BLDNG # COMMENT DIALER ACT TEST ZONE SUPERVISORY TIME TROUBLE TIME BATTERIES Type 12V QUANTITY ALARM TIME
115 OPI CG5561 ZN 25 30 sec 38 sec GOOD 7 A/H & 7A/H 2 & 2 37 sec
118 PROTESTANT CHAPEL CG5561 ZN 27 N/A 44 sec GOOD 7 A/H 2 35 sec
119 CHAPEL NO PANEL TO BLDG 115 CG5561 ZN 28 N/A 43 sec NONE TIE 115 N/A N/A 42 sec
120 MUSEUM CG5561 ZN 30 45 sec 38 sec GOOD 7 A/H 2 40 sec
126 AMMS FISCAL BLDG. CG5561 ZN 19 33 sec 30 sec GOOD 17 A/H 2 32 sec
127 POLICE OFFICE BUILDING CG5561 ZN 18 N/A 42 sec GOOD 27 A/H 2 44 sec
128 ENGINEERING BLDG. CG5561 ZN 22 N/A 28 sec GOOD 7 A/H 2 21 sec
129 RESEARCH BLDG. CG5561 ZN 17 42 sec 29 sec GOOD 7 A/H 2 27 sec
131 TIES TO BLDG 143 PANEL CG5561 ZN 21 N/A 37 sec NONE TIE 143 N/A N/A 30 sec
135 BUILDINGS AND GROUNDS CG5561 ZN 14 N/A 26 sec GOOD 12 A/H 2 29 sec
143 WAREHOUSE CG5561 ZN 20 52 sec 46 sec GOOD 28 A/H 2 57 sec
147 BOILER PLANT CG5561 ZN 23 N/A 22 sec GOOD 7 A/H 2 33 sec
425 FISHER HOUSE CG5561 ZN 9 37 sec 42 sec GOOD 18 A/H 2 41 sec
302 PATRICK HOSPITAL CG5561 ZN 8 32 sec 32 sec GOOD 26 A/H 4 35 sec
305 REC. BLDG. CG5561 ZN 32 N/A 33 sec GOOD 7 A/H 2 17 sec
310 TIED TO BLDG. 330 CG5561 ZN 2 28 sec 23 sec NONE N/A N/A 32 sec
315 MOBILE SIMULATION CG5561 ZN 4 41 sec 41 sec GOOD 7 A/H 2 37 sec
320 LAKESIDE MANOR CG5561 ZN 29 N/A 31 sec GOOD 7 A/H 4 26 sec
321 OPERATORS CG5561 ZN 5 N/A 36 sec GOOD 7 A/H 2 32 sec
330 PATIENT TOWER CG5561 ZN 1 27 sec 31 sec GOOD 55 A/H 2 32 sec
340 GI CLINIC CG5561 ZN 37 N/A 28 sec GOOD 7 A/H 4 27 sec
401 CHILD CARE CENTER CG5561 N/A N/A GOOD 7 A/H & 18 A/H 1 & 2 PANEL DOES NOT DIAL OUT
Quarterly Test Report DECEMBER QUARTERLY by Ryan Steimle
Company Name: Dayton VA
Contact Name: Gerry Pennington
937-268-6511 Police X1184 GERRY X2826
BLDNG # COMMENT DIALER ACT TEST ZONE SUPERVISORY TIME TROUBLE TIME BATTERIES Type 12V QUANTITY ALARM TIME
408 COLONEL HARRIS CG5561 ZN 6 35 sec 33 sec GOOD 7 A/H 2 23 sec
409 PBS, HRMS, HOMELESS ETC. CG5561 ZN 7 22 sec 32 sec GOOD 40 A/H 2 25 sec
410 Rehabilitation Care CG5561 ZN 11 30 sec 35 sec GOOD 17 A/H 2 17 sec
411 NURSING HOME KITCHEN CG5561 ZN 12 sec 26 sec GOOD 7 A/H 2 25 sec
1301 CEMETERY ADMIN BLDG. CG5561 ZN 24 N/A 24 sec GOOD 24 A/H 2 18 sec
38 WELDING HUT CG5561 ZN 34 N/A N/A N/A BATTERIES IN 128 N/A 21 sec
335 MRI Building CG5561 ZN 38 26 sec 28 sec GOOD 18 A/H 2 35 sec
350 HOSPICE GG5661 31 sec 20 sec GOOD 20 A/H 2 25 sec
Load test
Discharge Test
Temperature
Voltage Checked
Date test for expiration
Functions Checked
Fuses Checked
Lamps and LED Checked
Primary Power Supply Checked
Trouble Signals
Ground-fault monitoring
Annunciators
NOTES
* BUILDING 401 WAS BEING FUMIGATED SO WE DIDN’T INSPECT*
*THE DAY CARE IS NO LONGER IN THE BUILDING*
CONTROL MAIN PANEL TEST INCLUDES
BATTERY TEST INCLUDES
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Dayton VA - #115 4100 W. Third Street Dayton, Ohio 45428
This inspection was performed in accordance with NFPA 101, EDITION 2012, LIFE SAFETY CODE, NFPA 72, EDITION 2010, FIRE ALARM SYSTEMS and/or other regulatory standards applicable to this inspection.
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Inspection Completion Date May 21, 2024
Building: Dayton VA - #115 Company: Integrated Protection Services, Inc.
Contact: Gerry Pennington Contact: Joe Merry
Title: Manager Title: Inspector Fire Alarm Testing Report
Page of 1 20 Executive Summary
Integrated Protection Services, Inc. Download Date: 03/19/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: Dayton VA - #115 Contact: Gerry Pennington
Address: 4100 W. Third Street Phone: 937-268-6511
Address: Fax:
City/State/ZIP Code: Dayton, Ohio 45428 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Integrated Protection Services, Inc. Inspector: Joe Merry
Address: 5303 Lester Road Phone: 513-460-6577
Address: Fax:
City/State/ZIP Code: Cincinnati, OH 45213 Mobile:
Country: United States of America Email: jmerry@integratedprotection.com
System Control Unit Manufacturer: EST Inspection Date: 04/30/2024 IDC Style: A Model Number: EST 3 Install Date: 05/01/1995 SLC Style:
Software Version: 5.31 Version Date: 04/18/2019 NAC Style: Y Location: 1st Back Hall Current Protection: Breaker
Page of 2 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
Inspection Completion Date: May 21, 2024 Building: Dayton VA - #115 EC 02.03.05 EP 02 Six-month testing of tamper switches and vane-type and pressure-type water-flow devices. Quarterly testing of mechanical water-flow devices. NFPA 72-2010 Table 14.4.5; NFPA 25-2011 Table 5.1.1.2.
Devices Tested This Quarter Pass Fail Tested YTD (2024) Total Quantity Waterflow Switch 1 1 0 1 1
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72-2010 Table 14.4.5; 17.14.
Devices Tested This Quarter Pass Fail Tested YTD (2024) Total Quantity Duct Detector 2 2 0 2 2
Heat Detector 1 1 0 1 1
Pull Station 10 10 0 10 10
Smoke Detector 21 21 0 21 21
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door-releasing devices. NFPA 72-2010 Table 14.4.5
Devices Tested This Quarter Pass Fail Tested YTD (2024) Total Quantity Speaker 11 11 0 11 11
Strobe 14 14 0 14 14
LS 02.01.34 EP 02 Protected master fire alarm control panel Devices Tested This Quarter Pass Fail Tested YTD (2024) Total Quantity Control Panel 2 2 0 2 2
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2012 18/19.3.4 and NFPA 72-2010 Table 14.4.5 (For Ambulatory Health Care see LS 03.01.34 EP 10)
Devices Tested This Quarter Pass Fail Tested YTD (2024) Total Quantity Battery 3 3 0 3 3
Total Device Count: 65
Page of 3 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
Certification
Company: Integrated Protection Services, Inc. Building: Dayton VA - #115
Inspector: Joe Merry Contact: Gerry Pennington
Page of 4 20 Notes & Recommendations
Integrated Protection Services, Inc. Download Date: 03/19/2025
Notes & Recommendations Generated by: BuildingReports.com
Building: Dayton VA - #115 Control Panel: 22 - EST EST 3 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 02 Six-month testing of tamper switches and vane-type and pressure-type water-flow devices.
Quarterly testing of mechanical water-flow devices. NFPA 72-2010 Table 14.4.5; NFPA 25-2011 Table 5.1.1.2.
1 Waterflow Switch Basement West Sprinkler Room Passed 16934181 Tested by others javascript:editViewDevice('16934181');
Page of 5 20 Inspection & Testing
Integrated Protection Services, Inc. Download Date: 03/19/2025
Inspection & Testing Generated by: BuildingReports.com
Building: Dayton VA - #115 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 02
Six-month testing of tamper switches and vane-type and pressure-type water-flow devices. Quarterly testing of mechanical water-flow devices. NFPA 72-2010 Table 14.4.5; NFPA 25-2011 Table 5.1.1.2.
Vane-type and pressure switch-type waterflow alarm devices shall be tested semiannually. Per NFPA 25, Section 5.3.3.1, mechanical waterflow alarm devices shall be tested quarterly. Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems.
(2010 ed.) (NFPA 72 Table 14.4.2.2 (14j)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Waterflow Switch 1 1 0 1 1
Device Type Location ScanID Address Q2/23 Q2/24 Waterflow Switch Basement West Sprinkler Room 16934181 22-02 0129 05/01-P 05/21-P
Device Total: 1 Return to Executive Summary
Page of 6 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72-2010 Table 14.4.5; 17.14.
In addition to testing in place to ensure smoke entry into the sensing chamber and an alarm response, duct smoke detectors utilizing sampling tubes shall be tested by verifying the correct pressure differential (within the manufacturer's published ranges) between the inlet and exhaust tubes using a method acceptable to the manufacturer to ensure that the device will properly sample the airstream. (2010 ed.) (NFPA 72 Table 14.4.2.2 (14g.
6)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Duct Detector 2 2 0 2 2
Device Type Location ScanID Address Q2/23 Q2/24 Duct Detector Basement North AHU-1 39703514 22-02 0008 05/01-P 04/30-P Duct Detector Basement South AHU #2 39703515 22-02 0013 05/01-P 04/30-P
Device Total: 2 Return to Executive Summary
Page of 7 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72-2010 Table 14.4.5; 17.14.
Restorable: Heat test shall be performed with a heat source per the manufacturer's published instructions. Non- Restorable: Heat tests shall not be performed. Functionality shall be tested mechanically and electrically. (2010 ed.)
(NFPA 72 Table 14.4.2.2 (14d)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Heat Detector 1 1 0 1 1
Device Type Location ScanID Address Q2/23 Q2/24 Heat Detector Ground Elevator Lobby Mechanical
Room 05340041 22-02 0023 05/01-P 04/30-P
Page of 8 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72-2010 Table 14.4.5; 17.14.
Manual fire alarm boxes shall be operated per the manufacturer's published instructions. Key-operated presignal and general alarm manual fire alarm boxes shall both be tested. (2010 ed.) (NFPA 72 Table 14.4.2.2 (14e)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Pull Station 10 10 0 10 10
Device Type Location ScanID Address Q2/23 Q2/24 Pull Station Ground Front Lobby 05340017 22-02 0154 05/01-P 04/30-P Pull Station Basement Northeast Stairwell 05340018 22-02 0155 05/01-P 04/30-P Pull Station Basement Northwest Stairwell 05340019 22-02 0156 05/01-P 04/30-P Pull Station Basement Southwest Stairwell 05340020 22-02 0156 05/01-P 04/30-P Pull Station 1st East Hall 05340011 22-02 0150 05/01-P 04/30-P Pull Station 1st Northwest Stairwell 05340013 22-02 0152 05/01-P 04/30-P Pull Station 1st Southwest Stairwell 05340012 22-02 0151 05/01-P 04/30-P Pull Station 2nd Center Stairwell 05340014 22-02 0145 05/01-P 04/30-P Pull Station 2nd Northwest Stairwell 05340015 22-02 0146 05/01-P 04/30-P Pull Station 2nd South Stairwell 05340016 22-02 0147 05/01-P 04/30-P
Device Total: 10 Return to Executive Summary
Page of 9 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72-2010 Table 14.4.5; 17.14.
Smoke detectors/smoke alarms shall be tested in place to ensure smoke entry into the sensing chamber and an alarm response. Sensitivity shall be checked every alternate year. Any of the following tests shall be performed to ensure that each smoke detector is within its listed and marked sensitivity range: 1) Calibrated test method, 2) Manufacturer's calibrated sensitivity test instrument, 3) Listed control equipment arranged for the purpose, 4) Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit when its sensitivity is outside its listed sensitivity range, 5) Other calibrated sensitivity test method approved by the authority having jurisdiction. (2010 ed.) (NFPA 72 Table 14.4.2.2 (14g.1); 14.4.5.3.2) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Smoke Detector 21 21 0 21 21
Device Type Location ScanID Address Q2/23 Q2/24 Smoke Detector Ground Elevator Lobby Mechanical
Room 05340040 22-02 0024 05/01-P 04/30-P
Smoke Detector Ground Elevator Lobby Rear 05340039 22-02 0022 05/01-P 04/30-P Smoke Detector Basement Elevator Lobby 05340038 22-02 0015 05/01-P 04/30-P Smoke Detector Basement North Hall 1 05340024 22-02 0020 05/01-P 04/30-P Smoke Detector Basement North Hall 2 05340025 22-02 0021 05/01-P 04/30-P Smoke Detector Basement South Hall 1 05340023 22-02 0016 05/01-P 04/30-P Smoke Detector Basement South Hall 2 05340022 22-02 0017 05/01-P 04/30-P Smoke Detector Basement South Hall 3 05340021 22-02 0018 05/01-P 04/30-P Smoke Detector Basement Switchgear Room 12 05340026 22-02 0019 05/01-P 04/30-P Smoke Detector 1st Elevator Lobby Front 05340042 22-02 0014 05/01-P 04/30-P Smoke Detector 1st Back East Hall 05340027 22-02 0007 05/01-P 04/30-P Smoke Detector 1st North Hall 1 05340031 22-02 0011 05/01-P 04/30-P Smoke Detector 1st North Hall 2 05340030 22-02 0012 05/01-P 04/30-P Smoke Detector 1st South Hall #1 05340028 22-02 0009 05/01-P 04/30-P Smoke Detector 1st South Hall 2 05340029 22-02 0010 05/01-P 04/30-P Smoke Detector 2nd Elevator Lobby 05340043 22-02 0001 05/01-P 04/30-P Smoke Detector 2nd North 1 05340036 22-02 0002 05/01-P 04/30-P Smoke Detector 2nd North 2 05340037 22-02 0003 05/01-P 04/30-P Smoke Detector 2nd South 1 05340035 22-02 0004 05/01-P 04/30-P Smoke Detector 2nd South 2 05340034 22-02 0005 05/01-P 04/30-P Smoke Detector 2nd South 3 05340033 22-02 0006 05/01-P 04/30-P
Device Total: 21 Return to Executive Summary
Page of 10 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door-releasing devices. NFPA 72-2010 Table 14.4.5
Periodic Testing shall comply with the following: Sound pressure levels shall be measured with a sound level meter meeting ANSI S1.4a, Specifications for Sound Level Meters, Type 2 requirements. Sound pressure levels throughout the protected area shall be measured to confirm that they are in compliance with Chapter 18 where building, system, or occupancy changes have occurred. The sound level meter shall be set in accordance with ANSI S3.41, American National Standard Audible Evacuation Signal, using the time-weighted characteristic F (FAST). Audible information shall be verified to be distinguishable and understandable. (2010 ed.) (NFPA 72 Table
14.4.2.2 (15b)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Speaker 11 11 0 11 11
Device Type Location ScanID Address Q2/23 Q2/24 Speaker Ground Main Entry 04894616 1 05/01-P 04/30-P Speaker Basement File Room 04894607 1 05/01-P 04/30-P Speaker Basement File Room 04894608 1 05/01-P 04/30-P Speaker Basement File Room Cage Area 04894612 1 05/01-P 04/30-P Speaker Basement by Stairwell 04894606 1 05/01-P 04/30-P Speaker 1st by Room 100 04894592 1 05/01-P 04/30-P Speaker 1st by Room 105 04894593 1 05/01-P 04/30-P Speaker 1st by Room 107 04894595 1 05/01-P 04/30-P Speaker 2nd by Room 204 04894599 1 05/01-P 04/30-P Speaker 2nd by Room 207 04894602 1 05/01-P 04/30-P Speaker 2nd by Stairs 04894598 1 05/01-P 04/30-P
Device Total: 11 Return to Executive Summary
Page of 11 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door-releasing devices. NFPA 72-2010 Table 14.4.5
Test shall be performed in accordance with the manufacturer's published instructions. (2010 ed.) (NFPA 72 Table
14.4.2.2 (15c)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Strobe 14 14 0 14 14
Device Type Location ScanID Address Q2/23 Q2/24 Strobe Ground Main Entry 04894615 1 05/01-P 04/30-P Strobe Basement File Room 04894609 1 05/01-P 04/30-P Strobe Basement File Room Cage Area 04894611 1 05/01-P 04/30-P Strobe Basement by Stairwell 04894605 1 05/01-P 04/30-P Strobe 1st Mens Restroom #114a 30967281 1 05/01-P 04/30-P Strobe 1st Womens Restroom #115 04894614 1 05/01-P 04/30-P Strobe 1st by Room 102 04894594 1 05/01-P 04/30-P Strobe 1st by Room 112 04894596 1 05/01-P 04/30-P Strobe 1st East Hall 04894591 1 05/01-P 04/30-P Strobe 2nd In Mens Restroom 212 b 16934179 1 05/01-P 04/30-P Strobe 2nd In Womens Restroom 214 30967280 1 05/01-P 04/30-P Strobe 2nd by Room 202 04894600 1 05/01-P 04/30-P Strobe 2nd by Room 208 04894601 1 05/01-P 04/30-P Strobe 2nd by Stairs 04894597 1 05/01-P 04/30-P
Device Total: 14 Return to Executive Summary
Page of 12 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
LS 02.01.34 EP 02 Protected master fire alarm control panel
At a minimum, control equipment shall be tested to verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (2010 ed.) (NFPA 72 Table 14.4.2.2 (1.a)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Control Panel 2 2 0 2 2
Device Type Location ScanID Address Q2/23 Q2/24 Control Panel 1st Back Hall 05340044 1 05/01-P 04/30-P Control Panel 1st Back Hall 16934176 22 05/01-P 04/30-P
Page of 13 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2012 18/19.3.4 and NFPA 72-2010 Table 14.4.5 (For Ambulatory Health Care see LS 03.01.34 EP 10)
Annually - With the batteries fully charged and connected to the charger, the voltage across the batteries shall be measured with a voltmeter. Semi-annually, under load, the battery shall perform in accordance with the battery manufacturer's specifications. (2010 ed.) (NFPA 72 Table 14.4.2.2 (6d.1,2)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Battery 3 3 0 3 3
Device Type Location ScanID Address Q2/23 Q2/24 Battery 1st Back Hall 16934177 1-left side 05/01-F 04/30-P Battery 1st Back Hall 16934178 1-right side 05/01-F 04/30-P Battery 1st Back Hall Main Fire Panel Above
Ceiling 16934184 2-Both batteries 05/01-F 04/30-P
Device Total: 3 Return to Executive Summary
Page of 14 20 Service Summary
Integrated Protection Services, Inc. Download Date: 03/19/2025
Service Summary Generated by: BuildingReports.com
Building: Dayton VA - #115 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed Battery Tested 3 Control Panel Tested 2 Duct Detector Tested 2 Heat Detector Visually Checked 1 Pull Station Tested 10 Smoke Detector Tested 21 Speaker Tested 11 Strobe Tested 14 Waterflow Switch Visually Checked 1
Total 65 Grand Total 65
Page of 15 20 Auxiliary Functions Testing
Integrated Protection Services, Inc. Download Date: 03/19/2025
Auxiliary Functions Testing Generated by: BuildingReports.com
Building: Dayton VA - #115 Control Panel: 22 - EST EST 3 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed Duct Detector
AHU Shutdown Basement North AHU-1 Passed 39703514 AHU Shutdown Basement South AHU #2 Passed 39703515
Heat Detector Elevator Recall Ground Elevator Lobby Mechanical Room Passed 05340041
Smoke Detector Elevator Recall Ground Elevator Lobby Mechanical Room Passed 05340040 Elevator Recall Ground Elevator Lobby Rear Passed 05340039 Elevator Recall Basement Elevator Lobby Passed 05340038 Elevator Recall 1st Elevator Lobby Front Passed 05340042 javascript:editViewDevice('39703514');
javascript:editViewDevice('39703515');
javascript:editViewDevice('05340041');
javascript:editViewDevice('05340040');
javascript:editViewDevice('05340039');
javascript:editViewDevice('05340038');
javascript:editViewDevice('05340042');
Page of 16 20 Battery & Power Supply Testing
Integrated Protection Services, Inc. Download Date: 03/19/2025
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: Dayton VA - #115 Control Panel: 1 - EST EST 3 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed Sealed Lead Acid 1st Back Hall 7 Ah 12 V Sealed Lead Acid 1st Back Hall 7 Ah 12 V
Building: Dayton VA - #115 Control Panel: 2 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed Sealed Lead Acid 1st Back Hall Main Fire Panel
Above Ceiling 9 12
Page of 17 20 Inventory & Warranty Report
Integrated Protection Services, Inc. Download Date: 03/19/2025
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Dayton VA - #115 Control Panel: 1 - EST EST 3 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Battery Control 4.62% 3
Control Panel Control 3.08% 2
Duct Detector Initiating 3.08% 2
Heat Detector Initiating 1.54% 1
Pull Station Initiating 15.38% 10
Smoke Detector Initiating 32.31% 21
Speaker Indicating 16.92% 11
Strobe Indicating 21.54% 14
Waterflow Switch Initiating 1.54% 1
Type Qty Model # Description Install Date
In Service - 5 Years to 10 Years Power-Sonic
Battery 2 PS-127F1 Sealed Lead Acid 12/01/2019
In Service - 25 Years or Older
EST
Control Panel 1 EST 3 05/01/1995 Speaker 11 757-1A-S70 05/01/1995 Strobe 14 202-7AT 05/01/1995
Building: Dayton VA - #115 Control Panel: 2 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date
In Service - 5 Years to 10 Years Power-Sonic
Battery 1 PS-1290F2 Sealed Lead Acid 03/25/2019
Building: Dayton VA - #115 Control Panel: 22 - EST EST 3 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date
In Service - 25 Years or Older Waterflow Switch 1 05/01/1995
Page of 18 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
EST
Control Panel 1 EST 3 05/01/1995 Duct Detector 2 SIGA-SD Photoelectric 05/01/1995 Heat Detector 1 SIGA-HRS Rate-of-Rise 05/01/1995 Pull Station 10 SIGA-278 Single Action 05/01/1995 Smoke Detector 21 SIGA-PS Photoelectric 05/01/1995
Page of 19 20 Zone Address Report
Integrated Protection Services, Inc. Download Date: 03/19/2025
Zone Address Report Generated by: BuildingReports.com
Building: Dayton VA - #115 Control Panel: 1 - EST EST 3 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID Zone/Circuit: left side
Battery 1st Back Hall Sealed Lead Acid 16934177 Zone/Circuit: right side
Battery 1st Back Hall Sealed Lead Acid 16934178
Building: Dayton VA - #115 Control Panel: 2 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID Zone/Circuit: Both batteries
Battery 1st Back Hall Main Fire Panel Above Ceiling
Sealed Lead Acid 16934184
Building: Dayton VA - #115 Control Panel: 22 - EST EST 3 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID Zone/Circuit: 02
0001 Smoke Detector 2nd Elevator Lobby Photoelectric 05340043 0002 Smoke Detector 2nd North 1 Photoelectric 05340036 0003 Smoke Detector 2nd North 2 Photoelectric 05340037 0004 Smoke Detector 2nd South 1 Photoelectric 05340035 0005 Smoke Detector 2nd South 2 Photoelectric 05340034 0006 Smoke Detector 2nd South 3 Photoelectric 05340033 0007 Smoke Detector 1st Back East Hall Photoelectric 05340027 0008 Duct Detector Basement North AHU-1 Photoelectric 39703514 0009 Smoke Detector 1st South Hall #1 Photoelectric 05340028 0010 Smoke Detector 1st South Hall 2 Photoelectric 05340029 0011 Smoke Detector 1st North Hall 1 Photoelectric 05340031 0012 Smoke Detector 1st North Hall 2 Photoelectric 05340030 0013 Duct Detector Basement South AHU #2 Photoelectric 39703515 0014 Smoke Detector 1st Elevator Lobby Front Photoelectric 05340042 0015 Smoke Detector Basement Elevator Lobby Photoelectric 05340038 0016 Smoke Detector Basement South Hall 1 Photoelectric 05340023 0017 Smoke Detector Basement South Hall 2 Photoelectric 05340022 0018 Smoke Detector Basement South Hall 3 Photoelectric 05340021 0019 Smoke Detector Basement Switchgear Room 12 Photoelectric 05340026 0020 Smoke Detector Basement North Hall 1 Photoelectric 05340024 javascript:editViewDevice('16934177');
javascript:editViewDevice('16934178');
javascript:editViewDevice('16934184');
javascript:editViewDevice('05340043');
javascript:editViewDevice('05340036');
javascript:editViewDevice('05340037');
javascript:editViewDevice('05340035');
javascript:editViewDevice('05340034');
javascript:editViewDevice('05340033');
javascript:editViewDevice('05340027');
javascript:editViewDevice('39703514');
javascript:editViewDevice('05340028');
javascript:editViewDevice('05340029');
javascript:editViewDevice('05340031');
javascript:editViewDevice('05340030');
javascript:editViewDevice('39703515');
javascript:editViewDevice('05340042');
javascript:editViewDevice('05340038');
javascript:editViewDevice('05340023');
javascript:editViewDevice('05340022');
javascript:editViewDevice('05340021');
javascript:editViewDevice('05340026');
javascript:editViewDevice('05340024');
Page of 20 20
Integrated Protection Services, Inc. Download Date: 03/19/2025
Address Device Type Location Type ScanID 0021 Smoke Detector Basement North Hall 2 Photoelectric 05340025 0022 Smoke Detector Ground Elevator Lobby Rear Photoelectric 05340039 0023 Heat Detector Ground Elevator Lobby Mechanical Room Rate-of-Rise 05340041 0024 Smoke Detector Ground Elevator Lobby Mechanical Room Photoelectric 05340040 0129 Waterflow Switch Basement West Sprinkler Room 16934181 0145 Pull Station 2nd Center Stairwell Single Action 05340014 0146 Pull Station 2nd Northwest Stairwell Single Action 05340015 0147 Pull Station 2nd South Stairwell Single Action 05340016 0150 Pull Station 1st East Hall Single Action 05340011 0151 Pull Station 1st Southwest Stairwell Single Action 05340012 0152 Pull Station 1st Northwest Stairwell Single Action 05340013 0154 Pull Station Ground Front Lobby Single Action 05340017 0155 Pull Station Basement Northeast Stairwell Single Action 05340018 0156 Pull Station Basement Northwest Stairwell Single Action 05340019 0156 Pull Station Basement Southwest Stairwell Single Action 05340020 javascript:editViewDevice('05340025');
javascript:editViewDevice('05340039');
javascript:editViewDevice('05340041');
javascript:editViewDevice('05340040');
javascript:editViewDevice('16934181');
javascript:editViewDevice('05340014');
javascript:editViewDevice('05340015');
javascript:editViewDevice('05340016');
javascript:editViewDevice('05340011');
javascript:editViewDevice('05340012');
javascript:editViewDevice('05340013');
javascript:editViewDevice('05340017');
javascript:editViewDevice('05340018');
javascript:editViewDevice('05340019');
javascript:editViewDevice('05340020');
For
Dayton VA - #118 4100 W. Third Street Dayton, Ohio 45428
This inspection was performed in accordance with NFPA 101, EDITION 2012, LIFE SAFETY CODE, NFPA 72, EDITION 2010, FIRE ALARM SYSTEMS and/or other regulatory standards applicable to this inspection.
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Inspection Completion Date Apr 30, 2024
Building: Dayton VA - #118 Company: Integrated Protection Services, Inc.
Contact: Gerry Pennington Contact: Joe Merry
Page of 1 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: Dayton VA - #118 Contact: Gerry Pennington
Address: 4100 W. Third Street Phone: 937-268-6511
Address: Fax:
City/State/ZIP Code: Dayton, Ohio 45428 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Integrated Protection Services, Inc. Inspector: Joe Merry
Address: 5303 Lester Road Phone: 513-460-6577
Address: Fax:
City/State/ZIP Code: Cincinnati, OH 45213 Mobile:
Country: United States of America Email: jmerry@integratedprotection.com
System Control Unit Manufacturer: EST Inspection Date: 04/30/2024 IDC Style: B Model Number: EST-3 Install Date: 05/01/2012 SLC Style: 4 Software Version: 5.31 Version Date: 04/18/2019 NAC Style: Y Location: 1st South East Exit Current Protection: Breaker
Central Station Signal Verification Type: Mfg: Model #:
Test Time/Date: Restore Time: Note:
Type of Signal Signal Confirmation Notes Alarm Confirmed Time:
Page of 2 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
Inspection Completion Date: Apr 30, 2024 Building: Dayton VA - #118 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72-2010 Table 14.4.5; 17.14.
Devices Tested This Quarter Pass Fail Tested YTD (2024) Total Quantity Duct Detector 4 4 0 4 4
Pull Station 7 7 0 7 7
Smoke Detector 17 17 0 17 17
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door-releasing devices. NFPA 72-2010 Table 14.4.5
Devices Tested This Quarter Pass Fail Tested YTD (2024) Total Quantity Horn/Strobe 17 17 0 17 17
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72-2010 Table 14.4.5
Devices Tested This Quarter Pass Fail Tested YTD (2024) Total Quantity Monitoring 1 1 0 1 1
LS 02.01.34 EP 02 Protected master fire alarm control panel Devices Tested This Quarter Pass Fail Tested YTD (2024) Total Quantity Control Panel 1 1 0 1 1
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2012 18/19.3.4 and NFPA 72-2010 Table 14.4.5 (For Ambulatory Health Care see LS 03.01.34 EP 10)
Devices Tested This Quarter Pass Fail Tested YTD (2024) Total Quantity Battery 1 0 1 1 1
Total Device Count: 48
Page of 3 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
Certification
Company: Integrated Protection Services, Inc. Building: Dayton VA - #118
Page of 4 18 Discrepancy Report
Integrated Protection Services, Inc. Download Date: 03/19/2025
Discrepancy Report Generated by: BuildingReports.com
Building: Dayton VA - #118 Control Panel: 35 - EST EST-3 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2012 18/19.3.4 and NFPA 72-2010 Table 14.4.5 (For Ambulatory Health Care see LS 03.01.34 EP 10) Battery
16934967 1st Below Panel Total of 2 Date Expired 35 javascript:editViewDevice('16934967');
Page of 5 18 Proposed Solutions Report
Integrated Protection Services, Inc. Download Date: 03/19/2025
Proposed Solutions Report Generated by: BuildingReports.com
Building: Dayton VA - #118 Control Panel: 35 - EST EST-3 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2012 18/19.3.4 and NFPA 72-2010 Table 14.4.5 (For Ambulatory Health Care see LS 03.01.34 EP 10)
Battery 16934967 1st Below Panel Total of 2 Replace Battery PS-1290 F2 T/M
PO #: (none) T/M
Page of 6 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
Notes & Recommendations Generated by: BuildingReports.com
Building: Dayton VA - #118 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note All Duct Detectors Shut Down Air Handler Units Properly.
Page of 7 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
Inspection & Testing Generated by: BuildingReports.com
Building: Dayton VA - #118 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72-2010 Table 14.4.5; 17.14.
In addition to testing in place to ensure smoke entry into the sensing chamber and an alarm response, duct smoke detectors utilizing sampling tubes shall be tested by verifying the correct pressure differential (within the manufacturer's published ranges) between the inlet and exhaust tubes using a method acceptable to the manufacturer to ensure that the device will properly sample the airstream. (2010 ed.) (NFPA 72 Table 14.4.2.2 (14g.
6)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Duct Detector 4 4 0 4 4
Device Type Location ScanID Address Q2/23 Q2/24 Duct Detector Basement AHU-1 16934975 35-02 0001 05/01-P 04/30-P Duct Detector Basement AHU-2 16934976 35-02 0002 05/01-P 04/30-P Duct Detector Basement AHU-3 16934977 35-02 0003 05/01-P 04/30-P Duct Detector Basement AHU-4 16934978 35-02 0004 05/01-P 04/30-P
Device Total: 4 Return to Executive Summary
Page of 8 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72-2010 Table 14.4.5; 17.14.
Manual fire alarm boxes shall be operated per the manufacturer's published instructions. Key-operated presignal and general alarm manual fire alarm boxes shall both be tested. (2010 ed.) (NFPA 72 Table 14.4.2.2 (14e)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Pull Station 7 7 0 7 7
Device Type Location ScanID Address Q2/23 Q2/24 Pull Station Basement Bottom Of Steps 16934974 35-02 0128 05/01-P 04/30-P Pull Station 1st Clock Tower Bottom 16934970 35-02 0136 05/01-P 04/30-P Pull Station 1st NorthEast Exit 16934969 35-02 0127 05/01-P 04/30-P Pull Station 1st South East Exit 16934968 35-02 0126 05/01-P 04/30-P Pull Station 1st South West Exit 16934973 35-02 0129 05/01-P 04/30-P Pull Station Mezzanine Clock Tower Top 16934971 35-02 0134 05/01-P 04/30-P Pull Station Penthouse Chapel Ladder 40567463 35-02 0137 05/01-P 04/30-P
Device Total: 7 Return to Executive Summary
Page of 9 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72-2010 Table 14.4.5; 17.14.
Smoke detectors/smoke alarms shall be tested in place to ensure smoke entry into the sensing chamber and an alarm response. Sensitivity shall be checked every alternate year. Any of the following tests shall be performed to ensure that each smoke detector is within its listed and marked sensitivity range: 1) Calibrated test method, 2) Manufacturer's calibrated sensitivity test instrument, 3) Listed control equipment arranged for the purpose, 4) Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit when its sensitivity is outside its listed sensitivity range, 5) Other calibrated sensitivity test method approved by the authority having jurisdiction. (2010 ed.) (NFPA 72 Table 14.4.2.2 (14g.1); 14.4.5.3.2) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Smoke Detector 17 17 0 17 17
Device Type Location ScanID Address Q2/23 Q2/24 Smoke Detector Basement Bottom Of Steps 3907137138 35-02 0018 05/01-P 04/30-P Smoke Detector Basement Storage Room 3907136520 35-02 0017 05/01-P 04/30-P Smoke Detector Basement Under Step Storage 3956713185 35-02 0019 05/01-P 04/30-P Smoke Detector Basement Center #1 04892993 35-2 9 05/01-P 04/30-P Smoke Detector Basement Center #2 3907127382 35-02 0010 05/01-P 04/30-P Smoke Detector Basement Center #3 3907137466 35-02 0011 05/01-P 04/30-P Smoke Detector Basement Center #4 3907127214 35-02 0012 05/01-P 04/30-P Smoke Detector Basement North#1 3907137800 35-02 0006 05/01-P 04/30-P Smoke Detector Basement North#2 3907137183 35-02 0007 05/01-P 04/30-P Smoke Detector Basement North#3 3907128020 35-02 0008 05/01-P 04/30-P Smoke Detector Basement Pipe Organ Blower Room 3907136636 35-02 0016 05/01-P 04/30-P Smoke Detector Basement South#1 04892991 35-2 13 05/01-P 04/30-P Smoke Detector Basement South#2 3907138647 35-02 0014 05/01-P 04/30-P Smoke Detector Basement South#3 3907138678 35-02 0015 05/01-P 04/30-P Smoke Detector 1st Above Panel 16934965 35-02 0021 05/01-P 04/30-P Smoke Detector Mezzanine Clock Tower 16934972 35-02 0005 05/01-P 04/30-P Smoke Detector Penthouse Chapel Ladder 40567464 35-02 0020 05/01-P 04/30-P
Device Total: 17 Return to Executive Summary
Page of 10 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door-releasing devices. NFPA 72-2010 Table 14.4.5
Audibles: Periodic Testing shall comply with the following: Sound pressure levels shall be measured with a sound level meter meeting ANSI S1.4a, Specifications for Sound Level Meters, Type 2 requirements. Sound pressure levels throughout the protected area shall be measured to confirm that they are in compliance with Chapter 18.
Visibles: Test shall be performed in accordance with the manufacturer's published instructions. (2010 ed.) (NFPA 72 Table 14.4.2.2 (15a,c)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Horn/Strobe 17 17 0 17 17
Device Type Location ScanID Address Q2/23 Q2/24 Horn/Strobe Basement 30966424 1 05/01-P 04/30-P Horn/Strobe Basement 30966425 1 05/01-P 04/30-P Horn/Strobe Basement 30966426 1 05/01-P 04/30-P Horn/Strobe Basement Pipe Organ Blower Room 30966423 1 05/01-P 04/30-P Horn/Strobe Basement Southwest 30966427 1 05/01-P 04/30-P Horn/Strobe Basement Southwest Stairwell 30966428 1 05/01-P 04/30-P Horn/Strobe 1st Sanctuary Restroom 30966421 1 05/01-P 04/30-P Horn/Strobe 1st Northeast Exit 30966433 1 05/01-P 04/30-P Horn/Strobe 1st Northwest Exit 30966431 1 05/01-P 04/30-P Horn/Strobe 1st Southeast Chapel 40567466 1 05/01-P 04/30-P Horn/Strobe 1st Southeast Exit 30966434 1 05/01-P 04/30-P Horn/Strobe 1st Southwest Chapel 40567467 1 05/01-P 04/30-P Horn/Strobe 1st Southwest Exit 30966429 1 05/01-P 04/30-P Horn/Strobe 1st Southwest Stairs 30966430 1 05/01-P 04/30-P Horn/Strobe 1st West Behind Stage 30966432 1 05/01-P 04/30-P Horn/Strobe 2nd Tower 30966422 1 05/01-P 04/30-P Horn/Strobe Penthouse Chapel Ladder 40567465 1 05/01-F 04/30-P
Device Total: 17 Return to Executive Summary
Page of 11 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
EC 02.03.05 EP 05
Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72-2010 Table 14.4.5
Test shall be performed on all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Initiating device shall be actuated. Receipt of the correct initiating device signal at the supervising station within 90 seconds shall be verified. Upon completion of the test, the system shall be restored to its functional operating condition.
(2010 ed.) (NFPA 72 Table 14.4.2.2 (19a)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Monitoring 1 1 0 1 1
Device Type Location ScanID Address Q2/23 Q2/24 Monitoring 16934966 35 05/01-P 04/30-P
Page of 12 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
LS 02.01.34 EP 02 Protected master fire alarm control panel
At a minimum, control equipment shall be tested to verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (2010 ed.) (NFPA 72 Table 14.4.2.2 (1.a)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Control Panel 1 1 0 1 1
Device Type Location ScanID Address Q2/23 Q2/24 Control Panel 1st South East Exit 16934964 35 05/01-P 04/30-P
Page of 13 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2012 18/19.3.4 and NFPA 72-2010 Table 14.4.5 (For Ambulatory Health Care see LS 03.01.34 EP 10)
Annually - With the batteries fully charged and connected to the charger, the voltage across the batteries shall be measured with a voltmeter. Semi-annually, under load, the battery shall perform in accordance with the battery manufacturer's specifications. (2010 ed.) (NFPA 72 Table 14.4.2.2 (6d.1,2)) Devices Tested Q2/24 Pass Q2/24 Fail Q2/24 Tested YTD (2024) Total Quantity Battery 1 0 1 1 1
Device Type Location ScanID Address Q2/23 Q2/24 Battery 1st Below Panel Total of 2 16934967 35 05/01-P 04/30-F
Page of 14 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
Service Summary Generated by: BuildingReports.com
Building: Dayton VA - #118 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Failed/Other Battery Tested 1
Total 1
Passed Control Panel Tested 1 Duct Detector Tested 4 Horn/Strobe Tested 17 Monitoring Tested 1 Pull Station Tested 7 Smoke Detector Tested 17
Total 47 Grand Total 48
Page of 15 18 Auxiliary Functions Testing
Integrated Protection Services, Inc. Download Date: 03/19/2025
Auxiliary Functions Testing Generated by: BuildingReports.com
Building: Dayton VA - #118 Control Panel: 35 - EST EST-3 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed Duct Detector
AHU Shutdown Basement AHU-1 Passed 16934975 AHU Shutdown Basement AHU-2 Passed 16934976 AHU Shutdown Basement AHU-3 Passed 16934977 AHU Shutdown Basement AHU-4 Passed 16934978 javascript:editViewDevice('16934975');
javascript:editViewDevice('16934976');
javascript:editViewDevice('16934977');
javascript:editViewDevice('16934978');
Page of 16 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: Dayton VA - #118 Control Panel: 35 - EST EST-3 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Failed/Other Sealed Lead Acid 1st Below Panel Total of 2 9 Ah 12 V
Page of 17 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Dayton VA - #118 Control Panel: 1 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Battery Control 2.08% 1
Control Panel Control 2.08% 1
Duct Detector Initiating 8.33% 4
Horn/Strobe Indicating 35.42% 17
Monitoring Monitor 2.08% 1
Pull Station Initiating 14.58% 7
Smoke Detector Initiating 35.42% 17
Type Qty Model # Description Install Date
In Service - 10 Years to 15 Years
EST
Horn/Strobe 17 G1F- HDVM 05/01/2012
Building: Dayton VA - #118 Control Panel: 35 - EST EST-3 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date
In Service - 5 Years to 10 Years Power-Sonic
Battery 1 PS-1290 F2 Sealed Lead Acid 03/25/2019
In Service - 10 Years to 15 Years Acadian
Monitoring 1 C218-5561 ZN 27 Alarm 05/01/2012
EST
Control Panel 1 EST-3 05/01/2012 Duct Detector 4 SIGA-SD Photoelectric 05/01/2012 Pull Station 1 SIGA-278 Dual Action 05/01/2012 Pull Station 6 SIGA-278 Single Action 05/01/2012 Smoke Detector 17 SIGA-PS Photoelectric 05/01/2012
Page of 18 18
Integrated Protection Services, Inc. Download Date: 03/19/2025
Zone Address Report Generated by: BuildingReports.com
Building: Dayton VA - #118 Control Panel: 35 - EST EST-3 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID Zone/Circuit: 02
0001 Duct Detector Basement AHU-1 Photoelectric 16934975 0002 Duct Detector Basement AHU-2 Photoelectric 16934976 0003 Duct Detector Basement AHU-3 Photoelectric 16934977 0004 Duct Detector Basement AHU-4 Photoelectric 16934978 0005 Smoke Detector Mezzanine Clock Tower Photoelectric 16934972 0006 Smoke Detector Basement North#1 Photoelectric 3907137800 0007 Smoke Detector Basement North#2 Photoelectric 3907137183 0008 Smoke Detector Basement North#3 Photoelectric 3907128020
Zone/Circuit: 2 9 Smoke Detector Basement Center #1 Photoelectric 04892993
Zone/Circuit: 02 0010 Smoke Detector Basement Center #2 Photoelectric 3907127382 0011 Smoke Detector Basement Center #3 Photoelectric 3907137466 0012 Smoke Detector Basement Center #4 Photoelectric 3907127214
Zone/Circuit: 2 13 Smoke Detector Basement South#1 Photoelectric 04892991
Zone/Circuit: 02 0014 Smoke Detector Basement South#2 Photoelectric 3907138647 0015 Smoke Detector Basement South#3 Photoelectric 3907138678 0016 Smoke Detector Basement Pipe Organ Blower Room Photoelectric 3907136636 0017 Smoke Detector Basement Storage Room Photoelectric 3907136520 0018 Smoke Detector Basement Bottom Of Steps Photoelectric 3907137138 0019 Smoke Detector Basement Under Step Storage Photoelectric 3956713185 0020 Smoke Detector Penthouse Chapel Ladder Photoelectric 40567464 0021 Smoke Detector 1st Above Panel Photoelectric 16934965 0126 Pull Station 1st South East Exit Single Action 16934968 0127 Pull Station 1st NorthEast Exit Single Action 16934969 0128 Pull Station Basement Bottom Of Steps Single Action 16934974…