version 1.6 05-2011

Installation Date:

Contractor Name and Person Installing:

For Emergency Service Call:

FEMA

Tank and Pump System

General Information, Commissioning and Decommissioning Instructions

Table of Contents Section 1 - Safety & Warnings

1.1 - Safety Guidelines

1.2 - Unpacking

1.3 - General Safety Information

Section 2 - System Description

Section 3 - Installation Instructions

3.1 - Initial Inspection

3.2 - Moving

Section 4 - Air Bleeding the System If Motor Runs but has no Flow

Section 5 - Water Fill and Drain Connection Diagrams

5.1 - System Water Connection Diagram

IMPORTANT: ALL INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE.

Consult factory for the most up to date version of this manual - 1-800-345-8207.

- Please take the time to complete the forms on the back of this manual.

- Additional information can be found attached to the back of this manual.

Section 1 - Safety & Warnings

1.1 Safety Guidelines

This manual contains information that is very important to know and understand. This information is provided for SAFETY and to PREVENT EQUIPMENT PROBLEMS. To help recognize this information, observe the following symbols.

Danger indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.

Warning indicates a potentially hazardous situation which, if not avoided COULD result in death or serious injury.

Caution indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.

Notice indicates important information, that if not followed may cause damage to equipment.

1.2 Unpacking

After unpacking the unit, carefully inspect for any damage that may have occurred during transit, Make sure to tighten fittings, bolts, etc., before putting unit into service.

Do not operate unit if damaged during shipping, handling or use.

1.3 General Safety Information

1. Read all manuals included with this product carefully. Be thoroughly familiar with the controls and the proper use of the equipment

2. Follow all local electrical and safety codes as well as National Electrical Codes (NEC), Occupational Safety and Health Act (OSHA), and National Fire Protection Association (NFPA)

3. Only persons familiar with these rules of safe operation should be allowed to use the equipment.

4. Keep visitors away and NEVER allow children in the work area.

5. Wear safety glasses and use hearing protection when operating the unit.

6. Do not stand on or use the unit as a handhold.

7. Periodic inspection and test of this equipment is required. Consult your installer and local codes to meet all requirements.

8. Check all fasteners at frequent intervals for proper tightness.

DANGER

WARNING

CAUTION

NOTICE

1.3 General Safety Information (Continued)

- Motors, Electrical Equipment and Controls can cause electrical arcs that will ignite a flammable gas or vapor.

- Never operate or repair in or near a flammable gas or vapor.

- Never store flammable liquids or gases in the vicinity of the system.

- For up to date fire protection information please consult the National Fire Protection Association at www.nfpa.org.

Use a backup wrench when adjusting any water piping on the tank or pumping unit

Moving the piping without the use of a backup wrench will turn the suction elbow inside of the tank out of position.

Section 1 - Safety & Warnings

NOTICE

1.4 Narrow Water Tank Safety Information

- Fill tank with water and hold for at least 5 hours PRIOR to use to identify leakage through unsecured fittings, shipping damage or manufacturing defects. The tank manufacturer's warranty is void unless upon installation of the tank, the tank is water pre-tested as a final test of suitability.

- DO NOT use for vacuum or pressure applications. Tank must be properly vented.

- Continuous operating temperatures above 140°F (60°C) are NOT RECOMMENDED. Consult factory for operating temperature above 100°F (38°C).

- Protect tanks from impact (especially sharp blows).

- Installation sites for tank and pump systems should be on a solid, stable and compacted pad no smaller than 4' x 8'.

RECOMMENDED. Tank should not be used for anything other than water. WATER ONLY IN TANK

- Use expansion joints or other flexible connection methods at all tank fittings to prevent damage from differential expan-sion and contraction of piping and tank. The use of rigid piping or the failure to provide for the expansion of the tank will void all warranties.

- Observe all local, state and federal codes.

- Ensure tank is clean from debris before filling tank with water.

WARNING

WARNING

WARNING

This manual includes information that shall not be disclosed outside the Government and shall not be duplicated, used, or disclosed—in whole or in part.

Section 2 - System Description

This unit is a pump/tank is packaged and specifically designed for FEMA Tank and Pump Systems.

Section 3 - Installation Instructions

3.1 Initial Inspection

When the tank and pump system is received, they should be immediately inspected for damage. If the equipment has been damaged in shipment or shortages are noticed, immediately notify FEMA immediately. If hidden damage to the residential pump system is suspected, it is recommended that the system be filled with water as a leak check prior to installation.

3.2 Moving Tank and Pump System:

A forklift is requMoving the tank and pump enclosure must be performed by a forklift only.ired to move the tank and pump system.

UNDER NO CIRCUMSTANCES SHOULD THE PIPING BE USED IN LIFTING OR

MOVING THE SYSTEMS.

THE SYSTEM MUST BE INSTALLED ON A LEVEL.

CAUTION

CAUTION

Section 4 - Air Bleeding the System If Motor Runs but has no Flow When first filling up the system, ensure that all of the air is bled out of the pump and piping. The pump is supplied with a hex bolt on the housing (see below) that allows the pump casing to be vented. Loosen the hex bolt to allow air to escape.

Once the pump casing is filled with water, tighten the hex bolt. If the pump does not have a hex bolt, crack the union or flange on the pump discharge pipe.

Hex Bolt Stainless-Steel Pump

Section 5 - Water Fill and Drain Connection Diagram

5.1 System Water Fill and Drain Connection Diagram : Fill tank with garden hose. Only use water inside tank.

Installation of Tank and Pump Enclosure GSH 201510.2

1. Site Preparation

The tank and pump enclosure site must be prepared in accordance with state and local building codes.

1. To move or relocate the TPS a Forklift is required.

2. The tank and pump enclosure must be placed on level surface no less than (4 feet by 8 feet) created by using compacted gravel or a similar substrate. The tank and pump enclosure must be lifted with adequate support, the use of a forklift is required to maintain control of the enclosure and place on the ground without damage.

3. Place enclosure in accordance with FEMA’s instructions (see illustration below).

4. Remove 2-anchor straps from inside the tank and pump system. The anchor straps are located immediately inside the access door on the floor.

Minimum TPS pad site 4’ x 8’

5. Install 1 (one) tie down straps on each side of the MHU. There is 1 (one) BP-10 receiver for each of the 2 (two) anchor straps located on the lower edge-side of the tank and pump enclosure.

6. Anchors must be installed to their full depth and embedded below the frost line and to be at least 12" above the water table at a 45 degree angle.

2. Remove Installation Parts Box

Remove the installation parts box from Tank and Pump Enclosure.

Part are as follows:

Qty 1 – 90 elbow 1 ½ inch Qty 1 – 45 elbow 1 ½ inch Qty 1 - Close 1 ½ inch Qty 1 – Roll pipe tape Qty 1 – Raychem Splice Kit Qty 1 - Enclosure Key Qty 1 - Electrical Circuit Box Key

3. Installation of Insulated Water Supply Line

1. Carefully Remove zip ties

2. Carefully unwind insulated water supply line to prevent damage.

3. Locate riser connection under Manufactured housing unit.

4. Attach fittings using a type of thread seal or plumbers putty to attach and install insulated water supply line to MHU riser. Additional plumbing fittings are located in the installation parts box.

5. Remove the wire that attached the cam lock to the hose. Keep wire, the wire is for storage of the cam lock and keeping the cam lock in ‘closed position’ on the riser. The cam lock is removable to aide in attaching to riser. After attaching to the riser (under MHU) place cam lock in ‘closed’ position. Use the wire to ensure the cam lock stays closed.

4. Installation of the Heat Tape

1. Read Raychem installation guide completely prior to installation. A copy is provided in this packet. Any questions with Raychem products call Raychem technical support.

2. Remove end cap from Heat tape (orange wire) by cutting the heat tape about ¼” from the cap. Throw away cap.

3. Use the Raychem-S (see Raychem installation guide) to attach heat trace (orange wire pictured above) from water supply line to heat trace wire on riser of manufactured housing unit.

5. Installation of Electrical wire

1. Carefully remove zip ties.

2. Carefully unwind electrical wire by rotating wires to ensure no damage.

3. Plug into mechanical interlock located on the rear of the Manufactured housing unit.

System is now operational. If you have any question or concerns contact your supervisor immediately.

Tank and Pump System: Heater The heater is located on the wall to the left of the door.

To Operation

1. Turn on the power supply to heater.

2. Rotate thermostat knob fully clockwise.

3. Allow the room to reach desired temperature, then rotate thermostat knob counter clockwise until the heater de-energizes.

Maintenance and Cleaning of Heater

The heater should be cleaned at least annually to prevent excess build-up of dirt and lint accumulated under normal operating conditions. To clean heater first Disconnect the heater form the main power source. Then remove the grille. Using a vacuum cleaner with soft bush attachment clean the fan blade and element of any accumulated dirt or link. Be careful not to bend the petals of the blade. When the cleaning is finished, re-install the grille and restore power. DO NOT OPERATE THE HEATER WITHOUT THE

GRILLE.

TPS Battery Commission/Decommission Instruction

When power is off and the pump-tank unit is being decommissioned the blue wire between the battery and the terminal marked “Batt +” must be disconnected or the batteries will keep the box powered and will drain.

When the wire is disconnected the metal portion of the electrical connector must be covered with electrical tape as shown below.

When the TPS is put back into service and power is delivered to the pump-tank unit the blue wire on the battery must be connected on the “Batt +” terminal as shown in figure 1.

Remove insulation and install to BATT+ terminal

Figure 1

TPS Temperature Controller Programming

The following is the programming steps for the temperature controllers

• Hold the SET button and press the UP ARROW button

• Screen will show “C I.Cn”

• Press the DOWN ARROW button

• Screen will show “CI.L.L”

• Hold the SET button and press the UP ARROW button until “38” appears on the screen

• Press the DOWN ARROW button

• Screen will show “CI.H.L”

• Hold the SET button and press the DOWN ARROW button until “38” appears on the screen

• Press the DOWN ARROW button

• Screen will show “CI.H.Y”

• Hold the SET button and press the UP ARROW button until “3” appears on the screen

• Release all buttons. The screen will show “CI.H.Y” for several seconds then it will show the ambient temperature.

• Programming is Complete

Note: Once programming is complete if ambient temperature is below 35°F the temperature alarm will sound.

Up Arrow Button

Down Arrow Button

Set Button

Decommissioning of Tank and Pump Enclosure

Decommission of Tank and Pump Enclosure

1. To move or relocate the TPS a Forklift is required. Lift the side with the sign “Lift this side”.

2. Remove tie down strap from anchor located in ground.

3. Remove the tie down strap form the BP-10 receiver located on the lower edge-side of the tank and pump enclosure.

4. Place 2-anchor straps inside the tank and pump system immediately inside the access door on the floor zip tie (use two) to the pipe to prevent movement.

Decommissioning of Insulated Water Supply Line

1. Locate riser and insulated water hose connection below the

MHU.

2. Cut the orange wire (heat trace) as close to the Raychem Splice. You will make two cuts. One on each end of the Raychem Splice kit. This kit can be disposed.

3. Add a Raychem end cap on both cut ends of the orange wire.

4. Carefully Remove wire from cam lock

5. Open Cam lock

6. Remove Male fitting – Hose is now disconnected from MHU.

7. Carefully wrap the insulated water supply line around the hose hanger located on the rear of the MHU. Use zip ties to secure hose.

Decommissioning of Electrical wire

1. Remove Pad Lock from Mechanical interlock located on rear of MHU.

2. Turn to knob to off/unlock

3. Remove plug

4. Carefully wrap electrical wire to ensure no damage.

5. Hang on hanger located on rear of TPS Enclosure.

6. Secure with zip ties.

If you have any question or concerns, contact your supervisor immediately.

Piping Tested By Date Inspected By Date Assembly

Tested By Date Inspector Date

Service Sheet

E-215284 REV 1 WIRING DIAGRAM 230V 1PH 60Hz FOR GSH-ALABAMA.PDF