HVAC Replacement Drawings.pdf

PDF 8 MB Posted

Attached to
HVAC Replacement at JBCC Bldg 2410
Solicitation number
6913G624Q300024
Issued by

About this file

This document is the HVAC Replacement Drawings for Building #2410 at Joint Base Cape Cod in Sandwich, MA, which is related to a federal contract opportunity with Solicitation Number 6913G624Q300024.

The key details are: This is a Request for Quotation (RFQ) for the replacement of the inoperable rooftop HVAC unit at Building #2410, which is leased by the U.S. Department of Transportation's Volpe Center and used for testing of backup GPS and PNT systems. The work entails construction renovation tasks as per the provided drawings and specifications. Quotations must be submitted by 4:00 PM ET on May 8, 2024. This is a Total Small Business set-aside with NAICS code 238220 and a $19 million size standard. The government will not pay for any quote preparation costs. Relevant attachments include the Solicitation, Statement of Work, Specifications, Drawings, and SF 1449 form.

View the file

Other files

File Type Posted
6913G624Q300024 0004.pdf PDF
6913G624Q300024 0003.pdf PDF
6913G624Q300024 0002.pdf PDF
6913G624Q300024 0001.pdf PDF
Solicitation 6913G624Q300024.pdf PDF
HVAC Replacement Specifications.pdf PDF
SF1449 6913G624Q300024.pdf PDF
HVAC Replacement SOW.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PANELBOARD - MDP VOLTAGE 208 / 120 AMP BUS 400 SPECIAL FEATURES - EXISTING

MOUNTING - SURFACE PHASE 3 AMP MCB ------

A.I.C. RATING - 10,000 WIRE 4 AMP MLO 400

LOAD DESCRIPTION

LOAD (VA) BREAKER

CIRCUIT

3 PH.

CIRCUIT

BREAKER LOAD (VA)

LOAD DESCRIPTION

LIGHT RECEP. HVAC MISC. AMP POLES A B C POLES AMP LIGHT RECEP. HVAC MISC.

1 2

3 100

DWH TANK (abandoned) 20 2

3 4

TANK MONITOR ALERT

5 6 7 8 9 10 11 12

13 14

PANELBOARD - RP9373

15 16 17 18

NOTES:

1) REFER TO CLIN 0600 LIGHTING PLAN FOR POINT OF CONNECTION LOCATIONS TO EXISTING CIRCUITS #1, #3, #5, #7.

Connected Loads By Phase (VA) Total Connected Loads By Type (VA) Demand Factors

Total Demand Loads By Type (VA)

Total Phase A 20,379 Lighting 1,970 Lighting 1.00 Lighting 1,970 Total Phase B 18,611 Receptacles 4,800 Receptacles 0.50 Receptacles 7,400 Total Phase C 16,607 HVAC 48,327 HVAC 0.85 HVAC 41,078

Miscellaneous 500 Miscellaneous 0.65 Miscellaneous 325 Total

55,597

Subtotal

50,773

Spare Capacity 25% Spare 12,693

Total Demand Load

63,466

Total Demand Amps

PANELBOARD - RP VOLTAGE 208 / 120 AMP BUS 225 SPECIAL FEATURES -

MOUNTING - SURFACE PHASE 3 AMP MCB ------

A.I.C. RATING - 22,000 WIRE 4 AMP MLO 225

LOAD DESCRIPTION

LOAD (VA) BREAKER

CIRCUIT

3 PH.

CIRCUIT

BREAKER LOAD (VA)

LOAD DESCRIPTION

LIGHT RECEP. HVAC MISC. AMP POLES A B C POLES AMP LIGHT RECEP. HVAC MISC.

(future) EXHAUST FANS 1224 20 1 1 2 1 20 TANKLESS WATER HEATER RM 2, RECEPT RM 2

(future) UH-1

20 2

3 4 1 20 RECEPTACLES BATHROOM RM 5

1650 5 6 1 20 RECEPTACLES SHOWER RM 6

(new) RTU-1

80 3 7 8 1 20 RECEPTACLES RM 1 Northeast

4323 9 10 1 20 RECEPTACLES RM 1 Southeast 4323 11 12 1 20 RTU-1 GFCI & RECEPTACLES RM 1 Northwest

40 3 13 14 1 20 RECEPTACLES RM 1 Southwest 15 16

17 18

FIRE ALARM PANEL 20 1 19 20

21 22 23 24 25 26

27 28 1 SPACE

DRILL PRESS (relocated) 20 3 29 30 1 SPACE

31 32 1 SPACE

SPARE 20 1 33 34 1 SPACE

SPARE 20 1 35 36 1 SPACE

SPACE 1 37 38 1 SPACE

SPACE 1 39 40 1 SPACE

SPACE 1 41 42 1 SPACE

NOTES: REFER TO CLIN 0200 ELECTRICAL PLAN FOR POINT OF CONNECTION LOCATIONS TO EXISTING CIRCUITS #1, #2, #4, #6, $8, #10, #12, #14, #16, #18, #20.

Connected Loads By Phase (VA) Total Connected Loads By Type (VA) Demand Factors

Total Demand Loads By Type (VA)

Total Phase A 9,747 Lighting 0 Lighting 1.00 Lighting 0 Total Phase B 9,373 Receptacles 7,320 Receptacles 1.00 Receptacles 7,320 Total Phase C 8,693 HVAC 19,493 HVAC 0.85 HVAC 16,569

Miscellaneous 1,000 Miscellaneous 0.65 Miscellaneous 650 Total

27,813

Subtotal

24,539

Spare Capacity 25% Spare 6,135

Total Demand Load

30,674

Total Demand Amps

Scale

Project number

Date

Drawn by

Checked by

A B

Submission

OCTOBER 23, 2023

DOT REDESIGN OF

BUILDING #2410

JOINT BASE CAPE COD

SANDWICH, MA

USDOT/VOLPE

CENTER

55 BROADWAY CENTER

CAMBRIDGE, MA 02142-1001

No. Description Date

20 1 existing RTU-1

3 225

CONSTANT CURRENT REGULATOR

2 20 spareWW FIELD (overhead lines to Field) 60 2

1 20

RECEPTACLES RM 7 STORAGE, RM 3 MECH RM

RECEPTACLES RM 4 West

UPS for DAS2 30

PANELBOARD

SCHEDULES

SHEET 06

1 20

20 1EQUIPMT RM LTS (SOUTH)

OFFICE LTS. and DOOR #4 EXIT SIGN

STORAGE, MECH, WORKSHOP, BATHRMS LTS

EQUIPMT RM LTS (NORTH) and DOOR#1 EXIT SIGN 1 20 1 20 1

OUTDOOR LTS 20 1

OUTDOOR LTS 20 1

RTU-1_E-201

RECEPTACLES RM 4 East 1 20

File details come from the government source that posted it. Updated .