IFB J27219 SPECIFICATIONS.pdf

PDF 576 KB Posted

Attached to
IFB J27219 Hoapili Hale Air Conditioning and Ventilation Systems
Solicitation number
B27000550
Issued by
Hawaii

About this file

IFB J27219 Summary

This Invitation for Bids (IFB) issued by The Judiciary, State of Hawaii, solicits proposals for comprehensive air conditioning and ventilation system maintenance services and chemical water treatment at the Hoapili Hale facility (Judiciary, Second Circuit) located at 2145 Main Street, Wailuku, Maui. The scope of work includes routine and preventive maintenance of two operational helical liquid chillers (CH-1, CH-2), one air-cooled scroll chiller (ACC-1, currently inoperable), two cooling towers (CT-1, CT-2), air handling units, pumps, ventilating exhaust fans, valves, and related mechanical equipment. Services required encompass monthly, quarterly, semi-annual, and annual maintenance tasks, emergency service response within one to two hours, diagnostic troubleshooting, chemical water treatment of cooling towers, condenser and chilled water systems, and all associated labor, materials, parts, and refrigerants. The pre-bid meeting is scheduled for September 4, 2026, with questions due by an unspecified deadline and responses provided via the Hawaii Electronic Procurement System (HIePRO). Bids are due October 21, 2026, at 12:00 PM Hawaii Standard Time, with a tentative award date in October 2026. The contract commences January 1, 2027, and runs through December 31, 2027, with three optional one-year renewal extensions subject to fund availability.

Bidders must submit a lump-sum price covering all preventive maintenance services broken down by monthly, quarterly, semi-annual, and annual line items, plus separate pricing for the currently inoperable air-cooled chiller to commence upon restoration. Additional pricing must be provided for authorized extra work, including hourly labor rates for HVAC technicians and apprentices (regular and overtime), diagnostic calls, refrigerant purchases, and markups for OEM and non-OEM parts and equipment rental. Prospective offerors must be State of Hawaii certified to perform air conditioning maintenance, possess an active General Excise Tax license, hold a valid C-52 Contractor License, and demonstrate minimum five years' consecutive experience in helical and scroll chiller maintenance. The firm must employ at least four full-time air conditioning maintenance personnel, including two journeymen refrigeration/air conditioning mechanics (each with five years' experience) and two additional refrigeration mechanics (with three years' experience). All mechanics must hold universal refrigeration certification and self-contained breathing apparatus training. Offerors must provide three references, proof of required insurance coverage ($1,000,000 general liability, $1,000,000 automobile, workers' compensation, and $1,000,000 professional liability), and complete qualification and wage certificates. A mandatory 0.75% transaction fee (not to exceed $5,000 for the contract term) applies to awarded amounts through HIePRO. The Judiciary reserves the right to add or delete equipment, add up to five units without price increase, and assess liquidated damages of $250 per calendar day for failure to meet performance requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

THE JUDICIARY

STATE OF HAWAIʻI

INVITATION FOR BIDS

NO. J27219

PROVIDE AIR CONDITIONING AND

VENTILATION SYSTEM

MAINTENANCE SERVICE AND

CHEMICAL WATER TREATMENT

OF AIR CONDITIONING EQUIPMENT

AT THE JUDICIARY FACILITY ON MAUI

THE JUDICIARY, STATE OF HAWAIʻI

October 2026

TABLE OF CONTENTS

IFB ADMINISTRATIVE INFORMATION

SCHEDULE AND SIGNIFICANT DATES

SOLICITATION INFORMATION

SECTION ONE - AIR CONDITIONING AND VENTILATION SYSTEM SPECIFICATIONS

SECTION TWO – SPECIFICATIONS CHEMICAL WATER TREATMENT

SECTION THREE - SPECIAL PROVISIONS

SECTION FOUR - OFFER QUALIFICATION FORM

WAGE CERTIFICATE

ATTACHMENTS:

Hoapili Hale – Mechanical Equipment/Service Schedule with Chiller #3 General Conditions

Special Conditions Procedural Requirements Discrimination Harassment Free Workplace Policy Standards of Conduct Declaration Hawaii Bidder/Offeror Preference Certification Form (JUD-081)

THE JUDICIARY, STATE OF HAWAIʻI

HONOLULU, HAWAIʻI

INVITATION FOR BIDS NO. J27219

IFB ADMINISTRATIVE INFORMATION

IFB Title PROVIDE AIR CONDITIONING AND

VENTILATION SYSTEM MAINTENANCE

SERVICE AND CHEMICAL WATER

TREATMENT OF AIR CONDITIONING

EQUIPMENT AT THE JUDICIARY

FACILITY ON MAUI, THE JUDICIARY,

STATE OF HAWAIʻI

IFB Project Description (See Specifications)

IFB Point of Contact: (See Officer-In- Charge)

Name – Mr. Dino Edmalin Agency Name - Judiciary Email – honeydean.d.edmalin@courts.hawaii.gov

Submit proposals electronically via Hawaii Electronic Procurement System (HIePRO): (See Submission of Offer)

Electronic Submission hiepro.ehawaii.gov

IFB Closing Date: (See Schedule and Significant Dates)

October 21, 2026

IFB Closing Time: (See Schedule and Significant Dates)

12:00 PM, Hawaiʻi Standard Time (HST)

Initial Term of Contract and Renewals:

(See Term of Contract)

January 1, 2027 and end on December 31, 2027

With the possibility for an additional three (3) twelve (12) month options to extend, subject to the availability of funds.

TAKE NOTE THE MANDATORY .75% (.0075) TRANSACTION FEE TO HAWAII

INFORMATION CONSORTIUM, LLC DBA TYLER HAWAII IS BASED ON

SALES FOR AWARDS MADE IN HIEPRO. (DETAILED IN SECTION

ELECTRONIC PROCUREMENT AND SECTION PAYMENT TO HAWAII

INFORMATION CONSORTIUM, LLC DBA TYLER HAWAII.)

mailto:honeydean.d.edmalin@courts.hawaii.gov

SCHEDULE AND SIGNIFICANT DATES

The significant dates for this project are as follows:

BIDS DUE

October 21, 2026, 12:00 PM

Tentative Contract Award Date

October, 2026

Tentative Contract Start Date

January 1, 2027

SOLICITATION INFORMATION

GOVERNING LAWS AND REGULATIONS

This procurement is conducted by the Judiciary in accordance with the regulations and laws of the State of Hawaiʻi. Venue for any administrative or judicial action relating to this procurement, evaluation, and award shall be in the State of Hawaiʻi.

ELECTRONIC PROCUREMENT

The Judiciary has established the Hawaii State eProcurement (HIePRO) System to promote an open and transparent system for vendors to compete for state contracts electronically. Offerors interested in responding to this solicitation must be registered on lepro. Registration information is available at the State Procurement Office (SPO) website: https://hiepro.ehawaii.gov/welcome.html, select Herro Vendor Registration and then Vendor Registration Guide.

The Judiciary will use hero to issue the IFB, receive Offers, and issue Addenda to the IFB. Addenda and the other information and materials shall be provided by the Judiciary through HlePRO, including additions or changes with respect to the dates in Schedule and Significant Dates. The Judiciary is not responsible for any delay or failure of any Offeror to receive any materials updated through the IFB Process on a timely basis.

As part of this procurement process, Offerors are informed that awards made for this solicitation, if any, shall be done through HlePRO and shall, therefore, be subject to a mandatory .75% (.0075) transaction fee, not to exceed $5,000 for the total contract term.

hero Special Instructions. Offeror shall review all special instructions located in Herro.

Offerors are responsible for ensuring that all necessary files are attached to their offer prior to the bid deadline.

Offerors are advised that they should not wait until the last minute to submit their bid on HlePRO. Offerors should allow ample time to review their submitted bid, including attachments, prior to the bid deadline.

IFB ADDENDA

Changes to this IFB including but not limited to contractual terms and procurement requirements shall only be changed through formal written addenda issued by the Judiciary.

The Judiciary accepts no responsibility for a prospective Offeror not receiving solicitation documents and/or revisions to the solicitation. It is the responsibility of the prospective Offeror to monitor the Hawaii State eProcurement System (HlePRO) to obtain IFB addenda or other information relating to the IFB.

QUESTIONS REGARDING IFB CONTENTS

If a Prospective Offeror believes that any provision of the IFB is unclear, potentially defective, or would prevent from providing a meaningful Offer, the Offeror shall submit questions regarding this solicitation through HIePRO on or before the deadline indicated in Schedule and Significant Dates. Each question shall identify the page, section number, paragraph, and line or sentence of such provision(s) of the IFB to which the question applies. The Judiciary will respond by the response date specified in Schedule and Significant Dates. The Judiciary may issue Addenda in response to written questions received regarding the IFB.

ELECTRONIC SUBMISSION OF QUESTIONS

All questions must be submitted through the Hawaii State eProcurement System (HlePRO). Questions must be submitted by the question deadline date and time shown in Schedule and Significant Dates. Answers will be given via the Hawaii State eProcurement System (HlePRO) site as noted in Schedule and Significant Dates.

Offerors are cautioned about including context in questions that may reveal the source of questions. The identity of potential Offerors will not be published with the answers, but the text of questions will be restated, to the extent possible, to exclude information identifying potential Offerors.

CANCELLATION OF PROCUREMENT AND BID REJECTION

The Judiciary reserves the right to cancel this IFB and to reject any and all bids in whole or in part and waive any defects when it is determined to be in the best interest of the Judiciary, pursuant to HAR §3-122-96 thru HAR §3-122-97.

FIRM OFFERS

Responses to this IFB, including proposed prices and/or fees will be considered firm for 90 days from the bid due date.

RIGHT TO ACCEPT ALL OR PORTION OF BIDS

Unless otherwise specified in the solicitation, the Judiciary may accept any item or combination of items as specified in the solicitation or of any bid unless the Offeror expressly restricts an item or combination of items in its Bids and conditions its response on receiving all items for which it provided a bid. If the Offeror so restricts its Bid, the Judiciary may consider the Offeror's restriction and evaluate whether the award on such basis will result in the best value to the Judiciary. The Judiciary may otherwise determine at its sole discretion that such restriction is non-responsive and renders the Offeror ineligible for further evaluation

OWNERSHIP OF DISPOSITION OF BIDS AND OTHER MATERIALS SUBMITTED

All costs incurred by the Offeror in preparing or submitting a bid shall be the Offeror's sole responsibility whether any award results from this IFB. The Judiciary shall not reimburse such costs. All bids become the property of the State of Hawaii.

ADDITIONAL INFORMATION

The Offeror shall provide additional information regarding aspects of an Offeror's Bid within five (5) business days of the Judiciary's request unless the Judiciary specifies another period. As noted, each Offeror shall submit only one Bid. If an Offeror submits more than one Bid, then the Judiciary reserves the right to reject and or dismiss the Offeror from the IFB Process.

PAYMENT TO HAWAII INFORMATION CONSORTIUM, LLC DBA TYLER HAWAII

A mandatory .75% (.0075) transaction fee is charged to the awarded Contractor(s) based on the awarded amount. HlePRO is administered by Hawaii Information Consortium, LLC dba Tyler Hawaii. Hawaii Information Consortium, LLC shall invoice the awarded Contractor(s) directly for payment of transaction fees. Payment must be made to Hawaii Information Consortium, LLC within thirty (30) days from receipt of invoice. Hawaii Information Consortium, LLC is an intended third-party beneficiary of transaction fees, which are used to fund the operation, maintenance, and future enhancements of the HlePRO system.

END OF SECTION

Judiciary, Second Circuit (Hoapili Hale)

SECTION ONE

AIR CONDITIONING AND VENTILATION SYSTEM SPECIFICATIONS

1.1 SCOPE

The Contractor shall furnish all labor, materials, parts, tools, lubricants, refrigerants, equipment, transportation and supervision necessary for the complete maintenance, inspections and diagnostics to the Air Conditioning and Ventilation Systems for the Judiciary, Second Circuit (Hoapili Hale) and in accordance to these Specifications, the Special Provisions and the General Conditions attached hereto and by reference made a part hereof. The Contractor shall perform routine maintenance of all air conditioning, ventilation and listed systems within this contract.

1.2 JOB SITE

The Contractor shall provide air conditioning, ventilation and listed services for the Judiciary, Second Circuit, Hoapili Hale located at 2145 Main Street, Wailuku, Hawaii 96793.

1.3 DESCRIPTION OF WORK

The Contractor shall be responsible to maintain all systems for complete and satisfactory operations and in accordance with the best commercial standards. Any questions as to the satisfactory performance of maintenance service and the satisfactory operation of all equipment and systems shall be determined by the Officer-in-Charge or designee.

The Contractor shall perform complete maintenance and diagnostic services, including inspections and emergency calls for all equipment included under this contract. The service shall consist of thorough maintenance work in accordance with the best commercial practice governing the maintenance of air conditioning, ventilation and listed systems. Such service shall include regularly scheduled maintenance tasks and inspections of each unit listed herein. All maintenance tasks, diagnostics and inspections shall consist of, but not limited to furnishing of all labor, equipment, parts, materials and tools necessary to perform a thorough servicing of all integral parts, lubrication, adjusting, protective painting and replacing of all parts where needed to keep the units in continuous operating condition.

The Contractor shall not be responsible for repairs due to flagrant vandalism, fire, storm or related damages which can be attributed to causes beyond his control. However, the Contractor shall be responsible for such repairs if the damages are caused by the Contractor’s failure to properly maintain and repair the equipment, e.g., failure to reinstall protective covers causes the motor to burn during a rainstorm.

All services performed by the Contractor will be subject to inspection by the Office-in-Charge or designee and shall include applicable items listed but, not be limited to the following maintenance tasks.

Reported discrepancies to be followed up with a repair submittal as required within these specifications.

Abbreviations:

CHW – Chilled Water CHWS – Chilled Water Supply VFD – Variable Frequency Drive VAV – Variable Air Valve CH – Chiller Deg. F – Degrees Fahrenheit ARI – Air Conditioning and Refrigeration Institute PSI – Pounds Per Square Inch UV – Ultra Violet EXV – Electric Expansion Control Valve RTWD – Trane, Helical Rotary Chiller CT – Cooling Tower GPM – Gallons Per Minute ZRC – High Zinc Cold Galvanizing Compound MERV - Minimum Efficiency Reporting Value (Air filter rating)

A. AIR HANDLING UNIT

Monthly Service

1. Change all disposable air filters at least once a month; use FARR 30/30 or equal with the exception of AHU’s 1-1 & 1-2 which use merv 13 filters.

2. Clean and clear all drip pans, flush all related condensate drain lines with nitrogen and add algae tabs as required. (Note: Contractor may be liable for water damage due to clogged drains)

3. Lubricate and oil all fan and motor bearings and connections of dampers and vanes.

Note: Do not over lubricate items which may lead to premature failure.

4. Check all drives/sheaves for wear; adjust belt tension and alignment. Replace belt as required.

5. Operate equipment, check for unusual noise and vibration, check UV lights for proper operation;

adjust all equipment and controls as required; clean up all equipment.

6. Check condition of insulation; repair/reinsulate anytime disturbing of insulation is required to make repairs, or upon discovery or notification.

7. Certify performance of monthly services and that all discrepancies are reported and corrected as required.

Annual Service

1. Clean cooling coils of dirt accumulation using nitrogen, high pressure air/water, steam or chemical coil cleaner solution. Note: This service will be conducted as an after hour service scheduled with Facilities Management. Therefore, Contractor shall include this after hour service schedule cost in their bid price.

2. Clean all fan wheels, interior and exterior of equipment housings.

3. Secure all loose housings, access doors, safety guards, seal leaks, and touch up paint after cleaning all rust.

4. Replace UV lights in all AHU’s equipped with this system. Note: Parts shall be included in the bid price.

5. Certify performance of annual service, report all discrepancies and correct as required.

B. VALVES AND CHILLED WATER LINES, EQUIPMENT AND SUPPORTS

Annual Service

1. The contractor shall exercise all equipment shut-off valves annually for proper operation and tightness.

2. Check all chilled water line insulation for proper coverage and leaks.

3. Check all chilled water lines, valves and actuators for proper bracing/support.

4. Certify that all discrepancies are reported and corrected as required.

C. HELICAL LIQUID CHILLER - CH-1, CH-2

Note: Refer to the manufacturer’s technical service manual attached and located in the Facilities Maintenance Office.

WARNING - Hazardous Voltage!

Disconnect all electric power, including remote disconnects and discharge all. Motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged.

Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.

Monthly After the unit has operated for approximately 30 minutes and system has been stabilized, check the operating conditions and complete the procedures below:

1. Log the chiller (Supplied - manufactures check list)

2. Visual checks for water, refrigerant and oil leakage.

3. Certify performance of monthly maintenance service, correct and report all discrepancies.

Quarterly

1. Perform Monthly Maintenance and Checks procedures.

2. Review chiller log.

3. Check evaporator and condenser pressures with gauges and compare to the reading on the

RTWD 90 (chiller control panel). Pressure readings should fall within the specified ranges listed under Operating conditions. Note: Optimum condenser pressure is dependent on condenser water temperature, and should equal the saturation pressure of the refrigerant at the temperature 2 to 5 deg. F above that of leaving condenser water at full load.

4. Clean all water strainers in both the chilled and condensing water piping systems.

5. Measure the oil filter pressure drop. Replace oil filter if required. Refer to "Service Procedures" located in the Facilites Maintenance office.

6. Measure and log the subcooling and superheat.

7. If operating conditions indicate a refrigerant shortage, leak check the unit and confirm using soap bubbles.

8. Clean condenser coils.

9. Trim refrigerant charge until the unit operates in the conditions listed in the note below. Note:

ARI conditions are: condenser water: 85deg. F and 3 GPM per ton and evaporator water: 54-44 deg. F.

Table 123.RTWD Operating Conditions at Full Load Description Condition Evaporator pressure 30-45 psi Condensing pressure 75-125 psi Discharge superheat 10-15 deg. F Subcooling 5-10 deg. F

All conditions stated above are based on the unit running fully loaded, running at ARI conditions. If full load conditions cannot be met, refer to note below to trim the refrigerant charge.

Note: Conditions at minimum must be:

Entering condenser water: 85° F Entering evaporator water: 55° F Table 124.RTWD Operating Conditions at Minimum Load Description Condition Evaporator approach - less than 7 deg. F (non-glycol applications) Condensing approach - less than 7 deg. F Subcooling 2-3 deg. F.

EXV percent open 10-20% open

10. Test and adjust “make-up” water and expansion tank.

11. Check chiller response at various cooling load conditions for proper operation and calibration of capacity control system.

12. Certify performance of quarterly maintenance service, correct and report all discrepancies.

Annually Shut down the chiller once each year to check the following:

1. Perform all monthly and quarterly maintenance procedures.

2. Check the refrigerant charge and oil level. Refer to "Maintenance Procedures". Routine oil changing is not necessary on a hermetic system.

3. Have a qualified laboratory perform an oil analysis to determine system moisture content and acid level. Results will be submitted to the Officer-in-Charge or designee. Note: Due to the hygroscopic properties of the POE oil, all oil must be stored in metal containers. The oil will absorb water if stored in a plastic container. Check the pressure drop across the oil filter. Refer to "Maintenance Procedures".

4. Contact a qualified service organization, as approved by the Officer-in-Charge or designee, to leak check the chiller, to inspect safety controls, and inspect electrical/electronic components for deficiencies.

5. Inspect all piping components for leakage and/or damage. Clean out any inline strainers.

6. Clean and repaint any areas that show signs of corrosion.

7. Test vent piping of all relief valves for presence of refrigerant to detect improperly sealed relief valves. Replace any leaking relief valve.

8. Remove heads of condenser and internally brush tubes at the same time the cooling tower is cleaned.

9. Check to make sure that the crank case heater is working.

10. Contact a qualified service organization, as approved by the Officer-in-Charge or designee to perform Megger (electrical test to measure wire insulation resistance) i.e. condition of chiller/compressor motor; check starter relay and control contacts and electrical connections for tightness and clean as required.

11. Submit and certify performance of annual maintenance service and correct and report in writing to Officer-in-Charge or designee all discrepancies.

Three-Year

1. Use a nondestructive tube test to inspect the condenser and evaporator tubes (Due December

2028). Chiller plant (3 Chillers) and cooling tower commissioning date December 14, 2011.

D. AIR COOLED CHILLER (SCROLL LIQUID CHILLER) ACC-1 (Currently Inoperable)

Note: Refer to manufacturer’s technical service manual, located in the Facilities Maintenance Office.

***This chiller is currently inoperable. The Judiciary plans to restore this chiller to operational status during the contract term. Then upon approval, the contractor would commence preventive maintenance services at the contract price submitted.

Monthly After the unit has operated for approximately 30 minutes and system has been stabilized, check the operating conditions and complete the procedures below:

1. Log the chiller (Supplied - manufactures check list)

2. Visual checks for water, refrigerant and oil leakage.

3. Certify performance of monthly maintenance service, correct and report all discrepancies.

Quarterly

1. Check for debris and clean water rinse condenser coils. (See CAUTION on next page)

2. Check moisture indicating sight glass for possible refrigerant loss and presence of moisture.

3. Check refrigerant charge.

4. Check all refrigerant joints and valves for refrigerant leaks.

5. Check chilled water flow switch operation.

6. Check all condenser fans for proper operation.

7. Check compressor oil level.

8. Certify performance of quarterly maintenance service, correct and report all discrepancies as required.

1. Check all electrical connections, tighten as necessary.

2. Inspect all contactors and relays, replace as necessary.

3. Check accuracy of thermistors, replace if greater than± 2 deg. F variance from calibrated thermometer.

4. Obtain and test an oil sample. Change oil only if necessary.

5. Check refrigerant filter driers for excessive pressure drop, replace as necessary.

6. Check chilled water strainers, clean as necessary.

7. Check cooler heater operation, if equipped.

8. Check condition of condenser fan blades and that they are securely fastened to the motor shaft.

9. Perform Service Test to confirm operation of all components.

10. Check for excessive cooler approach (Leaving Chilled Water Temperature — Saturated Suction

Temperature) which may indicate fouling. Clean cooler vessel if necessary.

11. Contact a qualified service organization, as approved by the Officer-in-Charge or designee to perform Megger (electrical test to measure wire insulation resistance) i.e. condition of chiller/compressor motor; check starter relay and control contacts and electrical connections for tightness and clean as required.

12. Test operate control switches, compressor unloading and safeties.

13. Calibrate and record settings. Adjust as required.

14. Submit and certify performance of annual maintenance service and correct and report in writing to Officer-in-Charge or designee all discrepancies.

CAUTION

Do not apply any chemical cleaners to MCHX condenser coils. These cleaners can accelerate corrosion and damage the coil. Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following steps should be taken to clean MCHX condenser coils. Refer to manufacturer's technical service manual. (Attached)

E. COOLING TOWER - CT-1, CT-2

Note: Refer to manufacturer's technical service manual, located in the Facilities Maintenance Office.

1. Clean pan strainer – monthly or as needed.

2. Check and adjust bleed-off valve to make sure it is operative.

3. Check operating level in pan and adjust float valve if necessary.

4. Check water distribution system and spray pattern.

5. Check belt tension, adjust and replace as needed.

6. Check fan screens, inlet louvers and fans.

7. Remove any dirt or debris.

8. Submit and certify performance of monthly maintenance service and correct and report in writing to Officer-in-Charge or designee all discrepancies.

1. Clean and flush pan – quarterly or as needed.

2. Check drift eliminators.

3. Check the fan blades for cracks, missing balancing weights, and vibrations.

4. Lubricate fan shaft bearings – every 1000 hours of operation or every three months.

5. Electronic Water Level Controller – Clean probe ends of scale build-up.

6. Submit and certify performance of quarterly maintenance service and correct and report in writing to Officer-in-Charge or designee all discrepancies.

Semi-Annually

1. Drain, clean and flush tower; coordinate with water treatment and chiller services.

2. Clean condenser suction screen, drift eliminators and spray nozzles.

3. Electronic Water Level Controller – Inspect junction box for loose wiring and moisture.

4. Submit and certify performance of semi-annual maintenance service and correct and report in writing to Officer-in-Charge or designee all discrepancies.

1. Check sheaves and bushings for corrosion. Scrape and coat with ZRC.

2. Sliding motor base – Inspect and grease – or as needed.

3. Inspect and clean protective finish – Galvanized: scrape and coat with ZRC.

4. Check water quality for biological contamination.

5. Clean unit as needed and contact a water treatment company for recommended water treatment program.

6. Electronic Water Level Controller –Clean inside the standpipe.

7. Solenoid Make-up Valve - Inspect and clean valve of debris.

8. Submit and certify performance of annual maintenance service and correct and report in writing to Officer-in-Charge or designee all discrepancies.

F. VALVES AND CONDENSER WATER LINES

Quarterly

1. The Contractor shall exercise all equipment shut-off valves for proper operations and tightness.

2. Certify performance of quarterly maintenance service.

Annually

1. Wire brush, prime and paint rust from pipe surface to prevent further rusting as needed.

2. Certify performance of annual maintenance service.

G. CHEMICAL FEED SYSTEM

Contractor is required to have a certified water treatment contractor complete this service and is responsible for all costs of chemicals, transportation, storage, disposal, chemical feed equipment and of all listed according to State, Federal and EPA standards.

1. Check adequate chemical supply available for upcoming month. Arrange for delivery of needed chemicals and coordinate through Facilities Management.

2. Check for leaks. Repair as required to stop leaks. Report findings.

3. Check all chemical feed equipment operations and replace as required.

4. Test and analyze samples of chilled water. Report findings in a written report. The report shall include the present concentrations, biological growth, total dissolved solids and conductivity readings, and recommendations or adjustments to set points.

5. Add chemicals to increase concentration as required.

6. A copy of the monthly written report will accompany the monthly invoice with all recommendations of repairs and analysis.

H. PUMPS - CONDENSER AND CHILLED WATER

1. Lubricate and check pump and motor bearings for abnormal temperature and unusual noise or vibration and correct as required.

2. Check packing glands and seals for excessive leakage. Adjust, tighten and correct as required.

3. Certify performance of quarterly service and correct and report all discrepancies.

Semi-Annually

1. Remove and clean strainer for all condenser pumps after tower cleaning.

2. Check and blow down strainer to chilled water pumps after tower cleaning. Remove and clean strainer if excessive debris is noted.

3. Check condition of insulation.

4. Log suction and discharge pressures.

5. Clean and remove all dust and foreign matter. Clean all rust spots and scratch and touch up paint with matching color.

6. Check motor coupling for alignment; mounting bolts are secure.

7. Check Valves and Condenser Water Lines, Equipment and Supports

8. Certify performance of semi-annual service and correct and report all discrepancies.

Annually

1. The contractor shall exercise all equipment shut-off valves annually for proper operation and tightness.

2. Wire brush, prime and paint rust from pipe, equipment and support surface to prevent further rusting.

3. Certify performance of annual service and correct and report all discrepancies.

I. VARIABLE FREQUENCY DRIVES

Note: Refer to manufacturer's technical service manual located in the Facilities Maintenance Office.

1. Check and clean heatsink.

2. Check cooling fan operation and clean/replace enclosure intake and exhaust filter as needed

(CHWS AND CT fan, Motor Speed Controllers).

3. Check VFD operational values for pump/fan performance (CHWS AND CT fan, Motor Speed

Controllers).

4. Certify performance of semi-annual service and correct and report all discrepancies.

J. CLEANING OF MECHANICAL EQUIPMENT ROOMS OR ENCLOSURES

Quarterly

1. Vacuum or wipe clean all equipment surfaces and all related appurtenances.

2. Vacuum or sweep complete floor and platform areas. DO NOT wet floor and platform area where there is no waterproofing.

3. Wet wash complete floor area with tap water where allowed. Remove all used, deteriorated, replaced, discarded parts and related debris. CAUTION: DO NOT splash water onto the electrical and mechanical equipment.

4. Notify Officer-in-Charge or designee of any dangerous conditions, improper storage of furniture, materials and supplies which impacts your work within rooms and enclosures, including vandalism.

K. SUMP PUMPS – SEWAGE, STORM and SKIMMER (LOCATED IN PARKING GARAGE)

1. Lubricate and check pump and motor bearings including pump couplings for abnormal temperature and unusual noise or vibration.

2. Adjust floats, lubricate linkages, check alarm system for proper operation and contact Facilities group to check the BAS for alarms.

3. Certify performance of monthly service and correct and report all discrepancies.

Semi-Annually

1. Exercise all shut off valves and check for leakage.

2. Check packing glands and seals for excessive leakage. Adjust, tighten, repair or replace as required.

3. Check and remove all dust and foreign matter. Check for rust spots, sand and paint as needed.

4. Certify performance of semi-annual service and correct and report all discrepancies.

L. VENTILATING EXHAUST FANS

Quarterly

1. Check fan collars, bearings and shaft for wear.

2. Check motor-controlled and back-draft dampers for proper operation. Lubricate damper linkage for free movement.

3. Lubricate fan and motor bearings.

4. Check belt wear and tension; adjust/replace as needed.

5. Check sheaves for wear; realign sheaves.

6. Certify quarterly fan maintenance service and correct and report all discrepancies.

Annually

1. Check fan wheel for smooth operation and housing.

2. Check ducting for proper flow and air leaks.

3. Remove and wash intake grille. (Rest rooms)

4. Certify performance of annual maintenance service.

M. FRESH AIR INTAKE GRILL

Quarterly

1. Grills shall be cleaned with brush, vacuum or if heavily sooted, the grill shall be cleaned with approved detergent and rinsed with tap water.

1. Grills shall be cleaned with brush, vacuum or if heavily sooted, the grill shall be cleaned with approved detergent and rinsed with tap water.

2. Certify performance of annual maintenance service.

N. REMOTE WATER COOLER

Quarterly

1. Dust/wipe down the exterior of complete unit and vacuum.

2. Clean condenser and internal cabinet, adjust water temperature and stream. Check compressor operation.

3. Certify performance of monthly service and report all discrepancies.

1.4 PARTS, MATERIALS & LABOR

The Contractor shall restore to serviceability all parts that are found to cost less to restore than to replace with a new part. Where parts are worn out and cannot be restored, the Contractor shall replace these parts with new parts. Only new, standard parts manufactured by the maker of each unit or parts of equal quality shall be used.

All systems and components listed are expected to be operating within acceptable ranges and Contractor is required to report any and all deficiencies with a cost and time estimate to repair in order to maintain serviceability. Diagnostic trouble shooting of up to 2 hours per month will be included in the base price of this contract. All repair estimate submittals will be time and materials not to exceed a pre-determined amount.

The Contractor shall stock and maintain a supply of spare parts and materials that are required for normal repairs of the air conditioning units. The Contractor shall notify the Judiciary whenever parts are not locally available to accomplish the repairs. The Judiciary reserves the right to have the parts sent by air freight at the expense of the Judiciary.

1.5 EMERGENCY SERVICE AND AUTHORIZED EXTRA WORK

Emergency Service Emergency service required between regularly scheduled maintenance calls shall be rendered within two

(2) hours with the exception of the main chiller room and cooling tower which shall be rendered within one (1) hour after the Contractor is notified, non-work days excluded. Emergency service required during non-work days shall be rendered within eight (8) hours.

Authorized Extra Work Repairs due to unforeseen events or authorized extra work are chargeable. For as-needed or unforeseen repairs authorized by the Facilities Management Division, the Judiciary shall compensate the Contractor for replaced mechanical parts, units or components and the connected accessories at supplier’s invoice price plus mark-up which shall include the cost of material, shipping cost if applicable, overhead, profit, taxes and any other incidental expenses. Compensation for mark-up and labor shall be in accordance with the Contractor’s mark-up and hourly labor rate price.

The Contractor shall provide firm labor rates and markups on the offer proposal. These rates shall remain firm for the duration of the contract and shall be used when the Facilities Management Division authorizes repairs or replacement work not included in the preventative maintenance services.

Unauthorized extra work performed on an emergency service may not be compensated, as determined by the Facilities Management Division.

Contractor shall bill chargeable emergency services separately from the contract price.

1.6 EMERGENCY SERVICE PROCEDURES

1. Facilities Management Division notifies Contractor of problem and assigns a repair title with unit numbers.

2. Contractor will report to Facilities Management Division that day or call the following day and report the status of the emergency call by title and unit number.

a. If completed, Contractor will inform Facilities Management Division of their evaluation of the trouble and the action taken to remedy the situation.

b. If not completed, Contractor will inform Facilities Management Division of the problem and provide an estimated completion date.

3. Once a week the Contractor shall report on all outstanding emergency calls and their estimated completion date and/or action pending.

1.7 SPECIAL REPORTS

The Contractor will submit completed monthly service and water chemical treatment reports (Signed by the Contractor and Facilities Management) to the Facilities Manager and 1 copy will accompany each service invoice prior to being processed for payment.

The Contractor shall also maintain a separate book, record, documents and other evidence pertaining to the maintenance, repair and costs of each air conditioning and ventilation system to the extent and in such detail as will properly and adequately reflect the past maintenance history and cost (labor, materials, parts and equipment).

The Contractor shall also submit an annual updated inventory of all equipment at the end of each calendar year.

1.8 MAINTENANCE CHECKLIST

The Contractor shall maintain a Judiciary supplied maintenance checklist/log and post a checklist/log on each unit as described herein. The supplied checklist includes all maintenance services due for each piece of equipment to be dated, signed by the performing technician and signed/dated by Facilities Management. It will be the Contractor’s responsibility to maintain the checklist/log book by recording the maintenance, discrepancies and emergency repairs data after each scheduled visit. The checklist/log will be kept in the Facilities Maintenance Office, and a copy will accompany the monthly invoice prior to processing for payment. At the end of the contract period, the Contractor shall submit with their final invoice a completed checklist/log book of all air conditioning, ventilation and listed equipment services.

1.9 CLEANUP AND WORK PRACTICE

The Contractor shall keep the job site free of debris, litter, refuse, fingerprints, smudges, insulation, etc.

and shall clean all oil drippings during the daily progress of work. The Contractor shall remove from premises: all used filters, tools, waste oils, fluids, parts, refrigerant and equipment upon completion of all services and repairs and legally dispose of, whether hazardous or not, in accordance with EPA and/or other government regulations. The Contractor shall support and defend the Judiciary legally and financially with regard to these regulations.

The Contractor shall exercise caution during the progress of the maintenance and repair work to prevent damage to the ceilings, roofing and other building structure. Contractor shall restore all damages caused by his negligence, at his own expense.

The Contractor does not to perform maintenance and repair work until all switches are de-energized, locked, and tagged. The Contractor shall comply with all applicable safety regulations promulgated by OSHA, EPA, and other governmental agencies.

1.10 WORK SCHEDULE

The Contractor shall perform maintenance and inspection services to the air conditioning, ventilation and listed systems at Hoapili Hale, all in accordance with the best commercial practices and as required to provide assurance of safety and operational reliability.

All scheduled maintenance of the listed equipment has been prepared to reflect the services due throughout the year in a work order per month. A copy of all completed maintenance work orders will be kept in the Facilities Maintenance Office, and a copy will be sent with the original monthly invoice to the Fiscal Office for processing.

All maintenance tasks described herein shall be performed between the hours of 7:30 A.M. to 4:00 P.M.

on normal working days, Monday through Friday, excluding State holidays, except as noted.

1. Monthly maintenance tasks shall be performed in the last week of the month or as coordinated through Facilities Management.

2. Quarterly maintenance tasks shall be performed in March, June, September and December or as coordinated through Facilities Management.

3. Semi-Annual maintenance tasks shall be performed in June and December, or as coordinated through Facilities Management.

4. Annual maintenance tasks shall be performed in December, or as coordinated through Facilities Management. The annual air handling unit coil cleaning shall be performed on a weekend, therefore, the half-time labor (overtime) cost for this weekend work shall be included in the Contractor's offer price as submitted in the offer proposal. No additional compensation will be allowed for this weekend’s work.

In the event the Judiciary requests the Contractor to perform maintenance tasks on the weekend or after normal working hours, the Judiciary shall compensate the Contractor only for the difference between his normal labor rate & overtime labor rate (1/2). The Contractor shall be responsible for all other costs as if the work was performed during normal working hours. As noted above (1.3, A., 2a., Air Handling Unit, Annual Service) coil cleaning which shall be performed during non-working hours (weekends), therefore, the half-time labor (overtime) cost for this weekend’s work shall be included in the Contractor's offer price as submitted in the offer proposal. No additional compensation will be paid by the Judiciary for this weekend’s work.

All work performed shall be subject to random periodic inspection by Facilities Management or a representative of the Judiciary. The Judiciary reserves the right to have the Contractor present at such inspections to be scheduled by the Judiciary periodically.

The Contractor shall be informed of all deficiencies found by the Facilities Management or a representative of the Judiciary. The Contractor shall correct all deficiencies within seven (7) days. If deficiencies are not corrected within the seven-day period, the provision on liquidated damages will be applicable.

1.11 WARRANTY

The Contractor shall submit a written warranty for replacement of any integral part of equipment listed herein, such as compressors, fan motors, etc., as guaranteed by the factory.

The warranty shall consist of period covered from date of installation, make, model number, serial number, department and location of equipment (1st floor, 2nd floor, etc.).

SECTION TWO - SPECIFICATIONS

CHEMICAL WATER TREATMENT

2.1 SCOPE

The Contractor may subcontract for the services of a Water Treatment Contractor (WTC) who shall have a minimum of five (5) years water treatment service experience in Hawaii. The Contractor shall provide all necessary equipment, chemicals and services required to control corrosion, scale, algae, and slime in the following systems:

1. Cooling tower

2. Condenser

3. Chilled water

All in accordance with the specifications, special provisions, and terms and conditions herein.

The treatment supplied by the Contractor shall be one that has been designed and tailor-made for the water being used in this system.

The Contractor shall warrant that the chemicals used in the water treatment program and offered herein will not endanger the health or safety of persons coming into contact with the materials and will not damage personal or real property as long as the Contractor's instructions are followed.

Contractor also warrants that the chemicals used in the water treatment program shall have no detrimental effect on the metallic or non-metallic materials in the equipment being treated.

The chemical containers and equipment shall be located within a leak containment system. The Contractor shall have an absorbent and/or clean-up system/program that must be available and be submitted and approved by the Judiciary prior to start date of services.

2.2 MINIMUM REQUIREMENTS OF THE TREATMENT PROGRAM

1. Scale and Corrosion Control

a. Scale and corrosion shall be inhibited by the controlled use of scale and corrosion prevention materials as herein noted.

1. The use of essentially toxic and staining corrosion inhibitors such as chromate will not be permitted with the exception of the chilled water system since it is located in a closed system.

2. The use of inhibitors such as the organic phosphorous type will be permitted.

3. Corrosion inhibitors selected shall have been proven effective by at least two years’ usage in the State of Hawaii by the water treatment contractor.

4. Poly-phosphates are not considered effective corrosion inhibitors and shall not be permitted.

b. An automatic feed system is installed at the service site for the Contractor's use; however, the

Contractor must verify this information and shall maintain the system to adequately maintain the proper chemical balance.

1. The system shall be a completely automatic proportional pump feed and the bleed-off shall be in direct proportion to equipment load indicated by the makeup water.

2. Control shall be by means of a solid state conductivity meter and flow through probe sensor.

3. The controller is to be programmed to bleed-off the system and to regulate a preset solution feed pump.

4. A biocide timer to regulate a preset solution feed pump.

5. Closed system valve by-pass Pot feeder.

c. The water treatment must constantly prevent the build-up of adherent mineral deposits on the heat transfer surfaces of the equipment being treated. Periodic circulation of inhibited descaling acids will not be considered as meeting these specifications.

d. The Contractor shall install a test system immediately at the start of the contract. The test system shall include strainer, isolation and Dole valves, piping kit and test coupons. Prior to installation, the Contractor must submit to the Judiciary for approval the proposed test system installation plan layout or schematic piping diagram. The Contractor to perform an ISO 9000 corrosion analysis and test coupons replacement semi-annually at the end of June and December. Make adjustments to the water treatment program as required by findings and submit reports to the Judiciary within one (1) month of coupon replacements. Corrosion rates shall be less than 2 mil per year for copper and 4 mil per year for steel - both with pitting.

2. Biological Growth Control

a. Bacteria, algae and slime growth shall be prevented in all water circuits by using suitable biocides.

b. Chemicals may be fed into water circuits requiring continuous make-up by automatic proportional feeding devices or by adding directly to the tower sump as required. Chemicals shall be slug fed into the system on a regular basis and not added continuously.

c. Bromine oxidizing biocides may be used, but shall not include metallic salts, such as tin. A sufficient halogen residual shall be maintained to prevent Ligonella. Quaternaries may be used, but only with oxidizing biocides.

3. Chemicals

a. All chemicals shall be supplied in their original factory containers and no dilution of chemicals is allowed.

b. The chemicals provided must meet OSHA, Environmental Protection Agency, and ISO 9000 requirements for safety to personnel and the environment, and must be approved by the State.

c. All chemicals supplied shall have been registered and in satisfactory use in Hawaii for at least two years. Offeror may be required to provide evidence of satisfactory performance of the chemical offered. The Judiciary shall be the sole judge of such satisfaction and the Judiciary's decision shall be final.

d. Chemicals, other than those presently being used in the water treatment program, hereinafter referred as "new chemicals", shall be compatible with the existing chemicals, scale and corrosion inhibitor and broad spectrum bacteriostats.

1. Verification by an independent testing laboratory for the compatibility of the new chemicals shall be submitted upon award and prior to commencement of work.

2. This verification is required for all chemicals not presently being used in the treatment program.

3. Should the new chemicals be determined to be incompatible with the chemicals presently in use, the Contractor shall be responsible for flushing the system to remove all chemicals before the new chemicals are introduced into the system. Any damages to the system resulting from the failure of the Contractor to satisfactorily flush the system shall be repaired by the Contractor at his expense and at no cost to the Judiciary.

2.3 SERVICE REQUIREMENTS

1. Upon award of the contract the representative designated in the offer by the Contractor shall visit the service site to make an initial water analysis and to establish the prescribed treatment program.

a. The initial service call shall include establishment of treatment dosages, bleed schedules, and intervals to replenish chemicals for automatic feed system.

b. The Contractor shall submit report on the results of the initial water analysis and the prescribed water treatment program including findings and recommendations. This report shall be submitted within three (3) calendar days following the service call to the Judiciary.

c. Contractor shall also submit supplemental reports subsequent to any changes required in the initial prescribed water treatment program.

2. The designated representative of the Contractor shall make service calls and water analysis at intervals of a maximum of thirty (30) calendar days. He shall notify the Facilities Management prior to conducting the test and upon completion of the test.

a. The representative shall make initial application of each material and shall continuously furnish specific treatment of the water as required.

b. He shall also investigate any unusual conditions pertaining to scale deposition as indicated by condenser operating data, corrosion, and algae growths, & implement corrective action, as required.

c. The Contractor shall submit the results of the water analysis and the prescribed water treatment including findings and recommendations in a report. This report shall be submitted within three

(3) calendar days following the service call to Facilities Management.

3. Contractor shall be totally responsible for a continuous water treatment program.

a. Contractor shall be available on-site during the performance of the cooling tower and tube cleaning and coordinate the inspection with Facilities Management.

b. Chiller tube box for inspection shall be coordinated with Facilities Management as necessary.

c. The Contractor shall be totally responsible for the water treatment equipment and shall keep it functioning at its optimum through proper maintenance, repair, or replacement as required including piping and electrical.

4. Chilled Water Chemical Feed System shall be serviced monthly as follows:

a. Check chemical feed pumps for proper operation and/or adjust as needed.

b. Check agitator motor where applicable.

c. Check condition of chemical drums and containment system for leaks and repair/replace and refill as required.

d. Check operations of automatic chemical controller system for proper sensor and piping for proper operation. Check for leaks and repair.

e. Calibrate chemical feed as required by water analysis from test results.

f. Remove empty chemical containers and clean area.

g. Certify that system has received monthly service and report all adjustment/discrepancies.

5. Contractor shall maintain a "service log" at each chiller room for recording the following information for each visit:

a. Name of service representative.

b. Date of service.

c. Items services, adjusted, repaired, etc.

d. Record set points and recommended ranges including (make-up and bleed water meter readings at location where available) and quantities of each chemical used.

e. Record and analyze readings of raw and systems water samples to include but be not limited to:

P, conductivity (micro-mho), silica, alkalinity, calcium hardness, magnesium, chlorides, bio-organism counts and nitrite residuals.

6. All work done and all material furnished shall be subject to inspection and approval of the Facilities Management so as to ascertain that the services rendered are in accordance with the requirements and intentions of the specifications, special provisions, and the general conditions.

2.4 PENALTIES

The Contractor shall not be responsible for repairs/penalties due to flagrant vandalism, fire, storm, or related damages that can be attributed to causes beyond his control. However, the Contractor shall be responsible for such repairs/penalties if the damages are caused by the Contractor’s negligence or failure to properly maintain and repair the equipment/system.

1. The Contractor shall clean the system at no cost to the Judiciary within thirty (30) days of discovery of the Contractor’s failure to meet minimum and service requirements.

2. If the corrosion rate exceeds 2 mils per year for copper and/or 4 mils per year for…