RFQ HSSS01‐16‐Q‐0308 Electrical Upgrade Questions and Answers

Question Answer

1 Will there be a site visit? No, there is not a scheduled site visit for this requirement.

2 Is there a drop ceiling in each room? Yes

3 Wilkie Building Rooms 117A & 117B: How far is the electrical panel from the equipment location?

117A ‐ 50 feet 117B – 75 feet

4 Merletti Building Rooms 203 & 204: What type of computer furniture is currently in the room and how many circuits?

New computer furniture to be installed, should be Eaton LINX Modular computer Stations.

Currently has 25 dual electrical outlets, 50 computer circuits and 25 telephone circuits

5 Merletti Building Rooms 203 & 204: Where is the electrical closet located and distance in relation to these rooms?

Down a hallway, approximately 75 feet

6 Merletti Buildling Room 154 &155: How many monitors/televisions are going into these rooms, respectively?

Three total, one on front wall of Rm 155 and two in ceiling of Rm 154

7 Merletti Buildling Room 154 & 155: Where is the electrical closet located and distance in relation to these rooms, respectively?

Down a hallway, from Rm 155 it is approximately 75 feet; from Rm 154 it is approximately 40 feet

8 Moran Building Rooms A & B: Where is the electrical closet located and distance in relation to these rooms, respectively?

In adjacent room, from Rm. A it is 25 feet from Rm B it is approximately 60 feet

9 Baughman Building Rooms A & B: Where is the electrical closet located and distance in relation to these rooms, respectively?

Electrical closet is in adjacent room approximately 25 feet from each class room

10 Drummond Building: How many projection screens are being installed?

One

11 Drummond Building: Is there a drop ceiling where the projection screens are being installed?

Yes

12 Knight Building Rooms 109, 201, & 202: Is there a drop ceiling in these rooms?

Yes

13 Requirements 2.1 through 2.6 do not show the distances between the items to be connected and the corresponding electrical breaker/panels, what is the distance for each room?

M203 – 65 feet M204 – 75 feet M154 – 40 feet M155 – 75 feet W117A – 50 feet W117B – 75 feet K109 – 100 feet K201 – 70 feet

RFQ HSSS01‐16‐Q‐0308 Electrical Upgrade Questions and Answers

K202 – 125 feet Moran A – 25 feet Moran B – 60 feet Baughman A – 25 feet Baughman B – 25 feet Drummond – 40 feet

14 Are there enough spare circuit breakers to accommodate the new circuits?

Yes

15 Can you please provide the DOL Wage Determination?

23160 ‐ Electrician

16 Do you require a bond for this project? No, a bond will not be required for this requirement.

17 How long does the contractor have to complete the project?

Will work in coordination with A/V contractor renovating the class rooms along with general contractor providing new furniture and accordion wall.

18 Can drawings to identify electrical closets, feeders, and lengths between the closets and panels be provided?

Where available, not all are. General Lengths are provided in previous answers

19 Can you provide the electrical specification to identify the wire size, power load data, Grounding and Bonding, conduit size and box types?

No

20 Can you provide the wiring and riser diagram to identify pathways and raceway?

No

21 Can you provide the electrical schedule to identify the Electrical Switchboard and Panelboard?

Available for some buildings

22 Has a contractor performed similar work?

Can you provide the incumbent contract number?

No, this is a new requirement.

23 Are there any plan sheets showing the size and/or layout of the circuits/receptacles or quantities needing connection in each classroom?

No

24 Is there an appropriate Davis‐Bacon Wage Scale for this requirement?

No, this requirement is subject to the Service Contract Labor Act.