault 16.695 kA BoltedFault 36.117 kA SystemNominalVoltage 480.0 V
E N
4000 A ATS
CHILLER GEN ATS BUS
IncidentEnergy 0 Cal/cm^2 PPE Category AF_ArcingFault 0.000 kA BoltedFault 0.000 kA SystemNominalVoltage 480.0 V
CBL-0160
CableSize 2500 AWG/kcmil QtyPerPhase 1 Length 5.0 ft Ampacity 2500.0 A
4000 A ATS LOAD SIDE BUS
IncidentEnergy 149.86 Cal/cm^2 PPE Category Dangerous!
AF_ArcingFault 16.695 kA BoltedFault 36.117 kA SystemNominalVoltage 480.0 V
E N
ATS
ATS BUS
IncidentEnergy 0 Cal/cm^2 PPE Category AF_ArcingFault 0.000 kA BoltedFault 0.000 kA SystemNominalVoltage 480.0 V
PANEL MPD MAIN BKR
Manufacturer SQUARE D Frame/Model MJ Frame/Rating 800.0 A InterruptingRating 65.0 kA Sensor/Trip 500.0 A Plug 0.0 A Settings LTPU/LTD Fixed (500A); Fixed INST (2-8 x S) 2 (1000A)
PANEL MPD BUS
IncidentEnergy 0.88 Cal/cm^2 PPE Category 0 AF_ArcingFault 3.689 kA BoltedFault 5.100 kA SystemNominalVoltage 480.0 V
BLDG 16 ATS BUS
IncidentEnergy 29.31 Cal/cm^2 PPE Category 4 AF_ArcingFault 3.689 kA BoltedFault 5.100 kA SystemNominalVoltage 480.0 V
LV BLDG 16 XFMR
IncidentEnergy 38.67 Cal/cm^2 PPE Category 4 AF_ArcingFault 4.769 kA BoltedFault 6.887 kA SystemNominalVoltage 480.0 V
CBL-0227
CableSize 500 AWG/kcmil QtyPerPhase 2 Length 200.0 ft Ampacity 860.0 A
BLDG 42 MAIN BKR
Manufacturer SQUARE D Frame/Model MG Frame/Rating 800.0 A InterruptingRating 35.0 kA Sensor/Trip 800.0 A Plug 0.0 A Settings LTPU/LTD Fixed (800A); Fixed INST (2-8 x S) 2 (1600A)
BLDG 42 MAIN BUS (HDP)
IncidentEnergy 1.04 Cal/cm^2 PPE Category 0 AF_ArcingFault 4.307 kA BoltedFault 6.114 kA SystemNominalVoltage 480.0 V
BUS 394
IncidentEnergy 0.44 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.485 kA BoltedFault 5.596 kA SystemNominalVoltage 13800.0 V
E N
USB KNIFE SWITCH E N
CHILLER 3 KNIFE SWITCH
CBL-0341
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
CORALVILLE SIDE CHILLER 3 SWT
IncidentEnergy 0.44 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.484 kA BoltedFault 5.595 kA SystemNominalVoltage 13800.0 V
CBL-0342
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
BACK CHILLER 3 SWITCH
IncidentEnergy 0.44 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.484 kA BoltedFault 5.595 kA SystemNominalVoltage 13800.0 V
CBL-0343
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
CORALVILLE SIDE USB SWT
IncidentEnergy 0.44 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.484 kA BoltedFault 5.595 kA SystemNominalVoltage 13800.0 V
BACK USB SWITCH
IncidentEnergy 0.43 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.285 kA BoltedFault 5.388 kA SystemNominalVoltage 13800.0 V
BUS 402
IncidentEnergy 0.43 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.285 kA BoltedFault 5.388 kA SystemNominalVoltage 13800.0 V
CBL-0151
CableSize 600 AWG/kcmil QtyPerPhase 1 Length 1.0 ft Ampacity 600.0 A
IOWA CITY SIDE CHILLER 3 SWT
IncidentEnergy 0.43 Cal/cm^2 PPE Category 0 AF_ArcingFault 5.284 kA BoltedFault 5.388 kA SystemNominalVoltage 13800.0 V