Sample Firestopping Detail 5.pdf

PDF 130 KB Posted

Attached to
Z1DA--620A4-19-202 Replace Chilled Water Lines Construction at Castle Point VAMC
Solicitation number
IFB-36C77625B0036
Issued by

About this file

This document is a technical specification sheet for a firestopping system (System No. F-A-1011) issued by 3M Fire Protection Products. The specification details a fire protection solution for metallic pipe penetrations through concrete floors or walls with the following key characteristics:

The system is rated for a 2-hour fire and temperature resistance (F Rating and T Rating of 2 Hr) and applies to concrete assemblies at least 6 inches thick. It accommodates metallic pipes, conduits, or tubing with a maximum opening diameter of 2 inches, including steel pipe, electrical conduit, and copper tubing/pipe up to 1 inch in diameter. The penetration can be installed concentrically or eccentrically with an annular space between 0 and 7/8 inches. The firestop is achieved using 3M CP 25WB+ caulk or FB-3000 WT sealant, applied with a minimum 1/2 inch thickness and a 1/2 inch diameter bead at the penetrant/concrete interface on both sides of the floor or wall.

View the file

Other files

File Type Posted
Amendment 5 - 36C77625B0036 0005 8-5-2025.pdf PDF
Online Bid Opening Meeting Info.docx DOCX document
Sample Firestopping Detail 3.pdf PDF
03 30 00.pdf PDF
Sample Firestopping Detail 6.pdf PDF
Sample Firestopping Detail 4.pdf PDF
Sample Firestopping Detail 1.pdf PDF
RFI TRACKING SHEET - SOLICITATION 36C77625B0036 - Project 620A4-19-202.pdf PDF
Amendment 4 - 36C77625B0036 0004 7-30-25.pdf PDF
Construction Wage Rates - Dutchess County - 7-25-25.pdf PDF
Sample Firestopping Detail 2.pdf PDF
chilled water lines photos - Question 26.zip ZIP file
Amendment 3 - 36C77625B0036 0003 7-21-25.pdf PDF
Amendment 2 - 36C77625B0036 0002 7-16-2025.pdf PDF
Construction Wage Rates - Dutchess County - 7-4-25.pdf PDF
Amendment 1 - 36C77625B0036 0001 7-8-2025.pdf PDF
Castle Point Site Visit Sign-in Sheet 7-8-25.pdf PDF
Attachment 2 - 620A4-19-202 Combined Plans-Bid Documents.pdf PDF
Attachment 6 - Site Visit Instructions.pdf PDF
Attachment 3 - 620A4-19-202 VHA PCRA 2024_1.1 5-20-25.pdf PDF
Attachment 7 - RFI TRACKING SHEET - SOLICITATION 36C77625B0036 - Project 620A4-19-202.xlsx XLSX spreadsheet
IFB 36C77625B0036.pdf PDF
Attachment 5 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 4 - Construction Wage Rates - Dutchess County - 6-20-25.pdf PDF
Attachment 1 - 620A4-19-202 Specifications Combined.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M et a lli c P ip es Th ro ug h Pe ne tra tio ns

S er ie s

C on cr et e

3Fire Protection Products www.3m.com/firestop

Product Support Line 1-800-328-1687F-A-1011 • 1 of 1

FA

System No. F-A-1011 September 07, 2004

F Rating – 2 Hr T Rating – 2 Hr

1. Floor or Wall Assembly – Min 6 in. thick UL Classified hollow-core Precast Concrete Units*. Floor may also be constructed of any min 6

in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Max diam of opening is 2 in.

See Precast Concrete Units (CFTV) category in the Fire Resistance Directory for names of manufacturers.

2. Through Penetrants – One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system.

Pipe, conduit or tubing to be rigidly supported on both sides of floor assembly. The annular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in. (point contact) to max 7/8 in. The following types and sizes of metallic pipes, conduits or tubings may be used:

A. Steel Pipe – Nom 1 in. diam (or smaller) Schedule 5 (or heavier) steel pipe.

B. Conduit – Nom 1 in. diam (or smaller) steel electrical metallic tubing or steel conduit.

C. Copper Tubing – Nom 1 in. diam (or smaller) Type L (or heavier) copper tube.

D. Copper Pipe – Nom 1 in. diam (or smaller) Regular (or heavier) copper pipe.

3. Fill, Void or Cavity Materials* – Caulk or Sealant – Min 1/2 in. thickness of fill material applied within annulus, flush with each surface of floor. Min 1/2 in. diam bead of caulk applied to the penetrant/concrete interface at the point contact location on both sides of floor.

3M COMPANY – CP 25WB+ caulk or FB-3000 WT sealant.

*Bearing the UL Classification Marking

Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc.

Copyright © 2010 Underwriters Laboratories Inc.®