(INFORMATIONAL) Reznor-UDX-TSL Specs.pdf
PDF 600 KB Posted
- Attached to
- ESB Arlington Shop Unit Heater
- Solicitation number
- S-73000-00008945
- Issued by
- Baker County, Barlow City, Oregon
About this file
This document contains the technical specifications for the Reznor UDX-TSL gas-fired unit heater. The heater is available in 14 different sizes ranging from 30,000 to 400,000 BTUh input and is certified for use in industrial, commercial, and residential applications in the United States and Canada. Key features include a patented single-burner combustion system, a TCORE2 titanium-stabilized aluminized-steel heat exchanger, and a variety of factory-installed and field-installed options such as gas valve configurations, heat exchanger materials, louver types, and control accessories. The document provides detailed technical data on the unit sizes, including input and output heating capacities, thermal efficiencies, electrical characteristics, airflow, and sound levels. It also includes information on clearances, weights, dimensions, and throw distances for the heater's standard horizontal louvers.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ESB_RFCQ_Attachments_279C.docx | DOCX document | |
| 35876 Intent To Award.xlsx | XLSX spreadsheet | |
| (INFORMATIONAL) PicHeatingUnit.docx | DOCX document | |
| ITB-Willow Creek Tenant Improvements Public Notice.pdf | ||
| ESB_RFCQ_279C_Final~3.docx | DOCX document | |
| Exhibit 1 (Technical Specifications)~1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Revision: UDX-TSL (07-23) REV-A
TECHNICAL SPECIFICATIONS FOR MODEL UDX
Supersedes: 652F-1122
GAS-FIRED, POWER-VENTED, LOW-STATIC AXIAL FAN,
COMMERCIAL/INDUSTRIAL/RESIDENTIAL, 82–83% THERMAL EFFICIENT UNIT HEATER
TABLE OF CONTENTS
Unit Sizes Features Factory-Installed Options Field-Installed Options Technical Data Certification Heater Throw Distances with Standard Horizontal Louvers Installation Codes Clearances Weights Dimensions
In keeping with our policy of continuous product improvement, we reserve the right to alter, at any time, the design, construction, dimensions, weights, etc., of equipment information shown here.
2 UDX-TSL (07-23) REV-A
TECHNICAL SPECIFICATIONS—CONTINUED
Unit Sizes
These heaters are available in fourteen unit sizes based on 30,000–400,000 BTUh input.
Features
• 115/1/60 supply
• Integrated circuit board with seven-segment display
• Easily-viewed status-indicating LED
• Hinged access door panel with quarter-turn latch
• Improved cabinet design with removable front face
• Two-toned white and black powder paint
• Patented single-burner combustion system
• Natural gas or propane
• 50–60°F temperature rise
• TCORE2® titanium-stabilized aluminized-steel heat exchanger
• External terminal strip for 24V wiring
• Built in disconnect switch
• Four-point suspension standard on all unit sizes (two-point suspension available on unit sizes 030–125 when installed without downturn nozzle or stepdown transformer)
Factory-Installed Options
Option Description AA1 Natural gas AA2 Propane AC1 Aluminized-steel heat exchanger AC2 409 SST heat exchanger AC4 316 SST heat exchanger AG1 Single-stage combination gas valve AG2 Two-stage combination gas valve AK1 115/1/60 voltage AL1 Open drip-proof motor AL14 Totally-enclosed motor
Option Description CC1 Vent cap CC21 SST vent cap CD1 Vertical louvers, direct discharge air to provide wider throw pattern CD2 Downturn nozzle, 25- to 65-degree variable air deflection range CD3 Downturn nozzle, 50- to 90-degree variable air deflection range CD4 Downturn nozzle, 25- to 65-degree variable air deflection range with vertical louvers CE1 Manual shutoff valve, natural gas or propane CG1 208V–115V stepdown transformer CG2 230V–115V stepdown transformer CG4 460V–115V stepdown transformer CK8 Adapts 3/8-inch hangers for two-point suspension from 1-inch threaded pipe CK10 Adapts 3/8-inch hangers for four-point suspension from 1-inch threaded pipe CK22 Angle brackets for low ceiling mounting (does not include hanger rods) CL1 Single-stage thermostat CL22 Two-stage thermostat
Field-Installed Options
3UDX-TSL (07-23) REV-A
Option Description
CL31, CL32 Multiple fan control: option CL31 includes components for one control unit and one additional unit— option CL32 includes components for each additional non-control unit
CM1 Locking cover for CL1 thermostat CM1B Locking cover for CL22 thermostat CM3 Bracket assembly for mounting thermostat on unit DJ20 High-elevation conversion DL2 Propane conversion
Parameter Unit of Measure
Unit Size 030 045 060 075 100 125
Input heating capacity BTUh 30,000 45,000 60,000 75,000 105,000 120,000 kW 8.8 13.2 17.6 22.0 30.8 35.2 Thermal efficiency % 82 83 83 83
Output heating capacity* BTUh 24,600 37,350 49,800 62,250 87,150 99,600 kW 7.2 10.9 14.6 18.2 25.5 29.2
Gas connection, natural gas** inch
1/2 Gas connection, propane** Vent connection diameter*** 4
Control, 24V amp
1.0 Full load amps, 115V 1.9 2.4 2.4 3.7 4.3 5.6
Maximum overcurrent protection, 115V† 15
Normal power consumption watt 109 155 155 217 276 354 Discharge air temperature rise °F 50 55 60 60
Air volume
CFM 456 629 769 961 1345 1537
meter3/minute 12.9 17.8 21.8 27.5 36.7 45.9
Discharge air opening area feet2 0.96 1.25 2.01 meter2 0.09 0.12 0.19
Output velocity
FPM 475 656 616 770 668 763
meter/minute 145 200 188 235 204 233 Open fan motor size
HP
0.02 0.03 0.03 0.06 1/30 1/20
Totally-enclosed fan motor size 0.06 0.06 1/4 Fan motor speed RPM 1550 1550 1050 Fan diameter inch 10 12 16 Sound level @ 15 feet dBa 40 40 49 54 55
*ETL ratings for elevations up to 2,000 feet.
**Size shown is for gas connection to a single-stage gas valve—not supply line size.
***Smaller and/or larger vent and combustion air pipe diameters may be permissible (refer to appropriate venting instructions).
†MOCP = 2.25 × (largest motor FLA) + smallest motor FLA. Answer is rounded to the next lower standard circuit breaker size.
Technical Data
Parameter Unit of Measure
Unit Size 150 175 200 225 250 300 350 400
Input heating capacity BTUh 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000 kW 44.0 51.3 58.6 65.9 73.3 87.9 102.6 117.2
Thermal efficiency % 83
Output heating capacity* BTUh 124,500 145,250 166,000 186,750 207,500 249,000 290,500 332,000 kW 36.5 42.6 48.7 54.7 60.8 73.0 85.1 97.3
Gas connection, natural gas** inch
1/2 3/4 3/4 Gas connection, propane** Vent connection diameter*** 5 5 6
*ETL ratings for elevations up to 2,000 feet.
**Size shown is for gas connection to a single-stage gas valve—not supply line size.
***Smaller and/or larger vent and combustion air pipe diameters may be permissible (refer to appropriate venting instructions).
4 UDX-TSL (07-23) REV-A
Certification
These unit heaters are listed by Intertek for use in industrial and commercial installations in the United States and Canada. In addition, unit sizes 030, 045, 060, 075, 100, and 125 are listed in the United States and Canada as utility heaters for use in non-living spaces that are attached to, adjacent to, or part of a structure that contains space for family living quarters.
Heater Throw Distances with Standard Horizontal Louvers
The graphic shows throw patterns and the table lists throw distances for heaters suspended at varying mounting heights. The louver angles listed are relative to the top of the heater.
Z = Distance at which air velocity drops below 50 feet (15.2 meters) per minute
TECHNICAL SPECIFICATIONS—CONTINUED
Technical Data—Continued
Parameter Unit of Measure
Unit Size 150 175 200 225 250 300 350 400
Control, 24V amp
1.0 Full load amps, 115V 3.8 4.6 7.5 7.5 11.0
Maximum overcurrent protection, 115V† 15 15 20
Normal power consumption watt 392 491 747 747 1086 Discharge air temperature rise °F 60
Air volume
CFM 1921 2242 2562 2882 3202 3843 4483 5123
meter3/minute 54.4 63.5 72.5 81.6 90.7 108.8 126.9 145.1
Discharge air opening area feet2 2.56 3.51 3.51 4.79 meter2 0.24 0.33 0.33 0.45
Output velocity
FPM 752 877 1003 820 911 802 936 1069
meter/minute 229 267 306 250 278 244 285 326 Open fan motor size
HP
1/6
1/4 1/4 1/2 Totally-enclosed fan motor size 1/4 Fan motor speed RPM 1050 Fan diameter inch 18 20 20 24 Sound level @ 15 feet dBa 51 52 53 56 56 59 61 62 †MOCP = 2.25 × (largest motor FLA) + smallest motor FLA. Answer is rounded to the next lower standard circuit breaker size.
5UDX-TSL (07-23) REV-A
H* (Feet
(Meters)) Distance* or Angle
Unit Size 030 045 060 075 100 125 150
Feet (Meters)
5 (1.5)
X 6 (1.8) 7 (2.1) 8 (2.4) 9 (2.7) 9 (2.7) 10 (3.0)
Y 14 (4.3) 16 (4.9) 18 (5.5) 20 (6.1) 20 (6.1) 22 (6.7) Z 30 (9.1) 40 (12.2) 45 (13.8) 57 (17.4) 59 (18.0) 65 (19.9)
Downward louver angle 21° 20° 16° 14° 18° 14°
8 (2.4)
X 7 (2.1) 9 (2.7) 10 (3.0) 12 (3.7) 11 (3.4) 12 (3.7) 13 (4.0) Y 13 (4.0) 16 (4.9) 18 (5.5) 22 (6.7) 21 (6.4) 23 (7.0) 24 (7.3) Z 26 (7.9) 37 (11.3) 42 (12.8) 54 (16.5) 56 (17.1) 63 (19.2) 73 (22.3)
Downward louver angle 39° 34° 29° 25° 28° 24° 26°
10 (3.0)
X 6 (1.8) 9 (2.7) 10 (3.0) 12 (3.7) 12 (3.7) 13 (4.0) 14 (4.3) Y 11 (3.4) 15 (4.6) 17 (5.2) 22 (6.7) 20 (6.1) 24 (7.3) 24 (7.3) Z 22 (6.7) 33 (10.0) 39 (11.9) 52 (15.8) 52 (15.8) 60 (18.3) 69 (21.0)
Downward louver angle 52° 43° 37° 32° 36° 30° 32°
12 (3.7)
X
8 (2.4) 10 (3.0) 12 (3.7) 11 (3.4) 14 (4.3) 14 (4.3) Y 12 (3.7) 16 (4.9) 21 (6.4) 19 (5.8) 23 (7.0) 24 (7.3) Z 27 (8.2) 34 (10.4) 48 (14.6) 47 (14.3) 57 (17.4) 64 (19.5)
Downward louver angle 55° 46° 39° 44° 36° 39°
14 (4.3)
X
9 (2.7) 12 (3.7) 11 (3.4) 14 (4.3) 14 (4.3) Y 14 (4.3) 19 (5.8) 17 (5.2) 22 (6.7) 22 (6.7) Z 29 (8.8) 44 (13.4) 42 (12.8) 53 (16.1) 59 (18.0)
Downward louver angle 56° 46° 51° 43° 45°
16 (4.9)
X
11 (3.4) 10 (3.0) 13 (4.0) 13 (4.0) Y 17 (5.2) 14 (4.3) 20 (6.1) 20 (6.1) Z 38 (11.6) 34 (10.4) 47 (14.3) 53 (16.2)
Downward louver angle 54° 58° 50° 51°
18 (5.5)
X
11 (3.4) 11 (3.4) Y 17 (5.2) 17 (5.2) Z 40 (12.2) 44 (13.4)
Downward louver angle 57° 58°
H* (Feet
(Meters)) Distance* or Angle
Unit Size 175 200 225 250 300 350 400
Feet (Meters)
8 (2.4)
X 15 (4.6) 16 (4.9) 14 (4.3) 16 (4.9) 15 (4.6) 17 (5.2) 18 (5.5) Y 28 (8.5) 30 (9.1) 27 (8.2) 29 (8.8) 28 (8.5) 31 (9.4) 34 (11.3) Z 90 (27.4) 93 (28.0) 86 (26.2) 93 28.3 94 (28.7) 105 (32.0) 113 (34.4)
Downward louver angle 22° 20° 24° 21° 24° 20° 17°
10 (3.0)
X 17 (5.2) 17 (5.2) 15 (4.6) 17 (5.2) 16 (4.9) 18 (5.5) 20 (6.1) Y 29 (8.8) 31 (9.4) 27 (8.2) 30 (9.1) 28 (8.5) 32 (9.8) 35 (10.7) Z 87 (26.6) 91 (27.7) 82 (25.0) 90 27.4 89 (27.1) 103 (31.4) 110 (33.5)
Downward louver angle 27° 25° 30° 26° 29° 25° 21°
12 (3.7)
X 18 (5.5) 18 (5.5) 16 (4.9) 18 (5.5) 17 (5.2) 19 (5.8) 21 (6.4) Y 29 (8.8) 31 (9.4) 27 (8.2) 30 (9.1) 28 (8.5) 32 (9.8) 36 (11.0) Z 84 (25.6) 88 (26.8) 78 (23.8) 87 26.5 85 (25.9) 98 (29.9) 108 (32.9)
Downward louver angle 32° 30° 35° 31° 34° 30° 25°
14 (4.3)
X 18 (5.5) 19 (5.8) 16 (4.9) 18 (5.5) 17 (5.2) 20 (6.1) 23 (7.0) Y 28 (8.5) 30 (9.1) 26 (7.9) 30 (9.1) 27 (8.2) 32 (9.8) 35 (10.7) Z 79 (24.1) 84 (25.6) 73 (22.3) 83 25.3 80 (24.4) 95 (29.0) 105 (32.0)
Downward louver angle 37° 34° 41° 36° 40° 34° 29°
16 (4.9)
X 18 (5.5) 19 (5.8) 16 (4.9) 19 (5.8) 17 (5.2) 21 (6.4) 23 (7.0) Y 27 (8.2) 29 (8.8) 24 (7.3) 28 (8.5) 25 (7.6) 31 (9.4) 35 (10.7) Z 74 (22.6) 79 (24.1) 67 (20.4) 78 23.8 74 (22.6) 90 (27.4) 101 (30.8)
Downward louver angle 42° 39° 47° 41° 45° 38° 33°
18 (5.5)
X 17 (5.2) 19 (5.8) 14 (4.3) 18 (5.5) 16 (4.9) 20 (6.1) 23 (7.0) Y 26 (7.9) 28 (8.5) 22 (6.7) 27 (8.2) 24 (7.3) 30 (9.1) 35 (10.7) Z 68 (20.7) 74 (22.6) 60 (18.3) 72 (21.9) 66 (20.1) 85 (25.9) 97 (26.9)
Downward louver angle 48° 44° 53° 46° 51° 43° 37°
*See graphic above.
6 UDX-TSL (07-23) REV-A
Heater Surface
Unit Size 030–125 150–400
Minimum Clearance (Inches (mm)) Top 1 (25) 4 (102)
Flue connector 6 (152) 6 (152) Access panel 18 (457) 18 (457)
Non-access side 1 (25) 2 (51)
Bottom* 1 (25) 1 (25)
Rear** 18 (457) 18 (457)
Front Refer to values for variable X (distance from heater to start of floor coverage) in Heater Throw Distances with Standard Horizontal Louvers section
*Suspend the heater so that the bottom is a minimum of 5 feet (1.5 meters) above the floor.
**Measure rear clearance from the fan motor.
Weights
Type
Unit Size
030 045 060 075 100 125 150 175, 200 225 250 300 350 400
Pounds (kg)
Unit 57 (26)
(28)
(32)
(34)
(46)
(48)
(81)
(88)
(96)
(101)
(126)
(137)
(143)
Shipping 63 (29)
(31)
(34)
(37)
(54)
(57)
(93)
(100)
(112)
(117)
(147)
(158)
(163)
TECHNICAL SPECIFICATIONS—CONTINUED
Installation Codes
• These units must be installed in accordance with local building codes. In the absence of local codes, in the United States, the unit must be installed in accordance with the National Fuel Gas Code, ANSI Z223.1. A Canadian installation must be in accordance with the CSA B149 Natural Gas and Propane Installation Code. This code is available from CSA Information Services, 1-800-463-6727. Local authorities having jurisdiction should be consulted before installation is made to verify local codes and installation procedure requirements.
• Installations in aircraft hangars should be in accordance with ANSI/NFPA No. 409 (latest edition), Standard for Aircraft Hangars. Installations in public garages should be in accordance with ANSI/NFPA No. 88A (latest edition), Standard for Parking Structures. Installations in repair garages should be in accordance with ANSI/NFPA No. 88B (latest edition), Standard for Repair Garages. In Canada, installations in aircraft hangars should be in accordance with the requirements of the enforcing authorities, and in public garages, in accordance with the CSA B149 code.
• If the heater is being installed in the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or licensed gas fitter.
Clearances
Units must be located so that clearances are provided for with regards to combustion air space, inspection, and service and for proper spacing from combustible construction. Clearance to combustibles is defined as the minimum distance from the heater to a surface or object for which it is necessary to ensure that a surface temperature of 90°F (50°C) above the surrounding ambient temperature is not exceeded.
7UDX-TSL (07-23) REV-A
TOP VIEW REAR VIEW
FRONT VIEW SIDE VIEW
A C
B D F
E
Q
THERMOSTAT
CONNECTION
P
N
R
M
K H
G J
S
T
GAS
CONNECTION
VENT CONNECTION
Dimensions
Dimension (See Graphic
Above)
Unit Size 030, 045 060 075 100 125 150, 175, 200 225, 250 300, 350, 400
Inches (mm) A 13-3/4 (349) 16-3/4 (425) 24-3/4 (629) 20-1/8 (511) 26-1/8 (664) 34-1/8 (867) B 27 (686) 38-3/16 (970) 41 (1041) C 10 (254) 13 (330) 21 (533) 16 (406) 22 (559) 30 (762) D 13-13/16 (351) 23 (584) E 29-3/4 (756) 32-23/32 (831) 31-29/32 (810) 34-9/32 (871) 34-9/32 (871) 48-7/16 (1230) 48-29/32 (1243) F 25-9/16 (649) 40 (1016) G 6 (152) 8-11/16 (221) 15-5/16 (389) 9-5/8 (244) 13-1/16 (332) 17-1/16 (433) H 5-15/16 (151) 8-5/16 (211) 8-1/2 (216) J 3-1/2 (89) 6 (152) 8-29/32 (226) 5-3/8 (137) 9 (229) 11-13/16 (300) K 3-11/32 (85) 6-1/2 (165) 7-5/16 (186)
M* 17-3/8 (441) 25-11/16 (652) 27-11/16 (703)
N* 1-9/16 (40) 1-13/32 (36)
P* 4-9/32 (109) 8-1/8 (206)
Q* 13 (330) 22-3/16 (564)
R** 11-9/16 (294) 16-3/8 (416) 15-5/8 (397) 16-1/4 (413)
S 3-3/4 (95) 4-1/16 (103) 5-15/32 (139) 5-1/2 (140) 8-1/16 (205) 11-9/16 (294) T 2-15/16 (75) 4-1/4 (108) 4-5/16 (110) 4-1/2 (114)
*Heater suspension points for four-point suspension (3/8-16 FEM).
**Heater suspension points for two-point suspension (3/8-16 FEM).
Specifications and illustrations subject to change without notice or incurring obligations.
Latest version of this document is available at www.reznorhvac.com.
©2023 Nortek Global HVAC LLC, O’Fallon, MO. All rights reserved.
UDX-TSL (07-23) REV-A
AG
ENCY PROCESS
ST
A
R T-
U P
PRODUCT
C U
STO
M
ER
WARRANTY
CONVERGENT
QUALITY SYSTEM
CQSCQS
For more information on Reznor HVAC products:
• Contact your local Reznor representative at 1-800-695-1901
• Refer to the manuals and additional consumer materials found at www.reznorhvac.com
⚠ DANGER ⚠
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
• Improper installation, adjustment, alteration, service, or maintenance can cause serious injury, death, or property damage.
• Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
• Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a phone remote from the building. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
http://www.reznorhvac.com http://www.reznorhvac.com
| TECHNICAL SPECIFICATIONS FOR MODEL UDX |
| Unit Sizes |
| Features |
| Factory-Installed Options |
| Field-Installed Options |
| Technical Data |
| Certification |
| Heater Throw Distances with Standard Horizontal Louvers |
| Installation Codes |
| Clearances |
| Weights |
| Dimensions |