HVAC_SOW PDF.pdf
PDF 2 MB Posted
- Attached to
- HVAC Repair
- Solicitation number
- FA282325QA025
About this file
This Statement of Work (SOW) details urgent air conditioner repair for multiple HVAC units at Building 15312 in Duke Field, 96th Test Wing facility. The scope encompasses repairs for five non-functioning air conditioning units, with specific repair requirements for each unit including replacing evaporator coils (Units A, F, and H), replacing the compressor (Unit G), and replacing the condensing fan motor (Unit J). All units are Bard brand, wall-mounted exterior units with 3-ton capacity, and each requires unique interventions such as refrigerant recharging, system evacuation, component replacements, and motor/capacitor changes. The technical requirements mandate pulling units A, F, H, and G into a vacuum and recharging them according to manufacturer specifications, with detailed steps for each unit's specific repair needs.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| HVAC_SOW PDF.pdf | ||
| Model numbers.jpg | JPG image | |
| SITE VISIT.pdf | ||
| USA000392-25-DPCAP.pdf | ||
| DAF-Contracting-SPE-Delegate--Open-Letter-to-Contractors-21-Mar-25.pdf | ||
| USA000368-25-DPCAP.pdf | ||
| SITE VISIT.pdf | ||
| COMBO_Redacted.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK
for
Air conditioner repair at Bldg. 15312 Duke Field
1.0 INTRODUCTION
1.1 Background
Urgent air conditioner repair at Duke Field 96th TW (15312) facility that has no current maintenance contract
1.2 Scope
Multiple (5) air conditioning units are currently not working and need repair before more of the units fail due to strain.
2.0 TECHNICAL REQUIREMENTS
At a minimum, the Contractor shall accomplish the requirements of this order through fulfilling the following specifications:
• Replace the evaporator coils on unit A, H and F. Replace the compressor on unit G, and replace the condensing fan motor for unit J. Pull units A, F, H, and G into a vacuum, and charge according per manufacturers specifications..
3.0 DELIVERABLES
Unit A: Replace Evaporator Coil and Recharge
Install New Evaporator Coil (Up flow A-Coil) Recharge the system with R410A Evacuate the system to remove impurities prior to recharge Type of Unit- Exterior Wall Brand- Bard Serial numbers- 278J1936739-02 Tonnage- 3
Unit F: Replace Evaporator Coil and Recharge
Install New Evaporator Coil (Up flow A-Coil) Recharge the system with R410A Evacuate the system to remove impurities prior to recharge Type of Unit- Exterior Wall Brand- Bard Serial number-278J193671749-02 Tonnage- 3
Unit G: Refrigerant Leak at evaporator has caused it to lose all the Refrigerant Compressor is inoperable
Evacuate the system to remove impurities prior to recharge Recharge the system with R410A
Replace 2.0 Ton Compressor Change Out 1 Phase to include:
Up to 8lbs of refrigerant
Drier replacement Capacitor replacement Refrigerant Recovery
1/2HP-1/6HP, 1075/240V
Rescue Blower Motor Replace an inoperative 1/6 HP Belt Drive furnace blower motor Type of Unit- Exterior Wall Brand- Bard Serial number- 278J193671742-02 Tonnage- 3
Unit H: Replace Evaporator Coil and Recharge Install New Evaporator Coil (Up flow A-Coil) Recharge the system with R410A Evacuate the system to remove impurities prior to recharge Type of Unit- Exterior Wall Brand- Bard Serial number- 278J193671745-02 Tonnage- 3
Unit J: Condenser Fan Motor is Inoperable Replace Condensing Fan Motor w/ capacitor Condenser Motor 825 RPM Replacement of 825 RPM condenser fan motor w/new capacitor Open system disconnects, check electric power "OFF", remove old motor & capacitor, install new, check fan operation Type of Unit- Exterior Wall Brand- Bard Serial number- 278J193671740-02 Tonnage- 3