i. Argus Titan Controller Panel 5_TC5 Drawings.pdf

PDF 1 MB Posted

Attached to
Coeur d'Alene Nursery Argus Titan Control Panel Wiring and Relay Installation
Solicitation number
1284LL25Q0057
Issued by

About this file

This document is a comprehensive set of technical drawings and wiring diagrams for a USDA (United States Department of Agriculture) facility located in Coeur d'Alene, focusing on control systems and network infrastructure. The drawings, created by Argus Control Systems Ltd. on December 10, 2021, detail the electrical and network configuration for a complex control system designated as TC5, which appears to manage various environmental control functions for a greenhouse or agricultural facility. Key systems include roof and sidewall ventilation controls, heater systems for different building zones, exhaust fans, pad pump, HAF (Horizontal Air Flow) fans, and LED lighting, all connected through a sophisticated Titan controller network with multiple IO (Input/Output) modules.

The technical documentation provides intricate details of the control system's architecture, including network segment layouts, power supply connections, transformer specifications, and field wiring diagrams. The system operates on a 120 VAC input with 24 VAC control circuits, utilizing Class 1 and Class 2 field wiring approaches. Multiple IO modules (TC5-IO[B5-7-A], TC5-IO[B5-7-B]) are configured to manage different equipment zones, with precise control interfaces for each component. The drawings emphasize careful network segmentation, power management, and include specific warnings about using copper conductors rated for 75°C and following equipment suppliers' specific connection instructions.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL PROPERTY OF

ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS INTENDED APPLICATION

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - SITE & NETWORK.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 3

Network & Site Layout Drawing Revisions

DRAWING REVISION NOTES:

REV. NO: CHANGES: BY: DATE:

1 CREATED DRAWING TH 12/20/2020

CHANGED NAME OF TC6-IO[P1,2&4,5-A] to TC6-IO[EAST-A]

PL 3/28/2024ADDED TC6-IO[EAST-B], TC6-IO[EAST-C] & TC6-IO[EAST-D] to the TC6 IO NETWORK

CHANGED NAME OF RCP-P6-9-01 TO RCP-B5-7-01

PL 11/28/2024ADDED TC5-IO[B5-7-B] TO THE TC5 IO NETWORK

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2 604-538-3531

R

100'

ACCESS POINT

RCP-P12-15-01 RCP-P10-11-01

RCP-S1-01

AP

2IO1 3 IO

IO

RCP-B5-7-01

RCP-PH&QA-01

IO

RCP-S2-01

IO

A

RCP-P1,2&4,5-01

IO

WS

IO

RCP-B1-4-01

IO

TC4-IO[S3-A]

IO

THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL PROPERTY OF

ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS INTENDED APPLICATION

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - SITE & NETWORK.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 3

SITE LAYOUT

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2 604-538-3531

R

NORTH

DRAWING IS A VISUAL

REPRESENTATION OF CONTROLS

AND PANEL LOCATIONS.

CONTROLS EQUIPMENT IS NOT

DRAWN TO SCALE. ALL SIZES AND

DISTANCES ARE APPROXIMATE

IO NETWORK DEVICE

CONNECTION

IO NETWORK SEGMENT

ACCESS POINT WITH IOPS

LOCATED WITHIN 15' OF

ARGUS COMPUTER

CONTROL NETWORK

SEGMENT

WEATHER STATION

WITH NFLP AND FLP

PASSIVE COUPLER /

REPEATER

CONTROLS ENCLOSURE

RCP-XX-01

IO

RP

TC

AP

CONTROLLER

NETWORK DEVICE

CONNECTION

WS

LEGACY DEVICE NETWORK

SEGMENT

NT

NUTRIENT IO

CONNECTION

LIGHTING PANELS

MSC PANELS

SEE SITE LAYOUT PAGE 3

FOR FURTHER DETAILS

SECTION 2

SEE SITE LAYOUT PAGE 2

FOR FURTHER DETAILS

SECTION 1

ACCESS POINT

AP

RCP-S2-01

IO

THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL PROPERTY OF

ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS INTENDED APPLICATION

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - SITE & NETWORK.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 3

SITE LAYOUT

RCP-B5-7-01

IO

A

RCP-P1,2&4,5-01

IO

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2 604-538-3531

R

NORTH

DRAWING IS A VISUAL

REPRESENTATION OF CONTROLS

AND PANEL LOCATIONS.

CONTROLS EQUIPMENT IS NOT

DRAWN TO SCALE. ALL SIZES AND

DISTANCES ARE APPROXIMATE

IO NETWORK DEVICE

CONNECTION

IO NETWORK SEGMENT

ACCESS POINT WITH IOPS

LOCATED WITHIN 15' OF

ARGUS COMPUTER

CONTROL NETWORK

SEGMENT

WEATHER STATION

WITH NFLP AND FLP

PASSIVE COUPLER /

REPEATER

CONTROLS ENCLOSURE

RCP-XX-01

IO

RP

TC

AP

CONTROLLER

NETWORK DEVICE

CONNECTION

WS

LEGACY DEVICE NETWORK

SEGMENT

NT

NUTRIENT IO

CONNECTION

LIGHTING PANELS

MSC PANELS

SECTION 1-1

SECTION 1-2

TC5

IO NETWORK

LAYOUT

TC5-IOPS[1]

IO NETWORK

POWER

SUPPLY

RCP-B5-7-01

CONTROLLER

I/O

CNTL

TC5-TITAN

CONTROLLER

I/O MODULE

TC5-IO

[B5-7-A]

= NETWORK TERMINATOR

ALL TITAN NETWORKS TO BE WIRED WITH

WESTPENN AQ224 CABLE NO SUBSTITUTIONS

ALL BOARDS MUST BE CORRECTLY GROUNDED

FOR PROPER LIGHTNING PROTECTION

T

= AQ224 AQUASEAL CONNECTIONS

= SF/UTP 22 AWG - 2 PAIRS BELDEN

= CAT 5/6 ETHERNET CONNECTIONS

= ANALOG PHONE LINE CONNECTIONS

T

I/O MODULE

TC5-IO

[B5-7-A]T

THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL PROPERTY OF

ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS INTENDED APPLICATION

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

USDA - SITE & NETWORK.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 3

Project Mngr: Drawn by:

Dwg:

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

Current Revision:Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

RCP-B5-7-01

Drawing Revisions

REVISION NOTES:

REV. NO: CHANGES: BY: DATE:

1 CREATED DRAWING AK 12/10/2021

RENAMED PANEL RCP-B5-7-01

PL 11/28/2024

ADDED TC5-IO[B5-7-B]

ADDED EXHAUST FAN CONTROLS TO IO[B5-7-A] - OP1 A - D

RENAMED EXISTING INPUTS & OUTPUTS

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

RCP-B5-7-01

PANEL LAYOUT

H

IN

G E

SI

D

E

2TX75

RM-B5-7-TX1

C

LA

SS

L O

W V

O

LT

A G

E W

IR

IN

G

C

LA

SS

L O

W V

O

LT

A G

E W

IR

IN

G

CLASS 2 - LOW VOLTAGE WIRING ONLY

C

LA

SS

L O

W V

O

LT

A G

E W

IR

IN

G

C

LA

SS

TC5-IOPS[1]

CONTROLLER NETWORK

POWER SUPPLY

TC5

TC5-CNPS[1]

GROUND

GROUND

GROUND

GROUND

GROUND

GROUND

GROUND

GROUND

CLASS 1 SUPPLY AND

LINE VOLTAGE FIELD

WIRING CONDUIT ENTRY

CLASS 2 CONTROLS,

SENSOR AND NETWORK

WIRING CONDUIT ENTRY

CLASS 2 CONTROLS,

SENSOR AND NETWORK

WIRING CONDUIT ENTRY

CLASS 2 CONTROLS,

SENSOR AND NETWORK

WIRING CONDUIT ENTRY

RPTR[A]

K-B5-7-06

K-B5-7-05 K-B5-7-04 K-B5-7-03

K-B5-7-02 K-B5-7-01

TC5-IO[B5-7-A]

TC5-IO[B5-7-B]

H

IN

G E

SI

D

E

R

RCP-B5-7-01

Manufacturer:

Factory Identification:

Enclosure Type Rating:

Argus Control Systems Ltd.

#101 - 18445 53rd Avenue

Surrey, BC, V3S 7A4, 604-538-3531

Supply Ratings:

Max. Supply Voltage:

UL 4, 12 Steel

120 VAC

Voltage:

SCCR:

Terminal:

Largest Motor FLA/HP:

Maximum Circuit Size:

Total FLA:

Wire Range:

Torque:

No. of PH: F =120 VAC 2A

5KA, RMS, SYMMETRICAL

RM-B5-7-TX1; 13, 15

Not Applicable 15A

12 AWG - 14 AWG

N/A

1 60 HZ

PH1 =

Field Wiring Diagram:

(LOCATED AT INNER SIDE OF THE DOOR)

USDA - TC5 - RCP-B5-7-01.DWG

Height:

Bonding Conductor Size:

Wire Range:

Width: Depth:

Maximum Voltage:

SCCR:

ENCLOSURE INFORMATION

36" 36" 8"

UL Type 4, 12 Steel Enclosure Door Hinged On Left Side Painted White With Green Argus Logo On Panel Door

10 AWG

240 VAC

10 AWG - 22 AWG

5kA RMS Symmetrical

240 VAC Maximum

FIELD WIRING INFORMATION

Refer To Equipment Supplier's Instructions For Connection Details Use Only Copper Conductors That Are Rated For A Minimum Of 75°C (167°F) T.P. = Thermally Protected Disconnect Switches By Installer Branch Circuit Protection By Installer

Location:

Terminals:

Torque:

Voltage:

Ø1 FLA:

Maximum Circuit Size:

Largest Motor FLA:

Short Circuit Current:

Wire Range:

CONTROL TRANSFORMERS

Field Wiring Landing Terminals:

RM-B5-7-TX1

13, 15

N/A

120 VAC, 60HZ, 1Ø

2 Amps 15 Amps

N/A 5kA RMS

Symmetrical

12 AWG - 14 AWG

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2 604-538-3531

R

SECTION 1

SEE PANEL LAYOUT

PAGE 2 FOR FURTHER

DETAILS

SEE PANEL LAYOUT

PAGE 2 FOR FURTHER

DETAILS

SECTION 2

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

RCP-B5-7-01

PANEL LAYOUT

K-B5-7-06

K-B5-7-05

K-B5-7-04

K-B5-7-03

K-B5-7-02

K-B5-7-01

Manufacturer:

Factory Identification:

Enclosure Type Rating:

Argus Control Systems Ltd.

#101 - 18445 53rd Avenue

Surrey, BC, V3S 7A4, 604-538-3531

Supply Ratings:

Max. Supply Voltage:

UL 4, 12 Steel

120 VAC

Voltage:

SCCR:

Terminal:

Largest Motor FLA/HP:

Maximum Circuit Size:

Total FLA:

Wire Range:

Torque:

No. of PH: F =120 VAC 2A

5KA, RMS, SYMMETRICAL

RM-B5-7-TX1; 13, 15

Not Applicable 15A

12 AWG - 14 AWG

N/A

1 60 HZ

PH1 =

Field Wiring Diagram:

(LOCATED AT INNER SIDE OF THE DOOR)

USDA - TC5 - RCP-B5-7-01.DWG

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2 604-538-3531

R

SECTION 1 SECTION 2

RPTR[A]

CONTROLLER NETWORK

REPEATER

CNTL

NET

SEE CNTL NETWORK LAYOUT DIAGRAM

FOR FURTHER DETAILS

CNTL

NET

SEE CNTL NETWORK LAYOUT DIAGRAM

FOR FURTHER DETAILS

CNTL

NET

SEE CNTL NETWORK LAYOUT DIAGRAM

FOR FURTHER DETAILS

- PO

R T

C

PO

R T

B

1.0A 1.0A

PO

R

T A

IO NET FUSE A1

IO NET FUSE A2

POWER IN FUSE

0.5A

IO NET FUSE B11.

0A

IO NET FUSE B21.

0A

IO NET FUSE C11.

0A

IO NET FUSE C21.

0A

1A F

U

SE

X

POWER IN

12-30 VDC

PORT C NETWORK

CONNECTION

PORT A NETWORK

CONNECTION

1A F

U

SE

X

0.

5A

F U

SE

C B A

EARTH

CONNECTION

EARTH

CONNECTION

POWER STATUS

POWER FAULT

POWER STATUS

POWER FAULT

POWER

STATUS

POWER

FAULT

PORT B NETWORK

CONNECTION

NETWORK

TRAFFIC

NOTE: THIS DEVICE PROVIDES AN ISOLATION POINT FOR

POWER AND AN AMPLIFICATION OF THE

COMMUNICATIONS SIGNAL. PLEASE REFER TO YOUR

ACTIVE REPEATER MANUAL FOR FURTHER DETAILS.

IF YOU ARE HAVING TROUBLE WITH NETWORK

COMMUNICATIONS YOU SHOULD POWER CYCLE ALL

NETWORK POWER SUPPLIES AND VERIFY THAT

APPROPRIATE TERMINATORS ARE IN PLACE.

IF YOU HAVE ANY QUESTIONS OR CONCERNS PLEASE

CONTACT ARGUS CONTROL SYSTEMS FOR FURTHER

ASSISTANCE.

PORT A

NETWORK

TERMINATOR

PORT B

NETWORK

TERMINATOR

PORT C

NETWORK

TERMINATOR

CONTROLLER NETWORK

REPEATERT

IT

A N

N E T W

O R

K T E R

M

IN

A T O

R

T

IT

A N

N E T W

O R

K T E R

M

IN

A T O

R

T

IT

A N

N E T W

O R

K T E R

M

IN

A T O

R

RPTR[A]

THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL PROPERTY OF

ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS INTENDED APPLICATION

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

LEGEND

WEST = ZONE WEST

GL = GLOBAL

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2

TC5

TITAN CONTROLLER

CONNECTIONS

100 Ohm 1/4W

NETWORK

TERMINATOR

I/O

NET

SEE IO NETWORK LAYOUT DIAGRAM

FOR FURTHER DETAILS

C N

TL

N

ET

F

U

SE

C N

TL

N

ET

F

U

SE

I/O N

ET

F

U

SE

I/O N

ET

F

U

SE

1.0A1.0A

1.0A1.0A

I/O

NET

CNTL

NET

SEC : #########

SD MEMORY CARD

1.0 1.0

1.0 1.0

I/O N

ET

F

U

SE

I/O N

ET

F

U

SE

C N

TL

N

ET

F

U

SE

C N

TL

N

ET

F

U

SE

TO CNTL NET

POWER SUPPLY

LEGACY DEVICE

NETWORK

CONNECTION

IO NET POWER FAULT

IO NET POWER STATUS

CNTL NET POWER FAULT

CNTL NET POWER STATUS

CNTL NET ACTIVITY

CNTL NET CPU STATUS

CONTROLLER

STATUS

SECURITY CODE

ETHERNET

PRIMARY

CONNECTION

SD MEMORY CARD

SD CARD STATUS

USB

ALTERNATIVE

SERVICE

CONNECTION

TITAN

CONTROLLER

I/O NET

CNTL NET

TC5

CNTL

NET

SEE CNTL NETWORK LAYOUT DIAGRAM

FOR FURTHER DETAILS

CNTL NETWORK

POWER SUPPLY V1.3

TC5-CNPS[1]

THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL PROPERTY OF

ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS INTENDED APPLICATION

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

LEGEND

WEST = ZONE WEST

GL = GLOBAL

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2 604-538-3531

R

**WARNING**

REFER TO EQUIPMENT SUPPLIER'S

INSTRUCTIONS FOR CONNECTION

DETAILS.

USE ONLY COPPER CONDUCTORS

FIELD WIRING MUST BE RATED

FOR MINIMUM OF 75°C (167°F)

CALL ARGUS CONTROLS AT

1-888-667-2091 FOR ASSISTANCE.

TC5-IOPS[1]

TITAN IO NETWORK POWER

SUPPLY WIRING

TTN-TXFORMER

120 VAC - 24 VAC

75 VA

I/O

NET

SEE IO NETWORK LAYOUT DIAGRAM

FOR FURTHER DETAILS

24 VAC IN

POWER FUSE

6.

0A

I/O

NET

6.

0A POWER FUSE

6A FAST ACTING FUSE X2

24 VAC IN

CPU STATUS

POWER OUT

STATUS

TITAN IO NETWORK

POWER SUPPLY

I/O NET

TC5-IOPS[1]

NOTE: REFER TO PANEL WIRING PAGE 1

FOR TRANSFORMER WIRING DETAILS

THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL PROPERTY OF

ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS INTENDED APPLICATION

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

LEGEND

WEST = ZONE WEST

GL = GLOBAL

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2

TC5-IO[B5-7-A]

TITAN IO MODULE

I/O

NET

SEE IO NETWORK LAYOUT DIAGRAM

FOR FURTHER DETAILS

O P2

O P3

O P4

+ O

P1

I/O N

ET

F

U

SE

I/O N

ET

F

U

SE

1.0A 1.0A

V

D C

F U

SE

0.5A

S/N : #######

SEC : #########

SECURITY CODE

OP1

OP4

OP3

OP2

STATUS

PWR FAULT

PWR STATUS

IN7

IN6

IN5

IN4

IN3

IN2

IN1

CHA+

FREQUENCY INPUT

ANALOG INPUT

CHB+

A/B -

A N

A

LO

G C

O M

M O

N

V

D C

C O

M M

O N

+24 VDC POWER

OUTPUT

C O

M M

O N

+2

VD

C

O U

TP

U

T

PWR STATUS

ACTIVITY

IO NET

24 VDC

IO NET

IO MODULE

POWER

DISCONNECT

JUMPER

TITAN

IO MODULE

I/O NET

1.0 1.0

I/O N

ET

F

U

SE

I/O N

ET

F

U

SE

0.5

V

D C

F U

SE

TC5-IO[B5-7-A]

TITAN D4

ST

AT

U S B

C

D

PWR

A

PWRPWR

A

B

C

PWR

D

PWR

D

C

B

A WEST-EXHAUST

FANS 1

WEST-EXHAUST

FANS 2

WEST-EXHAUST

FANS 3

WEST-EXHAUST

FANS 4

AUTO ON

OFF

AUTO

OFF

ON

AUTO

OFF

ON

AUTO

OFF

ON

CONNECT TO EQUIPMENT INTERFACE

SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND

WIRING DIAGRAM FOR WIRING INFORMATION

REFER TO DATASHEET FOR CONNECTION DETAILS

CLASS II POWER ONLY (3.2 AMPS MAX)

TITAN D4

ST

AT

U S B

C

D

PWR

A

PWRPWR

A

B

C

PWR

D

PWR

D

C

B

A WEST-PAD PUMP

(COOLING WALL)

WEST

HAF FANS 1

WEST

HAF FANS 2

WEST

LED LIGHTS

AUTO ON

OFF

AUTO

OFF

ON

AUTO

OFF

ON

AUTO

OFF

ON

CONNECT TO EQUIPMENT INTERFACE

SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND

WIRING DIAGRAM FOR WIRING INFORMATION

REFER TO DATASHEET FOR CONNECTION DETAILS

CLASS II POWER ONLY (3.2 AMPS MAX)

IPB

OMNI

SEN-OSM-4.0/RHT

WEST-TEMP/RH2 WIRE SENSOR SIGNAL

OMNI PWR

15'

TN21/S IPB WEST-BACKUP TEMP.SEE SENSOR DATASHEET SIGNAL

COMTN21/HM2 IPB WEST-SOIL TEMP.SEE SENSOR DATASHEET SIGNAL

COM

AU

TO

S

TA

TU

S

PWR

PWR PWR

PWR

TITAN P1T

WEST

ROOF VENT

BAY 5,6,7 WEST 1

CLOSE

OPEN AUTO

OPEN

OFF

CLOSE

C

O

C

O

CONNECT TO EQUIPMENT INTERFACE

SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND

WIRING DIAGRAM FOR WIRING INFORMATION

REFER TO DATASHEET FOR CONNECTION DETAILS

CLASS II POWER ONLY (3.2 AMPS MAX)

AU

TO

S

TA

TU

S

PWR

PWR PWR

PWR

TITAN P1T

WEST

ROOF VENT

BAY 5,6,7 WEST 2

CLOSE

OPEN AUTO

OPEN

OFF

CLOSE

C

O

C

O

CONNECT TO EQUIPMENT INTERFACE

SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND

WIRING DIAGRAM FOR WIRING INFORMATION

REFER TO DATASHEET FOR CONNECTION DETAILS

CLASS II POWER ONLY (3.2 AMPS MAX)

THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL PROPERTY OF

ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS INTENDED APPLICATION

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

LEGEND

WEST = ZONE WEST

GL = GLOBAL

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2 604-538-3531

R

**WARNING**

REFER TO EQUIPMENT SUPPLIER'S INSTRUCTIONS FOR CONNECTION DETAILS.

USE ONLY COPPER CONDUCTORS

FIELD WIRING MUST BE RATED FOR MINIMUM OF 75°C (167°F)

CALL ARGUS CONTROLS AT 1-888-667-2091 FOR ASSISTANCE.

TC5-IO[B5-7-B]

TITAN IO MODULE

100 Ohm 1/4W

NETWORK

TERMINATOR

I/O

NET

SEE IO NETWORK LAYOUT DIAGRAM

FOR FURTHER DETAILS

O P2

O P3

O P4

+ O

P1

I/O N

ET

F

U

SE

I/O N

ET

F

U

SE

1.0A 1.0A

V

D C

F U

SE

0.5A

S/N : #######

SEC : #########

SECURITY CODE

OP1

OP4

OP3

OP2

STATUS

PWR FAULT

PWR STATUS

IN7

IN6

IN5

IN4

IN3

IN2

IN1

CHA+

FREQUENCY INPUT

ANALOG INPUT

CHB+

A/B -

A N

A

LO

G C

O M

M O

N

V

D C

C O

M M

O N

+24 VDC POWER

OUTPUT

C O

M M

O N

+2

VD

C

O U

TP

U

T

PWR STATUS

ACTIVITY

IO NET

24 VDC

IO NET

IO MODULE

POWER

DISCONNECT

JUMPER

TITAN

IO MODULE

I/O NET

1.0 1.0

I/O N

ET

F

U

SE

I/O N

ET

F

U

SE

0.5

V

D C

F U

SE

TC5-IO[B5-7-B]

AU

TO

S

TA

TU

S

PWR

PWR PWR

PWR

TITAN P1T

WEST

SIDEWALL VENT

(COOLING WALL)

CLOSE

OPEN AUTO

OPEN

OFF

CLOSE

C

O

C

O

CONNECT TO EQUIPMENT INTERFACE

SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND

WIRING DIAGRAM FOR WIRING INFORMATION

REFER TO DATASHEET FOR CONNECTION DETAILS

CLASS II POWER ONLY (3.2 AMPS MAX)

TITAN D4

ST

AT

U S B

C

D

PWR

A

PWRPWR

A

B

C

PWR

D

PWR

D

C

B

A WEST-HEATER 1

BAY 1-4

WEST-HEATER 2

BAY 5-7

WEST-HEATER

FAN BAY 1-7

AUTO ON

OFF

AUTO

OFF

ON

AUTO

OFF

ON

AUTO

OFF

ON

CONNECT TO EQUIPMENT INTERFACE

SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND

WIRING DIAGRAM FOR WIRING INFORMATION

REFER TO DATASHEET FOR CONNECTION DETAILS

CLASS II POWER ONLY (3.2 AMPS MAX)

TITAN D4

ST

AT

U S B

C

D

PWR

A

PWRPWR

A

B

C

PWR

D

PWR

D

C

B

A AUTO ON

OFF

AUTO

OFF

ON

AUTO

OFF

ON

AUTO

OFF

ON

CONNECT TO EQUIPMENT INTERFACE

SEE EQUIPMENT SUPPLIERS INSTRUCTIONS AND

WIRING DIAGRAM FOR WIRING INFORMATION

REFER TO DATASHEET FOR CONNECTION DETAILS

CLASS II POWER ONLY (3.2 AMPS MAX)

THE INFORMATION CONTAINED WITHIN THIS DRAWING IS THE INTELLECTUAL PROPERTY OF

ARGUS CONTROL SYSTEMS LTD. IT SHALL BE USED ONLY FOR ITS INTENDED APPLICATION

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

LEGEND

WEST = ZONE WEST

GL = GLOBAL

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2 604-538-3531

R

**WARNING**

REFER TO EQUIPMENT SUPPLIER'S INSTRUCTIONS FOR CONNECTION DETAILS.

USE ONLY COPPER CONDUCTORS

FIELD WIRING MUST BE RATED FOR MINIMUM OF 75°C (167°F)

CALL ARGUS CONTROLS AT 1-888-667-2091 FOR ASSISTANCE.

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

RCP-B5-7-01

PANEL WIRING

TC5-IOPS[1]

POWER SUPPLY

TO TC5-IO[B5-7-A] - OP1

SURGE ARRESTOR

SURGE ARRESTOR

RM-B5-7-TX1

2TX75

TC5-IOPS[1]

POWER

TX1A: 75 VA

TC5-IO[B5-7-A; -B] OP:[1-4]; [1-3]

CONTROL POWER

TX1B: 75 VA

120 VAC

120 VAC

24 VAC

24 VAC

LINE 1

N

2 AMP FUSES

CLASS 1

FIELD WIRING

120 VAC 60HZ 1Ø - 15 AMPS

DEDICATED BREAKER

PROVIDED BY INSTALLER

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

RCP-B5-7-01

PANEL WIRING

CLASS 2

FIELD WIRING

CLASS 2

FIELD WIRING

D4 A B C D

IO[B5-7-A] - OP1

24 VAC POWER FROM

RM-B5-7-TX1 TB: 7, 9

D4 A B C D

IO[B5-7-A] - OP2

WEST-EXHAUST FANS 1

24 VAC 5VA MAX (0.20A)

CONTROL INTERFACE

WEST-PAD PUMP (COOLING WALL)

24 VAC 5VA MAX (0.20A)

CONTROL INTERFACE

WEST-HAF FANS 1

24 VAC 5VA MAX (0.20A)

CONTROL INTERFACE

WEST-HAF FANS 2

24 VAC 5VA MAX (0.20A)

CONTROL INTERFACE

WEST-LED LIGHTS

24 VAC 5VA MAX (0.20A)

CONTROL INTERFACE

WEST-EXHAUST FANS 2

24 VAC 5VA MAX (0.20A)

CONTROL INTERFACE

P1T

IO[B5-7-A] - OP4

C O

WEST-ROOF VENT; BAY 5,6,7 WEST 2

24 VAC 5VA MAX (0.20A)

CONTROL INTERFACE

P1T

IO[B5-7-A] - OP3

24 VAC POWER FROM

IO[B5-7-A] - OP2

C O

WEST-ROOF VENT; BAY 5,6,7 WEST 1

24 VAC 5VA MAX (0.20A)

CONTROL INTERFACE

CLOSE

COMMON

OPEN

CLOSE

COMMON

OPEN

WEST-EXHAUST FANS 3

24 VAC 5VA MAX (0.2A)

CONTROL INTERFACE

WEST-EXHAUST FANS 4

24 VAC 5VA MAX (0.2A)

CONTROL INTERFACE

ON/OFF

COMMON

ON/OFF

COMMON

ON/OFF

COMMON

ON/OFF

COMMON

ON/OFF

COMMON

ON/OFF

COMMON

ON/OFF

COMMON

ON/OFF

COMMON

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2

AND MUST BE MAINTAINED IN CONFIDENCE. NO PORTION OF THIS DRAWING SHALL BE

REPRODUCED OR USED WITHOUT THE EXPRESS WRITTEN PERMISSION OF ARGUS CONTROL

SYSTEMS LTD.

ALL FIELD WIRING MUST FOLLOW

LOCAL CODES AND REGULATIONS

USDA - TC5 - RCP-B5-7-01.DWG

USDA COEUR D’ALENE

JP AK

DEC 10, 2021 2

RCP-B5-7-01

PANEL WIRING

CLASS 2

FIELD WIRING

FIELD WIRING

BY INSTALLER

P1T

IO[B5-7-B] - OP1

24 VAC POWER FROM

IO[B5-7-A] - OP4

C O

D4 A B C D

IO[B5-7-B] - OP2

K-B5-7-01: (PILOT DUTY)

WEST-HEATER 1 BAY 1-4 -1 24 VAC 3A MAX (BY INSTALLER)

A1

A2

CONTROL INTERFACE

K-B5-7-02: (PILOT DUTY)

WEST-HEATER 1 BAY 1-4 -2 24 VAC 3A MAX (BY INSTALLER)

A1

A2

CONTROL INTERFACE

K-B5-7-03: (PILOT DUTY)

WEST-HEATER 1 BAY 1-4 -3 24 VAC 3A MAX (BY INSTALLER)

A1

A2

CONTROL INTERFACE

K-B5-7-04: (PILOT DUTY)

WEST-HEATER 2 BAY 5-7 -1 24 VAC 3A MAX (BY INSTALLER)

A1

A2

CONTROL INTERFACE

K-B5-7-05: (PILOT DUTY)

WEST-HEATER 2 BAY 5-7 -2 24 VAC 3A MAX (BY INSTALLER)

A1

A2

CONTROL INTERFACE

K-B5-7-06: (PILOT DUTY)

WEST-HEATER 2 BAY 5-7 -3 24 VAC 3A MAX (BY INSTALLER)

A1

A2

CONTROL INTERFACE

D4 A B C D

IO[B5-7-B] - OP3

WEST-SIDEWALL VENT (COOLING WALL)

24 VAC 5VA MAX (0.2A)

CONTROL INTERFACE

CLOSE

COMMON

OPEN

WEST-HEATER FAN BAY 1-7

24 VAC 5VA MAX (0.2A)

CONTROL INTERFACE

ON/OFF

COMMON

Project Mngr: Drawn by:

Current Revision:

Dwg:

Creation Date:

19900 84 AVENUE

LANGLEY, BC

V3Y 3C2

Sheets and Views
USDA - SITE & NETWORK-Revision List
USDA - SITE & NETWORK-SITE
USDA - SITE & NETWORK-SITE (2)
USDA - SITE & NETWORK-IO NET TC(5)
USDA - TC5 - RCP-B5-7-01-Revision List
USDA - TC5 - RCP-B5-7-01-RCP LAYOUT
USDA - TC5 - RCP-B5-7-01-RCP LAYOUT (2)
USDA - TC5 - RCP-B5-7-01-RPTR(A)
USDA - TC5 - RCP-B5-7-01-TC
USDA - TC5 - RCP-B5-7-01-IOPS
USDA - TC5 - RCP-B5-7-01-IO
USDA - TC5 - RCP-B5-7-01-IO (2)
USDA - TC5 - RCP-B5-7-01-RCP WIRING (1)
USDA - TC5 - RCP-B5-7-01-RCP WIRING (2)
USDA - TC5 - RCP-B5-7-01-RCP WIRING (3)

File details come from the government source that posted it. Updated .