Spec Section 08 51 13 Revised May 5, 2017
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Abstract_17-B-PRV127.pdf | ||
| Amendment0001_17-B-PRV127.pdf | ||
| P7235170DWG_H.pdf | ||
| IFB_HSCGG117BPRV127.pdf | ||
| Appendix_A_-Supplemental_Requirements_to_Section_27_10_00.pdf | ||
| P7235170DWG_A.pdf | ||
| P7235170DWG_G.pdf | ||
| P7235170DWG_C.pdf | ||
| P7235170SPEC.pdf | ||
| P7235170DWG_J.pdf | ||
| P7235170DWG_D.pdf | ||
| General_Decision_Number_ME170034_01062017__ME34.pdf | ||
| P7235170DWG_L.pdf | ||
| P7235170DWG_F.pdf | ||
| P7235170DWG_E.pdf | ||
| P7235170DWG_B.pdf | ||
| P7235170DWG_K.pdf |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTOR NNE, BUILDINGS 1 & 2, MAJOR MAINTENANCE AND REPAIR 7235170
CG SECTOR NNE, SOUTH PORTLAND, ME
SECTION 08 51 13
ALUMINUM WINDOWS
05/11
REVISED MAY 05, 2017
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 1503 (2009) Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections
AAMA 2603 (2015) Voluntary Specification, Performance Requirements and Test Procedures for Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 701/702 (2011) Voluntary Specification for Pile Weatherstripping and Replaceable Fenestration Weatherseals
AAMA 902 (2014) Voluntary Specification for Sash Balances
AAMA/WDMA/CSA 101/I.S.2/A440 (2011; Update 1 2014) North American Fenestration Standard/Specification for Windows, Doors, and Skylights
NATIONAL FENESTRATION RATING COUNCIL (NFRC)
NFRC 100 (2014) Procedure for Determining Fenestration Product U-Factors
1.2 CERTIFICATION
Each prime window unit must bear the AAMA Label warranting that the product complies with AAMA/WDMA/CSA 101/I.S.2/A440 . Certified test reports attesting that the prime window units meet the requirements of AAMA/WDMA/CSA 101/I.S.2/A440 , including test size, will be acceptable in lieu of product labeling.
1.3 SUBMITTALS
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Windows
SECTION 08 51 13 Page 1
Fabrication Drawings
SD-03 Product Data
Windows
Hardware
Fasteners
Window Performance
Thermal-Barrier Windows
Screens
Weatherstripping
Accessories
Thermal Performance
SD-05 Design Data
Structural Calculations for Deflection
Design Analysis
Submit design analysis with calculations showing that the design of each different size and type of aluminum window unit and its anchorage to the structure meets the minimum antiterrorism standards required by paragraph "Minimum Antiterrorism Performance", unless conformance is demonstrated by standard Airblast Test results . Calculations verifying the structural performance of each window proposed for use, under the given loads, must be prepared and signed by a registered Professional Engineer. The window components and anchorage devices to the structure, as determined by the design analysis, must be reflected in the shop drawings.
SD-06 Test Reports
Minimum Condensation Resistance Factor
SD-10 Operation and Maintenance Data
Windows, Data Package 1
Submit in accordance with Section 01 78 23 OPERATION AND
MAINTENANCE DATA.
1.4 QUALITY ASSURANCE
1.4.1 Shop Drawing Requirements
Provide drawings that indicate elevations of windows, full-size sections, thickness and gages of metal, fastenings, proposed method of anchoring, size and spacing of anchors, details of construction, method of glazing, SECTION 08 51 13 Page 2 details of operating hardware, method and materials for weatherstripping, method of attaching screens, material and method of attaching subframes, stools, casings, sills, trim, installation details, and other related items.
1.4.2 Design Data Requirements
Submit calculations to substantiate compliance with deflection requirements. A registered Professional Engineer must provide calculations.
Submit design analysis with calculations showing that the design of each different size and type of aluminum window unit and its anchorage to the structure meets the requirements of paragraph "Minimum Antiterrorism Performance Criteria" . Calculations verifying the structural performance of each window proposed for use, under the given loads, must be prepared and signed by a registered professional engineer. Reflect the window components and anchorage devices to the structure, as determined by the design analysis, in the shop drawings.
1.4.3 Test Report Requirements
Submit test reports for each type of window attesting that identical windows have been tested and meet the requirements specified herein for conformance to AAMA/WDMA/CSA 101/I.S.2/A440 including test size and minimum condensation resistance factor (CRF).
1.5 DELIVERY AND STORAGE
Deliver windows to project site in an undamaged condition. Use care in handling and hoisting windows during transportation and at the jobsite.
Store windows and components out of contact with the ground, under a weathertight covering, so as to prevent bending, warping, or otherwise damaging the windows. Repair damaged windows to an "as new" condition as approved. If windows can not be repaired, provide a new unit.
1.6 PROTECTION
Protect finished surfaces during shipping and handling using the manufacturer's standard method. Do not apply coatings or lacquers to surfaces to which caulking and glazing compounds must adhere.
1.7 FIELD MEASUREMENTS
Take field measurements prior to preparation of the drawings and fabrication.
1.8 PERFORMANCE REQUIREMENTS
1.8.1 Wind Loading Design Pressure
Design window components, including mullions, hardware, and anchors, to withstand a wind-loading design pressure of at least 63 pounds per square foot (psf) (130 mph, Risk Category IV).
1.9 DRAWINGS
Submit the Fabrication Drawings for aluminum window units showing complete window assembly including hardware, weatherstripping, and subframe
SECTION 08 51 13 Page 3 assembly details.
1.10 WINDOW PERFORMANCE
Aluminum windows must meet the following performance requirements.
Perform testing requirements by an independent testing laboratory or agency.
1.10.1 Structural Performance
Structural test pressures on window units must be for positive load (inward) and negative load (outward). After testing, there will be no glass breakage, permanent damage to fasteners, hardware parts, support arms or actuating mechanisms or any other damage which could cause window to be inoperable. There must be no permanent deformation of any main frame, sash or ventilator member in excess of the requirements established by AAMA/WDMA/CSA 101/I.S.2/A440 for the window types and classification specified in this section.
1.10.2 Air Infiltration
Air infiltration must not exceed the amount established by AAMA/WDMA/CSA 101/I.S.2/A440 for each window type.
1.10.3 Water Penetration
Water penetration must not exceed the amount established by AAMA/WDMA/CSA 101/I.S.2/A440 for each window type.
1.10.4 Thermal Performance
Non-residential aluminum windows (including frames and glass) must be certified by the National Fenestration Rating Council with a U-factor maximum of 0.35 Btu/hr-ft 2-F in accordance with NFRC 100.
1.11 QUALIFICATION
Window manufacturer must specialize in designing and manufacturing the type of aluminum windows specified in this section, and have a minimum of 5 years of documented successful experience. Manufacturer must have the facilities capable of meeting contract requirements, single-source responsibility and warranty.
1.12 WARRANTY
Provide Manufacturer's standard performance guarantees or warranties that extend beyond a 1 year period.
PART 2 PRODUCTS
2.1 WINDOWS
Provide prime windows that comply with AAMA/WDMA/CSA 101/I.S.2/A440 and the requirements specified herein. In addition to compliance with AAMA/WDMA/CSA 101/I.S.2/A440 , window framing members for each individual light of glass must not deflect to the extent that deflection perpendicular to the glass light exceeds L/175 of the glass edge length when subjected to uniform loads at specified design pressures. Provide Structural calculations for deflection to substantiate compliance with
SECTION 08 51 13 Page 4 deflection requirements. Provide windows of types, performance classes, performance grades, combinations, and sizes indicated or specified.
Provide aluminum window frames with a minimum recycled content of 20 percent. Design windows to accommodate hardware, glass, weatherstripping, screens, and accessories to be furnished. Each window must be a complete factory assembled unit with or without glass installed. Dimensions shown are minimum. Provide windows with insulating glass and thermal break necessary to achieve a minimum Condensation Resistance Factor (CRF) of 51 when tested in accordance with AAMA 1503.
2.1.1 Hung Windows (H)
Double Hung, Type H-AW40. Test and rate sash balance to conform with
AAMA 902.
Design windows, mullions, hardware, and anchors to withstand the wind loading specified.
2.1.1.1 Window Materials
Window frames and sash members, mullions, mullion covers, screen frames, and glazing beads must be fabricated in accordance with
AAMA/WDMA/CSA 101/I.S.2/A440 .
Provide woven wool pile weatherstripping 0.210 inch thick, conforming to AAMA 701/702 , or polypropylene multifilament fiber weatherstripping installed in an integral weatherstripping groove in the sash or frame, and flexible polyvinylchloride weatherstripping installed in the sill member.
2.1.2 Glass and Glazing
Materials are specified in Section 08 81 00 GLAZING.
2.1.3 Caulking and Sealing
Are specified in Section 07 92 00 JOINT SEALANTS.
2.1.4 Weatherstripping
AAMA/WDMA/CSA 101/I.S.2/A440 .
2.2 FABRICATION
Fabrication of window units must comply with AAMA/WDMA/CSA 101/I.S.2/A440 .
2.2.1 Provisions for Glazing
Design windows and rabbets suitable for glass thickness shown or specified. Design sash for outside double glazing and for securing glass with metal beads.
2.2.2 Weatherstripping
Provide for ventilating sections of all windows to ensure a weather-tight seal meeting the infiltration requirements specified in AAMA/WDMA/CSA 101/I.S.2/A440 . Provide easily replaceable factory-applied weatherstripping. Use molded vinyl, molded or molded-expanded neoprene or molded or expanded Ethylene Propylene Diene Terpolymer (EPDM) compression-type weatherstripping for compression contact surfaces. Use
SECTION 08 51 13 Page 5 treated woven pile or wool, or polypropylene or nylon pile bonded to nylon fabric and metal or plastic backing strip weatherstripping for sliding surfaces. Do no use neoprene or polyvinylchloride weatherstripping where exposed to direct sunlight.
2.2.3 Fasteners
Use window manufacturer's standard for windows, trim, and accessories.
Self-tapping sheet-metal screws are not acceptable for material more than 1/16 inch thick.
2.2.4 Joint Sealants
Provide joint sealants as specified in Section 07 92 00 JOINT SEALANTS.
For interior application of joint sealants, comply with applicable regulations regarding reduced VOC's, and as specified in Section 07 92 00
JOINT SEALANTS.
2.2.5 Drips and Weep Holes
Provide continuous drips over heads of top ventilators. Provide drips and weep holes as required to return water to the outside.
2.2.6 Transom Bars
Secure transom bars to adjoining construction and window units in such a manner as to permit expansion and contraction and to form a weathertight joint. Coordinate louver installation with mechanical specifications.
2.2.7 Accessories
Provide windows complete with necessary hardware, fastenings, clips, fins, anchors, glazing beads, and other appurtenances necessary for complete installation and proper operation. Furnish extruded aluminum subframe receptors and subsill with each window unit.
2.2.7.1 Hardware
AAMA/WDMA/CSA 101/I.S.2/A440 . The item, type, and functional characteristics must be the manufacturer's standard for the particular window type. Provide hardware of suitable design and of sufficient strength to perform the function for which it is used. Equip all operating ventilators with a lock or latching device which can be secured from the inside.
2.2.7.2 Fasteners
Provide concealed anchors of the type recommended by the window manufacturer for the specific type of construction. Anchors and fasteners must be compatible with the window and the adjoining construction. Provide a minimum of three anchors for each jamb located approximately 6 inches from each end and at midpoint.
2.2.7.3 Window Anchors
Anchoring devices for installing windows must be made of aluminum, cadmium-plated steel, stainless steel, or zinc-plated steel conforming to
AAMA/WDMA/CSA 101/I.S.2/A440 .
SECTION 08 51 13 Page 6
2.2.8 Finishes
Exposed aluminum surfaces must be factory finished with an organic coating. Color must be as selected from manufacturer's full range. All windows for both Buildings 1 and 2 must have the same finish.
2.2.8.1 Organic Coating
Clean and prime exposed aluminum surfaces. Provide a baked enamel finish in accordance with AAMA 2603 with total dry film thickness not less than
0.8 mil with total dry film thickness of not less than 1.2 mils.
2.2.9 Screens
AAMA/WDMA/CSA 101/I.S.2/A440 . Provide one insect screen for each operable exterior sash or ventilator. Design screens to be rewirable, easily removable from inside the building, and to permit easy access to operating hardware.
2.3 THERMAL-BARRIER WINDOWS
Provide thermal-barrier windows, complete with accessories and fittings, where indicated.
Specify material and construction except as follows:
a. Aluminum alloy must be 6063-T6.
b. Frame construction, including operable sash, must be factory-assembled and factory-sealed inner and outer aluminum completely separated from metal-to-metal contact. Join assembly by a continuous, concealed, low conductance divider housed in an interlocking extrusion of the inner frame. Metal fasteners, straps, or anchors must not bridge the connection between the inner and outer frame.
c. Operating hardware for each sash must consist of spring-loaded nylon cushion blocks and pin locks designed to lock in predetermined locations.
d. Sash must be completely separated from metal-to-metal contact by means of woven-pile weatherstripping, plastic, or elastomeric separation members.
e. Operating and storm sash must be factory-glazed with the type of glass indicated and of the quality specified in Section 08 81 00 GLAZING.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Method of Installation
Install in accordance with the window manufacturer's printed instructions and details. Build in windows as the work progresses or install without forcing into prepared window openings. Set windows at proper elevation, location, and reveal; plumb, square, level, and in alignment; and brace, strut, and stay properly to prevent distortion and misalignment. Protect ventilators and operating parts against accumulation of dirt and building materials by keeping ventilators tightly closed and locked to frame. Bed
SECTION 08 51 13 Page 7 screws or bolts in sill members, contacts of windows with sills, built-in fins, and subframes in mastic sealant of a type recommended by the window manufacturer. Install and caulk windows in a manner that will prevent entrance of water and wind. Fasten insect screens securely in place.
Any materials that show visual evidence of biological growth due to the presence of moisture must not be installed on the building project.
3.1.2 Dissimilar Materials
Where aluminum surfaces are in contact with, or fastened to masonry, concrete, wood, or dissimilar metals, except stainless steel or zinc, protect the aluminum surface from dissimilar materials as recommended in the Appendix to AAMA/WDMA/CSA 101/I.S.2/A440 . Do not coat surfaces in contact with sealants after installation with any type of protective material.
3.1.3 Anchors and Fastenings
Make provision for securing units to each other, to masonry, and to other adjoining construction. Windows installed in masonry walls must have head and jamb members designed to recess into masonry wall not less than 7/16 inch.
3.1.4 Adjustments After Installation
After installation of windows and completion of glazing and field painting, adjust all ventilators and hardware to operate smoothly and to provide weathertight sealing when ventilators are closed and locked.
Lubricate hardware and operating parts as necessary. Adjust double hung windows to operate with maximum applied force of 25 pounds in either direction, not including breakaway friction force. Verify that products are properly installed, connected, and adjusted.
3.2 CLEANING
Clean interior and exterior surfaces of window units of mortar, plaster, paint spattering spots, and other foreign matter to present a neat appearance, to prevent fouling of weathering surfaces and weather-stripping, and to prevent interference with the operation of hardware. Replace all stained, discolored, or abraded windows that cannot be restored to their original condition with new windows.
-- End of Section --