This document is the HVAC Replacement Drawings for Building #2410 at Joint Base Cape Cod in Sandwich, MA, which is related to a federal contract opportunity with Solicitation Number 6913G624Q300024.
The key details are: This is a Request for Quotation (RFQ) for the replacement of the inoperable rooftop HVAC unit at Building #2410, which is leased by the U.S. Department of Transportation's Volpe Center and used for testing of backup GPS and PNT systems. The work entails construction renovation tasks as per the provided drawings and specifications. Quotations must be submitted by 4:00 PM ET on May 8, 2024. This is a Total Small Business set-aside with NAICS code 238220 and a $19 million size standard. The government will not pay for any quote preparation costs. Relevant attachments include the Solicitation, Statement of Work, Specifications, Drawings, and SF 1449 form.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 6913G624Q300024 0004.pdf | ||
| 6913G624Q300024 0003.pdf | ||
| 6913G624Q300024 0002.pdf | ||
| 6913G624Q300024 0001.pdf | ||
| Solicitation 6913G624Q300024.pdf | ||
| HVAC Replacement Specifications.pdf | ||
| SF1449 6913G624Q300024.pdf | ||
| HVAC Replacement SOW.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PANELBOARD - MDP VOLTAGE 208 / 120 AMP BUS 400 SPECIAL FEATURES - EXISTING
MOUNTING - SURFACE PHASE 3 AMP MCB ------
A.I.C. RATING - 10,000 WIRE 4 AMP MLO 400
LOAD DESCRIPTION
LOAD (VA) BREAKER
CIRCUIT
3 PH.
CIRCUIT
BREAKER LOAD (VA)
LOAD DESCRIPTION
LIGHT RECEP. HVAC MISC. AMP POLES A B C POLES AMP LIGHT RECEP. HVAC MISC.
1 2
3 100
DWH TANK (abandoned) 20 2
3 4
TANK MONITOR ALERT
5 6 7 8 9 10 11 12
13 14
PANELBOARD - RP9373
15 16 17 18
NOTES:
1) REFER TO CLIN 0600 LIGHTING PLAN FOR POINT OF CONNECTION LOCATIONS TO EXISTING CIRCUITS #1, #3, #5, #7.
Connected Loads By Phase (VA) Total Connected Loads By Type (VA) Demand Factors
Total Demand Loads By Type (VA)
Total Phase A 20,379 Lighting 1,970 Lighting 1.00 Lighting 1,970 Total Phase B 18,611 Receptacles 4,800 Receptacles 0.50 Receptacles 7,400 Total Phase C 16,607 HVAC 48,327 HVAC 0.85 HVAC 41,078
Miscellaneous 500 Miscellaneous 0.65 Miscellaneous 325 Total
55,597
Subtotal
50,773
Spare Capacity 25% Spare 12,693
Total Demand Load
63,466
Total Demand Amps
PANELBOARD - RP VOLTAGE 208 / 120 AMP BUS 225 SPECIAL FEATURES -
MOUNTING - SURFACE PHASE 3 AMP MCB ------
A.I.C. RATING - 22,000 WIRE 4 AMP MLO 225
LOAD DESCRIPTION
LOAD (VA) BREAKER
CIRCUIT
3 PH.
CIRCUIT
BREAKER LOAD (VA)
LOAD DESCRIPTION
LIGHT RECEP. HVAC MISC. AMP POLES A B C POLES AMP LIGHT RECEP. HVAC MISC.
(future) EXHAUST FANS 1224 20 1 1 2 1 20 TANKLESS WATER HEATER RM 2, RECEPT RM 2
(future) UH-1
20 2
3 4 1 20 RECEPTACLES BATHROOM RM 5
1650 5 6 1 20 RECEPTACLES SHOWER RM 6
(new) RTU-1
80 3 7 8 1 20 RECEPTACLES RM 1 Northeast
4323 9 10 1 20 RECEPTACLES RM 1 Southeast 4323 11 12 1 20 RTU-1 GFCI & RECEPTACLES RM 1 Northwest
40 3 13 14 1 20 RECEPTACLES RM 1 Southwest 15 16
17 18
FIRE ALARM PANEL 20 1 19 20
21 22 23 24 25 26
27 28 1 SPACE
DRILL PRESS (relocated) 20 3 29 30 1 SPACE
31 32 1 SPACE
SPARE 20 1 33 34 1 SPACE
SPARE 20 1 35 36 1 SPACE
SPACE 1 37 38 1 SPACE
SPACE 1 39 40 1 SPACE
SPACE 1 41 42 1 SPACE
NOTES: REFER TO CLIN 0200 ELECTRICAL PLAN FOR POINT OF CONNECTION LOCATIONS TO EXISTING CIRCUITS #1, #2, #4, #6, $8, #10, #12, #14, #16, #18, #20.
Connected Loads By Phase (VA) Total Connected Loads By Type (VA) Demand Factors
Total Demand Loads By Type (VA)
Total Phase A 9,747 Lighting 0 Lighting 1.00 Lighting 0 Total Phase B 9,373 Receptacles 7,320 Receptacles 1.00 Receptacles 7,320 Total Phase C 8,693 HVAC 19,493 HVAC 0.85 HVAC 16,569
Miscellaneous 1,000 Miscellaneous 0.65 Miscellaneous 650 Total
27,813
Subtotal
24,539
Spare Capacity 25% Spare 6,135
Total Demand Load
30,674
Total Demand Amps
Scale
Project number
Date
Drawn by
Checked by
A B
Submission
OCTOBER 23, 2023
DOT REDESIGN OF
BUILDING #2410
JOINT BASE CAPE COD
SANDWICH, MA
USDOT/VOLPE
CENTER
55 BROADWAY CENTER
CAMBRIDGE, MA 02142-1001
No. Description Date
20 1 existing RTU-1
3 225
CONSTANT CURRENT REGULATOR
2 20 spareWW FIELD (overhead lines to Field) 60 2
1 20
RECEPTACLES RM 7 STORAGE, RM 3 MECH RM
RECEPTACLES RM 4 West
UPS for DAS2 30
PANELBOARD
SCHEDULES
SHEET 06
1 20
20 1EQUIPMT RM LTS (SOUTH)
OFFICE LTS. and DOOR #4 EXIT SIGN
STORAGE, MECH, WORKSHOP, BATHRMS LTS
EQUIPMT RM LTS (NORTH) and DOOR#1 EXIT SIGN 1 20 1 20 1
OUTDOOR LTS 20 1
OUTDOOR LTS 20 1
RTU-1_E-201
RECEPTACLES RM 4 East 1 20